INSTALLATION INSTRUCTIONS Rfiflfi™
Transcript of INSTALLATION INSTRUCTIONS Rfiflfi™
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
In a continuing effort to offer the best product possible we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Web: www.hubbellhealthcare.com • Tech Support: 888•777•4832
Remedi™
™
CAUTION! – READ THIS FIRST - IMPORTANT SAFETY INSTRUCTIONS
*Carefully read the instructions pertaining to your fixture. IF YOU HAVE ANY QUESTIONS REGARDING THE PROPER INSTALLATION OR LOCAL CODES, CONSULT A QUALIFIED ELECTRICIAN.
*To avoid shock hazard, do not work with live electrical wires.
*Install the fixture in only indoor applications.
*Do not install outdoors or in applications other than the intended use.*Install and wire the fixture in locations in compliance with the National Electric Code and any local codes.
*Do not remove any protective films over the lens or reflectors until installation is complete. Do not energize the fixture without removing the protective films from the lens or reflectors.
WARNING: THIS PRODUCT MUST BE INSTALLED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE AND/OR ANY LOCAL CODES BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. IF YOU HAVE ANY QUESTIONS REGARDING THE PROPER INSTALLATION OR LOCAL CODES, CONSULT A QUALIFIED ELECTRICIAN.
WARNING: RISK OF FIRE, MINIMUM OF 90°C SUPPLY CONDUCTOR. CONSULT A QUALIFIED ELECTRICIAN TO ENSURE CORRECT BRANCH CIRCUIT CONDUCTOR.
WARNING: TO AVOID SHOCK HAZARD, DISCONNECT THE POWER AT THE PANEL BOARD (CIRCUIT BREAKER BOX) BEFORE BEGINNING INSTALLATION.
WARNING: INSTALL THE FIXTURE IN ONLY AN INDOOR ENVIRONMENT AND FOR THE INTENDED USE.
WARNING: INJURY TO PERSONS AND DAMAGE TO THE FIXTURE AND/OR MOUNTING SURFACE MAY RESULT If THE FIXTURE IS PULLED FROM THE SURFACE. TO REDUCE THE LIKELIHOOD OF SUCH INJURY OR DAMAGE, MOUNT ONLY ON A SURFACE THAT IS MECHANICALLY SOUND.
The Remedi luminaire is intended to be installed vertically centered 6’3” above finished floor. Components shown in images may vary based on the configuration ordered. The steps for installation are as follows:
A. MOUNTING THE BACKPLATE
1. Remove the backplate from the packaging. Remove the 6 flat head screws and the two piece wireway covers. If desired, remove the 4 wing nuts and the gear plates to reduce the weight of the backplate for installation. Figures 1 and 2 detail the wireway and gear plate removal.
2. Position the backplate to the desired mounting location on the wall. Note: It is recommended to center the fixture vertically at 6'-3" above finished floor for optimum performance. Make sure that the electrical access hole in the backplate is aligned with the electrical box. Level the fixture and mark the mounting points (points 1-7) shown in Figure 3.
3. Position the backplate and install the fasteners. Mount directly to the wall structure or use suitable wall anchors.
4. If removed, replace the gear plates and hand-tighten the 4 wing nuts.
Figure 1: The wireway covers are disassembled by removing (6) flat head screws.
BOTTOM WIREWAY COVER
TOP WIREWAY COVER
FLAT HEAD SCREWS(X6)
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
In a continuing effort to offer the best product possible we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Web: www.hubbellhealthcare.com • Tech Support: 888•777•4832
Remedi™
™
B. MAKING ELECTRICAL CONNECTIONS
Note: The circuit should be shut-off at the breaker before beginning this step.
1. Locate ground and common leads, as well as the input leads for the Ambient, Reading, Exam, Night Light, LVC, and/or Pull Chain loads (depending on product configuration), and connect accordingly. The input leads from the fixture are labeled for identification.
2. If a Low Voltage Controller (LVC) is present, locate the low voltage switching wires of the in-fixture device and terminate to corresponding wiring of the nurse call system (supplied by others). Refer to Figures 9-19 in Section E for more details on how to connect the LVC option to the nurse call system.
3. If the Bed Safety Switches (BSS) are present, connect the leads from the fixture labeled “BSS” in series with the wiring to the wall receptacle that the motorized patient bed will be plugged into.. See the wiring diagram in Figure 4.
Figure 4: Bed Safety Switch option: cuts off power to the electrical receptacle for the motorized patient bed if the fixture is displaced.
Figure 3: The backplate mounts to the wall in (7) designated locations.
