Installation Instructions NBOX(B)TMNE, G, H

16
NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 1 Installation Instructions NBOX(B)TMNE, G, H Trend Modem Node Controller Important: Retain these instructions These instructions shall be used by trained service personnel only If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. 1 Dimensions 3 INSTALLATION 1 UNPACKING 2 STORING It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code). CONTENTS 1 Unpacking .....................................................................1 2 Storing ...........................................................................1 3 Installation ....................................................................1 3.1 Installation - Mounting ...................................................1 3.2 Installation - Configuration ............................................5 4 Limitations of Use........................................................14 5 Resetting the Node .....................................................16 6 Disposal .......................................................................16 7 Cleaning and Maintenance .........................................16 2 +50 °C (122 °F) 0 -10 °C (14 °F) 90 %RH TMNE 20 90 %RH TMNH, TMNG H O 70 mm (2.75”) 181 mm (7.125”) TMNH only 230 mm (9.05”) ../24 only ../24?USA only ../230 only TMNH only TMNG only NBOX(B)/TMNE, G,H Installation Instructions (TG200729) TMN TX RX OK 2 m (6’ 7”) 132 mm (5.2”) 35 mm (1.3”) TMNG only antenna bracket 87 mm (3.42”) 70 mm (2.75”) 50 mm (2”) 100 mm (4”) 3.1 Installation - Mounting

Transcript of Installation Instructions NBOX(B)TMNE, G, H

Page 1: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 1

Installation Instructions

NBOX(B)TMNE, G, HTrend Modem Node Controller

Important: Retain these instructions

These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

1 Dimensions

3 INsTallaTION

1 UNpaCkING

2 sTORINGIt is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

CONTENTs1 Unpacking .....................................................................12 Storing ...........................................................................13 Installation ....................................................................13.1 Installation - Mounting ...................................................1

3.2 Installation - Configuration ............................................54 Limitations of Use ........................................................145 Resetting the Node .....................................................166 Disposal .......................................................................167 Cleaning and Maintenance .........................................16

2

+50 °C(122 °F)

0-10 °C(14 °F)

90 %RHTMNE

20 90 %RHTMNH, TMNG

H O

70 mm (2.75”)

181

mm

(7.1

25”)

TMNH only

230 mm (9.05”)

EJ1

05383

../24 only

../24?USAonly

../230 only

TMNH only TMNG only

NBOX(B)/TMNE, G,H Installation Instructions (TG200729)

TMN

TX RX

OK

2 m (6’ 7”)

132

mm

(5.2

”)

35 mm (1.3”)

TMNG only

antenna bracket

87 mm (3.42”)

70 mm (2.75”) 50 mm (2”)

100 mm (4”)

3.1 Installation - Mounting

Page 2: Installation Instructions NBOX(B)TMNE, G, H

2 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

2 Mounting

3 Mount in Enclosure

4 Mount antenna (TMNG only)

3.1 Installation - Mounting (continued)

TMNG only

If using ENCLS/MBOX

ENCLS/MBOX/IQ22x Installation Instructions(TG200203).

209 mm (8.23”)

172

mm

(6.7

7”)

104.5 mm (4.11”)

7 mm (0.28”)

� � �

Ø 6 mm (0.24”)

Ø 6 mm(0.24”)

Fixing details for mounting in a 3rd party enclosure

Altitude < 2000 m (6562”)Pollution degree 2 (only non-conducting pollution occurs

2

0 °C(32 °F)

+45 °C(113 °F)

20 %RH 90 %RH

protection :Ip30 (NEMa 2)

0 %RH 90 %RHTMNH, TMNG

TMNE

H O

Mount antenna away from souces of interference (e.g. domestic appliances, computer monitors or TV receivers, machinery with high HF leakage)

Do not operate near unshielded or susceptible equipment (e.g. some vehicles, pacemakers, certain areas of hospital or medical centres, aircraft, areas designated blasting areas).

TMNG only

>=20 cm (8")

The unit must be installed in an enclosure rated to at least IP20 or equivalent

� � � �

� � �

� � �

� � � � � � � � � � � � � � � � � � � � �

�� � �

� � � � � � � � � �

� � �

!

For -/USA/UL/24VAC only unitrated as UL916, accessoryto open energy managementequipment

Only use the supplied antenna. An unauthorised antenna could damage the modem and may contravene local RF emission regulations or invalidate type approval.

!Do not use the modem with a damaged antenna. If a damaged antenna comes into contact with the skin a minor burn may result. Replace a damaged antenna immediately.

!

