Installation, Operation and Maintenance Instructions Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
1 General Information ...............................................................................................................................................3
2 Type overview horizontal weather-proof louvres...................................................................................................4 2.1 WSG-H3-Fu ......................................................................................................................................................4 0°–35° (bottom flange without duct connection / drainage over-roof) 2.2 WSG-H3-Fu-KA ................................................................................................................................................4 0°–35° (bottom flange with duct connection / drainage over-roof) 2.3 WSG-H3-Fo ......................................................................................................................................................4 0°–35° (top flange without duct connection / internal drainage by pipes) 2.4 WSG-H3-Fo-KA ................................................................................................................................................4 0°–35° (top flange with duct connection / internal drainage by pipes) 2.5 WSG-H3-SDf ....................................................................................................................................................5 36°–54° (top flange without duct connection / drainage over-roof) 2.6 WSG-H3-SDf- KA ..............................................................................................................................................5 36°–54° (top flange with duct connection / drainage over-roof) 2.7 WSG-H3-SDs ....................................................................................................................................................5 55°–80° (top flange without duct connection / drainage over-roof) 2.8 WSG-H3-SDs-KA ..............................................................................................................................................5 55°–80° (top flange with duct connection / drainage over-roof)
3 Mounting frame for horizontal weather-proof louvres for pitched roofs (optional) .............................................6 3.1 Mounting frame for weather-proof louvre WSG-H3-Fu+Fo / 0°–35° ..............................................................6 3.2 Mounting frame for weather-proof louvre WSG-H3-SDf+SDs / 36°–80° .......................................................6
4 Roof systems ............................................................................................................................................................ 7 4.1 Single ventilated pitched roof with scaled covering (e.g. tiles) ...................................................................... 7 4.2 Single ventilated pitched roof with seamed covering (e.g. double seam roof) .............................................. 7 4.3 Non-ventilated pitched roof (e.g. sandwich panels in industrial areas)......................................................... 7
5 Assembly instructions .............................................................................................................................................8 5.1 General assembly instructions ........................................................................................................................8 5.2 Installation in single ventilated pitched roof with scaled covering (e.g. tiles) ............................................. 10 a) WSG-H3-Fu ................................................................................................................................................ 10
0°–35° (bottom flange without duct connection / drainage over-roof) b) WSG-H3-Fu-KA ..........................................................................................................................................12
0°–35° (bottom flange with duct connection / drainage over-roof) c) WSG-H3-Fo ................................................................................................................................................ 14
0°–35° (top flange without duct connection / internal drainage by pipes) d) WSG-H3-Fo-KA ..........................................................................................................................................16
0°–35° (top flange with duct connection / internal drainage by pipes) e) WSG-H3-SDf ...............................................................................................................................................18
36°–54° (top flange without duct connection / drainage over-roof) f) WSG-H3-SDf- KA ...................................................................................................................................... 20
36°–54° (top flange with duct connection / drainage over-roof) g) WSG-H3-SDs ..............................................................................................................................................22
55°–80° (top flange without duct connection / drainage over-roof) h) WSG-H3-SDs-KA ...................................................................................................................................... 24
55°–80° (top flange with duct connection / drainage over-roof)
LUCOMA AG, Weekendweg 5, CH-3646 Einigen, SwitzerlandTel: +41 33 655 00 44, Fax: +41 33 655 00 45, www.lucoma.com, [email protected]
Page 2 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
5.3 Installation in single ventilated pitched roof with seamed roofing (double seamed roof) ..........................26 a) WSG-H3-Fu ................................................................................................................................................26
0°–35° (bottom flange without duct connection / drainage over-roof) b) WSG-H3-Fu-KA .........................................................................................................................................28
0°–35° (bottom flange with duct connection / drainage over-roof) c) WSG-H3-Fo ............................................................................................................................................... 30
0°–35° (top flange without duct connection / internal drainage by pipes) d) WSG-H3-Fo-KA .........................................................................................................................................32
0°–35° (top flange with duct connection / internal drainage by pipes) e) WSG-H3-SDf ..............................................................................................................................................34
36°–54° (top flange without duct connection / drainage over-roof) f) WSG-H3-SDf- KA ....................................................................................................................................... 36
36°–54° (top flange with duct connection / drainage over-roof) g) WSG-H3-SDs ..............................................................................................................................................38
55°–80° (top flange without duct connection / drainage over-roof) h) WSG-H3-SDs-KA ......................................................................................................................................40
55°–80° (top flange with duct connection / drainage over-roof)
5.4 Non-ventilated pitched roof (e.g. sandwich panels in the industrial sector) .............................................. 42 a) WSG-H3-Fu ............................................................................................................................................... 42
0°–35° (bottom flange without duct connection / drainage over-roof) b) WSG-H3-Fu-KA ........................................................................................................................................ 44
0°–35° (bottom flange with duct connection / drainage over-roof) c) WSG-H3-Fo ................................................................................................................................................46
0°–35° (top flange without duct connection / internal drainage by pipes) d) WSG-H3-Fo-KA .........................................................................................................................................48
0°–35° (top flange with duct connection / internal drainage by pipes)
6 Transport / Handling ............................................................................................................................................ 50
7 Maintenance ........................................................................................................................................................ 50
8 Disclaimer / Warranty .......................................................................................................................................... 50
Page 3 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
1 GeneralStandards – SIA 271 “Abdichtungen von Hochbauten” (Seals on build-ing constructions)
– EN 1873+A1:2016 Prefabricated accessories for roofing, 6.5.2 Impact resistance (SIA 232.306+A1 Civil engineering)
Certificates Lucoma AG has the following certificate and approvals. Please visit www.lucoma.ch to view the latest documents. – ISO 9001 Quality Management System – KTA 1401 and IAEA 50-C-Q (Product manufacture for nuclear installations)
– Explosion Protection Directive ATEX 2014/34/EU (Non-electrical equipment for use in potentially explosive at-mospheres)
Work safetyIn matters of work safety, the local standards and regula-tions must be observed. In particular, fall-through protec-tion must be provided until the weather-proof louvre is in-stalled. Do not walk on weather-proof louvres themselves despite the fact that they have been tested and certified for fall-through protection.
