Installation Instructions T/PO - Energy Controls Online · T/PO Installation Instructions TG100241A...

4
T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 1 Installation Instructions T/PO PRT Outside Air Temperature Sensor Important: Retain these instructions These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com 1 Dimensions 2 Requirements 3 Mount on Wall T / P O T / P O T / P O T / P O T / P O 85 mm (3.35”) drill 2 pilot holes tighten screws 2 off No 6 (M3.5) screws 2 INSTALLATION 1 BOX CONTENTS It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code). CONTENTS 1 Box Contents .................................................................1 2 Installation .....................................................................1 3 Disposal .........................................................................4 T/PO T/PO Instalaltion Instructions (TG100241A) M A N U F A C T U R E D I N E U T R E N D C O N T R O L S Y S T E M S L T D U K T / P O 57 mm (2.24”) 105 mm (4.13”) 97 mm (3.82”) domed brass sensor cap H O 2 -40 °C (-40 °F) +50 °C (+122 °F) 0 %RH 95 %RH ambient limits Protection :IP67, NEMA6 T / P O T / P O measurement range -30 °C (-22 °F) +50 °C (+122 °F)

Transcript of Installation Instructions T/PO - Energy Controls Online · T/PO Installation Instructions TG100241A...

Page 1: Installation Instructions T/PO - Energy Controls Online · T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 3 Installation Instructions T/PO 10 Configure IQ IQ Configuration

T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 1

Installation Instructions

T/POPRT Outside air Temperature Sensor

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specifi ed by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com

1 Dimensions

2 Requirements

3 Mount on Wall

� � � �

� � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � �

� � � � � �

� � � �

���

���

���

���

������

����

���

����

�����

����

���

���

����

���������������������������������������

������

����

���

����

�����

������

����

���

����

���������

����

���

����

85 mm (3.35”)drill 2 pilot holes

tighten screws

2 off No 6 (M3.5) screws

2 InSTaLLaTIOn

1 BOX COnTEnTS

It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

COnTEnTS1 Box Contents .................................................................12 Installation .....................................................................1

3 Disposal .........................................................................4

T/PO T/PO Instalaltion Instructions (TG100241A)

� � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � �

� � � � � �

� � � �

57 mm (2.24”)

105

mm

(4.1

3”)

97 mm (3.82”)

domed brass sensor cap

� � ��

-40 °C(-40 °F)

+50 °C (+122 °F)

0 %RH 95 %RHambient limits

Protection :IP67, NEMA6

� � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � �

� � � � � �

� � � �� � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � �

� � � � � �

� � � �

measurement range-30 °C(-22 °F)

+50 °C (+122 °F)

Page 2: Installation Instructions T/PO - Energy Controls Online · T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 3 Installation Instructions T/PO 10 Configure IQ IQ Configuration

2 T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015.

T/PO Installation Instructions

4 Remove Lid 5 Lift Board

Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken throughout the operation to prevent damage to the units. BS EN100015/1 Basic Specifi cation: protection of electrostatic sensitive devices.

6 Insert Cable

either use M20 fl exible conduit or use M16 cable gland

7 Wire to Controller

IQ1xx, IQ2xx

polarity independent

Sensor24 VdcIN

Terminate screen at IQ end only

Analogue input channel linked for current (I)

IQ system TP/I/22/HF/200 (Belden 8761) cable recommended.

Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)

Note: Connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V), instead connect to AUX+ (+24V).

IQ3Sensor 0(0 V)

N(in)+ (24 V)N

8 Replace Board 9 Replace Lid

Note: IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened.

2 InSTaLLaTIOn (continued)

Page 3: Installation Instructions T/PO - Energy Controls Online · T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 3 Installation Instructions T/PO 10 Configure IQ IQ Configuration

T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 3

Installation Instructions T/PO

10 Configure IQ

� �

IQ Configuration Manual 90-1533� �

or

11 Set up IQ Sensor Type

It is recommended to use SET for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, select the appropriate SET Unique Sensor Reference from the following:

PRT I -40+50 (°C)PRT I -40+122 F (°F)

Alternatively set sensor scaling mode to 5 (characterise) and enter the scaling manually as defined in the table below.

Y input type 2 (current)

E Exponent 3

Units °C °F

U Upper 50 122

L Lower -40 -40

P Points 2 2

x Ix Ox Ox

1 4 -40 -40

2 20 50 122

12 Test System

∆ T

� � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � � � �

� � � � � �

� � � �

IQ

Note: For IQ3 the scaling mode and exponent (E) do not need to be set up.

For all other IQ controllers see Sensor Scaling Reference Card (TB100521A).

2 InSTaLLaTIOn (continued)

Page 4: Installation Instructions T/PO - Energy Controls Online · T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015. 3 Installation Instructions T/PO 10 Configure IQ IQ Configuration

4 T/PO Installation Instructions TG100241A Issue 6, 18-Dec-2015.

T/PO Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems LimitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

TR CU Certification

3 DISPOSaL

WEEE Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.

Do not dispose of with normal household waste.Do not burn.