Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module...

40
Installer manual LEK LEK SMO 05 Accessories IHB GB 1146-1 431199

Transcript of Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module...

Page 1: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Installer manual

LEK

LEK

SMO 05Accessories

IHB GB 1146-1431199

Page 2: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

A detailed explanation of the button functions can be found on page 17.

How to scroll through menus and make different settings is described on page 18.

The mode for setting the indoor temperature is reached, when in the start mode in the main menu, by pressing theOK button twice. Read more about the settings on page 19.

To temporarily increase the amount of hot water (if a hot water heater is installed to your SMO 05), first push thedown button once to mark menu 2 (water droplet) and then press the OK button twice. Read more about the settingson page 23.

In event of disturbances in comfort

If a disturbance in comfort of any type occurs there are some measures that can be taken before you need to contactyour installer. See page 29 for instructions.

Page 3: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Table of Contents1 Important information 2

Safety information 2

2 Delivery and handling 5Mounting 5

Supplied components 6

Removing the covers 6

3 The Control Module Design 7Room unit 7

Unit box 7

4 Pipe connections 8General 8

Docking alternatives 8

5 Electrical connections 10General 10

Connections 10

Settings 15

Connecting accessories 15

6 Commissioning and adjusting 16Preparations 16

Commissioning with NIBE air/water heatpump 16

Commissioning without NIBE air/water heatpump 16

Check the reversing valve 16

7 Control - Introduction 17Room unit 17

Menu system 17

8 Control - Menus 19Menu 1 - INDOOR CLIMATE 19

Menu 2 - HOT WATER 23

Menu 3 - INFO 24

Menu 4 MY SYSTEM 25

Menu 5 - SERVICE 27

9 Disturbances in comfort 29Manage alarm 29

Troubleshooting 29

Add. heat only 30

10 Accessories 31

11 Technical data 32Dimensions and setting-out coordinates 32

Technical specifications 34

Electrical circuit diagram 35

Item register 36

1Table of Contents |SMO 05

Page 4: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Safety informationThis manual describes installation and service proceduresfor implementation by specialists.

This appliance is not intended for use by persons (includ-ing children) with reduced physical, sensory or mentalcapabilities, or lack of experience and knowledge, unlessthey have been given supervision or instruction concern-ing use of the appliance by a person responsible for theirsafety.Children should be supervised to ensure that they do notplay with the appliance.Rights to make any design or technical modifications arereserved.©NIBE 2011.

Symbols

NOTE

This symbol indicates danger to machine orperson.

Caution

This symbol indicates important informationabout what you should observe when maintain-ing your installation.

TIP

This symbol indicates tips on how to facilitateusing the product.

Marking

This accessory is CE marked and fulfils IP20 (room unit)and IP21 (unit box).

The CE marking means that NIBE ensures that the productmeets all regulations that are placed on it based on relev-ant EU directives. The CE mark is obligatory for mostproducts sold in the EU, regardless where they are made.

IP20 means that the product can be touched by hand,that objects with a diameter larger than or equivalentto12.5 mm cannot penetrate and cause damage.

Serial number

The serial number can be found on one long side of thecover on the unit box.

Install the cover on the unit box so that the serial numberis visible.

LEK

Caution

Always give the product's serial number whenreporting a fault.

Country specific information

Installer manual

This installer manual must be left with the customer.

Great Britain

This installation is subject to building regulation approval,notify the local Authority of intention to install.

Use only manufacturer’s recommended replacementparts.

Benchmark places responsibilities on both manufacturersand installers. the purpose is to ensure that customersare provided with the correct equipment for their needs,that it is installed, commissioned and serviced in accord-ance with the manufacturers instructions by competentpersons and that it meets the requirements of the appro-priate Building Regulations. The Benchmark Checklist canbe used to demonstrate compliance with Building Regu-lations and should be provided to the customer for futurereference.Installers are required to carry out the installation, com-missioning and servicing work in accordance with theBenchmark Code of practice which is available from theHeating and Hotwater Industry Council who manage andpromote the Scheme. Visit www.centralheating.co.uk forinformation.

SMO 05Chapter 1 | Important information2

1 Important information

Page 5: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Warranty information

Thank you for installing a new NIBE heat pump in yourhome.

NIBE heat pumps are manufactured in Sweden to thevery highest standard so we are pleased to offer ourcustomers a comprehensive guarantee.

The product is guaranteed for 24 months for parts andlabour from the date of installation or 33 months fromthe date of manufacture, whichever is the shorter.

The NIBE guarantee is based on the unit being installedand commissioned by a NIBE accredited installer, servicedevery year and the Benchmark documents completed.Where this condition is not met, any chargeable spareparts or components issued within the applicable guaran-tee period still benefit from a 12 month warranty fromthe date of issue by the manufacturer.

We recommend the installer completes and returns assoon as possible, your guarantee registration card orcompletes the guarantee form on the NIBE websitewww.nibe.co.uk.

3Chapter 1 | Important informationSMO 05

Page 6: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Inspection of the installation

Current regulations require the heating installation to be inspected before it is commissioned. The inspection must becarried out by a suitably qualified person. Fill in the page for information about installation data in the User manual.

DateSignatureNotesDescription✔

Communication, heat pump

Electricity (page 10)

Supply connected 230 V

Outside sensor

Room sensor

Hot water sensor

Room unit

Bridge at installation of room unit

Dipswitch

Miscellaneous

Checking additional heater

Checking the function of the reversing valve

SMO 05Chapter 1 | Important information4

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

......

.

Page 7: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Mounting

NOTE

For wall mounting, use the mounting adaptedfor the base.

Unit box

10

0

235

250

16

0

17

5

Room unit

Mounting

SMO 05 cannot be installed directly against a wall be-cause the connection terminal protrudes from the reverse.

Install SMO 05 either in a spare apparatus box or on theplastic spacer supplied.

If you want to use the room temperature sensor in SMO05 the position of the room unit is important. See page12.

1.

LEK

Open SMO 05 by inserting a screwdriver in one ofthe 4 mm wide gaps in the edge. Press the screw-

driver straight in to open the clips. Repeat for theother three clips.

2.

LEK

Without plastic spacer: Place the rear panel in frontof the apparatus box and screw to the wall.

With plastic spacer: Screw the plastic spacer into thewall. Then screw the the rear panel into the plasticspacer with the two screws supplied.

