Instrumentation Cables

BS 5308, Part 1BS 5308, Part 2

andgen. to BS 5308, Part 1

Page 2: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

contents BS5308.doc KERPENWERK GmbH & Co. 2002 1/2

CONTENTS

Instrument CablesBS 5308, Part 1BS 5308, Part 2Zero halogen gen. to BS 5308 Part 1

BS 5308, Part 1

Colour CodeA Identification of not individually screened pairsB Identification of individually screed pairs

Cable TypesSingle and multipair cables, collective screen, Type 1.................................................. 2

Single and multitriple cables, collective screen, Type 1 ............................................... 5

Multipair cables, individual and collective screen, Type 1............................................. 8

Multitriple cables, individual & collective screen, Type 1.............................................. 11

Single and multipair cables, collective screen, armour, Type 2 ................................... 14

Multipair cables, individual and collective screen, armour, Type 2................................ 17

Single and multitriple cables, collective screen, armour, Type 2................................... 20

Multitriple cables, individual & collective screen, armour, Type 2.................................. 23

Single and multipair cables, collective screen, lead sheath, armour, Type 3 ................ 26

Multipair cables, individual and collective screen, lead sheath, armour, Type 3............ 29

Single and multitriple cables, collective screen, lead sheath, armour, Type 3............... 32

Multitriple cables, individual and collective screen, lead sheath, armour, Type 3.......... 35

Page 3: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

contents BS5308.doc KERPENWERK GmbH & Co. 2002 2/2

CONTENTS

Instrument CablesBS 5308, Part 1BS 5308, Part 2Zero halogen gen. to BS 5308 Part 1

BS 5308, Part 2

Colour CodeA Identification of not individually screened pairsB Identification of individually screed pairsC Identification of cores

Cable TypesMulticore cables, collective screen, Type 1................................................................................ 39

Single and multipair cables, collective screen, Type 1 .............................................................. 41

Multipair cables, individual and collective screen, Type 1 ......................................................... 43

Multicore cables, collective screen, armour, Type 2 .................................................................. 45

Multipair cables, collective screen, armour, Type 2 ................................................................... 47

Multipair cables, individual and collective screen, armour, Type 2............................................ 49

Zero halogen gen. to BS 5308 Part 1Single and multipair cables, collective screen, LSZH sheath, Type 1 ....................................... 51

Multipair cables, individual and collective screen, LSZH sheath, Type 1 .................................. 54

Single and multitriple, collective screen, LSZH sheath, Type 1................................................. 57

Multitriple, individual and collective screen, LSZH sheath, Type 1............................................ 60

Single and multipair cables, collective screen, armour, LSZH sheath, Type 2.......................... 63

Multipair cables, individual and collective screen, armour, LSZH sheath, Type 2..................... 66

Single and multitriple, collective screen, armour, LSZH sheath, Type 2 ................................... 69

Multitriple, individual and collective screen, armour, LSZH sheath, Type 2 .............................. 72

Single and multipair cables, XLPE insulation, collective screen, LSZH sheath, Type 1............ 74

Multipair cables, XLPE insulation, individual and collective screen, LSZH sheath, Type 1....... 77

Single and multipair cables, XLPE insulation, collective screen, armour, LSZH sheath,

Type 2......................................................................................................................................... 80

Multipair cables, XLPE insulation, individual and collective screen, armour, LSZH sheath,

Type 2......................................................................................................................................... 83

Page 4: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

BS 5308 part 1

A) Identification of not individually screened pairs

Two-pair unscreened or overall screened cables are colour coded in clockwise orderof rotation: black, blue, green, brown.

All other cables up to 50 pairs conform to the coding of following table:

Pair-No. a-wire b-wire Pair-No a-wire b-wire

12345

6789

10

1112131415

1617181920

2122232425

blackblackblueblackblue

greenblackbluegreenbrown

blackbluegreenbrownwhite

blackbluegreenbrownwhite

redblackbluegreenbrown

bluegreengreenbrownbrown

brownwhitewhitewhitewhite

redredredredred

orangeorangeorangeorangeorange

orangeyellowyellowyellowyellow

2627282930

3132333435

3637383940

4142434445

4647484950

whiteredorangeblackblue

greenbrownwhiteredorange

yellowblackbluegreenbrown

whiteredorangeyellowgrey

blackbluegreenbrownwhite

yellowyellowyellowgreygrey

greygreygreygreygrey

greyvioletvioletvioletviolet

violetvioletvioletvioletviolet

turquoiseturquoiseturquoiseturquoiseturquoise

B) Identification of individually screened pairs

Screened pairs are identified by a numbered tape under the separator tapes of the pairscreens.

Each pair has one black and one blue core.

Page 5: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable click to return to table of contents

Flame Retardant BS 5308 Part 1 Type 1

Single- & Multi-Pair, PE-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl

I//16.12.98 Page 2©KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 1 Type 1 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenYfl outer sheath of PVC

flame retardant

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 6: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 1

Single- & Multi-Pair, PE-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl

I//16.12.98 Page 3©KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.5 35 7279B0000

2 q 0.5 0.8 6.8 55 7279B0001

5 0.5 1.1 10.9 125 7279B0002

10 0.5 1.2 14.4 215 7279B0003

15 0.5 1.2 16.5 300 7279B0004

20 0.5 1.3 18.8 385 7279B0005

30 0.5 1.3 22.3 545 7279B0006

50 0.5 1.5 28.5 875 7279B0007

1.0 mm² (solid)

1 0.6 0.8 6.6 50 7279B0015

2 q 0.6 0.8 8.0 80 7279B0016

5 0.6 1.2 13.5 205 7279B0017

10 0.6 1.2 17.7 350 7279B0018

15 0.6 1.3 20.6 495 7279B0019

20 0.6 1.5 23.8 670 7279B0020

30 0.6 1.5 28.4 975 7279B0021

50 0.6 2.0 36.6 1580 7279B0022

0.5 mm² (flexible)

1 0.6 0.8 6.2 45 7279B0030

2 q 0.6 0.8 7.6 60 7279B0031

5 0.6 1.1 12.4 145 7279B0032

10 0.6 1.2 16.5 245 7279B0033

15 0.6 1.3 19.2 345 7279B0034

20 0.6 1.3 21.7 435 7279B0035

30 0.6 1.5 26.4 640 7279B0036

50 0.6 1.7 33.4 1010 7279B0037

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 7: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 1

Single- & Multi-Pair, PE-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl

I//16.12.98 Page 4©KERPENWERK GmbH & Co. 1998

0.75 mm² (flexible)

1 0.6 0.8 6.7 50 727900019

2 q 0.6 0.9 8.4 75 727900020

5 0.6 1.2 13.8 185 727900021

10 0.6 1.3 18.4 325 727900022

15 0.6 1.3 21.1 445 727900023

20 0.6 1.5 24.4 595 727900024

30 0.6 1.7 29.5 835 727900025

50 0.6 2.0 37.6 1385 727900026

1.5 mm² (stranded)

1 0.6 0.8 7.5 70 7279B0045

2 q 0.6 0.9 9.3 120 7279B0046

5 0.6 1.2 15.6 280 7279B0047

10 0.6 1.3 20.9 515 7279B0048

15 0.6 1.5 24.6 740 7279B0049

20 0.6 1.5 27.8 940 7279B0050

30 0.6 1.7 33.7 1380 7279B0051

50 0.6 2.0 43.0 2245 7279B0052

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 8: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Triple, PE-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl

TPM/Ki//24.02.99 Page 5© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;continuously numbered on cores (1-1-1, 2-2-2 ..)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black or blue for intrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenYfl outer sheath of PVC

flame retardant

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 9: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Triple, PE-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl

TPM/Ki//24.02.99 Page 6© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.8

2 0.5 0.9 9.6

5 0.5 1.1 12.0

10 0.5 1.2 16.4

15 0.5 1.3 18.8

20 0.5 1.3 21.2

30 0.5 1.5 25.8

50 0.5 1.7 32.7

1.0 mm² (solid)

1 0.6 0.8 6.9

2 0.6 1.1 12.0

5 0.6 1.2 14.9

10 0.6 1.3 20.5

15 0.6 1.5 23.8

20 0.6 1.5 26.9

30 0.6 1.7 32.6

50 0.6 2.2 42.0

0.5 mm² (flexible)

1 0.6 0.8 6.5

2 0.6 1.1 11.3

5 0.6 1.2 13.9

10 0.6 1.3 19.1

15 0.6 1.3 21.6

20 0.6 1.5 25.0

30 0.6 1.7 30.3

50 0.6 2.0 38.5

Page 10: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Triple, PE-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl

TPM/Ki//24.02.99 Page 7© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 7.1

2 0.6 1.2 12.5

5 0.6 1.2 15.3

10 0.6 1.3 21.0

15 0.6 1.5 24.4

20 0.6 1.5 27.6

30 0.6 1.7 33.5

50 0.6 2.2 43.1

1.5 mm² (stranded)

1 0.6 0.8 7.9

2 0.6 1.2 13.5

5 0.6 1.2 17.3

10 0.6 1.5 24.4

15 0.6 1.5 27.8

20 0.6 1.7 32.0

30 0.6 2.0 38.9

50 0.6 2.2 49.3RT = radial thickness

Page 11: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 1

Multi-Pair, PE-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl PiMF

TPM/Ki/70540100.002/17.12.98 Page 1©KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 1 Type 1 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenYfl outer sheath of PVC

flame retardantPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 12: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 1

Multi-Pair, PE-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl PiMF

TPM/Ki/70540100.002/17.12.98 Page 2©KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm²

2 0.5 0.9 9.7 95 7279B008

5 0.5 1.2 13.0 180 7279B009

10 0.5 1.2 16.9 310 7279B010

15 0.5 1.3 19.7 440 7279B011

20 0.5 1.3 22.3 560 7279B012

30 0.5 1.5 27.1 820 7279B013

50 0.5 2.0 35.0 1370 7279B014

1.0 mm²

2 0.6 1.1 11.9 135 7279B023

5 0.6 1.2 15.4 250 7279B024

10 0.6 1.3 20.5 450 7279B025

15 0.6 1.5 24.1 675 7279B026

20 0.6 1.7 27.7 875 7279B027

30 0.6 2.0 33.7 1290 7279B028

50 0.6 2.2 42.5 2055 7279B029

0.5 mm²

2 0.6 1.1 11.2 110 7279B038

5 0.6 1.2 14.5 200 7279B039

10 0.6 1.3 19.3 350 7279B040

15 0.6 1.5 22.6 510 7279B041

20 0.6 1.5 25.7 620 7279B042

30 0.6 1.7 31.0 895 7279B043

50 0.6 2.2 39.9 1535 7279B044

0.75 mm²

2 0.6 1.1 12.1 128 72790027

5 0.6 1.2 15.7 238 72790028

10 0.6 1.3 20.9 421 72790029

15 0.6 1.5 24.6 614 72790030

20 0.6 1.5 27.9 806 72790031

30 0.6 2.0 34.4 1188 72790032

50 0.6 2.2 43.5 1880 72790033

1.5 mm²

Page 13: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 1

Multi-Pair, PE-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl PiMF

TPM/Ki/70540100.002/17.12.98 Page 3©KERPENWERK GmbH & Co. 1998

2 0.6 1.2 13.6 180 7279B053

5 0.6 1.3 17.7 340 7279B054

10 0.6 1.5 23.9 635 7279B055

15 0.6 1.7 28.0 915 7279B056

20 0.6 1.7 31.7 1165 7279B057

30 0.6 2.0 38.6 1725 7279B058

50 0.6 2.2 48.9 2770 7279B059

RT = radial thickness

Page 14: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Triple, PE-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl TiMF

TPM/Ki//01.03.99 Page 11© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;with numbered tape under separator tape of the triple screen

Triple screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black or blue for intrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenYfl outer sheath of PVC

flame retardantTiMF triple screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 15: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Triple, PE-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl TiMF

TPM/Ki//01.03.99 Page 12© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 1.1 11.0

5 0.5 1.2 14.1

10 0.5 1.3 19.4

15 0.5 1.3 22.0

20 0.5 1.5 25.4

30 0.5 1.7 30.8

50 0.5 2.0 39.2

1.0 mm² (solid)

2 0.6 1.2 13.3

5 0.6 1.2 16.8

10 0.6 1.5 23.8

15 0.6 1.5 27.0

20 0.6 1.7 31.1

30 0.6 2.0 37.8

50 0.6 2.2 47.9

0.5 mm² (flexible)

2 0.6 1.2 12.5

5 0.6 1.2 15.9

10 0.6 1.3 21.8

15 0.6 1.5 25.4

20 0.6 1.7 29.2

30 0.6 2.0 35.4

50 0.6 2.2 44.8

0.75 mm² (flexible)

