INSTALLATION MANUAL AND OPERATING INSTRUCTIONS ARGO AR SERIES CONTROLS AR822-II, AR861-2II, AR861-3II P/N 240005122, Rev. A [06/08] An ISO 9001-2000 Certified Company AR822-II AR861-2II AR861-3II ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 (Corporate Sales) 85 Middle Road Dunkirk, NY 14048 www.argocontrols.com

Transcript of INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will...

Page 1: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

INST

ALLA

TIO

N M

ANUA

L AN

D O

PERA

TIN

G IN

STRU

CTIO

NS

ARGO AR SERIES CONTROLSAR822-II, AR861-2II, AR861-3II

P/N 240005122, Rev. A [06/08]

An ISO 9001-2000 Certified Company

AR822-II

AR861-2II

AR861-3II

ARGO (Technical Support)2201 Dwyer AvenueUtica, NY 13501

(Corporate Sales)85 Middle RoadDunkirk, NY 14048www.argocontrols.com

Page 2: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone
Page 3: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

3

instAllAtiOn mAnuAlAnd OpeRAtinG instRuctiOns

Safety Symbols...............................................................................4 Introduction .....................................................................................5Mounting Instructions .....................................................................5Electrical Specifications & wiring ...................................................6AR822-II Single Zone Relay

AR822-II Control Features ........................................................6AR822-II Sequence Of Operation .............................................7AR822-II Control Board ............................................................7AR822-II wiring Schematic ......................................................8AR822-II Applications ...............................................................9AR822-II with Zone Valve Priority ..........................................10

AR861-2II & AR 861-3IIAR861-2II & AR 861-3II Control Features .............................11AR861-2II & AR 861-3II Sequence of Operation ....................11AR861-2II Control Board & Wiring Schematic ........................12AR861-3II Control Board & Wiring Schematic ........................13AR861-2II & AR 861-3II Applications ......................................14AR861-2II & AR 861-3II Expansion Control ............................18

AR Series with DPM-2 Outdoor Reset Control ............................19Replacement Parts .......................................................................20Technical Support .........................................................................20

RetAin tHis mAnuAl FOR FutuRe ReFeRence

tAble OF cOntents

160627

Page 4: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

4

sAFety symbOls

! !

! !

! !

! !

The following defined symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.

dAnGeR

indicates an imminently hazardous situation which, if not avoided, Will result in death or serious injury.

WARninG

indicates a potentially hazardous situation which, if not avoided, cOuld result in death or serious injury.

cAutiOn

Indicates a potential hazardous situation which, if not avoid-ed, MAY result in minor or moderate injury. It may also be used to alert against unsafe practices.

impORtAnt: Read the following instructions COMPLETELY before installing!!

WARninG

All installations should be done only by a qualified expert and in accordance with the appropriate Argo manual. in-stalling an electric appliance with improper methods or materials may result in serious injury or death due to fire.

Page 5: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

5

This manual is intended to familiarize the installer and user of the Argo AR Series of controls with their installation and operation to assure normal trouble-free operation.

Argo controls are designed and manufactured with quality compo-nents for maximum life and durability and require minimal service. To insure a satisfactory installation, it is imperative that the instruc-tions be followed carefully before operating the control. Failure to do so may result in breach of warranty.

intROductiOn

mOuntinG instRuctiOns

Mount the Argo AR Series Control vertically on a solid wall or parti-tion. For your convenience it is recommended that the control be mounted as close as possible to the device to be controlled. The control should never be mounted more than 75 feet away. Select a location that is easily accessible for installation and service.

nOte: To reduce the possible transformer hum and relay noise that is sometimes amplified by mounting surfaces such as sheet metal, plasterboard, and similar materials, place rubber or felt washers between the case and the mounting surface.

1. Position the control and mark the mounting holes.

2. Start screws (not provided) for the keyhole type mount-ing holes in the upper corner(s). Tighten the screws down to about ⅛” (3mm) from the surface. The AR822-II will require a screw to be installed in the lower left hand corner after the control is hung and leveled.