For mounting of the Antenna, refer to the mounting instructions supplied with the Antenna kit.

connecting Antenna

Page 3: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 3

Installation Instructions NBOX(B)TMNE, G, H

5 Connect power

3.1 Installation - Mounting (continued)

DO NOT

sWITCH ON

Shrouded plug kitE N l

~E N L

/230 version (shrouded plug kit must be used)

Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)

/24 version (USA only)

Consumption < = 7.5 VA

The 230V supply must include a dedicated 5A fuse complying with BS1632 and a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit. A 5A circuit breaker with high breaking capacity may be used as an alternative .Do not position the equipment so that the disconnecting device is difficult to operate

/24 24 Vac or 24 Vdc

Mat-N-Loc to

terminals adaptor

(supplied)

This unit is protected to safety class 2.The earth on this unit is NOT a protective earth, but it is essential that an earth is fitted for functional reasons.

383501JE

V42

24 Vdc: +24V 0v24 Vac: 24 Vac 0V

Earth (ground)

Note that for the UL 24 Vac theinput power connections must

be made using 18 AWG orlarger wire rated at least 90°C.

The 24V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unitDo not position the equipment so that the disconnecting device is difficult to operate

Consumption <5 VA

Earth/groundthe bus bar

Earth/groundthe bus bar

Page 4: Installation Instructions NBOX(B)TMNE, G, H

4 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

Connect to psTN (or IsDN)8

10 Close Enclosure

Cable 1k2 baud 4k8 baud 9k6 baud 19k2 baud

38k4 baud

No. of Wires

Belden 9182 1000 m (1090 yds)

1000 m (1090 yds)

1000 m (1090 yds)

700 m (765 yds)

500 m(545 yds) 2

Belden 9207 1000 m (1090 yds)

1000 m (1090 yds)

1000 m (1090 yds)

500 m (545 yds)

350 m(380 yds) 2

Trend TP/1/1/22/HF/200 (Belden 8761) 1000 m (1090 yds)

1000 m (1090 yds)

700 m (765 yds)

350 m (380 yds)

250 m(270 yds) 2

Trend TP/2/2/22/HF/200 (Belden 8723) 1000 m (1090 yds)

1000 m (1090 yds)

500 m (545 yds)

250 m (270 yds)

125 m(135 yds) 4

3.1 Installation - Mounting (continued)

� � � � � � � ���

��

� � �

� � � � � � � � � �

� � � � � � � � �

� � � � �

� � � � � � � ���

��

� � � � � � � � ��

��

��

� � � � � � � � � � � �

� � � � �

Connect Network6

2 wireTerminal sizes 0.5 to 2.5 mm2 (14 to 20 AWG)

4 wire

additional terminals

(unless direct connected to single device - old IQs or configuration)

Network Engineering Manual 92-1735

earth (ground) bus

polarity independent

additional terminals

if TMNE if TMNH

Connect to Modem or Terminal adaptor (if TMNE)7

Modem/terminal adaptor

25 Way D type Male

25 Way D type Female

standard 25 way cable (wired 1 to 1, through to 25 to 25)

connect

Modem/terminal adaptor

See limitations of use (section 4)

9 Close Flap

� � � �

� � �

� � �

� � � � � � � � � � � � � � � � � � � � �

�� � �

� � � � � � � � � �

if fitted in ENCLS/MBOX Other enclosure

connect

Page 5: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 5

Installation Instructions NBOX(B)TMNE, G, H

switch 1 2 Open Enclosure

3.2 Installation-Configuration

off

if fitted in ENCLS/MBOX Other enclosure

3 Open Flap

BAUD B BAUD A

BAUD B BAUD A

� � �� �� �� ��

� � � � � � �

� �

� � � �

� � � �

/

/

/

= A

= A to A+5

= A to A+5= A to A+5

NBOX(B)/TMN

set the Network address 5

SET

NOT SET

Address = A

e.g.

Address = 2 + 16 = 18

Lan

TMN

I/NLan Lan

TMN

A = 1 to 99autosense device address

A = 100 to 114autosenseLan number

recommended:11 to 99 device address on Lan100 to 114 Lan number on internetwork

address

0, 2, 3,10 or >119if position ‘autosense’ (see 3.2 step 21)

BAUD B BAUD A

set the Network Baud Rate 4

Network Baud Rate = R1(or RS232 to single device)

= R1

= R1

= R1= R1

move link to set baud rate(Baud a)

e.g 9k6

(or Device A RS232 baud rate if connected to single device)

BaUD a

or high baud rate 38k4

Note: needs extra link

(only for use on high speed internetwork segments)

O

I

Page 6: Installation Instructions NBOX(B)TMNE, G, H

6 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

3.2 Installation-Configuration (continued)

BAUD B BAUD A

BAUD B BAUD A

� � � � � � �

� �

� � � �

� � � �

set Dumb/Normal switch 6

Normal for all other networks

Dumb only for pre Network+ (pre 1985)e.g.

set modem/terminal adaptor baud rate7

move link to set baud rate(Baud B)

e.g 19k2set baud rate to maximum baud rate of modem or terminal adaptor up to 19k2.