3.

LEK

Connect the room unit, see page 11.

4.

LEK

Angle the front panel approx. 30 ° and secure thetwo clips on one side. Then close the unit and securethe two clips on the other side.

For dimensions and setting-out coordinates see page 33.

5Chapter 2 | Delivery and handlingSMO 05

2 Delivery and handling

Page 8: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Supplied components

LEK

LEK

Plastic spacerframe

Room unitOutside sensor

LEK

Room sensorTemperaturesensor

Unit box

LE

K

LE

K

Insulation tapeCable tiesAluminium tape

LEK

LEK

Auxiliary relaywith relay socketbase and wiring

Terminal block

Removing the coversUnit box

LEK

Remove the four screws in their respective corners andlift the cover.

The outdoor temperature sensor/Roomtemperature sensor

LEK

SMO 05Chapter 2 | Delivery and handling6

Page 9: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Room unitFront

Rear side

+12V GND B A

Electrical componentsRoom unitAA 25Terminal block, communication connectionJ 3

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

Unit box

LEK

AA5-X4

AA5-S2

AA5-X2 AA5-X9 X1

FC1

AA5-F1AA5

Electrical componentsMiniature circuit-breakerFC1

Terminal block, power supplyX1

Accessory cardAA5

Terminal block, sensors and externalblocking

AA5-X2

Terminal block, communicationAA5-X4

Terminal block, circulation pump, mixingvalve and auxiliary relay

AA5-X9

DIP switchAA5-S2

Fine-wire fuseAA5-F1

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

7Chapter 3 | The Control Module DesignSMO 05

3 The Control Module Design

Page 10: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

GeneralPipe installation must be carried out in accordance withcurrent norms and directives. See manual for NIBEF2015/F2016 for installation of the heat pump.

Symbol key

MeaningSymbol

Shut-off valve

Non-return valve

Shunt / shuttle valve

Safety valve

Trim valve

Tundish

Temperature sensor

Pressure gaugeP

Circulation pump

Particle filter

Temperature sensor installation on pipe

K

Install the temperature sensors with cable ties (secure thefirst cable tie to the pipe on the centre of the sensor andthe second about 5 cm after the sensor) and aluminiumtape. Then insulate with supplied insulation tape.

NOTE

Sensor and communication cables must not beplaced near power cables.

Docking alternativesSMO 05 can be connected in several different ways, someof which are shown below.

Further option information is available at www.nibe.co.ukand in the respective assembly instruction for the access-ory used. See page 31 move the list of the accessoriesthat can be used to SMO 05.

NOTE

This is the outline diagram. Actual installationsmust be planned according to applicable stand-ards.

ExplanationSMO 05AA25Room unitAA4Accessory cardAA5Temperature sensor, outdoorBT1Room sensorBT50Auxiliary relay, immersion heaterK1External electrical additionEB1Circulation pumpGP12Auxiliary relay, additionKA1Heat pumpEB100Temperature sensor, flow pipeBT2Temperature sensor, returnBT3External addition (gas boiler)EM1Circulation pumpGP12

Miscel-laneous

Temperature sensor, hot water chargingBT6Temperature sensor, hot water topBT7External temperature sensor, flow lineBT25Accumulator tank with hot water coilCP1Buffer vessel (UKV)CP5Safety valveFL2Circulation pump, climate systemGP10Circulation pump, charge pumpGP12Particle filterHQ1Tapping valveQM1Shut-off valveQM31Reversing valve, heating/hot waterQN10Non-return valveRM10, RM11Trim valveRN10

Designations according to standards 81346-1 and 81346-2.

SMO 05Chapter 4 | Pipe connections8

4 Pipe connections

Page 11: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

SMO 05 with NIBE F2015/F2016 docked to NIBE VPB 200N and additional heat.

CP5

EM1

EM1

GP12

HQ1RN10 GP12

RM10

QM31EB100

GP10

QM1

QN10FL2

BT3

CP1

BT2

Tillsatsvärme

BT50

AA25

AA25AA25

AA25-AA4

K1AA5

BT1

BT7

BT6

BT25RM11

EB1

KA1

EB1

GP12

In this docking option SMO 05 controls the heat pump,addition (electric/gas), circulation pumps, reversing valveetc. The heat pump works with floating condensingagainst the climate system and prioritises hot watercharging via the reversing valve (QN10).

If the heat pump does not manage the actual heatingdemand, additional heat from the immersion heater/gasboiler is engaged.

In the event of a large heating demand, hot water isheated using the immersion heater in the water heater.

A circulation pump (GP10) and a UKV tank (CP5) is in-stalled as a volume and flow increaser. An external flowtemperature sensor (BT25) is placed in the UKV tank.

Hot water heating is started and stopped by the temper-ature at the hot water sensor (BT6).

Caution

Hot water production can be activated in menu5.2.

9Chapter 4 | Pipe connectionsSMO 05

Page 12: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

General

NOTE

All electrical connections must be carried out byan authorised electrician.

Electrical installation and wiring must be carriedout in accordance with the stipulations in force.

When installing SMO 05, NIBE's air/water heatpump and any addition must be current free.

Caution

The relay outputs on the accessory card (AA5)can have a max load of 2 A (230 V) in total.

Connections

NOTE

To prevent interference, unscreened communic-ation and/or sensor to external connectionscables must not be laid closer than 20 cm tohigh voltage cable when cable routing.

Connecting the supply

Connect the power supply to terminal block X1 as illus-trated.

3

2

1 N230V 50Hz-X1

LPE

Communication with heat pump

NIBE F2015

The heat pump is connected to terminal X4:1 (A), X4:2(B) and X4:3 (GND) on the accessories card (AA5) fromterminal -AA21:J2 i F2015.

Use a cable of at least 0.5 mm² cable area.

GND

B

A

6

5

4

7

3

2

1

8ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

34

SMO 05Chapter 5 | Electrical connections10

5 Electrical connections

Page 13: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

NIBE F2016

The heat pump is connected to terminal X4:1, X4:2 andX4:3 on the accessories card (AA5) from terminal -X5 (3,4, 5, 6) i F2016, as illustrated.

Use a cable of at least 0.5 mm² cable area.

