Adiabatic Cooling Systems
INSTALLATION, OPERATION AND INSTALLATION, OPERATION AND INSTALLATION, OPERATION AND INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONSMAINTENANCE INSTRUCTIONSMAINTENANCE INSTRUCTIONSMAINTENANCE INSTRUCTIONS
1
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
İÇİNDEKİLER
1. ABOUT THIS MANUAL/ GENERAL .............................................................................................. 3
1.1 Examining the operating manual .......................................................................................................... 3
1.2 Responsibilities ...................................................................................................................................... 3
1.2.1 Manufacturer’s Responsibilities ..................................................................................................... 3
1.2.2 Contractor’s Responsibilities (Installation, Commissioning) .......................................................... 4
1.2.3 Operator’s or Owner’s Responsibilities (Operation and Maintenance) ......................................... 4
1.3 Warranty ................................................................................................................................................ 5
2. SAFETY REGULATIONS .............................................................................................................. 6
2.1 Symbols and warning signs.................................................................................................................... 6
2.2 Personal protection ............................................................................................................................... 7
2.2.1 Personal protection signs ............................................................................................................... 7
2.2.2 Warning signs ................................................................................................................................. 8
2.3 Warnings................................................................................................................................................ 8
2.4 Improper Use ......................................................................................................................................... 9
2.4.1 Hazardous rotating machinery ....................................................................................................... 9
2.4.2 Hazardous voltage .......................................................................................................................... 9
2.4.3 Hazardous thermal ....................................................................................................................... 10
2.5 Environmental protection ................................................................................................................... 10
3. SPRAY SYSTEM DEFINITION ..................................................................................................... 10
3.1 Ecomesh water spray system .............................................................................................................. 10
3.2 Direct Adiabatic Water Spray System.................................................................................................. 13
3.3 Adiabatic Cooling Pad System ............................................................................................................. 14
3.3.1. Recirculated Adiabatic Cooling Pad System .......................................................................... 15
3.3.2. Uncirculated Adiabatic Cooling Pad System .......................................................................... 15
4. TRANSPORT AND STORAGE ................................................................................................... 16
4.1 Check for completeness and transport damage ................................................................................. 16
4.2 Transport ............................................................................................................................................. 16
5. INSTALLATION ....................................................................................................................... 17
5.1 Location ............................................................................................................................................... 17
5.2 Requirements at the set up point ....................................................................................................... 18
5.2.1 Horizontal types set up side by side ............................................................................................. 18
5.2.2 Vertical types set up next to wall ................................................................................................. 18
5.2.3 Vertical types set up in pit-hallow ................................................................................................ 19
5.2.4Horizontal types set up in pit-hallow ............................................................................................ 20
2
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
5.2.5Horizontal types set up next to wall .............................................................................................. 21
6. COMPONENTS OF ADIABATIC COOLING SYSTEM ..................................................................... 22
6.1 Water Spraying System ....................................................................................................................... 22
6.1.1 Fitting group ................................................................................................................................. 23
6.1.2 Nozzles .......................................................................................................................................... 23
6.1.3 Water spraying pipes .................................................................................................................... 25
6.2 Meshes ................................................................................................................................................ 25
6.3 Cooling Pad .......................................................................................................................................... 26
6.4 Fittings, Tighten elements and system installation ............................................................................. 26
6.4.1 Installation for vertical and horizontal type units ........................................................................ 27
6.4.2 Installation for V type units .......................................................................................................... 29
6.4 Controller and Electric connection ...................................................................................................... 41
6.4.1 Direct adiabatic water spray system controller ........................................................................... 41
6.4.2 Ecomesh spray system controller ................................................................................................. 41
6.4.3 Controller Working Principle and Definition ................................................................................ 42
6.4.4 Electric connection system ........................................................................................................... 43
6.5.5 Adiabatic cooling pad system controller ...................................................................................... 45
7. OPERATION ........................................................................................................................ 45
7.1 Initial commissioning ........................................................................................................................... 47
7.2 Regular commissioning........................................................................................................................ 47
7.2.1 Spraying system water characteristics ......................................................................................... 47
7.3 Shutting down ..................................................................................................................................... 48
8. MAINTENANCE ....................................................................................................................... 48
8.1 Maintenance intervals ......................................................................................................................... 48
8.3 Periodical Controls (Once a year) ........................................................................................................ 49
8.4 Cleaning ............................................................................................................................................... 49
9. TROUBLESHOOTING .............................................................................................................. 50
3
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
1. ABOUT THIS MANUAL/ GENERAL
This document specifies the instructions for installation, operating and maintenance of the
products which have water spry system (FDH, FDV, FDW, FCH, FCV, FCW, NCH and NCV
models) manufactured by FRITERM A.Ş., Turkey.
The instructions below must be followed strictly for the labor health and safety reasons during
installation and maintenance of products.
Upon receipt, the product should be visually inspected, and in case of any damage or fault, the
supplier must be notified within 7 days.
The manufacturer will not accept any responsibility in these situations;
• Damages caused by persons,
• Damages product due to the disregarding of the recommendations indicated in this handbook.
1.1 Examining the operating manual
To follow the instructions defined in this document is a prerequisite for safety of the staff and for
the products to be operated in a fault-free and safe manner.
• The operating manual must always be available. In case of absence of this manual another
copy could be obtained from the manufacturers’ web page. It should be printed out and kept
in an accessible place to everyone whoever should carry out any work regarding the product.
(http://www.friterm.com/tr-TR/catalogue/4 )
• All persons who are responsible for the transport, assembly, initial commissioning, operating,
maintenance or repair of the component must be acquainted with the operating manual. The
operator should accept in written form that they are acquainted with the operating manual.