J15 (TMNE)J4 (TMNH, TMNG)

Modem or Terminal Adaptor Baud Rate = R2

= R2

TMNE

= R2Modem or

Terminal Adaptor

Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damatge to the unit.

BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices

Dev A

Note: Connecting a cable to the DevA connector disables Lan A communications

BaUD B

plug in local device connector if to be direct connected

8Switch Off Remove cover

9

switch off and Remove cover if to be direct connected or if TMNG

NOTE THaT BaUD RaTE MUsT BE 19k2 (default) FOR TMNH, TMNG

O

I

1

Dev A

J15/J4

1

black sheath

10 Way Female Molexlinks between pins 2-4, 3-5

CABLE/EJ100179A001

25 Way D type Female

Page 7: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 7

Installation Instructions NBOX(B)TMNE, G, H

plug in sIM Card (TMNG only)10Obtain sIM Card plug in sIM Card

1 Contact a GSM service provider. (In UK Trend recommend O2 or Orange.)

2 Obtain a GSM data enabled SIM card with a data number (9600 bps) in addition to the normal voice number. (For O2 or Orange stress Mobile Terminator Data SIM required; if O2 also stress analog data number required.)

3 Communications with an /ADL require the SIM card to have a 2400 bps data number.

4 Request the GSM service provider to activate the SIM end to turn off automatic SIM updates.

5 Clear the SIM’s default password by plugging into a mobile phone and selecting security clearance from the menu. (Alternatively, to maintain password, set up ‘Additional init string’ in modem module, see step 21.)

Note that plugging in the SIM card will result in some of the modem settings being cleared: they must be reconfigured as in step 22.

14 apply power

Replace Cover (if appropriate)11

Close Flap13

set Battery links On (if NBOXB)12��

���

ON

OFF

ON

OFF

Check Node Controller

Check supply

TMN Faulty

b (watchdog) (red)

a (power) (green)

Note: Batteries must be charged for 16 hours before they will support unit during mains failure

3.2 Installation-Configuration (continued)

O

I

15

Page 8: Installation Instructions NBOX(B)TMNE, G, H

8 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

� � � � � � � � � � � �

� � � � �

NBOX(B)/TMN

NBOX(B)/TMN

?

NBOX(B)/TMN

?

� � � � � � � � � � � �

� � � � �

Check Network Not if local device connector plugged into Dev A (step 10)

16

b TX (yellow)

a RX (yellow)

c OK (green)

TMN Faulty

Check network cabling for short circuits with a multimeter (NOT Megger)

Check baud rate . Power up other nodes until faulty node is found (OK ). Correct fault.

Network Address Invalid 0,2,3 or >119

OK

OK

17 Connect local pC (for local configuration)If set up as in step 9

Cable /58-0750

25 Way D type Male

9 Way D type Female

SET

� � �

� � �

18 Configure

e.g. select deFault module

• SET• If on Lan or direct connected set Lan x, address = switch setting.• If on Internetwork set Lan = switch setting and address = switch setting.

Direct connections see steps 9 and 17 (where supported)

or

Autodialling Manual, (90-1353)TMNE, G, H Data Sheet, (TA200734)

to eXit module having changed parameter

to Quit module and discard changes

top Menu :Status Record List Delaylist deFault Help eXit

Note that a PIN may be required to make changes in configuration mode. If the PIN has been forgotten the user should contact Technical Support quoting the default generator number (Default Module) whereupon a default PIN will be supplied. This will only work during the same configuration mode session i.e. the utility must not be exited between reading the generator and entering the default PIN. After the PIN is entered a new PIN should be set up and remembered.

3.2 Installation-Configuration (continued)

F

X Q

Page 9: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 9

Installation Instructions NBOX(B)TMNE, G, H

19 Check settings - Default

20 settings to be Made

3.2 Installation-Configuration (continued)

Leave the following TMN default configuration settings unchanged for normal operation.

Notes

(1) If records are not being used, they should be kept clear so as not to duplicate addresses on local Lan.

(2) The modification of position to localnet or internet may prohibit further configuration (i.e. cannot be changed back) until general reset (see section 5). DO NOT CHaNGE UNlEss IMpERaTIVE.

(3) If auto-dialling passwords are set incorrectly, THEY WIll pROHIBIT COMMUNICaTION. There is a special procedure to correct password on remote TMN (see Auto-dialling Manual).

Notes

(1) The oWn lan, and laN parameters are alternatives which are not both available simultaneously: the oWn lan is only present when the TMN thinks it is positioned on the Lan, whereas the laN is only when positioned on the internetwork.

(2) Always set TMN oWn lan number to match local INC address or (if no INC on Lan) to give identity to Lan.

(3) The target TMN alarm address may be auto-dialled. If so it must be set up in a record of this TMN.