2 0.6 1.2 13.5

5 0.6 1.2 17.2

10 0.6 1.5 24.3

15 0.6 1.5 27.6

20 0.6 1.7 31.8

30 0.6 2.0 38.6

50 0.6 2.2 49.0

Page 16: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Triple, PE-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-2Y(St)Yfl TiMF

TPM/Ki//01.03.99 Page 13© KERPENWERK GmbH & Co. 1999

1.5 mm² (stranded)

2 0.6 1.2 15.0

5 0.6 1.3 19.4

10 0.6 1.5 27.2

15 0.6 1.7 31.4

20 0.6 2.0 36.3

30 0.6 2.2 43.8

50 0.6 2.2 55.2

RT = radial thickness

Page 17: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 2

Single- & Multi-Pair, PE-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl

TPM/Ki//17.12.98 Page 14©KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyethylene PE, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 1 Type 2 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation & bedding

of PE(St) collective screenSWA steel wire armourYfl outer sheath of PVC

flame retardant

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 18: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 2

Single- & Multi-Pair, PE-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl

TPM/Ki//17.12.98 Page 15©KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.5 0.9 1.3 9.9 190 7674B000

2 q 0.5 0.8 6.8 0.9 1.3 11.2 240 7674B001

5 0.5 1.1 10.9 0.9 1.4 15.5 400 7674B002

10 0.5 1.2 14.4 1.25 1.6 20.1 695 7674B003

15 0.5 1.2 16.5 1.25 1.6 22.2 840 7674B004

20 0.5 1.3 18.8 1.6 1.7 25.4 1160 7674B005

30 0.5 1.3 22.3 1.6 1.8 29.1 1460 7674B006

50 0.5 1.5 28.5 1.6 2.0 35.7 2020 7674B007

1.0 mm² (solid)

1 0.6 0.8 6.6 0.9 1.3 11.0 220 7674B015

2 q 0.6 0.8 8.0 0.9 1.4 12.6 300 7674B016

5 0.6 1.2 13.5 1.25 1.5 19.0 645 7674B017

10 0.6 1.2 17.7 1.25 1.7 23.6 930 7674B018

15 0.6 1.3 20.6 1.6 1.8 27.4 1345 7674B019

20 0.6 1.5 23.8 1.6 1.8 30.6 1625 7674B020

30 0.6 1.5 28.4 1.6 2.0 35.6 2095 7674B021

50 0.6 2.0 36.6 2.0 2.2 45.0 3482 7674B022

0.5 mm² (flexible)

1 0.6 0.8 6.2 0.9 1.3 10.6 200 7674B030

2 q 0.6 0.8 7.6 0.9 1.3 12.0 245 7674B031

5 0.6 1.1 12.4 0.9 1.5 17.2 460 7674B032

10 0.6 1.2 16.5 1.25 1.6 22.2 790 7674B033

15 0.6 1.3 19.2 1.6 1.7 25.8 1140 7674B034

20 0.6 1.3 21.7 1.6 1.8 28.5 1310 7674B035

30 0.6 1.5 26.4 1.6 1.9 33.4 1720 7674B036

50 0.6 1.7 33.4 2.0 2.1 41.6 2640 7674B037

Page 19: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 2

Single- & Multi-Pair, PE-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl

TPM/Ki//17.12.98 Page 16©KERPENWERK GmbH & Co. 1998

0.75 mm² (flexible)

1 0.6 0.8 6.7 0.9 1.3 11.1 230 76740044

2 q 0.6 0.9 8.4 0.9 1.4 13.0 295 76740045

5 0.6 1.2 13.8 1.25 1.6 19.5 645 76740046

10 0.6 1.3 18.4 1.6 1.7 25.0 1090 76740047

15 0.6 1.3 21.1 1.6 1.8 27.9 1300 76740048

20 0.6 1.5 24.4 1.6 1.9 31.4 1570 76740049

30 0.6 1.7 29.5 2.0 2.0 37.5 2020 76740050

50 0.6 2.0 37.6 2.5 2.3 47.2 3210 76740051

1.5 mm² (stranded)

1 0.6 0.8 7.5 0.9 1.4 12.1 270 7674B045

2 q 0.6 0.9 9.3 0.9 1.4 13.9 360 7674B046

5 0.6 1.2 15.6 1.25 1.6 21.3 800 7674B047

10 0.6 1.3 20.9 1.6 1.8 27.7 1385 7674B048

15 0.6 1.5 24.6 1.6 1.9 31.6 1750 7674B049

20 0.6 1.5 27.8 2.0 2.0 35.8 2315 7674B050

30 0.6 1.7 33.7 2.0 2.1 41.9 3040 7674B051

50 0.6 2.0 43.0 2.5 2.4 52.8 4810 7674B052

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 20: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 2

Multi-Pair, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl PiMF

TPM/Ki//17.12.98 Page 17©KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyethylene PE, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 1 Type 2 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation & bedding

of PE(St) collective screenSWA steel wire armourYfl outer sheath of PVC

flame retardantPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 21: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 2

Multi-Pair, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl PiMF

TPM/Ki//17.12.98 Page 18©KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 0.9 9.7 0.9 1.4 14.3 345 7674B008

5 0.5 1.2 13.0 1.25 1.5 18.5 610 7674B009

10 0.5 1.2 16.9 1.25 1.7 22.8 870 7674B010

15 0.5 1.3 19.7 1.6 1.7 26.3 1265 7674B011

20 0.5 1.3 22.3 1.6 1.8 29.1 1475 7674B012

30 0.5 1.5 27.1 1.6 1.9 34.1 1915 7674B013

50 0.5 2.0 35.0 2.0 2.2 43.4 3075 7674B014

1.0 mm² (solid)

2 0.6 1.1 11.9 0.9 1.5 16.7 435 7674B023

5 0.6 1.2 15.4 1.25 1.6 21.1 755 7674B024

10 0.6 1.3 20.5 1.6 1.8 27.3 1300 7674B025

15 0.6 1.5 24.1 1.6 1.9 31.1 1665 7674B026

20 0.6 1.7 27.7 2.0 2.0 35.7 2240 7674B027

30 0.6 2.0 33.7 2.0 2.2 42.1 2950 7674B028

50 0.6 2.2 42.5 2.5 2.5 52.5 4639 7674B029

0.5 mm² (flexible)

2 0.6 1.1 11.2 0.9 1.5 16.0 400 7674B038

5 0.6 1.2 14.5 1.25 1.6 20.2 680 7674B039

10 0.6 1.3 19.3 1.6 1.8 26.1 1175 7674B040

15 0.6 1.5 22.6 1.6 1.8 29.4 1420 7674B041

20 0.6 1.5 25.7 1.6 1.9 32.7 1680 7674B042

30 0.6 1.7 31.0 2.0 2.1 39.2 2415 7674B043

50 0.6 2.2 39.9 2.5 2.4 49.7 3940 7674B044

0.75 mm² (flexible)

2 0.6 1.1 12.1 0.9 1.5 16.9 437 76740052

5 0.6 1.2 15.7 1.25 1.6 21.4 755 76740053

10 0.6 1.3 20.9 1.6 1.7 27.5 1291 76740054

15 0.6 1.5 24.6 1.6 1.9 31.6 1680 76740055

20 0.6 1.5 27.9 1.6 1.9 34.9 2202 76740056

30 0.6 2.0 34.4 2.0 2.2 42.8 2880 76740057

50 0.6 2.2 43.5 2.5 2.5 53.5 4406 76740058

1.5 mm² (stranded)

2 0.6 1.2 13.6 1.25 1.6 19.3 635 7674B053

Page 22: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 2

Multi-Pair, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl PiMF

TPM/Ki//17.12.98 Page 19©KERPENWERK GmbH & Co. 1998

5 0.6 1.3 17.7 1.6 1.7 24.3 1070 7674B054

10 0.6 1.5 23.9 1.6 1.9 30.9 1605 7674B055

15 0.6 1.7 28.0 2.0 2.0 36.0 2280 7674B056

20 0.6 1.7 31.7 2.0 2.1 39.9 2730 7674B057

30 0.6 2.0 38.6 2.5 2.5 48.6 4075 7674B058

50 0.6 2.2 48.9 2.5 2.7 59.3 5765 7674B059

RT = radial thickness

Page 23: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Triple, PE-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl

TPM/Ki//01.03.99 Page 20© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;continuously numbered on cores (1-1-1, 2-2-2 ..)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyethylene PE, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black or blue for intrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation & bedding

of PE(St) collective screenSWA steel wire armourYfl outer sheath of PVC

flame retardant

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 24: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Triple, PE-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl

TPM/Ki//01.03.99 Page 21© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.8 0.9 1.3 10.2 210 76740123

2 0.5 0.9 9.6 0.9 1.4 14.2 330 76740124

5 0.5 1.1 12.0 0.9 1.5 16.8 470 76740125

10 0.5 1.2 16.4 1.25 1.6 22.1 840 76740126

15 0.5 1.3 18.8 1.6 1.7 25.4 1170 76740127

20 0.5 1.3 21.2 1.6 1.8 28.0 1410 76740128

30 0.5 1.5 25.8 1.6 1.9 32.8

50 0.5 1.7 32.7 2.0 2.1 40.9

1.0 mm² (solid)

1 0.6 0.8 6.9 0.9 1.3 11.3 270 76740144

2 0.6 1.1 12.0 0.9 1.5 16.8 450 76740145

5 0.6 1.2 14.9 1.25 1.6 20.6 760 76740146

10 0.6 1.3 20.5 1.6 1.7 27.1 1330 76740147

15 0.6 1.5 23.8 1.6 1.8 30.6 1670 76740148

20 0.6 1.5 26.9 1.6 1.9 33.9 2000 76740149

30 0.6 1.7 32.6 2.0 2.1 40.8

50 0.6 2.2 42.0 2.5 2.4 51.8

0.5 mm² (flexible)

1 0.6 0.8 6.5 0.9 1.3 10.9

2 0.6 1.1 11.3 0.9 1.5 16.1

5 0.6 1.2 13.9 1.25 1.6 19.6

10 0.6 1.3 19.1 1.6 1.7 25.7

15 0.6 1.3 21.6 1.6 1.8 28.4

20 0.6 1.5 25.0 1.6 1.9 32.0

30 0.6 1.7 30.3 2.0 2.0 38.3

50 0.6 2.0 38.5 2.5 2.3 48.1

Page 25: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Triple, PE-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl

TPM/Ki//01.03.99 Page 22© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 7.1 0.9 1.3 11.5 270 76740108

2 0.6 1.2 12.5 1.25 1.5 18.0 440 76740134

5 0.6 1.2 15.3 1.25 1.6 21.0 750 76740135

10 0.6 1.3 21.0 1.6 1.8 27.8 1300 76740136

15 0.6 1.5 24.4 1.6 1.9 31.4 1630 76740137

20 0.6 1.5 27.6 1.6 1.9 34.6 1940 76740138

30 0.6 1.7 33.5 2.0 2.1 41.7

50 0.6 2.2 43.1 2.5 2.4 52.9

1.5 mm² (stranded)

1 0.6 0.9 8.1 0.9 1.4 12.7 320 76740155

2 0.6 1.2 13.5 1.25 1.5 19.0 650 76740156

5 0.6 1.2 17.3 1.25 1.7 23.2 960 76740157

10 0.6 1.5 24.4 1.6 1.9 31.4 1720 76740158

15 0.6 1.5 27.8 1.6 1.9 34.8 2160 76740159

20 0.6 1.7 32.0 2.0 2.1 40.2 2950 76740160

30 0.6 2.0 38.9 2.5 2.3 48.5

50 0.6 2.2 49.3 2.5 2.6 59.5

RT = radial thickness

Page 26: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl TiMF

TPM/Ki//01.03.99 Page 23© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;with numbered tape under separator tape of the triple screen

Triple screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyethylene PE, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black or blue for intrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation & bedding

of PE(St) collective screenSWA steel wire armourYfl outer sheath of PVC

flame retardantTiMF triple screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 27: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl TiMF

