Installation and Operating Instruction
© CEDES Safety & Automation AG Version 1.00/ January 2011 109 558 E
Muting
English Deutsch
IMPORTANT INFORMATION FOLLOW THE INSTRUCTIONS GIVEN IN THIS MANUAL CAREFULLY. FAILURE TO DO SO MAY CAUSE CUSTOMER COMPLAINTS AND SERIOUS CALL BACK. KEEP
INSTRUCTION MANUAL ON SITE.
Muting System
Muting Installation and Operating Instruction
2 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
Content 1. Introduction 2 1.1. The CEDES Muting Solutions 2 1.2. Features 3 1.3. Safety Sensors for muting 3 2. Description 3 2.1. Muting Function 4 3. Muting Types 5 3.1. T-Type 2 Sensor 5 3.2. T-Type 4 Sensor 5 3.3. L-Type 2 Sensor 5
4. Installation 6 5. Mounting 6
5.1. Mounting Column 6 5.2. Muting Cantilever 7 5.3. Mounting of the light curtain 7
5.3.1. Safe2 / Safe4 7 5.3.2. Safe400 Profile Slim 7 5.3.3. Safe400 Profile Reinf. 8
5.4. Mounting of the muting sens. 8 5.5. Mounting of the retro-reflect. 9 5.6. Mounting of the muting controller box 9
6. Wiring 10 6.1. Two Sensor Muting with Safe4 10 6.2. Four Sensor Muting with Safe400 10 6.3. Muting of Laser Scanners or other Safety Sensors 11 6.4. Pin Assignment 12
7. Configuration Tool Software and OptiLink 13
7.1. Muting with Safe400 15 7.2. 2 Beam or 4 Beam Muting 15
8. Adjustment 15 8.1. Adjustment of the safety light curtain 15 8.2. Adjustment of Safe4 or Safe2 safety light curtain 16 8.3. Adjustment of the light curtain Safe400 16 8.4. Adjustment of the muting sensors and retro-reflectors 16
9. Indication 17 9.1. Safety light curtain 17
9.2. Muting Sensor 17 9.3. Muting box 18 9.4. Muting Lamp 18
10.Operating 19 10.1. Reset 19 10.2. Mute Dependent Override 19 10.3. Lockout and Restart 20
11.Trouble Shooting 20 11.1. Error indications 21 11.2. Error in Sequence 21 11.3. Lockout 21
12. Application Restrictions 21 13. Technical data 22 14. Approvals and conformity 22 Reference Documents Doc 1 Datasheet Muting Doc 2 104 720 Manual SafeCIS 3, Doc 3 102 261 Manual Safe4 Safety Light Curtains Doc 4 103 373 Manual Safe400 Safety Light
Curtains Doc 5 105 784 Manual Configuration tool
software(Controller) Doc 6 Installation Instruction Mounting Column Doc 7 Installation Instruction Cantilever
1. Introduction
Muting is the temporary suspension of a safety light curtain function. This is often used, when material is transported automatically into or out of a manufacturing area with a hazardous zone. The transported good is triggering the muting sensors in the right sequence and suspending the light curtain output. A human interrupting the light curtain would not activate the muting sensors in the right sequence and therefore the safety light curtain would protect the human from any hazard.
1.1. The CEDES Muting Solutions
The CEDES muting system is designed according the technical specification TS/IEC 62046. The muting system is based on the SafeCIS 3 safety controller. By default the muting box is configured for a 2 Beam T-Type muting with Safe2+ Safety Light Curtain for Category 2 or Safe4 for Category 4 muting.
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 3
Features
2 sensor T-type muting D) 2 sensor L-type muting 2 sensor L-type muting with enable 4 sensor T-type muting Muting disable input Start input Status outputs Preconfigured control unit Flexibility due separate components Easy to install Muting lamp included Start and Override function in one switch Controller boxes with PNP outputs
GuardShield Micro400, Safe2, Safe4 (445L) or GuardShield 440L light curtains (including POC and PAC)
Change of time settings for specific muting applications possible
1.2. Safety Sensors for muting
GuardShield Micro400 GuardShield Micro400 (PAC) GuardShield Safe2 D) GuardShield Safe4 D) GuardShield (440L) D) other safety sensors, e.g. laserscanner Safety sensors with relay outputs -> (exclude
cross fault monitoring!) D) Default Settings
2. Description
The CEDES stand alone muting system consists of a muting controller box, mounting stand and cantilever. Any Safety Light Curtain Safe4 or Safe2 may be connected. To connect a Safe400 Safety Light Curtain the settings has to be changed with the OptiLink (104 565). The controller box is ready to connect a muting sensor with an M8-4-Pin connection.
