INSTALLATION INSTRUCTIONS R 410A Single Package …

24
516 01 2403 00 1/21/15 INSTALLATION INSTRUCTIONS R410A Single Package Rooftop Heat Pump RHS090 120 These instructions must be read and understood completely before attempting installation. DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product. DANGER Immediate hazards which will result in severe personal injury or death. WARNING Hazards or unsafe practices which could result in severe personal injury or death. CAUTION Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or operation. Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal word CAUTION is used throughout this manual in the following manner: Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures on product labels. WARNING Safety Labeling and Signal Words ! CAUTION WARNING ! ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury and/or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF posi- tion. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignitions sources away from refrigerants and oils. ! WARNING ! CAUTION CUT HAZARD Failure to follow this caution may result in personal in- jury Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts. UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. R410A refrigerant systems operate at higher pressures than standard R22 systems. Do not use R22 service equipment or components on R410A refrigerant equipment. ! WARNING

Transcript of INSTALLATION INSTRUCTIONS R 410A Single Package …

Page 1: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 1/21/15

INSTALLATION INSTRUCTIONSR−410A Single Package Rooftop Heat Pump

RHS090 − 120

These instructions must be read and understood completely before attempting installation.

DANGER, WARNING, CAUTION, andNOTEThe signal words DANGER, WARNING,CAUTION, and NOTE are used to identify levels ofhazard seriousness. The signal word DANGER isonly used on product labels to signify an immediatehazard. The signal words WARNING, CAUTION,and NOTE will be used on product labels andthroughout this manual and other manuals that mayapply to the product.

DANGER − Immediate hazards which will result insevere personal injury or death.

WARNING − Hazards or unsafe practices whichcould result in severe personal injury or death.

CAUTION − Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.

NOTE − Used to highlight suggestions which willresult in enhanced installation, reliability, oroperation.

Signal Words in Manuals

The signal word WARNING is used throughout thismanual in the following manner:

The signal word CAUTION is used throughout thismanual in the following manner:

Signal Words on Product Labeling

Signal words are used in combination with colorsand/or pictures on product labels.

WARNING

Safety Labeling and Signal Words

!

CAUTION

WARNING

!

! WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury and/or death.

Before installing, modifying, or servicing system, mainelectrical disconnect switch must be in the OFF posi-tion. There may be more than 1 disconnect switch.Lock out and tag switch with a suitable warning label.

PERSONAL INJURY AND ENVIRONMENTALHAZARD

Failure to follow this warning could cause personalinjury or death.

Relieve pressure and recover all refrigerant beforesystem repair or final unit disposal.

Wear safety glasses and gloves when handlingrefrigerants. Keep torches and other ignitionssources away from refrigerants and oils.

! WARNING

! CAUTIONCUT HAZARD

Failure to follow this caution may result in personal in-jury

Sheet metal parts may have sharp edges or burrs. Usecare and wear appropriate protective clothing andgloves when handling parts.

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personalinjury, death and/or equipment damage.

R−410A refrigerant systems operate at higherpressures than standard R−22 systems. Do notuse R−22 service equipment or components onR−410A refrigerant equipment.

! WARNING

Page 2: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 002

NOTE: Read the entire instruction manual before starting theinstallation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,or use can cause explosion, fire, electrical shock or otherconditions which may cause personal injury or property damage.Consult a qualified installer, service agency, or your distributor orbranch for information or assistance. The qualified installer oragency must use factory−authorized kits or accessories whenmodifying this product. Refer to the individual instructionspackaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Usequenching cloths for brazing operations and have a fireextinguisher available. Read these instructions thoroughly andfollow all warnings or cautions attached to the unit. Consult localbuilding codes and appropriate national electrical codes (in USA,ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSAC22.1) for special requirements.

It is important to recognize safety information. This is the

safety−alert symbol . When you see this symbol on the unit andin instructions or manuals, be alert to the potential for personalinjury.

Understand the signal words DANGER, WARNING, CAUTION,and NOTE. These words are used with the safety−alert symbol.DANGER identifies the most serious hazards which will result insevere personal injury or death. WARNING signifies hazardswhich could result in personal injury or death. CAUTION is used toidentify unsafe practices, which may result in minor personal injuryor product and property damage. NOTE is used to highlightsuggestions which will result in enhanced installation, reliability, oroperation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal injury ordeath.

Before performing service or maintenance operations on unit,always turn off main power switch to unit and install lockouttag. Unit may have more than one power switch.

! WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal injury,death and/or equipment damage.

R−410A refrigerant systems operate at higher pressures thanstandard R−22 systems. Do not use R−22 service equipmentor components on R−410A refrigerant equipment.

! WARNING

PERSONAL INJURY AND ENVIRONMENTAL HAZARD

Failure to follow this warning could cause personal injury ordeath.

Relieve pressure and recover all refrigerant before systemrepair or final unit disposal.

Wear safety glasses and gloves when handling refrigerants.Keep torches and other ignition sources away fromrefrigerants and oils.

! WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wearappropriate protective clothing, safety glasses and gloves when handlingparts and servicing heat pump units.

CAUTION!

Page 3: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 3

FIGURE 1 Base Unit Dimensions: RHS090−102

RH

S09

1

RH

S09

0

Page 4: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 004

Connection Sizes (DIA)

Thru the Base Chart, Holes Required For Use WithCRBTMPWR002A01

Threaded Conduit Size Wire Use Required Hole Sizes (Max.)A 1-3/8” [35] Field Power Supply Hole W 1/2” ACC 7/8” [22.2]B 2/1/2” [64] Power Supply Knockout X 1/2” 24V 7/8” [22.2]C 1-3/4” [44] Gauge Access Plug Y 1-1/4” (002) Power 1-3/4” [44.4]D 7/8” [22] Field Control Wiring HoleE 3/4”-14 NPT Condensate DrainG 2” [51] Power Supply Knock-out

FIGURE 1A Base Unit Dimensions: RHS120

Horizontal Connections / Economizer

Vertical Connections / Economizer

15-7/8[403]

49-3/8[1253]

35-5/8[905]

Page 5: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 5

Figure 1B Unit Weights and Center of Gravity RHS090−120

RHS120

Center of Gravity

Y

X

Z

*Standard unit weight is without electric heat and without packaging.For options and accessories refer to the priduct specifications.

Page 6: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 006

INSTALLATIONJobsite Survey

Complete the following checks before installation.

1. Consult local building codes and the NEC (National ElectricalCode) ANSI/NFPA 70 for special installation requirements.

2. Determine unit location (from project plans) or select unit loca-tion.

3. Check for possible overhead obstructions which may interferewith unit lifting or rigging.

Step 1 — Plan for Unit LocationSelect a location for the unit and its support system (curb or other)that provides for the minimum clearances required for safety. Thisincludes the clearance to combustible surfaces, unit performanceand service access below, around and above unit as specified inunit drawings. See Fig. 2.NOTE: Consider also the effect of adjacent units.

Unit may be installed directly on wood flooring or on Class A, B, or Croof−covering material when roof curb is used.

Do not install unit in an indoor location. Do not locate air inlets nearexhaust vents or other sources of contaminated air.

18” (457)

42" (1067)

18" (457)42" (1067)

1

Required bottom condensate drain connection.Otherwise, 36” (914mm) for condensate connection.

1

Figure 2 Service Clearance Dimensional Drawing

Although unit is weatherproof, avoid locations that permit waterfrom higher level runoff and overhangs to fall onto the unit.

Select a unit mounting system that provides adequate height toallow for removal and disposal of frost and ice that will form durringthe heating−defrost mode as well as allow installation ofcondensate trap per requirements. Refer to Step 9 — InstallExternal Condensate Trap and Line – for required trap dimensions.

Roof mount

Check building codes for weight distribution requirements. Unitoperating weight is shown in Table 1.

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate differentsequences for the steps of unit installation. For example, oncurb−mounted units, some accessories must be installed on theunit before the unit is placed on the curb. Review the following forrecommended sequences for installation steps.