General requirements for Switzerland – SUVA Swiss Federal Accident Insurance Fund, 6004 Lucerne, www.suva.ch
– Ordinance on construction work (BauAV) – EKAS Swiss Federal Coordination Commission for Health and Safety, 6002 Lucerne, www.ekas.ch
Fall-through protectionRoofs are now more frequently used actively. They are planted, serve as water retention surfaces or act as loca-tions for installing solar and building service equipment. There is a more frequent requirement for roofs to be accessible, also for foot traffic. This increases the risk of falling from the roof due to insufficiently secured roof accesses (skylights, weather-proof louvres, etc.)If one of the items below applies, roof accesses must have a shatter-proof design.1. The building area is freely accessible to third parties.2. Technical equipment that requires regular maintenance
(e.g. more than once yearly), e.g. vents, solar systems etc. are located on the roof.
3. The roof is intensively or extensively planted.4. There are unsecured traffic paths on the building area
with roof access.
5. The building area has roof accesses which are not iden-tified as such for night work or snow clearing.
Horizontal weather-proof louvres WSG-H3 are guaran-teed fall-through proof in compliance with EN 1873+A1:2016 (or SIA 232.306+A1). Tested and confirmed by Empa Dübendorf (Swiss Federal Laboratories for Materials Science and Technology) in Test Report 5214019875. Remark: Horizontal weather-proof louvres from Lucoma are fall-through proof but not walkable, it is strictly prohib-ited to walk on horizontal weather-proof louvres. This would damage the louvres. Lucoma assumes no liability for walking on weather-proof louvres and recommends that this be prevented by additional building measures.
Fire protectionCompliance is mandatory with all relevant international, national and local standards and regulations for fire pro-tection.
Lightning protectionWeather-proof louvres must be connected to the lightning protection system in compliance with international, na-tional and local standards and regulations.
Explosion protectionWeather-proof louvres are only approved if they have the appropriate design and are properly labelled according to ATEX Directive 2014/34/EU for Zone 1, 21 or 2, 22. Please also note the remarks under the individual items in these instructions.
Page 4 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
2 Type overview horizontal weather-proof louvres
2.1 WSG-H3-Fu (bottom flange without duct connection / drainage over-roof)
The weather-proof louvre can be used on all flat roof types with a pitch of 0°–35°. Drainage is over-roof.
2.2 WSG-H3-Fu-KA (bottom flange with duct connection / drainage over-roof)
The weather-proof louvre can be used on all flat roof types with a pitch of 0°–35°. Drainage is over-roof. The louvre is also equipped at the base with a duct connec-tion.
2.3 WSG-H3-Fo (top flange without duct connection / internal drainage by pipes)
The weather-proof louvre can be used on all flat roof types with a pitch of 0°–35°. Drainage is by internal drain pipes.
2.4 WSG-H3-Fo-KA (top flange with duct connection / internal drainage by pipes)
The weather-proof louvre can be used on all flat roof types with a pitch of 0°–35°. Drainage is by internal drain pipes. The louvre is also equipped at the base with a duct connection.
Page 5 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
2.5 WSG-H3-SDf (top flange without duct connection / drainage over-roof)
The weather-proof louvre can be used for all inclined roof types with an inclination of 36°–54°. Drainage is via the roof.
2.6 WSG-H3-SDf-KA (top flange with duct connection / drainage over-roof)
The weather-proof louvre can be used for all inclined roof types with an inclination of 36°–54°. Drainage is via the roof. The grillee is additionally equipped with a duct connection at the bottom.
2.7 WSG-H3-SDs (top flange without duct connection / drainage over-roof)
The weather-proof louvre can be used for all inclined roof types with an inclination of 55°–80°. Drainage is via the roof.
2.8 WSG-H3-SDs-KA (top flange with duct connection / drainage over-roof)
The weather-proof louvre can be used for all inclined roof types with an inclination of 55°–80°. Drainage is via the roof. The grillee is additionally equipped with a duct connection at the bottom.