The floor mounting stand and cantilevers allows an easy mounting and alignment in any environment. Due the height of 2000mm, the light curtain and muting sensors may be mounted according the application requirement. .
Light Curtain(Safe2, Safe4 oder Safe400)
Muting Sensor
Mounting Stand
Cantilever
Muting Controller Box(SafeCIS3)
Floor mounting plate(Included in Mounting Column)
Reflector
Muting System
The CEDES muting products can be combined together for a stand alone muting system or the muting box can be integrated into any machine. It contains the operating buttons and indicators. The controller SafeCIS 3 which contains the
muting function can even be used alone and be mounted onto any Din-rail into an electrical compartment.
Muting Installation and Operating Instruction
4 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
Stand Alone Muting System Integrated Muting Muting with SafeCIS 3
The sensors and muting controller
box are mounted on the floor mounting stand and cantilever.
Integrated Muting
Discrete Muting
Stand Alone Application ✔
Easy to Install ✔✔ ✔
All inclusive ✔✔ ✔
Din-Rail mounting ✔
OSSD PNP output ✔ ✔ ✔
Relay output (on request) (on request) ✔
2 Beam, T-Type ✔ (D) ✔ (D) ✔ (D)
2 Beam, L-Type ✔ (C) ✔ (C) ✔ (C)
4 Beam, T-Type ✔ (C) ✔ (C) ✔ (C)
2 Beam, T-Type with enable ✔ (C) ✔ (C) ✔ (C)
GuardShield Safe4 ✔ (D) ✔ (D) ✔ (D)
GuardShield Micro 400 ✔ (C) ✔ (C) ✔ (C)
GuardShield Type 4 (440L) ✔ (D) ✔ (D) ✔ (D)
GuardShield Safe2 ✔ (C) ✔ (C) ✔ (C)
GuardShield Type 2 (440L) ✔ (D) ✔ (D) ✔ (D)
RightSight Sensor ✔ 4-Pin Pico(M8)-QD connector ✔ 4-Pin Pico(M8)-QD connector ✔
VisiSight Sensor ✔ 4-Pin Pico(M8)-QD connector ✔ 4-Pin Pico(M8)-QD connector ✔
Other Sensor ✔ 4-Pin Pico(M8)-QD connector ✔ 4-Pin Pico(M8)-QD connector ✔
(D) Default, (C) Configurable with OptiLink Part No. 104 565
2.1. Muting Function
Moving goods (e.g. pallet) through the muting station leads to the timing diagram. During the mute time t(mute) the muting lamp is lightening. Muting sensor S1 and Muting sensor S2 must have a timing delay of at least >50 ms.
ESPE
Muting Sensor S1
Muting Sensor S2
tSENStSENStESPE tESPE
tMUTE
Mute
Timing diagram for 2 Sensor T-Type
Muting Installation and Operating Instruction
5 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
3. Muting Types
The international standard IEC 62046 describes 2- and 4-Sensor T- and L-type muting. Sensor positions recommended below are taken from IEC62046 (chap. 5.5 and Annex F) and IEC61496 (A.7).
Caution The light curtain has to detect the good – not the carrier (pallet).