Curb−mounted installationInstall curbInstall field−fabricated ductwork inside curbInstall accessory thru−base service connection package (affectscurb and unit) (refer to accessory installation instructions fordetails)Prepare bottom condensate drain connection to suit plannedcondensate line routing (refer to Step 9 for details)

Rig and place unitInstall outdoor air hoodInstall condensate line trap and pipingMake electrical connectionsInstall other accessories

Pad−mounted installation

Prepare pad and unit supportsCheck and tighten the bottom condensate drain connection plugRig and place unitConvert unit to side duct connection arrangementInstall field−fabricated ductwork at unit duct openingsInstall outdoor air hoodInstall condensate line trap and pipingMake electrical connectionsInstall other accessories

Frame−mounted installation

Frame−mounted applications generally follow the sequence fora curb installation. Adapt as required to suit specific installationplan.

Step 3 — Inspect unit

Inspect unit for transportation damage. File any claim withtransportation agency.

Confirm before installation of unit that voltage, amperage andcircuit protection requirements listed on unit data plate agree withpower supply provided.

Step 4 — Provide Unit Support

Roof Curb Mount

Accessory roof curb details and dimensions are shown in Fig. 3.Assemble and install accessory roof curb in accordance withinstructions shipped with the curb.

NOTE: The gasketing of the unit to the roof curb is critical for awatertight seal. Install gasket supplied with the roof curb as shownin Fig. 5. Improperly applied gasket can also result in air leaks andpoor unit performance.

Curb should be level. This is necessary for unit drain to functionproperly. Unit leveling tolerances are show in Fig. 3. Refer toAccessory Roof Curb Installation Instructions for additionalinformation as required.

Install insulation, cant strips, roofing felt, and counter flashing asshown. Ductwork must be attached to curb and not to the unit. Theaccessory thru−the−base power package must be installed before theunit is set on the roof curb.

If electric and control wiring is to be routed through the basepan,attach the accessory thru−the−base service connections to thebasepan in accordance with the accessory installation instructions.

Slab Mount (Horizontal Units Only)

Provide a level concrete slab that extends a minimum of 6 in. (150mm) beyond unit cabinet. Install a gravel apron in front ofcondenser coil air inlet to prevent grass and foliage fromobstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Alternate Unit Support (In Lieu of Curb or Slab Mount)

A non−combustible sleeper rail can be used in the unit curb supportarea. If sleeper rails cannot be used, support the long sides of the unitwith a minimum of 3 equally spaced 4−in. x 4−in. (102 mm x 102mm) pads on each side.

Page 7: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 7

Table 1 – Operating Weights

RHSUNITS LB (KG)

090 102 120Base Unit 885 (401) 910 (413) 1050 (476)Economizer

Vertical 80 (36) 80 (36) 80 (36)Horizontal 105 (48) 105 (48) 105 (48)

Curb14−in/356 mm 143 (65) 143 (65) 143 (65)24−in/610 mm 153 (69) 153 (69) 153 (69)

A-B0.5” (13)

B-C1.0” (25)

A-C1.0” (25)

MAXIMUM ALLOWABLEDIFFERENCE IN. (MM)

Figure 3 Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall notexceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112Pa) without economizer.

Cabinet return-air static pressure (a negative condition) shall notexceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112Pa) without economizer.For vertical ducted applications, secure all ducts to roof curb andbuilding structure. Do not connect ductwork to unit.

Insulate and weatherproof all external ductwork, joints, and roofopenings with counter flashing and mastic in accordance withapplicable codes.

Ducts passing through unconditioned spaces must be insulatedand covered with a vapor barrier.If a plenum return is used on a vertical unit, the return should beducted through the roof deck to comply with applicable fire codes.

For units with accessory electric heaters: Horizontal applicationsrequire a minimum clearance to combustible surfaces of 1−in (25mm) from duct for first 12−in (305 mm) away from unit. Verticalapplications do not require a minimum clearance.

Minimum clearance not required around ductwork.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are not requiredif top crating is left on unit. Rollers may be used to move unitacross a roof. Level by using unit frame as a reference. See Table1 and Fig. 4 for additional information.

Lifting holes are provided in base rails as shown in Fig. 5. Refer torigging instructions on unit.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.

All panels must be in place when rigging. Unit is not designed forhandling by fork truck.

CAUTION!

Before setting the unit onto the curb, recheck gasketing on curb.

Figure 4 Rigging Details

UNITMAX WEIGHT

DIMENSIONSA B C

LB KG IN MM IN MM IN MMRHS090 1235 560 88.13 2238 39.94 1024 49.38 1253RHS102 1260 572 88.13 2238 39.63 1006 49.38 1253RHS120 1695 770 88.13 2238 36.50 925 49.38 1253

NOTES: 1. Dimensions in ( ) are in millimeters.2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center

of gravity. Use wooden top to prevent rigging straps from damaging unit.

Page 8: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 008

Roof Curb Accessory A Unit SizeCRRFCURB003A01 1’ 2 “ [356]

RHS090−120CRRFCURB004A01 2’ 0” [610]

Connector Pkg. Acc. B C D Alt. Drain Hole Power Control Accessory Power

CRBTMPWR001A01

2’−8 7/16”[827]

1’ 10”[583]

1l−3/4”[44.5]

3/4” [19] NPT1l−1/4” [31.7]

NPT 1/2” [12.7] NPT 1/2” [12.7] NPTCRBTMPWR002A01

CRBTMPWR003A01 3/4” [19.0] NPT

CRBTMPWR004A011l−1/4” [31.7]

NPT

NOTES: 1. Roofcurb accessory is shipped disassembled.2. Insulated panels, 1” thick polyurethane foam, 1-3/4# density.3. Dimensions in. [ ] in millimeters.4. Roofcurb 18 ga steel on 14” curb, 16 ga steel in 24” curb.5. Attach ductwork to curb (Flanges of duct rest on curb)6. Service clearance 4' on each side.7. Direction of airflow.8. Connector pkg. CRBTMPWR001A01 and CRBTMPWR002A01 are for thru-the-curbconnections. Pkg. CRBTMPWR003A01 and CRBTMPWR004A01 are forthru-the-bottom connections.

Figure 5 Roof Curb Details RHS090−120

4'-1 3/4”[1284]

6'-6”[1581]

0'-3 5/16”[6.30]

RHS120 has single fan

15-11/16”[385]

31-3/8”

Return Air

Supply Air

41-1/16”

15-5/16”

A

Page 9: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 9

Positioning on Curb —

Position unit on roof curb so that the following clearances aremaintained: 1/4 in. (6.4 mm) clearance between the roof curb andthe base rail inside the front and rear, 0.0 in. clearance betweenthe roof curb and the base rail inside on the duct end of the unit.This will result in the distance between the roof curb and the baserail inside on the condenser end of the unit being approximatelyequal to Fig. 3, section C−C.

Although unit is weatherproof, guard against water from higherlevel runoff and overhangs.

After unit is in position, remove the compressor access panel.Holding the blocking between compressors with one hand, cut thestrapping. Carefully remove the blocking without damaging tubing,wiring, or controls. Remove the strapping and replace the accesspanel.

Remove all shipping materials and top skid. Recycle or dispose ofall shipping materials.

Step 7 — Convert to Horizontal and Connect Ductwork(when required)

Unit is shipped in the vertical duct configuration. Unit withoutfactory−installed economizer or return air smoke detector optionmay be field−converted to horizontal ducted configuration. Toconvert to horizontal configuration, remove screws from side ductopening covers and remove covers. Using the same screws, installcovers on vertical duct openings with the insulation−side down.Seals around duct openings must be tight. See Fig. 6.

Figure 6 HORIZONTAL CONVERSION PANELS

Field−supplied flanges should be attached to horizontal ductopenings and all ductwork should be secured to the flanges.Insulate and weatherproof all external ductwork, joints, and roof orbuilding openings with counter flashing and mastic in accordancewith applicable codes.

Do not cover or obscure visibility to the unit’s informative data platewhen insulating horizontal ductwork.

Step 8 — Install Outside Air Hood

Economizer Hood Removal and Setup − FactoryOption

1. The hood is shipped in knock−down form and located in the returnair compartment. It is attached to the economizer using two plastictie−wraps.

2.To gain access to the hood, remove the filter access panel. (SeeFig. 7.)

3. Locate and cut the (2) plastic tie−wraps, being careful to notdamage any wiring. (See Fig. 8.)

4. Carefully lift the hood assembly through the filter access openingand assemble per the steps outlined in Economizer Hood andTwo–Position Hood on following page.