TPM/Ki//01.03.99 Page 24© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm²

2 0.5 1.1 11.0 0.9 1.5 15.8 400 76740129

5 0.5 1.2 14.1 1.25 1.6 19.8 690 76740130

10 0.5 1.3 19.4 1.6 1.7 26.0 1190 76740131

15 0.5 1.3 22.0 1.6 1.8 28.8 1450 76740132

20 0.5 1.5 25.4 1.6 1.9 32.4 1760 76740133

30 0.5 1.7 30.8 2.0 2.0 38.8

50 0.5 2.0 39.2 2.5 2.3 48.8

1.0 mm²

2 0.6 1.2 13.3 1.25 1.5 18.8 590 76740150

5 0.6 1.2 16.8 1.25 1.6 22.5 840 76740151

10 0.6 1.5 23.8 1.6 1.8 30.6 1480 76740152

15 0.6 1.5 27.0 1.6 1.9 34.0 1900 76740153

20 0.6 1.7 31.1 2.0 2.0 39.1 2570 76740154

30 0.6 2.0 37.8 2.5 2.3 47.4

50 0.6 2.2 47.9 2.5 2.6 58.1

0.5 mm²

2 0.6 1.2 12.5 1.25 1.5 18.0

5 0.6 1.2 15.9 1.25 1.6 21.6

10 0.6 1.3 21.8 1.6 1.8 28.6

15 0.6 1.5 25.4 1.6 1.9 32.4

20 0.6 1.7 29.2 2.0 2.0 37.2

30 0.6 2.0 35.4 2.0 2.2 43.8

50 0.6 2.2 44.8 2.5 2.5 54.8

0.75 mm²

2 0.6 1.2 13.5 1.25 1.5 19.0 620 76740139

5 0.6 1.2 17.2 1.25 1.7 23.1 860 76740140

10 0.6 1.5 24.3 1.6 1.9 31.3 1570 76740141

15 0.6 1.5 27.6 1.6 1.9 34.6 1920 76740142

20 0.6 1.7 31.8 2.0 2.1 40.0 2600 76740143

30 0.6 2.0 38.6 2.5 2.3 48.2

50 0.6 2.2 49.0 2.5 2.6 59.2

Page 28: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)2YSWAYfl TiMF

TPM/Ki//01.03.99 Page 25© KERPENWERK GmbH & Co. 1999

1.5 mm²

2 0.6 1.2 15.0 1.25 1.6 20.7 730 76740161

5 0.6 1.3 19.4 1.6 1.7 26.0 1230 76740162

10 0.6 1.5 27.2 1.6 1.9 34.2 1950 76740163

15 0.6 1.7 31.4 2.0 2.0 39.4 2760 76740164

20 0.6 2.0 36.3 2.0 2.2 44.7 3390 76740165

30 0.6 2.2 43.8 2.5 2.5 53.8

50 0.6 2.2 55.2 2.5 2.9 66.0

RT = radial thickness

Page 29: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 3

Single- & Multi-Pair, PE-Insulation, Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl

TPM/Ki//17.12.98 Page 26©KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group IIclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply. Recommended for direct burial, especially in the presence of aggressive chemical substances. Forindoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Metal sheath........... lead alloy

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 1 Type 3 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:15 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenY bedding of PVCMz sheath of lead alloySWA steel wire armourYfl outer sheath of PVC

flame retardant

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 30: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 3

Single- & Multi-Pair, PE-Insulation, Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl

TPM/Ki//17.12.98 Page 27©KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

RT oflead

sheathnom.(mm)

Dia. overlead

sheathapprox.

(mm)

RT ofbedding

nom.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 1.1 8.4 0.8 0.9 1.4 14.6 620 7294B000

2 q 0.5 0.8 1.1 9.2 0.8 0.9 1.4 15.4 700 7294B001

5 0.5 1.1 1.1 13.7 0.8 1.25 1.6 21.0 1210 7294B002

10 0.5 1.2 1.1 17.2 1.0 1.6 1.7 25.8 1775 7294B003

15 0.5 1.2 1.2 19.5 1.0 1.6 1.8 28.3 2110 7294B004

20 0.5 1.3 1.3 22.0 1.0 1.6 1.8 30.8 2480 7294B005

30 0.5 1.3 1.4 25.7 1.0 1.6 1.9 34.7 3060 7294B006

50 0.5 1.5 1.5 32.0 1.2 2.0 2.1 42.6 4470 7294B007

1.0 mm² (solid)

1 0.6 0.8 1.1 9.5 0.8 0.9 1.4 15.7 710 7294B015

2 q 0.6 0.8 1.1 10.4 0.8 0.9 1.5 16.8 825 7294B016

5 0.6 1.2 1.1 16.3 1.0 1.6 1.7 24.9 1680 7294B017

10 0.6 1.2 1.2 20.7 1.0 1.6 1.8 29.5 2260 7294B018

15 0.6 1.3 1.3 23.8 1.0 1.6 1.9 32.8 2765 7294B019

20 0.6 1.5 1.4 27.1 1.2 2.0 2.0 37.5 3640 7294B020

30 0.6 1.5 1.5 31.9 1.2 2.0 2.1 42.5 4525 7294B021

50 0.6 2.0 1.8 40.7 1.4 2.5 2.4 53.3 7115 7294B022

0.5 mm² (flexible)

1 0.6 0.8 1.1 9.1 0.8 0.9 1.4 15.3 675 7294B030

2 q 0.6 0.8 1.1 10.0 0.8 0.9 1.4 16.2 760 7294B031

5 0.6 1.1 1.1 15.2 0.8 1.25 1.6 22.5 1335 7294B032

10 0.6 1.2 1.2 19.5 1.0 1.6 1.8 28.3 2063 7294B033

15 0.6 1.3 1.3 22.4 1.0 1.6 1.8 31.2 2480 7294B034

20 0.6 1.3 1.3 24.9 1.0 1.6 1.9 33.9 2805 7294B035

30 0.6 1.5 1.5 29.9 1.2 2.0 2.1 40.5 4020 7294B036

50 0.6 1.7 1.7 37.3 1.4 2.5 2.3 49.7 5960 7294B037

Page 31: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 3

Single- & Multi-Pair, PE-Insulation, Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl

TPM/Ki//17.12.98 Page 28©KERPENWERK GmbH & Co. 1998

0.75 mm² (flexible)

1 0.6 0.8 1.1 9.6 0.8 0.9 1.5 16.0 715 72940016

2 q 0.6 0.9 1.1 10.8 0.8 1.25 1.5 17.9 820 72940017

5 0.6 1.2 1.1 16.6 1.0 1.6 1.7 25.2 1700 72940018

10 0.6 1.3 1.3 21.6 1.0 1.6 1.8 30.4 2275 72940019

15 0.6 1.3 1.3 24.3 1.0 1.6 1.9 33.3 2765 72940020

20 0.6 1.5 1.5 27.9 1.2 2.0 2.0 38.3 3625 72940021

30 0.6 1.7 1.6 33.2 1.2 2.0 2.2 44.0 4495 72940022

50 0.6 2.0 1.8 41.7 1.4 2.5 2.5 54.5 7046 72940023

1.5 mm² (stranded)

1 0.6 0.8 1.1 10.4 0.8 0.9 1.5 16.8 795 7294B045

2 q 0.6 0.9 1.1 11.7 0.8 1.25 1.5 18.8 1040 7294B046

5 0.6 1.2 1.2 18.6 1.0 1.6 1.7 27.2 2005 7294B047

10 0.6 1.3 1.3 24.1 1.0 1.6 1.9 33.1 2815 7294B048

15 0.6 1.5 1.4 27.9 1.2 2.0 2.0 38.3 3785 7294B049

20 0.6 1.5 1.5 31.3 1.2 2.0 2.1 41.9 4475 7294B050

30 0.6 1.7 1.7 37.6 1.4 2.5 2.3 50.0 6350 7294B051

50 0.6 2.0 2.0 47.5 1.6 2.5 2.6 60.9 9120 7294B052

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 32: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 3

Multi-Pair, PE-Insulation, Individual & Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl PiMF

TPM/Ki//17.12.98 Page 29©KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply. Recommended for direct burial, especially in the presence of aggressive chemical substances. Forindoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Metal sheath........... lead alloy

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 1 Type 3 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:15 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenY bedding of PVCMz sheath of lead alloySWA steel wire armourYfl outer sheath of PVC

flame retardantPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 33: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 3

Multi-Pair, PE-Insulation, Individual & Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl PiMF

TPM/Ki//17.12.98 Page 30©KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

RT oflead

sheathnom.(mm)

Dia. overlead

sheathapprox.

(mm)

RT ofbedding

nom.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 0.9 1.1 12.5 0.8 1.25 1.5 19.6 1080 7294B008

5 0.5 1.2 1.1 15.8 0.8 1.25 1.6 23.1 1430 7294B009

10 0.5 1.2 1.2 19.9 1.0 1.6 1.7 28.5 2150 7294B010

15 0.5 1.3 1.3 22.9 1.0 1.6 1.9 31.9 2630 7294B011

20 0.5 1.3 1.4 25.7 1.2 2.0 1.9 35.9 3350 7294B012

30 0.5 1.5 1.5 30.6 1.2 2.0 2.0 41.0 4260 7294B013

50 0.5 2.0 1.8 39.1 1.4 2.5 2.3 51.5 6660 7294B014

1.0 mm² (solid)

2 0.6 1.1 1.1 14.7 0.8 1.25 1.6 22.0 1290 7294B023

5 0.6 1.2 1.2 18.4 1.0 1.6 1.7 27.0 1970 7294B024

10 0.6 1.3 1.3 23.7 1.0 1.6 1.8 32.5 2715 7294B025

15 0.6 1.5 1.5 27.6 1.2 2.0 2.1 38.2 3800 7294B026

20 0.6 1.7 1.6 31.4 1.2 2.0 2.2 42.2 4540 7294B027

30 0.6 2.0 1.7 37.6 1.4 2.5 2.4 50.2 6290 7294B028

50 0.6 2.2 2.0 47.0 1.6 2.5 2.7 60.6 8880 7294B029

0.5 mm² (flexible)

2 0.6 1.1 1.1 14.0 0.8 1.25 1.6 21.3 1215 7294B038

5 0.6 1.2 1.1 17.3 1.0 1.6 1.7 25.9 1765 7294B039

10 0.6 1.3 1.3 22.5 1.0 1.6 1.9 31.5 2500 7294B040

15 0.6 1.5 1.4 26.0 1.2 2.0 2.0 36.4 3365 7294B041

20 0.6 1.5 1.5 29.2 1.2 2.0 2.1 39.8 3960 7294B042

30 0.6 1.7 1.6 34.7 1.2 2.0 2.2 45.5 4900 7294B043

50 0.6 2.2 1.9 44.2 1.4 2.5 2.6 57.2 7745 7294B044

0.75 mm² (flexible)

2 0.6 1.2 1.1 15.1 0.8 1.25 1.6 22.4 1304 72940024

5 0.6 1.2 1.2 18.7 1.0 1.6 1.7 27.3 1979 72940025

10 0.6 1.3 1.3 24.1 1.0 1.6 1.9 33.1 2715 72940026

15 0.6 1.5 1.5 28.1 1.2 2.0 2.0 38.5 3775 72940027

20 0.6 1.7 1.6 32.0 1.2 2.0 2.2 42.8 4513 72940028

30 0.6 2.0 1.8 38.5 1.4 2.5 2.4 51.1 6265 72940029

50 0.6 2.2 2.0 48.0 1.6 2.5 2.7 61.6 8830 72940030

1.5 mm² (stranded)

2 0.6 1.2 1.1 16.4 1.0 1.6 1.7 25.0 1660 7294B053

Page 34: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 1 Type 3

Multi-Pair, PE-Insulation, Individual & Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl PiMF

TPM/Ki//17.12.98 Page 31©KERPENWERK GmbH & Co. 1998

5 0.6 1.3 1.2 20.7 1.0 1.6 1.8 29.5 2245 7294B054

10 0.6 1.5 1.5 27.4 1.2 2.0 2.1 38.0 3725 7294B055

15 0.6 1.7 1.6 31.7 1.2 2.0 2.2 42.5 4595 7294B056

20 0.6 1.7 1.7 35.6 1.4 2.5 2.3 48.0 5895 7294B057

30 0.6 2.0 1.9 42.9 1.4 2.5 2.4 55.5 7670 7294B058

50 0.6 2.2 2.2 53.8 1.6 2.5 2.9 67.8 10965 7294B059

RT = radial thickness

Page 35: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 3

Single- & Multi-Triple, PE-Insulation, Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl

TPM/Ki//01.03.99 Page 32© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply. Recommended for direct burial, especially in the presence of aggressive chemical substances. Forindoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;continuously numbered on cores (1-1-1, 2-2-2 ..)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Metal sheath........... lead alloy

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black or blue for intrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 3 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:15 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenY bedding of PVCMz sheath of lead alloySWA steel wire armourYfl outer sheath of PVC

flame retardant

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 36: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 3

Single- & Multi-Triple, PE-Insulation, Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl

TPM/Ki//01.03.99 Page 33© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

RT oflead

sheathnom.(mm)

Dia. overlead

sheathapprox.