Set up following parameters for correct operation.

Default settings that can normally remain unchanged

Parameter Setting Function Condition See Note

Record All records clear 1

Default

access numBer (blank)Default answer mode visitor networkVisitor network dial out onPosition autosense 2

alarm reporting: tExt on

security:Auto-dial password off 3Config password offdial-In off

settings that must be made

parameter setting Function Condition s e e Note

Default own Tele telephone number telephone number of this TMN all

oWn lan Lan number Lan number of this TMN 1,2

alarm reporting:

addRess network address network address of TMN alarm target

all 3

laN Lan number Lan number of TMN alarm target if TMN on internetwork

1

Page 10: Installation Instructions NBOX(B)TMNE, G, H

10 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

21 settings for special conditions

3.2 Installation-Configuration(continued)

Set up following parameters if special conditions apply.

Settings to be made under special circumstances

Parameter Setting Function Condition See Note

Record addR network address

network address of node being accessed

If being used by IQ controller, 822+/Toolbox,or for retransmission to a radiopager or mobile by a supervisor

1,2,3,4,5

Lan Lan number Lan number of node being accessed as above

Tele telephone number

telephone number of node being accessed

as above 6,12,13

Ext. addr extended address

additional protocol to select target device

if being used for radiopaging, set to radiopager ‘pager number (space) password (space)’. For SMS set to mobile number

13

Default access numBer

telephone number

additional 20 digit constant number sustituted for letter B in telephone number

if telephone number exceeds 20 characters (e.g. for Mercury), can be used in TMN or supervisor records

6

Visitor network dial out

off prohibits use of this TMN for dialling out by supervisors

if TMN is being reserved for incoming calls (e.g alarm priority) - only 921 v2.5, 94x, 96x series

Position localnet forces position to be on Lan independent of address setting

if addressing is becoming a problem 7

internet forces position to be on internetwork independent of address setting

alarm reporting:

tExt off TMN’s alarms reported in coded form if sending to 921 v1 or 951 supervisors 8

security: Auto-dial password

matching password

if correct password is set up, it will enable access to protected TMNs

if sending to protected TMN, (password at each end must match)

9,10

Config password

a password if set to a password will protect the TMN from configuration changes without entry of this password

if configuration changes need protecting 11

dial-In on Will only allow incoming messages if they come from an TMN with same auto-dial password

if this site needs protecting 9

Modem Additional init string null Additional modem initialisation string to be sent to modem after fixed initialsation string

Do not change without instruction from technical support except for setting SIM PIN (TMNG only)

14

Sms text comms off Prohibits text comms via SMS (TMNG only)

if additional seciurity required to stop a mobile user accessing parameters via text comms

Max sms transmit per hour

(default =10) Maximum number of SMS messages sent from TMG (TMNG only)

typical use is to send alarms to mobiles by SMS. This limits number and hence cost of calls

Restart tmn every 24 hours

on TMN will restart every 24 hours after power up (without AONL alarm generation)

if system experiences problems from interference

Notes

(1) If TMN being used by local 921 pre v 2.5, reserve record 2 for 921.

(2) An outstation number may be entered in more than one record with different telephone numbers, so that if more than three failed attempts to connect have accumulated in the delay list, the TMN will proceed to use the next number on the next attempt (Alternative number dialling - see Auto-dialling Manual).

(3) If a supervisor is passing alarms to a radiopager, the supervisor auto-dialling mechanism must not be used, instead the radiopager number must be set up in a TMN record.

(4) The target TMN alarm address may be auto-dialled. If so it must be set up in a record of this TMN.

(5) The sharing of TMN/ANC+/AND and XN28s by a 940 or 943 may require the number to be set up in an TMN record rather than in the supervisor.

(6) Telephone numbers may contain a to Z, 0 to 9 # * : ; < = , the PABX number may be included (e.g. 9 to dial out, extension number to dial in) and special control characters:J - wait for secondary dial tone, k -2 second pausel - pulse dialling, M - tone diallingB - substitute access number (not in access number itself)

(7) The modification of position to localnet or internet may prohibit further configuration (i.e. cannot be changed back) until general reset (see section 5). DO NOT CHaNGE UNlEss IMpERaTIVE.

(8) All alarms passed to radiopagers or by SMS must be text on alarms.

(9) If using auto-dial passwords, make sure that all TMN/ANC+/ANDs involved have the same password set up, and have dial-In set to on.

(10) If auto-dialling passwords are set incorrectly, THEY WIll pROHIBIT COMMUNICaTION. There is a special procedure to correct password on remote TMN (see Auto-dialling Manual).

(11) There is a special procedure to clear a wrong, or forgotten configuration password (see Auto-dialling Manual).

(12) If sending to radiopager,or sending to mobile via SMS bureau, set tele to bureau number prefixed by RR.