3. Hang the control on the screw(s), position the case, and start the bottom screws.

4. Tighten all screws.

Page 6: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

6

Electrical Specificationspart

numbermodel

numbertransformer

VoltageRelay switching

Actioncontact/control Amp

draw (120VAc)Z140 AR822-II 120V/60Hz/40Va DPDT 7.2

Z209 AR861-2II 120V/60Hz/75Va DPDT 7.2

Z210 AR861-3II 120V/60Hz/75Va DPDT 7.2

AR822-ii cOntROl FeAtuRes

Auto-Reset Electronic Fuse Protection • – Eliminates Nuisance Service Calls

15VA Transformer • – Robust Components Provide Years of Trouble -Free Service

Ice Cube Technology • – Plug-In Replacement Relays

5-Year Warranty•

electRicAl speciFicAtiOns & WiRinG

! ! WARninG

electRicAl sHOck HAzARd! disconnect power be-fore installing or servicing. can cause severe personal injury, death, or substantial property damage if ignored.

– GeneRAl WiRinG nOtice –

All primary wiring must be 14 AwG minimum. Torque terminal screws 6 to 7 inch pounds.

u.s.A. - National Electric Code and any other national, state, or local code requirements. wiring must be N.E.C. Class 1.

cAnAdA - C.S.A. C22.1 Canadian Electrical Code Part 1 and any other national, provincial, or local code requirements. wiring must be C.S.A. C22.1 C.E.C. Part 1.

Page 7: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

7

AR822-ii cOntROl bOARd

The following describes the function of each terminal.

• L1: Hot leg of 120VAC power input

• L2: Common leg of 120VAC power input

AR822-ii sequence OF OpeRAtiOn

1. when the thermostat connection to TR/Tw calls for heat the “circuit ON” LED is illuminated.

2. The relay will then close.

3. The contacts between 3/4 NO and 5/6 NO will close.

4. The contacts between 3/4NC and 5/6NC will open.EL

ECTR

ON

IC F

USE

VAC

CIRC

UIT

ON

120

L2NO

4NC

4

SCREWSTORQUE TERMINAL

6 TO 7 INCH LBSAR822-TTARGO TT

TTR W

24V

C 5 6NO

6NC

RE

LAy

Factory Installed Jumper Between L1 & 3

Class 2Terminals

PrimaryTerminals

Page 8: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

8

• 3: Input to one pole of relay contacts

• 4 NO: Normally open output, between 3 and 4 NO

• 4 NC: Normally closed output, between 3 and 4 NC

• 5: Input to one pole of relay contacts

• 6 NO: Normally open output, between 5 and 6NO

• 6 NC: Normally closed output, between 5 and 6NC

T/R and T/w are the thermostat connections. when a Thermostat calls completing the circuit the relay is activated.

AR822-ii WiRinG scHemAtics

AR822-ii cOntROl bOARd

Page 9: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

9

TO BURNER

OR BURNER

CONTROL

DO NOT USE

AR822-ii ApplicAtiOns

AR822-ii dual zone Applicationwithout tankless coiler boiler

AR822-ii single zone Applicationwith tankless coil boiler

Page 10: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

10

L2120VAC

L1

CIRC

UIT

ON +

NO

3NC

4 4

ARGO AR822

WR CTT 24V

5 6 6NO NC

BURNER CONTROLTO BURNER OR

DO NOT USE

L8148

2

1

T

C2

B1

C1

B2

T

PRIORITYCIRC.

24 VAC

COM

TX-X TT TT T TT TTON

ZONE 2

END SW 2

X2X1

END SW 1

X1 X2

ZONE 121 3 4 1 2

AZ-

3

ARG

O

Zone

Val

ve C

ontr

olle

r

ZONE 343 1 2 43

AZ-

5

ZONE 41 2 43 3

ZONE 51 2 4

SUPPLIEDWITH RELAY AZ-5

STAT STAT STAT STAT STAT

VALVE VALVE VALVE VALVE VALVE

DOMESTICHOT

WATER

L

N

120VAC

JUMPER

N120VAC L

HEATINGZONEPUMP

120VAC

L

N

nOte: Thermostats must be mercury switch style or battery powered for this installation to function properly.