56

42

31

6

5

4

7

3

2

1

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

LEK

Room unit

The room unit is connected to terminal block X4:4 (A),X4:5 (B), X4:7 (GND) and X4:8 (+12V) on the accessorycard (AA5). Fit a bridge between X4:6 and X4:7.

Use a cable of at least 0.5 mm² cable area.

6

5

4

7

3

2

1

8

A

B

GND

+12V

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Outside sensor

Install the outside temperature sensor (BT1) in the shadeon a wall facing north or north-west, so it is unaffectedby the morning sun.

Connect the sensor to terminal block X2:23 and X2:24on the accessory card (AA5). Use a 2 core cable of at least0.5 mm² cable area.

If a conduit is used it must be sealed to prevent condens-ation in the sensor capsule.

24 20212223 171819ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

11Chapter 5 | Electrical connectionsSMO 05

Page 14: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Room sensor

SMO 05 is delivered with a room sensor supplied (BT50).The room temperature sensor has up to three functions:

1. Show current room temperature in the heat pump'sdisplay.

2. Option of changing the room temperature in °C.

3. Makes it possible to change/stabilise the room tem-perature.

Install the sensor in a neutral position where the settemperature is required. A suitable location is on a freeinner wall in a hall approx. 1.5 m above the floor. It isimportant that the sensor is not obstructed from measur-ing the correct room temperature by being located, forexample, in a recess, between shelves, behind a curtain,above or close to a heat source, in a draft from an extern-al door or in direct sunlight. Closed radiator thermostatscan also cause problems.

SMO 05 operates without the sensor, but if one wishesto read off the accommodation's indoor temperature inSMO 05’s display the sensor must be installed. Connectthe room temperature sensor to X2:15 and X2:16 on theaccessory card (AA5).

Use a 2 core cable of at least 0.5 mm² cable area.

24 20212223 1516171819

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Caution

Changes of temperature in accommodation taketime. For example, short time periods in combin-ation with underfloor heating will not give anoticeable difference in room temperature.

Temperature sensor, hot water charging

The temperature sensor, hot water charging (BT6) isplaced in the submerged tube on the water heater.

Connect the sensor to terminal block X2:21 and X2:22on the accessory card (AA5). Use a 2 core cable of at least0.5 mm² cable area.

Hot water charging can be activated in menu 5.2.

24 20212223 171819

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Temperature sensor, hot water top

A temperature sensor for hot water top (BT7) can beconnected to SMO 05 for showing the water temperatureat the top of the tank (placed in submerged tube).

Connect the sensor to terminal block X2:19 and X2:20on the accessory card (AA5). Use a 2 core cable of at least0.5 mm² cable area.

24 20212223 171819

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Temperature sensor, external flow line

The temperature sensor, external flow line (BT25) is con-nected terminal block X2:17 and X2:18 on the accessorycard (AA5). Use a 2 core cable of at least 0.5 mm² cablearea.

24 20212223 16171819

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

SMO 05Chapter 5 | Electrical connections12

Page 15: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Switch for external blocking of additionand/or compressor

In those cases external blocking of addition (B) and/orcompressor (A) is wanted, this can be connected to ter-minal block X2:11 and X2:12 (addition) respectively ter-minal block X2:13 and X2:14 (compressor) on the access-ory card (AA5).

The addition and/or the compressor are disconnected byconnecting a potential free switch function to actual ter-minal block. Use a 2 core cable of at least 0.5 mm² cablearea.

External blocking of addition and compressor can becombined.

A closed contact results in the electrical output beingdisconnected.

1516 111121314

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Contact for external adjustment.

An external contact function can be connected to SMO05 to change the supply temperature and the roomtemperature.

When the contact is closed, the offset heating curve ischanged by the number of steps selected in the menu1.9.2 "external adjustment". If a room temperaturesensor is installed and activated the desired room temper-ature (°C) is set in the menu.

The contact must be potential free and connected toterminal block X2:9 and X2:10 on the accessory card(AA5).

1516 1011121314 89

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Connection of the circulation pump (GP10)

The circulation pump is connected to terminal block X9:7(N), X9:8 (230 V) and X1:3 (PE) on the accessory card(AA5).

NOTE

During the emergency mode function, the circu-lation pump requires external voltage.

1

2

3

4

5

6

7

8

9

L

N

PE

3

2

1ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Connection of the reversing valve motor(QN10)

The reversing valve is connected to terminal block X9:5(N), X9:6 (230 V during hot water production, 0 V duringheating) and X10:2 (230 V) on the accessory card (AA5).

1

2

3

4

5

6

7

8

9

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Connection of additional heat (EM1/EB1)

The additional relay (QA1) is connected to the accessoriescard (AA5) as illustrated from QA1:A1 to AA5-X9:2 (230V) and from QA1:A2 to AA5-X9:1 (N).

1

2

3

A1 A2ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

13Chapter 5 | Electrical connectionsSMO 05

Page 16: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Connection of add. heat for hot water

The additional relay (QA1) is connected to the accessoriescard (AA5) as illustrated from QA1:A1 to AA5-X9:4 (230V) and from QA1:A2 to AA5-X9:3 (N).

1

2

3

4A1 A2

L

N

L

N

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Connection of immersion heater for hot wa-ter (with auxiliary relay)

Install the auxiliary relay on the relay base as illustratedbelow.

LEK LEK

After step 2 has been completed, install the entire relayon the rail in the unit box by the miniature circuit-breaker(FC1) as illustrated and connect to the accessory card(AA5) as illustrated from K1:A1 to AA5:X9:4 and fromK1:A2 to AA5:X9:3.

Supply (L, for the immersion heater) is connected to K1:11and incoming supply to the immersion heater is connec-ted to K1:14. Neutral (N) is connected to terminal blockX2:1 and ground (PE) to X2:2 as illustrated.

3

2

1

2

1

ON1

23

45

67

8

2

1

1

L

N

PE

2

3

4

5

6

A1 A2

11 14

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

SMO 05Chapter 5 | Electrical connections14

Page 17: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

SettingsDIP switch

The DIP switch on the accessory card must be set as fol-lows.

ON1

23

45

67

8

ON 1

23

45

67

8

-X9

-X2

24 20212223 1516171819 1011121314 56789 1

1

N

L

PE

PE

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9234

-X8

-X4

-X10

-X1

Connecting accessoriesInstructions for connecting other accessories are in theinstallation instructions provided. See page 31 for the listof the accessories that can be used with SMO 05.