Page 6 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
3 Mounting frame for horizontal weather-proof louvres for pitched roofs (optional)
3.1 Mounting frame for weather-proof louvre WSG-H3-Fu+Fo / 0°–35°
3.2 Mounting frame for weather-proof louvre WSG-H3-SDf+SDs / 36°–80°
The mounting frame for the installation of horizontal weather-proof louvres WSG-H3-Fu+Fo or inclined roof weather-proof louvres WSG-H3-SDf+SDs is optionally available on order and is made to measure for specific projects.
The mounting frame is supplied prefabricated in individual parts including fasteners and must be assembled on site by the contractor. Detailed installation instructions for the mounting frames can be obtained from www.lucoma.ch.
Page 7 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
The weather-proof louvres incl. the system-compatible mounting frames can be used for all inclined roof systems. These installation instructions cover the three most common types of pitched roofs. The derivations for any
other inclined roof types can be taken from these three instructions. In case of doubt, LUCOMA’s specialists are available for enquiries.
4 Roof systems
4.1 Single ventilated pitched roof with scaled covering (e.g. tiles)
4.2 Single ventilated pitched roof with seamed covering (e.g. double seam roof)
4.3 Non-ventilated pitched roof (e.g. sandwich panels in industrial areas)
E Structure (e.g. rafters)D UnderroofC Counter battening / ventilationB Roof lathingA Scaled covering (e.g. tiles)
04 / Dachsystemea) Einfach belüftetes, geneigtes Dach / geschuppte Deckung
MST 1:10, Format Din A4, Gez. ma 20.08.2019
EDCBA F
F Thermal insulation
G
G Vapour control layer
G Vapour control layerF Thermal insulation
04 / Dachsystemeb) Einfach belüftetes, geneigtes Dach / gefalzte Deckung
MST 1:10, Format Din A4, Gez. ma 22.08.2019
E Structure (e.g. rafters)D Underroof
A Folded covering (double seam roof)B Wooden formworkC Counterbattening / Ventilation
EDCBA F G
E Structure (e.g. rafters)D UnderroofC Counter battening / ventilationB Roof lathingA Scaled covering (e.g. tiles)
04 / Dachsystemea) Einfach belüftetes, geneigtes Dach / geschuppte Deckung
MST 1:10, Format Din A4, Gez. ma 20.08.2019
EDCBA F
F Thermal insulation
G
G Vapour control layer
G Vapour control layerF Thermal insulation
04 / Dachsystemeb) Einfach belüftetes, geneigtes Dach / gefalzte Deckung
MST 1:10, Format Din A4, Gez. ma 22.08.2019
E Structure (e.g. rafters)D Underroof
A Folded covering (double seam roof)B Wooden formworkC Counterbattening / Ventilation
EDCBA F G
04 / Dachsystemec) Nicht belüftetes, geneigtes Dach / Sandwichpaneele
MST 1:10, Format Din A4, Gez. ma 22.08.2019
A Sandwich panels
A
B Structure (e.g. steel girder)
B
04 / Dachsystemec) Nicht belüftetes, geneigtes Dach / Sandwichpaneele
MST 1:10, Format Din A4, Gez. ma 22.08.2019
A Sandwich panels
A
B Structure (e.g. steel girder)
B
Page 8 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
5 Assembly instructions
Horizontal weather-proof louvres for flat roofs always re-quire a supporting structure. The suitable mounting frame can be optionally ordered from LUCOMA or the customer can make an appropriate frame construction himself. With louvres larger than 6 m2 or louvres consisting of sev-
eral louvres, the customer also requires an additional sup-porting structure for the peripheral water channel or at the point where the multiple louvres abut. The designing engineer or the installer is responsible for producing ade-quate support.
Supporting structure for weather-proof louvres with top flange
Supporting structure for multi-part grids
Water channel Water channel
Support structure (customer)
Support structure (customer)
Water channelWater channelWater channel
Support structure (customer)
Support structure (customer)
Support structure (customer)
5.1 General
Page 9 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
The Lucoma type H3 weather-proof louvre can be used on all flat roof types with a pitch of 0°–35°. If the roof con-struction has a slope, it must be taken into consideration when installing the louvre. To ensure trouble-free drain-age of the louvre, water outlets and the blade alignment
must be positioned as shown in the drawings below. Undesired water flow may occur if the installation is not carried out properly. In this case, the manufacturer cannot assume any liability for consequential damage.
On horizontal weather-proof louvres at locations exposed to extreme weather, the customer should fit a seal along the contact surface between the flange and the frame. Make absolutely certain that the flanges are fully seated along the entire periphery when the louvre is installed. On weather-proof louvres which have air duct connection nozzles and/or internal water drain pipes, the nozzles or pipes must have a torsion-free connection. The weath-er-proof louvres are then fully functional.
ATEX: Compliance is mandatory with all relevant interna-tional and national standards and regulations for Ex zones. With louvres in ATEX design in particular, the louvre housing must be earthed using the earth wires fitted by the manufacturer. When using sealing materials, make sure that they are suitable for the particular ATEX zone. It is prohibited to make any mechanical modifications to the product. In addition, do not attach any components (frost monitors, temperature sensors etc.) to the louvres if these components have not been analysed for danger of igni-tion by their manufacturer or approved for the particular ATEX zones.