• Whenever you have difficulty in understanding and/or comprehend and description or
definition given/expressed in this manual, please immediately ask for help from an expert
or from then manufacturer. It is of great importance to understand this manual completely and
correctly for the sake of labor health and safety.
1.2 Responsibilities
1.2.1 Manufacturer’s Responsibilities
• The manufacturer is strictly responsible for supplying a manual accompanying the product
which comprises the necessary and enough detailed information regarding the
installation/mounting and operation of the product. Besides, the product is expected to fulfill
the requirements and satisfy with the anticipated functioning.
• The construction of the product should comply with the presumed operational conditions. The
product is expected to be robust enough and resistive against all the mechanical, thermal
4
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
and chemical challenges. The material used to produce should be compatible with the fluid
and the mixture of fluids used as heat transfer media.
• All the materials and components used in constructing the product should be resistive
against all the stress and pressure that the product will be subjected to.
1.2.2 Contractor’s Responsibilities (Installation, Commissioning)
• Should follow all the instructions and provide all the conditions stated in this manual.
• All the documentation accompanying the product is complementary to this manual. The safety
instructions and all other information stated in this manual should be considered.
• The national regulations regarding the protection of environment and labor safety should be
strictly followed besides the instructions for safe and correct operation.
• In case of any problem encountered during the installation, FRITERM A.Ş. should be
informed and asked for technical assistance if necessary.
• Emergency instructions and the required infrastructure should be prepared and ready for use
in any case.
• The regular maintenance/servicing periods and instructions should be determined and
defined.
• The additive in order to prevent the freezing of the operating fluid should be feed as requires
and as much as required.
• If storage of the product for a long period is needed, a clean, non-hazardous and low humidity
environment is recommended.
• The fans of the products that are stored horizontally are recommended to be run for 4-5 hours
a week. In case of difficulty of running the fans, then they should be covered and protected
from rain and excess humidity.
• In case of storing vertically, it is not recommended to store more than 1 month.
1.2.3 Operator’s or Owner’s Responsibilities (Operation and Maintenance)
• The director is the responsible person who employs the adequate staff for servicing
operating and monitoring the system.
• All requirements and instructions in this operating manual must be complied with.
• The documentation of purchased products is a constituent part of this operating manual. All
safety information in this operating manual and all other information must be observed.
• All relevant regulations concerning accident prevention and environmental protection must be
complied as well as the confirmed technical regulations for safe and proper working.
• Personal ineligibility. All the work should be conducted by authorized and trained personnel.
• Any defect/damage/malfunction caused by disregarding the instructions given in this manual
is the responsibility of the operator.
5
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
• Any defect/damage/malfunction caused by the misuse of the product is the responsibility of
the operator.
• The product should not be put in operation without the completion of the installation and
commissioning.
• The personnel who is responsible for the operation/servicing/maintenance of the product
should be provided with all the necessary documentation including this manual.
1.3 Warranty
• The manufacturer warrants that the equipment delivered to the client shows no defects
caused by failure of design, material, manufacturing and/or workmanship within the warranty
period.
• The client must notify in written form within 10 days from the receipt of the goods, any
perceptible defects including transport damages. For hidden defects, he must notify and
explain in details the defect in written form within 10 days from observation time.
• Unless otherwise agreed, the warranty period shall be 24 months starting from the date of
delivery.
• The warranty does not cover defects in the product’s operation stemming from a fault in
materials or parts provided by the client, nor shall it cover an installation that has not been
assembled according to the manufacturer’s instructions and according to professional
practice. The products or parts that the costs are not paid to the producer are out of
manufacturer’s warranty.
• The warranty shall not cover equipment and/or its accessories if they have been modified by
the client without manufacturer’s written consent.
• The warranty clause can only be invoked by the client if the equipment is used normally and
in conformity with its purpose and manufacturer’s instructions.
• The manufacturer’s liability hereunder shall be limited to repair, modify or replace the parts or
equipment that shows defect within the limitation of the items under this article.
• The warranty period of the repaired or modified or replaced parts or equipment shall in no
way extend the warranty period of the original ones.
• The works resulting from the warranty conditions shall be carried out in the manufacturer’s
workshop after the client has sent the defective equipment or parts for repair or replacement.
• The manufacturer’s responsibility is strictly limited to the obligations as stipulated herein and it
is expressly agreed that he shall not be found to make any other indemnity. In particular, he
shall in no case be liable to compensate loss caused directly or indirectly by a defect in the
equipment delivered.
6
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
• The product should be installed and commissioned in accordance with the
national/international regulations and rules.
• For the fans having thermal protection, the related wiring should be definitely done and it is
considered as contractor’s and/or owners’ responsibility. Any defect caused by misconnection
of the thermal protection wiring in accordance to the circuit diagrams given in this manual
would be out of manufacturer’s warranty.
• The power supply which the product is supplies should not deviate 10% from the values given
on the label.
2. SAFETY REGULATIONS
2.1 Symbols and warning signs
The following terms and/or symbols are used in the operating manual for particularly important
information.
Safety messages and symbols are quoted at the relevant positions in the operating manual if
there is danger such as death, personal injury and environmental damage. These safety
warnings must be strictly adhered to.
Indicates a hazardous situation which, if not avoided, may
result in death or serious injury
Indicates a hazardous situation which, if not avoided, may result
in serious injury.
Indicates a hazardous situation which, if not avoided, may result
in moderate or minor injury.
Additional notes, information and tips.
Rev. Tarihi:20.09.2017
IN CASE OF DANGER
• Switch off the power
• Switch off the main
• Please ask assistance from an authorized
• Please do not try to resolve any problem by trial and error.