Figure 2: The gear plates may be removed by unfastening (4) wing nuts.
1
5
2
6
3 4
7
16.0046.65
2.50
NORMOPEN
COM
BLACK BLUE
RED JUMPER
CONNECT BLACK AND BLUE WIRES IN SERIESWITH BED CONTROL WIRES IN WALL.
BUILDINGSUPPLY
NORMOPEN
COM
GEAR PLATE(X2)
WING NUT(X4)
ENGAGEMENT FLANGE(X4)
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
C. INSTALLING THE HOUSING
1. Remove the housing assembly from the packaging.
2. Remove the 4 socket head screws using the supplied 9/64” Allen wrench and the outer end pieces. See Figure 5.
3. Align the end flanges of the backplate with the corresponding slots in the end pieces of the housing assembly, and hook the housing assembly onto the backplate. The construction will allow the housing to rest on the vertical back plate flanges. If the bed safety switches are present, ensure that the switch levers are depressed on both ends of the fixture. This step is detailed in Figure 6A.
4. Place a provided metal spacer onto a supplied machine screw and fasten through the backplate into one of the threaded bosses in the end piece. Ensure that the metal spacer is fully within the backplate hole and does not pinch the backplate while being installed. Repeat this step so that the housing assembly is fastened to the backplate in all four locations. Confirm that the fixture housing can slide upward along the slot and can return back to the original resting position. This step is detailed in Figure 6C and 6D.
5. Feed the LED wire harnesses through the opening in the end pieces, making sure that no wires are pinched. Connect the color-coded wire harnesses at each end of the fixture. If night light switches are present, connect the low voltage wire connector to the module on the right gear plate.
Figure 5: The outer end piece comes off with the removal of two socket head screws.
Figure 6: The housing is aligned in step A, placed on the backplate in step B, and fastened in C and D
SOCKET HEAD SCREW(X2 PER END)
OUTER ENDPIECE
THREADED BOSS(X2 PER END)
SPACER(X2 PER END)
MACHINE SCREW(X2 PER END)
A B
DC
OPENING FOR LED WIRE HARNESSES FROM BACKPLATE
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
D. FINAL INSTALLATION STEPS
1. Reinstall the outer end pieces with the 4 socket head screws.
2. Reinstall the two-piece wireway covers with the 6 flat head screws. When reinstalling the wireway covers, ensure that no wires are pinched. Start by installing the lower portion of the cover. If a pull chain is present, attach the plastic extension cord to the chain and feed through the bushing in the lower wireway cover. After the lower portion of the cover has been installed, follow the steps shown in Figure 7 to attach the pendant to the pull cord. Install the top portion of the cover, making sure to insert it into the lower portion as shown in the cross section in Figure 8.
a edcb
Figure 7: The antimicrobial plastic extension cord is assembled.
Figure 8: Remedi’s two piece wireway cover allows for access to the fixture’s components with minimal disassembly.
TOP WIREWAYCOVER
BOTTOMWIREWAYCOVER
BACKPLATE
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
E. LOW VOLTAGE CONTROL (LVC) CONNECTION
Locate the wiring diagram in Figures 9-19 that matches the selected LVC option. Make the connections shown on the low voltage switch wires within the dashed lines. DO NOT ALTER THE WIRING OF THE LOAD AND/OR DIMMING LEADS IN THE FIXTURE.