15Chapter 5 | Electrical connectionsSMO 05

Page 18: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

PreparationsNIBE F2015/F2016 must have a control card with dis-play with version 2.10 or later. The control card ver-sion is displayed in the heat pump's display upon start-up.

SMO 05 must be ready-connected.

Read how to use the room unit on page 17.

Commissioning with NIBEair/water heat pumpNIBE F2015

Follow the instructions in the heat pump's Installationand Maintenance under section "Commissioning andadjustment" – "Start-up and inspection".

NIBE F2016Follow the instructions in the heat pump's Installationmanual under section "Commissioning and adjust-ment" – "Start-up and inspection".

SMO 051. Power the heat pump.

2. Power SMO 05.

3. Make settings that affect actual docking.

4. Set curve slope and offset heating curve in menu1.9.1. See page 20.

5. Set the correct flow during hot water productionaccording to the heat pump's Installation manual.Check the difference between BT2 and BT3 in menu3.

Commissioning without NIBEair/water heat pump1. Go to menu 4.2 op. mode.

2. Mark ”add. heat only” using the up and down but-tons and then press the OK button.

3. Return to the main menus by pressing the Back but-ton.

Caution

When commissioning without NIBE air/waterheat pump an alarm communication error mayappear in the room unit.

Reset the alarm when setting ”add. heat only“in menu 4.2.

Check the reversing valve1. Change menu 4.2 to manual operating mode with

heating permitted.

2. Change degree minutes to 0 in menu 4.9.3 "currentvalue".

3. Create hot water demand.

4. Check that the reversing valve is open for hot watercharging.

5. Change degree minutes in menu 4.9.3 "currentvalue" to a lower value than shown in menu 4.9.3"start addition" (factory setting: -400).

6. Check that the reversing valve is set to open forheating operation.

7. Change menu 4.2 to desired operating mode.

8. Reset menu 4.9.3 "current value" to 0.

SMO 05Chapter 6 | Commissioning and adjusting16

6 Commissioning and adjusting

Page 19: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Room unit

DisplayInstructions, settings and operational informationare shown on the display.

A

Stand-by buttonThe room unit can be switched to stand-by modeusing the stand-by button. Heat pump operationis not affected by pressing the button.

B

Back buttonThe back button is used to:

go back to the previous menu.change a setting that has not been con-firmed.

C

OK buttonThe OK button is used to:

confirm selections of sub menus/options/setvalues.

D

Up and down buttonsWith the up and down buttons you can:

scroll in menus and between options.increase and decrease the values.change page in multiple page instructions

E

Menu systemWhen the room unit starts up you come to the informa-tion menu. Basic information about your system statusis shown here.

Press any button to go to the main menu.

The information menu shows:

on starting

when the back button in the main menu is pressed

after 15 minutes of inactivity.

In the event of an alarm a symbol is shown in the displaytogether with the alarm's number. See page 29 for in-structions.

In the other menus the alarm symbol is shown in thebottom right hand corner.

17Chapter 7 | Control - IntroductionSMO 05

7 Control - Introduction

Page 20: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 1 - INDOOR CLIMATE

Setting the indoor climate. See page 19.

Menu 2 - HOT WATER

Setting the hot water production. See page 23.

This menu only appears if a water heater is activated inthe menu system.

Menu 3 - INFO

Display of temperature and other operating information.See page 24.

Menu 4 - MY INSTALLATION

Setting operating mode etc. See page 25.

Menu 5 - SERVICE

Advanced settings. These settings are not available to theend user. The menu is visible by pressing the back buttonfor 7 seconds. See page 27.

Operation

To move the cursor, press the up or down button. Themarked position is brighter and/or has a turned up tab.

Selecting menu

To advance in the menu system select a sub-menu bymarking it by using the up and down buttons and thenpressing the OK button.

Selecting options

In an options menu the current selected option isindicated by a green tick.

To select another option:

Mark the applicable option using the up ordown button. One of the options is pre-selec-ted (white).

1.

Press the OK button to confirm the selectedoption. The selected option has a green tick.

2.

Setting a value

To set a value:

Mark the value you want to set using theup or down button.

1.

Press the OK button. The background ofthe value becomes green, which meansthat you have accessed the setting mode.

2.

Press the up button to increase the valueor the down button to reduce the value.

3.

Press the OK button to confirm the valueyou have set. To undo and return to theoriginal value, press the back button.

4.

SMO 05Chapter 7 | Control - Introduction18

Page 21: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 1 - INDOOR CLIMATE Overview

1.1 - temperature1 - INDOOR CLIMATE

1.9.1 - heating curve1.9 - advanced

1.9.2 - external adjustment

1.9.3 - min. flow line temp.

1.9.4 - room sensor settings

Sub-menus

For the menu INDOOR CLIMATE there are several sub-menus. Status information for the relevant menu can befound on the display to the right of the menus.

temperature Setting the temperature for the climatesystem. The status information shows the set values forthe climate system.

advanced Setting of heat curve, adjusting with externalcontact, minimum value for supply temperature and roomsensor.

Menu 1.1 - temperature

Set the temperature (with room sensors installedand activated):

Setting range: 5 - 30 °C

Default value: 20

The value in the display appears as a temperature in °Cif the heating system is controlled by a room sensor.

To change the room temperature, use the up and downbuttons to set the desired temperature in the display.Confirm the new setting by pressing the OK button. Thenew temperature is shown on the right-hand side of thesymbol in the display.

Setting the temperature (without room sensorsactivated):

Setting range: -10 to +10

Default value: 0

The display shows the set values for heating (curve offset).To increase or reduce the indoor temperature, increaseor reduce the value on the display.

Use the up and down buttons to set a new value. Confirmthe new setting by pressing the OK button.

The number of steps the value has to be changed toachieve a degree change of the indoor temperature de-pends on the heating unit. One step for under floorheating whilst radiators may require three.

Setting the desired value. The new value is shown on theright-hand side of the symbol in the display.

Caution

An increase in the room temperature can beslowed by the thermostats for the radiators orunder floor heating. Therefore, open the thermo-stat valves fully, except in those rooms where acooler temperature is required, e.g. bedrooms.

TIP

Wait 24 hours before making a new setting, sothat the room temperature has time to stabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope in menu1.9.1 by one increment.

