Thank you for choosing another quality product from Amperes Electronics.
EP1200A is enhanced version with RS485 data output, enabling the unit to be used together with iPX5151 IP client for LAN based PA System. Emergency paging and siren activation shall be available throughout the entire network from main rack.
Extra feature available from EP1200A is the availability of a dry contact, which is closed whenever the unit is activated. This allows connection to volume controller for overriding purpose.
We believe that this product shall be able to meet your demanding requirement with affordable pricing and uncompromised features and quality. Though it is rather simple in the installation works, a brief read through the manual is recommended and we are confident that you are getting a product of excellence.
INSTRUCTION MANUAL
EP1200AEmergency Paging Microphone Panel
VER 2 / 2015
FIRE
Parts Identification
PAGE 2 EP1200A | EMERGENCY PAGING MICROPHONE PANEL
Front View:
Rear View:
1 2 3
5
4
FIRE
6
7
8
9
10 11 12 13 14
1. FIRE INDICATOR
2. EMERGENCY PAGING
This EMERGENCY PAGING button shall active all zones as well as sending emergency paging mode to other related equipment.
3. SIREN SWITCH
4. HANDHELD PAGING MICROPHONEPressing the microphone switch shall have priority over other inputs such as Siren, External Message input as well as normal paging or BGM feeds. For emergency paging which is to override VC and activate ALL CALL, press the emergency paging button (2) before start to talk.
Press the siren button shall activate the siren which is momentary. FIRE indicator shall lit and the MIC switch relay contact (8) shall close. Release of the switch shall deactivate the siren, Pressing it continuously shall activate the unit for about 10 seconds, after which the unit shall reset.
Whenever siren or external activation device is triggered, the FIRE indicator shall flash alongside with siren audio broadcast.
EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 3
Parts Identification
5. 24V INPUTThe unit operates on 24V DC. It is preferred that the unit to be supplied directly from the uninterrupted power source. ie. Back up batteries. Alternatively, connect it to a regulated power supply unit which is in turned has back up supply.
8. RELAY CONTACTTriggering the front panel mic switch shall activate an internal relay. This ports provide a dry contact which can be used to connect E/M overriding signal or to activate ALL CALL at speaker zone selector. The recommended rating for the contact is 3A. In case higher rating is required, please use external relay or contactor to accomodate the high current requirement.
7. REMOTE TRIGGER PORT FOR SIRENExternal sensor device such as heat detector or fire alarm interface device can be connected to this unit to activate the siren. The external device or switch must be voltage free to avoid damage to the unit. Siren activation shall be approximately 10 seconds, after which another contact is required to broadcast the siren.
6. EXTERNAL MESSAGE TRIGGER PORTExternal message player can be linked to it and can be broadcasted to the speakers when this port is triggered. A voltage free contact is recommended to trigger the message playback.
10. HANDHELD MIC LEVEL CONTROLThis is to adjust the front paging mic volume. It is recommended that the setting is made during testing and commissioning works.
11. SIREN OUTPUT LEVEL CONTROLAdjust the siren output to an optimum level during testing and commissiong works.
12. EXTERNAL MESSAGE AUDIO INPUTThe external message playback signal shall be balanced line level. ( e.g: audio from MR1301 )
13. PRE-AMPLIFIER INPUT JACKOutput from pre-amplifier mixer (balanced line level ) is connected to the unit which is normally closed when the unit is not activated. Triggering the panel shall bypass the signal to allow higher priority audio to the PA system.
14. DATA AUDIO OUTPUTAudio output from the decoder is balanced line output level. RJ45 connector consists of audio, data and power with the following pin configuration:-
Pin 1 - Data A Pin 2 - Data B Pin 3 - Relay Trigger SignalPin 4 - NC
Pin 5 - +24V SupplyPin 6 - Audio -ve outputPin 7 - GroundPin 8 - Audio +ve Output
9. RS485 PORTExternal controls or interface devices shall be able to communicate with the unit. It shall be able to communicate with software using RS485 to USB converter which shall be available in near future.