3.1. T-Type 2 Sensor
d4d3
h1h2
d3 d4
d1 d2
d5
Hazardous Zone
The distance d5 should be as short as practicable in order to avoid persons entering the hazardous zone without being detected by following immediately after the pallet or the transport system.
h1: Lowest beam of safety light curtain h2 >= h1 h2: height of muting sensor d5: distance from the safety light curtain to the muting sensor crossing point)
3.2. T-Type 4 Sensor
d1 d3d2 d2
h1h2
d1 d3d2 d2
h1: Lowest beam of safety light curtain h2: Muting sensor height d1: Distance Light curtain – Muting Sensor d3: Distance Light curtain – Muting Sensor d2: Distance Muting Sensor – Muting Sensor
Recommended mounting position according IEC62046 F.2: d1 <200 mm d2 >250 mm d3 <200 mm h2 >= h1
3.3. L-Type 2 Sensor
d1d2
h1h2
d1d2
h1: Lowest beam of safety light curtain h2: Muting sensor height
Recommended mounting position according IEC62046 F.2:
Muting Installation and Operating Instruction
6 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
d1: Distance Light curtain – Muting Sensor d2: Distance Muting Sensor – Muting Sensor
d1 <200 mm d2 >250 mm h2 >= h1
4. Installation
The installation of the muting system is very easy. T-Nuts and screws for the muting sensor, safety light curtain and muting box* are included with the cantilever and floor mounting stand. The installation follows the procedure of four steps:
1) Mounting Chapter 5 o column Step 1 Page 6 o cantilever Step 2 Page 7 o safety light curtain Step 3a – 3d Pages 7 - 8 o muting sensor Step 4 Page 8 o retro-reflector Step 5 Page 9 o muting controller box Step 6 Page 9
2) Wiring Chapter 6 o 2-Sensor Muting with Safe4 Page 10 o 4-Sensor Muting with Safe400 Page 10 o Muting of Laser Scanners or other Sensors Page 11
3) Adjustment Chapter 8 o Safety Light Curtain Page 15 o Safe4 or Safe2 Page 16 o Safe400 Page 10 o Muting Sensors and Retro-Reflector Page 16
5. Mounting
5.1. Mounting Column
Step 1 Fix the mounting column onto the floor plate. See mounting column installation instruction Doc 5 Check for desired positioning of the front side of the column. Check the sliding nuts position for light curtain, sensor bar and controller box.
* T-Nuts and Screws for: • Safety light curtain Safe4, Safe2, • Muting sensor bracket 60-2649 (RightSight) and 92-39 Reflector • Muting box
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 7
5.2. Muting Cantilever
Step 2 Mount the muting sensor bar according to the muting type (e.g. 2 Sensor T-Type). See sensor bar installation instruction Doc 6. Adjust the height of the muting sensors. The muting sensors should be positioned at the same level as or higher than the lowest beam of the safety light curtain. See chapter 3.
5.3. Mounting of the light curtain
5.3.1. Safe2 / Safe4
Step 3a M4 T-Slot Nut and screws are included with the floor mounting column. The mounting brackets are included with the safety light curtain. Premount the mounting kits on the T-Slot nuts
Before mounting the light curtain, check for height position and cable exit (bottom or top).
5.3.2. Safe400 Profile Slim
Step 3b The mounting brackets are included with the safety light curtain. T-Slot M4-nut and screws are incluced with the floor mounting column. Premount the upper and lower bracket in the T-Slot nuts. Before mounting, check for height and cable exit position (bottom or top).
Muting Installation and Operating Instruction
8 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
Step 3c 1) Put the light curtain into mounting position
and tilt it to preassemble the side screws of the upper and lower mounting bracket.
1 2 3
2) Tighten the screws altering between the
upper and lower mounting brackets… 3) ... until the light curtain is securely mounted.
5.3.3. Safe400 Profile Reinforced
Step 3d The Safe400 reinforced profile uses the same mounting brackets as the Safe4. They are supplied with the light curtain. T-Slot nuts and screws are incluced with the floor mounting column. Before mounting, check for height and cable exit position (bottom or top).
5.4. Mounting of the muting sensors
Step 4 Before starting with mounting of the muting sensors, check chapter 3 for the mounting position with respect to the muting type. Mount the muting sensor according to its instruction. Check for good visibility of the sensor indicator diodes.
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 9
5.5. Mounting of the retro-reflectors
Step 5 Check chapter 3 for the mounting position for the chosen muting type. T-Slot nuts and screws are provided with the cantilever.
5.6. Mounting of the muting controller box
Step 6 Mount the brackets on the muting box. Tighten the screws properly.