(13) If sending SMS directly to mobile (TMNG only) set Tele to mobile number prefixed by sM, and set Ext.addr to mobile number.

(14) If setting up PIN to access SIM (TMNG only), set ‘Additional Init String’ to AT+CPIN=4321 (where 4321 is PIN)

Page 11: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 11

Installation Instructions NBOX(B)TMNE, G, H

• If 94x is using both TMNs/ANCs and XN28s then see Auto-dialling manual. If 94x is 945 1.01 or greater see 945 Engineering Manual.

• 962/963 can automatically seek next available autodialler (ANC, MNC, TMN, XN28) or can have particular devices allocated to particular autodiallers (e.g. to ensure XN28s are used correctly).

• If dialling a TMNG, use its data number• In 963, using TMNG, in Tcommsrv.ini set IdleTimeToDropline=100, and RemoteATDSites=60000 and ensure

[Grouping] has ‘TMN-G=G’.• In PowerTool using TMNG in TrendCommsCodes.ini change mG=German Modem to ‘mG=TMN’, and add

‘cG=GSMIntegral’.

94x/962/963

modem

963

mobile phone

allows 963 to transmit text messages (SMS) to mobile phone, (no need for TMN)

direct

SMS modem

( 963 SMS )

direct

ExitConfiguration23

" Exit from Utility"

3.2 Installation-Configuration(continued)

ConfigureGSMmodemsettings22 (TMNG only)

As a result of inserting the SIM card, type ‘init’ at the top level config prompts (see step 18) to automatically re-initialize modem (v4.5 and greater only).For TMNG v4.4 the settings must be entered manually:• In configuration mode with the top menu prompts displayed, type ‘direct’.• Type “dAT+CNMI=2,1,1,0,0” to enable SMS received notification• Type “dAT+CSMS=1” to set SMS commands to Phase 2+ version• Type “dAT+ILRR=0” to disable data rate reports• Type “dAT+CAOC=1” to disable charging information reports• Type “dAT+CMGF=1” to set SMS message mode to text• Type “dAT+CSMP=17,196,0,0” to set SMS validity period to 4 weeks• Type “dAT+CSAS” to save the SMS settings• Type “dAT&W” to save settings to modem stored profile

RS232

set up device (communicating via TMN)24Devices:

TMNTMN

Lan I/NIQ/822WupDn

IQ/822 TMN

Device TMN

• For autodialled or critical alarms target, set Outstation address as appropriate with Lan number set to zero if TMN a local Lan, and set to destination Lan number if TMN on Internetwork. Put outstation address, Lan, and phone number in TMN record.

• IC Comms - use with caution - see Auto-dialling manual • WupDn doesn’t inform if connected• If dialling a TMNG, use its data number

directonly old IQ or 822+/Toolbox -see steps 10 and 18

TMNTMN

Lan I/N921 921 modemdirect

via SANC - no need for TMN.

• Use 921 auto-dialling mode. Use ‘==’ method to put Lan number in auto-dial number table, and enter TMN address - see 921 Manual.

• If dialling a TMNG, use its data number

TMNTMN

Lan I/N921/SET

921/SET*

modemdirect

via SANC - no need for TMN.

• Use 921 auto-dialling mode. Either set autodialler address to 2 to find any available TMN (Lan or I/N), or set autodialler address to specific TMN address.

• If 921 shares TMNs/ANCs and XN28s then they must be specifically addressed.• If dialling a TMNG, use its data number

TMNTMN

Lan I/N94x/962/963

921 < v 2.5

IQ822+/Toolbox

WupDn RS232

RS232

921 => v 2.5sET

94x series/962/963(+841, 842, 843, 845)

powerTool

*SET v4

X

1

4

2 3

65

7

*8 9

#0

PHONE

Page 12: Installation Instructions NBOX(B)TMNE, G, H

12 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

Configuremodem/terminaladaptor25

• Dropping DTR causes modem or terminal adaptor to terminate call and enter command mode (AT&Dn).

• DCD is used to indicate a call connected (AT&Cn).• Modem or terminal adaptor baud rate must be locked

to TMN speed (locking DTE speed) (AT&Bn).• RTS/CTS flow control is enabled (XON/XOFF

disabled) (AT&Hn).• No echo of TMN commands by the modem (ATEn).• Modem or terminal adaptor message indicating call

progress must be numeric (ATVn).• Turn off data compression (AT&Kn). If unclear, check with Technical Support.

Connect to a PC

PCmodem/terminal adaptor

Windows terminal

e.g.

AT&F

AT&W0AT&W1

set up device (communicating via TMN) (continued)24

Mobile phone• A mobile phone can send text comms messages to TMNG only (see IQ

configuration manual, 90-1533, for text comms codes)• It must set telephone number to TMNG’s data number• Message must include outsation address, Lan no., and passwords e.g.l1 O16 p1234 a1234 S1($,V) - Note space between parameters.lan 1, Outstation 16, outstation pIN 1234, autodialling password 1234,

sensor 1 label($) and Value

see Auto-dialling Manual (90-1353) AND section for example settings.