2.2 Personal protection
While working on and standing by the product, protective clothing must be worn.
• Safety shoes
• Safety helmet
• Protective gloves for fitting and rep
• Chemical-resistant clothing and protective gloves for cleaning work, especially when
handling solvents
• Safety goggles for cleaning work, especially while handling solvents or using compressed
air for cleaning
• Hearing protection
2.2.1 Personal protection signs
Head Protection
Foot Protection
Rev.No:1 Dok. No: KLV.008.ENG
IN CASE OF DANGER!
Please ask assistance from an authorized technician or expert.
Please do not try to resolve any problem by trial and error.
Personal protection
While working on and standing by the product, protective clothing must be worn.
Protective gloves for fitting and repair work
resistant clothing and protective gloves for cleaning work, especially when
Safety goggles for cleaning work, especially while handling solvents or using compressed
Personal protection signs
Head Protection Eye Protection
Foot Protection High Visibility Clothing
7
Rev.No:1 Dok. No: KLV.008.ENG
While working on and standing by the product, protective clothing must be worn.
resistant clothing and protective gloves for cleaning work, especially when
Safety goggles for cleaning work, especially while handling solvents or using compressed
Eye Protection
Clothing
Rev. Tarihi:20.09.2017
Protective Clothing
Respiratory Protection
2.2.2 Warning signs
No SmokingFlammable
High Voltage
Hand Injuries
Fire Risk
2.3 Warnings
• In an unexpected situation use the emergency stop button which is set up on an easily
accessible place.
Rev.No:1 Dok. No: KLV.008.ENG
Protective Clothing Hand Protection
Respiratory Protection
No SmokingFlammable
High Voltage Hot Surfaces
Hand Injuries Poisoning Danger
Fire Risk Frostbite Hazard
unexpected situation use the emergency stop button which is set up on an easily
8
Rev.No:1 Dok. No: KLV.008.ENG
Hot Surfaces
Poisoning Danger
Frostbite Hazard
unexpected situation use the emergency stop button which is set up on an easily
Rev. Tarihi:20.09.2017
• Do not exceed maximum operating pressure given on the unit’s type plate.
• Unless the advised safety devices available or fully active the unit must not be
• Set up the unit with extreme cleanliness.
• The unit must not be operated if it is damaged. FR
damages.
• The unit must be installed, operated and maintained by authorized/qualified personnel
only.
• No modification is allowed on the product without written permission from the
manufacturer.
• Operational conditions are limited within the specified range by the manufacturer. In case
of need to operate the product out of the range, a confirmation should be asked from
FRITERM A.Ş.
2.4 Improper Use
Danger of injuries in improper using;
2.4.1 Hazardous rotating machinery
Danger of cutting hands and fingers. Lids should be unscrewed by an authorized
technician.
Use hand protection.
2.4.2 Hazardous voltage
Electrical voltage can cause serious injuries or death. Do not contact with
voltage direct or indirect. Do not forget to power off the unit before you begin
maintenance work.
Rev.No:1 Dok. No: KLV.008.ENG
Do not exceed maximum operating pressure given on the unit’s type plate.
Unless the advised safety devices available or fully active the unit must not be
Set up the unit with extreme cleanliness.
The unit must not be operated if it is damaged. FRİTERM A.Ş. must be informed about all
The unit must be installed, operated and maintained by authorized/qualified personnel
is allowed on the product without written permission from the
Operational conditions are limited within the specified range by the manufacturer. In case
of need to operate the product out of the range, a confirmation should be asked from
Danger of injuries in improper using;
Hazardous rotating machinery
Danger of cutting hands and fingers. Lids should be unscrewed by an authorized
Use hand protection.
Electrical voltage can cause serious injuries or death. Do not contact with
voltage direct or indirect. Do not forget to power off the unit before you begin
maintenance work.
9
Rev.No:1 Dok. No: KLV.008.ENG
Do not exceed maximum operating pressure given on the unit’s type plate.
Unless the advised safety devices available or fully active the unit must not be operated.
. must be informed about all
The unit must be installed, operated and maintained by authorized/qualified personnel
is allowed on the product without written permission from the
Operational conditions are limited within the specified range by the manufacturer. In case
of need to operate the product out of the range, a confirmation should be asked from
Danger of cutting hands and fingers. Lids should be unscrewed by an authorized
Electrical voltage can cause serious injuries or death. Do not contact with
voltage direct or indirect. Do not forget to power off the unit before you begin
Rev. Tarihi:20.09.2017
2.4.3 Hazardous thermal
Danger of burns and frostbites.
Adiabatic cooling systems are design to work at summer season when the
temperature is high.
the system is full drained.
The danger of frostbite can occur if there is insufficient frost
the unit cannot be drained completely, frostbite hazard occurs after draining.
2.5 Environmental protection
While handling the product, it has to be ensured that materials which can endanger the
environment are disposed of properly. Service materials must not be allowed to enter the
sewerage system and the ground water system.
All relevant national regulations
safe and proper working must be complied.
3. SPRAY SYSTEM DEFINITION
3 types of adiabatic cooling systems
direct,ecomesh and cool pad adiabatic cooling systems
3.1 Ecomeshwater spray system
Ecomesh Spray System concept is based on intermittently and efficiently evaporating water
on a large mesh area in front of the heat rejection surface of
Rev.No:1 Dok. No: KLV.008.ENG
Danger of burns and frostbites.
Adiabatic cooling systems are design to work at summer season when the
temperature is high. When the temperature is low at winter season; be sure that
the system is full drained.