(mm)

RT ofbedding

nom.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 1.1 8.7 0.8 0.9 1.4 14.9 660 72940070

2 0.5 0.9 1.1 12.0 0.8 1.25 1.6 19.3 1050 72940071

5 0.5 1.2 1.1 15.0 0.8 1.25 1.6 22.3 1350 72940072

10 0.5 1.2 1.2 19.4 1.0 1.6 1.8 28.2 2100 72940073

15 0.5 1.3 1.3 22.0 1.0 1.6 1.9 31.0 2510 72940074

20 0.5 1.3 1.3 24.4 1.0 1.6 1.9 33.4 2850 72940075

30 0.5 1.5 1.5 29.3 1.2 2.0 2.1 39.9

50 0.5 1.7 1.7 36.6 1.4 2.5 2.3 49.0

1.0 mm² (solid)

1 0.6 0.8 1.1 9.8 0.8 0.9 1.5 16.2 760 72940091

2 0.6 1.1 1.1 14.4 0.8 1.25 1.6 21.7 1290 72940092

5 0.6 1.2 1.2 17.9 1.0 1.6 1.7 26.5 1940 72940093

10 0.6 1.3 1.3 23.7 1.0 1.6 1.9 32.7 2750 72940194

15 0.6 1.5 1.4 27.1 1.2 2.0 2.0 37.5 3690 72940195

20 0.6 1.5 1.5 30.4 1.2 2.0 2.1 41.0 4340 72940096

30 0.6 1.7 1.7 36.5 1.4 2.5 2.3 48.9

50 0.6 2.2 2.0 46.5 1.6 2.5 2.6 59.9

0.5 mm² (flexible)

1 0.6 0.8 1.1 9.4 0.8 0.9 1.5 15.8

2 0.6 1.1 1.1 13.7 0.8 1.25 1.6 21.0

5 0.6 1.2 1.1 16.7 1.0 1.6 1.7 25.3

10 0.6 1.3 1.3 22.3 1.0 1.6 1.9 31.3

15 0.6 1.3 1.4 25.0 1.0 1.6 1.9 34.0

20 0.6 1.5 1.5 28.5 1.2 2.0 2.0 38.9

30 0.6 1.7 1.6 34.0 1.2 2.0 2.2 44.8

50 0.6 2.0 1.9 42.8 1.4 2.5 2.5 55.6

Page 37: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 3

Single- & Multi-Triple, PE-Insulation, Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl

TPM/Ki//01.03.99 Page 34© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.9 1.1 10.2 0.8 0.9 1.5 16.6 770 72940068

2 0.6 1.2 1.1 14.9 0.8 1.25 1.6 22.2 1320 72940081

5 0.6 1.2 1.2 18.3 1.0 1.6 1.7 26.9 1950 72940082

10 0.6 1.3 1.3 24.2 1.0 1.6 1.9 33.2 2740 72940083

15 0.6 1.5 1.5 27.9 1.2 2.0 2.0 38.3 3770 72940084

20 0.6 1.5 1.5 31.1 1.2 2.0 2.1 41.7 4210 72940085

30 0.6 2.0 1.7 38.0 1.4 2.5 2.3 50.4

50 0.6 2.2 2.0 47.6 1.6 2.5 2.7 61.2

1.5 mm² (stranded)

1 0.6 0.9 1.1 11.0 0.8 1.25 1.5 18.1 960 72940102

2 0.6 1.2 1.1 16.4 1.0 1.6 1.7 25.0 1700 72940103

5 0.6 1.3 1.2 20.5 1.0 1.6 1.8 29.3 3010 72940114

10 0.6 1.5 1.5 27.9 1.2 2.0 2.0 38.3 3860 72940115

15 0.6 1.7 1.6 31.9 1.2 2.0 2.2 42.7 4770 72940116

20 0.6 1.7 1.7 35.9 1.4 2.5 2.3 48.3 6110 72940107

30 0.6 2.0 1.9 43.2 1.4 2.5 2.6 56.2

50 0.6 2.2 2.2 54.2 1.6 2.5 2.9 68.2

RT = radial thickness

Page 38: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 3

Multi-Triple, PE-Insulation, Individual & Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl TiMF

TPM/Ki//01.03.99 Page 35© KERPENWERK GmbH & Co. 1999

For transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply. Recommended for direct burial, especially in the presence of aggressive chemical substances. Forindoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;with numbered tape under separator tape of the triple screen

Triple screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Metal sheath........... lead alloy

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black or blue for intrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 3 FRRT

Technical Data AbbreviationsFlame retardancy: BS 4066-1

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:15 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenY bedding of PVCMz sheath of lead alloySWA steel wire armourYfl outer sheath of PVC

flame retardantTiMF triple screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 39: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 3

Multi-Triple, PE-Insulation, Individual & Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl TiMF

TPM/Ki//01.03.99 Page 36© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

RT oflead

sheathnom.(mm)

Dia. overlead

sheathapprox.

(mm)

RT ofbedding

nom.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 1.1 1.1 13.8 0.8 1.25 1.6 21.1 1210 72940076

5 0.5 1.2 1.1 16.9 1.0 1.6 1.7 25.5 1750 72940077

10 0.5 1.3 1.3 22.6 1.0 1.6 1.9 31.6 2550 72940078

15 0.5 1.3 1.4 25.4 1.2 1.6 1.9 34.8 3100 72940079

20 0.5 1.5 1.5 28.9 1.2 2.0 2.0 39.3 3960 72940080

30 0.5 1.7 1.6 34.5 1.2 2.5 2.3 46.5

50 0.5 2.0 1.9 43.5 1.4 2.5 2.6 56.5

1.0 mm² (solid)

2 0.6 1.2 1.1 16.1 1.0 1.6 1.7 24.7 1640 72940097

5 0.6 1.2 1.2 19.8 1.0 1.6 1.8 28.6 2170 72940098

10 0.6 1.5 1.4 27.1 1.2 2.0 2.0 37.5 3585 72940099

15 0.6 1.5 1.5 30.5 1.2 2.0 2.1 41.1 4300 72940100

20 0.6 1.7 1.6 34.8 1.2 2.5 2.3 46.8 5570 72940101

30 0.6 2.0 1.9 42.1 1.4 2.5 2.5 54.9

50 0.6 2.2 2.2 52.8 1.6 2.5 2.9 66.8

0.5 mm² (flexible)

2 0.6 1.2 1.1 15.3 1.0 1.25 1.7 23.2

5 0.6 1.2 1.2 18.9 1.0 1.6 1.7 27.5

10 0.6 1.3 1.4 25.2 1.2 1.6 1.9 34.6

15 0.6 1.5 1.5 28.9 1.2 2.0 2.0 39.3

20 0.6 1.7 1.6 32.9 1.2 2.0 2.2 43.7

30 0.6 2.0 1.8 39.5 1.4 2.5 2.4 52.1

50 0.6 2.2 2.0 49.3 1.6 2.5 2.7 62.9

0.75 mm² (flexible)

2 0.6 1.2 1.1 16.3 1.0 1.6 1.7 24.9 1640 72940086

5 0.6 1.3 1.2 20.4 1.0 1.6 1.8 29.2 2170 72940087

10 0.6 1.5 1.5 27.8 1.2 2.0 2.0 38.2 3600 72940088

15 0.6 1.5 1.5 31.1 1.2 2.0 2.1 41.7 4290 72940089

20 0.6 1.7 1.7 35.7 1.4 2.5 2.3 48.1 5770 72940090

30 0.6 2.0 1.9 42.9 1.4 2.5 2.6 55.9

50 0.6 2.2 2.2 53.9 1.6 2.5 2.9 67.9

Page 40: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant gen. to BS 5308 Part 1 Type 3

Multi-Triple, PE-Insulation, Individual & Collective Screen, Lead Sheath, Armour, PVC-Sheath 70°C / 300/500 VRE-2Y(St)YMzYSWAYfl TiMF

TPM/Ki//01.03.99 Page 37© KERPENWERK GmbH & Co. 1999

1.5 mm² (stranded)

2 0.6 1.2 1.2 18.0 1.0 1.6 1.7 26.6 1900 72940108

5 0.6 1.3 1.3 22.6 1.0 1.6 1.9 31.6 2610 72940109

10 0.6 1.5 1.5 30.7 1.2 2.0 2.1 41.3 4310 72940110

15 0.6 1.7 1.6 35.1 1.2 2.5 2.3 47.1 5720 72940111

20 0.6 2.0 1.8 40.4 1.4 2.5 2.4 53.0 7080 72940112

30 0.6 2.2 2.0 48.3 1.6 2.5 2.7 61.9

50 0.6 2.2 2.2 60.1 1.6 2.5 2.9 74.1

RT = radial thickness

Page 41: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

BS 5308 part 2

A) Identification of not individually screened pairs

Two pair unscreened or collectively screened cables shall be cabled in quad formationand colour coded in clockwise order of rotation: blue, green, orange, brown.

All other cables up to 50 pairs conform to the coding of following table:

Pair-No. a-wire b-wire Pair-No a-wire b-wire

12345

6789

10

1112131415

1617181920

2122232425

whitewhitewhitewhitewhite

redredredredred

blackblackblackblackblack

yellowyellowyellowyellowyellow

white-bluewhite-bluewhite-bluewhite-bluewhite-blue

blueorangegreenbrowngrey

blueorangegreenbrowngrey

blueorangegreenbrowngrey

blueorangegreenbrowngrey

blueorangegreenbrowngrey

2627282930

3132333435

3637383940

4142434445

4647484950

red-bluered-bluered-bluered-bluered-blue

blue-blackblue-blackblue-blackblue-blackblue-black

yellow-blueyellow-blueyellow-blueyellow-blueyellow-blue

white-orangewhite-orangewhite-orangewhite-orangewhite-orange

orange-redorange-redorange-redorange-redorange-red

blueorangegreenbrowngrey

blueorangegreenbrowngrey

blueorangegreenbrowngrey

blueorangegreenbrowngrey

blueorangegreenbrowngrey

B) Identification of individually screened pairs

Screened pairs are identified by numbered tape under the seperator tapes of the pairscreens.Each pair has one white and one blue core.

C) Identification of cores

Core 1 to 40: yellow with both printed numbers and written word in black,"10, TEN"

Core 41 to 80: black with both printed numbers and written word in yellow,"10, TEN"

Page 42: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable BS 5308 Part 2 Type 1Flame Retardant

Multi-Core, PVC-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-Y(St)Y-fl

TPM/AD//17.12.98 Page 39© KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² multistranded,

0.75 mm² multistranded or 1.5 mm² stranded

Insulation............... polyvinyl chloride PVC

Colour code........... yellow with both printed numbers and written word in black(1 - 40) up to 40 cores and black with both printed numbers and written word in yellow (1 - 40) up to 80 cores (e.g. 10 TEN)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 2 Type 1 RP

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cableY insulation & outer

sheath of PVC(St) collective screen-fl reduced flame

propagation

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5multistranded

0.75multistranded

1.5stranded

Conductor resistance max. Ω/km 39.0 26.0 12.1

Insulation resistance min. MΩ x km 25

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 250

Capacitance between anycore or screen at 1 kHz max. pF/m 400

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 43: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable BS 5308 Part 2 Type 1Flame Retardant

Multi-Core, PVC-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-Y(St)Y-fl

TPM/AD//17.12.98 Page 40© KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofcores

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (multistranded)

2 0.6 0.8 6.2 50 7774B045

3 0.6 0.8 6.6 60 7774B046

4 0.6 0.8 7.2 70 7774B047

6 0.6 0.9 8.6 100 7774B048

10 0.6 1.1 11.2 150 7774B049

20 0.6 1.2 14.2 260 7774B050

40 0.6 1.3 18.7 470 7774B051

80 0.6 1.5 26.5 900 7774B052

0.75 mm² (multistranded)

2 0.6 0.8 6.7 60 7774B053

3 0.6 0.8 7.2 70 7774B054

4 0.6 0.8 7.8 80 7774B055

6 0.6 0.9 9.4 120 7774B056

10 0.6 1.1 12.2 190 7774B057

20 0.6 1.2 15.6 330 7774B058

40 0.6 1.3 20.6 610 7774B059

80 0.6 1.5 28.5 1160 7774B060

1.5 mm² (stranded)

2 0.6 0.8 8.0 90 7774B061

3 0.6 0.9 8.2 100 7774B062

4 0.6 0.9 9.0 130 7774B063

6 0.6 1.1 11.0 190 7774B064

10 0.6 1.2 14.0 290 7774B065

20 0.6 1.3 17.9 530 7774B066

40 0.6 1.5 24.0 1010 7774B067

80 0.6 1.7 32.9 1920 7774B068

RT = radial thickness

Page 44: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 1

Single- & Multi-Pair, PVC-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-Y(St)Y-fl

TPM/AD//17.12.98 Page 41© KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² multistranded,

0.75 mm² multistranded or 1.5 mm² stranded

Insulation............... polyvinyl chloride PVC

Colour code........... according to BS 5308 PART 2 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 2 Type 1 RP

