    Instrument Transformers

    - Instrument transformers are designed to

    transform voltage or current from the high values

    in the transmission and distribution systems to

    the low values that can be utilized by low voltagemetering devices and protection.

  • 8/10/2019 Instruments Transformers

    3/15

    Instrument Transformers Primary

    Applications:

    1. metering- for energy billing and transaction purposes

    2. protection control - for system protection and protective

    relaying purposes

    3. load survey - for economic management of industrial

    loads.

  • 8/10/2019 Instruments Transformers

    4/15

    Instrument Transformers Functions

    1. To transform current or voltage from high value to handle for protection

    relays and instruments.

    2. To insulate the metering circuit from the primary high voltage system.

    3. To provide possibilities of standardizing the instruments to a few rated

    currents and voltages.

  • 8/10/2019 Instruments Transformers

    5/15

    Types Instrument Transformers

    1. Current Transformer (CT)

    2. Voltage Transformer or Capacitive

    Voltage Transformer (CVT)

  • 8/10/2019 Instruments Transformers

    6/15

    Instrument Transformers Typical

    Output Level

    CT VT

    1-5 Amperes 115 120 Volts

  • 8/10/2019 Instruments Transformers

    7/15

    Current Transformers

    Are instrument transformers that provide

    insulation against the high voltage of the powercircuit and also supply the relays with quantities

    proportional to those of the power circuit but

    sufficiently reduced in magnitude so that relays

    can be made relatively small and inexpensive.

    CT usually place near the circuit breaker of anycircuit. IF CT breakdown, the protective

    equipment is both Blind and Deaf.

  • 8/10/2019 Instruments Transformers

    8/15

  • 8/10/2019 Instruments Transformers

    9/15

    Manufacturer ABB (Sweden)

    Type/Model IMBD 245 A5; A4; A2

    Rated Voltage 245 kV

    Rated Currents 50-4000 A

    Insulation level 460-1050 kV

    Highest system voltage 245 kV

    Frequency 60 Hz

    Insulation level 460-1050 kV

    Standard IEC 185

    Class: Metering 0.2FS10 and 0.5FS10

    Protection 5P20/X

    Total mass 1720 kg

    Mass of oil 315 kg

    Current Transformers

    Specifications

  • 8/10/2019 Instruments Transformers

    10/15

    Capacitive Voltage Transformer

    A voltage transforming equipment using acapacitance voltage divider connected between

    phase and ground of a power circuit. CVT are

    placed at the entry point of a

    switchyard/substation for voltage indication on

    an energized circuit.

  • 8/10/2019 Instruments Transformers

    11/15

    Capacitive Voltage Transformer

  • 8/10/2019 Instruments Transformers

    12/15

    Capacitive Voltage Transformer

  • 8/10/2019 Instruments Transformers

    13/15

    Instrument Transformer Basic Tests

    Dos and Donts for Instrument Transformer

    1. Never open circuit a current transformer secondary

    while the primary is energized.

    CTs are intended to be proportional current devices.

    Very high voltages can result from open circuiting the

    secondary circuit of an energized CT. Even very small

    primary currents can cause damage

  • 8/10/2019 Instruments Transformers

    14/15

    Instrument Transformer Basic Tests

    Dos and Donts for Instrument Transformer

    2. Never short circuit the secondary of an energized VT

    VTs are intended to be used as proportional voltage

    devices.

    Damaging current will result from short circuiting the

    secondary circuit of an energized VT.

  • 8/10/2019 Instruments Transformers