The danger of frostbite can occur if there is insufficient frost
the unit cannot be drained completely, frostbite hazard occurs after draining.
Environmental protection
While handling the product, it has to be ensured that materials which can endanger the
environment are disposed of properly. Service materials must not be allowed to enter the
sewerage system and the ground water system.
All relevant national regulations concerning environmental protection and the technical issues for
safe and proper working must be complied.
AY SYSTEM DEFINITION
3 types of adiabatic cooling systems can be applied to dry coolers and condenser of
adiabatic cooling systems.
water spray system
Ecomesh Spray System concept is based on intermittently and efficiently evaporating water
on a large mesh area in front of the heat rejection surface of Condensers
10
Rev.No:1 Dok. No: KLV.008.ENG
Adiabatic cooling systems are design to work at summer season when the
When the temperature is low at winter season; be sure that
The danger of frostbite can occur if there is insufficient frost protection. Also if
the unit cannot be drained completely, frostbite hazard occurs after draining.
While handling the product, it has to be ensured that materials which can endanger the
environment are disposed of properly. Service materials must not be allowed to enter the
concerning environmental protection and the technical issues for
dry coolers and condenser of Friterm A.Ş;
Ecomesh Spray System concept is based on intermittently and efficiently evaporating water
Condensers and Dry Coolers.
11
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Water spray provides an adiabatic cooling effect of till 25 °C for the incoming air stream and
it can be initiated via an ambient sensor or alternatively by external control override. As soon
as settings exceed, a pre-set level controller initiates water spray in order to make air
temperature lower during high ambient periods.
Advantages of Ecomesh Water Spray System:
• Running Cost: Lower condensing temperature provides reliable operation and lower
annual electricity running costs.
• Reduced Water Consumption:Water is used whenever it is required at significantly
reduced quantities.
• Flexible System:Sectional panel and coil clip design suits with any brand and model of
mini-splits, air cooled chillers, rooftop units, air cooled condensers and dry coolers on the
market.
• Lower Maintenance Cost:Reduced condenser pressure leads to reduced discharge
temperature which extends the compressor reliability and life.
• Quick Response:Large mesh surface area provides efficient adiabatic cooling surface
with minimum air flow reduction, hence, water evaporates very rapidly to cool the
incoming air.
• Eliminates Health Risks:It uses water directly without any water reservoir, hence, the
health risks associated with a still water reservoir are completely eliminated.
• Green Solution: Reduced energy consumption, hence, less indirect CO2 emission.
• Continuity of heat transfer efficiency:Since the water is not sprayed directly to the heat
exchanger fin surface, it is sprayed on the ecomeshsurface; no lime layer is formed on
the fins. Thus, the reduction of the thermal transfer efficiency is prevented.
Mois
ture
Co
nte
nt
Temperature
12
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Picture 1- Ecomesh water spray system at vertical type condensers
Picture 2- Ecomesh water spray system at V type condensers
Picture 3-Ecomesh water spray system at horizontal type condensers
Picture 4- Ecomesh water spray system at V type dry coolers
Picture 5-Ecomesh water spray system at horizontal type dry coolers
13
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
3.2 Direct Adiabatic Water Spray System
Directadiabatic water spray system comprises a series of specialized water nozzles fitted
intermittently. The nozzles are designed to pulverize the water and provide a very fine mist of
atomized water droplets which are readily absorbed by the high temperature ambient air
approaching the coil.
It is necessary that the water used in this system must undergo for a strict water treatment regime
to reduce the risk of corrosion and prevent dirty water in the water circuit. Moreover the hardness
of the water should be taken and pass from high efficiency filtration system.Otherwise, the lime
and residue that accumulates on the heat exchanger fins will eventually reduce product capacity
and shorten its lifetime.
Epoxy coated fins can be used for dry coolers with spraying systems as an additional protection
due to the abrasive effects. The epoxy coating has a very high resistance to salt and acid in the
environment.It is preferred that the unit is made of epoxy-powder coated galvanized steel and
stainless steel in advanced corrosive environments.It is important to take these precautions to
ensure the dry coolers are long-lived, although they are much less exposed to the harmful effects
of water than the water towers.
The amount of water to be consumed in order to saturate the intake air, varies depending on the
sprayer used and the spraying pressure.The choice depends on the relative humidity of the
ambient air; It should be ensured that water is sprayed in sufficient quantity to bring the relative
humidity as close to 100% as possible.For this reason, some more water is sprayed from the
completely evaporating amount and the increased water remains as the liquid in the environment.
This measure also provides safety against the loss that can occur over time in the performance of
the spray system.
Picture 6-Horizontal type condenser with direct spraying system
14
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Picture 7-V type dry cooler with direct spraying system
3.3Adiabatic Cooling Pad System
In adiabatic cooling pad systems, coolpads are placed in special sheet metal assemblies which
are mounted in front of fin block. With the aid of the pump, water wets the pads from the upper
part of the pad system. The outside air, which is dry and hot, is pre-cooled by passing it through
wet cooling pads.The temperature of the air that contact with the wet cooling pads is
approximated to the wet thermometer temperature.
The water does not contact directly with the fins. Thusfins lifetime is longer than the direct
spraying systems.Also pads prevent contamination of fins.
Since the microorganisms, minerals and similar parts do not mix into the air during the
evaporation phase of water, the working principle is completely healthy.
The system ensures that product efficiency can be increased with minimum water consumption.
15
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
System can be built in two ways as recirculated and uncirculated.
3.3.1. Recirculated Adiabatic Cooling Pad System
In recirculated adiabatic systems, water that flow over the pads, collected at the drain pan. When
it reaches a certain level, it is pumped back to the upper part water spraying line by the circulation
pump.
