AB-6567 © 2005–2018 Azbil Corporation All Rights Reserved. 1 Specifications/Instructions Infilex FC Fan Coil Unit Controller for SC-bus Communication Overview Infilex FC Model WY5205W is a DDC controller for FCU. In addition to FCU ON/OFF operation, valve control, and fan speed changeover, Infilex FC provides advanced controls such as setback and interlock operations with OAHU. Infilex FC in combination with room user terminal(s) allows room occupants to operate FCU. Infilex FC also communicates to our BMS. This enables to centrally monitor and control the scheduled operation, operating status, and temperature measurement of FCU. BMS: Building management system DDC: Direct digital control FCU: Fan coil unit OAHU: Outdoor air handling unit Features Compact size: Small sized body fits inside an FCU. Two kinds of FCU control: Valve ON/OFF control and valve proportional control for FCU are available. Advanced controls in combination with our BMS: Infilex FC combined with our BMS allows FCU to interlock with OAHU and to control mixing loss between perimeter and interior zones. Standalone control: Infilex FC is not only connected to our BMS but also used as a standalone controller. Room user terminals: Our user terminal (Neopanel or Neoplate) is connectable to Infilex FC, allowing the room occupants to turn on/off FCU and change temperature setting. Easy installation: Screwless push-in terminals (for pipe temperature sensor input, DI, FCU ON/OFF output, and control valve output) and modular jacks (for communication, user terminal connection, and temperature sensor input) reduce wiring workload. CE Marking certified product: Infilex FC Models WY5205W100_ and WY5205W201_ conform to all the applicable standards of CE Marking.

Transcript of Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two...

Page 1: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

© 2005–2018 Azbil Corporation All Rights Reserved.

1

Specifications/Instructions

Infilex FC

Fan Coil Unit Controller for SC-bus Communication

Overview

Infilex FC Model WY5205W is a DDC controller for FCU. In addition to FCU ON/OFF operation, valve control, and fan speed changeover, Infilex FC provides advanced controls such as setback and interlock operations with OAHU.

Infilex FC in combination with room user terminal(s) allows room occupants to operate FCU.

Infilex FC also communicates to our BMS. This enables to centrally monitor and control the scheduled operation, operating status, and temperature measurement of FCU.

BMS: Building management system DDC: Direct digital control FCU: Fan coil unit OAHU: Outdoor air handling unit

Features

Compact size: Small sized body fits inside an FCU.

Two kinds of FCU control: Valve ON/OFF control and valve proportional control for FCU are available.

Advanced controls in combination with our BMS: Infilex FC combined with our BMS allows FCU to interlock with OAHU and to control mixing loss between perimeter and interior zones.

Standalone control: Infilex FC is not only connected to our BMS but also used as a standalone controller.

Room user terminals: Our user terminal (Neopanel or Neoplate) is connectable to Infilex FC, allowing the room occupants to turn on/off FCU and change temperature setting.

Easy installation: Screwless push-in terminals (for pipe temperature sensor input, DI, FCU ON/OFF output, and control valve output) and modular jacks (for communication, user terminal connection, and temperature sensor input) reduce wiring workload.

CE Marking certified product: Infilex FC Models WY5205W100_ and WY5205W201_ conform to all the applicable standards of CE Marking.

Page 2: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

2

Safety Precautions

Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual nearby for quick

reference.

Restrictions on Use

This product was developed, designed, and manufactured for general air conditioning use.

Do not use the product in a situation where human life may be at risk or for nuclear applications in radiation controlled areas. If you wish to use the product in a radiation controlled area, please contact Azbil Corporation.

Particularly when the product is used in the following applications where safety is required, implementation of fail-safe design, redundant design, regular maintenance, etc., should be considered in order to use the product safely and reliably.

• Safety devices for protecting the human body

• Start/stop control devices for transportation machines

• Aeronautical/aerospace machines

For system design, application design, instructions for use, or product applications, please contact Azbil Corporation.

Azbil Corporation bears no responsibility for any result, or lack of result, deriving from the customer's use of the product.

Warnings and Cautions

WARNING Alerts users that improper handling may cause death or serious injury.

CAUTION Alerts users that improper handling may cause minor injury or material loss.

Signs

Alerts users to possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside indicates the specific type of danger. (For example, the sign on the left warns of the risk of electric shock.)

Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside graphically indicates the prohibited action. (For example, the sign on the left means that disassembly is prohibited.)

Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside graphically indicates the actual action to be carried out. (For example, the sign on the left indicates general instructions.)

WARNING

Be sure to ground the product with ground resistance of less than 100 Ω. Improper grounding might cause electric shock or malfunction.

Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover. Failure to do so might cause electric shock.

Before wiring and maintenance, be sure to turn off the power to the product. Failure to do so might cause electric shock.

CAUTION (1/2)

Install the product in a location that satisfies the operating conditions (temperature, humidity, power, vibration, shock, mounting direction, atmospheric condition, etc.) as listed in the specifications and use the product within the operating ranges as listed in the specifications. Failure to do so might cause fire or device failure.

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

All wiring must comply with applicable codes and ordinances.

Connect the cables to the product power supply terminals with the terminal lugs or an equivalent method to assure permanent connection.

Be sure to provide a circuit breaker for the power to the product as the product does not have a power switch.

Page 3: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

3

CAUTION (2/2)

To connect the wires to the screw terminals, use crimp terminal lugs with insulation. Failure to do so might cause fire or device failure due to short circuit.

Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating.

For wiring, strip each wire insulation for the length specified in this manual. If the strip length is longer than the specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent terminals. If it is shorter, the stripped part will not contact the connector.

If more than the rated power voltage is applied to the product, replace the product with new one for your safety. Failure to do so might cause fire.

Do not disassemble the product. Doing so might cause device failure.

Dispose of this product as industrial waste in accordance with your local regulations. Do not reuse all or a part of this product.

IMPORTANT: This product adopts the screwless push-in terminals with the inclined surface. When a currently installed our Intelligent FCU Controller (IFC) is replaced with Infilex FC, a screwdriver with short grip may be required for wiring as IFC requires a smaller maintenance clearance than Infilex FC.