Check the height positioning with respect to the cable wiring of the light curtain, muting sensors and muting lamp. Connectors normally are positioned on the bottom side of the muting box. Premount the muting box with the T-Slot nuts to the mounting column. Do not thighten the screws until the box is in right position. As last step, tighten the screws alternately.
Muting Installation and Operating Instruction
10 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
6. Wiring
Step 7 Connect Muting components, power and output according the corresponding muting type picture below.
6.1. Two Sensor Muting with Safe4
S1 S2 S3 S4
Tx-GS/Tx-S4Rx-GS Rx-S4
Safe4 Tx
Safe4 Rx
Muting sensorswith retro-reflectors
ControlCabinet
Rx Micro 400 Tx Micro 400
MutingLamp
PWR I/O
Outputs
Two Sensor T-Type Muting with Safe4
6.2. Four Sensor Muting with Safe400
S1 S2 S3 S4
Tx-GS/Tx-S4Rx-GS Rx-S4
Safe400 Rx
Safe400 Tx
Muting sensorswith retro-reflectors
ControlCabinet
Rx Micro 400 Tx Micro 400
MutingLamp
PWR I/O
Outputs
Wiring of 4 Sensor T-Type Muting with Safe400
Caution When using Safe400 in a muting system, the configuration must be changed according to chapter 7.
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 11
6.3. Muting of Laser Scanners or other Safety Sensors
S1 S2 S3 S4
Tx-GS/Tx-S4Rx-GS Rx-S4
Muting sensorswith retro-reflectors
ControlCabinet
Rx Micro 400 Tx Micro 400
MutingLamp
PWR I/O
Outputs
Laser Scanneror otherSafety Sensor
Pin1 24 VPin2 OSSD 2Pin3 GNDPin4 OSSD 1Pin5 Earth
Wiring of 2 Sensor Muting with Laser Scanner or other Safety Sensor wit PNP output.
Caution When using a Laser Scanner or an other safety sensor in a muting system, the configuration must be changed according to chapter 7.
Muting Installation and Operating Instruction
12 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
6.4. Pin Assignment
Connector PWR/IO (Power)
SafeCIS 3 Signal Cord set 190 110
Pin1 Status Safety Output Info1 White
Pin2 24V 24V Brown
Pin3 Earth Earth Green
Pin4 Status Lockout Info2 Yellow
Pin5 OSSD1 OSSD1 Grey
Pin6 OSSD2 OSSD2 Pink
Pin7 GND GND Blue
Pin8 Start In1(Start) Red
Connector Out (Output)
SafeCIS 3 Ext 2CSignal
Cord set 190 111
Pin1 Relay NC 2 NC 2 - 23 Brown
Pin2 Relay NC 1 NC 1 - 14 White
Pin3 Relay NC 1 NC 1 - 13 Blue
Pin4 Relay NC 2 NC 2 - 24 Black
Pin5 EDM - Start Release In 2 Grey
Connector Lamp SafeCIS 3 Signal Cord set 190 113
Pin 1 24V 24V Brown
Pin 2 Lamp Lamp White
Pin 3 NC NC Blue
Pin 4 NC NC Black
Connector Muting Sensor S1, S2, S3 and S4
SafeCIS 3 Signal Cord set
Pin 1 24V 24V Brown
Pin 2 DO NC White
Pin 3 GND GND Blue
Pin 4 LO GPIO1 Black
Connector Tx (Emitter GuardShield Safe 2 or Safe 4)
SafeCIS 3 Signal Cord set 889D-F5BCDM-X
Pin1 24 V 24 V Brown
Pin2 Test Pin 2 - Pin 4 White
Pin3 GND GND Blue
Pin4 Test Pin 4 - Pin 2 Black
Pin5 Earth Earth Grey
Connector Rx-S4 (Receiver Safe 2 or Safe 4)
SafeCIS 3 Signal
Cord set 889D-F5BCDM-X
Pin1 24 V 24 V Brown
Pin2 OSSD 2 GPIO 4 White
Pin3 GND GND Blue
Pin4 OSSD 1 GPIO 3 Black
Pin5 Earth Earth grey
Connector Rx-GS (Receiver Allen-Bradley GuardShield 440L)
SafeCIS 3 Signal
Pin1 NC NC
Pin2 24V 24V
