Industrial Ventilation vs. IAQ

130
Industrial Ventilation vs. IAQ Heating Ventilation Air Conditioning

description

Industrial Ventilation vs. IAQ. H eating V entilation A ir C onditioning. Industrial Ventilation vs. IAQ. 24. Industrial Ventilation vs. IAQ. Industrial Ventilation vs. IAQ. Routes of Entry. Inhalation Ingestion Absorption Injection. Control Options. Process change Substitution - PowerPoint PPT Presentation

Transcript of Industrial Ventilation vs. IAQ

Page 1: Industrial Ventilation vs. IAQ

Industrial Ventilation vs. IAQ

Heating

Ventilation

Air

Conditioning

Page 2: Industrial Ventilation vs. IAQ

Industrial Ventilation vs. IAQ

HVAC System Functions

Heating

Cooling

Ventilation

Filtration

Dehumidification

Humidification

Distribution

Page 3: Industrial Ventilation vs. IAQ

Industrial Ventilation vs. IAQ

Page 4: Industrial Ventilation vs. IAQ

Industrial Ventilation vs. IAQ

Page 5: Industrial Ventilation vs. IAQ

Routes of Entry

• Inhalation

• Ingestion

• Absorption

• Injection

Page 6: Industrial Ventilation vs. IAQ

Control Options

• Process change

• Substitution

• Isolation

• Ventilation

• Administrative control

• Personal protective equipment

Page 7: Industrial Ventilation vs. IAQ

Problem Characterization

BURTON 2-1

EMISSION SOURCE

AIRFLOW

Page 8: Industrial Ventilation vs. IAQ

Burton Ex. 2-1

BURTON 2-4

GROUP EXERCISE

Study the figure on page 2-4 and discuss potential control measures that you might use to correct the problem.

Page 9: Industrial Ventilation vs. IAQ

THE BEHAVIOR OF AIR

Page 10: Industrial Ventilation vs. IAQ

The Atmosphere

• Reaches 50 miles into space.

• Pressure = 14.7 pounds per square inch.

Page 11: Industrial Ventilation vs. IAQ

Composition of Air

Percentage Composition by Volume

Nitrogen

Oxygen

Argon

Page 12: Industrial Ventilation vs. IAQ

Pressure Measurement

VacuumAtmospheric Pressure14.7 psia

Page 13: Industrial Ventilation vs. IAQ

Pressure Measurement

14.7 psia =407in. Water

14.7 psia =29.92 in. Mercury (Hg.)

Page 14: Industrial Ventilation vs. IAQ

How Do We Make Air Move ?

Page 15: Industrial Ventilation vs. IAQ

Pressure

• Differences in air pressure cause movement.

Page 16: Industrial Ventilation vs. IAQ

Pressure Differential Causes Movement

BURTON 3-6

FLOW LOW HIGH

FAN

Page 17: Industrial Ventilation vs. IAQ

Negative Pressure = Less Than Atmospheric

Page 18: Industrial Ventilation vs. IAQ

Positive Pressure = Greater Than Atmospheric

Page 19: Industrial Ventilation vs. IAQ

Pressure Relationships

Page 20: Industrial Ventilation vs. IAQ

Pressure Terms

• Static Pressure

• Velocity Pressure

• Total Pressure

Page 21: Industrial Ventilation vs. IAQ

Static Pressure

SPFlow

Static pressure (SP) isexerted in all directions.

Page 22: Industrial Ventilation vs. IAQ

Velocity Pressure

SPFlow

Velocity Pressure (VP) iskinetic (moving pressure) resulting from air flow.

VP

Page 23: Industrial Ventilation vs. IAQ

Total Pressure

SPFlow

Total pressure (TP) is the algebraic sum of the VP and SP.

VP

TP

Page 24: Industrial Ventilation vs. IAQ

Pressure Upstream and Downstream of the Fan

BURTON 3-8

TP SP VP

Up-stream - - +

Down-stream + + +

Page 25: Industrial Ventilation vs. IAQ

What is use of the term “Velocity Pressure” ?

• Determine the air flow.

• To design the system.

• V = 4005(VP)1/2

Page 26: Industrial Ventilation vs. IAQ

What is use of the term “Static Pressure” ?

• Accelerate the air.

• Overcome resistance to friction.