AR822-ii ApplicAtiOns

AR822-ii indirect tank prioritywith zone Valve control

Page 11: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

11

AR861-2ii & AR861-3ii sequence OF OpeRAtiOn

iF tHe pRiORity sWitcH is in tHe “OFF” pOsitiOn

1. When a zone calls for heat the corresponding zone LED is illuminated.2. The relay for the corresponding zone will then close.3. A/R terminals will close starting the boiler.4. The corresponding GZ/HZ terminals will be energized with 120 Volts.

iF tHe pRiORity sWitcH is in tHe “On” pOsitiOn

1. Zone 1 becomes the priority zone.2. when zone 1 calls for heat, the priority zone is activated and all other zones are deactivated (circulators for zones 2 and higher will not operate). Zone 1 LED is illuminated indi-cating a call for heat.3. Zone 1 relay will close.4. A/R terminals will close starting the boiler.5. GZ 1/HZ 1 will be energized with 120 Volts.

2-Zone AR861-2II or 3-Zone AR861-3II•

Auto-Reset Electronic Fuse Protection • – Eliminates Nuisance Service Calls

15VA Transformer • – Robust Components Provide Years of Trouble -Free Service

Ice Cube Technology • – Plug-In Replacement Relays

Priority Function•

5-Year Warranty •

AR861-2ii & AR861-3ii cOntROl FeAtuRes

Page 12: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

12

AR861-2ii cOntROl bOARd & WiRinG scHemAtic

RE

LAy

RE

LAy

RE

LAy

Class 2 Terminals

Primary Terminals

Page 13: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

13

RE

LAy

RE

LAy

RE

LAy

RE

LAy

AR861-3ii cOntROl bOARd And WiRinG scHemAtic

Class 2 Terminals

Primary Terminals

Page 14: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

14

The diagrams on the following pages represent the AR861-3II. The AR861-2II is wired in a similar fashion.

Priority T-Stat

Primary Wiring

Class 2 Wiring

AR861-3II

Primary WiringJumper

Priority Circ L4006A

T-StatT-Stat

Circ

L2G W L A R GZ1

T1 T1 T2 T2 T3 T3

HZ1 GZ2 HZ2 GZ3 HZ3

G Circ

120 VACL1Hot

Milli VoltGas Valve

AR861-2ii & AR861-3ii ApplicAtiOns

RE

LAy

RE

LAy

RE

LAy

RE

LAy

Each of the low voltage controllers (SPST Thermostats) will actuate a circulator and start the burner when used in conjunction with an isolated switch aquastat.

Jumper: To be placed between terminals l and W . In this position A and R become the isolated end switch. (Jumper is factory installed in this position)

Terminals A and R Isolated End Switch

Page 15: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

15

Priority T-Stat

Primary Wiring

Class 2 Wiring

AR861-3II

Primary WiringJumper

Priority Circ L4006A

T-StatT-Stat

Circ

L2G W L A R GZ1

T1 T1 T2 T2 T3 T3

HZ1 GZ2 HZ2 GZ3 HZ3

G Circ

Milli VoltGas Valve

120 VACL1Hot

24VTransformer

Priority T-Stat

L8148

Primary Wiring

To Burner or

Burner Control

DoNotUse

Class 2 Wiring

AR861-3II

Primary WiringJumper

Priority Circ

T-Stat

T-Stat

TT

1

2

Circ

G W L A R GZ1

T1 T1 T2 T2 T3 T3

C1

C2

B2

B1

HZ1 GZ2 HZ2 GZ3 HZ3

CircL2

G

120 VACL1Hot

AR861-2ii & AR861-3ii ApplicAtiOns

Page 16: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

16

AR861-2ii & AR861-3ii ApplicAtiOns

! ! WARninGAR relays will not work properly if 120 VAC polarity is not the same at the 120 VAC L and N terminals on both the AR control and the boiler aquastat. The neutral and hot wires must not be reversed. Reversing the L and N wires could result in a secondary source of power that may activate the boiler under certain circumstances that may cause serious injury or death.