Pin3 Earth Earth
Pin4 NC NC
Pin5 OSSD 1 GPIO 3
Pin6 OSSD 2 GPIO 4
Pin7 GND GND
Pin8 NC NC
Connector Tx-400 (Emitter Safe400)
SafeCIS 3 Signal
Cord set 107 145
Pin 1 CIS3 Tx-1
Pin 2 CIS3 Tx-2
Pin 3 CIS3 Tx-3
Pin 4 CIS3 Tx-4
Pin 5 CIS3 Tx-5
Pin 6 CIS3 Tx-6
Pin 7 CIS3 Tx-7
Pin 8 CIS3 Tx-8
Connector Rx-400 (Receiver Safe400)
SafeCIS 3 Signal
Cord set 107 145
Pin 1 CIS3 Rx-1
Pin 2 CIS3 Rx-2
Pin 3 CIS3 Rx-3
Pin 4 CIS3 Rx-4
Pin 5 CIS3 Rx-5
Pin 6 CIS3 Rx-6
Pin 7 CIS3 Rx-7
Pin 8 CIS3 Rx-8
Muting Installation and Operating Instruction
13 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
7. Configuration Tool Software and OptiLink
The default configuration is set for 2 Beam T-Type muting of a Safe2 or Safe4 safety light curtain. Other muting type settings can be selected with the confiugration tool software and
downloaded with the OptiLink. The safety software is supplied with the OptiLink or available on http://csa.cedes.com (Product SafeCIS 3).
Settings
Muting Type Safety Light Curtain Comments
2 Beam, T-Type
2 Beam, L-Type
4 Beam, T-Type
2 Beam, T-Type Enable
Safe2 or Safe4 Safe400
Other Safety Sensor
Default ✔ ✔ ✔ ✔ Default Setting
Selectable ✔ ✔ ✔ ✔
Selectable ✔ N/A ✔ N/A
Selectable ✔ N/A ✔ N/A
Configurable with SafeCIS 3 Safety Software and download with OptiLink
Inputs Outputs Safety
IN1 IN2 Info1 Info2 Stop delay Device Monitor
Default Start None Safety Output Lockout No
Selectable Test Input
Start
Start EDM
Start Release
See SafeCIS 3 Configuration
Software
See SafeCIS 3 Configuration
Software 0...120s
No, EDM,
Start Release
Additonal Settings Time Settings
M-Lamp monitored
Mute depend. Override active
Muted Light Curtain
Light Curtain interrupt. Monitored
T(sens) T(espe) T(mute) T(mdo) T(msdel)
Default No Yes OSSD Yes 4 s 5 s 5 min 60 s 0.05 s
Selectable Yes No
Yes No
OSSD GS Micro400
Yes No
0 - 10 s 0 - 10 s 0 - 4’320 min 0 - 1275 s 0 - 2.55s
Muting Installation and Operating Instruction
14 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
SafeCIS 3 configuration software
For detailed description about muting features and settings, refer to Doc 5 105 784 Manual Configuration tool software(Controller).
Step 8 Download with OptiLink In case the default configuration (see above) will not be used, the created configuration has to be downloaded with the OptiLink (104 595) to the SafeCIS 3 controller.
1) Clip the sucction head cap into the black fastener
2) Connect the USB plug into your computer 3) Start the configuration software 4) Create or load a configuration file
Download the configuration (Menu File – download)
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 15
7.1. Muting with Safe400
For muting a Safe400 safety light curtain use the configuration tool software to create a configuration accordingly and download it to the
SafeCIS 3 controller according Step 8.
7.2. 2 Beam or 4 Beam Muting
The SafeCIS 3 offers 2 beam and 4 beam muting according chapter 3. The controller box is delivered by default with the 2-Beam T-Type muting. Another muting can be selected with the configuration tool software and downloaded with the OptiLink.
