Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal...

30
Instrument Current Transformers electronics

Transcript of Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal...

Page 1: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

Instrument Current Transformers Instrument Current Transformers

electronicselectronics

Page 2: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

Company ProfilePrincipal Business

Falco is a preferred supplier because of its

ability to provide effective solutions. Falco

began operations in the USA and Mexico in

1991 and has been manufacturing in China

since 1996. In 2005 Falco added an

operation in India. In 2008 the Mexican

operation was expanded to include metal

stamping, molding, and mechanical

assemblies. Falco is an ISO 9001 registered

company by UL since 1998. Falco is a

strategic supplier to many of the leading

OEMs in the power conversion and

metering industries

To provide effective and competitive solutions and service to our customers from the design stage

through mass production.

To design magnetic-based electronic components for the power conversion industry, power distribution,

energy metering, and solar inverter industries.

Mission

Current Range from 50A to 6000AAC

UL and cUL recognized per ANSI/IEEE Standard

Routine and Design Tested per IEEE C57.13

and IEC 61869-1

Basic Insulation Levels (BIL) of 10kV full wave

Accuracy Class as low as 0.15

Rectangular and Toroidal CT Models to meet any

footprint application

Single and three-phase, multi-ratio models available

1A and 5A secondaries. Custom designs available

upon request

Features

Page 3: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

Details

Product Overview

meet accuracy from 10% of nominal current to rating factor. The transformers

are encapsulated into recognized plastic housings and epoxy potted to meet

mechanical requirements.

APPLICATION

Instrument current transformers are precision devices designed to accurately

meter current on an electrical circuit. They provide a means to protect the

metering instrumentation from the power available in the circuit, safely isolating

secondary control circuitry from high currents.

End Product applications include: Motor Control Centers, UPS Systems, Utility

Metering, Low and Medium Voltage Switchgear.

Falco transformers comply with IEEE C57.13 industry standard for

instrument transformers in the US and Canada. They are certified to

Falco Part Numbers Width Multi-Ratio

ICT890XX 5.00" Wide

ICT11AXX 3.94" Wide Y

ICT820XX 3.00" Wide

ICT82AXX 3.00" Wide Y

ICT780XX 1.28" Wide

ICT910XX 3.38" Wide

ICT91AXX 3.38" Wide Y

ICT870XX 5.00" Wide

ICT960XX 3.50" Wide

ICT96AXX 3.50" Wide Y

ICT980XX 7.00" Wide

ICT98AXX 7.00" Wide Y

ICT400XX 2.25" Wide

ICRT60XX 1.80" Wide

7.00" Internal Diameter

Description

5.50" Internal Diameter

5.75" Internal Diameter

5.70" Internal Diameter

6.30" Internal Diameter

3P 2.0" & 2.5" Internal Diameter

2.1" X 3.1" Retangular Window

6.50" Internal Diameter

ICT11AXX

ICT890XX

ICT82AXX

ICT820XX

ICT780XX

ICT910XX

..............4

..............6

..............7

..............8

..............10

..............12

..............14

..............16

..............18

..............20

..............22

..............24

..............26

..............28

ICT870XX

ICT91AXX

ICT960XX

ICT96AXX

ICT98AXX

ICT980XX

ICT400XX

ICRT60XX

Page 4: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 50.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 50.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 5.00”

5.50” Internal Diameter

MECHANICAL SPECIFICATIONS

B0.1 B0.2 B0.5 B0.9 B1.8

ICT89001 200:5 C50 0.3 0.6 1.2 1.2 2.4 0.08 2.0

ICT89002 600:5 C200 0.3 0.3 0.3 0.3 0.3 0.31 2.0

ICT89003 1200:5 C400 0.3 0.3 0.3 0.3 0.3 0.62 2.0

ICT89004 1500:5 C400 0.3 0.3 0.3 0.3 0.3 0.72 1.5

ICT89005 1600:5 C400 0.3 0.3 0.3 0.3 0.3 0.77 1.5

ICT89006 2000:5 C400 0.3 0.3 0.3 0.3 0.3 0.96 1.5

ICT89007 2500:5 C400 0.3 0.3 0.3 0.3 0.3 1.21 1.5

ICT89008 3200:5 C400 0.3 0.3 0.3 0.3 0.3 1.50 1.3

ICT89009 4000:5 C400 0.3 0.3 0.3 0.3 0.3 2.38 0.8

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT

RATIO (A)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ SECONDARY WINDING

RESISTANCE (OHMS @75C)

DIMENSIONS IN INCHES[MM]

X1X2

H19.880

[250.95]

FRONT VIEW

Φ 0.560[14.22]

4 HOLES

SIDE VIEW

5.000[127.00]7.500[190.50]

Φ 5.500[139.70]

0.551”[14.00]

1.170[29.71]

7.500[190.50]

9.880[250.95]

WIDTH

0.940[23.87]

4

E469271

R

C US

Page 5: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1 0 0

1 0 0 0

1 0 0 0 0

0 .0 1 0 0 .1 0 0 1 .0 0 0

4 0 0 0 :5

3 2 0 0 :5

3 0 0 0 :5

10

100

1000

0.010 0.100 1.000

2 5 00 :5

2 0 00 :5

1 6 00 :5

1 5 00 :5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

1

10

10 0

10 00

0.01 0 0.10 0 1.00 0

1 2 00 :5

1 0 00 :5

6 0 0:5

4 0 0:5

2 0 0:5

1 0 0:5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 5.00”

5.50” Internal Diameter, Excitation Curves

5

Page 6: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.94”

5.70” Internal Diameter, Multi-Ratio

ELECTRICAL SPECIFICATIONS

DIMENSIONS IN INCHES[MM]

FRONT VIEW SIDE VIEW CONNECTION DIAGRAM

X2 X1

H1

X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

TURNS

TURNS

TURNS

TURNS

20105040

20604040

402010080

8016060100

X2 X1X3X4X5

TURNS20024060100

600:5A

800:5A

1200:5A

2000:5A

3000:5A

X5 X4 X3 X2 X1

4000:5A 200 200 300 100TURNS

11.34[288.00]

0.42[10.80]

5.71[145.00]

14.09[358.00]

Ø 0.400[10.10]

(4) HOLES

12.60[320.00]

4.00[101.60]

1.180[30.00]

3.94[100.00]

WIDTH

5.71[145.00]

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 40.0 lbs

Excitation curves upon request

Secondary terminals are brass screws No. 10-32 with one

flatwasher, lockwasher, accessible from either side

Tested per ANSI/IEEE C57.13, CAN3-C13-M83

and IEC 61869-2 standards.