1-800-235-7500
Figure 8: LVC1- Independent control of reading mode with one SPST momentary switch
S1
S1
BLUE
BROWN
RED
LC-060
LC-060
BLUE
BROWN
RED
240/277 VAC APPLICATIONS
120 VAC APPLICATIONS
N
ACBLACK
GREEN
N
N
AC
YELLOW
PINK
YELLOW
PINK
WHITE
WHITE
BLACK
GREEN
BLACK/RED
WHITE/RED
N
BLACK/RED
WHITE/RED
READINGLOAD
READINGLOAD
Connections made in �eld by Contractor
Connections made in �eld by Contractor
Figure 9: LVC2__- Sequential control of two modes with one SPST momentary switch
LC-060BLUE
BROWN
RED
240/277 VAC APPLICATIONS
N
AC
YELLOW
PINK
WHITE
BLACK
GREEN
BLACK/RED
WHITE/RED
N
LOAD 1 LOAD 2After power up: Off Off
1st Switch On Off
2nd Switch Off On
3rd Switch On On
4th Switch Off Off
Sequential
S1
BLUE
BROWN
RED
LC-060
120 VAC APPLICATIONS
N
ACBLACK
GREEN
NYELLOW
PINK
WHITE
BLACK/RED
WHITE/RED
S1READING
LOAD
Connections made in �eld by Contractor
Connections made in �eld by Contractor
AMBIENTLOAD
READINGLOAD
AMBIENTLOAD
Figure 10: LVC2__- Sequential control of two modes with one SPST momentary switch
Figure 9: LVC1- Independent control of reading mode with one SPST momentary switch
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
1-800-235-7500
Figure 10: LVC2__- Independent control of two modes with two SPST momentary switch
S2
S1
S2
S1 BLUE
BROWN
RED
LC-060
LC-060
BLUE
BROWN
RED
240/277 VAC APPLICATIONS
120 VAC APPLICATIONS
N
ACBLACK
GREEN
N
N
AC
YELLOW
PINK
YELLOW
PINK
WHITE
WHITE
BLACK
GREEN
BLACK/RED
WHITE/RED
N
BLACK/RED
WHITE/RED
Connections made in �eld by Contractor
Connections made in �eld by Contractor
READINGLOAD
AMBIENTLOAD
READINGLOAD
AMBIENTLOAD
Figure 11: LVC31 - Independent control of all three modes with three SPST momentary switches
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
MS1 MS2 MS3
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTIONS HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2SWITCH 3
COMMON
COMMON
COMMON
AMBIENTLOAD
MODE SELECT SWITCH READINGLOAD
NLLOAD
• MS1=OFF (0)• MS2=OFF (0)• MS3=OFF (0)
OFF (0)
ON (1)
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
ORANGE
BROWNGRAY
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 11: LVC2__- Independent control of two modes with two SPST momentary switch
Figure 12: LVC31 - Independent control of all three modes with three SPST momentary switches
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
Figure 12: LVC32 - Sequential control of ambient and reading modes with one SPST momentary switch and Independent control of night light with second SPST momentary switch
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
MS1 MS2 MS3
OPTIONAL WALL SWITCH(ES)
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 3
AMBIENTLOAD
MODE SELECT SWITCH READINGLOAD
NLLOAD
• MS1=ON (1)• MS2=OFF (0)• MS3=OFF (0)
OFF (0)
ON (1)
LVC CONTROL CONNECTION S HIGH VOLTAGE SOURCE/OUTPUTS
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
DIM2 0-10V
LOAD 1
LOAD 2
EARTH GROUND/CHASSIS
LOAD 3
COMMON
HOT 120-277VAC
LOAD 1 LOAD 2After power up: O
1st Switch On
2nd Switch O On
3rd Switch On On
4th Switch O
Sequential
COMMON
COMMON
COMMON
PINK
YELLOW
ORANGE
BLACK
WHITE
GREEN
BROWNGRAY
RED
Connections made in �eld by Contractor
Figure 13: LVCDST1 and LVCDSM1 - Independent dimming control of ambient mode and independent non-dim control of reading mode and night light
0-10v ANALOG CONTROL
MS1 MS2 MS3
MODE SELECT SWITCHSMOOTH DIMMINGSTEP DIMMING
• MS1=OFF (0)• MS2=ON (1)• MS3=ON (1)
OFF (0)
ON (1)
MS1 MS2 MS3
• MS1=OFF (0)• MS2=ON (1)• MS3=OFF (0)
OFF (0)
ON (1)
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTIONS HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2SWITCH 3
COMMON
COMMON
COMMONAMBIENT
LOAD
READINGLOAD
NLLOAD
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
ORANGE
BROWNGRAY
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 13: LVC32 - Sequential control of ambient and reading modes with one SPST momentary switch and Independent control of night light with second SPST momentary switch
Figure 14: LVCDST1 and LVCDSM1 - Independent dimming control of ambient mode and independent non-dim control of reading mode and night light
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
Figure 14: LVCDST2 and LVCDSM2 - Independent dimming control of reading mode and independent non-dim control of ambient mode and night light.