3.3.2. Uncirculated Adiabatic Cooling Pad System
In uncirculated systems, the amount of water supplied through the cooling pads is provided by
the appropriate automation system, depending on the external air relative humidity.
A small amount of water collected in the pan under the pads is drained by a drainage line.
16
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Picture 8- V Type dry cooler with adiabatic cool pad system
4. TRANSPORT AND STORAGE
4.1 Check for completeness and transport damage
• Attention! May cause severe injuries or unrecoverable damages in case of uncontrolled
fall down.
• Instructions on lift and transportation should be strictly followed.
• Check if there is any damage on product or package. Immediately after receipt, the
delivery must be inspected for possible transport damage. Any damage must be reported
immediately to the shipping company. If it is to be expected that the transport damage
may affect proper operation, then the product must not be commissioned.
• Upon receipt, the product should be visually inspected, and in case of any damage or
shortage, the supplier should be notified within 7 days.
4.2 Transport
The product may only be lifted and moved by persons who:
1. Are authorised to operate crane systems,
2. Are authorised to drive motorised handling product
3. Also know the transport and lifting instructions according to the operating manual and the
assembly drawing.
17
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Suitable transport equipment must be used.
5. INSTALLATION
The system installer is responsible for the proper installation according to standards and
guidelines (DIN EN 292 / 294) which contains installation and security guidelines.
Before installing, it must be ensured that the technical specifications of the product are in
accordance with the desired working conditions.
5.1 Location
• The spraying system is designed only for permanent installation. It should be fixed to a
stable base.
• In recirculated or uncirculatedadiabatic cooling pad systems, excess water accumulating
in the drain pan and must be properly well trained. Product must be installed in such a
way that will not obstruct the drainage.
The working area should be well ventilated and should not be contained any hazardous
substances or explosives.
• Air motion should not be adversely affected by obstructions and inlet air should not be
undesirably heated or cooled by some other product.
• All the blind bolts and/or flanges should be removed right before the installation.
• The site where the installation process is being carried out should be provided as clean as
possible and low humidity.
18
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
5.2 Requirements at the set up point
5.2.1 Horizontal types set up side by side
5.2.2 Vertical types set up next to wall
Smin ≥ H
19
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
5.2.3 Vertical types set up in pit-hallow
20
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
5.2.4Horizontal types set up in pit-hallow
� ≥ 0,5 ∗�
� = 450 − 600 mm
21
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
5.2.5Horizontal types set up next to wall
To avoid bypassing of the blowing air due to the side wall, a blocking accessory should be used.
Also a dry-cooler half-width lifting case or higher feet should be used to facilitate the suction from
down side. (700-1200 mm)
K ≥ W/2
22
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
6. COMPONENTS OF ADIABATIC COOLING SYSTEM
Adiabatic cooling systems comprises of the following equipment;
1) Water spraying system
2) Meshes (for ecomesh systems)
3)Cool pads (for cool pad systems)
4) Fittings, tighten elements and system installation
5)Controller and electric connection
Quick change type plastic nozzles connected in series and parallel arrangement in order to
provide uniform coverage area for an effective evaporation process.
6.1Water Spraying System
Picture 9- Water spraying system
Water spray system comprises of the following equipment.
1) Fitting group
2) Nozzle
3) Water spraying pipes
Water spraying pipe
Water spraying pipe
Nozzle Nozzle
Nozzle Nozzle
Clamp Clamp Clamp
Clamp Clamp Clamp
Fitting Group
23
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
6.1.1 Fitting group
The fitting group is provided to the customer as a whole fitted together. It comprises nipple,
solenoid valve, hydrometer, water strainer and globe valve.
At the entrance of the installation there is a water filter. There is also a wire filter inside the nozzle
to avoid dirt. Filters should be checked at periodic intervals.
6.1.2 Nozzles
Nozzles are sent to the customer with the utilities. Nozzle connections are made to the holes on
the utility.
While the pulverizes are working there should not be any leakage except from the nozzle if there
is a leakage, the connections should be checked and leakage must be prevented.
Nozzles are designed to operate with very low pressure and they can operate with normal city
mains water pressures 1.5 - 3 bar and above.
Water Filter
Hydrometer Selenoid Valve
Spraying line Globe valve
Water inlet line
24
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Nozzles should be mounted approximately the angle of 45° as shown above. The nozzles should
be placed in a way that the water will be sprayed widely and equally to the meshes.
For direct spraying systems the distance between nozzles and fins should be 400- 600 mm.
Picture 10- Nozzles mounting angle
25
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
6.1.3 Water spraying pipes
Water spraying pipes are sent to the customer with the unit. It is mounted to the mounting holes
on the product with the help of the clamps.
Extra loading on the piping system may cause leakage on the piping.
6.2Meshes
Nonmetallic mesh provides an effective coverage area for an efficient evaporation surface with
minimal air pressure drop. Meshes are fixed in front of the heat rejection surface via spacer bars
and/or fixing brackets to suit the unit configuration. Various size sectional mesh panels are either
joined together to form a full mesh area or alternatively flexible mesh roll cut to fit to a required
size in front of the heat rejection surface.
26
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
The dust on the meshes should be cleaned with pressurized air or water at least once in a week.
6.3 Cooling Pad
Cellulosic Media Pad
It is a cellulosic paper impregnated with chemicals that provide easy wettability and durability.
The wavy and cross-channel structure expands the surface area, facilitating air to water contact
and minimizing air resistance.
The pad materials are flammable.
6.4Fittings, Tighten elements and system installation
Installation and electrical connections must only be carried out by qualified personnel.
During installation, the product should not be connected to an electrical source.