FILTER ACCESS PANEL

OUTDOOR-AIR OPENING ANDINDOOR COIL ACCESS PANEL

COMPRESSORACCESS PANEL

Figure 7 Typical Access Panel Locations

Economizer

Cut Plastic Ties(2) Places

Remove Hood Parts

Figure 8 Economizer Wiring

Two Position Damper Hood Removal and Setup −Factory Option

1. The hood is shipped in knock−down form and assembled toa metal support tray using plastic stretch wrap. Located inthe return air compartment, the assembly’s metal tray is at-tached to the basepan and also attached to the damper us-ing two plastic tie−wraps.

2. To gain access to the hood, remove the filter access panel.(See Fig. 7.)

3. Locate the (2) screws holding the metal tray to the basepanand remove. Locate and cut the (2) plastic tie−wraps secur-ing the assembly to the damper. (See Fig. 9.) Be careful tonot damage any wiring or cut tie−wraps securing any wiring.

4. Carefully lift the hood assembly (with metal tray) through thefilter access opening and assemble per the steps outlined inEconomizer Hood and Two–Position Hood on followingpage.

Page 10: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0010

Hood Parts

Plastic Tie WrapQty (2)

Screws for Metal TrayQty (2)

Figure 9 Damper Assembly

Economizer Hood and Two−Position Hood

NOTE: If the power exhaust accessory is to be installed on theunit, the hood shipped with the unit will not be used and must bediscarded. Save the aluminum filter for use in the power exhausthood assembly.

1. The indoor coil access panel will be used as the top of thehood. Remove the screws along the sides and bottom of theindoor coil access panel. See Fig. 10.

Figure 10 Indoor Coil Access Panel Relocation

SIDEPANEL

INDOORCOILACCESSPANEL

INDOORCOILACCESSPANEL

CAULKHERE

TOPSIDEPANEL

2. Swing out indoor coil access panel and insert the hood sidesunder the panel (hood top). Use the screws provided to attachthe hood sides to the hood top. Use screws provided to attachthe hood sides to the unit. See Fig. 11.

Figure 11 Economizer Hood Construction

B

TOPPANEL

INDOOR COILACCESS PANEL

19 1/16”SCREW

HOOD DIVIDER

LEFTHOODSIDE

33 3/8”(848mm)

(483mm)

3. Remove the shipping tape holding the economizer barometricrelief damper in place.

4. Insert the hood divider between the hood sides. See Fig. 11and 12. Secure hood divider with 2 screws on each hood side.The hood divider is also used as the bottom filter rack for thealuminum filter.

5. Open the filter clips which are located underneath the hoodtop. Insert the aluminum filter into the bottom filter rack (hooddivider). Push the filter into position past the open filter clips.Close the filter clips to lock the filter into place. See Fig. 12.

Page 11: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 11

Figure 12 Economizer Filter Installation

DIVIDER

BAROMETRICRELIEF

CLEANABLEALUMINUMFILTER

FILTER

HOOD

FILTERCLIP

OUTSIDEAIR

6. Caulk the ends of the joint between the unit top panel and thehood top.

7. Replace the filter access panel.

Step 9 — Install External Condensate Trap and Line

The unit has one 3/4-in. condensate drain connection on the end ofthe condensate pan and an alternate connection on the bottom.See Fig. 13. Unit airflow configuration does not determine whichdrain connection to use. Either drain connection can be used withvertical or horizontal applications.

When using the standard side drain connection, ensure the redplug in the alternate bottom connection is tight. Do this beforesetting the unit in place. The red drain pan can be tightened with a1/2−in. square socket drive extension.

To use the alternate bottom drain connection, remove the red drainplug from the bottom connection (use a 1/2−in. square socket driveextension) and install it in the side drain connection.

Figure 13 Condensate Drain Pan (Side View)

DRAIN(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARDSIDE DRAIN

ALTERNATEBOTTOM DRAIN

The piping for the condensate drain and external trap can becompleted after the unit is in place. See Fig. 14.

Figure 14 Condensate Drain Piping Details

NOTE: Trap should be deep enough to offset maximum unit staticdifference. A 4” (102) trap is recommended.

MINIMUM PITCH1” (25mm) PER10’ (3m) OF LINE

BASE RAIL

OPENVENT

TO ROOFDRAIN

DRAIN PLUG

ROOFCURB

SEE NOTE

2˝ (51) MIN

All units must have an external trap for condensate drainage.Install a trap at least 4-in. (102 mm) deep and protect againstfreeze-up. If drain line is installed downstream from the externaltrap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3m) of run. Do not use a pipe size smaller than the unit connection(3/4 -in.).

Step 10 — Make Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury ordeath.

Do not use gas piping as an electrical ground. Unit cabinetmust have an uninterrupted, unbroken electrical ground tominimize the possibility of personal injury if an electrical faultshould occur. This ground may consist of electrical wireconnected to unit ground lug in control compartment, orconduit approved for electrical ground when installed inaccordance with NEC (National Electrical Code); ANSI/NFPA70, latest edition (in Canada, Canadian Electrical Code CSA[Canadian Standards Association] C22.1), and local electricalcodes.

! WARNING

NOTE: Check all factory and field electrical connections fortightness. Field−supplied wiring shall conform with the limitations of63�F (33�C) rise.

Field Power Supply

On a unit without a unit−mounted disconnect, connect the sourceleads to compressor contactor C and indoor fan contactor IFCpressure lugs with unit field power leads.

All units except 208/230-v units are factory wired for the voltageshown on the nameplate. If the 208/230-v unit is to be connectedto a 208-v power supply, the control transformer must be rewiredby moving the black wire with the 1/4 -in. female spade connectorfrom the 230−v connection and moving it to the 208-v 1/4 -in. maleterminal on the primary side of the transformer. Refer to unit labeldiagram for additional information. Field power wires will beconnected line−side pressure lugs on the power terminal block orat factory−installed option non−fused disconnect.

Field power wires are connected to the unit at line−side pressurelugs on compressor contactor C and indoor fan contactor IFC orterminal board (see wiring diagram label for control box component

Page 12: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0012

arrangement) or at factory−installed option non−fused disconnectswitch. Max wire size is #2 AWG (copper only). (See Fig. 16)

NOTE: TEST LEADS − Unit may be equipped with short leads(pigtails) on the field line connection points on contactor C oroptional disconnect switch. These leads are for factory run−testpurposes only; remove and discard before connecting field powerwires to unit connection points. Make field power connectionsdirectly to line connection pressure lugs only.

! WARNINGFIRE HAZARD

Failure to follow this warning could result in intermittentoperation or performance satisfaction.

Do not connect aluminum wire between disconnect switchand furnace. Use only copper wire. (See Fig. 15.)

Figure 15 Disconnect Switch and Unit

COPPER

WIRE ONLY

ELECTRICDISCONNECT

SWITCH

ALUMINUMWIRE

Units Without Factory−Installed Disconnect

When installing units, provide a disconnect switch per NEC(National Electrical Code) of adequate size. Disconnect sizing datais provided on the unit informative plate. Locate on unit cabinet orwithin sight of the unit per national or local codes. Do not cover unitinformative plate if mounting the disconnect on the unit cabinet.

Units with Factory−Installed Disconnect (80 Amp max.)

The factory−installed option disconnect switch is located in aweatherproof enclosure located under the main control box. Themanual switch handle is accessible through an opening in theaccess panel. Discard the factory test leads (see Fig. 16).

Figure 16 Power Wiring Connections

All units

All field wiring must comply with NEC and all local codes. Size wirebased on MCA (Minimum Circuit Amps) on the unit informativeplate. See Fig. 16 and the unit label diagram for power wiringconnections to the unit power terminal blocks and equipmentground. Maximum wire size is #2 ga AWG per pole.

Provide a ground−fault and short−circuit over−current protectiondevice (fuse or breaker) per NEC Article 440 (or local codes).Refer to unit informative data plate for MOCP (MaximumOver−current Protection) device size.

All field wiring must comply with the NEC and local requirements.

Page 13: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 13

Convenience Outlets

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury ordeath.