Page 4: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

4

Model Numbers

Base model number

Power Control

type — DI

Temperature input

Description

WY5205 Infilex FC for SC-bus communication

W 100 V AC - 240 V AC

1 Valve ON/OFF control 2 Valve proportional control

0 Fixed

0 No DI point 1 Two DI points

0 RTD (Pt100) K RTD (Pt1000)

Note: Base model number is available with the following suffix numbers: W1000, W100K, W2010, W201K

IMPORTANT:

Infilex FC cannot be connected to the system including SmartScreen or SCM (Sub Controller Master: Model WY7222).

Part Numbers of Optional Auxiliary Device, Parts, and Tools

Item Part number Remark

Auxiliary device

Temperature sensor for pipe surface (to automatically change between cooling and heating modes, for valve ON/OFF and proportional control types)

Part No. 81301851-001 1.3 m long Part No. 81301851-002 2.5 m long

Parts Modular branch unit Part No. DY7203A0000 — Modular extension unit Part No. DY7202A0000 5 pieces/set Adapters for connecting to a Pt100 temperature sensor

Part No. DY7204A0003 For connection of Pt100 temperature sensor, 10 pieces/set

Connector cable for two terminals (short cable)

Part No. DY7221A00X0 For connection of Pt 1000 temperature sensor, 10 pieces/set

Modular plug Part No. DY7207A0100 100 pieces/set Mounting bracket (small) Part No. DY7208A0001 — Mounting bracket (large) Part No. DY7208A0002 —

Tools Modular crimper Part No. DY7205A0002 — Modular cable tester Part No. DY7206A0000 —

Page 5: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

5

System Configurations

Infilex FC for connection to our BMS

For BMS and devices that are compatible to Infilex FC, ask our salesperson.

Notes: *1 Maximum number of Infilex ZM and/or DIF-II that can be connected to BMS varies depending on your system configurations. *2 Maximum of 50 sub-remote units (also known as "sub controllers") such as Infilex VC and Infilex FC can be connected to Infilex ZM via

SC-bus. *3 Up to two Neopanel (digital user terminal) or one Neoplate (analog user terminal) can be connected to one Infilex FC. *4 Neopanel/Neoplate and a temperature sensor can be connected to the same Infilex FC.

Figure 1. System configuration example: Infilex FC integrated into our FX BMS

Infilex FC for standalone use

Note: If Infilex FC for standalone use is set for BMS network connection, chilled/hot water cannot be detected by using the temperature sensor for

pipe surface.

Figure 2. Connection example: Infilex FC for standalone use with chilled/hot water valve and two Neopanel

Other connectable devices to NC-bus: DIF-II*1/Energy meter

BACnet IP

BMS: Building management system DIF-II: DGP (Data Gathering Panel) line interface-II

Client PC BMS

Infilex AC Model WY5117C

Infilex GC Model WY5111

Infilex GD Model WY5110

NC-bus (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)

Infilex FC Model WY5205

SC-bus*2 (Max. 50 units and 1000 m)

Neopanel Model QY7205

Infilex FC Model WY5205

Temperature sensor

Temperature sensor*4

Neoplate*3, 4

Model QY7290

Infilex ZM*1 Model WY5122

Temperature sensor

Neopanel Model QY7205

Temperaturesensor

Infilex VC Model WY5206

SC-bus*2 (Max. 50 units and 1000 m)

Infilex ZM*1 Model WY5122

Infilex VC Model WY5206

Neopanel Model QY7205

Neopanel*3 Model QY7205

Infilex FC Model WY5205

Neopanel*3

Model QY7205

Infilex FC Model WY5205

Infilex VC Model WY5206

Coil

Valve

: Modular plug

Modular branch unit

Neopanel Model QY7205

Neopanel Model QY7205

Temperature sensor for pipe surface

: LAN cable Fan

Infilex FC Model WY5205

Page 6: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

6

Specifications

Basic specifications

Item Specification

Power Rated voltage 100 V AC to 240 V AC at 50 Hz/60 Hz Operating voltage 85 V AC to 264 V AC Power consumption Valve ON/OFF control type: 6 VA or less

Valve proportional control type: 7 VA or less Environmental conditions

Operating conditions

Ambient temperature 0 °C to 50 °C Ambient humidity 10 %RH to 90 %RH (non-condensing) Altitude Max. 2,000 m Vibration Max. 3.2 m/s² (at 10 Hz to 150 Hz)

Transport /storage conditions

Ambient temperature -20 °C to 60 °C Ambient humidity 5 %RH to 95 %RH (non-condensing) Vibration Max. 9.8 m/s² (at 10 Hz to 150 Hz) for transport

Max. 3.2 m/s² (at 10 Hz to 150 Hz) for storage Mounting location Side surface of FCU, inside of the ceiling, inside of control panel, inside of a box Mounting With two M4 x 10 mm long screws Address setting Rotary switch setting Weight Valve ON/OFF control type: 270 g (main unit only)

Valve proportional control type: 480 g (main unit only) Materials Modified PPE, equivalent to UL 94 V-0

PPE: Polyphenylene ether

Input/output specifications (1/2)

Unit to be connected Input/output description Input/output specification

Temperature sensor Temperature input Measuring range 0 °C to 50 °C Input signal RTD (Pt100)

RTD (Pt1000)*1 Temperature sensor for pipe surface*2

(Part No. 81301851-001 / 81301851-002)

Pipe surface temperature input (for cooling/heating changeover)

Measuring range 0 °C to 50 °C

External relay, etc.*2 Contact input (for cooling/heating changeover)

Connectable output type Potential free contact (maintained) * Min. applicable load: 0.1 mA or lower

Control valve*3 ON/OFF output (for valve ON/OFF control type) Floating proportional output (for valve proportional control type)

Connectable output type Voltage N.O. contact

Contact capacity 0.8 A / 125 V AC or less 0.4A / 250 V AC or less

Min. applicable load 10 mA AC * For the power of valve ON/OFF control type, the power of the fan is used. Select ON/OFF valve with the rated power equal to the FCU power.