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cableY insulation & outer

sheath of PVC(St) collective screen-fl reduced flame

propagation

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5multistranded

0.75multistranded

1.5stranded

Conductor resistance max. Ω/km 39.7 26.5 12.3

Insulation resistance min. MΩ x km 25

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 250

Capacitance between anycore or screen at 1 kHz max. pF/m 400

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 45: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 1

Single- & Multi-Pair, PVC-Insulation, Collective Screen, PVC-Sheath 70°C / 300/500 VRE-Y(St)Y-fl

TPM/AD//17.12.98 Page 42© KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (multistranded)

1 0.6 0.8 6.2 40 7774B000

2 q 0.6 0.8 7.6 70 7774B001

5 0.6 1.1 12.4 160 7774B002

10 0.6 1.2 16.5 280 7774B003

15 0.6 1.3 19.2 390 7774B004

20 0.6 1.3 21.7 450 7774B005

30 0.6 1.5 26.4 730 7774B006

50 0.6 1.7 33.4 1160 7774B007

0.75 mm² (multistranded)

1 0.6 0.8 6.7 50 7774B015

2 q 0.6 0.8 8.2 80 7774B016

5 0.6 1.2 13.8 200 7774B017

10 0.6 1.3 18.4 350 7774B018

15 0.6 1.3 21.1 490 7774B019

20 0.6 1.5 24.4 660 7774B020

30 0.6 1.7 29.5 960 7774B021

50 0.6 2.0 37.6 1540 7774B022

1.5 mm² (stranded)

1 0.6 0.8 7.5 70 7774B030

2 q 0.6 0.9 9.3 130 7774B031

5 0.6 1.2 15.6 300 7774B032

10 0.6 1.3 20.9 540 7774B033

15 0.6 1.5 24.6 810 7774B034

20 0.6 1.5 27.8 1030 7774B035

30 0.6 1.7 33.7 1510 7774B036

50 0.6 2.0 43.0 2470 7774B037

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 46: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 1

Multi-Pair, PVC-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-Y(St)Y-fl PiMF

TPM/AD//17.12.98 Page 43© KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² multistranded,

0.75 mm² multistranded or 1.5 mm² stranded

Insulation............... polyvinyl chloride PVC

Colour code........... white / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 2 Type 1 RP

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cableY insulation & outer

sheath of PVC(St) collective screen-fl reduced flame

propagationPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5multistranded

0.75multistranded

1.5stranded

Conductor resistance max. Ω/km 39.7 26.5 12.3

Insulation resistance min. MΩ x km 25

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 250

Capacitance between anycore or screen at 1 kHz max. pF/m 400

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 47: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 1

Multi-Pair, PVC-Insulation, Individual & Collective Screen, PVC-Sheath 70°C / 300/500 VRE-Y(St)Y-fl PiMF

TPM/AD//17.12.98 Page 44© KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (multistranded)

2 0.6 1.1 11.2 120 7774B008

5 0.6 1.2 14.6 210 7774B009

10 0.6 1.3 19.4 370 7774B010

15 0.6 1.5 22.7 540 7774B011

20 0.6 1.5 25.9 690 7774B012

30 0.6 1.7 31.2 950 7774B013

50 0.6 2.2 40.1 1650 7774B014

0.75 mm (multistranded)

2 0.6 1.1 12.2 130 7774B023

5 0.6 1.2 15.8 250 7774B024

10 0.6 1.3 21.1 450 7774B025

15 0.6 1.5 24.9 650 7774B026

20 0.6 1.7 28.6 850 7774B027

30 0.6 2.0 34.7 1260 7774B028

50 0.6 2.2 43.9 2000 7774B029

1.5 mm (stranded)

2 0.6 1.2 13.6 190 7774B038

5 0.6 1.3 17.8 360 7774B039

10 0.6 1.5 24.1 670 7774B040

15 0.6 1.7 28.2 970 7774B041

20 0.6 1.7 31.9 1240 7774B042

30 0.6 2.0 38.8 1830 7774B043

50 0.6 2.2 49.1 2940 7774B044

RT = radial thickness

Page 48: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 2

Multi-Core, PVC-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-Y(St)YSWAY-fl

TPM/AD//17.12.98 Page 45© KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² multistranded,

0.75 mm² multistranded or 1.5 mm² stranded

Insulation............... polyvinyl chloride PVC

Colour code........... yellow with both printed numbers and written word in black(1 - 40) up to 40 cores and black with both printed numbers andwritten word in yellow (1 - 40) up to 80 cores (e.g. 10 TEN)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 2 Type 2 RP

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cableY insulation, bedding &

outer sheath of PVC(St) collective screenSWA steel wire armour-fl reduced flame

propagation

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5multistranded

0.75multistranded

1.5stranded

Conductor resistance max. Ω/km 39.0 26.0 12.1

Insulation resistance min. MΩ x km 25

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 250

Capacitance between anycore or screen at 1 kHz max. pF/m 400

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 49: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 2

Multi-Core, PVC-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-Y(St)YSWAY-fl

TPM/AD//17.12.98 Page 46© KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofcores

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (multistranded)

2 0.6 0.8 6.7 0.9 1.3 11.1 210 7776B045

3 0.6 0.8 6.6 0.9 1.3 11.0 250 7776B046

4 0.6 0.8 7.2 0.9 1.3 11.6 280 7776B047

6 0.6 0.9 8.6 0.9 1.4 13.2 330 7776B048

10 0.6 1.1 11.2 0.9 1.5 16.0 460 7776B049

20 0.6 1.2 14.2 1.25 1.6 19.9 760 7776B050

40 0.6 1.3 18.7 1.6 1.7 25.3 1290 7776B051

80 0.6 1.5 25.8 1.6 1.9 32.8 2060 7776B052

0.75 mm² (multistranded)

2 0.6 0.8 7.2 0.9 1.3 11.6 240 7776B053

3 0.6 0.8 7.2 0.9 1.3 11.6 280 7776B054

4 0.6 0.8 7.8 0.9 1.4 12.4 310 7776B055

6 0.6 0.9 9.4 0.9 1.4 14.0 380 7776B056

10 0.6 1.1 12.2 0.9 1.5 17.0 520 7776B057

20 0.6 1.2 15.6 1.25 1.6 21.3 870 7776B058

40 0.6 1.3 20.6 1.6 1.8 27.4 1510 7776B059

80 0.6 1.5 28.5 1.6 2.0 35.7 2400 7776B060

1.5 mm² (stranded)

2 0.6 0.8 8.0 0.9 1.4 12.6 280 7776B061

3 0.6 0.9 8.2 0.9 1.4 12.8 330 7776B062

4 0.6 0.9 9.0 0.9 1.4 13.6 380 7776B063

6 0.6 1.1 11.0 0.9 1.4 15.6 480 7777B064

10 0.6 1.2 14.0 1.25 1.6 19.7 790 7776B065

20 0.6 1.3 17.9 1.6 1.7 24.5 1320 7776B066

40 0.6 1.5 24.0 1.6 1.9 31.0 2110 7776B067

80 0.6 1.7 32.9 2.0 2.1 41.1 3650 7776B068

RT = radial thickness

Page 50: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 2

Multi-Pair, PVC-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-Y(St)YSWAY-fl

TPM/AD//17.12.98 Page 47© KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² multistranded,

0.75 mm² multistranded or 1.5 mm² stranded

Insulation............... polyvinyl chloride PVC

Colour code........... according to BS 5308 PART 2 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 2 Type 2 RP

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cableY insulation, bedding &

outer sheath of PVC(St) collective screenSWA steel wire armour-fl reduced flame

propagation

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5multistranded

0.75multistranded

1.5stranded

Conductor resistance max. Ω/km 39.7 26.5 12.3

Insulation resistance min. MΩ x km 25

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 250

Capacitance between anycore or screen at 1 kHz max. pF/m 400

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 51: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 2

Multi-Pair, PVC-Insulation, Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-Y(St)YSWAY-fl

TPM/AD//17.12.98 Page 48© KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (multistranded)

1 0.6 0.8 6.2 0.9 1.3 10.6 230 7776B000

2 q 0.6 0.8 7.1 0.9 1.3 11.5 260 7776B001

5 0.6 1.1 12.4 0.9 1.5 17.2 490 7776B002

10 0.6 1.2 16.5 1.25 1.6 22.2 840 7776B003

15 0.6 1.3 19.2 1.6 1.7 25.8 1220 7776B004

20 0.6 1.3 21.7 1.6 1.8 28.5 1430 7776B005

30 0.6 1.5 26.4 1.6 1.9 33.4 1890 7776B006

50 0.6 1.7 33.4 2.0 2.1 41.6 2910 7776B007

0.75 mm² (multistranded)

1 0.6 0.8 6.7 0.9 1.3 11.1 250 7776B015

2 q 0.6 0.8 7.7 0.9 1.4 12.3 300 7776B016

5 0.6 1.2 13.8 1.25 1.5 19.3 670 7776B017

10 0.6 1.3 18.4 1.6 1.7 25.0 1190 7776B018

15 0.6 1.3 21.1 1.6 1.8 27.9 1390 7776B019

20 0.6 1.5 24.4 1.6 1.8 31.2 1700 7776B020

30 0.6 1.7 29.6 2.0 2.0 37.6 2490 7776B021

50 0.6 2.0 37.6 2.5 2.3 47.3 3930 7776B022

1.5 mm² (stranded)

1 0.6 0.8 7.5 0.9 1.4 12.1 290 7776B030

2 q 0.6 0.9 8.8 0.9 1.4 13.4 390 7776B031

5 0.6 1.2 15.6 1.25 1.6 21.3 850 7776B032

10 0.6 1.3 20.9 1.6 1.8 27.7 1460 7776B033

15 0.6 1.5 24.6 1.6 1.9 31.6 1900 7776B034

20 0.6 1.5 27.8 1.6 2.0 35.0 2240 7776B035

30 0.6 1.7 33.7 2.0 2.1 41.9 3310 7776B036

50 0.6 2.0 43.0 2.5 2.4 52.8 5290 7776B037

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 52: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 2

Multi-Pair, PVC-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-Y(St)YSWAY-fl PiMF

TPM/AD//17.12.98 Page 49© KERPENWERK GmbH & Co. 1998

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² multistranded,

0.75 mm² multistranded or 1.5 mm² stranded

Insulation............... polyvinyl chloride PVC

Colour code........... white / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. polyvinyl chloride PVC, black

Armour................... galvanized round steel wires

Outer sheath.......... polyvinyl chloride PVC, black

Cable marking........ KERPENWERK BS 5308 Part 2 Type 2 RP

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3

Outer sheath:Amount of halogen acid gas: max. 17%

(BS 6425-1)Limiting Oxygen Index (LOI): min. 30%

(IEC 60332-3 annex B)Temperature index (TI): min. 300°C

(ASTM-D-2863)Sunlight resistance: (UL 1581 section 1200)Oil resistance: (ICEA S-82-552)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cableY insulation, bedding &

outer sheath of PVC(St) collective screenSWA steel wire armour-fl reduced flame

propagationPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5multistranded

0.75multistranded

1.5stranded

Conductor resistance max. Ω/km 39.7 26.5 12.3

Insulation resistance min. MΩ x km 25

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 250

Capacitance between anycore or screen at 1 kHz max. pF/m 400

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 53: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableFlame Retardant BS 5308 Part 2 Type 2

Multi-Pair, PVC-Insulation, Individual & Collective Screen, Armour, PVC-Sheath 70°C / 300/500 VRE-Y(St)YSWAY-fl PiMF

TPM/AD//17.12.98 Page 50© KERPENWERK GmbH & Co. 1998

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (multistranded)

2 0.6 0.8 10.6 0.9 1.3 15.0 430 7776B008

5 0.6 1.1 14.3 0.9 1.5 19.1 720 7776B009

10 0.6 1.2 19.1 1.25 1.6 24.8 1240 7776B010

15 0.6 1.3 22.2 1.6 1.7 28.8 1520 7776B011

20 0.6 1.3 25.3 1.6 1.8 32.1 1790 7776B012

30 0.6 1.5 30.6 1.6 1.9 37.6 2570 7776B013

50 0.6 1.7 38.9 2.0 2.1 47.1 4210 7776B014

0.75 mm² (multistranded)

2 0.6 0.8 11.5 0.9 1.4 16.1 460 7776B023

5 0.6 1.2 15.7 1.25 1.5 21.2 800 7776B024

10 0.6 1.3 20.9 1.6 1.7 27.5 1360 776B025

15 0.6 1.3 24.2 1.6 1.8 31.0 1700 7776B026

20 0.6 1.5 27.9 1.6 1.8 34.7 2340 7776B027

30 0.6 1.7 33.8 2.0 2.0 41.8 3050 7776B028

50 0.6 2.0 43.1 2.5 2.3 52.7 4800 7776B029

1.5 mm² (stranded)