Units with convenience outlet circuits may use multipledisconnects. Check convenience outlet for power statusbefore opening unit for service. Locate its disconnect switch, ifappropriate, and open it. Tag−out this switch, if necessary.

! WARNING

One type of factory installed convenience outlet is offered on RHSmodels: Non−powered which provide a 125−volt GFCI(ground−fault circuit−interrupter) duplex receptacle rated at 15−Abehind a hinged waterproof access cover, located on the endpanel of the unit. See Fig. 17.

Figure 17 Convenience Outlet Locations

Installing Weatherproof Cover

A weatherproof while-in-use cover for the factory-installedconvenience outlets is now required by UL standards. This covercannot be factory-mounted due its depth; it must be installed atunit installation. For shipment, the convenience outlet is coveredwith a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control box. Thekit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCEOUTLET.

Remove the blank cover plate at the convenience outlet; discardthe blank cover.

Loosen the two screws at the GFCI duplex outlet, untilapproximately 1/2-in (13 mm) under screw heads are exposed.Press the gasket over the screw heads. Slip the backing plate overthe screw heads at the keyhole slots and align with the gasket;tighten the two screws until snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as shown inFig. 18. Remove two slot fillers in the bottom of the cover to permitservice tool cords to exit the cover. Check for full closing andlatching.

Figure 18 Waterproof Cover Installation

RECEPTACLENOT INCLUDED

COVER – WHILE-IN-USE WEATHERPROOF

BASE PLATE FOR GFCI RECEPTACLE

Non−powered convenience outlet: This type requires the fieldinstallation of a general−purpose 125−volt 15−A circuit poweredfrom a source elsewhere in the building. Observe national andlocal codes when selecting wire size, fuse or breaker requirementsand disconnect switch size and location. Route 125−v powersupply conductors into the bottom of the utility box containing theduplex receptacle.

Test the GFCI receptacle by pressing the TEST button on the faceof the receptacle to trip and open the receptacle. Check for propergrounding wires and power line phasing if the GFCI receptacledoes not trip as required. Press the RESET button to clear thetripped condition.

Using unit−mounted convenience outlets: Units with unit−moundedconvenience outlet circuits will often require that two disconnectsbe opened to de−energize all power to the unit. Treat all units aselectrically energized until the convenience outlet power is alsochecked and de−energization is confirmed. Observe NationalElectrical Code Article 210, Branch Circuits, for use ofconvenience outlets.

Field Installed Option Thru−Base Connections

This service connection kit consists of a 1/2−in electrical bulkheadconnector and a 3/4−in electrical bulkhead connector, allfactory−installed in the embossed (raised) section of the unitbasepan in the condenser section. The 1/2−in bulkhead connectorenables the low−voltage control wires to pass through thebasepan. The 3/4−in electrical bulkhead connector allows thehigh−voltage power wires to pass through the basepan. See Fig.19.

Check tightness of connector lock nuts before connecting electricalconduits.

Page 14: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0014

Figure 19 Thru−Base Connection Fittings

LOW VOLTAGECONDUITCONNECTOR

HIGH VOLTAGECONDUITCONNECTOR

Field−supplied and field−installed liquidtight conduit connectorsand conduit may be attached to the connectors on the basepan.Pull correctly rated high voltage and low voltage throughappropriate conduits. Connect the power conduit to the internaldisconnect (if unit is so equipped) or to the external disconnect(through unit side panel). A hole must be field cut in the maincontrol box bottom on the left side so the 24−v control connectionscan be made. Connect the control power conduit to the unit controlbox at this hole.

Units Equipped With Thru−Base Connections

1. Install power wiring conduit through side panel openings. In-stall conduit between disconnect and control box.

2. Install power lines to terminal connections as shown in Fig.16.

All Units

Voltage to compressor terminals during operation must be withinvoltage range indicated on unit nameplate. See Table 5. On3−phase units, voltages between phases must be balanced within2% and the current within 10%. Use the formula shown in thelegend for Table 5, Note 2 to determine the percent of voltageimbalance. Operation on improper line voltage or excessive phaseimbalance constitutes abuse and may cause damage to electricalcomponents. Such operation would invalidate any applicable ICPwarranty.

Field Control Wiring

The RHS unit requires an external temperature control device.This device can be a thermostat emulation device provided as partof a third−party Building Management System.

Thermostat

Install an approved accessory 2 stage Cooling/Heating thermostataccording to installation instructions included with the accessory.The RHS models do not require a thermostat with an O function tocontrol the reversing valve operation. If using an electronicthermostat, configure it for “non−heat pump” operation. Locate thethermostat accessory on a solid wall in the conditioned space tosense average temperature in accordance with the thermostatinstallation instructions.

If the thermostat contains a logic circuit requiring 24−v power, usea thermostat cable or equivalent single leads of different colorswith minimum of seven leads. If the thermostat does not require a24−v source (no “C” connection required), use a thermostat cableor equivalent with minimum of six leads. Check the thermostatinstallation instructions for additional features which might requireadditional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American WireGage) insulated wire (35�C minimum). For 50 to 75 ft. (15 to 23 m),use no. 16 AWG insulated wire (35�C minimum). For over 75 ft.(23 m), use no. 14 AWG insulated wire (35�C minimum). All wiresizes larger than no. 18 AWG cannot be directly connected to thethermostat and will require a junction box and splice at thethermostat.

Figure 20 Low Voltage Connections

X

C

G

W2

W1

R

Y2

Y1

X

C

G

W2

W1

R

Y2

Y1

Thermostat

TerminalBoard

Unit without thru−base connection kit

Pass the thermostat control wires through the hole provided in thecorner post; then feed the wires through the raceway built into thecorner post to the control box. Pull the wires over to the terminalstrip on the upper−left corner of the Central Terminal Board (CTB).See Fig. 21.

NOTE: If thru−the−bottom connections accessory is used, refer tothe accessory installation instructions for information on routingpower and control wiring.

Heat Anticipator Settings

Set heat anticipator settings at 0.14 amp for the first stage and0.14 amp for second−stage heating, when available.

Page 15: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 15

Figure 21 Field Control Wiring Raceway

RACEWAY

HOLE IN END PANEL (HIDDEN)

Electric Heaters

RHS units may be equipped with field−installed accessory electricheaters. The heaters are modular in design, with heater framesholding open coil resistance wires strung through ceramicinsulators, line−break limit switches and a control contactor. One ortwo heater modules may be used in a unit.Heater modules are installed in the compartment below the indoor(supply) fan outlet. Access is through the indoor access panel.Heater modules slide into the compartment on tracks along thebottom of the heater opening. See Fig. 22, Fig. 23 and Fig. 24.

Not all available heater modules may be used in every unit. Useonly those heater modules that are UL listed for use in a specificsize unit. Refer to the label on the unit cabinet for the list ofapproved heaters.Unit heaters are marked with Heater Model Numbers. But heatersare ordered as and shipped in cartons marked with acorresponding heater Sales Package part number. See Table 2 forcorrelation between heater Model Number and Sales Package partnumber.NOTE: The value in position 9 of the part number differs betweenthe sales package part number (value is 1 or 3) and a bare heatermodel number (value is 0).

Figure 22 Typical Access Panel Location

DISCONNECT MOUNTINGLOCATION

UNIT BLOCK-OFFPANEL

OUTDOORACCESS PANEL

INDOORACCESSPANEL

Table 2 – Heater Model Number

Bare Heater Model Number C R H E A T E R 0 0 1 A 0 0

Heater Package Model NumberIncludes: Bare Heater Carton and packing materials Installation sheet

C R H E A T E R 1 0 1 A 0 0

Figure 23 Typical Component Location

DISCONNECTMOUNTINGLOCATION

EMT OR RIGID CONDUIT(FIELD-SUPPLIED)

SINGLEPOINT BOX

CENTERPOST

HEATERCOVERS

HEATERMOUNTINGBRACKET

HEATERMODULE(LOCATION 2)

HEATERMODULE(LOCATION 1)

SINGLE POINTBOXMOUNTINGSCREW

BRACKET ANDCONDUITDRIP BOOT

MAINCONTROLBOX

CONTROL WIRE TERMINAL BLOCK

MANUAL RESETLIMIT SWITCH

Page 16: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0016

Figure 24 Typical Module Installation

TRACK

FLANGE

Single Point Boxes and Supplementary Fuses — When the unitMOCP device value exceeds 60−A, unit−mounted supplementaryfuses are required for each heater circuit. These fuses areincluded in accessory Single Point Boxes, with power distributionand fuse blocks. The single point box will be installed directlyunder the unit control box, just to the left of the partition separatingthe indoor section (with electric heaters) from the outdoor section.The Single Point Box has a hinged access cover. See Fig. 25.The Single Point Box also includes pigtails to complete the wiringbetween the Single Point Box and the unit’s main control boxterminals. Refer to the accessory heater and Single Point Boxinstallation instructions for details on tap connections

Figure 25 Typical Single Point Installation

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

1113

2123

OD

22.2

3123

ISTED AIRNDITIONINGUIP ACCESS 346N.