Page 27: Industrial Ventilation vs. IAQ

Static Pressure and Velocity Pressure are Mutually

ConvertibleWhen air is accelerated, the static pressure is converted to velocity pressure.

When air is decelerated, the velocity pressure can be transformed back into static pressure.

=

Page 28: Industrial Ventilation vs. IAQ

Conservation of Mass

• Mass in = Mass out.

• Air speeds up when the duct area is smaller.

Q = VA

Q = Cubic Feet Per MinuteV = VelocityA = Area

Page 29: Industrial Ventilation vs. IAQ

Dilution Ventilation

BURTON 4-1

YES• non-hazardous

• gas, vapor, respirable particle

• uniform time emission

• emissions not close to people

• moderate climate

NO• toxic material

• large particulate

• emission varies widely over time

• large, point source emissions

• people in vicinity

• severe climate

• irritation or complaints

Page 30: Industrial Ventilation vs. IAQ

Volume Vapor Flow Rate

BURTON 4-3

Page 31: Industrial Ventilation vs. IAQ

Estimating Dilution Air Volume

BURTON 4-5

Page 32: Industrial Ventilation vs. IAQ

Poor Dilution

Page 33: Industrial Ventilation vs. IAQ

Good Dilution

Page 34: Industrial Ventilation vs. IAQ

Example 4-1

BURTON 4-6

What is q, the volume flow rate of vapor formed, if 0.5 gallons of toluene are evaporated uniformly over an 8-hr. shift? What volume flow rate Qd is required for dilution to 10 ppm, if Kmixing = 2 ? (Assume STP; d = 1.0)

What is the average face velocity of air in a room 10ft. * 8ft. * 40ft for these conditions?

Page 35: Industrial Ventilation vs. IAQ

Strategy Ex. 4-2

Step 1: Calculate the volume flow rate of the vapor

emitted q.

q = (387 * lbs. evaporated)/ (MW * t * d)

Note:lbs. Evaporated = gal. * 8.31 * SG

Step 2. Calculate the dilution air volume flow rate

Qd.

Qd = q * 106 * K mixing

Ca (ppm)

Step 3: Calculate the face velocity.

V face = Qd/A

Step 4: Calculate the air changes/ hour.

N = (Qd * 60)/Vr

Page 36: Industrial Ventilation vs. IAQ

Purge and Buildup

BURTON 4-9

• Purge and buildup - predict contaminant buildup or purge rate.

• Steady state -equilibrium maintained.

Page 37: Industrial Ventilation vs. IAQ

Example 4-5

An automobile garage was severely contaminated with carbon monoxide.

How long will it take to purge the garage?

BURTON 4-11

Page 38: Industrial Ventilation vs. IAQ

BURTON 11-1

Chapter 11 - Makeup Air Balance

• Exhausted air must be replaced.

• Negative pressure without makeup air.

Page 39: Industrial Ventilation vs. IAQ

Make up Air

• Fresh air supplied into the breathing zone of the associate.

Page 40: Industrial Ventilation vs. IAQ

Overcoming Negative Static Pressure

BURTON 11-2

• Changes in static pressure involving radial (squirrel cage) fans cause a small change in the volumetric flow rate.

• Changes in static pressure involving axial (propeller) fans cause a large change in the volumetric flow rate.

Page 41: Industrial Ventilation vs. IAQ

Good Makeup Air

INDUSTRIAL VENTILATION 2-4

Page 42: Industrial Ventilation vs. IAQ

Bad Makeup Air

INDUSTRIAL VENTILATION 2-4

Page 43: Industrial Ventilation vs. IAQ

Reentrainment

BURTON 11-9

Page 44: Industrial Ventilation vs. IAQ

Reentrainment

BURTON 11-9

Page 45: Industrial Ventilation vs. IAQ

Avoiding Reentrainment10-50-3000 RULE

BURTON 14-5

Page 46: Industrial Ventilation vs. IAQ

Recirculation of Exhaust Air

BURTON 12-1

• Good for non-toxic particulate control.

• Can recover 40-60% of heat energy.

Page 47: Industrial Ventilation vs. IAQ

Types of Ventilation Systems

BURTON 5-1

Page 48: Industrial Ventilation vs. IAQ

Why Choose Local Ventilation?