27
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
6.4.1Installation for vertical and horizontal type units
The installation pipes on which the nozzles are mounted, are mounted with the clamps to the
plate.
Once the installation pipes have been installed in place, the clamping assembly is fastened
with M8 bolts to the nut rivets previously punched.
28
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Then the fitting group is installed at the end of the installation pipe.
The mesh is attached to the special rails on the product with the clips sent alongside the
product. (For ecomesh installation)
29
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
After all the meshes are mounted, the tensioning devices are set and fixed. (For network
connection)
6.4.2Installation for V type units
6.4.2.1 Installation of ecomesh system
First, the mesh tensioning assembly is connected to the mounting holes on the unit with
M16 studs. Clamps are mounted on the net tensioning device and on the sheet metal at
the collector side.
30
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
The straight pipe on which the spraying nozzles are located arefitted with the clamps
connected to the net tensioning device.
After the straight pipe installation is completed on both sides, the U pipe connecting both
pipes is installed.
31
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
The fitting group installed to the end of the U pipe.
The mesh is attached to the special rails on the product with the clips sent alongside the
product.
32
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
After all the meshes are mounted, the tensioning devices are set and fixed. (For network
connection)
6.4.2.2 Installation of direct spraying system
First of all, the installation support sheet is mounted on the mirrors shown in the technical
drawing. Then we will use it when connecting to the installation, clamps are mounted by
adding the studs prepared to the back.
33
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Then the flat installation pipes are attached to the clamps and mounted on the product.
After the installation of the flat pipes, the installation of the U pipe connecting these pipes
is carried out.
34
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Finally, fitting group is installed at the end of the U pipe.
Rev. Tarihi:20.09.2017
6.4.2.3 Adiabatic cooling pad system installation
In the standard assembly of the unit, firstly, the side cover plates which are prepared with
the necessary fasteners
Additional shhet parts are mounted underneath the side cover sheets which overlap with
the middle plates.
Rev.No:1 Dok. No: KLV.008.ENG
cooling pad system installation
In the standard assembly of the unit, firstly, the side cover plates which are prepared with
fasteners are mounted.
Additional shhet parts are mounted underneath the side cover sheets which overlap with
35
Rev.No:1 Dok. No: KLV.008.ENG
In the standard assembly of the unit, firstly, the side cover plates which are prepared with
Additional shhet parts are mounted underneath the side cover sheets which overlap with
Rev. Tarihi:20.09.2017
Then the bottom cover plates are mounted.
Pre-assembled cooling pad modules are mounted on the nuts on the side cover plates.
Rev.No:1 Dok. No: KLV.008.ENG
Then the bottom cover plates are mounted.
assembled cooling pad modules are mounted on the nuts on the side cover plates.
36
Rev.No:1 Dok. No: KLV.008.ENG
assembled cooling pad modules are mounted on the nuts on the side cover plates.
Rev. Tarihi:20.09.2017
After the assembly of the sheet metals
pads are pushed in from the outside as shown below, until they reach the upright position.
When the pads are in the upright position
Make sure that the pads are correctly positioned and there are no visible gaps between
them.
When all the pads have been settled, the pad retaining parts are
retaining screws.
Rev.No:1 Dok. No: KLV.008.ENG
the assembly of the sheet metals is completed, the cooling pads can be placed. The
pushed in from the outside as shown below, until they reach the upright position.
When the pads are in the upright position, they will fit well on the side plates.
Make sure that the pads are correctly positioned and there are no visible gaps between
When all the pads have been settled, the pad retaining parts are mounted
37
Rev.No:1 Dok. No: KLV.008.ENG
is completed, the cooling pads can be placed. The
pushed in from the outside as shown below, until they reach the upright position.
fit well on the side plates.
Make sure that the pads are correctly positioned and there are no visible gaps between
mounted with the help of
Rev. Tarihi:20.09.2017
After the assembly of the pad modules is completed,
the pump system is assembled. The coarse partic
pump is installed.
Rev.No:1 Dok. No: KLV.008.ENG
After the assembly of the pad modules is completed, is the system is recirculated system,
the pump system is assembled. The coarse particle filter must be installed before the
38
Rev.No:1 Dok. No: KLV.008.ENG
is the system is recirculated system,
le filter must be installed before the
Rev. Tarihi:20.09.2017
After the pump installation is done , the
modules, is mounted between two drainage outlets.
Pump and cool pad water supply will be done as
required for this installation.)
Rev.No:1 Dok. No: KLV.008.ENG
After the pump installation is done , the PVC pipe which connects the two cooling pad
is mounted between two drainage outlets.
Pump and cool pad water supply will be done as follows. (PVC pipe welding machine is
required for this installation.)
39
Rev.No:1 Dok. No: KLV.008.ENG
the two cooling pad
follows. (PVC pipe welding machine is
Rev. Tarihi:20.09.2017
The system feed is made from the nipple input shown below.
Rev.No:1 Dok. No: KLV.008.ENG
The system feed is made from the nipple input shown below.
40
Rev.No:1 Dok. No: KLV.008.ENG
41
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
6.4Controller and Electric connection
6.4.1Direct adiabatic water spray system controller
The system is controlled by a thermostat. The stepped thermostat on the product controls the cut-
in and cut-out of the fans and it commands in an integrated manner to the turn on/off of the
solenoid valve. If fan control is not to be done, only the solenoid valve is switched on and off with
a single-stage thermostat.
6.4.2Ecomeshspray system controller
A custom-made intelligent PLC based controller records the ambient conditions and at a pre-set
value, which is adjustable by the operator, initiates inline solenoid valve(s).