P / N 2- 5610-4 REV

1113

2123

CONTROLBOX

BUSHING

SINGLEPOINT BOXMOUNTINGSCREWS

FOAMBUSHING

DRIP BOOTBRACKETMOUNTINGSCREWS

HEATERRELAYS

POWERWIRES

HEATERMOUNTINGSCREWS

All fuses on RHS units are 60−A. (Note that all heaters arequalified for use with a 60−A fuse, regardless of actual heaterampacity, so only 60−A fuses are necessary.)Single Point Boxes without Fuses — Refer to accessory heaterand Single Point Box installation instructions for details on tapconnections.Low−Voltage Control Connections — Run the low−voltagecontrol leads from the heater module(s) − VIO and BRN (two ofeach if two modules are installed; identify for Module #1) − to the4−pole terminal board TB4 located on the heater bulkhead to theleft of Heater #1. Connect the VIO leads from Heater #1 andHeater #2 to terminal TB4−1. Connect the BRN leads to terminalTB4−3. See Fig. 26.

Figure 26 Accessory Electric Heater Control Connections

DEFROSTBOARD

ORN

BRN

FieldConnections

E-HEAT

P3-3

1 3

ORN BRN

VIO BRN BRNVIO

TB4

VIO HR2

HR1

BRN

VIO BRN

Elec Htr

HR1: On Heater 1 in Position #1HR2: On Heater 2 in Position #2 (if installed)

Figure 27 RHS Control Box Component Locations

Page 17: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 17

Table 3 – Unit Wire/Fuse or HACR Breaker Sizing Data − Single Speed Indoor Fan MotorU

NIT

UN

IT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER

***A00Nom (kW) FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

50T

CQ

D08

208/2

30-

3-

60

STD

NONE - - 38/38 50/50 40/39 210 42/42 50/50 44/44 214

117A 7.8/10.4 21.7/25.0 65/69 70/70 65/68 232/235 69/73 70/80 69/72 236/239

110A 12.0/16.0 33.4/38.5 80/86 80/90 78/83 243/249 84/90 90/90 82/88 247/253

111A 18.6/24.8 51.7/59.7 103/112 110/125 99/108 262/270 107/116 110/125 103/112 266/274

112A 24.0/32.0 66.7/77.0 122/134 125/150 116/128 277/287 125/138 125/150 121/132 281/291

112A+117A 31.8/42.4 88.4/102.0 149/165 150/175 141/157 387/414 152/169 175/175 146/161 391/418

MED

NONE - - 41/41 50/50 43/43 246 45/45 50/50 48/47 250

117A 7.8/10.4 21.7/25.0 68/72 70/80 68/72 268/271 72/76 80/80 73/76 272/275

110A 12.0/16.0 33.4/38.5 83/89 90/90 82/87 279/285 87/93 90/100 86/92 283/289

111A 18.6/24.8 51.7/59.7 106/116 110/125 103/112 298/306 110/120 110/125 107/116 302/310

112A 24.0/32.0 66.7/77.0 125/137 125/150 120/132 313/323 129/141 150/150 124/136 317/327

112A+117A 31.8/42.4 88.4/102.0 152/169 175/175 145/160 423/450 156/173 175/175 149/165 427/454

HIGH

NONE - - 41/41 50/50 43/43 246 45/45 50/50 48/47 250

117A 7.8/10.4 21.7/25.0 68/72 70/80 68/72 268/271 72/76 80/80 73/76 272/275

110A 12.0/16.0 33.4/38.5 83/89 90/90 82/87 279/285 87/93 90/100 86/92 283/289

111A 18.6/24.8 51.7/59.7 106/116 110/125 103/112 298/306 110/120 110/125 107/116 302/310

112A 24.0/32.0 66.7/77.0 125/137 125/150 120/132 313/323 129/141 150/150 124/136 317/327

112A+117A 31.8/42.4 88.4/102.0 152/169 175/175 145/160 423/450 156/173 175/175 149/165 427/454

460-

3-

60

STD

NONE - - 18 20 19 104 20 25 21 106

116A 13.9 16.7 39 40 38 121 41 45 40 123

113A 16.5 19.8 43 45 42 124 45 45 44 126

114A 27.8 33.4 60 60 57 137 62 70 59 139

115A 33.0 39.7 68 70 64 144 70 70 66 146

114A+116A 41.7 50.2 81 90 76 204 83 90 79 206

MED

NONE - - 20 25 21 122 22 25 23 124

116A 13.9 16.7 41 45 40 139 43 45 42 141

113A 16.5 19.8 45 45 43 142 47 50 46 144

114A 27.8 33.4 62 70 59 155 64 70 61 157

115A 33.0 39.7 70 70 66 162 71 80 68 164

114A+116A 41.7 50.2 83 90 78 222 85 90 81 224

HIGH

NONE - - 20 25 21 122 22 25 23 124

116A 13.9 16.7 41 45 40 139 43 45 42 141

113A 16.5 19.8 45 45 43 142 47 50 46 144

114A 27.8 33.4 62 70 59 155 64 70 61 157

115A 33.0 39.7 70 70 66 162 71 80 68 164

114A+116A 41.7 50.2 83 90 78 222 85 90 81 224

575-

3-

60

STD

NONE - - 13 15 13 77 17 20 18 81

118A 17.0 20.4 39 40 37 97 42 45 41 101

119A 34.0 40.9 64 70 60 118 68 70 65 122

MED

NONE - - 14 20 15 92 18 20 19 96

118A 17.0 20.4 40 40 38 112 44 45 43 116

119A 34.0 40.9 65 70 62 133 69 70 66 137

HIGH

NONE - - 14 20 15 92 18 20 19 96

118A 17.0 20.4 40 40 38 112 44 45 43 116

119A 34.0 40.9 65 70 62 133 69 70 66 137

NOTE: See page 22 for table legend and notes.

Page 18: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0018

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data − Single Speed Indoor Fan Motor (cont)U