BURTON 5-2

• No other controls • Containment• Employee in vicinity• Emissions vary with

time• Sources large and

few• Fixed source• Codes

Page 49: Industrial Ventilation vs. IAQ

Exercise 5-3

BURTON 5-3

Form your group and try exercise 5-3. Compare the operation to the parameters listed below:

• No other controls available

• Hazardous contaminant

• Employee in immediate vicinity

• Emissions vary with time

• Emission sources large and few

• Fixed emission source

• Codes & standards

Page 50: Industrial Ventilation vs. IAQ

Components of a Local Exhaust System

BURTON 5-4

Page 51: Industrial Ventilation vs. IAQ

Static Pressure Review

BURTON 5-5

Page 52: Industrial Ventilation vs. IAQ

Energy Conservation

BURTON 5-6

Page 53: Industrial Ventilation vs. IAQ

Basic Air Flow Equations

BURTON 5-7

• Q = V * A

• TP = SP + VP

• V = 4005(VP/d)0.5

Page 54: Industrial Ventilation vs. IAQ

Static Pressure Loss

BURTON 5-8

• Static Pressure Loss = Kloss * VP * d

Page 55: Industrial Ventilation vs. IAQ

Elbow Loss

BURTON 5-9

Air moving through elbows spends static pressure because of:

• directional change • friction • shock losses• turbulent mixing• air bunching up • SP(loss) = K(elbow )* VP * d

Page 56: Industrial Ventilation vs. IAQ

Elbow Loss Ex. 5-8

BURTON 5-9

What is the elbow loss factor K(elbow) where the elbow radius of curvature is R/D = 2.0 in a smooth transition elbow.

Page 57: Industrial Ventilation vs. IAQ

Elbow Loss Exercise 5-9

BURTON 5-10

What is the actual loss in inches of water of air flowing through a 60-degree, 3-piece elbow at V = 3440 fpm? R/D = 1.5, STP, d=1.

Page 58: Industrial Ventilation vs. IAQ

Elbow Loss Exercise 5-9

• SPloss = K * VP * d

• Use Chart 13, Appendix pg. 25 for information on a 90-degree 3- piece elbow with R/D = 1.5

• Let K = (angle/90) * K 90

• VP = (V/4005)2

Page 59: Industrial Ventilation vs. IAQ

Friction Loss as a Function of Duct Length

BURTON 5-11

Friction Loss = K * VP * L * R * d• K is a value taken from Chart #5,

appendix page 9 • VP is duct velocity pressure, in w.g.• L is the length of the duct in feet• d is the density correction factor• R is roughness correction factor

Page 60: Industrial Ventilation vs. IAQ

Exercise 5-10

What is the friction loss for a length of galvanized duct with the following parameters? D = 8in., Q = 1000scfm, L = 43 ft. R = 1.

Page 61: Industrial Ventilation vs. IAQ

Tee Losses

BURTON 5-11

Page 62: Industrial Ventilation vs. IAQ

Tee Losses Ex. 5-12

BURTON 5-12

What is the estimated static pressure loss in inches of water for a branch entry of 30 degrees where the branch entry velocity is 4500 fpm?

Page 63: Industrial Ventilation vs. IAQ

Converting Static Pressure To Velocity Pressure

BURTON 6-2

At the hood, all of the available static pressure is converted to velocity pressure and hood entry loss.

SPh = VP + he

Page 64: Industrial Ventilation vs. IAQ

Measuring Hood Static Pressure

BURTON 6-2

Measure hood static pressure 4-6 duct diameters downstream from the hood.

4-6 D

Page 65: Industrial Ventilation vs. IAQ

Hood Entry Losses

BURTON 6-2

The hood entry loss is the sum total of all losses from the hood face to the point of measurement in the duct.

SP(loss) = K * VP * d

he = K * VP * d

Page 66: Industrial Ventilation vs. IAQ

BURTON 6-3

Example 6-1

What is the hood static pressure when the duct velocity pressure is VP = 1.10 in. w.g. and the hood entry loss is

he = 1.00 in w.g.

SPh = VP + he

SPh = 1.10+ 1.00

= -2.10 in w.g.

Page 67: Industrial Ventilation vs. IAQ

Vena Contracta

BURTON 6-3

The greatest loss normally occurs at the entrance to the duct, due to the vena contracta formed in the throat of the duct.

Page 68: Industrial Ventilation vs. IAQ

Hood Efficiency

BURTON 6-4

A hood’s efficiency can be described by the ratio of actual to ideal flow. This ratio is called the Coefficient of Entry, Ce.