B
H
max. 3
5
Page 10 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
a) WSG-H3-Fu / 0°–35° (bottom flange without duct connection / drainage over-roof)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
H (clear size of weather protection grille)150
150
Ventilation
Einbaubeispiel Längsschnitt
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss / Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (Ziegel)
H
Sheet metal edging (on-site)
30
440
min.
300
Flange
Flange
Frame (optional delivery LUCOMA / standard height 440mm) 50(clear size of mounting frame)
drainage
Thermal insulation (on-site / standard thickness 80mm)
Roof lathing (on-site) Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Roofing tile (on-site) Lead strip (on-site)
5.2 Installation in single ventilated pitched roof with scaled covering (e.g. tiles)
Page 11 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
Thermal insulation (on-site / standard thickness 80mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Ziegel)
B
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss / Entwässerung über Dach)
Lead lobes (on-site)
B(clear size of weather protection grille)150 150
Flange Flange
(clear size of mounting frame)
Roof lathing (on-site) Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Roofing tile (on-site)
Border (on-site)
Page 12 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
b) WSG-H3-Fu-KA / 0°–35° (bottom flange with duct connection / drainage over-roof)
Roof lathing (on-site) Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Roofing tile (on-site) Lead strip (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Ventilation
Einbaubeispiel Längsschnitt
WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (Ziegel)
H
Sheet metal edging (on-site)
30
440
min.
300
30
(clear size of weather protection grille)
Frame (optional delivery LUCOMA / standard height 440mm)
150
150
Flange
Flange
H
50
Ventilation duct (on-site)
(clear size of mounting frame)
drainageThermal insulation (on-site / standard thickness 80mm)
Page 13 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
Thermal insulation (on-site / standard thickness 80mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Lead lobes (on-site)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Ziegel)
B(clear size of weather protection grille)150 150
B
WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)
Ventilation duct (on-site)
Flange Flange
(clear size of mounting frame)
Roof lathing (on-site) Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Roofing tile (on-site)
Page 14 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
c) WSG-H3-Fo / 0°–35° (top flange without duct connection / internal drainage by pipes)
Roof lathing (on-site)
Lead strip (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Frame (optional delivery LUCOMA / standard height 440mm)
Ventilation
Einbaubeispiel Längsschnitt
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (Ziegel)
H
Sheet metal edging (on-site)
50
30
H (clear size of weather protection grille)
150
150
Flange
Flange
440
min.
300
(clear size of mounting frame)
Thermal insulation (on-site / standard thickness 80mm)
Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Roofing tile (on-site)
Page 15 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
Thermal insulation (on-site / standard thickness 80mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
150
Lead lobes (on-site)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Ziegel)
(clear size of weather protection grille)150
B
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)
BFlange Flange
(clear size of mounting frame)
Thermal insulation (on-site)Vapour check (on-site)
Underroof (on-site) Counter battening / ventilation (on-site)
Roofing tile (on-site) Roof lathing (on-site) Border (on-site)
Page 16 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
d) WSG-H3-Fo-KA / 0°–35° (top flange with duct connection / internal drainage by pipes)
Roof lathing (on-site)
Lead strip (on-site)
Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Roofing tile (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Drainage pipe in ventilation duct (on-site)
Ventilation
Einbaubeispiel Längsschnitt
WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (Ziegel)
H
Sheet metal edging (on-site)
50
30
H (clear size of weather protection grille)
150
150
Flange
Flange
440
Frame (optional delivery LUCOMA / standard height 440mm)
min.
300
(clear size of mounting frame)
Thermal insulation (on-site / standard thickness 80mm)
Page 17 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Roof lathing (on-site)
Thermal insulation (on-site)Vapour check (on-site)
Underroof (on-site) Counter battening / ventilation (on-site)
Roofing tile (on-site)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
Thermal insulation (on-site / standard thickness 80mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Lead lobes (on-site)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Ziegel)
B(clear size of weather protection grille)150 150
B
WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)
Ventilation duct (on-site)
Flange Flange
(clear size of mounting frame)
Page 18 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
e) WSG-H3-SDf / 36°–54° (top flange without duct connection / drainage over-roof)
Thermal insulation 40mm (on-site)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-SDf / 35° - 55° (Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
drainage
Ventilation
H(clear size of weather protection grille)
Roof lathing (on-site)
75
75
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)
Flange
Flange
Sheet metal edging (on-site)
min. 12
0mm
30mm on
board
50
H
Einfach belüftetes, geneigtes Dach (Ziegel)
340
H(clear size of roof opening)
(clear size of mounting frame)
Lead strip (on-site)
Underroof (on-site) Counter battening / ventilation (on-site)
Roofing tile (on-site)
Page 19 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site)Vapour check (on-site)
Underroof (on-site) Lead lobes (on-site)
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
B75 75(clear size of weather protection grille)
B
30
Einfach belüftetes, geneigtes Dach (Ziegel)
340
30
WSG-H3-SDf / 35° - 55° (Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