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 40.0 lbs

Excitation curves upon request

Secondary terminals are brass screws No. 10-32 with one

flatwasher, lockwasher, accessible from either side

Tested per ANSI/IEEE C57.13, CAN3-C13-M83

and IEC 61869-2 standards.

MECHANICAL SPECIFICATIONS

6

B0.1 B0.2 B0.5 B0.9 B1.8

ICT11A06 600:5 C100 0.3 0.3 0.3 0.3 0.16 2.0

ICT11A20 800:5 N/A 0.3 0.3 0.3 0.3 0.22 2.0

ICT11A05 1200:5 C200 0.3 0.3 0.3 0.3 0.3 0.43 2.0

ICT11A16 1200:5 N/A 0.3 0.3 0.3 0.3 0.3 0.51 2.0

ICT11A15 1600:5 C400 0.3 0.3 0.3 0.3 0.3 0.66 2.0

ICT11A10 2000:5 C400 0.3 0.3 0.3 0.3 0.3 0.72 2.0

ICT11A03 2000:5 C400 0.3 0.3 0.3 0.3 0.3 0.73 2.0

ICT11A02 3000:5 C400 0.3 0.3 0.3 0.3 0.3 1.22 1.3

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO

(A), (X1-X5)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

B0.1 B0.2 B0.5 B0.9 B1.8

ICT11A07 600:5 C200 0.3 0.3 0.3 0.3 0.24 2.0

ICT11A01 1200:5 C400 0.3 0.3 0.3 0.3 0.3 0.63 2.0

ICT11A04 2000:5 C800 0.3 0.3 0.3 0.3 0.3 0.96 2.0

ICT11A08 3000:5 C800 0.3 0.3 0.3 0.3 0.3 1.60 1.3

ICT11A09 4000:5 C800 0.3 0.3 0.3 0.3 0.3 1.96 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO

(A), (X1-X5)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

2.5 V.A 5.0 V.A 12.5 V.A 30 V.A 50 V.A

ICT11A11 1200:5 10P20 50VA 0.2 0.2 0.2 0.2 0.33 1.2

ICT11A19 1200:5 N/A 0.2 0.2 0.2 0.2 0.38 1.2

ICT11A13 1200:5 5P20 40VA 0.2 0.2 0.2 0.2 0.2 0.40 1.2

ICT11A14 1200:5 N/A 0.2 0.2 0.2 0.2 0.2 0.42 1.2

ICT11A18 1200:5 5P20 10VA 0.2 0.2 0.2 0.2 0.2 0.43 1.2

ICT11A12 2000:5 10P20 50VA 0.2 0.2 0.2 0.2 0.2 0.86 1.2

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO

(A), (X1-X5)

RELAY

CLASS

IEC METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

B0.1 B0.2 B0.5 B0.9 B2.0

ICT11A21 1200:5 2.5L400 0.3 0.3 0.3 0.3 0.3 0.63 2.0

ICT11A17 2000:5 2.5L200 0.3 0.3 0.3 0.3 0.3 0.61 2.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO

(A), (X1-X5)

RELAY

CLASS

CAN METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

Page 7: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.00”

5.75” Internal Diameter, Multi-Ratio

7

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 18.0 lbs

Excitation curves upon request

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 18.0 lbs

Excitation curves upon request

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

B0.1 B0.2 B0.5 B0.9 B1.8

ICT82A18 600:5 C50 0.3 0.3 0.3 0.3 0.6 0.20 2.0

ICT82A02 1200:5 C100 0.3 0.3 0.3 0.3 0.3 0.53 1.5

ICT82A08 2000:5 C100 0.3 0.3 0.3 0.3 0.3 1.12 1.3

ICT82A04 3000:5 C200 0.3 0.3 0.3 0.3 0.3 1.48 1.0

ICT82A03 3200:5 C200 0.3 0.3 0.3 0.3 0.6 1.02 1.0

ICT82A01 4000:5 C200 0.3 0.3 0.3 0.3 0.3 1.69 1.0

ICT82A06 5000:5 C200 0.3 0.3 0.3 0.3 0.3 1.53 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO (A),

(X1-X5)

RELAY

CLASS

ANSI METERING ACCURACY CLASS AT 60HZ (X1-X5) TYPICAL SECONDARY RESISTANCE

(OHMS @75C), (X1-X5)

MECHANICAL SPECIFICATIONS

DIMENSIONS IN INCHES[MM]

X1X2

H19.210

[233.93]

FRONT VIEW

Φ 0.550[13.97]

(4) HOLES

3.000[76.20]7.450[189.23]

Φ 5.750[146.05]

0.551”[14.00]

0.880[22.35]

7.450[189.23]

9.210[233.93]

WIDTH

0.750[19.05]0.750[19.05]

1.500[38.10]

SIDE VIEW CONNECTION DIAGRAM

X2 X1

H1

X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

TURNS

TURNS

TURNS

TURNS

20105040

402010080

8016060100

20024060100

X2 X1X3X4X5

TURNS100300200200

600:5A

1200:5A

2000:5A

3000:5A

4000:5A

X5 X4 X3

E469271

R

C US

Page 8: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

DIMENSIONS IN INCHES[MM]