0-10v ANALOG CONTROL
MS1 MS2 MS3
MODE SELECT SWITCHSMOOTH DIMMINGSTEP DIMMING
• MS1=OFF (0)• MS2=ON (1)• MS3=ON (1)
OFF (0)
ON (1)
MS1 MS2 MS3
• MS1=OFF (0)• MS2=ON (1)• MS3=OFF (0)
OFF (0)
ON (1)
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTION S HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2SWITCH 3
COMMON
COMMON
COMMONREADING
LOAD
AMBIENTLOAD
NLLOAD
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
ORANGE
BROWNGRAY
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 15: LVCDST3 and LVCDSM3 - Independent dimming control of ambient and reading modes and independent non-dim control of night light
0-10v ANALOG CONTROL
0-10v ANALOG CONTROL
MS1 MS2 MS3
MODE SELECT SWITCHSMOOTH DIMMINGSTEP DIMMING
• MS1=ON (1)• MS2=ON (1)• MS3=ON (1)
OFF (0)
ON (1)
MS1 MS2 MS3
• MS1=ON (1)• MS2=ON (1)• MS3=OFF (0)
OFF (0)
ON (1)
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTIONS HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2SWITCH 3
COMMON
COMMON
COMMONAMBIENT
LOAD
READINGLOAD
NLLOAD
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
ORANGE
BROWNGRAY
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 15: LVCDST2 and LVCDSM2 - Independent dimming control of reading mode and independent non-dim control of ambient mode and night light.
Figure 16: LVCDST3 and LVCDSM3 - Independent dimming control of ambient and reading modes and independent non-dim control of night light
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
Figure 16: LVCDST4 and LVCDSM4 - Independent dimming control of ambient mode and Independent non-dim control of reading mode
0-10v ANALOG CONTROL
MS1 MS2 MS3
MODE SELECT SWITCHSMOOTH DIMMINGSTEP DIMMING
• MS1=OFF (0)• MS2=ON (1)• MS3=ON (1)
OFF (0)
ON (1)
MS1 MS2 MS3
• MS1=OFF (0)• MS2=ON (1)• MS3=OFF (0)
OFF (0)
ON (1)
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTIONS HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2
COMMON
COMMONAMBIENT
LOAD
READINGLOAD
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
BROWN
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 17: LVCDST5 and LVCDSM5 - Independent dimming control of reading mode and independent non-dim control of ambient mode
0-10v ANALOG CONTROL
MS1 MS2 MS3
MODE SELECT SWITCHSMOOTH DIMMINGSTEP DIMMING
• MS1=OFF (0)• MS2=ON (1)• MS3=ON (1)
OFF (0)
ON (1)
MS1 MS2 MS3
• MS1=OFF (0)• MS2=ON (1)• MS3=OFF (0)
OFF (0)
ON (1)
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTIONS HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2
COMMON
COMMONREADING
LOAD
AMBIENTLOAD
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
BROWN
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 17: LVCDST4 and LVCDSM4 - Independent dimming control of ambient mode and Independent non-dim control of reading mode
Figure 18: LVCDST5 and LVCDSM5 - Independent dimming control of reading mode and independent non-dim control of ambient mode
93082478 9/19/17Web: www.hubbellhealthcare.com • Tech Support: 864•678•1000701 Millennium Blvd. • Greenville, SC 29607 U.S.A.Copyright ©2017 Healthcare Solutions, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved. • Specifications subject to change without notice. • Printed in U.S.A.
INSTALLATION INSTRUCTIONS
4' Multi-Function Patient Bed Light
Remedi™
™
Figure 18: LVCDST6 and LVCDSM6 - Independent dimming control of ambient and reading mode
0-10v ANALOG CONTROL
0-10v ANALOG CONTROL
MS1 MS2 MS3
MODE SELECT SWITCHSMOOTH DIMMINGSTEP DIMMING
• MS1=ON (1)• MS2=ON (1)• MS3=ON (1)
OFF (0)
ON (1)
MS1 MS2 MS3
• MS1=ON (1)• MS2=ON (1)• MS3=OFF (0)
OFF (0)
ON (1)
EARTH GROUND
HOT/LINE 120 TO 277 VAC
COMMON
OPTIONAL WALL SWITCH(ES)
LVC CONTROL CONNECTIONS HIGH VOLTAGE SOURCE/OUTPUTS
SWITCH 1
TO NURSE CALL SYSTEM RECEPTACLE
SWITCH 2
COMMON
COMMONAMBIENT
LOAD
READINGLOAD
LVC
SWITCH 1
SWITCH 2
SWITCH 3
SWITCH COMMON
DIM1 COMMON
DIM1 0-10V
DIM2 COMMON
LOAD 1
LOAD 2
EARTH GRO U ND/CHASSIS
LOAD 3
COMMON
HOT 120-277VACDIM2 0-10V
PINK
YELLOW
BROWN
BLUE
RED
BLACK
WHITE
GREEN
Connections made in �eld by Contractor
Figure 19: LVCDST6 and LVCDSM6 - Independent dimming control of ambient and reading mode
REPLACEMENT PARTS
Replacement parts can be ordered by contacting Hubbell Lighting at 864-678-1000, Monday-Friday from 8:00am – 5:00pm EST.