TMNTMN

Lan I/N915, 916

915, 916

modemdirect

via SANC - no need for TMN

• Put outstation address, Lan, and phone number in TMN record.• If dialling a TMNG, use its data number

Check signal strength26either use TMNG• Enter configuration mode (see steps 8, 9, 10, 12, 14 and 17 above).• Type ‘direct’ at top configuration menu prompts.• Type ‘dAT+CSQ’ to request signal strength.• Value is of form x,y. If x <=18 or =99 relocate antenna and try again (see section 3.1).• Exit Configuration mode (see step 23) and reconnect system

or use a moble phone• Use a mobile phone using the same service provider • Check its indicator shows a good signal strength at location of TMNG antenna. if not relocate antenna and try again (see section 3.1)

Check Modem Mode lED27 (TMNG only)

1 Open flap, remove cover (see steps 2, 8)

2 Check Modem mode LED

check power to modemmodem mode (red)

check SIM activated, check SIM password

3 Replace cover, close flap, (see steps 11, 13)

slow

fast

on network

active call

3.2 Installation-Configuration (continued)

1

4 2

3

6

57

* 8

9#

0

PHONE

(TMNG only)

916

Page 13: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 13

Installation Instructions NBOX(B)TMNE, G, H

� � � � �� � �

Install auto-dialled end28

Test system29

Dialling messages are displayed by some supervisors and may help fault diagnosis.

DIALLING 01234123456 Dialling the numberUNOBTAINABLE WAIT xxmxxs Modem has dialled and obtained busy signal or number unobtainable (must wait for delay

to expire)CONNECTED 01234123456 Connection achieved between IQ systemsDISCONNECTED 01234123456 Modem disconnected due to time out, or manual overrideLINK-FAIL 01234123456 Failure of current linkREMOTE DISCONNECTION Another device has requested priority use of far end modemLOCAL DISCONNECTION Another device has requested priority use of local modemSECURITY FAIL Auto-dial passwords do not match between TMNs.

In addition to normal network alarms the following alarms may be sent from the TMN to the TMN alarm destination node:

AONL (Autodialler on line) TMN powered upBTNR (No answer far site) Lines engaged or telephone fault caused five failed attempts to connect. Further dialling inhibited

until re-dial delay expired (or general reset).LINR (No dial tone) Modem fails to produce dial tone at start of call.MONR (Local modem fault) Modem failed to acknowledge request to dial.PGNR (Pager bureau fault) Pager failed to receive message although connection to pager bureau achieved.

TMNDevice DeviceA/D

Install

e.g.

Alarms

DeviceTMN☎a Check telephone systemCheck for dial and modem answer tones

b Check communication

� � �

DTRA (yellow)

TMN Busy to Device A

Dev A connected only

DTRB(yellow)

TMN Busy to MODEM

TMNE only

CTSA (yellow)

Device A busyDev A connected only

CTSB(yellow)

MODEM Busy to TMN

TMNE only

Modem communicatingMODEM(yellow)

Modem not communicating

A/D may be: MNC >=v2.54 AND 11

TMNH, TMNE <v4 TMNH, TMNE v4 TMNH, TMNE v4.4 915 + modem IQ2xx/ADL TMNG mobile phone When MNC dials into TMN it must have telephone number

prefixed with SW. TMNE may not be able to communicate with MNC if its

modem cannot achieve V21.TMN cannot dial into 915 + modem but 915 + modem can

dial into TMN >= v4. TMN must be >= v4. To dial a TMNG, must use the TMNG's data number To communicate with an IQ2xx/ADL a TMNG must have

a 2k4 bps enabled SIM and the IQ2xx/ADL must dial the TMNG's 2k4 bps data number

To communicate with TMNG, adjust TMN v4.3 or greater Modem Link configuration setting 'Originate Msg Delay' to 10 secs.

• Enter configuration mode (see steps 8, 9, 10, 12, 14 and 17 above).

• Type ‘modem’ at top configuration menu prompts.

• Type G3X to set ‘oriGinate msg delay time’ to 10s. • Type X to exit configuration mode. MNC or TMNH, TMNE <v4.3 cannot communicate with

TMNG TMNH, TMNE must use BT landline to dial TMNG Mobile phone can be dialled from TMNE, TMNH by SMS

bureau or direct by TMNG. Mobile phone can only dial TMNG.