If it is cold outdoors and the room temperatureis too high, lower the curve slope menu 1.9.1by one increment.

If it is warm outdoors and the room temperatureis too low, increase the value in menu 1.1 byone increment.

If it is warm outdoors and the room temperatureis too high, reduce the value in menu 1.1 by oneincrement.

Menu 1.9 - advanced

Menu advanced has orange text and is intended for theadvanced user. This menu has several sub-menus.

heating curve Setting the heating curve slope.

external adjustment Setting the heat curve offset whenthe external contact is connected.

min. flow line temp. Setting minimum permitted flowline temperature.

room sensor settings Settings regarding the room sensor.

19Chapter 8 | Control - MenusSMO 05

8 Control - Menus

Page 22: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 1.9.1 - heating curve

heating curve

Setting range: 1 - 15

Default value: 13

offset

Setting range: -10 to +10

Default value: 0

In the menu heating curve the so-called heating curvefor your house can be set. The task of the heating curveis to give an even indoor temperature, regardless of theoutdoor temperature, and thereby energy efficient oper-ation. It is from this heating curve that the heat pump’scontrol computer determines the temperature of thewater to the heating system, flow line temperature, andtherefore the indoor temperature. You can select heatingcurve and read off how the flow line temperature changesat different outdoor temperatures here.

Curve coefficient

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Brantare kurvlutning

The slope of the heating curve indicates how many de-grees the supply temperature is to be increased/reducedwhen the outdoor temperature drops/increases. Asteeper slope means a higher supply temperature at acertain outdoor temperature.

The optimum slope depends on the climate conditionsin your location, if the house has radiators or under floorheating and how well insulated the house is.

The heating curve is set when the heating installation isinstalled, but may need adjusting later. Thereafter theheating curve should not need further adjustment.

Caution

In the event of making fine adjustments for theindoor temperature, the heat curve must beoffset up or down instead, this is done in menu1.1 temperature .

Curve offset

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Förskjuten värmekurva

An offset of the heating curve means that the supplytemperature changes as much for all the outdoor temper-atures, e.g. that a curve offset of +2 steps increases thesupply temperature by 5 °C at all outdoor temperatures.

Setting automatic heating controls with diagram

The diagrams are based on the dimensioned outdoortemperature in the area and the dimensioned supplytemperature of the climate system. When these two val-ues "meet", the heating control's curve slope can beread.

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

- 40

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70

FR

AM

LED

NIN

GS

TE

MP

ER

AT

UR

- 20 - 30

FÖRSKJUTNINGVÄRMEKURVA (-2)

VÄRMEKURVA

SMO 05Chapter 8 | Control - Menus20

Page 23: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

30

40

50

60

70

FR

AM

LED

NIN

GS

TE

MP

ER

AT

UR

- 40

UTETEMPERATUR

- 10010 - 20 - 30

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

VÄRMEKURVA

- 5

+ 5

FÖRSKJUTNINGVÄRMEKURVA (0)

1514 13 12 11 108

7

6

5

4

3

2

1

- 40

UTETEMPERATUR

- 10010

- 5

+ 5

30

40

50

60

70

FR

AM

LED

NIN

GS

TE

MP

ER

AT

UR

- 20 - 30

FÖRSKJUTNINGVÄRMEKURVA (+2)

9

VÄRMEKURVA

Flow line temperature– maximum and minimumvalues

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Maximivärde

Minimivärde

Because the flow line temperature cannot be calculatedhigher than the set maximum value or lower than the setminimum value the heating curve flattens out at thesetemperatures.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max temperature for your floor withyour installer/floor supplier.

Use the up and down buttons to set a new value. Confirmthe new setting by pressing the OK button.

To select another heat curve (slope):1. Press the OK button to access the setting mode

2. Select a new heating curve. The heating curves arenumbered from 1 to 15, the greater the number, thesteeper the slope and the greater the supply temper-ature.

3. Press the OK button to exit the setting.

TIP

Wait 24 hours before making a new setting, sothat the room temperature has time to stabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope by one incre-ment.

If it is cold outdoors and the room temperatureis too high, lower the curve slope by one incre-ment.

If it is warm outdoors and the room temperatureis too low, increase the curve offset by one incre-ment.

If it is warm outdoors and the room temperatureis too high, lower the curve offset by one incre-ment.

Menu 1.9.2 - external adjustment

climate system (with room temperature sensorsinstalled and activated)

Setting range: 5 - 30 °C

Default value: 20

climate system (without room temperaturesensors activated)

Setting range: -10 to +10

Default value: 0

Connecting an external contact, for example, a roomthermostat or a timer allows you to temporarily or period-ically raise or lower the room temperature. When thecontact is on, the heat curve offset is changed by thenumber of steps selected in the menu. If a room sensoris installed and activated the desired room temperature(°C) is set.

21Chapter 8 | Control - MenusSMO 05

Page 24: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 1.9.3 - min. flow line temp.

climate system

Setting range: 15 – 50 °C

Default value: 15 °C

Set the minimum temperature on the supply temperatureto the climate system. This means that SMO 05 nevercalculates a temperature lower than that set here.

TIP

The value can be increased if you have, for ex-ample, a cellar that you always want to heat,even in summer.

You may also need to increase the value in "stopheating" menu 4.9.2 "auto mode setting".

Menu 1.9.4 - room sensor settings

factor system

Setting range: 0.1 - 6.0

Default value: 2.0

Room sensors to control the room temperature can beactivated here.

Here you can set a factor that determines how much thesupply temperature is to be affected by the differencebetween the desired room temperature and the actualroom temperature. A higher value gives a greater changeof the heating curve's set offset.

SMO 05Chapter 8 | Control - Menus22

Page 25: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 2 - HOT WATER Overview

2.1 - temporary lux2 - HOT WATER

2.2 - comfort mode

2.9.1 - periodic increases2.9 - advanced

Sub-menus

For the menu HOT WATER there are several sub-menus.Status information for the relevant menu can be foundon the display to the right of the menus.

temporary lux Activation of temporary increase in thehot water temperature. Status information displays “off"or what length of time of the temporary temperature in-crease remains.

comfort mode Setting hot water comfort. The statusinformation displays what mode is selected, "economy","normal" or "luxury".

advanced Setting periodic increase in the hot watertemperature.