Fan Fan ON/OFF output Fan speed changeover output

Valve ON/OFF control, valve proportional control types (M/H output) Connectable output

type Potential free N.O. contact

Contact capacity 3 A / 125 V AC or less 1.5 A / 250 V AC or less

Min. applicable load 10 mA AC Valve proportional control type (L output) Connectable output

type Potential free N.O. contact

Contact capacity 6 A / 125 V AC or less 3 A / 250 V AC or less

Min. applicable load 10 mA AC Neopanel (digital user terminal)

Temperature setting FCU ON/OFF, etc.

Transmission system Serial voltage transmission

Transmission speed 100 bps

RTD: Resistance temperature detector Notes: *1 Because the Pt1000 temperature sensor is a two-wire type sensor, the wire resistance will cause measuring error. For instance,

1.25 mm2 size wire causes approx. 0.1 °C measuring error every 10 m. Correct the measuring error by setting Infilex FC. *2 Either the pipe surface temperature input by the temperature sensor for pipe surface or the contact input by the external relay is used for

cooling/heating changeover of Infilex FC for standalone use. *3 Proportional control valve with less than 30-second operating time (for full stroke) is not connectable. Ask our salesperson for details.

Page 7: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

7

(2/2) Unit to be connected Input/output description Input/output specification

Neoplate (analog user terminal)

FCU switch Connectable output type Potential free contact (instantaneous) x 1 Applied voltage 12 V DC typ. Applied current 10 mA DC typ.

LED output Output type Transistor output Output current 10 mA DC Output voltage 12 V DC typ. Output limiting resistance 1.2 kΩ typ.

Temperature setting input Potentiometer input (1 kΩ to 10 kΩ) Communication SC-bus Transmission system Serial voltage transmission

Transmission speed 4800 bps Power — 100 V AC to 240 V AC (85 V AC to 264 V AC) External switch, etc. DI (contact input) Connectable output type Potential free contact (maintained) x 1

Applied voltage 12 V DC typ. Applied current 5 mA DC typ.

Wire specifications

Item End connection Wire specification Wiring length

Pt100 temperature sensor Connecter connection*1 LAN cable*2 Max. 50 m Pt1000 temperature sensor Connecter connection*3 1.25 mm2 to 2.5 mm2 lead wires + connector

cable for two terminals (Part No. DY7221A) Max. 50 m

Temperature sensor for pipe surface (for cooling/heating changeover of Infilex FC standalone use)

Screwless push-in terminal connection

JIS CVV 1.25 mm2 or equivalent Max. 50 m

External relay, etc. (for cooling/heating changeover of Infilex FC standalone use)

Screwless push-in terminal connection

JIS CVV 1.25 mm2 or equivalent Max. 50 m

Control valve Screwless push-in terminal connection

24 V AC JIS CVV 1.25 mm2 or equivalent Max. 50 m 100 V AC JIS CVV 2.0 mm2 or equivalent

Fan Screwless push-in terminal connection

JIS CVV 2.0 mm2 or equivalent Max. 50 m

Neopanel Connecter connection*1 LAN cable*2 Max. 50 m Neoplate Connecter connection*1 LAN cable*2 Max. 50 m Communication Connecter connection*1 LAN cable*2 Max. 1 km (in total) Power M3.5 screw terminal connection JIS CVV 2.0 mm2 or equivalent — External switch, etc. Screwless push-in terminal

connection JIS CVV 1.25 mm2 or equivalent Max. 50 m

JIS: Japanese Industrial Standards Notes: *1 For connector connection, use Bel Stewart Connector’s Plug: Model SS-37000-002. This plug is also available at Azbil Corporation. (Part No. DY7207A0100, 100 pieces/set) *2 LAN cable compliant with EIA/TIA-568 Category 3 or over (0.5 mm x 4 pairs) is required.

For *1 and *2, the connector cable (regular cable: Part No. DY7210, short cable: Part No. DY7220) are available at Azbil Corporation. *3 Use the short connector cable for two terminals (Part No. DY7221A). Other cables are not acceptable.

Page 8: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

8

100 37 13

9

1(in

terv

al b

etw

een

mou

ntin

g sc

rew

s)

150

120 45

189

1(in

terv

al b

etw

een

mou

ntin

g sc

rew

s)

200

Dimensions

The following figures are images of Infilex FC Pt100 input type. Dimensions of the Infilex FC Pt1000 input type are the same as those of the Infilex FC Pt100 input type.

<Valve ON/OFF control type>

Figure 3. Dimensions (mm): Model WY5205W100X

<Valve proportional control type>

Figure 4. Dimensions (mm): Model WY5205W201X

Page 9: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

9

Installation

CAUTION

Install the product in a location that satisfies the operating conditions (temperature, humidity, power, vibration, shock, mounting direction, atmospheric condition, etc.) as listed in the specifications and use the product within the operating ranges as listed in the specifications. Failure to do so might cause fire or device failure.

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

Precautions for installation

For installing Infilex FC, securely fix with the screws.

Leave maintenance clearance as shown in Figs. 5 and 6.

Vertically mount Infilex FC (upright). Be sure to mount it in a location where the product indication on the front surface can be checked.

Figure 5. Clearances for maintenance (mm): front view

To replace a currently installed IFC (Intelligent Fan Coil Unit Controller) and other former series of FCU controller with Infilex FC, a screwdriver with long grip may not be usable. In such a case, a screwdriver with short grip or wiring before the installation is required.

Figure 6. Clearances for maintenance (mm): side view

Mount Infilex FC upright unless it is protected in a dust-proof housing. (See ‘B’ in Fig. 7.) If this product is mounted with its front surface facing upwards, dust may accumulate on the connectors. (See ‘A’ in Fig. 7.)

.

Figure 7. Mounding direction

Min. 200 Min. 120

Min

. 140

M

in.

70

100 mm long screwdriver

200 mm long screwdriver

Same maintenance clearance is required for the terminals on the lower part.

[1] 7

0 or

mo

re

[2] 1

40 o

r m

ore

[1] 20 or more [2] 20 or more

[1] 20 or more [2] 20 or more

[1] 7

0 or

mo

re

[2] 1

40 o

r m

ore

Note: [1] for 100 mm long screwdriver [2] for 200 mm long screwdriver

Dust Vertical direction

Horizontal direction

A. Bad B. Good

Page 10: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

10

Screw-mount directly on the mounting surface

1) Open two holes for M4 screws on the mounting surface. Leave 139 mm 1 mm interval for valve ON/OFF control type and 189 mm 1 mm interval for valve proportional control type.