Ce = Q(actual)/Q(ideal)

Page 69: Industrial Ventilation vs. IAQ

Hood Static Pressure and Entry Losses Example 6-5

BURTON 6-5

The average velocity in a duct serving a hood is V = 2000 fpm. The loss factor for the hood has been obtained from the manufacturer as Khood = 2.2. What are the he and SPh? (Assume STP, d = 1)

Page 70: Industrial Ventilation vs. IAQ

Hand Grinding Table Example 6-6

BURTON 6-6

Assume that a special hand grinding table hood has been built and the following data have been measured:

SPh = -2.50 in w.g., V = 4000fpm, and the duct diameter is 18 in. (Assume STP, d=1)

Page 71: Industrial Ventilation vs. IAQ

Types of Hoods

• Receiving

• Capturing

• Enclosing

BURTON 6-10

Page 72: Industrial Ventilation vs. IAQ

Hood Types

• SLOTTED HOOD

Page 73: Industrial Ventilation vs. IAQ

Hood Types

• ENCLOSED HOOD

Page 74: Industrial Ventilation vs. IAQ

Hood Types

• ENCLOSING HOOD

Page 75: Industrial Ventilation vs. IAQ

Hood Types

• CAPTURING HOOD

Page 76: Industrial Ventilation vs. IAQ

Grinding Wheel Hood Example Example 6-9

BURTON 6-12

Determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh, for a grinding wheel hood, wheel diameter = 13in. (low surface speed), straight take off [sto], STP)

Page 77: Industrial Ventilation vs. IAQ

EXERCISE 6-10USEFUL FORMULAS

Q = V * A

V = 4005(VP)1/2

VP = (V/4005)2

he = K * VP

SPh = VP + he

BURTON 6-12 AND 6-13

Page 78: Industrial Ventilation vs. IAQ

Exercise 6-10a Where appropriate, determine the volume flow rate,

transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a grinding wheel hood with a wheel diameter of 14 in. (low surface speed, tapered takeoff [tto]. Note: the picture in the book is for a buffing hood.

BURTON 6-12

Page 79: Industrial Ventilation vs. IAQ

Exercise 6-10a Strategy

1. Use Chart 11C, appendix pg. 18 to find Q, Vtrans., K, and Ce.

2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.

3. Calculate Vactual = Q/A

4. VP = (Vactual/4005)2

5. he = K * VP

6. SPh = VP + he

Page 80: Industrial Ventilation vs. IAQ

Exercise 6-10b

Where appropriate, determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a hand grinding table 10 feet long by 2 feet wide.

BURTON 6-13

Page 81: Industrial Ventilation vs. IAQ

Exercise 6-10b Strategy1. Use Chart 11C, appendix

pg. 18 to find Q, Vtrans., K, and Ce.

2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.

3. Calculate Vactual = Q/A

4. VP = (Vactual/4005)2

5. he = K * VP

6. SPh = VP + he

Page 82: Industrial Ventilation vs. IAQ

Exercise 6-10c

Where appropriate, determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a band saw used to cut wood that has a blade width of 1 inch.

BURTON 6-13

Page 83: Industrial Ventilation vs. IAQ

Exercise 6-10c Strategy

1. Use Chart 11E, appendix pg. 20 to find Q, Vtrans., K, and Ce.

2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.

3. Calculate Vactual = Q/A

4. VP = (Vactual/4005)2

5. he = K * VP

6. SPh = VP + he

Page 84: Industrial Ventilation vs. IAQ

Exercise 6-10d

Where appropriate, determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a bell-mouthed hood used for welding. X=10 in., Vc = 100 fpm, Vtrans = 3000 fpm.

BURTON 6-13

Page 85: Industrial Ventilation vs. IAQ

Exercise 6-10d Strategy

1. Use Chart 11A, appendix pg. 16 to find Q, K, and Ce.

2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.

3. Calculate Vactual = Q/A

4. VP = (Vactual/4005)2

5. he = K * VP

6. SPh = VP + he

Page 86: Industrial Ventilation vs. IAQ

Exercise 6-10e Where appropriate,

determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a canopy hood used for a hot-liquid open surfaced tank. P = 16 ft., X = 3 ft., Vcontrol = 125 fpm, Vtrans = 2000fpm.