2 0.6 0.9 13.0 0.9 1.4 17.6 670 7776B038

5 0.6 1.2 17.5 1.25 1.6 23.2 1130 7776B039

10 0.6 1.3 23.5 1.6 1.8 30.3 1710 7776B040

15 0.6 1.5 27.6 1.6 1.9 34.6 2420 7776B041

20 0.6 1.5 31.3 1.6 2.0 38.5 2900 7776B042

30 0.6 1.7 38.0 2.0 2.1 46.2 4300 7776B043

50 0.6 2.0 48.5 2.5 2.4 58.3 6140 7776B044

RT = radial thickness

Page 54: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Pair, PE-Insulation, Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H

TPM/AD//01.03.99 Page 51© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH outer sheath of LSZH

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 55: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Pair, PE-Insulation, Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H

TPM/AD//01.03.99 Page 52© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.5 45 7645B000

2 q 0.5 0.8 6.8 55 7645B001

5 0.5 1.1 10.9 130 7645B002

10 0.5 1.2 14.4 220 7645B003

15 0.5 1.2 16.5

20 0.5 1.3 18.8 390 7645B005

30 0.5 1.3 22.3

50 0.5 1.5 28.5

1.0 mm² (solid)

1 0.6 0.8 6.6 65 7645B030

2 q 0.6 0.8 8.0 80 7645B031

5 0.6 1.2 13.5 200 7645B032

10 0.6 1.2 17.7 350 7645B033

15 0.6 1.3 20.6

20 0.6 1.5 23.8 665 7645B035

30 0.6 1.5 28.4

50 0.6 2.0 36.6

0.5 mm² (flexible)

1 0.6 0.8 6.2 50 7645B010

2 q 0.6 0.8 7.6 60 7645B011

5 0.6 1.1 12.4 145 7645B012

10 0.6 1.2 16.5 245 7645B013

15 0.6 1.3 19.2

20 0.6 1.3 21.7 430 7645B015

30 0.6 1.5 26.4

50 0.6 1.7 33.4

Page 56: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Pair, PE-Insulation, Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H

TPM/AD//01.03.99 Page 53© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 6.7 55 7645B020

2 q 0.6 0.9 8.4 80 7645B021

5 0.6 1.2 13.8 185 7645B022

10 0.6 1.3 18.4 315 7645B023

15 0.6 1.3 21.1

20 0.6 1.5 24.4 580 7645B025

30 0.6 1.7 29.5

50 0.6 2.0 37.6

1.5 mm² (stranded)

1 0.6 0.8 7.5 80 7645B040

2 q 0.6 0.9 8.8 114 7645B041

5 0.6 1.2 15.6 280 7645B042

10 0.6 1.3 20.9 500 7645B043

15 0.6 1.5 24.6

20 0.6 1.5 27.8 940 7645B045

30 0.6 1.7 33.7

50 0.6 2.0 43.0

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 57: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Pair, PE-Insulation, Individual & Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H PiMF

TPM/AD//01.03.99 Page 54© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH outer sheath of LSZHPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 58: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Pair, PE-Insulation, Individual & Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H PiMF

TPM/AD//01.03.99 Page 55© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

(outer sheathblack)

0.5 mm² (solid)

2 0.5 0.9 9.7 90 7645B050

5 0.5 1.2 13.0 180 7645B051

10 0.5 1.2 16.9 310 7645B052

15 0.5 1.3 19.7

20 0.5 1.3 22.3 550 7645B054

30 0.5 1.5 27.1

50 0.5 2.0 35.0

1.0 mm² (solid)

2 0.6 1.1 11.9 135 7645B080

5 0.6 1.2 15.4 255 7645B081

10 0.6 1.3 20.5 500 7645B082

15 0.6 1.5 24.1

20 0.6 1.7 27.7 870 7645B084

30 0.6 2.0 33.7

50 0.6 2.2 42.5

0.5 mm² (flexible)

2 0.6 1.1 11.2 110 7645B060

5 0.6 1.2 14.5 200 7645B061

10 0.6 1.3 19.3 350 7645B062

15 0.6 1.5 22.6

20 0.6 1.5 25.7 635 7645B064

30 0.6 1.7 31.0

50 0.6 2.2 39.9

Page 59: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Pair, PE-Insulation, Individual & Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H PiMF

TPM/AD//01.03.99 Page 56© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

2 0.6 1.1 12.1 130 7645B070

5 0.6 1.2 15.7 240 7645B071

10 0.6 1.3 20.9 420 7645B072

15 0.6 1.5 24.6

20 0.6 1.5 27.9 770 7645B074

30 0.6 2.0 34.4

50 0.6 2.2 43.5

1.5 mm² (stranded)

2 0.6 1.2 13.6 180 7645B090

5 0.6 1.3 17.7 340 7645B091

10 0.6 1.5 23.9 640 7645B092

15 0.6 1.7 28.0

20 0.6 1.7 31.7 940 7645B094

30 0.6 2.0 38.6

50 0.6 2.2 48.9

RT = radial thickness

Page 60: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Triple, PE-Insulation, Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H

TPM/AD//01.03.99 Page 57© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;continuously numbered on cores (1-1-1, 2-2-2 ..) for multitriples

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH outer sheath of LSZH

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 61: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Triple, PE-Insulation, Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H

TPM/AD//01.03.99 Page 58© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.8

2 0.5 0.9 9.6

5 0.5 1.1 12.0

10 0.5 1.2 16.4

15 0.5 1.3 18.8

20 0.5 1.3 21.2

30 0.5 1.5 25.8

50 0.5 1.7 32.7

1.0 mm² (solid)

1 0.6 0.8 6.9

2 0.6 1.1 12.0

5 0.6 1.2 14.9

10 0.6 1.3 20.5

15 0.6 1.5 23.8

20 0.6 1.5 26.9

30 0.6 1.7 32.6

50 0.6 2.2 42.0

0.5 mm² (flexible)

1 0.6 0.8 6.5

2 0.6 1.1 11.3

5 0.6 1.2 13.9

10 0.6 1.3 19.1

15 0.6 1.3 21.6

20 0.6 1.5 25.0

30 0.6 1.7 30.3

50 0.6 2.0 38.5

Page 62: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Triple, PE-Insulation, Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H

TPM/AD//01.03.99 Page 59© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 7.1 70 7645B104

2 0.6 1.2 12.5

5 0.6 1.2 15.3

10 0.6 1.3 21.0

15 0.6 1.5 24.4

20 0.6 1.5 27.6

30 0.6 1.7 33.5

50 0.6 2.2 43.1

1.5 mm² (stranded)

1 0.6 0.8 7.9 100 7645B095

2 0.6 1.2 13.5

5 0.6 1.2 17.3

10 0.6 1.5 24.4

15 0.6 1.5 27.8

20 0.6 1.7 32.0

30 0.6 2.0 38.9

50 0.6 2.2 49.3

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 63: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Triple, PE-Insulation, Individual & Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H TiMF

TPM/AD//01.03.99 Page 60© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;with numbered tape under separator tape of the triple screen

Triple screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH outer sheath of LSZHTiMF triple screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 64: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Triple, PE-Insulation, Individual & Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H TiMF

TPM/AD//01.03.99 Page 61© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 1.1 11.0

5 0.5 1.2 14.1

10 0.5 1.3 19.4

15 0.5 1.3 22.0

20 0.5 1.5 25.4

30 0.5 1.7 30.8

50 0.5 2.0 39.2

1.0 mm² (solid)

2 0.6 1.2 13.3

5 0.6 1.2 16.8

10 0.6 1.5 23.8

15 0.6 1.5 27.0

20 0.6 1.7 31.1

30 0.6 2.0 37.8

50 0.6 2.2 47.9

0.5 mm² (flexible)

2 0.6 1.2 12.5

5 0.6 1.2 15.9

10 0.6 1.3 21.8

15 0.6 1.5 25.4

20 0.6 1.7 29.2

30 0.6 2.0 35.4

50 0.6 2.2 44.8

0.75 mm² (flexible)

2 0.6 1.2 13.5

5 0.6 1.2 17.2

10 0.6 1.5 24.3

15 0.6 1.5 27.6

20 0.6 1.7 31.8

30 0.6 2.0 38.6

50 0.6 2.2 49.0

Page 65: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Triple, PE-Insulation, Individual & Collective Screen, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)H TiMF

TPM/AD//01.03.99 Page 62© KERPENWERK GmbH & Co. 1999

1.5 mm² (stranded)

2 0.6 1.2 15.0

5 0.6 1.3 19.4

10 0.6 1.5 27.2

15 0.6 1.7 31.4

20 0.6 2.0 36.3

30 0.6 2.2 43.8

50 0.6 2.2 55.2

RT = radial thickness

Page 66: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Pair, PE-Insulation, Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH

TPM/Ki//22.02.99 Page 63© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial acc. to national regulations. For indoor and outdoor installation in dry and wet locations onracks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. zero halogen flame retardant compound LSZH, black

Armour................... galvanized round steel wires

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH bedding & outer sheath

of LSZHSWA steel wire armour

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 67: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Pair, PE-Insulation, Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH

TPM/Ki//22.02.99 Page 64© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.5 0.9 1.3 9.9 190 8013B000

2 q 0.5 0.8 6.8 0.9 1.3 11.2 250 8013B001

5 0.5 1.1 10.9 0.9 1.4 15.5 420 8013B002

10 0.5 1.2 14.4 1.25 1.6 20.1 720 8013B003

15 0.5 1.2 16.5 1.25 1.6 22.2 870 8013B004

20 0.5 1.3 18.8 1.6 1.7 25.4 1200 8013B005

30 0.5 1.3 22.3 1.6 1.8 29.1 1500 8013B006

50 0.5 1.5 28.5 1.6 2.0 35.7 2090 8013B007

1.0 mm² (solid)

1 0.6 0.8 6.6 0.9 1.3 11.0 230 8013B015

2 q 0.6 0.8 8.0 0.9 1.4 12.6 340 8013B016

5 0.6 1.2 13.5 1.25 1.5 19.0 660 8013B017

10 0.6 1.2 17.7 1.25 1.7 23.6 960 8013B018

15 0.6 1.3 20.6 1.6 1.8 27.4 1410 8013B019

20 0.6 1.5 23.8 1.6 1.8 30.6 1680 8013B020

30 0.6 1.5 28.4 1.6 2.0 35.6 2160 8013B021

50 0.6 2.0 36.6 2.0 2.2 45.0 3450 8013B022

0.5 mm² (flexible)

1 0.6 0.8 6.2 0.9 1.3 10.6 210 8013B030

2 q 0.6 0.8 7.6 0.9 1.3 12.0 260 8013B031

5 0.6 1.1 12.4 0.9 1.5 17.2 480 8013B032

10 0.6 1.2 16.5 1.25 1.6 22.2 810 8013B033

15 0.6 1.3 19.2 1.6 1.7 25.8 1170 8013B034

20 0.6 1.3 21.7 1.6 1.8 28.5 1350 8013B035

30 0.6 1.5 26.4 1.6 1.9 33.4 1770 8013B036

50 0.6 1.7 33.4 2.0 2.1 41.6 2720 8013B037

Page 68: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Pair, PE-Insulation, Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH

TPM/Ki//22.02.99 Page 65© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 6.7 0.9 1.3 11.1 230 80130050

2 q 0.6 0.9 8.4 0.9 1.4 13.0 310 80130051

5 0.6 1.2 13.8 1.25 1.6 19.5 660 80130052

10 0.6 1.3 18.4 1.6 1.7 25.0 1120 80130053

15 0.6 1.3 21.1 1.6 1.8 27.9 1340 80130054

20 0.6 1.5 24.4 1.6 1.9 31.4 1650 80130055

30 0.6 1.7 29.5 2.0 2.0 37.5 2390 80130056

50 0.6 2.0 37.6 2.5 2.3 47.2 3740 80130057

1.5 mm² (stranded)

1 0.6 0.8 7.5 0.9 1.4 12.1 270 8013B045

2 q 0.6 0.9 9.3 0.9 1.4 13.9 360 8013B046

5 0.6 1.2 15.6 1.25 1.6 21.3 820 8013B047

10 0.6 1.3 20.9 1.6 1.8 27.7 1400 8013B048

15 0.6 1.5 24.6 1.6 1.9 31.6 1820 8013B049

20 0.6 1.5 27.8 2.0 2.0 35.8 2430 8013B050

30 0.6 1.7 33.7 2.0 2.1 41.9 3120 8013B051

50 0.6 2.0 43.0 2.5 2.4 52.8 4930 8013B052

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 69: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable gen. to BS 5308 Part 1 Type 2Zero Halogen & Flame Retardant

Multi-Pair, PE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH PiMF

TPM/AD//01.03.99 Page 66© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial acc. to national regulations. For indoor and outdoor installation in dry and wet locations onracks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid,