Figure 8. Mounting holes layout

2) Mount Infilex FC with two M4 screws.

Figure 9. Mounting with two M4 screws

3) Make sure that Infilex FC is securely fixed on the mounting surface with the screws and does not come off.

IMPORTANT:

Check the length of the mounting screws. Long screws may damage devices behind the mounting surface. Mounting screw tabs of Infilex FC are 5 mm thick each. If you reuse the mounting screws for IFC (Intelligent FCU Controller), the screws are inserted 15 mm deeper inside the mounting surface than IFC.

Mount on the 9 mm (3/8 inches) threaded rod

To mount Infilex FC on a threaded rod (9 mm), use two cable ties.

1) Put cable ties through two holes on the screw tabs (one cable tie for each screw tab) and tie to the threaded rod.

• Infilex FC mounted on the threaded rod may rotate. Do not allow the tension on the cables when wiring.

• Instead of cable ties, two support brackets can be used to mount Infilex FC on the threaded rod. Refer to Fig. 10 for mounting with cable ties and with support brackets

• Mounting bracket Part No. DY7208A0001 (small)/ DY7208A0002 (large) can also be mounted on the threaded rod using cable ties or support brackets.

Figure 10. Mounting on a Ø9 mm threaded rod

2) Make sure that Infilex FC is securely fixed on the threaded rod with cable ties or support brackets and does not come off. Also, make sure that the cable ties or the support brackets are firmly tied to the threaded rod.

Two mounting holes for M4 screws

Valve ON/OFF control type:139 1 mm

Valve proportional control type:189 1 mm

Cable tie Support bracket

Screw tab Screw tab

189±

1mm

139±

1mm

Mountingscrew tab

Mountingscrew tab

5 mm 5 mm

Page 11: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

11

Wiring

WARNING

Be sure to ground the product with ground resistance of less than 100 Ω. Improper grounding might cause electric shock or malfunction.

Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover. Failure to do so might cause electric shock.

Before wiring and maintenance, be sure to turn off the power to the product. Failure to do so might cause electric shock.

CAUTION

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

All wiring must comply with applicable codes and ordinances.

Be sure to provide a circuit breaker for the power to the product as the product does not have a power switch.

To connect the wires to the screw terminals, use crimp terminal lugs with insulation. Failure to do so might cause fire or device failure due to short circuit.

Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating.

For wiring, strip each wire insulation for the length specified in this manual. If the strip length is longer than the specified, the stripped part of the wires will be exposed, causing electric shock or short circuit between adjacent terminals. If it is shorter, the stripped part will not contact the connector.

If more than the rated power voltage is applied to the product, replace the product with new one for your safety. Failure to do so might cause fire.

Page 12: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

12

Wiring diagram: Valve ON/OFF control type (Model WY5205W100X)

IMPORTANT:

Power for the valve actuators is supplied from FCU via Infilex FC. Since the actuator power supply cannot be separated from the FCU, the valves, unless the valve type is spring-return, will not be fully closed (in 0 % position) when the fan is turned off. (A valve in fully closed position is exceptional.)

Note: * For standalone use of Infilex FC in combination with Neoplate (as user terminal) and temperature sensor for pipe surface (for

heating/cooling changeover), use the Infilex FC valve proportional control type and wire ON/OFF valves as shown in Fig. 12.

Figure 11. Wiring diagram of Model WY5205W100X

Table 1. Wiring terminals for valve connection: Valve ON/OFF control type Unit to be connected Terminals 4 and 5 Terminals 6 and 7

Chilled water valve Chilled water valve Leave unconnected. Hot water valve Hot water valve Leave unconnected. Chilled/hot water valve Chilled/hot water valve Leave unconnected. Chilled water valve + hot water valve Chilled water valve Hot water valve Chilled water valve + chilled/hot water valve* Chilled water valve Chilled/hot water valve

Note: * Select the operating order of the valves by setting the parameter.

Infilex FC cannot recognize the status change of a fan coil unit (FCU) if Neoplate switches the FCU from OFF to L or M or H (ON) mode. Therefore, Infilex FC will not detect chilled water/hot water using the temperature sensor for pipe surface. In a case that the detection of chilled water/hot water using the temperature sensor for pipe surface is required, select the Infilex FC valve proportional control type and change its function to the valve ON/OFF control by using the power supply status monitoring. Ask our salesperson for details.

For the Infilex FC valve proportional control type serving the valve ON/OFF control, connect the valve 1 to the terminals 4 and 5 and the valve 2 to the terminals 7 and 8. Supply the power to the valve from a different source (not from Infilex FC).

Figure 12. Wiring of the valve to the Infilex FC valve proportional type serving the valve ON/OFF control

4 5 6 7 8 9

M M

Userterminal*

Temperaturesensor

FAN

100-240 V AC

Ground resistance: 100 Ω or lower

M

14 13 12 11 9 8 10 1 2 3 7 5 4 6

Connected to another Infilex FC (for connection to BMS)

Connected to Infilex ZM or another Infilex FC (for connection to BMS)

Infil

ex F

C

CN1 CN2 CN3 CN4

USER I/F Pt100/ Pt1000

SC-bus IN

SC-bus OUT

16 15

Temperature sensor for pipe surface* (for standalone use)

Contact for cooling/heating changeover (for standalone use)

CO

M

L M H For fan ON/OFF output, connect terminals 11 and 12 to FCU.

FCU

M

Page 13: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

13

Wiring diagram: Valve proportional control type (Model WY5205W201X)

IMPORTANT: If Infilex FC is continuously operated, in a 24-hour operation system for instance, be sure to fully close/open the

valves (in 0 % / 100 % position) at least once a day for accurate operation. (The valves can be forcibly opened/closed by setting the parameter.)

Notes: *1 Provide a transformer when necessary. *2 Connect the terminals 12 and 13 for standalone use.