8. Adjustment
8.1. Adjustment of the safety light curtain
Ligh
tcur
tain
Tx
Ligh
tcur
tain
Rx
Step 9 Position the emitter and receiver light curtain at the same height on the mounting column. Fully tighten the light curtain mounting screws.
Step 10 1) Preassemble the column with the floor
mounting plate on the floor. 2) Adjust with the floor plate adjustment screws
the position of the mounting column after mounting of a light curtain.
3) When the light curtain indicates uninterrupted protective field, fix the mounting screws on the floor plate.
Muting Installation and Operating Instruction
16 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
8.2. Adjustment of Safe4 or Safe2 safety light curtain
Use the Integrated Laser Alignment System (ILAS) for easy verification. Touching the symbol turns the laser on or off. The green LED indicator on the receiver light curtain confirms the correct alignment.
(If no laser is available, see Step 10)
8.3. Adjustment of the light curtain Safe400
The Safe400 light curtain is alligned according
Step 10. A green LED indicator on either the emitter or receiver light curtain confirms the correct alignment.
8.4. Adjustment of the muting sensors and retro-reflectors
Note: The image shows an example of a muting sensor. Normally the sensors are mounted on the side of the muting station and the reflectors on the other side.
Step 11 1) For the corresponding muting type, check
chapter 3 for sensor positions. 2) Thighten the cantilever screw when
positoned at correct height and th muting sensors at proper distance to the light curtain (see chapter 3)
3) Adjust the reflectors and muting sensors to each other. Check the status LED’s on the opto-retroreflective sensor for correct operation.
Caution ▪ A pallett should not interrupt the light curtain
nor the muting sensors. The light curtain and muting sensors should be interupted by the transported goods only.
▪ For a correct muting sequence the muting sensors must be interrupted with a time difference >50ms.
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 17
9. Indication
9.1. Safety light curtain
The green LED on the receiver light curtain indicates under normal operation if the protective field is uninterrupted. See corresponding light curtain manual.
Safe4, Safe2
Emitter LED = green on Normal operation POWER
Emitter
Power on(orange) POWER
Receiver
Power on(orange)
Output active(green)
Output inactive (red)
OKNormal operation (green)
TEST Test input(red)
OptiLink(IR light)
OptiLink(IR light)
Receiver LED = green on Protection field uninterrupted
LED = red on Protection field interrupted.
Safe400
LED = green on Protective field uninterrupted
LED = red on Protective field interrupted
9.2. Muting Sensor
Check the sensor manual for indication LED. The orange LED on the Allen-Bradley RightSight Sensor indicates correct allignment of an uninterrupted beam. If the red LED is off, the intensity is too low and the beam should be readjusted.
Muting Installation and Operating Instruction
18 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
9.3. Muting box
Three indicators show the condition of the muting box.
Muting lamp off Safety Light Curtain is active
white on Safety Light Curtain is muted
white flashing Muting Sequence Error
Output status off OSSD output = off green on OSSD output = on
Reset / RestartKey Switch
Connectors
Muting Lamp
Lamp Output Status
Lamp Error Status
Note: Error status will be changed to green.
Error status off Lockout green on ok
Caution The status output are the driven from the SafeCIS 3 output info 1 and 2. The meaning of the indication can be changed according the configuration downloaded to the SafeCIS 3 (see chapter 7).
9.4. Muting Lamp
The muting lamp warns an operator in the event that the light curtain is muted. Depending on the risk analysis often a muting lamp, monitored by the SafeCIS 3 control unit (controller box), signals the muting procedure. The size and the brightness of the connected lamp must also be designed as required by the safety analysis. By default the muting lamp is not monitored in the Muting controller box. However, a connected lamp will still work but it will not be monitored. In case of changing the state to ‘monitored’ (see chapter 7) and the lamp is defective or not connected, the SafeCIS 3 controller will not initiate a muting condition. If an error in the muting sequence has occurred, the muting lamp will blink (ca. 1 Hz), indicating that the muting condition will not be initiated, or has been discontinued. The plug ‚Muting lamp’ offers to connect an additional muting lamp to the controller box.