0.5 mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. zero halogen flame retardant compound LSZH, black

Armour................... galvanized round steel wires

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH bedding & outer sheath

of LSZHSWA steel wire armourPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 70: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable gen. to BS 5308 Part 1 Type 2Zero Halogen & Flame Retardant

Multi-Pair, PE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH PiMF

TPM/AD//01.03.99 Page 67© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 0.9 9.7 0.9 1.4 14.3 355 8013B008

5 0.5 1.2 13.0 1.25 1.5 18.5 635 8013B009

10 0.5 1.2 16.9 1.25 1.7 22.8 905 8013B010

15 0.5 1.3 19.7 1.6 1.7 26.3 1290 8013B011

20 0.5 1.3 22.3 1.6 1.8 29.3 1515 8013B012

30 0.5 1.5 27.1 1.6 1.9 34.2 1975 8013B013

50 0.5 2.0 35.0 2.0 2.2 43.5 3170 8013B014

1.0 mm² (solid)

2 0.6 1.1 11.9 0.9 1.5 16.7 455 8013B023

5 0.6 1.2 15.4 1.25 1.6 21.1 780 8013B024

10 0.6 1.3 20.5 1.6 1.8 27.3 1310 8013B025

15 0.6 1.5 24.1 1.6 1.9 31.1 1710 8013B026

20 0.6 1.7 27.7 2.0 2.0 35.8 2305 8013B027

30 0.6 2.0 33.7 2.0 2.2 42.1 3080 8013B028

50 0.6 2.2 42.5 2.5 2.5 52.6 4760 8013B029

0.5 mm² (flexible)

2 0.6 1.1 11.2 0.9 1.5 16.1 430 8013B038

5 0.6 1.2 14.5 1.25 1.6 20.2 710 8013B039

10 0.6 1.3 19.3 1.6 1.8 26.1 1195 8013B040

15 0.6 1.5 22.6 1.6 1.8 29.6 1465 8013B041

20 0.6 1.5 25.7 1.6 1.9 32.8 1730 8013B042

30 0.6 1.7 31.0 2.0 2.1 39.3 2520 8013B043

50 0.6 2.2 39.9 2.5 2.4 49.8 4050 8013B044

0.75 mm² (flexible)

2 0.6 1.1 12.1 0.9 1.5 16.9

5 0.6 1.2 15.7 1.25 1.6 21.4

10 0.6 1.3 20.9 1.6 1.7 27.5 1310 80130060

15 0.6 1.5 24.6 1.6 1.9 31.6

20 0.6 1.5 27.9 1.6 1.9 34.9

30 0.6 2.0 34.4 2.0 2.2 42.8

50 0.6 2.2 43.5 2.5 2.5 53.5

Page 71: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable gen. to BS 5308 Part 1 Type 2Zero Halogen & Flame Retardant

Multi-Pair, PE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH PiMF

TPM/AD//01.03.99 Page 68© KERPENWERK GmbH & Co. 1999

1.5 mm² (stranded)

2 0.6 1.2 13.6 1.25 1.6 19.4 660 8013B053

5 0.6 1.3 17.7 1.6 1.7 24.3 1130 8013B054

10 0.6 1.5 23.9 1.6 1.9 30.9 1675 8013B055

15 0.6 1.7 28.0 2.0 2.0 36.1 2350 8013B056

20 0.6 1.7 31.7 2.0 2.1 40.0 2835 8013B057

30 0.6 2.0 38.6 2.5 2.5 48.7 4180 8013B058

50 0.6 2.2 48.9 2.5 2.7 59.4 5910 8013B059

RT = radial thickness

Page 72: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Triple, PE-Insulation, Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH

TPM/AD//02.03.99 Page 69© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial acc. to national regulations. For indoor and outdoor installation in dry and wet locations onracks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... polyethylene PE

Colour code........... black / white / red;continuously numbered on cores (1-1-1, 2-2-2 ..)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. zero halogen flame retardant compound LSZH, black

Armour................... galvanized round steel wires

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH bedding & outer sheath

of LSZHSWA steel wire armour

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 73: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Triple, PE-Insulation, Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH

TPM/AD//02.03.99 Page 70© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.8 0.9 1.3 10.2

2 0.5 0.9 9.6 0.9 1.4 14.2

5 0.5 1.1 12.0 0.9 1.5 16.8

10 0.5 1.2 16.4 1.25 1.6 22.1

15 0.5 1.3 18.8 1.6 1.7 25.4

20 0.5 1.3 21.2 1.6 1.8 28.0

30 0.5 1.5 25.8 1.6 1.9 32.8

50 0.5 1.7 32.7 2.0 2.1 40.9

1.0 mm² (solid)

1 0.6 0.8 6.9 0.9 1.3 11.3

2 0.6 1.1 12.0 0.9 1.5 16.8

5 0.6 1.2 14.9 1.25 1.6 20.6

10 0.6 1.3 20.5 1.6 1.7 27.1

15 0.6 1.5 23.8 1.6 1.8 30.6

20 0.6 1.5 26.9 1.6 1.9 33.9

30 0.6 1.7 32.6 2.0 2.1 40.8

50 0.6 2.2 42.0 2.5 2.4 51.8

0.5 mm² (flexible)

1 0.6 0.8 6.5 0.9 1.3 10.9

2 0.6 1.1 11.3 0.9 1.5 16.1

5 0.6 1.2 13.9 1.25 1.6 19.6

10 0.6 1.3 19.1 1.6 1.7 25.7

15 0.6 1.3 21.6 1.6 1.8 28.4

20 0.6 1.5 25.0 1.6 1.9 32.0

30 0.6 1.7 30.3 2.0 2.0 38.3

50 0.6 2.0 38.5 2.5 2.3 48.1

Page 74: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Triple, PE-Insulation, Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH

TPM/AD//02.03.99 Page 71© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 7.1 0.9 1.3 11.5

2 0.6 1.2 12.5 1.25 1.5 18.0

5 0.6 1.2 15.3 1.25 1.6 21.0

10 0.6 1.3 21.0 1.6 1.8 27.8

15 0.6 1.5 24.4 1.6 1.9 31.4

20 0.6 1.5 27.6 1.6 1.9 34.6

30 0.6 1.7 33.5 2.0 2.1 41.7

50 0.6 2.2 43.1 2.5 2.4 52.9

1.5 mm² (stranded)

1 0.6 0.9 8.1 0.9 1.4 12.7

2 0.6 1.2 13.5 1.25 1.5 19.0

5 0.6 1.2 17.3 1.25 1.7 23.2

10 0.6 1.5 24.4 1.6 1.9 31.4

15 0.6 1.5 27.8 1.6 1.9 34.8

20 0.6 1.7 32.0 2.0 2.1 40.2

30 0.6 2.0 38.9 2.5 2.3 48.5

50 0.6 2.2 49.3 2.5 2.6 59.5

RT = radial thickness

Page 75: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH TiMF

TPM/AD//02.03.99 Page 72© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial acc. to national regulations. For indoor and outdoor installation in dry and wet locations onracks, in conduits.

ConstructionConductor.............. plain annealed copper, solid, sizes: 0.5 mm² or 1.0 mm²

Insulation............... polyethylene PE

Colour code........... black / white / red;with numbered tape under separator tape of the triple screen

Triple screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. zero halogen flame retardant compound LSZH, black

Armour................... galvanized round steel wires

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +70°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2Y insulation of PE(St) collective screenH bedding & outer sheath

of LSZHSWA steel wire armourTiMF triple screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5 1.0

Conductor resistance max. Ω/km 36.8 18.4

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 25

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 76: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Multi-Triple, PE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 70°C / 300/500 VRE-2Y(St)HSWAH TiMF

TPM/AD//02.03.99 Page 73© KERPENWERK GmbH & Co. 1999

Geometrical data

No. oftriples

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm²

2 0.5 1.1 11.0 0.9 1.5 15.8

5 0.5 1.2 14.1 1.25 1.6 19.8

10 0.5 1.3 19.4 1.6 1.7 26.0

15 0.5 1.3 22.0 1.6 1.8 28.8

20 0.5 1.5 25.4 1.6 1.9 32.4

30 0.5 1.7 30.8 2.0 2.0 38.8

50 0.5 2.0 39.2 2.5 2.3 48.8

1.0 mm²

2 0.6 1.2 13.3 1.25 1.5 18.8

5 0.6 1.2 16.8 1.25 1.6 22.5

10 0.6 1.5 23.8 1.6 1.8 30.6

15 0.6 1.5 27.0 1.6 1.9 34.0

20 0.6 1.7 31.1 2.0 2.0 39.1

30 0.6 2.0 37.8 2.5 2.3 47.4

50 0.6 2.2 47.9 2.5 2.6 58.1

RT = radial thickness

Page 77: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath 90°C / 300/500 VRE-2X(St)H

TPM/AD//01.03.99 Page 74© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... cross-linked polyethylene XLPE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +90°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2X insulation of XLPE(St) collective screenH outer sheath of LSZH

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 78: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath 90°C / 300/500 VRE-2X(St)H

TPM/AD//01.03.99 Page 75© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.5 40 7076B000

2 q 0.5 0.8 6.8 60 7076B001

5 0.5 1.1 10.9 130 7076B002

10 0.5 1.2 14.4 220 7076B003

15 0.5 1.2 16.5 300 7076B004

20 0.5 1.3 18.8 385 7076B005

30 0.5 1.3 22.3 545 7076B006

50 0.5 1.5 28.5 875 7076B007

1.0 mm² (solid)

1 0.6 0.8 6.6 50 7076B015

2 q 0.6 0.8 8.0(8.4?) 85 7076B016

5 0.6 1.2 13.5 200 7076B017

10 0.6 1.2 17.7 340 7076B018

15 0.6 1.3 20.6 510 7076B019

20 0.6 1.5 23.8 650 7076B020

30 0.6 1.5 28.4 950 7076B021

50 0.6 2.0 36.6 1570 7076B022

0.5 mm² (flexible)

1 0.6 0.8 6.2 40 7076B030

2 q 0.6 0.8 7.6 60 7076B031

5 0.6 1.1 12.4 145 7076B032

10 0.6 1.2 16.5 245 7076B033

15 0.6 1.3 19.2 345 7076B034

20 0.6 1.3 21.7 430 7076B035

30 0.6 1.5 26.4 640 7076B036

50 0.6 1.7 33.4 1005 7076B037

Page 79: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Single- & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath 90°C / 300/500 VRE-2X(St)H

TPM/AD//01.03.99 Page 76© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 6.7 60 70760019

2 q 0.6 0.9 8.4 80 70760020

5 0.6 1.2 13.8 185 70760021

10 0.6 1.3 18.4 320 70760022

15 0.6 1.3 21.1 440 70760023

20 0.6 1.5 24.4 585 70760024

30 0.6 1.7 29.5 825 70760025

50 0.6 2.0 37.6 1360 70760026

1.5 mm² (stranded)

1 0.6 0.8 7.5 65 7076B045

2 q 0.6 0.9 8.9 115 7076B046

5 0.6 1.2 15.6 280 7076B047

10 0.6 1.3 20.9 495 7076B048

15 0.6 1.5 24.7 735 7076B049

20 0.6 1.5 27.9 935 7076B050

30 0.6 1.7 33.8 1375 7076B051

50 0.6 2.0 43.1 2235 7076B052

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 80: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, LSZH-Sheath 90°C / 300/500 VRE-2X(St)H PiMF

TPM/AD//01.03.99 Page 77© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Not recommended for direct burial. For indoor and outdoor installation in dry and wet locations on racks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid,

0.5 mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... cross-linked polyethylene XLPE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 1 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +90°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:6 x cable-Ø

RE- instrumentation cable2X insulation of XLPE(St) collective screenH outer sheath of LSZHPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 81: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, LSZH-Sheath 90°C / 300/500 VRE-2X(St)H PiMF

TPM/AD//01.03.99 Page 78© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 0.9 9.7 90 7076B008

5 0.5 1.2 13.0 180 7076B009

10 0.5 1.2 16.9 310 7076B010

15 0.5 1.3 19.7 440 7076B011

20 0.5 1.3 22.3 550 7076B012

30 0.5 1.5 27.2 815 7076B013

50 0.5 2.0 35.1 1355 7076B014

1.0 mm² (solid)

2 0.6 1.1 11.9 135 7076B023

5 0.6 1.2 15.4 255 7076B024

10 0.6 1.3 20.5 460 7076B025

15 0.6 1.5 24.2 670 7076B026

20 0.6 1.7 27.8 870 7076B027

30 0.6 2.0 33.7 1285 7076B028

50 0.6 2.2 42.5 2050 7076B029

0.5 mm² (flexible)