Figure 13. Wiring diagram of Model WY5205W201X

Table 1. Wiring terminals for valve connection: Valve proportional control type Unit to be connected Terminals 4, 5, and 6 Terminals 7, 8, and 9

Chilled water valve Chilled water valve Leave unconnected. Hot water valve Hot water valve Leave unconnected. Chilled/hot water valve Chilled/hot water valve Leave unconnected. Chilled water valve + hot water valve Chilled water valve Hot water valve Chilled water valve + chilled/hot water valve* Chilled water valve Chilled/hot water valve

Note: * Select the operating order of the valves by setting the parameter.

FAN

16 15 13 12 11 1 2 3 5 4 6

100-240 V AC

Ground resistance: 100 Ω or lower

CN1 CN2 CN3 CN4 USER I/F

Pt100/ Pt1000

SC-bus IN

SC-bus OUT

Connected to another Infilex FC (For connection to BMS)

Connected to Infilex ZMor another Infilex FC

(For connection to BMS)

Userterminal

Temperaturesensor

20 19

H L M

FCU power monitoring

circuit

10 8 7 9 14

23 21 24 22

DI 2 pts. C

OM

Infil

ex F

C

(For standalone use)

Temperature sensor for pipe surface (for standalone use)

Contact for cooling/heating changeover (for standalone use)

FCU

See

Not

e 1

.

O

pen

CO

M

Clo

se

Ope

n

CO

M

Clo

se

Infil

ex F

C

See

Not

e 2

.

See

Not

e 2

.

For fan ON/OFF output, connect terminals 13 and 14 to FCU.

DI1 DI2 COM

M M

Page 14: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

14

Recommended cables

For the cables and wires recommended for wiring Infilex FC, refer to the Wire specifications section.

Power supply wiring

Crimp M3.5 terminals on the power supply wires and connect them to the screw terminals of the product.

IMIPORTANT:

Do not apply 98 Ncm or larger torque for connecting the screw terminals.

Push-in terminal connection

Wires of the temperature sensor for pipe surface (only for Infilex FC for standalone use), DI, FCU ON/OFF output, and control valve output are connected to the screwless push-in terminal block. Follow the procedure below for connecting these wires.

1) Remove the dust protective cover on the push-in terminals.

2) Strip the 5-6 mm insulation of the wire end. Note: * Scale is indicated on the front surface of Infilex FC. If the insulation stripped part is longer or shorter than 5-6 mm, it may get exposed or

may come off from the terminal.

3) Make sure that no wire fiber goes out of the wire end.

4) Connect the wire to the push-in terminal.

5) Gently pull out the wire to make sure it is completely held by the clamp.

6) Bind the cables with cable ties.

Notes: * If an unbound cable is strongly pulled, Infilex FC may get damaged. * Be sure to bind the modular cables separately from power cables.

IMPORTANT:

Do not position any connected cable on the Infilex FC front surface, as shown in Fig. 15.

1. Press.

2. Tilt.3. Insert.

4. Pull out.

Releasing the clamp: When pressing the screwdriver, tiltit along the curving surface insidethe square hole.

1. Insert a slotted screwdriver into a smaller square hole (for clamp release) of apush-in terminal on Infilex FC front surface. At this time, insert the screwdriverto the deep end (approx. 10 mm deep).

2. Tilt the screwdriver while pushing it into the hole. (Make sure the direction to tilt,as shown in Fig. 14.) When the screwdriver is proceeded to the deep end, the clamp is completelyreleased. The screwdriver remains in the inserted position even when yourelease your hand from the screwdriver.

Notes: * A slotted screwdriver with the blade 3.5 mm wide and 0.5 mm thick (straight

type) is acceptable. A screwdriver with the blade tip narrower than the shaftmay not be acceptable. Appropriate screwdriver (an example): Model 9900 (3 mm wide x 100 mm long) or Model 910 (3 mm wide x 75 mmlong) manufactured by Vessel Co., Inc.

* Since the terminal block has the inclined surface, required clearance formaintenance varies depending on the length of the screwdriver to be used.Note that a long screwdriver (80 mm or longer) may not be usable for the InfilexFC replaced from IFC since IFC requires smaller maintenance clearance.

3. Insert the wire end (5-6 mm long stripped part) into a larger square hole to thedeep end.

4. Pull out the screwdriver while keeping the wire end inserted.

Note: * For wiring of FCU ON/OFF output and control valve output, refer to the Wiring

diagram sections.

Figure 14. Connecting a wire to a screwless push-in terminal

Good cable binding

Bad cable binding

Figure 15. Good and bad cable binding.

Page 15: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

15

Note for connecting wires with 1.8 mm or smaller outer diameter to the push-in terminals Wires with 1.8 mm or smaller outer diameter connected to the push-in terminals may cause short-circuit due to dust accumulated in clearance in the terminal. To prevent short-circuit, put a tube* through the wire so that the terminal is covered. (See Fig. 16.) Separately order the tubes if necessary.

Note: * Tubes are commercially available and also available at Azbil Corporation. (Part No. 83167219-001, 6 pieces/set) Connection of 1.8 mm or smaller wires without tubes Connection of 1.8mm or smaller wires with tubes

Figure 16. Connection of 1.8 mm or thinner wires to the screwless push-in terminals with and without tubes

Wiring of user terminal / Pt100 temperature sensor to Infilex FC

User terminal and Pt100 temperature sensor are wired to Infilex FC with modular connection. For correctly crimping modular plugs on a LAN cable, refer to the following.

Modular connector connection

Modular connector is composed of a modular plug (male) and a modular jack (female). Modular jacks are provided on Infilex FC, and modular plugs will be crimped on LAN cables as required. Refer to the following procedure for crimping the modular plugs on the LAN cables and connecting them to the modular jacks.

Note: * For modular plugs, refer to Note *1 of the Wire specifications section.

1) Strip the outer sheath of a LAN cable end. Be sure not to scratch or peel off any wire insulation when stripping the sheath.

Figure 17. Stripping the sheath

Make sure there are eight wires inside the sheath.

2) Align the eight wires in the order specified by the LAN cable manufacturer. An alignment example of the LAN cable wires is shown in the table below.

Figure 18. Alignment of the wires

Note: * The wire colors shown above may not agree with your LAN cable specification. Ask your LAN cable manufacturer for the latest specification.