Water is sprayed intermittently to wet the meshes. The spray rate and duration are adjusted by
the controller to suit the ambient conditions, hence, minimal water consumption. Water usage is
based on total waste principle, hence, no health risk.
Ecomesh controller is provided with internal override terminals for a volt-free input which
overrides the temperature set limit and initiates intermittent spray as soon as this terminal is
linked. This facility can be used to provide head pressure or manual remote override flexibility.
42
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Picture 11- Ecomesh Controller
6.4.3 Controller Working Principle and Definition
43
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Picture 12- Ecomesh Controller Working Principle and Definition
6.4.4Electric connection system
Ecomesh Temperature AND Time Controller Block Diagram
The operator panel consists of two Printed Circuit Boards (PCB) which house the power supply,
sensor input conditioning circuitry, microcontroller, 7-segment Light Emitting diode (LED) display
for temperature and timer indication, status indicating LED, control and setting push buttons, and
output circuitry. The PCB is mounted inside a plastic enclosure. Both the display and the push
buttons are protected by the transparent cover. All the connections to the controller are via plug-
in screw terminals.
44
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Power supply
The control panel requires 110 or 240Vac 5VA max. 50/60Hz supply. Please specify the supply
voltage when order.
Sensor input
A platinum resistance thermometer PT100 temperature sensor is supplied as standard.
External override input
An optional volt-free contact can be connected to the external override input to force the
controller output to maximum when the contact is closed.
Control output
Opto-triac outputs are used for the control output. The ratings are 240Vac 1A max and 110Vac
2.1 A.
User interface
The user interface comprises of 3 digits 7-segment green LED display, 1 status indicating LED
and 3 push buttons.
The 7-segment display is used to indicate measured temperature, low set point temperature, high
set point temperature, and 3 sets of ON time setting and OFF time setting.
One red LED is used to show the output status of the controller.
One push button is used to scroll the parameter display. The two adjustment push buttons "UP"
and "DOWN" enable the temperature and time setting to be incremented and decremented.
Please note the display will revert to showing measured temperature after 1 minute of inactivity
on the push buttons.
6.4.4.1 Electrical installation
The Ecomesh controller can be wall mounted using the mounting kit provided. Please see
dimensional drawing for fixing holes arrangement.
All the electrical connections are via plug-in screw terminals. There are 4 sets of connections:
The sensor input (PRT100 sensor) is connected to a 2 way connector IN+ and IN- of the RT input
on the PCB. The sensor is not polarity sensitive.
The optional external override input (volt-free contact) is connected to a 2 way connector OVR+
and OVR- on the PCB. The external override input is not polarity sensitive.
The controller output is connected to a 2 way connector LINE and LOAD of the OUTPUT 1 on the
PCB. Please note from release 2.1 onwards, the LINE and LOAD should connect directly to the
external solenoid valve.
The mains supply is connected to a 2 way connector L and N of the mains input on the PCB.
Controller’s electrical connections can be check with the connection diagram below;
45
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Picture 13- Electric connection diagram
6.5.5 Adiabatic cooling pad system controller
The control device (thermostat) adjusted according to the applied system goes into operation with
the operation of the domestic line pump if the ambient conditions rise above the set values.
Water is conveyed from the top through the cooling pads, with the aid of the pump. Part of the
water flowing through the pads is collected in the pan, the reduced water is removed from the
network by means of a ballcock.
45
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
7. OPERATION
All the parameters in the Ecomesh controller can be accessed by pressing the scroll button. Apart from the measured temperature, all the
parameters can be set within their limits using the UP and DOWN button.The following are the list of parameters:
ECOMESH CONTROLLER SETTING DESCRIPTION
Menu Description
Controller
Minimum
Limit
Controller
Maximum
Limit
Initial factory setup
Units Moderate
Climate *
Hot
Climate *
Pressure
Control
*
t Ambient Dry Bulb Reading Sensor Sensor Sensor Sensor Sensor ºC
L Minimum (Set) Temperature 10 60 20 25 20 ºC
H Maximum (Set) Temperature 10 60 35 50 40 ºC
1 T1 - Spray Duration (1-99 Second) at L 1 99 5 10 15 Second
2 T2 - Spray Frequency y(1-99x10 Seconds) at L 0,5 99 1 0,5 0,5 Minute
3 T3 - Spray Duration (1-99 Second) at H 1 99 15 30 30 Second
4 T4 - Spray Frequency(1-99x10 Seconds) at H 0,5 99 45 30 18 Second
5 T5 - Flash Cycle ON Time (Sec) (Duration) 0 99 0 0 0 Second
6 T6 - Flash Cycle OFF Time (h) (Frequency) 0 99 0 0 0 Hour
* The initial setup values can be changed to its desire values according to the device installation environment by the operator.
46
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Ecomesh water spray system controller can be operated in 3 different conditions.
1) "t" Ambient temperature is between L (Minimum temperature) and H (Maximum temperature)
2) "t" Ambient temperature is above H (Maximum temperature) and
3) Independent of temperature
The detailed information are given below table.
ECOMESH KONTROLLER WORKING CONDITIONS
1.Condition:
"t" Ambient temperature is between L (Minimum
temperature) and H (Maximum temperature)
2.Condition:
"t" Ambient temperature is above H (Maximum
temperature)
L < t < H t > H
1
Water spraying period in seconds when the ambient
temperature (t) is between lower limit (L) and upper limit
(H)
3 Water spraying period in seconds when the ambient
temperature (t) is above the upper limit (H)
2
Off period (Value x 60 seconds) between two spraying
when the ambient temperature (t) is between lower limit
(L) and upper limit (H)
4
Off period (Value x 60 seconds) between two spraying
when the ambient temperature (t) is above the upper limit
(H)
3.Condition:
Independent of temperature values
5 Water spraying period in seconds when the system is independent of temperature values
6 Off period (Value x 60 seconds) between two spraying when the system is independent of temperature values
Rev. Tarihi:20.09.2017
7.1 Initial commissioning
Before running the unit for the first time, the following facts should be checked.