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER

***A00Nom (kW) FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

50T

CQ

D09 -

Un

its p

rod

uce

d o

n o

r aft

er

02/0

9/2

015

208/2

30-

3-

60

STD

NONE - - 40/40 50/50 42/42 225 44/44 50/50 46/46 229

117A 7.8/10.4 21.7/25.0 68/71 70/80 67/70 247/250 71/75 80/80 71/75 251/254

110A 12.0/16.0 33.4/38.5 82/88 90/90 80/86 258/264 86/92 90/100 85/90 262/268

111A 18.6/24.8 51.7/59.7 105/115 110/125 101/110 277/285 109/119 110/125 106/115 281/289

112A 24.0/32.0 66.7/77.0 124/136 125/150 119/130 292/302 128/140 150/150 123/134 296/306

112A+117A 31.8/42.4 88.4/102.0 151/168 175/175 144/159 402/429 155/171 175/175 148/163 406/433

MED

NONE - - 44/44 50/50 46/45 261 47/47 60/60 50/50 265

117A 7.8/10.4 21.7/25.0 71/75 80/80 70/74 283/286 75/79 80/80 75/79 287/290

110A 12.0/16.0 33.4/38.5 85/92 90/100 84/90 294/300 89/96 90/100 88/94 298/304

111A 18.6/24.8 51.7/59.7 108/118 110/125 105/114 313/321 112/122 125/125 109/118 317/325

112A 24.0/32.0 66.7/77.0 127/140 150/150 122/134 328/338 131/144 150/150 127/138 332/342

112A+117A 31.8/42.4 88.4/102.0 154/171 175/175 147/163 438/465 158/175 175/175 152/167 442/469

HIGH

NONE - - 44/44 50/50 46/45 261 47/47 60/60 50/50 265

117A 7.8/10.4 21.7/25.0 71/75 80/80 70/74 283/286 75/79 80/80 75/79 287/290

110A 12.0/16.0 33.4/38.5 85/92 90/100 84/90 294/300 89/96 90/100 88/94 298/304

111A 18.6/24.8 51.7/59.7 108/118 110/125 105/114 313/321 112/122 125/125 109/118 317/325

112A 24.0/32.0 66.7/77.0 127/140 150/150 122/134 328/338 131/144 150/150 127/138 332/342

112A+117A 31.8/42.4 88.4/102.0 154/171 175/175 147/163 438/465 158/175 175/175 152/167 442/469

460-

3-

60

STD

NONE - - 19 20 19 118 20 25 21 120

116A 13.9 16.7 40 40 38 135 41 45 40 137

113A 16.5 19.8 43 45 42 138 45 45 44 140

114A 27.8 33.4 60 60 58 151 62 70 60 153

115A 33.0 39.7 68 70 65 158 70 70 67 160

114A+116A 41.7 50.2 81 90 77 218 83 90 79 220

MED

NONE - - 20 25 21 136 22 25 23 138

116A 13.9 16.7 41 45 40 153 43 45 42 155

113A 16.5 19.8 45 45 44 156 47 50 46 158

114A 27.8 33.4 62 70 59 169 64 70 62 171

115A 33.0 39.7 70 70 67 176 72 80 69 178

114A+116A 41.7 50.2 83 90 79 236 85 90 81 238

HIGH

NONE - - 20 25 21 136 22 25 23 138

116A 13.9 16.7 41 45 40 153 43 45 42 155

113A 16.5 19.8 45 45 44 156 47 50 46 158

114A 27.8 33.4 62 70 59 169 64 70 62 171

115A 33.0 39.7 70 70 67 176 72 80 69 178

114A+116A 41.7 50.2 83 90 79 236 85 90 81 238

575-

3-

60

STD

NONE - - 16 20 16 85 19 25 20 89

118A 17.0 20.4 41 45 39 105 45 45 43 109

119A 34.0 40.9 67 70 63 126 70 80 67 130

MED

NONE - - 17 20 17 100 21 25 21 104

118A 17.0 20.4 42 45 40 120 46 50 45 124

119A 34.0 40.9 68 70 64 141 72 80 68 145

HIGH

NONE - - 17 20 17 100 21 25 21 104

118A 17.0 20.4 42 45 40 120 46 50 45 124

119A 34.0 40.9 68 70 64 141 72 80 68 145

NOTE: See page 22 for table legend and notes.

Page 19: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 19

Table 3 − Unit Wire/Fuse or HACR Breaker Sizing Data − Single Speed Indoor Fan Motor (cont)U

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER

***A00Nom (kW) FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

50T

CQ

D09 -

Un

its p

rod

uce

d o

n o

r p

rio

r to

02/0

8/2

015

208/2

30-

3-

60

STD

NONE - - 42/42 50/50 44/43 218 46/46 60/60 48/48 222

117A 7.8/10.4 21.7/25.0 69/73 70/80 69/72 240/243 73/77 80/80 73/76 244/247

110A 12.0/16.0 33.4/38.5 84/90 90/90 82/88 251/257 88/94 90/100 86/92 255/261

111A 18.6/24.8 51.7/59.7 107/117 110/125 103/112 270/278 111/120 125/125 107/116 274/282

112A 24.0/32.0 66.7/77.0 126/138 150/150 120/132 285/295 130/142 150/150 125/136 289/299

112A+117A 31.8/42.4 88.4/102.0 153/170 175/175 145/161 395/422 157/173 175/175 150/165 399/426

MED

NONE - - 46/45 60/60 47/47 254 49/49 60/60 52/52 258

117A 7.8/10.4 21.7/25.0 73/77 80/80 72/76 276/279 76/81 80/90 77/80 280/283

110A 12.0/16.0 33.4/38.5 87/94 90/100 86/91 287/293 91/97 100/100 90/96 291/297

111A 18.6/24.8 51.7/59.7 110/120 110/125 107/116 306/314 114/124 125/125 111/120 310/318

112A 24.0/32.0 66.7/77.0 129/142 150/150 124/136 321/331 133/146 150/150 128/140 325/335

112A+117A 31.8/42.4 88.4/102.0 156/173 175/175 149/164 431/458 160/177 175/200 153/169 435/462

HIGH

NONE - - 46/45 60/60 47/47 254 49/49 60/60 52/52 258

117A 7.8/10.4 21.7/25.0 73/77 80/80 72/76 276/279 76/81 80/90 77/80 280/283

110A 12.0/16.0 33.4/38.5 87/94 90/100 86/91 287/293 91/97 100/100 90/96 291/297

111A 18.6/24.8 51.7/59.7 110/120 110/125 107/116 306/314 114/124 125/125 111/120 310/318

112A 24.0/32.0 66.7/77.0 129/142 150/150 124/136 321/331 133/146 150/150 128/140 325/335

112A+117A 31.8/42.4 88.4/102.0 156/173 175/175 149/164 431/458 160/177 175/200 153/169 435/462

460-

3-

60

STD

NONE - - 20 25 20 109 21 25 22 111

116A 13.9 16.7 40 40 39 126 42 45 41 128

113A 16.5 19.8 44 45 43 129 46 50 45 131

114A 27.8 33.4 61 70 58 142 63 70 60 144

115A 33.0 39.7 69 70 66 149 71 80 68 151

114A+116A 41.7 50.2 82 90 78 209 84 90 80 211

MED

NONE - - 21 25 22 127 23 25 24 129

116A 13.9 16.7 42 45 41 144 44 45 43 146

113A 16.5 19.8 46 50 45 147 48 50 47 149

114A 27.8 33.4 63 70 60 160 65 70 62 162

115A 33.0 39.7 71 80 68 167 73 80 70 169

114A+116A 41.7 50.2 84 90 80 227 86 90 82 229

HIGH

NONE - - 21 25 22 127 23 25 24 129

116A 13.9 16.7 42 45 41 144 44 45 43 146

113A 16.5 19.8 46 50 45 147 48 50 47 149

114A 27.8 33.4 63 70 60 160 65 70 62 162

115A 33.0 39.7 71 80 68 167 73 80 70 169

114A+116A 41.7 50.2 84 90 80 227 86 90 82 229

575-

3-

60

575-

3-

60

STD

NONE - - 15 20 15 81 19 20 20 85

118A 17.0 20.4 41 45 39 101 44 45 43 105

119A 34.0 40.9 66 70 62 122 70 70 67 126

MED

NONE - - 16 20 17 96 20 25 21 100

118A 17.0 20.4 42 45 40 116 46 50 44 120

119A 34.0 40.9 67 70 64 137 71 80 68 141

HIGH

NONE - - 16 20 17 96 20 25 21 100

118A 17.0 20.4 42 45 40 116 46 50 44 120

119A 34.0 40.9 67 70 64 137 71 80 68 141

NOTE: See page 22 for table legend and notes.