LAN cable

Pin numbers 12345678

8 wires

LAN cable

Modular plug pin number

Wire alignment

Wire color code

1 Line 2 of pair 2 White and orange 2 Line 1 of pair 2 Orange 3 Line 2 of pair 3 White and Green 4 Line 1 of pair 1 Blue 5 Line 2 of pair 1 White and blue 6 Line 1 of pair 3 Green 7 Line 2 of pair 4 Brown and white 8 Line 1 of pair 4 Brown

Dust

Tube

1.8 mm or thinner wire

1.8 mm or thinner wire

Push-in terminal Push-in terminal

Page 16: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

16

3) Insert the aligned wires into a modular plug.

Figure 19. LAN cable insertion into a modular plug

Pin assignment of the modular plug in Fig. 19 is the image when the contacts and the cable stopper of the modular plug are viewed from above.

Before inserting the wires into the modular plug, even out the length using a nipper. Note that the modular plug may not be crimped on wires if the wires without the outer sheath are too long.

4) Crimp the modular plug using a crimper. Insert the wires into the modular plug so that the contacts of the modular plug stick into the wires after crimping. Crimped modular plug is secured on the LAN cable by the cable stopper of the modular plug. Check the contacts and the cable stopper when crimping the modular plug.

5) Follow 1) to 4) for the other end of the LAN cable.

6) Check continuity of the LAN cable. At the same time, make sure that the wires are aligned in the specified order, the modular plug contacts stick into the wires, and that there is no cable damage or disconnection.

Note: * Modular cable tester (Part No. DY7206A0000) facilitates the continuity check.

7) Connect the modular plugs to the modular jacks. After successfully finishing the continuity check, insert a modular plug of the LAN cable into the modular jack of Infilex FC and the other modular plug into the modular jack provided for connecting to the user terminal / Pt100 temperature sensor.

Note: * Insert a modular plug until it clicks and gently pull the cable to check complete connection.

Cable stopperContacts

Insert.

10 mm 3 mm

(For the recommended modular plug)

LAN cable

Modular plug

Pin numbers

8 7

4 5

3

1 2

6

Pin assignment of the modular plug

Page 17: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

17

Wiring of Pt1000 temperature sensor to Infilex FC

Pt1000 temperature sensor is also wired to Infilex FC with modular connection, and the short connector cable for two terminals Part No. DY7221A is required for wiring. Refer to the following for details.

1) Connect the modular plug of Part No. DY7221A to the connector CN2 of Infilex FC.

Figure 20. Connection of the connector cable for two terminals to Infilex FC

See the following for the pin assignment of the connector cable for two terminals Part No. DY7221A (between sides A and B).

Side A Side B

Wire color Pin number

Orange 1

Orange and white 2

Green 3

Blue and white 4

Blue 5

Green and white 6

Brown 7

Brown and white 8

2) Splice the two wires (side B) of Part No. DY7221A and the wires from the Pt1000 temperature sensor with insulation sleeves.

Note: * The Pt1000 temperature sensor is a two-wire sensor.

Because wire resistance causes measuring error, longer cable, which has larger wire resistance, will cause greater measuring error. Use Part No. DY7221A (0.1–1.0 m long), and extend the sensor cable (1.25–2.5 mm2 size) if needed.

CN2

Infilex FC Model WY5205WXXXK

Short connector cable for two terminals Part No. DY7221AXXXX

* "XXXX" differs depending on the cable length (0.1 m to 1.0 m).

Side A Side B

Page 18: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

18

Optional Parts and Tools

Precautions for use

The optional modular branch unit, modular relay unit, adapter for connecting to a user terminal, adapter for connecting to a Pt100 temperature sensor, short connector cable for two terminals must be installed inside junction boxes or in the control panel cabinet.

For modular connection, a modular plug must be inserted into a modular jack until it clicks. Gently pull the modular cable to check that the modular plug is locked in the modular jack after the connection.

Optional parts

Modular branch unit: Used to branch out the communication line for two user terminals to be connected.

Figure 21. Modular branch unit: Part No. DY7203A0000

Modular relay unit: Used to extend the communication line by connecting to another communication line.

Figure 22. Modular extension unit: Part No. DY7202A0000

Adapter for connecting to a user terminal: Used to connect analog user terminal (with fan speed changeover function) to this product.

Figure 23. Adapter for connecting to a user terminal: Part No. DY7204A0008

Adapter for connecting to a Pt100 temperature sensor: Used to connect a Pt100 temperature sensor to this product.

Figure 24. Adapter for connecting to a Pt100 temperature sensor: Part No. DY7204A0003

Connector cable for two terminals: Used to connect a Pt1000 temperature sensor to this product.

Figure 25. Connector cable for two terminals: Part No. DY7221A

Modular plug: Crimped on the end of LAN cable for connection to a modular jack.

Figure 26. Modular plug: Part No. DY7207A0100

Tube: Used when wires with 1.8 mm or smaller diameter are connected to the push-in terminals of Infilex FC. Prepare the tubes supplied by Azbil Corporation shown in Fig. 27 or the tubes that meets the specifications shown in Fig. 28.

Figure 27. Tubes (Part No. 83167219-001, 6 pieces/set)

JCS: Japanese Electric Wire and Cable Makers' Association Standard

Figure 28. Tube (commercially available)

55.6

64

40.5

50

1

Inte

rval

bet

wee

n m

ount

ing

scre

ws

Unit: mm

5.0

0.4

3.4

1.8

Applicable wire: JCS KV 0.5 mm2 Unit: mm

17.3

28.0 16.3 Unit: mm

Page 19: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

19

Mounting bracket (large and small sizes): Used to replace IFC with Infilex FC. Extra mounting holes will not be necessary by attaching Infilex FC to the mounting bracket.

Small mounting bracket Part No DY7208A0001 for Model WY5205W100X (valve ON/OFF control type)

Figure 29. Small mounting bracket (Part No. DY7208A0001)

Large mounting bracket Part No. DY7208A0002 for Model WY5205W201X (valve proportional control type)

Figure 30. Large mounting bracket (Part No. DY7208A0002)

Optional tools

Modular crimper: Used to crimp a modular plug on a LAN cable.