Lead lobes (on-site)
Flange Flange
(clear size of mounting frame)
Roof lathing (on-site)
Counter battening / ventilation (on-site)
Roofing tile (on-site)
Border (on-site)
Page 20 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
f) WSG-H3-SDf- KA / 36°–54° (top flange with duct connection / drainage over-roof)
Thermal insulation 40mm (on-site)
Roof lathing (on-site)
Sheet metal edging (on-site)Underroof (on-site) Counter battening / ventilation (on-site)
Roofing tile (on-site)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Lead strip (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-SDf- KA / 35° - 55° (Flansch oben mit Kanalanschluss / Entwässerung über Dachfläche)
drainage
Ventilation
H(clear size of weather protection grille)
75
75
Flange
Flange
min. 12
0mm
30mm on
board
50H
Einfach belüftetes, geneigtes Dach (Ziegel)
340
H(clear size of roof opening)
Ventilation duct (on-site)
(clear size of mounting frame)
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)
Page 21 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site)Vapour check (on-site)
Underroof (on-site) Lead lobes (on-site)Counter battening / ventilation (on-site)
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
B75 (clear size of weather protection grille)
B
30
Einfach belüftetes, geneigtes Dach (Ziegel)
340
WSG-H3-SDf- KA / 35° - 55° (Flansch oben mit Kanalanschluss / Entwässerung über Dachfläche)
Lead lobes (on-site)
75
30
Ventilation duct (on-site)
Flange Flange
(clear size of mounting frame)
Page 22 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
g) WSG-H3-SDs / 55°–80° (top flange without duct connection / drainage over-roof)
Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Lead strip (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
WSG-H3-SDs / 55° - 80° ( Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
drainage
VentilationH
(clear size of weather protection grille)
75
75
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)
Flange
Flange
min. 120mm
30mm on board
H
340
H(clear size of roof opening)
50
Einbaubeispiel Längsschnitt
Einfach belüftetes, geneigtes Dach (Ziegel)
Roofing tile (on-site)
Roof lathing (on-site)
Sheet metal edging (on-site) Isolation thermique 40mm (par maître d'ouvrage)
Roofing tile (on-site)
(clear size of mounting frame)
Page 23 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site)Vapour check (on-site)
Underroof (on-site) Lead lobes (on-site)Counter battening / ventilation (on-site)
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
B75 75(clear size of weather protection grille)
B
30
Einfach belüftetes, geneigtes Dach (Ziegel)
340
30
WSG-H3-SDs / 55° - 80° ( Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
Lead lobes (on-site)
Flange Flange
(clear size of mounting frame)
Border (on-site)
Page 24 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
h) WSG-H3-SDs-KA / 55°–80° (top flange with duct connection / drainage over-roof)
Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Lead strip (on-site)Roof lathing (on-site) Roofing tile (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
WSG-H3-SDs-KA / 55° - 80° (mit Kanalanschluss / Entwässerung über Dachfläche)
drainage
VentilationH
(clear size of weather protection grille)
75
75
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)
Flange
Flange
min. 120mm
30mm on board
H
340
H(clear size of roof opening)
50
Einbaubeispiel Längsschnitt
Einfach belüftetes, geneigtes Dach (Ziegel)
Ventilation duct (on-site)
(clear size of mounting frame)
Roofing tile (on-site) Sheet metal edging (on-site) Isolation thermique 40mm (par maître d'ouvrage)
Page 25 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site)Vapour check (on-site)
Underroof (on-site) Lead lobes (on-site)Counter battening / ventilation (on-site)
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
B75 75(clear size of weather protection grille)
B
30
Einfach belüftetes, geneigtes Dach (Ziegel)
340
30
WSG-H3-SDs-KA / 55° - 80° (Flansch oben mit Kanalanschluss / Entwässerung über Dachfläche)
Ventilation duct (on-site)
Lead lobes (on-site)
Flange Flange
(clear size of mounting frame)
Page 26 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
a) WSG-H3-Fu / 0°–35° (bottom flange without duct connection / drainage over-roof)
5.3 Installation in single ventilated pitched roof with seamed covering (e.g. double seamed roof)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
H (clear size of weather protection grille)150
150
Ventilation
Einbaubeispiel Längsschnitt
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss / Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
H (clear size of mounting frame)
30
min.
300
Flange
Flange
50
440
Frame (optional delivery LUCOMA / standard height 440mm)
drainage
Thermal insulation (on-site / standard thickness 80mm)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 27 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Counter battening / ventilation (on-site)
Einbaubeispiel Querschnitt
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
B
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss / Entwässerung über Dach)
B(clear size of weather protection grille)150 150
min. 100min. 100
FlangeFlange
Thermal insulation (on-site / standard thickness 80mm)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
(clear size of mounting frame)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Counter battening / ventilation (on-site)
Einbaubeispiel Querschnitt
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
B
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss / Entwässerung über Dach)
B(clear size of weather protection grille)150 150
min. 100min. 100
FlangeFlange
Thermal insulation (on-site / standard thickness 80mm)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
(clear size of mounting frame)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 28 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
b) WSG-H3-Fu-KA / 0°–35° (bottom flange with duct connection / drainage over-roof)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
(clear size of mounting frame)
H
Einbaubeispiel Längsschnitt
WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
H (clear size of weather protection grille)150
150
Ventilation
30
min.