Page 20: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0020

Table 4 – Unit Wire/Fuse or HACR Breaker Sizing Data − Two Speed Indoor Fan MotorU

NIT

UN

IT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER

***A00Nom (kW) FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

50T

CQ

D08

208/2

30-

3-

60

STD

NONE - - 39/39 50/50 40/40 197 43/42 50/50 45/44 201

117A 7.8/10.4 21.7/25.0 66/70 70/70 65/69 219/222 70/74 70/80 70/73 223/226

110A 12.0/16.0 33.4/38.5 80/87 90/90 79/84 230/236 84/90 90/90 83/89 234/240

111A 18.6/24.8 51.7/59.7 103/113 110/125 100/109 249/257 107/117 110/125 104/113 253/261

112A 24.0/32.0 66.7/77.0 122/135 125/150 117/129 264/274 126/139 150/150 121/133 268/278

112A+117A 31.8/42.4 88.4/102.0 149/166 150/175 142/157 374/401 153/170 175/175 146/162 378/405

MED

NONE - - 42/41 50/50 43/43 227 45/45 50/50 48/47 231

117A 7.8/10.4 21.7/25.0 69/72 70/80 68/71 249/252 72/76 80/80 73/76 253/256

110A 12.0/16.0 33.4/38.5 83/89 90/90 82/87 260/266 87/93 90/100 86/91 264/270

111A 18.6/24.8 51.7/59.7 106/115 110/125 103/111 279/287 110/119 110/125 107/116 283/291

112A 24.0/32.0 66.7/77.0 125/137 125/150 120/131 294/304 129/141 150/150 125/135 298/308

112A+117A 31.8/42.4 88.4/102.0 152/168 175/175 145/160 404/431 156/172 175/175 150/164 408/435

HIGH

NONE - - 42/41 50/50 43/43 227 45/45 50/50 48/47 231

117A 7.8/10.4 21.7/25.0 69/72 70/80 68/71 249/252 72/76 80/80 73/76 253/256

110A 12.0/16.0 33.4/38.5 83/89 90/90 82/87 260/266 87/93 90/100 86/91 264/270

111A 18.6/24.8 51.7/59.7 106/115 110/125 103/111 279/287 110/119 110/125 107/116 283/291

112A 24.0/32.0 66.7/77.0 125/137 125/150 120/131 294/304 129/141 150/150 125/135 298/308

112A+117A 31.8/42.4 88.4/102.0 152/168 175/175 145/160 404/431 156/172 175/175 150/164 408/435

460-

3-

60

STD

NONE - - 19 20 19 97 20 25 21 99

116A 13.9 16.7 40 40 38 114 41 45 40 116

113A 16.5 19.8 43 45 42 117 45 45 44 119

114A 27.8 33.4 60 60 58 130 62 70 60 132

115A 33.0 39.7 68 70 65 137 70 70 67 139

114A+116A 41.7 50.2 81 90 77 197 83 90 79 199

MED

NONE - - 20 25 20 113 21 25 22 115

116A 13.9 16.7 40 40 39 130 42 45 42 132

113A 16.5 19.8 44 45 43 133 46 50 45 135

114A 27.8 33.4 61 70 59 146 63 70 61 148

115A 33.0 39.7 69 70 66 153 71 80 68 155

114A+116A 41.7 50.2 82 90 78 213 84 90 80 215

HIGH

NONE - - 20 25 20 113 21 25 22 115

116A 13.9 16.7 40 40 39 130 42 45 42 132

113A 16.5 19.8 44 45 43 133 46 50 45 135

114A 27.8 33.4 61 70 59 146 63 70 61 148

115A 33.0 39.7 69 70 66 153 71 80 68 155

114A+116A 41.7 50.2 82 90 78 213 84 90 80 215

575-

3-

60

STD

NONE - - 14 20 15 79 18 20 19 83

118A 17.0 20.4 40 40 38 99 44 45 43 103

119A 34.0 40.9 65 70 62 120 69 70 66 124

MED

NONE - - 16 20 17 92 20 25 21 96

118A 17.0 20.4 42 45 40 112 45 45 45 116

119A 34.0 40.9 67 70 64 133 71 80 68 137

HIGH

NONE - - 16 20 17 92 20 25 21 96

118A 17.0 20.4 42 45 40 112 45 45 45 116

119A 34.0 40.9 67 70 64 133 71 80 68 137

NOTE: See page 22 for table legend and notes.

Page 21: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 21

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data − Two Speed Indoor Fan Motor (cont)U

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER

***A00Nom (kW) FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

50T

CQ

D09 -

Un

its p

rod

uce

d o

n o

r aft

er

02/0

9/2

015

208/2

30-

3-

60

STD

NONE - - 41/41 50/50 43/42 212 45/45 50/50 47/47 216

117A 7.8/10.4 21.7/25.0 68/72 70/80 68/71 234/237 72/76 80/80 72/75 238/241

110A 12.0/16.0 33.4/38.5 83/89 90/90 81/87 245/251 87/93 90/100 85/91 249/255

111A 18.6/24.8 51.7/59.7 106/116 110/125 102/111 264/272 110/119 110/125 106/115 268/276

112A 24.0/32.0 66.7/77.0 124/137 125/150 119/131 279/289 128/141 150/150 124/135 283/293

112A+117A 31.8/42.4 88.4/102.0 152/168 175/175 144/160 389/416 155/172 175/175 149/164 393/420

MED

NONE - - 44/43 50/50 46/45 242 48/47 60/60 50/49 246

117A 7.8/10.4 21.7/25.0 71/74 80/80 71/74 264/267 75/78 80/80 75/78 268/271

110A 12.0/16.0 33.4/38.5 86/91 90/100 84/89 275/281 89/95 90/100 89/93 279/285

111A 18.6/24.8 51.7/59.7 109/118 110/125 105/114 294/302 112/122 125/125 110/118 298/306

112A 24.0/32.0 66.7/77.0 127/139 150/150 122/133 309/319 131/143 150/150 127/138 313/323

112A+117A 31.8/42.4 88.4/102.0 154/171 175/175 147/162 419/446 158/174 175/175 152/167 423/450

HIGH

NONE - - 44/43 50/50 46/45 242 48/47 60/60 50/49 246

117A 7.8/10.4 21.7/25.0 71/74 80/80 71/74 264/267 75/78 80/80 75/78 268/271

110A 12.0/16.0 33.4/38.5 86/91 90/100 84/89 275/281 89/95 90/100 89/93 279/285

111A 18.6/24.8 51.7/59.7 109/118 110/125 105/114 294/302 112/122 125/125 110/118 298/306

112A 24.0/32.0 66.7/77.0 127/139 150/150 122/133 309/319 131/143 150/150 127/138 313/323

112A+117A 31.8/42.4 88.4/102.0 154/171 175/175 147/162 419/446 158/174 175/175 152/167 423/450

460-

3-

60

STD

NONE - - 19 25 20 111 21 25 22 113

116A 13.9 16.7 40 40 39 128 42 45 41 130

113A 16.5 19.8 44 45 42 131 46 50 44 133

114A 27.8 33.4 61 70 58 144 63 70 60 146

115A 33.0 39.7 69 70 65 151 70 80 67 153

114A+116A 41.7 50.2 82 90 77 211 84 90 79 213

MED

NONE - - 20 25 21 127 22 25 23 129

116A 13.9 16.7 41 45 40 144 43 45 42 146

113A 16.5 19.8 45 45 43 147 46 50 45 149

114A 27.8 33.4 62 70 59 160 63 70 61 162

115A 33.0 39.7 70 70 66 167 71 80 68 169

114A+116A 41.7 50.2 83 90 78 227 84 90 80 229

HIGH

NONE - - 20 25 21 127 22 25 23 129

116A 13.9 16.7 41 45 40 144 43 45 42 146

113A 16.5 19.8 45 45 43 147 46 50 45 149

114A 27.8 33.4 62 70 59 160 63 70 61 162

115A 33.0 39.7 70 70 66 167 71 80 68 169

114A+116A 41.7 50.2 83 90 78 227 84 90 80 229

575-

3-

60

STD

NONE - - 17 20 17 87 21 25 21 91

118A 17.0 20.4 42 45 40 107 46 50 45 111

119A 34.0 40.9 68 70 64 128 72 80 68 132

MED

NONE - - 18 20 19 100 22 25 23 104

118A 17.0 20.4 44 45 42 120 48 50 47 124

119A 34.0 40.9 70 70 66 141 73 80 70 145

HIGH

NONE - - 18 20 19 100 22 25 23 104

118A 17.0 20.4 44 45 42 120 48 50 47 124

119A 34.0 40.9 70 70 66 141 73 80 70 145

NOTE: See page 22 for table legend and notes.

Page 22: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0022

Table 4 − Unit Wire/Fuse or HACR Breaker Sizing Data − Two Speed Indoor Fan Motor (cont)U

NIT

NO

M.

V-

Ph

-H

Z

IFMTYPE

ELEC. HTR NO C.O. or UNPWR C.O.