PAGE 4 EP1200A | EMERGENCY PAGING MICROPHONE PANEL
FIRE
PUBLIC ADDRESS POWER AMPLIFIER
SIGNAL -40 dB
SIGNAL -10 dB
POWER
PROTECT
CLIP
PA 2480 amperes
OI
amperesMX2222
POWEROFF SELECT
TUNERCD
CASSOFF
MASTER
MUSIC SOURCESIG IN
BASSMAXMIN
EXT INPUT
MAX MAXMIN
SOURCE
MIN
SIG IN
CHIME MIXER TREBLEMAXMIN
TONE CTRLCH5 CH6CH4
SIG INSIG IN SIG INMAXMIN MAXMIN MIN
CH3CH1 CH2
SIG INSIG INMAXMIN MAXMIN MAXMIN MAX
AUX
SIG IN
INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC)
24V DC
24V DC
24V DC
24V DC
MX2222 PRE-AMP MIXER
EP1200A EMERGENCY PANEL
POWER AMPLIFIERS
ZS SPEAKER ZONE SELECTOR
SPK VOLUME CONTROLLERS
SPEAKERS
audio out - balanced
audio out - balanced
100V line audio output
100V line output24V E/M override24V E/M
override
100V line output
dry contact to activate ALL CALL and 24V E/M override signal
Schematic Diagram
The schematic shown above is typical for most conventional installations. Audio output from mixer shall go through EP1200A prior to amplifier inputs to enable emergengy paging being highest priority.
EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 5
Connecting The Unit
24V DC POWER SUPPLY / BACK UP
SUPPLY
TRIGGERING PORT TO ACTIVATE EXTERNAL PLAYBACK DEVICE
EXTERNAL AUDIO INPUT (BALANCED LINE SIGNAL) FROM MESSAGE
PLAYBACK DEVICE
OUTPUT FROM PRE-AMPLIFIER MIXER (BALANCED LINE LEVEL)
TO POWER AMPLIFIER INPUT (BALANCED LINE)
EXTERNAL SIREN ACTIVATION CONTACT
(VOLTAGE FREE) ie. FIRE CONTROL CENTER / SMOKE
DETECTORS, ETC
DRY CONTACT (NORMALLY OPEN)
CONNECT TO ZONE SELECTORS FOR E/M OVERRIDING SIGNAL
ACTIVATIONRS 485
ER1108 E/M OVERRIDE PANEL
EP1200A EMERGENCY PAGINGPANEL
ZONE 2AMPLIFIER
ZONE 5AMPLIFIER
AMPLIFIER
ZONE 1SPEAKERS
ZONE 8SPEAKERS
B G M 2
A no ther Q ua lity P roduct F rom
O U T P U T 4 O U T P U T 3 O U T P U T 2 O U T P U T 1O U T P U T 5O U T P U T 6O U T P U T 7O U T P U T 8
IN P U T 4 IN P U T 3 IN P U T 2 IN P U T 1IN P U T 5IN P U T 7IN P U T 8 IN P U T 6
PRIORITY INPUT
ZONE 3AMPLIFIER
ZONE 4AMPLIFIER
ZONE 7AMPLIFIER
ZONE 8AMPLIFIER
ZONE 1AMPLIFIER
MxP2188
MR1301
ZONE 6
PAGE 6 EP1200A | EMERGENCY PAGING MICROPHONE PANEL
Connecting The Unit - Matrix System
DC
24V
+
Audio
TriggerAudio
Trigger
In matrix installation, audio output shall be fed to ER1108 together with triggering signal. When EP1200A is active, all incoming audio from MxP2188 shall be bypassed to allow emergency paging.
Usage of DA2208 maybe required if quantity of amplifier is large.
EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 7
I NP
UTO
UTPU
T
P IN 8 -COMP IN 7 -24VP IN 6 -Z6P IN 5 -Z5P IN 4 -Z4P IN 3 -Z3P IN 2 -Z2P IN 1 -Z1
P IN 8 -COMP IN 7 -24VP IN 6 -Z12P IN 5 -Z11P IN 4 -Z10P IN 3 -Z9P IN 2 -Z8P IN 1 -Z7
+DC 24V
CONRLY
TRIGRLY
PRZS
MX2222
EP1200A
PA2480
EX2800
TD6240
ZS5121
PD2800MR1301
Audio
Audio
RS485 & Audio
AMP Output
Audio
Cat5eCat5e
Connecting The Unit - Conventional System
DC 24V+
Trigger
SPEAKER
PAGE 8 EP1200A | EMERGENCY PAGING MICROPHONE PANEL
iPX5151
iPX5151
LAN
iPX5101
iPX5151
P IN 8-COMP IN 7 -24VP IN 6 -Z6P IN 5 -Z5P IN 4 -Z4P IN 3 -Z3P IN 2 -Z2P IN 1 -Z1
P IN 8 -COMP IN 7 -24VP IN 6 -Z12P IN 5 -Z11P IN 4 -Z10P IN 3 -Z9P IN 2 -Z8P IN 1 -Z7
+DC 24V
CONRLY
TRIGRLY
PRZS
EP1200A
PD2800
MX2222
PA2480
ZS5121
TD6240
SPEAKER
Cat5e
Cat5e
Cat5e
Cat5e
Audio Output
RS485 (AB) Data
Cat5e
Audio
AMP Output
Cat5eCat5e
Configuring ALL CALL And E/M Overriding via iPX
EP1200A, which is installed at main rack for a large system using IP as communication interface, shall be able to override remote buildings / system as similar to single rack installation.