300
Flange
Flange
50
440 Frame (optional delivery LUCOMA / standard height 440mm)Ventilation duct (on-site)
drainage
Thermal insulation (on-site / standard thickness 80mm)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 29 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
MST 1:10, Format Din A4, Gez. ma 22.08.2019
(clear size of mounting frame)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)
B
B(clear size of weather protection grille)150 150
Flange
min. 100min. 100Ventilation duct (on-site)
Flange
Thermal insulation (on-site / standard thickness 80mm)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
MST 1:10, Format Din A4, Gez. ma 22.08.2019
(clear size of mounting frame)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)
B
B(clear size of weather protection grille)150 150
Flange
min. 100min. 100Ventilation duct (on-site)
Flange
Thermal insulation (on-site / standard thickness 80mm)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 30 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
c) WSG-H3-Fo / 0°–35° (top flange without duct connection / internal drainage by pipes)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Frame (optional delivery LUCOMA / standard height 440mm)
Ventilation
Einbaubeispiel Längsschnitt
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
H (clear size of mounting frame)50
H (clear size of weather protection grille)
150
150
Flange
Flange
440
min.
300
30
Double seam roof (on-site)
Thermal insulation (on-site / standard thickness 80mm)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 31 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Thermal insulation (on-site / standard thickness 80mm)
150
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
(clear size of weather protection grille)150
B
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)
B
min. 100min. 100
Flange Flange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Thermal insulation (on-site / standard thickness 80mm)
150
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
(clear size of weather protection grille)150
B
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)
B
min. 100min. 100
Flange Flange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 32 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
d) WSG-H3-Fo-KA / 0°–35° (top flange with duct connection / internal drainage by pipes)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Drainage pipe in ventilation duct (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
Einbaubeispiel Längsschnitt
WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
Ventilation
(clear size of mounting frame)
50
H (clear size of weather protection grille)
150
150
Flange
Flange
440
H
min.
300
30
Thermal insulation (on-site / standard thickness 80mm)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 33 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)
150(clear size of weather protection grille)150
B
B
min. 100min. 100
Ventilation duct (on-site)
FlangeFlange
Thermal insulation (on-site / standard thickness 80mm)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)
150(clear size of weather protection grille)150
B
B
min. 100min. 100
Ventilation duct (on-site)
FlangeFlange
Thermal insulation (on-site / standard thickness 80mm)
Frame / standard height e.g. 440 mm (optional delivery LUCOMA)
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 34 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
e) WSG-H3-SDf / 36°–54° (top flange without duct connection / drainage over-roof)
Thermal insulation 40mm (on-site)Underroof (on-site) Wood formwork (on-site)
Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
min. 12
0mm
Einbaubeispiel Längsschnitt
WSG-H3-SDf / 35° - 55° (Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
drainage
Ventilation
H(clear size of weather protection grille)
(clear size of mounting frame)
75
75
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)
Flange
30mm on
board
50
H
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
H(clear size of roof opening)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Flange
Double seam roof (on-site)
Page 35 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
MST 1:10, Format Din A4, Gez. ma 22.08.2019
(clear size of mounting frame)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDf / 35° - 55° (Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
MST 1:10, Format Din A4, Gez. ma 22.08.2019
(clear size of mounting frame)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDf / 35° - 55° (Flansch oben ohne Kanalanschluss / Entwässerung über Dachfläche)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 36 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
f) WSG-H3-SDf- KA / 36°–54° (top flange with duct connection / drainage over-roof)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)Ventilation duct (on-site)
min. 12
0mm
drainage
Ventilation
H(clear size of weather protection grille)
75
75
Flange
30mm on
board
50
Einbaubeispiel Längsschnitt
WSG-H3-SDf- KA / 35° - 55° (mit Kanalanschluss / Entwässerung über Dachfläche)Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
H
(clear size of roof opening)
H
(clear size of mounting frame)
Flange
Thermal insulation 40mm (on-site)Underroof (on-site) Wood formwork (on-site) Double seam roof (on-site)
Counter battening / ventilation (on-site) Underroof (on-site) Thermal insulation (on-site)Vapour check (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 37 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Ventilation duct (on-site)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDf- KA / 35° - 55° (mit Kanalanschluss / Entwässerung über Dachfläche)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Ventilation duct (on-site)
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDf- KA / 35° - 55° (mit Kanalanschluss / Entwässerung über Dachfläche)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 38 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
g) WSG-H3-SDs / 55°–80° (top flange without duct connection / drainage over-roof)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Thermal insulation 40mm (on-site)
Double seam roof (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
WSG-H3-SDs / 55° - 80° ( ohne Kanalanschluss / Entwässerung über Dachfläche)
drainage
VentilationH
(clear size of weather protection grille)
(clear size of mounting frame)
75
75
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)