Figure 31. Modular crimper: Part No. DY7205A0002

Modular cable tester: Used to check continuity of a LAN cable with modular plugs crimped on.

Figure 32. Modular cable tester: Part No. DY7206A0000

100 71.5 38 20 10

195

151

138

181

Two M4Two M4

M4

4.5(two holes)

5.5 (three holes)

4.5

M4

100 82 38

10

240

151

189

M4

4.5(two holes)

5.5 (three holes)

4.5

M4 Three M4

139

225

Page 20: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

20

Software Details (1/3)

Item Function Description Remarks

Operation (available for valve ON/OFF control and for valve proportional control types)

FCU ON/OFF Turns on/off the fan coil units (FCU) by operating the BMS client PC, digital input (DI), or the user terminal.

- Each Infilex FC can individually turn on/off the FCU.

- The latest user terminal/BMS client PC/DI operation is effective.*2

- FCU ON/OFF function using the user terminal can be disabled by the BMS client PC.

- Once FCU ON/OFF function is set, you can not turn on the Setback function with the user terminal. (The user terminal allows you to operate either FCU ON/OFF or FCU ON/Setback ON.)

Setback Adds/Subtracts the setback value to/from the set temperature. Switches to the Setback operation by operating the BMS client PC or the user terminal. The setback value is preset at Infilex FC.

- Each Infilex FC can individually change the set temperature for the setback operation.

- The latest user terminal/BMS client PC/DI operation is effective.

- Setback function using the user terminal can be disabled by the BMS client PC.

- Once Setback function is set, you can not turn off the FCU with the user terminal. (The user terminal allows you to operate either FCU ON/Setback ON or FCU ON/OFF.)

Temperature setting Changes the set temperature by operating the BMS client PC or the user terminal.

- The latest user terminal/BMS client PC operation is effective.*3

- High/low limit of the setpoint is set by the BMS client PC.

- Dual setting is available. *4

FCU interlocking with OAHU*1

Interlocks the ON/OFF operations of the FCU with those of the outdoor air handling units (OAHU) if the FCU and OAHU are mixed in the same group.

One Infilex ZM controls up to four groups.

- Do not set the OAHU interlocking with FCU function when you set the FCU interlocking with OAHU function.

- Do not operate FCU ON/OFF with the user terminal when you set the FCU interlocking with OAHU function.

OAHU interlocking with FCU*1

Interlocks the ON/OFF operations of the OAHU with those of the FCU if the OAHU and FCU are mixed in the same group, when any of FCU in the group is turned on.

- One Infilex ZM controls up to four groups.

- Do not set the FCU interlocking with OAHU function when you set the OAHU interlocking with FCU function.

Control (available for valve ON/OFF control type)

Temperature control Controls ON/OFF valves so that the actual (measured) temperature matches the preset temperature. *5

Fan speed control Controls fan speed at multiple speed levels in response to the difference between the actual temperature and the preset temperature. Fan speed levels are selectable from L/M/H(low/medium/high) type or L/M/H/OFF type.

Fan speed control function is available when the fan speed is set to AUTO. When L, M , or H fan speed is manually set, the set fan speed is maintained.

Control (available for valve proportional control type)

Temperature control PID-controls floating valves so that the actual (measured) temperature matches the preset temperature. *5

Noise control Shut off the valves when their position reaches or reaches below the specified to prevent the water flushing noise.

Fan speed control Controls fan speed at multiple speed levels in response to the difference between the actual temperature and the preset temperature. Fan speed levels are selectable from L/M/H(low/medium/high) type or L/M/H/OFF type. Water- or airflow-priority control*6 is selectable according to what is needed.

Fan speed control function is available when the fan speed is set to AUTO. When L, M , or H fan speed is manually set, the set fan speed is maintained.

Page 21: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

21

(2/3) Item Function Description Remarks

Control (available for valve ON/OFF control and for valve proportional control types)

Cooling/heating changeover*1

Receives the following items sent from the BMS when cooling/heating changeover is required: Enable cooling, enable heating, enable cooling and heating, fan only (disable cooling and heating).

One Infilex ZM controls up to eight groups for cooling/heating changeover.

Mixing loss control*1 Sets the difference between the set temperature of the perimeter zone air conditioning unit and the interior zone air conditioning unit that are interlocked. This prevents the mixing loss.

- One (group of) Infilex FC interlocks with another (group of) Infilex FC and one (group of) Infilex VC.

- Do not operate the air conditioning unit connected to slave-Infilex FC with the user terminal.

Optimum temperature control of OAHU supply air*1

Controls the OAHU supply air temperature at the optimum level in response to the operating load of FCU to provide comfort and to save energy for OAHU fan power.

One Infilex ZM controls up to four groups.

VWV/VWT control

Adequately controls supply water pump in response to the operating load of FCU to cut back the pump feed power. Also sets the chiller outlet temperature at the optimum level to enhance the chiller operating efficiency

One Infilex ZM controls up to four groups.

Parallel operation of multiple FCU: FCU ON/OFF, valve open/close, and fan speed*1

Concurrently turns on/off the multiple FCU, changes the position (opening) of multiple FCU valves, and changes the speed level of multiple FCU fans.

- Master- and slave- Infilex FC must be connected to the same SC-bus line.

- Fan speed levels setting of master- and slave- Infilex FC must be the same.

- L/M or L/M/H fan speed levels must be set for fan AUTO operation.

- Do not operate the FCU connected to slave-Infilex FC with the user terminal.

Monitoring (available with the BMS client PC).

Individual monitoring*1

Monitors and controls the point data of Infilex FC from the BMS client PC. The following are examples of the point data for Individual monitoring: FCU ON/OFF, alarm, room temperature, room temperature setting, high/low limit setting, setback, fan speed changeover, valve position, cooling/heating status, control status*7 (Not all of the items above are required to monitor or control with the client PC.)

Group monitoring*1 Monitors and controls the point data of grouped Infilex FC. The following are examples of the point data for Group monitoring. FCU ON/OFF, room temperature*8, room temperature setting, high/low limit setting, setback (Not all of the items above are required to monitor or control with the client PC.)

- One Infilex ZM controls up to 25 groups. (Various grouping is available.)

- Point data for group monitoring cannot be individually monitored or controlled.