Menu 2.1 - temporary lux

Setting range: 1, 3, 6 and 12 hours, and mode"off"

Default value: "off"

When hot water requirement has temporarily increasedthis menu can be used to select an increase in the hotwater temperature to lux mode for a selectable time.

Caution

If comfort mode "luxury" is selected in menu2.2 no further increase can be carried out.

The function is activated immediately when a time periodis selected and confirmed using the OK button. The timeto the right displays the remaining time at the selectedsetting.

When the time has run out SMO 05 returns to the modeset in menu 2.2.

Select “off" to switch off temporary lux .

Menu 2.2 - comfort mode

Setting range: economy, normal, luxury

Default value: normal

The difference between the selectable modes is thetemperature of the hot tap water. Higher temperaturemeans that the hot water lasts longer.

economy: This mode gives less hot water than the other,but is more economical. This mode can be used in smallerhouseholds with a small hot water requirement.

normal: Normal mode gives a larger amount of hot waterand is suitable for most households.

luxury: Lux mode gives the greatest possible amount ofhot water. In this mode the immersion heater may bepartially used to heat hot water, which may increase op-erating costs.

Menu 2.9 - advanced

Menu advanced has orange text and is intended for theadvanced user. This menu has several sub-menus.

Menu 2.9.1 - periodic increases

period

Setting range: 1 - 90 days

Default value: 14 days

To prevent bacterial growth in the water heater, thecompressor and the immersion heater can increase hotwater temperature at regular intervals.

The length of time between increases can be selectedhere. The time can be set between 1 and 90 days. Factorysetting is 14 days. Untick "activated" to switch off thefunction.

23Chapter 8 | Control - MenusSMO 05

Page 26: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 3 - INFOMenu 3.1 - service info

Information about the heat pump’s actual operatingstatus (e.g. current temperatures etc.) can be obtainedhere. No changes can be made.

The information is on several pages. Push the up anddown buttons to scroll between the pages.

SMO 05Chapter 8 | Control - Menus24

Page 27: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 4 MY SYSTEM Overview

4.2 - op. mode4 - MY SYSTEM

4.8 - alarm reset*

4.9.1 - op. prioritisation4.9 - advanced

4.9.2 - auto mode setting

4.9.3 - degree minute setting

4.9.4 - factory setting user

* Only shown in the event of an alarm.

Sub-menus

For the menu HEAT PUMP there are several sub-menus.Status information for the relevant menu can be foundon the display to the right of the menus.

op. mode Activation of manual or automatic operatingmode. The status information shows the selected operat-ing mode.

alarm reset Alarms can be reset here.

advanced Setting heat pump work mode.

Menu 4.2 - op. mode

op. mode

Setting range: auto, manual, add. heat only

Default value: auto

functions

Setting range: compressor, addition, heating

The heat pump operating mode is usually set to "auto".It is also possible to set the heat pump to "add. heatonly", but only when an addition is used, or "manual"and select yourself what functions are to be permitted.

Change the operating mode by marking the desired modeand pressing the OK button. When an operating modeis selected, selectable options are displayed to the right.To select selectable functions that are permitted or not,mark the function using the up and down buttons andpress the OK button.

Operating mode auto

In this operating mode you cannot select which functionsare to be permitted because it is handled automaticallyby the heat pump.

Operating mode manual

In this operating mode you can select what functions arepermitted. You cannot deselect "compressor" in manualmode.

Operating mode add. heat only

Caution

If you choose mode "add. heat only" the com-pressor is deselected and there is a higher oper-ating cost.

In this operating mode the compressor is not active andonly additional heating is used.

Functions

"compressor" is that which produces heating and hotwater for the accommodation. If "compressor" isdeselected, a symbol in the main menu on the heat pumpsymbol is displayed. You cannot deselect "compressor"in manual mode.

"addition" is what helps the compressor to heat theaccommodation and/or the hot water when it cannotmanage the whole requirement alone.

"heating" means that you get heat in the accommoda-tion. You can deselect the function when you do notwish to have heating running.

Caution

If you deselect "addition" it may mean that in-sufficient hot water and/or heating in the accom-modation is achieved.

Menu 4.8 - alarm reset

This menu is only available if an alarm has occurred.

Here you can reset any alarms that have occurred in SMO05 or heat pump.

Caution

In the event of an alarm reset, the control systemrestarts in the heat pump.

Menu 4.9 - advanced

Menu advanced has orange text and is intended for theadvanced user. This menu has several sub-menus.

25Chapter 8 | Control - MenusSMO 05

Page 28: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 4.9.1 - op. prioritisation

op. prioritisation hot water / heating

Setting range: 0 to 180

Default value: 20

Choose here how long the heat pump should work witheach requirement if there are two requirements at thesame time. If there is only one requirement the heat pumponly works with that requirement.

If 0 minutes is selected it means that requirement is notprioritised, but will only be activated when there is noother requirement.

Menu 4.9.2 - auto mode setting

stop heating

Setting range: 0 – 40 °C

Default value: 20

stop additional heat

Setting range: -20 – 40 °C

Default value: 15

filtering time

Setting range: 0 – 48 h

Default value: 24 h

When operating mode is set to "auto“ the heat pumpselects when start and stop of additional heat and heatproduction is permitted, dependent on the average out-door temperature.

Select the average outdoor temperatures in this menu.

You can also set the time over which (filtering time) theaverage temperature is calculated. If you select 0, thepresent outdoor temperature is used.

Caution

It cannot be set "stop additional heat" higherthan "stop heating".

Menu 4.9.3 - degree minute setting

current value

Setting range: -3000 – 100

start compressor

Setting range: -1000 – -30

Default value: -60

start addition

Setting range: -2000 – -30

Default value: -400

stop additional heat

Setting range: -2000 – -30

Default value: -230

Degree minutes are a measurement of the current heatingrequirement in the house and determine when the com-pressor respectively additional heat will start/stop.

Caution

Higher value on "start compressor" gives morecompressor starts, which increases wear in thecompressor. Too low value can give uneven in-door temperatures.

Menu 4.9.4 - factory setting user

All settings that are available to the user (including ad-vanced menus) can be reset to default values here.

Caution

After factory setting, personal settings such asheating curves must be reset.