BURTON 6-13

Page 87: Industrial Ventilation vs. IAQ

Exercise 6-10e Strategy

1. Use Chart 11B, appendix pg. 17 to find Q, K, and Ce.

2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.

3. Calculate Vactual = Q/A

4. VP = (Vactual/4005)2

5. he = K * VP

6. SPh = VP + he

Page 88: Industrial Ventilation vs. IAQ

Factors Influencing Hood Performance

• Competition• Mixing• Work practices

BURTON 6-17

Page 89: Industrial Ventilation vs. IAQ

Canopy Hoods

BURTON 6-19

• Use only for hot processes with rising air.

• Estimate initial and terminal velocities of rising air stream.

• The volume of air exhausted from the hood must exceed the volume of air arriving at the hood face.

• Warm rising air expands as it rises. Make the cross-sectional area of the hood face 125% larger than the plume of hot air.

• Avoid canopy hoods if an employee must work over the source.

Page 90: Industrial Ventilation vs. IAQ

Chapter 7Selection and Design of

Ductwork

BURTON 7-1

Page 91: Industrial Ventilation vs. IAQ

Exercise 7-2

BURTON 7-4

Standard air (d=1) moves through an 8 in. galvanized duct system at 4000 fpm. Estimate VP, find the loss factors K from the Charts, and then estimate static pressure loss for each component in each branch. (Note: treat the branch entry as two 45-degree entries and use the ACGIH value for K on Chart 14.)

Page 92: Industrial Ventilation vs. IAQ

Exercise 7-2a, Flanged Hood

BURTON 7-4

Page 93: Industrial Ventilation vs. IAQ

Exercise 7-2b, Plain Duct Hood

BURTON 7-4

Page 94: Industrial Ventilation vs. IAQ

Exercise 7-2c, Elbow, 3-piece

BURTON 7-4

Page 95: Industrial Ventilation vs. IAQ

Exercise 7-2d, Elbow, 5-piece

BURTON 7-4

Page 96: Industrial Ventilation vs. IAQ

Exercise7-2e, Elbow, 4-piece

BURTON 7-4

Page 97: Industrial Ventilation vs. IAQ

Exercise 7-2f, Branch Entry

BURTON 7-4

Page 98: Industrial Ventilation vs. IAQ

Exercise 7-2g, 50 ft. of Duct

BURTON 7-4

Page 99: Industrial Ventilation vs. IAQ

BURTON 7-5

RoughnessExample 7-1

Standard air is flowing in 40 feet of a 24 in. concrete pipe at the 4000 fpm. What is the correction factor, R? The loss factor K?

Page 100: Industrial Ventilation vs. IAQ

Duct Shapes

BURTON 7-6

Use round duct whenever possible, it resists collapsing, provides better aerosol transport conditions, and may be less expensive.

Page 101: Industrial Ventilation vs. IAQ

Pressure Diagrams

BURTON 7-11

Page 102: Industrial Ventilation vs. IAQ

Chapter 8 Fan Selection and Operation

AXIAL FANS• propeller fans

CENTRIFUGAL FANS• radial fans

• forward inclined

• backward inclined

BURTON 8-2

Page 103: Industrial Ventilation vs. IAQ

Fan Total Pressure

BURTON 8-3

The fan total pressure (FTP) represents all energy requirements for moving air through the ventilation system.

The fan total pressure is often referred to as the fan total static pressure drop.

FTP = TP outlet - TP inlet

FTP = SPout - VP out - SPin - VP in

FTP = SPout - SPin

Page 104: Industrial Ventilation vs. IAQ

Exercise 8-1

BURTON 8-3

Find the Fan Total Pressure given that the SPin = -5.0 in w.g, SPout = +0.40 in w.g.

VPin = VPout = 1.0 in. w.g.

FTP = SPout - SPin =

0.40 - (-5.0) = 5.4 in w.g.

Page 105: Industrial Ventilation vs. IAQ

Exercise 8-2Fan Static Pressure

BURTON 8-4

The fan static pressure out of the fan is defined as the fan total pressure minus the average velocity pressure out of the fan.

FSP = Fan TP - VPout

Page 106: Industrial Ventilation vs. IAQ

SOP and Fan Curves

BURTON 8-5

To develop a system curve, the fan should be turned at different rpms and the flow and the absolute values of the static pressures at the fan are plotted.