! ! WARninG

when using ZC-ZR careful attention must be paid to keeping the po-larity of the wiring consistent between the Argo control and the boiler aquastat. Failure to do so could result in a secondary source of power activating the boiler under certain circumstances which could result in serious injury or death. Always disconnect power to both the Argo control and the boiler when installing or servicing this product.

RE

LAy

RE

LAy

RE

LAy

RE

LAy

Terminals W and R to Aquastat( W to ZC and R to ZR)

Each of the low voltage controllers (SPST Thermostats) will actuate a circulator and start the burner when used in conjunction with a boiler aquastat control. If the boiler temperature drops below the low limit (circulator) setting, all circulating will cease until the temperature of the boiler water is increased.

Jumper: To be placed between terminals l and A . In this position a line voltage message is sent out R to ZR terminal on the aqustst and returns to W from the ZC terminal on the aqustst.

Page 17: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

17

Priority T-Stat

Primary Wiring

Burner

Class 2 Wiring

AR861-3II

Primary WiringJumper

Priority Circ

T-StatT-Stat

L8124A or C

T

T

L1

L2

Circ

G W L R GZ1

T1 T1 T2 T2 T3 T3

C1

C2

B2

B1

ZR

ZC

HZ1 GZ2 HZ2 GZ3 HZ3

CircL2

G

120 VACL1Hot

A

AR861-2ii & AR861-3ii ApplicAtiOns

Priority T-Stat

Primary Wiring

Burner

Class 2 Wiring

AR861-3II

Primary WiringJumper

Priority Circ

T-StatT-Stat

L8124A or C

T

T

L1

L2

Cad

Cell

Circ

G W L R GZ1

T1 T1 T2 T2 T3 T3

C1

C2

B2

B1

ZR

ZC

HZ1 GZ2 HZ2 GZ3 HZ3

CircL2

G

120 VACL1Hot

A

Page 18: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

18

AR861-2ii & AR861-3ii expAnsiOn tecHnique

THERMOSTATS

GZ2120 V CIRCULATOR

15VA

120VACG W L RA

PRIORITYGZ1 HZ1

PRIORITY OFF

PRIORITY ON

PRIORITYT1 T1 T2

GZ3HZ2 HZ3

T3T3T2

STATSTAT

CIRC CIRCDO NOTUSE

N

L

120VAC

CIRC

STAT

T2

120 V CIRCULATORGZ2

THERMOSTATS

15VA

L

120VAC

N

W120VAC

G L A GZ1PRIORITY

R HZ1

PRIORITY OFF

PRIORITY ON

2.7 K

1.0 K

2.7 K

1.0 K

PRIORITYT1 T2T1

CIRC

HZ2 GZ3 HZ3

1.0 K

2.7 K

T3 T3

STAT

CIRC

TO BOILERT-T

TO BOILERT-T

DOMESTIC

WATERHOT

JUMPER

JUMPER

TRIPLE RELAY AR861-3 IIARGO

TRIPLE RELAY AR861-3 IIARGO

The two controls on this page are capable of running six zones. when they are installed as shown below, only one priority and four standard zones (for a total of five zones) are available.

Important: Both left-hand T1 ter-minals must be connected together and both right-hand T1 terminals must be connected together. Reversing the wiring will result in the transformers being out of phase.

Page 19: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

19

AR seRies WitH dpm-2 OutdOOR Reset cOntROl

The DPM-2 Outdoor Reset Control is designed to raise or lower the temperature of the boiler supply water based upon a proportionate drop or rise in temperature at the outside sensor. This control plugs into Argo control equipment with a data port or as a stand alone device that can be easily wired into almost any system. See the separate DPM-2 Installation Manual for more information.

Page 20: INSTALLATION MANUAL AND OPERATING INSTRUCTIONS · Zone 1 relay will close. 4. A/R terminals will close starting the boiler. 5. GZ 1/HZ 1 will be energized with 120 Volts. • 2-Zone

Replacement partpart description Argo part number

Replacement Control Relay R35C

For technical support on this and all Argo products, please contact ECR International Technical Service at 1-800-325-5479. Please have your model number available when calling.

information needed When calling

Model Number

Installation Date

Installer

ReplAcement pARts

tecHnicAl suppORt

www.argocontrols.com