X1X2

H19.210

[233.93]

Φ 0.550[13.97]

4 HOLES

3.000[76.20]7.450[189.23]

Φ 5.750[146.05]

0.551”[14.00]

0.880[22.35]

7.450[189.23]

9.210[233.93]

WIDTH

0.750[19.05]

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 18.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 18.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.00”

5.75” Internal Diameter

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW

8

B0.1 B0.2 B0.5 B0.9 B1.8

ICT82014 50:5 4.8 0.02 2.0

ICT82011 75:5 2.4 4.8 0.03 2.0

ICT82012 100:5 1.2 2.4 4.8 0.03 2.0

ICT82013 150:5 C10 0.6 1.2 2.4 4.8 0.05 2.0

ICT82010 200:5 C10 0.6 0.6 1.2 2.4 4.8 0.06 2.0

ICT82015 250:5 C20 0.6 0.6 1.2 2.4 2.4 0.10 2.0

ICT82016 300:5 C20 0.3 0.3 0.6 1.2 2.4 0.10 2.0

ICT82009 400:5 C20 0.3 0.3 0.3 0.6 1.2 0.13 2.0

ICT82017 500:5 C50 0.3 0.3 0.3 0.3 0.6 0.15 2.0

ICT82018 600:5 C50 0.3 0.3 0.3 0.3 0.6 0.18 2.0

ICT82019 800:5 C50 0.3 0.3 0.3 0.3 0.6 0.32 2.0

ICT82020 1000:5 C100 0.3 0.3 0.3 0.3 0.3 0.40 1.5

ICT82006 1200:5 C100 0.3 0.3 0.3 0.3 0.3 0.48 1.5

ICT82021 1500:5 C100 0.3 0.3 0.3 0.3 0.3 0.69 1.5

ICT82007 1600:5 C100 0.3 0.3 0.3 0.3 0.3 0.64 1.5

ICT82008 2000:5 C100 0.3 0.3 0.3 0.3 0.3 1.02 1.3

ICT82022 2500:5 C200 0.3 0.3 0.3 0.3 0.3 1.32 1.0

ICT82004 3000:5 C200 0.3 0.3 0.3 0.3 0.3 1.35 1.0

ICT82003 3200:5 C200 0.3 0.3 0.3 0.3 0.3 0.77 1.0

ICT82001 4000:5 C200 0.3 0.3 0.3 0.3 0.3 1.54 1.0

ICT82002 5000:5 C200 0.3 0.3 0.3 0.3 0.3 1.39 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT

RATIO (A)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ SECONDARY WINDING

RESISTANCE (OHMS @75C)

E469271

R

C US

Page 9: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.00”

5.75” Internal Diameter, Excitation Curves

9

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

100

1000

0.001 0.010 0.100 1.000

2000:5

1600:5

1500:5

1200:5

1000:5

800:5

600:5

500:5

10

100

1000

0.001 0.010 0.100 1.000

5000:5

4000:5

3200:5

3000:5

2500:5

1

10

100

0.001 0.010 0.100 1.000

400:5

300:5

250:5

200:5

150:5

100:5

75:5

50:5

Page 10: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 3.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 3.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 1.28”

6.30” Internal Diameter

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW

10

B0.1 B0.2 B0.5 B0.9 B1.8

ICT78002 1200:5 C200 0.3 0.3 0.3 0.6 1.2 0.17 1.5

ICT78005 1600:5 C200 0.3 0.3 0.3 0.3 0.6 0.24 1.5

ICT78003 2500:5 C200 0.3 0.3 0.3 0.3 0.3 0.36 1.3

ICT78001 3000:5 C200 0.3 0.3 0.3 0.3 0.3 0.43 1.0

ICT78004 4000:5 C400 0.3 0.3 0.3 0.3 0.3 0.75 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT

RATIO (A)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ SECONDARY WINDING

RESISTANCE (OHMS @75C)

X1X2

H1

9.843[250.00]

Φ 0.433[11.00]

4 HOLES

7.500[190.50]

Φ 6.300[160.02]

0.62[15.75]

7.500[190.50]

8.740[222.00]

0.750[19.05]

1.280[32.51]WIDTH

9.292[236.02]

0.551”[14.00]

DIMENSIONS IN INCHES[MM]

E469271

R

C US

Page 11: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 1.28”

6.30” Internal Diameter, Excitation Curves

11

Typical Excitation Curves

Excitation current at 60Hz (A)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

100

0.010 0.100 1.000

4000:5

3200:5

3000:5

2500:5

2000:5

1

10

100

0.010 0.100 1.000

1600:5

1500:5

1200:5

1000:5

800:5

600:5

400:5

Page 12: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

H2

X1X2

X3X4

X5

8.382[212.90]

8.382[212.90]

Ø 0.580[14.73]

(3) HOLES

9.882[251.00]

0.750[19.05]

0.750[19.05]

6.500[165.10]

1.380[35.05]

3.380[85.85]

9.882[251.00]

H1side

WIDTH

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.38”

6.50” Internal Diameter

ELECTRICAL SPECIFICATIONS

DIMENSIONS IN INCHES[MM]