11 TMNG can dial into AND v2.5, but AND v2.5 cannot dial into TMNG

3.2 Installation-Configuration (continued)

Page 14: Installation Instructions NBOX(B)TMNE, G, H

14 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

Close Enclosure30

3.2 Installation-Configuration(continued)

4 limitations of Use4.1 TMNH INTEGRal MODEM (MT5600sMI-92 & MT2492sMI)Modem MT5600SMI-92 is only shipped to Australia and New Zealand and the Republic of South Africa, modem MT2492SMI is shipped to all other destinations.EMC, safety, and R&TTE Directive ComplianceThe CE mark is affixed to this product to confirm compliance with the following European Community Directives:Council Directive 2004/108/EC of 15 December 2004 on the approximation of the laws of Member States relating to electromagnetic compatibility;andCouncil Directive 2006/95/EC of 12 December 2006 on the harmonization of the laws of Member States relating to electrical equip-ment designed for use within certain voltage limits;andCouncil Directive 1999/5/EC of 9 March 1999 on radio equipment and telecommunications terminal equipment and the mutual rec-ognition of their conformity.

International Modem RestrictionsSome dialing and answering defaults and restrictions may vary for international modems. Changing settings may cause a modem to become non-compliant with national telecom requirements in specific countries. Also note that some software packages may have features or lack restrictions that may cause the modem to become non-compliant.

EMC Requirements for the United states47 CFR – FCC Part 15 Regulation – Class BThis equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to47 CFR – FCC Part 15 regulations. The stated limits in this regulation are designed to provide reasonable protection against harmful interference in a residential environment. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:• Reorient or relocate the receiving antenna.• Increase the separation between the equipment and receiver.• Plug the equipment into an outlet on a circuit different from that to which the receiver is connected.• Consult the dealer or an experienced radio/TV technician for help.This device complies with 47 CFR – FCC Part 15 rules. Operation of this device is subject to the following conditions:(1) This device may not cause harmful interference, and(2) This device must accept any interference that may cause undesired operation.Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.EMC Requirements for Industry CanadaThis Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.Cet appareil numérique de la classe B respecte toutes les exigences du Reglement Canadien sur le matériel brouilleur.This device complies with Industry Canada RSS Appliance radio exempt from licensing. The operation ispermitted for the following two conditions: (1) the device may not cause harmful interference, and (2) the user of the device must accept any interference suffered, even if the interference is likely to jeopardize the peration.Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:(1) l’appareil ne doit pas produire de brouillage, et(2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en

compromettre le fonctionnement.47 CFR part 68 Telecom1. This equipment complies with Part 68 of the 47 CFR rules and the requirements adopted by the ACTA. Located on this

equipment is a label that contains, among other information, the registration number and ringer equivalence number (REN) for this equipment or a product identifier in the format:

For current products is US:AAAEQ##Txxxx. For legacy products is AU7USA-xxxxx-xx-x. If requested, this number must be provided to the telephone company.2. A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable

47 CFR Part 68 rules and requirements adopted by the ACTA. It’s designed to be connected to a compatible modular jack that is also compliant.

3. The ringer equivalence number (REN) is used to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. For products approved after July 23, 2001, the REN for this product is part of the product identifier that has the format US:AAAEQ##Txxxx. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.

� � � �

� � �

� � �

� � � � � � � � � � � � � � � � � � � � �

�� � �

� � � � � � � � � �

if fitted in ENCLS/MBOX Other enclosure

Page 15: Installation Instructions NBOX(B)TMNE, G, H

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013 15

Installation Instructions NBOX(B)TMNE, G, H

4.1 limitations of Use (continued)4. If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary dis-

continuance of service may be required. But if advance notice isn’t practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.

5. The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the opera-tion of the equipment. If this happens, the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.

6. If trouble is experienced with this equipment, please contact Multi-Tech Systems, Inc. at the address shown below for details of how to have the repairs made. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the problem is resolved.

7. Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commis-sion or corporation commission for information.

8. No repairs are to be made by you. Repairs are to be made only by Multi-Tech Systems or its licensees. Unauthorized repairs void registration and warranty.

9. If your home has specially wired alarm equipment connected to the telephone line, ensure the installation of this equipment does not disable your alarm equipment.

If you have questions about what will disable alarm equipment, consult your telephone company or a qualified installer.10. Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commis-

sion or corporation commission for information.11. This equipment is hearing aid compatible.12. Manufacturing Information on telecommunications device (modem):

Manufacturer: Multi-Tech Systems, Inc.Trade Name: Socket Modem SocketModem Model Number: MT2492SMI MT5600SMIRegistration No: US:AU7MM01B2492SMI US:AU7USA-46014-MD-ERinger Equivalence: 0.1BModular Jack (USOC): RJ11C or RJ11W (single line)Service Center in USA: Multi-Tech Systems, Inc. 2205 Woodale Drive Mounds View, MN 55112 U.S.A. (763) 785-3500 (763) 785-9874 FaxNew Zealand Telecom Warning Notice (MT5600SMI-92 only)1. The grant of a Telepermit for any item of terminal equipment indicates only that Telecom has accepted that the item complies

with minimum conditions for connection to its network. It indicates no endorsement of the product by Telecom, nor does it provide any sort of warranty. Above all, it provides no assurance that any item will work correctly in all respects with another item of Telepermitted equipment of a different make or model, nor does it imply that any product is compatible with all of Telecom’s network services.