1. Check the input/output electric connections. If the connection is not done in correct way,
the value of the temperature will be appeared incorrectly.
2. Make sure that the sensor is working correctly. If there is any failure in function, the
value of the temperature will be appeared incorrectly.
3. The current ampere of the solenoid valve should not be over the
4. The screws of the control apparatus must be fastened tightly.
After the spray system is installed properly, the water system connection should be done
to the fitting group. The water system must be operated by the qualified
In order for the system to function proficient
fundamental requirement for optimum performance.
7.2 Regular commissioning
Material damage due to freezing hazard may occur.
Adiabatic cooling systems are design to work at summer season when the
temperature is high. When the temperature is low at winter season; be sure
that the system is full drained.
7.2.1 Spraying system water
UNI 8884 "Characteristics and
suggests that evaporative humidifiers be supplied with fresh water (as indicated in directive
98/83/EC) having the following characteristics:
Rev.No:1 Dok. No: KLV.008.ENG
Initial commissioning
Before running the unit for the first time, the following facts should be checked.
1. Check the input/output electric connections. If the connection is not done in correct way,
temperature will be appeared incorrectly.
2. Make sure that the sensor is working correctly. If there is any failure in function, the
value of the temperature will be appeared incorrectly.
3. The current ampere of the solenoid valve should not be over the recommended values.
4. The screws of the control apparatus must be fastened tightly.
After the spray system is installed properly, the water system connection should be done
to the fitting group. The water system must be operated by the qualified
In order for the system to function proficiently, the complete wetting of the
fundamental requirement for optimum performance.
Regular commissioning
Material damage due to freezing hazard may occur.
Adiabatic cooling systems are design to work at summer season when the
temperature is high. When the temperature is low at winter season; be sure
that the system is full drained.
Spraying system water characteristics
Characteristics and treatment of water for cooling and humidification circuits” ”
suggests that evaporative humidifiers be supplied with fresh water (as indicated in directive
98/83/EC) having the following characteristics:
47
Rev.No:1 Dok. No: KLV.008.ENG
Before running the unit for the first time, the following facts should be checked.
1. Check the input/output electric connections. If the connection is not done in correct way,
2. Make sure that the sensor is working correctly. If there is any failure in function, the
recommended values.
After the spray system is installed properly, the water system connection should be done
to the fitting group. The water system must be operated by the qualified operator only.
ly, the complete wetting of the media pads is a
Adiabatic cooling systems are design to work at summer season when the
temperature is high. When the temperature is low at winter season; be sure
treatment of water for cooling and humidification circuits” ”
suggests that evaporative humidifiers be supplied with fresh water (as indicated in directive
48
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
Electrical conductivity
<100 µS/ cm
Total hardness 2< x< 5° fH (50 ppm
CaCO3)
pH 6.5<pH<8.5
Chloride content < 20 mg/l
Silica content < 5 mg/ l
Demineralized or osmos water is not required.
7.3 Shutting down
To close the water sprinkler system completely, the electrical connection must be cut off and
the fluid circulation pump in the system must be switched off.
8. MAINTENANCE
8.1 Maintenance intervals
1. Maintenance operation is to be performed by qualified personnel only.
2. Ecomesh should be cleaned regularly once in week.
3. The system pipes and fitting group must be controlled regularly in order not to be
blocked of the flow line.
4. The connection of the meshes and the fitting should be controlled in order to prevent
from loosening any connection elements.
5. The electric and the sensor connections should be checked regularly.
Follow the instructions in the 'Initial Operation' section to operate the appliance after
maintenance and repair.
49
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
8.3 Periodical Controls (Once a year)
• Check the fins and pipes for corrosion that will occur in case of water coming into
contact with the coil block in the spraying systems. If the pipes are worn, they can
cause leakage.
• In adiabatic cooling pad systems pads can clogged due to external contaminants and
cause pressure loss and this may reduce the efficiency. Checks must be done.
8.4 Cleaning
Ecomesh Cleaning
• Ecomesh should be cleaned once per week.
Cooling Pad Cleaning
• Where necessary, the pads should be cleaned with a soft bristle brush and low-
pressure water. Dirt, rust, smoke and hard cleaners should be avoided. Soft cleaners
compatible with pads materials should be used.
• Clean and flush distribution headers on a regular basis to prevent buildup of deposits or
microbiological growth.
The dust on the ecomesh or cooling pad surface must be cleaned with compressed air or
water at least once a week.
50
Rev. Tarihi:20.09.2017 Rev.No:1 Dok. No: KLV.008.ENG
9.TROUBLESHOOTING
Faults Possible Causes Remedy
Unit capacity
not achieved
Fans are not running properly Repair or change fans
Polluted coils Clean
Different brine working
pressure
Adjust brine pressurising values to
reference values
Heat exchanger is very dirty,
frosted, iced on the air side
Clean, defrost heat exchanger
Fan motor is
not working
Fan blade stuck Enable fan to rotate freely
Power supply cut off Fix power supply
Unusual noise Defective Fan bearing Replace bearing or fans
Vibration
Defective fan blades Modify or change fan blades
Fan fixtures loosened Tighten the fixtures
Working fluid
escaping
Unit working fluid-carrying
components leaking
Switch off working fluid feed and fans,
close leak