Flange
Flange
30mm on board
H
H(clear size of roof opening)
50
Einbaubeispiel Längsschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
340
min. 120
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 39 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDs / 55° - 80° ( ohne Kanalanschluss / Entwässerung über Dachfläche)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDs / 55° - 80° ( ohne Kanalanschluss / Entwässerung über Dachfläche)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 40 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
h) WSG-H3-SDs-KA / 55°–80° (top flange with duct connection / drainage over-roof)
Thermal insulation 40mm (on-site)
Double seam roof (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
WSG-H3-SDs-KA / 55° - 80° (mit Kanalanschluss / Entwässerung über Dachfläche)
Einbaubeispiel Längsschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)
drainage
VentilationH
(clear size of weather protection grille)
(clear size of mounting frame)
75
75
Frame / standard height e.g. 340mm (optional delivery
LUCOMA)30mm on board
H
H(clear size of roof opening)
50
340
min. 120
Ventilation duct (on-site)
Flange
Flange
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 41 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDs-KA / 55° - 80° (mit Kanalanschluss / Entwässerung über Dachfläche)
Ventilation duct (on-site)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Thermal insulation 40mm (on-site)Frame / standard height e.g. 340mm (optional delivery LUCOMA)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (gefalzte Deckung)WSG-H3-SDs-KA / 55° - 80° (mit Kanalanschluss / Entwässerung über Dachfläche)
Ventilation duct (on-site)
B75 75(clear size of weather protection grille)
B
30
340
30
min. 100min. 100
FlangeFlange
(clear size of mounting frame)
Counter battening / ventilation (on-site)
Thermal insulation (on-site)Underroof (on-site)
Vapour check (on-site)
Wood formwork (on-site) Double seam roof (on-site)
Attention: On the ridge side, only one seam may hit the ventilation grille. Lateral drainage of at least 10 cm must be ensured. If there are two or more folds, a recessed gutter must be formed in accordance
Page 42 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
a) WSG-H3-Fu / 0°–35° (bottom flange without duct connection / drainage over-roof)
5.4 Non-ventilated pitched roof (e.g. sandwich panels in the industrial sector)
Supporting structure (on-site) Sanwichpanalee (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
H (clear size of weather protection grille)150
150
30
150
150
Thermal insulation (on-site / standard thickness 80mm)
Frame (optional delivery LUCOMA / standard height 440mm) 50
Ridge sheet metal (on-site) Sheet metal edging (on-site)
H
Flange
Flange
(clear size of mounting frame)
Sheet metal edging (on-site)
drainage
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site) Sanwichpanalee (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
H (clear size of weather protection grille)150
150
30
150
150
Thermal insulation (on-site / standard thickness 80mm)
Frame (optional delivery LUCOMA / standard height 440mm) 50
Ridge sheet metal (on-site) Sheet metal edging (on-site)
H
Flange
Flange
(clear size of mounting frame)
Sheet metal edging (on-site)
drainage
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Page 43 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site / standard thickness 80mm)
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss Entwässerung über Dach)
B
440
B(clear size of weather protection grille)150 150
Flange Flange
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site)
Sanwichpanalee (on-site)
Thermal insulation (on-site / standard thickness 80mm)
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)WSG-H3-FU / 0° - 35° (Flansch unten ohne Kanalanschluss Entwässerung über Dach)
B
440
B(clear size of weather protection grille)150 150
Flange Flange
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site)
Sanwichpanalee (on-site)
Page 44 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
b) WSG-H3-Fu-KA / 0°–35° (bottom flange with duct connection / drainage over-roof)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
3030
H (clear size of weather protection grille)
Frame (optional delivery LUCOMA / standard height 440mm)
Thermal insulation (on-site / standard thickness 80mm)
150
150
50
Supporting structure (on-site) Sanwichpanalee (on-site)
Ridge sheet metal (on-site)
Sheet metal edging (on-site)
Sheet metal edging (on-site)
H
Ventilation duct (on-site)
Flange
Flange
(clear size of mounting frame)
drainage
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
3030
H (clear size of weather protection grille)
Frame (optional delivery LUCOMA / standard height 440mm)
Thermal insulation (on-site / standard thickness 80mm)
150
150
50
Supporting structure (on-site) Sanwichpanalee (on-site)
Ridge sheet metal (on-site)
Sheet metal edging (on-site)
Sheet metal edging (on-site)
H
Ventilation duct (on-site)
Flange
Flange
(clear size of mounting frame)
drainage
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Page 45 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site / standard thickness 80mm)
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)
B(clear size of weather protection grille)150 150
Flange
Ventilation duct (on-site)
B
440
Flange
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site)
Sanwichpanalee (on-site)
Thermal insulation (on-site / standard thickness 80mm)
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)WSG-H3-FU-KA / 0° - 35° (Flansch unten mit Kanalanschluss / Entwässerung über Dach)
B(clear size of weather protection grille)150 150
Flange
Ventilation duct (on-site)
B
440
Flange
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site)
Sanwichpanalee (on-site)
Page 46 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
c) WSG-H3-Fo / 0°–35° (top flange without duct connection / internal drainage by pipes)
Supporting structure (on-site) Sanwichpanalee (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
50
30
H (clear size of weather protection grille)
150
150
Flange
Frame (optional delivery LUCOMA / standard height 440mm)
Thermal insulation (on-site / standard thickness 80mm)
Ridge sheet metal (on-site)Sheet metal edging (on-site)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
H
Flange
(clear size of mounting frame)
Sheet metal edging (on-site)