SMO 05Chapter 8 | Control - Menus26

Page 29: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 5 - SERVICE Overview

5.1.1 - hot water settings5.1 - operating settings5 - SERVICE

5.1.2 - max flow line temperature

5.1.4 - alarm actions

5.2 - system settings

5.5 - factory setting service

Hold the back button in for 7 seconds to access the Ser-vice menu.

Sub-menus

Menu SERVICE has orange text and is intended for theadvanced user. This menu has several sub-menus. Statusinformation for the relevant menu can be found on thedisplay to the right of the menus.

operating settings Operating settings for the heat pump.

system settings System settings for the heat pump, ac-tivating accessories etc.

factory setting service Total reset of all settings (includingsettings available to the user ) to default values.

NOTE

Incorrect settings in the service menus candamage the heat pump.

Menu 5.1 - operating settings

Operating settings can be made for the heat pump in thesub menus.

Menu 5.1.1 - hot water settings

economy

Setting range start temp. economy: 5– 70 °C

Factory setting start temp. economy: 41 °C

Setting range stop temp. economy: 5– 70 °C

Factory setting stop temp. economy: 45 °C

normal

Setting range start temp. normal: 5– 70 °C

Factory setting start temp. normal: 43 °C

Setting range stop temp. normal: 5– 70 °C

Factory setting stop temp. normal: 47 °C

luxury

Setting range start temp. lux: 5– 70 °C

Factory setting start temp. lux: 45 °C

Setting range stop temp. lux: 5– 70 °C

Factory setting stop temp. lux: 49 °C

stop temp. per. increase

Setting range: 55 – 70 °C

Default values: 55 °C

Recommended normal setting

StopStartWater heaterHeat pump

47 °C43 °CVPAF2026

46 °C42 °CVPBF2026

52 °C48 °CVPAF2300

50 °C46 °CVPBF2300

Here you set the start and stop temperature of the hotwater for the different comfort options in menu 2.2 aswell as the stop temperature for periodic increase in menu2.9.1.

The above values are the default settings when there aredifferent heater designs, sensor locations and otherfactors that are unique to each installation. These settingsmay therefore need adjusting.

27Chapter 8 | Control - MenusSMO 05

Page 30: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Menu 5.1.2 - max flow line temperature

climate system

Setting range: 10 – 80 °C

Default value: 55 °C

Set the maximum supply temperature for the climatesystem here. If the installation has more than one climatesystem, individual maximum supply temperatures can beset for each system.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max floor temperature with your floorsupplier.

Menu 5.1.4 - alarm actions

Select how you want the SMO 05 to alert you that thereis an alarm in the display here.

The different alternatives are that the system stops pro-ducing hot water (default setting) and/or reduces theroom temperature.

Caution

If no alarm action is selected, it can result inhigher energy consumption in the event of analarm.

Menu 5.2 - system settings

If the water heater is docked to the installation, hot watercharging must be activated here.

Menu 5.5 - factory setting service

All settings can be reset (including settings available tothe user) to default values here.

NOTE

When resetting, the start guide is displayed thenext time the heat pump is restarted.

SMO 05Chapter 8 | Control - Menus28

Page 31: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

In most cases, the heat pump notes malfunctions andindicates this with alarms and shows instructions in theroom unit display. See page 29 for information aboutmanaging alarms. If the malfunction does not appear inthe display, or if the display is not lit, the followingtroubleshooting guide can be used.

Manage alarm

In the event of an alarm, a malfunction has occurred,which is indicated by an alarm clock in the room unit.

Alarm

In the event of an alarm a malfunction has occurred thatSMO 05 cannot rectify itself. The display shows what typeof alarm it is.

Alarm list

Alarm AA25:## (where ## is a number) means that thealarm has occurred in SMO 05.

Alarm EB100:## (where ## is a number) means that thealarm has occurred in the heat pump (see the heat pumpmanual).

Sensor alarm BT1/BT6/BT25:

The sensor is probably broken or has lost contact withthe accessory card. The alarm resets automatically aftercorrect connection.

Check the connection of the sensor to the accessorycard and that the cable has not got a short-circuit.

If the above is not the source of the fault, replace thesensor.

Communication alarm heat pump

The heat pump has lost contact with the accessory card.

Check the connection between the heat pump andthe accessory card and that the cable has not got ashort-circuit.

Communication alarm accessory card

The room unit has lost contact with the accessory card.

Check the connection between the room unit andthe accessory card and that the cable has not got ashort-circuit.

Resetting the alarm

Alarm reset can be carried out in two ways.

1. Select "yes" in menu 4.8.

2. Restart of SMO 05 (on/off of voltage to SMO 05).

In the event of an alarm reset, the control system restartsin the heat pump and any alarms in SMO 05 are reset.

NOTE

Contact your installer if the alarm recurs.

TroubleshootingIf the malfunction is not shown in the display the follow-ing tips can be used or consult the heat pump manual.

Basic actions

Start by checking the following possible fault sources:

That the heat pump is running or that the supply cableto SMO 05 is connected.

Group and main fuses of the accommodation.

The property's earth circuit breaker.

The heat pump's miniature circuit breaker (FC1).

Low hot water temperature or a lack of hotwater

This part of the fault-tracing chapter only applies if theheat pump is docked to the hot water heater.

Heat pump in incorrect operating mode.

If mode "manual" is selected, select "addition".

Large hot water consumption.

Wait until the hot water has heated up. Tempor-arily increased hot water capacity (temporary lux)can be activated in menu 2.1.

Too low hot water setting.

Enter menu 2.2 and select a higher comfort mode.

Too low or no operating prioritisation of hot water.

Enter menu 4.9.1 and increase the time for whenhot water is to be prioritised.

Low room temperatureClosed thermostats in several rooms.

Set the thermostats to max in as many rooms aspossible. Adjust the room temperature via menu1.1 instead of choking the thermostats.

Installation in incorrect operating mode.

29Chapter 9 | Disturbances in comfortSMO 05

9 Disturbances in comfort

Page 32: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Enter menu 4.2. If mode "auto" is selected, selecta higher value on "stop heating“ in menu 4.9.2.

If mode "manual" is selected, select "heating".If this is not enough, select "addition".

Too low set value on the automatic heating control.

Enter menu 1.1 (temperature) and adjust the heatcurve offset of the heat curve. If the room temper-ature is only low in cold weather the curve slopein the menu 1.9.1 (heating curve) needs to beadjusted up.

Too low or no operating prioritisation of heat.

