Indoor Environmental Quality: Investigating the Problem Charles S. McCammon, Ph.D., CIH Tri-County Health Department

Transcript of Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job...

Page 1: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Indoor Environmental Quality: Investigating the Problem

Charles S. McCammon, Ph.D., CIH

Tri-County Health Department

Page 2: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 3: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Introduction

Politically Correct to say “Indoor Environmental Quality” – IEQRefers to any number of Building Associated Problems Including:– Comfort Complaints– Odor Complaints– Sick Building Syndrome– Building Related Illness

Page 4: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

How Big Is the Problem?

In 1990, EPA Estimate $65 Billion in Lost productivity: Value > $100 B NowEPA still ranks IAQ as #2 Environmental IssueWhy should you care about IAQ?– $$$$$$$$$$$$$$$$$$$$$$$$$– Civil lawsuits = $$$$$$$– Employee productivity.– Employee satisfaction.– Worker compensation claims = $$$$$– A Call from OSHA

Page 5: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Background

Why did we not hear about IAQ until 70-80s?

Arab Oil Embargo of 1973– ASHRAE Changed from 15 cfm to 5 cfm Outside Air per

person- term “Tight Building Syndrome”

Legionella Outbreak 1976– Realization that buildings can make you sick (even die!)

Awareness of Problem

Page 6: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 7: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 8: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Building Associated Illnesses

Complaint or Symptom Rates are Elevated

Investigation Confirms Relationship to Occupancy in Building

Occupants Feel Better Over Weekend, Start Getting Sick Early on Monday A.M.

Page 9: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Sick Building Syndrome - SBS

Symptoms Abate Upon Leaving and Worsen Upon Reentry of Building

Characterized by Absence of Routine Physical Signs and Clinical Abnormalities, i.e., Doctors can’t see what makes them sick

Symptoms NOT Associated with Specific Environmental or Other Casual Agents

Page 10: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

SBS Symptoms-WHO

Eye, Nose, Throat IrritationDry Mucous Membranes and SkinMental FatigueHeadachesLethargyNausea and DizzinessAirways Infection and Cough

Page 11: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Comfort and Odor Complaints

Most Common of Building Complaints– Too Hot– Too Cold– High/Low RH can trigger complaints

Odors– Most Common Trigger for Perception of

Poor Indoor Air Quality– Can result in nausea, headache, fatigue

Page 12: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Building Related Illness

Real Deal, like Legionella OutbreakHave Known CausesAccompanied by Physical Signs and Laboratory Findings, Docs can diagnoseDiseases Associated with Contamination Problems– Infectious Microorganisms– Allergenic compounds, e.g., molds– Chemicals

Page 13: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Possible Causes for Increased Complaints in IAQ

Physical Factors – >50% – HVAC system, design, maintenance, etc.

Chemical BiologicalPsychological

Page 14: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Common Chemical Sources in IAQ

Tobacco smoke- slowly dissipating as problem areaVolatile Organic Compounds (VOCs)– Formaldehyde-outgasses from many new

productsGases, like CO from combustions and Ozone from copiers/printersBiocides, pesticides, etc.

Page 15: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Physical Factors

Inadequate Ventilation is #1– Not enough outside air– Poor air distribution– Poor air filtration– Poor location of outside air intake– Modification of offices without HVAC mods– Poor location/type of air diffusers– No return air

Page 16: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

How are IAQ Investigations Conducted?

Page 17: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

IAQ Investigations

Building CharacterizationSymptom SurveyVentilation System EvaluationSource IdentificationSamplingRemediation

Page 18: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Building Characterization

Type and age of buildingConstruction materialsPrimary usesCleaning practices

Page 19: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Type and Age of Building

Previous ventilation systems.What remodeling has taken place?What were the prior uses?Is asbestos a concern?Is mold a concern?

Page 20: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Construction Materials

Wood Construction vrs MetalFire proofing materialCrawl spacesCarpeting and wall coverings

Page 21: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Primary Uses

Is a manufacturing area included?What is the occupant density?Computer usage.Has the primary usage changed?

Page 22: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Cleaning Practices

Who cleans the building?When is the building cleaned?Cleaning product storage.Cleaning product MSDS information?

Page 23: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Symptom Surveys

Questionnaires vs. InterviewsRisk: If problem not wide-spread, it will be after questionnaireThe survey must:

Cover a majority of the staff (80-90%).Be pre-tested.Eliminate bias.Not suggest answers.Not be a group effort.