- Not all the point data of grouped Infilex must be monitored or controlled in group. (e.g. VAV ON/OFF for group monitoring and room temperature for individual monitoring can be set.).

- One Infilex FC can belong to only one group.

Batch operation*1 Forcibly opens and closes all the FCU valves. This facilitates pipe flushing.

- Valves controlled by all the Infilex FC connected from a certain Infilex ZM are subject to batch operation.

- Batch operation can be performed by Infilex ZM as well as by the BMS client PC.

Automatic ON/OFF for standalone use (available for valve proportional control type)

FCU ON/OFF Automatically turns on/off FCU according to the FCU power status detected by the FCU power monitoring circuit.

When FCU turns on (from OFF state): Infilex FC will turn on. When FCU turns off (from ON state): Infilex FC will turn off. (Operating status is set with the parameter.).

VWV/VWT: Variable water volume/variable water temperature

Page 22: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

22

(3/3) Item Function Description Remarks

Digital inputs (available for valve proportional control type)

Alarm input Accepts the DI (digital input) 1 value to the alarm point. The alarm point is NML (0) when the contact of DI 1 is open and is ALM (1) when the contact of DI 1 is closed.

Status input Accepts the DI 2 value to the status point. The status point is OFF (0) when the contact of DI 2 is open and is ON (1) when the contact of DI 2 is closed.

Interlock operation with DI (available for valve proportional control type)

FCU interlocking with alarm input

Turns off the FCU when the alarm input is ALM. FCU ON/OFF function using the user terminal can be disabled when the alarm input is ALM.

The Automatic ON/OFF for standalone use function cannot be set when the FCU interlocking with status input function is enabled.

FCU interlocking with status input

Enables FCU ON/Setback ON function when the status input is OFF. FCU ON/OFF function using the user terminal can be disabled when the status input is OFF.

The Automatic ON/OFF for standalone use function cannot be set when the FCU interlocking with status input function is enabled.

Notes: *1 These functions are enabled by Infilex FC being combined with Infilex ZM and other controllers integrated in our BMS. *2 The latest ON/OFF operation with an analog user terminal may not be effective. *3 The latest setting operation with an analog user terminal is not effective. *4 Dual setting is the method to have cooling setting and heating setting separately. *5 Any combination of the following valves can be used for the temperature control:

Chilled/hot water valve, chilled water valve, hot water valve, chilled water valve + hot water valve, and chilled water valve + chilled/hot water valve. For the chilled water valve + chilled hot water valve combination, select the operating order of the valves by setting the parameter. Either of "chilled water valve chilled/hot water valve" or "chilled/hot water valve chilled water valve" is selectable.

*6 “Water-priority” control is the control that opens the valves first and then increases the fan speed. This prevents excessive fan speed (airflow volume) and fan noise. “airflow-priority” control is the control that closes the valves as much as possible at the low fan speed and widely opens the valves after increasing the fan speed. This widens the temperature difference between the coil inlet and outlet, leading to the effective chiller plant control.

*7 Control status is an index of FCU load. The index is used for supply air temperature control of OAHU or VWV/VWT control. *8 Room temperature for the group monitoring is either the average value in a group or the representative value of a group.

Page 23: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

23

LED Indication

After the power is applied to Infilex FC, check that the status indicator LED blinks in approx. 10 seconds. If it stays ON, Infilex FC is in an abnormal status. The LED is ON for several seconds immediately after the power is applied, but this does not indicate an error. LED indication is described on the front surface of Infilex FC. (See Figs. 33 and 34.)

Status LED indication (: ON / : OFF)

Normal Normal

Power OFF Power Off

SC-bus error SC-bus Err

Initializing / Error

Error 1

Minor error

Error 2

Figure 34. Descriptions of LED indication

Figure 33. LED indication

Setting

The following settings must be performed by a technical engineer.

Address setting Two address setting switches are located on the front surface of Infilex FC. The switch with "X10" indicates tens of the address, and the switch with "X1" indicates ones of the address. Turn the address setting switches using the Phillips screwdriver to set the address.

Parameter setting Infilex FC parameters are set in response to the size and type of FCU, room characteristics, and applications. Use our engineering tool Data Setter (Model QY5111) to set the parameters of Infilex FC. Connect Data Setter to Infilex ZM or to Infilex FC with the Data Setter adapter (Part No. DY7201W0000). For setting the parameters of Infilex FC for standalone use, Neopanel is also available.

To Connect Two User Terminals

Up to two digital user terminals (Neopanel Model QY7205C) can be connected to one Infilex FC.

To connect the two user terminals, the following are required.

Modular branch unit (Model DY7203A0000)

Neopanel with address 1 and with address 2 Note that two Neopanel with address 1 connected to the Infilex FC will not work.

For two Neopanel connection, provide Model QY7205CXXX1 for the address 1 and Model QY7205CXXX2 for the address 2. Address number is indicated on the shipping carton and on the label attached to the inside surface of the Neopanel main unit (with the base cover removed).

Notes: * The latest FCU ON/IFF operation or temperature setting operation with a Neopanel or with the BMS client PC is effective. * Neopanel with address 2 does not have the temperature measuring function.

1s 1s

0.25s 0.25s

1s 0.25 s

0.25 s 0.25 s

Valve proportional control type

LEDValve ON/OFF control type

LED

Descriptions of LED indication

Address setting switches

Descriptions of LED indication

Address setting switches

Page 24: Infilex FC Fan Coil Unit Controller for SC-bus ... · PDF fileConnector cable for two terminals ... BMS: Building management system DIF-II: DGP (Data Gathering Panel) ... Item Specification

AB-6567

Infilex, PARAMATRIX, and SmartScreen are trademarks of Azbil Corporation in Japan or in other countries. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). CompactFlash is a U.S. registered trademark of SanDisk Corporation.

Specifications are subject to change without notice.

Building Systems Company

http://www.azbil.com/

Rev. 9.0 Mar. 2018 AB-6567

(J: AI-6567 Rev. 5.3)

24

Install this product where it is accessible only to people with sufficient knowledge concerning electrical equipment. This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive (EMCD), the Low Voltage Directive (LVD) and the Restriction of Hazardous Substances Directive (RoHSD).