FRONT VIEWSIDE VIEW

MECHANICAL SPECIFICATIONS

12

B0.1 B0.2 B0.5 B0.9 B2.0

ICT91010 75:5 C10 2.4 2.4 0.01 2.0

ICT91011 100:5 C10 1.2 2.4 0.21 2.0

ICT91007 150:5 C20 0.6 1.2 2.4 0.44 2.0

ICT91008 200:5 C20 0.6 0.6 1.2 0.04 2.0

ICT91012 250:5 C20 0.6 0.6 1.2 2.4 0.06 2.0

ICT91013 300:5 C20 0.3 0.6 1.2 1.2 2.4 0.08 2.0

ICT91005 400:5 C50 0.3 0.3 0.6 1.2 1.2 0.11 2.0

ICT91014 500:5 C50 0.3 0.3 0.3 0.6 1.2 0.11 2.0

ICT91002 600:5 C50 0.3 0.3 0.3 0.6 0.6 0.12 2.0

ICT91016 800:5 C100 0.3 0.3 0.3 0.3 0.6 0.24 2.0

ICT91004 1000:5 C100 0.3 0.3 0.3 0.3 0.3 0.33 2.0

ICT91001 1200:5 C100 0.3 0.3 0.3 0.3 0.3 0.29 2.0

ICT91017 1500:5 C200 0.3 0.3 0.3 0.3 0.3 0.60 2.0

ICT91006 2000:5 C200 0.3 0.3 0.3 0.3 0.3 0.61 2.0

ICT91018 2500:5 C200 0.3 0.3 0.3 0.3 0.3 0.56 1.5

ICT91009 3000:5 C200 0.3 0.3 0.3 0.3 0.3 0.50 1.0

ICT91003 4000:5 C200 0.3 0.3 0.3 0.3 0.3 0.91 1.0

CURRENTRATING

FACTOR@30C

CATALOG

NUMBER

CURRENT

RATIO (A)

RELAY

CLASS

TYPICAL SECONDARY

RESISTANCE(OHMS @75C)

ANSI METERINGACCURACY CLASS AT60HZ

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 75 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 29.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher, lockwasher, accessible from either side

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 75 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 29.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher, lockwasher, accessible from either side

UL and cUL Certified per ANSI/IEEE C57.13 standard.

E469271

R

C US

Page 13: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.38”

6.50” Internal Diameter, Excitation Curves

13

Typical Excitation Curves

1

10

100

0.001 0.010 0.100 1.000

600:5

500:5

400:5

300:5

250:5

200:5

150:5

100:5

75:5

1

10

100

1000

0.001 0.010 0.100 1.000

4000:5

3000:5

2500:5

2000:5

1500:5

1200:5

1000:5

800:5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

Page 14: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

H1

X2X1

X3 X4

X5

8.382[212.90]

8.382[212.90]

9.882[251.00]

0.750[19.05]0.750

[19.05]

6.500[165.10]

1.380[35.05]

3.380[85.85]

9.882[251.00]

H2side

WIDTH

X2 X1

H1

X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

TURNS

TURNS

TURNS

TURNS

20105040

402010080

8016060100

20024060100

X2 X1X3X4X5

TURNS100300200200

600:5A

1200:5A

2000:5A

3000:5A

4000:5A

Ø 0.580[14.73]

(3) HOLES

ELECTRICAL SPECIFICATIONS

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.38”

6.50” Internal Diameter, Multi-Ratio

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW CONNECTION DIAGRAM

14

DIMENSIONS IN INCHES[MM]

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 30.0 lbs

Excitation curves upon request

Secondary terminals are brass screws No. 10-32 with one

flatwasher, lockwasher, accessible from either side

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 30.0 lbs

Excitation curves upon request

Secondary terminals are brass screws No. 10-32 with one

flatwasher, lockwasher, accessible from either side

UL and cUL Certified per ANSI/IEEE C57.13 standard.

B0.1 B0.2 B0.5 B0.9 B1.8

ICT91A03 600:5 C50 0.3 0.3 0.3 0.6 0.6 0.13 2.0

ICT91A01 1200:5 C100 0.3 0.3 0.3 0.3 0.3 0.32 2.0

ICT91A02 2000:5 C200 0.3 0.3 0.3 0.3 0.3 0.64 2.0

ICT91A04 3000:5 C200 0.3 0.3 0.3 0.3 0.3 0.55 1.0

ICT91A05 4000:5 C200 0.3 0.3 0.3 0.3 0.3 1.00 1.0

CURRENT RATING FACTOR

@30C

CATALOG

NUMBER

CURRENT RATIO (A),

(X1-X5)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

E469271

R

C US

Page 15: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Facts:

By combining our capabilities and global

presence, Falco has established a leading

magnetic component manufacturing of

Instrument Current Transformers.

“You have problems

We have solutions”

electronics

Page 16: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 5.00”

6.50” Internal Diameter

16

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 40.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 50 - 5000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 40.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

MECHANICAL SPECIFICATIONS

DIMENSIONS IN INCHES[MM]

X1X2

H19.880

[250.95]

FRONT VIEW

Φ 0.560[14.22]

4 HOLES

SIDE VIEW

5.000[127.00]7.500[190.50]

Φ 6.500[165.10]

0.551”[14.00]

1.170[29.71]

7.500[190.50]

9.880[250.95]

WIDTH

0.940[23.87]

B0.1 B0.2 B0.5 B0.9 B1.8

ICT87001 1200:5 C200 0.3 0.3 0.3 0.3 0.3 0.72 1.5

ICT87002 1500:5 C200 0.3 0.3 0.3 0.3 0.3 1.20 1.5

ICT87003 1600:5 C200 0.3 0.3 0.3 0.3 0.3 1.27 1.5

ICT87004 4000:5 C200 0.3 0.3 0.3 0.3 0.3 2.14 1.0

ICT87005 5000:5 C400 0.3 0.3 0.3 0.3 0.3 2.70 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT

RATIO (A)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ SECONDARY WINDING

RESISTANCE (OHMS @75C)

E469271

R

C US

Page 17: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 5.00”

6.50” Internal Diameter, Excitation Curves

17

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

10

10 0

10 00

0.01 0 0.10 0 1.00 0

3 0 00 :5

2 5 00 :5

2 0 00 :5

100

1000

0.010 0.100 1.000

5000:5

4000:5

3500:5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

100

1000

0.010 0.100 1.000

1600:5

1500:5

1200:5

600:5

200:5

100:5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

Page 18: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 75 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 34.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 75 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 34.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.50”