EP1200A | EMERGENCY PAGING MICROPHONE PANEL PAGE 9
Configuring ALL CALL And E/M Overriding
EP1200A
P IN 8 -COMP IN 7 -24VP IN 6 -Z6P IN 5 -Z5P IN 4 -Z4P IN 3 -Z3P IN 2 -Z2P IN 1 -Z1
+DC 24V
CONRLY
TRIG PRZS
EP1200A
PS9400 PSU
PM SERIESPAGING MIC
ZS5121 ZONE SELECTOR
Volume Controller
TO SPEAKERS
FR. ZONE SELECTOR 100V LINE OUTPUT
24V E/M Overriding
Signal
Connect this to allow EP1200A to trigger internal
relay of Zone Selector
+ -
The above diagram shows detailed connections for using EP1200A to override volume control and activating ALL CALL at zone selector.
PAGE 10 EP1200A | EMERGENCY PAGING MICROPHONE PANEL
Technical Specifications
Summary Of Features
Built in siren tone generator (constant signal)
Visual FIRE indicator
External voice message activation
Dual mode siren tone activation
Dry contact when paging mic is activated
Priority paging via front panel microphone, bypassing all other audio sources
Output level controls for siren and message / paging microphone
Interface to IP Paging Sytem via iPX5000
Power requirement 24V DCPower consumption 3.5W
MICROPHONEMic sensitivity -72 dB Omni directionalImpedance 600 OhmFrequency response 300 ~ 8 KHz
SIRENSiren frequency Continuous at 8 KHzSiren duration Continuous when activated Siren activation Front test switch / remote contact
Input channel Pre-amplifier output, message recorderOutput level Balanced line out (1.2V)Priority sequence Paging mic - siren - message - pre amp inIndicators Front FIRE with backlight illuminationDimension (WxHxD) 482 x 88 x 180 mmWeight 3.0 kg
Warranty Conditions
Disclaimer
Only Amperes Electronics Service Centres are allowed to make warranty repairs : a list of Amperes Electronics Service Centres may be asked for by the purchaser or send directly to Amperes Electronics Sdn Bhd at 70 Jalan Industri PBP 3, Tmn Perindustrian Pusat Bandar Puchong, 47100, Puchong, Selangor, Malaysia or its authorized master distributor, TNT Links Sdn Bhd / MyPA Systems Sdn Bhd. This warranty is not valid if repairs are performed by unauthorized personnel or service centres.
This warranty covers only repairs and replacement of defective parts ; cost and risks of transportation as well as removal and installation of the product from the main system are for the account of the purchaser. This warranty shall not extend to the replacement of the unit.
This warranty does not cover damages caused by misuse, neglect, accident of the product as well as using the product with power supply voltage other than shown on the product, or any other power supply source / adaptor not recommended by the manufacturer.
This warranty does not cover damages caused by fire, earthquakes, floods, lightning and every cause not directly related to the unit.
This warranty does not include any indemnity in favor of the purchaser or the dealer for the period out of use of the unit; moreover the warranty does not cover any damages which may be caused to people and things when using the product.
This warranty certificate is valid only for the described product, and is not valid if modifications are made on this certificate or on the identification label applied on the product.
This warranty covers all the material and manufacturing defects and is valid for a period of 12 months from the date of purchase or for a longer period in countries where this is stated by a national law. In this case, the extension is valid only in the country where the product is purchased.
Amperes Electronics Sdn Bhd is not obliged to modify previously manufactured products under warranty if the design changes or improvements are made.
Information contained in this manual is subject to change without prior notice and does not represent a commitment on the part of the vendor. AMPERES ELECTRONICS SDN BHD shall not be liable for any loss or damages whatsoever arising from the use of information or any error contained in this manual.
It is recommended that all services and repairs on this product be carried out by AMPERES ELECTRONICS SDN BHD or its authorized service agents.
AMPERES series must only be used for the purpose they were intended by the manufacturer and in conjunction with this operating manual.
AMPERES ELECTRONICS SDN BHD cannot accept any liability whatsoever for any loss or damages caused by service, maintenance or repair by unauthorized personnel, or by use other than that intended by the manufacturer.
Another Quality Product From
Amperes Electronics Sdn BhdCo Reg : 509025-X
www.ampereselectronics.com
This product has been manufactured under strictISO9001 : 2008 management system
Certificate no: 16895 / A / 0001 / UK / En
ISO 9001: 2008Design & Manufacture of Public Address Equipment and Systems
Certi�cate No. 16895 / A / 0001 / UK / En
EP1200A
EMERGENCY PAGING PANEL
Made In Malaysia Updated APRIL 2015