Muting Lamp Meaning
Off Safety light curtain active
On Light curtain muted
Flashing Error in Muting sequence
Muting Lamp
Muting Installation and Operating Instruction
19 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
10. Operating
The control of the muting is done with one spring return switch called Reset/Override. It triggers the start input of the SafeCIS 3 controller. The control signal on the Quick-QD M12 connector ‚PWR I/O’ – Pin 4 (Start) works in parallel to the key switch.
Caution Before restarting the muting operation, make sure nobody is in the hazardeous area.
10.1. Reset
The reset function switches on the OSSD safety outputs considering the safety light curtain is uninterrupted.
24V
Start 0V
24V
OSSD 0V
> 0.1 s
Reset function
10.2. Mute Dependent Override
Important safety notice An error in the muting signal sequence will discontinue the muting condition. If the safety light curtain is then interrupted the OSSD outputs will switch off. This normally leads to a stoppage of the movement of the material. The muting lamp will flash. For moving the material out of the protective field area in this situation (protective field interrupted), the start signal triggers the mute dependant override function.
The maximum activation time t(mdo)‡ for this override function is set to 1 minute by default. This time has to be considered on risk analysis of the application. The ‚Reset/Override’ switch has to be mounted at a location, where the dangerous area can be overseen. The mute dependant override function is auto-matically terminated after the mute dependant override time t(mdo) has elapsed, or when the safety light curtain is no longer interrupted.
24V
Start 0V
24V
OSSD 0V
> 0.1 s
Mute dependent override function
‡ Muting Dependant Override Time
Key Switch ‚Reset / Override’ Turn right (impuls) Reset Turn right (impuls) Mute dependent
override Turn right (10 sec) Power restart
Reset/Overide key switch on muting box is identical with the start signal from Connector ‚PWR I/O’ – Pin 4 (Start)
Muting Installation and Operating Instruction
20 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
10.3. Lockout and Restart
The following fault conditions will lead to a lockout: • The connection to the Safe400 safety light
curtain emitter or receiver is interrupted. • Defect in the electronics of Safe400 light
curtain or the SafeCIS 3 controller. • Supply over- or undervoltage • Error in EDM or Start release
24V
OutputStatus 0V
24VErrorStatus 0V
24V
Start 0V
24V
OSSD 0V
> 0.1 s> 10 sec
Power-Up function
A lockout is indicated with LED ‚Error Status’ (= off) and with the output signal ‘Lockout’ of connector ‘PWR/IO’ (Pin 6). On the Safe400 light curtain it is indicated with the red blinking LED (emitter and receiver)
The lockout mode may be reseted by one of two methods:
• Power down, then Power up. If the fault is still present the module will lockout again.
• A start signal of 10 sec on switch ‚Reset/Override’ Assuming the cause of the lockout has been
eliminated, with activating the ‚Reset/Override’ switch for 10 seconds, the controller starts up. If the safety light curtain is interrupted, e.g. due a pallet, the controller goes into a safe off mode. The ‚Reset/Override’ switch has to be reactivated again to start to mute-dependent-override function (see Figure 13).
• A start signal of min. 10 sec on connector ‚PWR I/O’ Pin 4
11. Trouble Shooting When the LED ‚Status Output’ and ‚Status Error’ are lightening indicates that the muting system is operating. A simple functional test can be performed interrupting each sensor for its own. Supposing that power is on, light curtain, muting sensors and the muting lamp are connected, the function of each sensor can be checked with the sensor LED indicator, Considering of correct operation of the light curtain and muting sensors, the muting lamp will
flash when interrupting one muting sensor for a few seconds. Check for the muting sequence according Timing diagram for 2 Sensor T-Type.
Muting Installation and Operating Instruction
21 http://csa.cedes.com © CEDES Safety & Automation AG /January 2010
11.1. Error indications
Muting Lamp
Output Status
Error Status
Possible Reason Possible Solution
off on on Operating, safety light curtain active
on on on Operating, safety light curtain muted
x off on Operating, OSSD ouput off Reset Make sure, that the safety light curtain and muting senors are operating and uninterrupted
x x off Lockout Reset for 10 seconds See chapter 10.3
flashing on on Mute Sequence Error Make sure, that the muting sensor and the safety light curtain are uninterruupted. Check allignment of the safety light curtain and muting sensors Clean the muting sensors and safety light curtain
x = on / off or flashing
11.2. Error in Sequence
If an error in the muting sequence has occurred, the muting lamp will blink (ca. 1 Hz), indicating that the muting condition will not be initiated, or has been discontinued. Make sure, that the muting sensor and the safety light curtain are uninterruupted. Check allignment of the safety light curtain and muting sensors. Eventually the muting sensors and safety light curtain have to been cleaned.