Page 107: Industrial Ventilation vs. IAQ

Developing Fan Curves

BURTON 8-6

Page 108: Industrial Ventilation vs. IAQ

SOP on Steep Part of Curve

BURTON 8-7

Page 109: Industrial Ventilation vs. IAQ

Example 8-1

BURTON 8-8

Choose an appropriate fan for a system operating point of Q = 10,000 scfm and FTP = 1.5 in. w.g.

Page 110: Industrial Ventilation vs. IAQ

Exercise 8-3

BURTON 8-8

Find a fan and appropriate rpm for a fan exhausting 15,000 cfm at a fan TP = 2.0 in. w.g.

Page 111: Industrial Ventilation vs. IAQ

Exercise8-4

BURTON 8-8

Find a suitable fan and the appropriate rpm for a ventilation system exhausting 480 cfm at a fan TP = 13.8 in. w.g.

Page 112: Industrial Ventilation vs. IAQ

Commercial Fan Curves

BURTON 8-9

Page 113: Industrial Ventilation vs. IAQ

Commercial Fan Curves

BURTON 8-10

Page 114: Industrial Ventilation vs. IAQ

Commercial Fan Curves

BURTON 8-11

Page 115: Industrial Ventilation vs. IAQ

System Effect Losses

BURTON 8-12

Page 116: Industrial Ventilation vs. IAQ

Six-and-Three Rule

BURTON 8-13

Page 117: Industrial Ventilation vs. IAQ

Air Horsepower

BURTON 8-14

Air horsepower refers to the minimum amount of power to move a volume of air against the fan total pressure. It represents the power to get the air through the duct system.

ahp = ( FTP * Q * d)/6356

Page 118: Industrial Ventilation vs. IAQ

Brake Horsepower

BURTON 8-15

Brake horsepower refers to the actual power required to operate the fan so that it fulfills the job of moving the specified cfm against the FTP. It takes into account fan inefficiencies, i.e. losses in the fan.

bhp = ahp/ME

Page 119: Industrial Ventilation vs. IAQ

Shaft Horsepower

BURTON 8-15

Shaft horsepower is bhp plus any power required for drive losses, bearing losses, and pulley losses between the fan and the shaft of the motor.

shp = bhp * Kdl

Page 120: Industrial Ventilation vs. IAQ

Rated Horsepower

• Rated horsepower is the nameplate horsepower on the motor.

BURTON 8-15

Page 121: Industrial Ventilation vs. IAQ

Example 8-4

BURTON 8-16

What is the required power for the system and what rated power motor would you use?

FTP = 5.0 in. w.g. ,

Q = 12000 scfm

ME = 0.60, Kdl = 1.10, d = 1,

f = 6356

Page 122: Industrial Ventilation vs. IAQ

Exercise 8-7

BURTON 8-17

Estimate the ahp, bhp, shp, and the rated power motor you would choose for the following system.

Fan TP = 10.0 in. w.g.,

Q = 5000 scfm

Kdl = 1.15, STP(d=1),

f = 6356, ME = 0.65

Page 123: Industrial Ventilation vs. IAQ

Fan Laws

BURTON 8-19

Page 124: Industrial Ventilation vs. IAQ

Local Exhaust Ventilation Design

BURTON 9-1

Page 125: Industrial Ventilation vs. IAQ

Plenum Design

BURTON 9-3

Page 126: Industrial Ventilation vs. IAQ

BALANCING

BURTON 9-4

Balancing during the design phase means adjusting losses in duct runs leading to a junction that the predicted loss in each run is essentially equal.

Page 127: Industrial Ventilation vs. IAQ

Example 9-2

BURTON 9-5

Design an local exhaust system based on the criteria listed in the example.

Page 128: Industrial Ventilation vs. IAQ

Name: Project: Example 9-2 8 in. duct 7 in. duct

Row Item Source Units (US)

PLANS 1. Duct ID Plans FROM -TO A-B A-B

2. Design Q Chart 11 cfm 1000 1000

3. Transport vel. Chart 9, 11 cfm 3000 3000

4. Slotted hood? Y-R5, N-R12 NO NO

5. Slot velocity Chart 11 fpm

6. Slot area R2/R5 sq. ft.

SLOTS/ 7. Slot VP Chart 7 in. w .g.