7.00” Internal Diameter

DIMENSIONS IN INCHES[MM]

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW

18

B 0.1 B 0.2 B 0.5 B 0.9 B 2.0

ICT96001 50:5 C5 4.8 4.8 0.016 2.0

ICT96009 75:5 C10 2.4 4.8 0.023 2.0

ICT96010 100:5 C15 2.4 4.8 0.031 2.0

ICT96003 150:5 C20 0.6 1.2 2.4 0.042 2.0

ICT96011 200:5 C25 0.6 1.2 1.2 0.067 2.0

ICT96012 250:5 C36 0.6 0.6 1.2 2.4 0.080 2.0

ICT96013 300:5 C40 0.6 0.6 1.2 1.2 2.4 0.100 2.0

ICT96006 400:5 C60 0.3 0.6 0.6 1.2 2.4 0.112 2.0

ICT96014 500:5 C75 0.3 0.3 0.3 0.6 1.2 0.165 2.0

ICT96007 600:5 C100 0.3 0.3 0.3 0.6 1.2 0.175 2.0

ICT96015 750:5 C100 0.3 0.3 0.3 0.6 0.6 0.280 2.0

ICT96016 800:5 C130 0.3 0.3 0.3 0.6 0.6 0.267 2.0

ICT96017 1000:5 C170 0.3 0.3 0.3 0.3 0.3 0.320 2.0

ICT96008 1200:5 C200 0.3 0.3 0.3 0.3 0.3 0.400 2.0

ICT96018 1500:5 C200 0.3 0.3 0.3 0.3 0.3 0.580 2.0

ICT96019 1600:5 C180 0.3 0.3 0.3 0.3 0.3 0.460 2.0

ICT96004 2000:5 C210 0.3 0.3 0.3 0.3 0.3 0.540 2.0

ICT96020 2500:5 C300 0.3 0.3 0.3 0.3 0.3 0.730 2.0

ICT96005 3000:5 C240 0.3 0.3 0.3 0.3 0.3 1.100 1.3

ICT96021 3500:5 C200 0.3 0.3 0.3 0.3 0.3 0.760 1.3

ICT96002 4000:5 C230 0.3 0.3 0.3 0.3 0.3 0.940 1.3

ICT96022 5000:5 C300 0.3 0.3 0.3 0.3 0.3 1.250 1.0

CURRENT RATING

FACTO R @ 30C

CATALO G

NUM B ER

CURRENT

RATIO (A)

RELAY

CLASS

TYPICAL SECO NDARY

RESISTANCE (O HM S @ 75C)

ANSI M ETERING ACCURACY CLASS AT 60HZ

B 0.1 B 0.2 B 0.5 B 0.9 B 2.0

ICT96023 250:1 C210 0.6 0 .6 1 .2 2 .4 4 .8 0 .900 3.0

ICT96024 1200:1 C640 0.3 0 .3 0 .3 0 .3 0 .3 6 .200 2.0

ICT96025 2500:1 C800 0.3 0 .3 0 .3 0 .3 0 .3 10.660 1.0

CUR R ENT R ATING

FACTO R @ 30C

CATALO G

NUM B ER

CUR R ENT

R ATIO (A)

R ELAY

CLASS

TYPICAL SECO ND AR Y

R ESISTANCE (O H M S @ 75C)

ANSI M ETER ING ACCUR ACY CLASS AT 60H Z

H1

X2X1

X3 X4

X5

8.882[225.60]

8.882[225.60]

10.75[273.05]

0.940[23.87]0.94

[23.87]

7.02[178.30]

1.380[35.05]

3.50[88.90]

10.75[273.05]

H2side

WIDTHØ 0.580[14.73]

(3) HOLES

E469271

R

C US

Page 19: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.50”

7.00” Internal Diameter, Excitation Curves

19

Typical Excitation Curves

1 0

1 0 0

1 0 0 0

0 .0 0 1 0 .0 1 0 0 .1 0 0 1 .0 0 0

3 0 0 0 :5

2 5 0 0 :5

2 0 0 0 :5

1 6 0 0 :5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

10

10 0

10 00

0.0 01 0.0 10 0.1 00 1.0 00

50 00:5

40 00:5

35 00:5

32 00:5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

100

1000

0.001 0.010 0.100 1.000

1500:5

1200:5

1000:5

800:5

750:5

600:5

500:5

400:5

300:5

250:5

200:5

150:5

100:5

75:5

50:5

Excitation current at 60Hz (A)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Page 20: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.50”

7.00” Internal Diameter, Multi-Ratio

ELECTRICAL SPECIFICATIONS

20

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 32.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 32.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

DIMENSIONS IN INCHES[MM]

B0.1 B0.2 B0.5 B0.9 B2.0

ICT96A07 600:5 C100 0.3 0.3 0.3 0.6 1.2 0.19 2.0

ICT96A01 800:5 C100 0.3 0.3 0.3 0.6 0.6 0.28 2.0

ICT96A08 1200:5 C200 0.3 0.3 0.3 0.3 0.3 0.44 2.0

ICT96A04 2000:5 C200 0.3 0.3 0.3 0.3 0.3 0.60 1.0

ICT96A02 3000:5 C200 0.3 0.3 0.3 0.3 0.3 1.19 1.0

ICT96A03 4000:5 C200 0.3 0.3 0.3 0.3 0.3 1.03 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO

(A), (X1-X5)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW CONNECTION DIAGRAM

H1

X2X1

X3 X4

X5

8.882[225.60]

8.882[225.60]

10.75[273.05]

0.940[23.87]0.94

[23.87]

7.02[178.30]

1.380[35.05]

3.50[88.90]