Page 24: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Questionnaire Topics

Demographic QuestionsComfort QuestionsMedication QuestionsDiagnosed Illness QuestionsSymptom QuestionsAir Quality Control QuestionsJob Satisfaction Questions

Page 25: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Comfort Factors

Complaint Low School High SchoolCold 32% 73%Hot 21% 50%Stuffy 7% 52%Moldy 14% 10%Dusty 11% 23%Noisy 0% 19%Dry 11% 25%Crowded 0% 17%

Page 26: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Typical HVAC System Problems

Design ProblemsConstruction ProblemsOperator ProblemsRenovation ProblemsOccupant Problems

Page 27: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Ventilation System EvaluationVisual inspection of System.Carbon dioxide (tracer gas) measurements.Look for the following:

Water infiltrationMaintenance historyGeneral conditionUse of local exhaustPlacement of exhausts and intakes

Page 28: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 29: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 30: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 31: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 32: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 33: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 34: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 35: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 36: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 37: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 38: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 39: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

HVAC SystemsAir Filters

Low Efficiency: 10-20%– Used to keep lint from clogging coils

Medium: 30-60%– Used to remove bacteria, pollens, insects, soot,

dust & dirt (often in combination with Low Eff.)

High: 85-95%– Exceptionally clean – not usual for most buildings

Page 40: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 41: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 42: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 43: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

HVAC SystemsAir Filter Considerations

Always use maximum system can handle (pleated type low Pressure Drop)Keep log, replace regularly– Inspect often for tears

Never, Ever Wet FiltersMake filters easy to access– Not often case for fan coil, reheat units

Page 44: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 45: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 46: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 47: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Ventilation System Characterization

System TypeConstant VolumeVariable Air VolumeUnit Ventilators

ZonesSingle ZoneMulti-Zone

Reheat or No ReheatDucts - Lined or Unlined

Page 48: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 49: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 50: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 51: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 52: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 53: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Unit Ventilators or Fan Coil Units

Not actually an air handling system.Mount on outside wall.Provide some filtration, conditioning, and movement.May have independent or centralized heating & coolingInduction units may provide outside air, others typically do not

Page 54: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 55: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 56: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 57: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Constant Volume Systems

Provides a constant supply airflow rate to zones with similar thermal loads.Air temperature is controlled at the air handler or with reheat coils.Outside air is determined by:

Outside air temp.Damper settingsTemperature demand

Page 58: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Variable Air Volume SystemsProvides a constant temperature air to the duct system.Air from the duct system is supplied to the zone to manage thermal load by the use of VAV boxes – common in multiple zone systems, like schools.Under ventilation due to no minimum stop or max supple too low for loads in zoneOutside air is determined by:

Thermal demand of zone.Outside air temperature.VAV box and damper minimum settings.

Page 59: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Results of CO2 and ACH Sampling

CV VAV UV

Mean of CO2 715 ppm 666 ppm 573 ppm

CO2 Range (ppm) 390 - 957 318 – 1,763 295 – 1,450

% of Time > 1000 ppm 0% 11% 9%

Mean ACH 4.6 2.8 2.7

Range ACH 1.9 – 7.5 0.8 – 4.6 0.4 – 4.6

Page 60: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Complaints by System Type

Type of Complaint More thanExpected

Less thanExpected

Too cold VAV CVIndividuals w/ complaints VAVEye Symptoms CV VAVHeadache Symptoms UV VAVNasal Symptoms UV VAV, CVThroat Symptoms UVDustiness Complaints UV CV

Page 61: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

HVAC SystemsOther Problem Areas

Heating & Cooling Coils– Make sure condensation drains away– If hot water not hot enough, causes OA to be

reduced and cannot heat spaces wellHumidification Systems– Avoid use when possible– Keep % RH <60%– If needed, use only clean steam injection type

Evaporative Coolers- also avoid

Page 62: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

HVAC SystemsOther Problem Areas

System balancing a must– ASHRAE 111-1988, every 3-5 yrs

Use unlined ductwork whenever possibleCheck location, operation of diffusersCheck return air plenums for contaminationInsure sufficient makeup air for exhausted areas: toilets, cooking areas, parking garages

Page 63: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Source Identification

Look for the following:Manufacturing areasPrint shopsConstructionCleaning agentsCombustion productsOther: pesticide treatment,

– Chemical storage

Page 64: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 65: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 66: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Sampling

Initial Site AssessmentSecondary Sampling

Page 67: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Initial Site Assessment

HVAC system measurements:Carbon dioxide, air flow.

Ambient air measurementsCarbon monoxide, carbon dioxide, temperature, relative humidity.

Page 68: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 69: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 70: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Secondary SamplingShould only be conducted when:

Specific information is to be collectedKnowledgeable personnel are present

HVAC measurementsTracer gas, duct velocities

Ambient AirChemicals - VOC’s, aldehydes, MVOC’s, odors, particulates, etc.