This equipment is not capable under all operating conditions of correct operating conditions of correct operation at the higher speed which it is designated. 33.6 kbps and 56 kbps connections are likely to be restricted to lower bit rates when connected to some PSTN implementations. Telecom will accept no responsibility should difficulties arise in such circumstances.

2. Immediately disconnect this equipment should it become physically damaged, and arrange for its disposal or repair.3. This modem shall not be used in any manner which could constitute a nuisance to other Telecom customers.4. This device is equipped with pulse dialing, while the Telecom standard is DTMF tone dialing. There is no guarantee that

Telecom lines will always continue to support pulse dialing. Use of pulse dialing, when this equipment is connected to the same line as other equipment, may give rise to ‘bell tinkle’ or

noise and may also cause a false answer condition. Should such problems occur, the user should NOT contact the Telecom Faults Service.

he preferred method of dialing is to use DTMF tones, as this is faster than pulse (decadic) dialing and is readily available on almost all New Zealand telephone exchanges.

5. Warning Notice: No ‘111’ or other calls can be made from this device during a mains power failure.6. This equipment may not provide for the effective hand-over of a call to another device connected to the same line.7. Some parameters required for compliance with Telecom’s Telepermit requirements are dependent on the equipment (PC)

associated with this device. The associated equipment shall be set to operate within the following limits for compliance with Telecom’s Specifications:

For repeat calls to the same number:• There shall be no more than 10 call attempts to the same number within any 30 minute period for any single manual

call initiation, and• The equipment shall go on-hook for a period of not less than 30 seconds between the end of one attempt and the

beginning of the next attempt.For automatic calls to different numbers:• The equipment shall be set to ensure that automatic calls to different numbers are spaced such that there is no less

than 5 seconds between the end of one call attempt and the beginning of another.8. For correct operation, total of the RN’s of all devices connected to a single line at any time should not exceed 5.south african statementThis modem must be used in conjunction with an approved surge protection device.

4.1.2 TMNG INTEGRal GsM MODEM (MTsMC-G-F4 & MTsMC-G2-ED)4.1.2.1 safety standardsTHIS GSM MODEM COMPLIES WITH ALL APPLICABLE RF SAFETY STANDARDS.This GSM modem meets the standards and recommendations for the protection of public exposure to RF electromagnetic energy established by governmental bodies and other qualified organizations, such as the following :Directives of the European Community,Directorate General V in Matters of Radio Frequency Electromagnetic Energy

Category DescriptionStandards GPRS Class 10Frequency Bands Quad-band GSM/EGPRS 850/900/1800/1900 MHzCompliance EMC Compliance

FCC Part 15EN55022EN55024

Radio ComplianceFCC Part 22 FCC Part 24RSS 132 RSS 133EN 301 511 EN 301 489-1EN 301 489-7AS/ACIF S042.1 AS/ACIF S042.3

Safety ComplianceUL 60950-1cUL 60950-1IEC 60950-1AS/NZS 60950-1

Network CompliancePTCRB

Page 16: Installation Instructions NBOX(B)TMNE, G, H

16 NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 5 , 17-Apr-2013

NBOX(B)TMNE, G, H Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2013 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control system Usa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

WEEE Directive:At the end of their useful life the packaging, product, and battery (if fitted) should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.

6 DIspOsal

5 Resetting the Node

Open Flap2Open Enclosure1

Check Network address and Dumb/Normal switch3 set all poles to Zero4

Wait 3 seconds5 set Network address Dumb/Normal swtichsection 3.2 - steps 6 & 7

6

Configuresection 3.2 - steps 18 - 237

� � �� �� �� ��

� � � � � � �

� �

� � � �

� � � �

� � � � � � �

� �

� � � �

� � � �

� � � � � � �

� �

� � � �

� � � �

Address = 2 + 16 = 18

SET NOT SET

DUMB

NORMAL

Reset to defaults (clears records, delay list, password, sets default module to defaults).

3 s

Ok

10 Close Enclosure

� � � �

� � �

� � �

� � � � � � � � � � � � � � � � � � � � �

�� � �

� � � � � � � � � �

if fitted in ENCLS/MBOX Other enclosure

if fitted in ENCLS/MBOX

Other enclosure

7 ClEaNING aND MaINTENaNCEThere are no serviceable parts inside the unit. Cleaning of the unit should be carried out in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning. Clean surfaces with a cloth moistened with water.