11.3. Lockout
A non iluminated LED ‚error status’ indicates a lockout as described in chapter 10.3. The reason for the lockout can be analyised with the OptiLink (part no. 104565) and the safety software (chapter 7)
12. Application Restrictions
The application is not intended for the following usage:
• In an explosive environnement (EX), • in radioactive areas • outside of a temperature range of 0 …
55°C.
Further restrictions see technical specification of the safety light curtain and SafeCIS 3 Safety Controller.
Muting Installation and Operating Instruction
22 http://csa.cedes.com © CEDES Safety & Automation AG /January 2011
13. Technical data
General data Temperature range Environment temp.: 0 ... +55°C
Stock temp.: -25 ... +70°C Enclosure rating according EN 60529
IP65
Net weight SafeCIS 3 130 g Muting box 1.7 kg
Housing dimensions 111 x 22,5 x 125 mm (incl. plugs) Approvals According SafeCIS 3 Interfaces I/O (24V), OptiLink
Weight and packaging
Dispatch packaging SafeCIS 3 280x 200 x 70mm Muting box 300x 200x 200mm
Dispatch weight SafeCIS 3 350 g Muting box 2.3 kg
OSSD semi conductor outputs (PNP)
Voltage UN - 2 V
Current Max 400 mA short-circuit protected and with cross-fault detection
Leakage current IMAX Off ≤ 0.1 mA (CLOAD ≤ 3.3 uF) Max. response time t(C) with UN protective mode ≤ 15 ms
Response time total t(tot LC OSSD)
For light curtain and controller see Configuration Control Document e.g. Safe400 /550-P3 -> 10ms
Output S1-S4 (SafeCIS 3 GPIO1 – GPIO4)
Nominal voltage UN – 2 V (coded) (Short-circuit protected)
Current max 100 mA (short-circuit protected)
Leakage current IMAX Off ≤ 0.05 mA (CLOAD ≤ 100 nF)
Status Outputs (PNP), SafeCIS 3 Info 1, Info 2
Voltage UN – 2 V
Current max 100 mA (short-circuit protected)
Leakage current IMAX Off ≤ 0.05 mA (CLOAD ≤ 4.7 uF)
Inputs (SafeCIS 3)
Power supply UN +24 VDC (EN 60204-1) at 5 % residual ripple 0.85 ... 1.15 UN Current consumption < 700 mA
Rush-In current: max 3.0 A (30 ms)Controller protection (external)
5 A slow
Control current into: IN 1, IN 2
2 mA each (min.) (in accordance with EN 61131-2)
Minimum voltage at: IN 1, IN 2
11 VDC at activated controller (EN 61131-2)
Start pulse duration Min. Max.
50 ms 5s
Mute sensor time delay > 50 ms Test pulse duration (min.) response time x 2 Control current into: GPIO1 – GPIO4 7 mA
Safety Prevention Lamp Minimum current at Lamp
8 mA with lamp switched on 0.9 A with lamp switched on
Safety Related Parameter
Probability of a dangerous failure per hour PFH
9.0 E-10 1/h SafeCIS 3 Main M. 3.0 E-10 1/h SafeCIS 3 Ext 4.0 E-9 1/h Safe400
14. Approvals and conformity
The Muting Station is based on the SafeCIS 3 Safety Controller. Relevant safety conformity and approvals may be found on the SafeCIS 3 and safety light curtain documentation.
Installation and Operating Instruction Muting
© CEDES Safety & Automation AG /January 2011 http://csa.cedes.com 23
Notes:
Muting Installation and Operating Instruction
© CEDES Safety & Automation AG +41 81 307 8200 Fax: +41 81 307 8201 [email protected] csa.cedes.com