10.75[273.05]

H2side

WIDTH

X2 X1

H1

X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

TURNS

TURNS

TURNS

TURNS

20105040

20604040

402010080

8016060100

X2 X1X3X4X5

TURNS20024060100

600:5A

800:5A

1200:5A

2000:5A

3000:5A

Ø 0.580[14.73]

(3) HOLES

X5 X4 X3 X2 X1

4000:5A 200 200 300 100TURNS

ICT96A07

1

1 0

1 0 0

1 0 0 0

0 .0 0 1 0 .0 1 0 0 .1 0 0 1 .0 0 0

6 0 0 :5

5 0 0 :5

4 5 0 :5

4 0 0 :5

3 0 0 :5

2 5 0 :5

2 0 0 :5

1 0 0 :5

5 0 :5

1

10

100

1000

0.001 0.010 0.100 1.000

800:5

700:5

600:5

500:5

400:5

300:5

200:5

100:5

ICT96A01

Excitation current at 60Hz (A)Excitation current at 60Hz (A)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

E469271

R

C US

Page 21: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 3.50”

7.00” Internal Diameter, Multi-Ratio Excitatioin Curves

21

ICT96A08

1

10

10 0

10 00

0.0 01 0.0 10 0.1 00 1.0 00

40 00:5

35 00:5

30 00:5

25 00:5

20 00:5

15 00:5

10 00:5

50 0:5

ICT96A03

ICT96A02

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

10 0

10 00

0.0 01 0.0 10 0.1 00 1.0 00

20 00:5

16 00:5

15 00:5

12 00:5

80 0:5

50 0:5

40 0:5

30 0:5

1

10

10 0

10 00

0.0 01 0.0 10 0.1 00 1.0 00

30 00:5

25 00:5

20 00:5

15 00:5

12 00:5

10 00:5

80 0:5

50 0:5

30 0:5

1

10

100

1000

0.001 0.010 0.100 1.000

1200:5

1000:5

800:5

600:5

500:5

400:5

300-5

200:5

100:5

ICT96A04

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

Excitation current at 60Hz (A)

Excitation current at 60Hz (A)

Excitation current at 60Hz (A)

Page 22: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

H1

X2X1

X3 X4

X5

8.882[225.60]

8.882[225.60]

0.940[23.87]0.94

[23.87]

7.02[178.30] H2

side

Ø 0.580[14.73]

(3) HOLES

7.00[177.80]

1.380[35.05]

10.75[273.05]

10.75[273.05]

ELECTRICAL SPECIFICATIONS

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 75 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 64.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Switchgear Relay and Metering

Frequency 50 - 400 Hz

AC capability 75 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 64.0 lbs

Other ratios available

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 7.00”

7.00” Internal Diameter

DIMENSIONS IN INCHES[MM]

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW

22

B0.1 B0.2 B0.5 B0.9 B2.0

ICT98007 50:5 C10 4.8 4.8 0.016 2.0

ICT98008 75:5 C20 2.4 2.4 4.8 0.023 2.0

ICT98009 100:5 C30 1.2 2.4 2.4 4.8 0.031 2.0

ICT98005 150:5 C40 0.6 1.2 1.2 2.4 4.8 0.042 2.0

ICT98010 200:5 C60 0.6 0.6 1.2 1.2 2.4 0.067 2.0

ICT98011 250:5 C80 0.3 0.6 0.6 1.2 2.4 0.080 2.0

ICT98001 300:5 C110 0.3 0.3 0.6 0.6 1.2 0.100 2.0

ICT98012 400:5 C130 0.3 0.3 0.3 0.6 0.6 0.112 2.0

ICT98013 500:5 C160 0.3 0.3 0.3 0.3 0.6 0.165 2.0

ICT98004 600:5 C210 0.3 0.3 0.3 0.3 0.3 0.175 2.0

ICT98014 700:5 C250 0.3 0.3 0.3 0.3 0.3 0.280 2.0

ICT98002 800:5 C270 0.3 0.3 0.3 0.3 0.3 0.267 2.0

ICT98015 1000:5 C340 0.3 0.3 0.3 0.3 0.3 0.320 2.0

ICT98003 1200:5 C425 0.3 0.3 0.3 0.3 0.3 0.400 2.0

ICT98016 1600:5 C400 0.3 0.3 0.3 0.3 0.3 0.580 2.0

ICT98006 2000:5 C460 0.3 0.3 0.3 0.3 0.3 0.540 2.0

ICT98017 2500:5 C580 0.3 0.3 0.3 0.3 0.3 0.730 2.0

ICT98018 3000:5 C660 0.3 0.3 0.3 0.3 0.3 1.100 1.3

ICT98019 4000:5 C460 0.3 0.3 0.3 0.3 0.3 0.940 1.3

ICT98020 5000:5 C500 0.3 0.3 0.3 0.3 0.3 1.730 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT

RATIO (A)

RELAY

CLASS

TYPICAL SECONDARY

RESISTANCE (OHMS @75C)

ANSI METERING ACCURACY CLASS AT 60HZ

E469271

R

C US

Page 23: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 7.00”

7.00” Internal Diameter, Excitation Curves

23

Typical Excitation Curves

Excitation current at 60Hz (A)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1 0

1 0 0

1 0 0 0

0 .0 0 1 0 .0 1 0 0 .1 0 0 1 .0 0 0

3 0 0 0 :5

2 5 0 0 :5

2 0 0 0 :5

1 6 0 0 :5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1 0

1 0 0

1 0 0 0

0 .0 0 1 0 .0 1 0 0 .1 0 0 1 .0 0 0

5 0 0 0 :5

4 0 0 0 :5

3 5 0 0 :5

3 2 0 0 :5

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

100

1000

0.001 0.010 0.100 1.000

1200:5

1000:5

800:5

700:5

600:5

500:5

400:5

300:5

250:5

200:5

150:5

100:5

75:5

50:5

Page 24: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 7.00”