Enter menu 4.9.1 and increase the time for whenheating is to be prioritised.

External switch for changing the room heating activ-ated.

Check any external switches.

High room temperatureToo high set value on the automatic heating control.

Enter menu 1.1 (temperature) and adjust the heatcurve offset downwards. If the room temperatureis only high in cold weather the curve slope inmenu 1.9.1 (heating curve) needs to be adjusteddown.

External switch for changing the room heating activ-ated.

Check any external switches.

Add. heat onlyIf you are unsuccessful in rectifying the fault and are un-able to heat the house, you can, whilst waiting for assist-ance, continue running SMO 05 in ”add. heat only”. Thismeans that SMO 05 only uses the additional heating toheat the house and domestic hot water.

Set SMO 05 to additional heat mode1. Go to menu 4.2 op. mode.

2. Mark ”add. heat only” using the control buttons andthen press the OK button.

3. Return to the main menus by pressing the Back but-ton.

SMO 05Chapter 9 | Disturbances in comfort30

Page 33: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Auxiliary relay HR 10

Part no. 089 423

External electrical addition ELK

ELK 5

Immersion heater

5 kW, 1 x 230 V

Part no. 069 025

ELK 8

Immersion heater

8 kW, 1 x 230 V

Part no. 069 026

Heat pump

F2015

6 kW Part no. 064 044

8 kW Part no. 064 014

11 kW Part no. 064 015

F2016

6 kW Part no. 064 081

8 kW Part no. 064 082

11 kW Part no. 064 083

Hot water control

VST 05

Three way valve, Cu-pipe Ø22

Max heat pump size 8 kW

Part no. 089 882

VST 11

Shuttle valve, Cu-pipe Ø28

Max heat pump size 10 kW

Part no. 089 152

VST 20

Reversing valve, Cu-pipe Ø35

Max heat pump size 20 kW

Part no. 089 388

Hot water heater

VPB 200N

Stainless steel Part no 087 730

31Chapter 10 | AccessoriesSMO 05

10 Accessories

Page 34: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Dimensions and setting-out coordinatesUnit box

10

0

235

250

16

0

17

5

SMO 05Chapter 11 | Technical data32

11 Technical data

Page 35: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Room unit

85 14 49

85

35

86

35

86

33Chapter 11 | Technical dataSMO 05

Page 36: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Technical specifications

Room unit

85(mm)Width

85(mm)Height

14(mm)Depth

49(mm)Depth (with spacer frame)

IP20Enclosure class

Unit box

250(mm)Width

175(mm)Height

100(mm)Depth

IP21Enclosure class

SMO 05

1Max number air/water heat pumps

5Max number of sensors

1Max number of charge pumps

1Max number of circulation pumps/climate systems

230 V 50 HzSupply voltage

2(A)Max. current

2Max number of additional steps

067 100Part No.

SMO 05Chapter 11 | Technical data34

Page 37: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Electrical circuit diagram

35Chapter 11 | Technical dataSMO 05

Page 38: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

Item registerAAccessories, 31

CCommissioning and adjusting, 16

Commissioning with NIBE air/water heat pump, 16Commissioning without NIBE air/water heat pump, 16Preparations, 16

Commissioning with NIBE air/water heat pump, 16Commissioning without NIBE air/water heat pump, 16Communication with heat pump, 10Connecting accessories, 15Connecting the supply, 10Connection of add. heat for hot water, 14Connection of additional heat, 13, 14Connection of the circulation pump, 13Connection of the reversing valve motor, 13Connections, 10Contact for external adjustment., 13Control, 17, 19

Control - Introduction, 17Control - Menus, 19

Control - Introduction, 17Menu system, 17Room unit, 17

Control - Menus, 19Menu 1 - INDOOR CLIMATE, 19Menu 2 - HOT WATER, 23Menu 3 - INFO, 24Menu 4 MY SYSTEM, 25Menu 5 - SERVICE, 27

DDelivery and handling, 5

Mounting, 5Removing the covers, 6Supplied components, 6

DIP switch, 15Disturbances in comfort, 29

Manage alarm, 29Only additional heat, 30Troubleshooting, 29

Docking alternatives, 8

EElectrical cabinets, 7Electrical connections, 10

Communication with heat pump, 10Connecting accessories, 15Connecting the supply, 10Connection of add. heat for hot water, 14Connection of additional heat, 13, 14Connection of the circulation pump, 13Connection of the reversing valve motor, 13Connections, 10Contact for external adjustment., 13Contact for external blocking of addition and/or compressor, 13General, 10Outdoor sensor, 11Room sensor, 12Room unit, 11Settings, 15Temperature sensor, external flow line, 12Temperature sensor, hot water charging, 12

Temperature sensor, hot water top, 12

IImportant information, 2

Safety information, 2Inspection of the installation, 4

MManage alarm, 29Marking, 2Menu 1 - INDOOR CLIMATE, 19Menu 2 - HOT WATER, 23Menu 3 - INFO, 24Menu 4 MY SYSTEM, 25Menu 5 - SERVICE, 27Menu system, 17Mounting, 5

OOnly additional heat, 30Outdoor sensor, 11

PPipe connections, 8

Docking alternatives, 8General, 8Symbol key, 8

Preparations, 16

RRemoving the covers, 6Room sensor, 12Room unit, 11, 17

SSafety information, 2

Inspection of the installation, 4Marking, 2Serial number, 2Symbols, 2Warranty information, 3

Serial number, 2Settings, 15

DIP switch, 15Supplied components, 6Switch for external blocking of addition and/or compressor, 13Symbol key, 8Symbols, 2

TTechnical data, 32

Technical Data, 34Technical Data, 34Temperature sensor, external flow line, 12Temperature sensor, hot water charging, 12Temperature sensor, hot water top, 12The Control Module Design, 7

Component locations, 7List of components, 7

The heat pump designComponent list electrical cabinets, 7Component location electrical cabinets, 7

Troubleshooting, 29

WWarranty information, 3

SMO 05Chapter 12 | Item register36

12 Item register

Page 39: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General
Page 40: Installer manual - NIBE · standard IEC 81346-1 and 81346-2. SMO 05 Chapter 3 | The Control Module Design 7 3 The Control Module Design. General

NIBE AB Sweden Hannabadsvägen 5Box 14 SE-285 21 [email protected]

431199