PLENUM 8. Slot entry loss factor -1.78

9. Acceleration factor -1

10. Plenum loss factor -2.78

11. Plenum SP R7*R10

12. Duct diameter Chart 5 inches 8 7

13. Duct area Chart 5 sq. ft. 0.0391 0.2673

DUCT 14. Duct velocity R2/R13 fpm 2865 3740

15. Duct VP Chart 7 inches 0.51 0.87

16. Duct length from plans feet 25 25

17. Friction R, duct Chart 10 or from mfg 2.4 2.4

18. Friction K Chart 5 0.03 0.035

19. Friction K, duct R16*R17*R18 1.8 2.1

20. Hood entry Chart 11 0.25 0.25

LOSS 21. Acceleration 1.0 at hoods 1 1

FACTOR 22. Elbow s Chart 13 0.27 0.27

K 23. Branch entry Chart 14 ACGIH 0 0

24. System effect Chart 16 0 0

25. Other K loss 0 0

26. Total K sum R19-R25 3.32 3.62

27. Duct SP R26*R15 inch 1.69 3.15

STATIC 28. SP at FROM location R33 inch 0 0

PRESSURE 29. Jxn. VP change at FROM Chart 14 inch 0 0

30. Other SP loss inch 0 0

31. Total SP at TO R11+(R27toR30) inch 1.69 3.15

32. Is this Governing SP y/n

JUNCTION 33. Governing SP at TO location inch

34. Actual Q = [R2*(R33/R31)^0.5

35. SPh [R11+(R15*(R20+R21))]inch 0.64 1.09HOOD 36. Total slot length plans feet

37. Slot w idth 12(R6/R36) inch

Page 129: Industrial Ventilation vs. IAQ

Example 9-3

BURTON 9-11

Design a local exhaust system based upon the criteria listed on this page.

Page 130: Industrial Ventilation vs. IAQ

Name: Group Exercise Project: Example 9-3

Row Item Source Units (US)

PLANS 1. Duct ID Plans FROM -TO A-B B-C C-D D-E

2. Design Q Chart 11 cfm 2400 1000 3421 3421

3. Transport vel. Chart 9, 11 cfm 3000 3000 3000 3000

4. Slotted hood? Y-R5, N-R12 YES NO NO NO

5. Slot velocity Chart 11 fpm 2000

6. Slot area R2/R5 sq. ft. 1.2

SLOTS/ 7. Slot VP Chart 7 in. w .g. 0.25

PLENUM 8. Slot entry loss factor 1.78

9. Acceleration factor 1

10. Plenum loss factor 2.78

11. Plenum SP R7*R10 0.7

12. Duct diameter Chart 5 inches 12 8 14 14

13. Duct area Chart 5 sq. ft. 0.7854 0.3491 1.069 1.069

DUCT 14. Duct velocity R2/R13 fpm 3056 2865 3200 3200

15. Duct VP Chart 7 inches 0.58 0.51 0.64 0.64

16. Duct length from plans feet 25 25 40 20

17. Friction R, duct Chart 10 1 2.4 1 1

18. Friction K Chart 5 0.018 0.03 0.015 0.015

19. Friction K, duct R16*R17*R18 0.45 1.8 0.6 0.3

20. Hood entry Chart 11 0.25 0.5 0 0

LOSS 21. Acceleration 1.0 at hoods 1 1 0 0

FACTOR 22. Elbow s Chart 13 0.39 0 1.95 0

K 23. Branch entry Chart 14 ACGIH 0 0.28 0 0

24. System effect Chart 16 0 0 0 0

25. Other K loss 0 0 0 0

26. Total K sum R19-R25 2.09 3.58 2.55 0.3

27. Duct SP R26*R15 inch 1.21 1.83 1.63 0.19

STATIC 28. SP at FROM location R33 inch 0 0 1.91

PRESSURE 29. Jxn. VP change at FROMChart 14 inch 0 0 0.1

30. Other SP loss inch 0 0 4

31. Total SP at TO R11+(R27toR30) inch 1.93 1.83 7.64

32. Is this Governing SP y/n YES NO

JUNCTION 33. Governing SP at TO location inch 1.91

34. Actual Q = [R2*(R33/R31)^0.5 1021

35. SPh [R11+ (R15*(R20+R21))]inch 1.43 0.77HOOD 36. Total slot length plans feet 10

37. Slot w idth 12(R6/R36) inch 1.44