7.00” Internal Diameter, Multi-Ratio

ELECTRICAL SPECIFICATIONS

24

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 64.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Relay and Metering

Frequency 50 - 400 Hz

AC capability 600 - 4000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 64.0 lbs

Secondary terminals are brass screws No. 10-32 with one

flatwasher & lockwasher.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

DIMENSIONS IN INCHES[MM]

MECHANICAL SPECIFICATIONS

FRONT VIEW SIDE VIEW CONNECTION DIAGRAM

X2 X1

H1

X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

X2 X1X3X4X5

TURNS

TURNS

TURNS

TURNS

20105040

20604040

402010080

8016060100

X2 X1X3X4X5

TURNS20024060100

600:5A

800:5A

1200:5A

2000:5A

3000:5A

B0.1 B0.2 B0.5 B0.9 B2.0

ICT98A01 600:5 C245 0.3 0.3 0.3 0.6 1.2 0.19 2.0

ICT98A03 1200:5 C425 0.3 0.3 0.3 0.3 0.3 0.44 2.0

ICT98A06 2000:5 C460 0.3 0.3 0.3 0.3 0.3 0.60 1.0

ICT98A02 3000:5 C660 0.3 0.3 0.3 0.3 0.3 1.19 1.0

CURRENT RATING

FACTOR @30C

CATALOG

NUMBER

CURRENT RATIO

(A), (X1-X5)

RELAY

CLASS

ANSI METERING CLASS AT 60HZ (X1-X5) SECONDARY WINDING RESISTANCE

(OHMS @75C), (X1-X5)

H1

X2X1

X3 X4

X5

8.882[225.60]

8.882[225.60]

0.940[23.87]0.94

[23.87]

7.02[178.30] H2

side

Ø 0.580[14.73]

(3) HOLES

7.00[177.80]

1.380[35.05]

10.75[273.05]

10.75[273.05]

Excitation current at 60Hz (A)

ICT98A03

1

10

100

1000

0.001 0.010 0.100 1.000

600:5

500:5

450:5

400:5

300:5

250:5

200:5

100:5

50:5

10

100

1000

0.001 0.010 0.100 1.000

1200:5

1000:5

800:5

600:5

500:5

400:5

300:5

200:5

100:5

Excitation current at 60Hz (A)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

ICT98A01

E469271

R

C US

Page 25: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 7.00”

7.00” Internal Diameter, Multi-Ratio Excitation Cures

25

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

1 0

1 0 0

1 0 0 0

0 .0 0 1 0 .0 1 0 0 .1 0 0 1 .0 0 0

3 0 0 0 :5

2 5 0 0 :5

2 0 0 0 :5

1 5 0 0 :5

1 2 0 0 :5

1 0 0 0 :5

8 0 0 :5

5 0 0 :5

3 0 0 :5

ICT98A02

1

10

10 0

10 00

0.0 01 0.0 10 0.1 00 1.0 00

20 00:5

16 00:5

15 00:5

12 00:5

80 0:5

50 0:5

40 0:5

30 0:5

Excitation current at 60Hz (A)

ICT98A06

Page 26: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

ELECTRICAL SPECIFICATIONS

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 2.25”

3P 2.0” & 2.5” Internal Diameter

MECHANICAL SPECIFICATIONS

26

Application - 3-Phase Metering

Frequency 50 - 400 Hz

AC capability 100 - 1000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 12.0 lbs

Other ratios available

Secondary leads are UL 1015, 105°C, CSA approved,

No. 10 AWG, 108in. long.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - 3-Phase Metering

Frequency 50 - 400 Hz

AC capability 100 - 1000 Amperes

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 12.0 lbs

Other ratios available

Secondary leads are UL 1015, 105°C, CSA approved,

No. 10 AWG, 108in. long.

UL and cUL Certified per ANSI/IEEE C57.13 standard.

B0.1 B0.2 B0.5 B0.9 B1.8

ICT40007 100:5 0.6 1.2 2.4 0.04 1.0 6.75 2.00

ICT40001 150:5 0.6 1.2 2.4 0.06 1.0 6.00 2.00

ICT40005 200:5 0.6 0.6 1.2 2.4 0.08 1.0 8.00 2.00

ICT40003 300:5 0.3 0.6 1.2 2.4 0.06 1.0 6.25 2.50

ICT40006 400:5 0.3 0.3 0.6 1.2 2.4 0.09 1.0 8.35 2.50

ICT40004 600:5 0.3 0.3 0.3 0.6 0.6 0.21 1.0 24.00 2.00

ICT40008 800:5 0.3 0.3 0.3 0.3 0.3 0.30 1.0 32.00 2.00

ICT40009 900:5 0.3 0.3 0.3 0.3 0.3 0.31 1.0 36.19 2.00

ICT40002 1000:5 0.3 0.3 0.3 0.3 0.3 0.28 1.0 25.10 2.00

HOLE

DIAMETER (in)

EXCITATION VOLTAGE

AT KNEE (V), 60 Hz

CATALOG

NUMBER

CURRENT

RATIO (A)

ANSI METERING CLASS AT 60HZ SECONDARY WINDING

RESISTANCE (OHMS @75C)

CURRENT RATING

FACTOR @30C

DIMENSIONS IN INCHES[MM]

TOP VIEW

13.750[349.25]

BOTTOM VIEW

4.750[120.65]

2.250[57.15]

SIDE VIEW

C1 C2 C3G

CG

H2

FRONT VIEW

H1

G CG C1 C2 C3 C3 CG

3.750[95.25]

12.750[323.85]

0.500[12.70]

0.500[12.70]

4.500[114.30] 4.500[114.30]

2.380[60.45]