2 0.6 1.1 11.2 110 7076B038

5 0.6 1.2 14.5 205 7076B039

10 0.6 1.3 19.3 350 7076B040

15 0.6 1.5 22.6 505 7076B041

20 0.6 1.5 25.7 630 7076B042

30 0.6 1.7 31.0 885 7076B043

50 0.6 2.2 39.9 1520 7076B044

0.75 mm² (flexible)

2 0.6 1.1 12.1 130 70760027

5 0.6 1.2 15.7 240 70760028

10 0.6 1.3 20.9 420 70760029

15 0.6 1.5 24.6 575 70760030

20 0.6 1.5 28.0 765 70760031

30 0.6 2.0 34.4 1165 70760032

50 0.6 2.2 43.5 1850 70760033

Page 82: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 1

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, LSZH-Sheath 90°C / 300/500 VRE-2X(St)H PiMF

TPM/AD//01.03.99 Page 79© KERPENWERK GmbH & Co. 1999

1.5 mm² (stranded)

2 0.6 1.2 13.6 185 7076B053

5 0.6 1.3 17.7 340 7076B054

10 0.6 1.5 24.0 630 7076B055

15 0.6 1.7 28.0 910 7076B056

20 0.6 1.7 31.8 1160 7076B057

30 0.6 2.0 38.7 1715 7076B058

50 0.6 2.2 49.0 2750 7076B059

RT = radial thickness

Page 83: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Pair, XLPE-Insulation, Collective Screen, Armour, LSZH-Sheath 90°C / 300/500 VRE-2X(St)HSWAH

TPM/Ki//22.02.99 Page 80© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial acc. to national regulations. For indoor and outdoor installation in dry and wet locations onracks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid, 0.5

mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... cross-linked polyethylene XLPE

Colour code........... according to BS 5308 PART 1 (see Appendix)

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. zero halogen flame retardant compound LSZH, black

Armour................... galvanized round steel wires

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +90°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2X insulation of XLPE(St) collective screenH bedding & outer sheath

of LSZHSWA steel wire armour

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHzone pair and two pairall other cables

max. nF/km115

7511585

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U max. V 300/500

Page 84: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Pair, XLPE-Insulation, Collective Screen, Armour, LSZH-Sheath 90°C / 300/500 VRE-2X(St)HSWAH

TPM/Ki//22.02.99 Page 81© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

1 0.5 0.8 5.5 0.9 1.3 9.9 190 8013B000

2 q 0.5 0.8 6.8 0.9 1.3 11.2 250 8013B001

5 0.5 1.1 10.9 0.9 1.4 15.5 420 8013B002

10 0.5 1.2 14.4 1.25 1.6 20.1 720 8013B003

15 0.5 1.2 16.5 1.25 1.6 22.2 870 8013B004

20 0.5 1.3 18.8 1.6 1.7 25.4 1200 8013B005

30 0.5 1.3 22.3 1.6 1.8 29.1 1500 8013B006

50 0.5 1.5 28.5 1.6 2.0 35.7 2090 8013B007

1.0 mm² (solid)

1 0.6 0.8 6.6 0.9 1.3 11.0 230 8013B015

2 q 0.6 0.8 8.0 0.9 1.4 12.6 340 8013B016

5 0.6 1.2 13.5 1.25 1.5 19.0 660 8013B017

10 0.6 1.2 17.7 1.25 1.7 23.6 960 8013B018

15 0.6 1.3 20.6 1.6 1.8 27.4 1410 8013B019

20 0.6 1.5 23.8 1.6 1.8 30.6 1680 8013B020

30 0.6 1.5 28.4 1.6 2.0 35.6 2160 8013B021

50 0.6 2.0 36.6 2.0 2.2 45.0 3450 8013B022

0.5 mm² (flexible)

1 0.6 0.8 6.2 0.9 1.3 10.6 210 8013B030

2 q 0.6 0.8 7.6 0.9 1.3 12.0 260 8013B031

5 0.6 1.1 12.4 0.9 1.5 17.2 480 8013B032

10 0.6 1.2 16.5 1.25 1.6 22.2 810 8013B033

15 0.6 1.3 19.2 1.6 1.7 25.8 1170 8013B034

20 0.6 1.3 21.7 1.6 1.8 28.5 1350 8013B035

30 0.6 1.5 26.4 1.6 1.9 33.4 1770 8013B036

50 0.6 1.7 33.4 2.0 2.1 41.6 2720 8013B037

Page 85: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation CableZero Halogen & Flame Retardant gen. to BS 5308 Part 1 Type 2

Single- & Multi-Pair, XLPE-Insulation, Collective Screen, Armour, LSZH-Sheath 90°C / 300/500 VRE-2X(St)HSWAH

TPM/Ki//22.02.99 Page 82© KERPENWERK GmbH & Co. 1999

0.75 mm² (flexible)

1 0.6 0.8 6.7 0.9 1.3 11.1 230 80130050

2 q 0.6 0.9 8.4 0.9 1.4 13.0 310 80130051

5 0.6 1.2 13.8 1.25 1.6 19.5 660 80130052

10 0.6 1.3 18.4 1.6 1.7 25.0 1120 80130053

15 0.6 1.3 21.1 1.6 1.8 27.9 1340 80130054

20 0.6 1.5 24.4 1.6 1.9 31.4 1650 80130055

30 0.6 1.7 29.5 2.0 2.0 37.5 2390 80130056

50 0.6 2.0 37.6 2.5 2.3 47.2 3740 80130057

1.5 mm² (stranded)

1 0.6 0.8 7.5 0.9 1.4 12.1 270 8013B045

2 q 0.6 0.9 9.3 0.9 1.4 13.9 360 8013B046

5 0.6 1.2 15.6 1.25 1.6 21.3 820 8013B047

10 0.6 1.3 20.9 1.6 1.8 27.7 1400 8013B048

15 0.6 1.5 24.6 1.6 1.9 31.6 1820 8013B049

20 0.6 1.5 27.8 2.0 2.0 35.8 2430 8013B050

30 0.6 1.7 33.7 2.0 2.1 41.9 3120 8013B051

50 0.6 2.0 43.0 2.5 2.4 52.8 4930 8013B052

RT = radial thickness q = 2 pairs are twisted in quad formation

Page 86: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable gen. to BS 5308 Part 1 Type 2Zero Halogen & Flame Retardant

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 90°C / 300/500 VRE-2X(St)HSWAH PiMF

TPM/AD//01.03.99 Page 83© KERPENWERK GmbH & Co. 1999

ApplicationFor transmission of analogue and digital signals in instrument and control systems; use in zone 1 and zone 2 group ΙΙclassified areas (IEC 60079 part 14). Not allowed for direct connection to low impedance source, e.g. the public mainselectricity supply.

Recommended for direct burial acc. to national regulations. For indoor and outdoor installation in dry and wet locations onracks, in conduits.

ConstructionConductor.............. plain annealed copper, sizes: 0.5 mm² solid, 1.0 mm² solid,

0.5 mm² flexible, 0.75 mm² flexible or 1.5 mm² stranded

Insulation............... cross-linked polyethylene XLPE

Colour code........... black / blue;with numbered tape under separator tape of the pair screen

Pair screen.......... 24 µm aluminium / PETP tape over tinned copper drainwire, 0.5 mm²

Wrapping................ at least 1 layer of plastic tape

Collective screen... 24 µm aluminium / PETP tape over tinned copperdrain wire, 0.5 mm²

Bedding.................. zero halogen flame retardant compound LSZH, black

Armour................... galvanized round steel wires

Outer sheath.......... zero halogen flame retardant compound LSZH, black or blue forintrinsically safe systems

Cable marking........ KERPENWERK gen. to BS 5308 Part 1 Type 2 LSZH

Technical Data AbbreviationsFlame retardancy: BS 4066-1Flame propagation: BS 4066-3Smoke density: BS 6724 appendix FDegree of acidity of gases: BS 6425-1Amount of halogen acid gas: 0%

(BS 6425-1)Outer sheath:Limiting Oxygen Index (LOI): min. 35%

(IEC 60332-3 annex B)Temperature index (TI): min. 250°C

(ASTM-D-2863)

Temperature range:-40°C up to +90°C(during operation)- 5°C up to +50°C(during installation)

Min. bending radius:8 x cable-Ø

RE- instrumentation cable2X insulation of XLPE(St) collective screenH bedding & outer sheath

of LSZHSWA steel wire armourPiMF pair screen

Electrical data at 20°CCharacter Unit Values

Conductor size nom. mm² 0.5solid

1.0solid

0.5flexible

0.75flexible

1.5stranded

Conductor resistance max. Ω/km 36.8 18.4 39.7 26.5 12.3

Insulation resistance min. MΩ x km 5000

Mutual capacitance at 0.8 resp. 1 kHz max. nF/km 115

Capacitance unbalance at 1 kHz max. pF/250 m 250

L/R (ratio) max. µH/Ω 25 40

Test voltage Urms core : coreUrms core : screen

VV

10001000

Rated voltage U0 / U V 300/500

Page 87: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable gen. to BS 5308 Part 1 Type 2Zero Halogen & Flame Retardant

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 90°C / 300/500 VRE-2X(St)HSWAH PiMF

TPM/AD//01.03.99 Page 84© KERPENWERK GmbH & Co. 1999

Geometrical data

No. ofpairs

RT ofinsulation

nom.(mm)

RT ofbedding

nom.(mm)

Dia. overbedding

approx.(mm)

Dia. ofarmour

wirenom.(mm)

RT ofouter

sheathnom.(mm)

OverallDiameter

approx.(mm)

Weight

approx.(kg/km)

Part No.

0.5 mm² (solid)

2 0.5 0.9 9.7 0.9 1.4 14.3 350 8112B050

5 0.5 1.2 13.0 1.25 1.5 18.5 625 8112B051

10 0.5 1.2 16.9 1.25 1.7 22.8 900 8112B052

15 0.5 1.3 19.7 1.6 1.7 26.3

20 0.5 1.3 22.3 1.6 1.8 29.1 1505 8112B054

30 0.5 1.5 27.1 1.6 1.9 34.1

50 0.5 2.0 35.0 2.0 2.2 43.4

1.0 mm² (solid)

2 0.6 1.1 11.9 0.9 1.5 16.7

5 0.6 1.2 15.4 1.25 1.6 21.1

10 0.6 1.3 20.5 1.6 1.8 27.3

15 0.6 1.5 24.1 1.6 1.9 31.1

20 0.6 1.7 27.7 2.0 2.0 35.7

30 0.6 2.0 33.7 2.0 2.2 42.1

50 0.6 2.2 42.5 2.5 2.5 52.5

0.5 mm² (flexible)

2 0.6 1.1 11.2 0.9 1.5 16.0 415 8112B060

5 0.6 1.2 14.5 1.25 1.6 20.2 700 8112B061

10 0.6 1.3 19.3 1.6 1.8 26.1 1190 8112B062

15 0.6 1.5 22.6 1.6 1.8 29.4

20 0.6 1.5 25.7 1.6 1.9 32.7 1740 8112B064

30 0.6 1.7 31.0 2.0 2.1 39.2

50 0.6 2.2 39.9 2.5 2.4 49.7

0.75 mm² (flexible)

2 0.6 1.1 12.1 0.9 1.5 16.9

5 0.6 1.2 15.7 1.25 1.6 21.4 780 8112B071

10 0.6 1.3 20.9 1.6 1.7 27.5 1310 8112B072

15 0.6 1.5 24.6 1.6 1.9 31.6

20 0.6 1.5 27.9 1.6 1.9 34.9 2220 8112B074

30 0.6 2.0 34.4 2.0 2.2 42.8

50 0.6 2.2 43.5 2.5 2.5 53.5

Page 88: Instrumentation Cables - ykeng.comykeng.com/kerpen/download/BS5308_432.pdf · Instrumentation Cables BS 5308, Part 1 BS 5308, Part 2 and gen. to BS 5308, Part 1

Instrumentation Cable gen. to BS 5308 Part 1 Type 2Zero Halogen & Flame Retardant

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, Armour, LSZH-Sheath 90°C / 300/500 VRE-2X(St)HSWAH PiMF

TPM/AD//01.03.99 Page 85© KERPENWERK GmbH & Co. 1999

1.5 mm² (stranded)

2 0.6 1.2 13.6 1.25 1.6 19.3 660 8112B090

5 0.6 1.3 17.7 1.6 1.7 24.3 1100 8112B091

10 0.6 1.5 23.9 1.6 1.9 30.9 1680 8112B092

15 0.6 1.7 28.0 2.0 2.0 36.0

20 0.6 1.7 31.7 2.0 2.1 39.9 2830 8112B094

30 0.6 2.0 38.6 2.5 2.5 48.6

50 0.6 2.2 48.9 2.5 2.7 59.3

RT = radial thickness