Supporting structure (on-site) Sanwichpanalee (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
50
30
H (clear size of weather protection grille)
150
150
Flange
Frame (optional delivery LUCOMA / standard height 440mm)
Thermal insulation (on-site / standard thickness 80mm)
Ridge sheet metal (on-site)Sheet metal edging (on-site)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
H
Flange
(clear size of mounting frame)
Sheet metal edging (on-site)
Page 47 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site / standard thickness 80mm)
MST 1:10, Format Din A4, Gez. ma 14.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
B
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)
150(clear size of weather protection grille)150B
440
Flange Flange
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site)
Sanwichpanalee (on-site)
Thermal insulation (on-site / standard thickness 80mm)
MST 1:10, Format Din A4, Gez. ma 14.08.2019
Einbaubeispiel Querschnitt
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
B
WSG-H3-FO / 0° - 35° (Flansch oben ohne Kanalanschluss / Innenliegende Entwässerung über Rohre)
150(clear size of weather protection grille)150B
440
Flange Flange
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site)
Sanwichpanalee (on-site)
Page 48 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
d) WSG-H3-Fo-KA / 0°–35° (top flange with duct connection / internal drainage by pipes)
Supporting structure (on-site) Sanwichpanalee (on-site)
Drainage pipe in ventilation duct (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
50
30
H (clear size of weather protection grille)
150
150
Frame (optional delivery LUCOMA / standard height 440mm)
Thermal insulation (on-site / standard thickness 80mm)
Ridge sheet metal (on-site) Sheet metal edging (on-site)
H
Ventilation duct (on-site)
Flange
Flange
(clear size of mounting frame)
Sheet metal edging (on-site)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Supporting structure (on-site) Sanwichpanalee (on-site)
Drainage pipe in ventilation duct (on-site)
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einbaubeispiel Längsschnitt
WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)Einfach belüftetes, geneigtes Dach (Sandwichpaneele)
50
30
H (clear size of weather protection grille)
150
150
Frame (optional delivery LUCOMA / standard height 440mm)
Thermal insulation (on-site / standard thickness 80mm)
Ridge sheet metal (on-site) Sheet metal edging (on-site)
H
Ventilation duct (on-site)
Flange
Flange
(clear size of mounting frame)
Sheet metal edging (on-site)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Page 49 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Thermal insulation (on-site / standard thickness 80mm)
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
Supporting structure (on-site)
Sanwichpanalee (on-site)
Einbaubeispiel Querschnitt
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)
B
150(clear size of weather protection grille)150B
440
Ventilation duct (on-site)
Flange Flange
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Thermal insulation (on-site / standard thickness 80mm)
Sheet metal edging (on-site)
Frame (optional delivery LUCOMA / standard height 440mm)
Supporting structure (on-site)
Sanwichpanalee (on-site)
Einbaubeispiel Querschnitt
MST 1:10, Format Din A4, Gez. ma 22.08.2019
Einfach belüftetes, geneigtes Dach (Sandwichpaneele)WSG-H3-FO-KA / 0° - 35° (Flansch oben mit Kanalanschluss / Innenliegende Entwässerung über Rohre)
B
150(clear size of weather protection grille)150B
440
Ventilation duct (on-site)
Flange Flange
(clear size of mounting frame)
Caution:For reasons of tightness, installations in sandwich panels should always be arranged in the immediate vicinity of the ridge.
Page 50 / September 2019
Horizontal weather-proof louvres WSG-H3-SD for pitched roofs
Installation, Operation and Maintenance Instructions
Depending on the degree of soiling, clean the louvre at regular intervals to remove leaves and similar deposits. WSGs may be cleaned using compressed air, leaf blowers or brushes. Make sure that as few solid particles (leaves, twigs, etc.) pass through the top mesh grids. During clean-ing work, it is absolutely forbidden to walk on the blades. With very large and poorly accessible WSG-h, we recom-mend covering the louvre with a wooden board or similar.Please make sure that the wooden board is long enough and contacts the louvre frame on both sides and does not
rest on the blades. The wooden board can be positioned so that it can be walked on during cleaning work. Suitable safety measures must be taken to safeguard the cleaning personnel (e.g. fall protection). This is the responsibility of the operator.
ATEX: Compliance is mandatory with all relevant inter-national and national standards and regulations for Ex zones.
These Installation, Operation and Maintenance Instructions are not legally binding installation documents for horizontal weather protection grilles and mounting frames. However, possible connection examples are published on the basis of representative superstructures.The specifications contained in this document were com-piled to the best of our knowledge based on current knowledge and experience. LUCOMA reserves the right to make changes at any time to match the current state of production practice. These planning documents make
no claim to completeness. No legally binding obligation can therefore be derived from them. Compliance is man-datory with the local construction laws, standards and regulations for design, component dimensioning, material selection, laying, and governing heat, moisture, noise and fire protection.
The product warranty according to the Swiss Code of Obligations is 2 years, provided that installation, opera-tion and maintenance are properly executed.
7 Maintenance
8 Exemption from liability / warranty
Basically, avoid any damage caused by external influences. Do not lift the louvre by the blades. Louvres with a maxi-mum weight of 50 kg can be lifted by their frame. Use the ring bolts provided for suspension on heavier louvres. Do not walk on the blades and never use them as foothold. Any damage e.g. deformed blades, dents, impacts, frame
distortion etc. may result in inadequate water drainage and undesirable noise. Therefore, report any damage im-mediately to the supplier or the manufacturer. They will then be able to assess whether there is any impaired func-tionality and possible risks.
6 Transport / handling