See chartfor hole

size

0.320 DIA.(4) HOLES

10AWG 108 in. longG = GreenCG = WhiteC1 = RedC2 = BlackC3 = Blue

CONNECTION DIAGRAM

X1 X2

H1

X1 X2

H1’

X1 X2

H1’’

C1C2C3 G CG

WIDTH

E469271

R

C US

Page 27: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 2.25”

3P 2.0” & 2.5” Internal Diameter, Excitation Curves

27

1

10

100

0.001 0.010 0.100 1.000

1000:5

900:5

800:5

600:5

400:5

300:5

200:5

150:5

100:5

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

Page 28: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

E469271

R

C US

5.630[143.00]

6.736[171.10]

2.060[52.32]

3.060[77.72]

0.770[19.55]

0.770[19.55]

1.050[26.67]

1.785[45.34]

0.689[17.50]

X1

X2

H2

1.800[45.72]

0.880[22.35]

0.401[10.20]

3.368[85.55]

Ø 0.344[8.74]

WIDTH

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 1.80”

2.1” x 3.1” Rectangular Window

28

ELECTRICAL SPECIFICATIONS

MECHANICAL SPECIFICATIONS

DIMENSIONS IN INCHES[MM]

FRONT VIEW SIDE VIEW

Application - Metering

Frequency 50 - 400 Hz

AC Capability 100 - 4000A

1 and 2 Amperes Secondaries

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 6.0 lbs

Burden ratings and other ratios available

Secondary terminals are brass No. 10-32 with one

flatwasher, lockwasher & nut

UL and cUL Certified per ANSI/IEEE C57.13 standard.

Application - Metering

Frequency 50 - 400 Hz

AC Capability 100 - 4000A

1 and 2 Amperes Secondaries

Insulation class 0.6 kV, 10 kV BIL full wave

Approximate Weight - 6.0 lbs

Burden ratings and other ratios available

Secondary terminals are brass No. 10-32 with one

flatwasher, lockwasher & nut

UL and cUL Certified per ANSI/IEEE C57.13 standard.

ICRT6004 100:1 0.6 1.0 0.08 1.33

ICRT6005 200:1 0.6 1.0 0.17 1.33

ICRT6006 250:1 0.6 1.5 0.42 1.33

ICRT6017 300:1 0.6 1.5 0.52 1.33

ICRT6007 400:1 0.3 1.5 0.71 1.33

ICRT6008 600:1 0.3 2.0 1.36 1.33

ICRT6016 630:1 0.3 2.0 1.44 1.33

ICRT6001 800:1 0.3 3.0 1.62 1.33

ICRT6009 1000:1 0.3 4.0 2.41 1.33

ICRT6010 1200:1 0.3 5.0 4.48 1.33

ICRT6018 1250:1 0.3 5.0 3.02 1.33

ICRT6019 1500:1 0.3 7.5 4.53 1.33

ICRT6011 1600:1 0.3 7.5 5.69 1.33

ICRT6012 2000:1 0.3 10.0 7.45 1.33

ICRT6020 2000:2 0.3 4.0 1.56 1.33

ICRT6013 2500:1 0.3 12.0 6.47 1.0

ICRT6021 2500:2 0.3 5.0 1.64 1.0

ICRT6014 3000:1 0.3 15.0 6.40 1.0

ICRT6022 3000:2 0.3 7.5 2.04 1.0

ICRT6023 3150:1 0.3 15.0 8.25 1.0

ICRT6015 3200:1 0.3 15.0 8.35 1.0

ICRT6024 3200:2 0.3 2.5 2.19 1.0

ICRT6002 4000:1 0.3 15.0 10.56 1.0

ICRT6003 4000:2 0.3 10.0 2.70 1.0

CATALOG

NUMBER

CURRENT

RATIO (A)VA

SECONDARY WINDING

RESISTANCE (OHMS @75C)

CURRENT RATING

FACTOR @30CACCURACY

Page 29: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

INSTRUMENT CURRENT TRANSFORMER

+1.305.662.7276 | www.falco.com | [email protected]

Width 1.80”

2.1” x 3.1” Rectangular Window, Excitation Curves

29

Typical Excitation Curves

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

1

10

100

1000

0.001 0.010 0.100 1.000

4000:1

3200:1

3000:2

2500:1

2000:1

1500:1

1250:1

630:1

100:1

1

10

100

1000

0.001 0.010 0.100 1.000

4000:2

3200:2

3150:1

3000:1

2500:2

2000:2

1

10

100

1000

0.001 0.010 0.100 1.000

1600:1

1200:1

1000:1

800:1

600:1

400:1

300:1

250:1

200:1

Seco

nd

ary

Vo

ltag

e a

t 60H

z (

V)

Excitation current at 60Hz (A)

Page 30: Instrument Current Transformers - Falco Electronics Falco Brochure.pdf · Company Profile Principal Business Falco is a preferred supplier because of its ability to provide effective

Miami, USA

Merate, (Lecco) Italy

Merida, Mexico

Xiamen, China

Bengaluru, India

Montevarchi, Italy

R&D Centers

Miami, USA

Merate, (Lecco) Italy

Merida, Mexico

Xiamen, China

Bengaluru, India

Sales Offices

Merida, Mexico

Bengaluru, India,

Xiamen, China

Plants

Los Angeles, USA

Amsterdam, NL

Helsinki, FIN

Main Warehouses

Put our services to the test, contact us for a free consultation today

FALCO

ELECTRONICSVisit for further informationwww.falco.com

UNITED STATES

6800 SW 40 STUnit 111Miami, FL 33155USAPh: +1 (305) 662-9076 ext:3210, 3204E-fax: +1 (928) [email protected]

MEXICO

Calle 23 #311Fracc. ItzincabMerida, YucatanMexico 97392Ph: +52 (999) 930-0270ext: 1509Fax: +52 (999) [email protected]