CRHEATER

***A00Nom (kW) FLA

NO P.E. w/ P.E. (pwrd fr/unit)

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

MCA

MAX FUSEor HACR

BRKR

DISC. SIZE

FLA LRA FLA LRA

50T

CQ

D09 -

Un

its p

rod

uce

d o

n o

r p

rio

r to

02/0

8/2

015

208/2

30-

3-

60

STD

NONE - - 43/43 50/50 44/44 205 47/47 60/60 49/48 209

117A 7.8/10.4 21.7/25.0 70/74 80/80 69/73 227/230 74/78 80/80 74/77 231/234

110A 12.0/16.0 33.4/38.5 85/91 90/100 83/88 238/244 89/95 90/100 87/93 242/248

111A 18.6/24.8 51.7/59.7 108/117 110/125 104/113 257/265 111/121 125/125 108/117 261/269

112A 24.0/32.0 66.7/77.0 126/139 150/150 121/133 272/282 130/143 150/150 125/137 276/286

112A+117A 31.8/42.4 88.4/102.0 153/170 175/175 146/161 382/409 157/174 175/175 150/166 386/413

MED

NONE - - 46/45 60/60 47/47 235 50/49 60/60 52/51 239

117A 7.8/10.4 21.7/25.0 73/76 80/80 72/75 257/260 77/80 80/80 77/80 261/264

110A 12.0/16.0 33.4/38.5 88/93 90/100 86/91 268/274 91/97 100/100 90/95 272/278

111A 18.6/24.8 51.7/59.7 110/120 110/125 107/115 287/295 114/123 125/125 111/120 291/299

112A 24.0/32.0 66.7/77.0 129/141 150/150 124/135 302/312 133/145 150/150 129/139 306/316

112A+117A 31.8/42.4 88.4/102.0 156/172 175/175 149/164 412/439 160/176 175/200 154/168 416/443

HIGH

NONE - - 46/45 60/60 47/47 235 50/49 60/60 52/51 239

117A 7.8/10.4 21.7/25.0 73/76 80/80 72/75 257/260 77/80 80/80 77/80 261/264

110A 12.0/16.0 33.4/38.5 88/93 90/100 86/91 268/274 91/97 100/100 90/95 272/278

111A 18.6/24.8 51.7/59.7 110/120 110/125 107/115 287/295 114/123 125/125 111/120 291/299

112A 24.0/32.0 66.7/77.0 129/141 150/150 124/135 302/312 133/145 150/150 129/139 306/316

112A+117A 31.8/42.4 88.4/102.0 156/172 175/175 149/164 412/439 160/176 175/200 154/168 416/443

460-

3-

60

STD

NONE - - 20 25 20 102 22 25 22 104

116A 13.9 16.7 41 45 40 119 43 45 42 121

113A 16.5 19.8 45 45 43 122 46 50 45 124

114A 27.8 33.4 62 70 59 135 63 70 61 137

115A 33.0 39.7 70 70 66 142 71 80 68 144

114A+116A 41.7 50.2 83 90 78 202 84 90 80 204

MED

NONE - - 21 25 21 118 23 25 23 120

116A 13.9 16.7 42 45 41 135 43 45 43 137

113A 16.5 19.8 46 50 44 138 47 50 46 140

114A 27.8 33.4 63 70 60 151 64 70 62 153

115A 33.0 39.7 70 70 67 158 72 80 69 160

114A+116A 41.7 50.2 84 90 79 218 85 90 81 220

HIGH

NONE - - 21 25 21 118 23 25 23 120

116A 13.9 16.7 42 45 41 135 43 45 43 137

113A 16.5 19.8 46 50 44 138 47 50 46 140

114A 27.8 33.4 63 70 60 151 64 70 62 153

115A 33.0 39.7 70 70 67 158 72 80 69 160

114A+116A 41.7 50.2 84 90 79 218 85 90 81 220

575-

3-

60

STD

NONE - - 16 20 17 83 20 25 21 87

118A 17.0 20.4 42 45 40 103 46 50 44 107

119A 34.0 40.9 67 70 64 124 71 80 68 128

MED

NONE - - 18 20 19 96 22 25 23 100

118A 17.0 20.4 43 45 42 116 47 50 46 120

119A 34.0 40.9 69 70 66 137 73 80 70 141

HIGH

NONE - - 18 20 19 96 22 25 23 100

118A 17.0 20.4 43 45 42 116 47 50 46 120

119A 34.0 40.9 69 70 66 137 73 80 70 141

Legend and Notes

LEGEND:CO − Convenient outletDISC − DisconnectFLA − Full load ampsIFM − Indoor fan motorLRA − Locked rotor ampsMCA − Minimum circuit ampsMOCP − Maximum over current protectionPE − Power exhaustUNPWR CO − Unpowered convenient outletNOTES: 1. In compliance with NEC requirements for multimotor

and combination load equipment (refer to NEC Ar-ticles 430 and 440), the overcurrent protective devicefor the unit shall be fuse or HACR breaker. Canadianunits may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply VoltageNever operate a motor where a phase imbalance insupply voltage is greater than 2%. Use the followingformula to determine the percentage of voltage imbal-ance.

% Voltage Imbalance = 100 xmax voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 vBC = 231 vAC = 226 v

Average Voltage =(224 + 231 + 226)

=681

3 3

= 227

Determine maximum deviation from average voltage.(AB) 227 – 224 = 3 v(BC) 231 – 227 = 4 v(AC) 227 – 226 = 1 vMaximum deviation is 4 v.Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximumallowable 2%.IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-tact your local electric utility company immediately.

Page 23: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 00 23

Economizer 2 Position Damper Unit Without Economizer or2 Position Damper

Figure 28 Economizer Wiring

Economizer Occupancy Switch

Refer to Fig. 28 for general Economizer wiring. Externaloccupancy control is managed through a connection on theCentral Terminal Board.

If external occupancy control is desired, connect a time clock orremotely controlled switch (closed for Occupied, open forUnoccupied sequence) at terminals marked OCCUPANCY onCTB. Remove or cut jumper JMP 2 to complete the installation.

Install Accessories

Available accessories include:

Roof CurbThru−base connection kit (must be installed before unit is set oncurb)Manual outside air damperTwo−Position motorized outside air damperPower ExhaustOutdoor enthalpy sensorDifferential enthalpy sensorElectric HeatersSingle Point kitsCO2 sensorPhase monitor control

Refer to separate installation instructions for information oninstalling these accessories.

Pre−Start and Start−Up

This completes the mechanical installation of the unit. Refer to theunit’s Service Manual for detailed Pre−Start and Start−upinstructions.

Page 24: INSTALLATION INSTRUCTIONS R 410A Single Package …

516 01 2403 0024

UNIT START-UP CHECKLIST(Remove and Store in Job File)

MODEL NO.: SERIAL NO.:

I. PRE-START-UP� VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT

� VERIFY INSTALLATION OF OUTDOOR AIR HOOD

� VERIFY INSTALLATION OF FLUE EXHAUST AND INLET HOOD

� VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS

� VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT

� CHECK THAT INDOOR−AIR FILTERS ARE CLEAN AND IN PLACE

� CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE

� VERIFY THAT UNIT IS LEVEL

� CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT

� VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED

� VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRRECT DIRECTION

� VERIFY INSTALLATION OF THERMOSTAT

II. START-UPELECTRICAL

SUPPLY VOLTAGE L1−L2 L2−L3 L3−L1

COMPRESSOR AMPS 1 L1 L2 L3

COMPRESSOR AMPS 2 L1 L2 L3

SUPPLY FAN AMPS L1 L2 L3

TEMPERATURES

OUTDOOR−AIR TEMPERATURE �F DB (DRY BULB)

RETURN−AIR TEMPERATURE �F DB �F WB (WET BULB)

COOLING SUPPLY AIR TEMPERATURE �F

PRESSURES

REFRIGERANT SUCTION CIRCUIT A PSIG

CIRCUIT B PSIG

REFRIGERANT DISCHARGE CIRCUIT A PSIG

CIRCUIT B PSIG

� VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS

GENERAL

� ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS (IF EQUIPPED)

� VERIFY SMOKE DETECTOR UNIT SHUTDOWN BY UTILIZING MAGNET TEST

Copyright 2015 International Comfort ProductsLewisburg, TN 37091 USA