Bioaerosol SamplingMedical monitoring

Page 71: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Why conduct tracer gas testing?

To determine air exchange rate for a building or area of a building.To determine fresh air distribution for a building or area of a building.To determine ventilation infiltration.To determine exhaust system effectiveness.To determine contaminant pathways

Page 72: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Tracer Gas Testing Methods

Tracer gas characteristics.Tracer gas introduction methods:

InjectionConstant FlowDuct injectionHood Testing

Concentration measurement methodsGCInfrared

Page 73: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Tracer Gas Testing Methods (Cont)

Tracer gas introduction:Air Change StudiesContamination StudiesHood Studies

Page 74: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Results

What do results indicate?Limitations!Comparisons with carbon dioxide methods for ventilation.

Page 75: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 76: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Particulate Sampling

MethodologyMass collectionParticle countersCondensation nuclei counters

Results - What do they mean????MassMass/particle sizeParticle numbersRatios

Page 77: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 78: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Particle Mass Conc., Cagewash, 2-29-2000

0.00E+00

1.00E-03

2.00E-03

3.00E-03

4.00E-03

5.00E-03

6.00E-03

7.00E-03

8.00E-03

9.00E-03

1.00E-02

9:17:3

29:2

7:32

9:37:3

29:4

7:32

9:57:3

210

:07:32

10:17

:3210

:27:32

10:37

:3210

:47:32

10:57

:3211

:07:32

11:17

:3211

:27:32

11:37

:3211

:47:32

Time

Parti

cle

Mas

s Co

nc. (

mg.

m3)

<0.5230.523-2.52.5-1010-20

Page 79: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Total Mass Conc, Powder-free Gloves, 8-30-2000

0.00E+00

1.00E-02

2.00E-02

3.00E-02

4.00E-02

5.00E-02

6.00E-02

7.00E-02

8.00E-02

9.00E-02

13:5

4:27

13:5

9:27

14:0

4:27

14:0

9:27

14:1

4:27

14:1

9:27

14:2

4:27

14:2

9:27

14:3

4:27

14:3

9:27

14:4

4:27

14:4

9:27

14:5

4:27

14:5

9:27

15:0

4:27

15:0

9:27

15:1

4:27

15:1

9:27

15:2

4:27

15:2

9:27

15:3

4:27

15:3

9:27

15:4

4:27

15:4

9:27

15:5

4:27

15:5

9:27

16:0

4:27

16:0

9:27

16:1

4:27

16:1

9:27

Time

Mas

s C

onc.

(mg/

m3)

Total Conc

Page 80: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Sampling complicationsInterpretation of results is difficult.Generally low probability of identifying a problem.High costGrab samples may give non-typical results.Source identification may not be possibleSource reduction will still need to be done.

Page 81: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Remediation

Increase outside air Decrease outside airControl sources

Local exhaust ventilationEliminationControl devices

Contain construction or remodelingIsolate manufacturing areas

Page 82: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 83: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building
Page 84: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Factors confounding IAQ investigations

IAQ Problems are the Sum of all stressors, other sources include:Ergonomic problemsLightingSmoking policiesComfort ComplaintsPsychosocial issuesOther job stressors

Page 85: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Job Stressors Leading to Job Strains

Interpersonal Factors– Social density too high/low– Abrasive personalities– Group pressure to conform

Physical Demands: noise, light, temp/RHIndividual factors– Behavior pattern, e.g., Type A– Hardy personality styles– Self esteem

Non-Work Factors: families, money, child rearing

Page 86: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Psychosocial Factor StudiesCornell University3-1\2 yr of 27 office buildings40% of bldg occupants reported at least 1 SBS symptomNo complaint correlation with extensive environmental measurementsHigh correlation of Symptoms with:– Job Stress– Job Satisfaction– Perception of Indoor Air Quality

Page 87: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

Psychosocial Factor Studies

Large Study by Bauer and RyanCorrelation of SBS Symptoms with:– Job Stress & Job Satisfaction– Belief that health is adversely effected by building– Perception of poor Indoor Air Quality– Off the job strains and conflicts

Solution to Problem: Form IAQ Committee with– Employees– Management– Building Maintenance Personnel

Page 88: Indoor Environmental Quality: Investigating the Problem...Correlation of SBS Symptoms with: – Job Stress & Job Satisfaction – Belief that health is adversely effected by building

How to Deal with Other Factors in IAQ

Many factors exist which are out of the hands of maintenance personnel alone-solve what you canProblem must be addressed as a multifactorial one, not just looking for the smoking gunNeed for lots of communications at all levels, from first-line HVAC Tech, through building occupants to Building ManagerGet employees involved with the IAQ problemsAs a last resort, find other work environments for few problem employees