Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... ·...

24
ABB Indoor Air Switch Disconnector, NAL Indoor Air Switch Disconnector, NALF Catalogue 1YMR602160-en

Transcript of Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... ·...

Page 1: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

���

Indoor Air Switch Disconnector, NALIndoor Air Switch Disconnector, NALF

Catalogue 1YMR602160-en

Page 2: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB2

ContentsNAL/NALF 12-17,5-24-36-40,5 1. General ....................................................................................... 3 2. Short-circuit making capacity .................................................... 3 3. Environmental withstand ability ................................................. 3 4. Functional description ............................................................... 3 5. Standard features ...................................................................... 4 6. Mechanisms ............................................................................... 4 7. Earthing switch ........................................................................... 5 8. Motor operation ..........................................................................5 9. Ordering codes ..........................................................................6 10.Options ....................................................................................... 7 11.Example of installed switches ................................................... 8 12.Technical Specifications ............................................................ 9 13.Ordering information ................................................ 11,12,13,14 14.Operating equipment and options ..................................... 15,16 15.Dimemsional drawing ................... 17, 18, 19, 20, 21, 22, 23, 24

Page 3: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 3

Fig. 1

Fig. 2

1. GENERALThe switch disconnector system NAL/NALF is based on a modularprinciple. The basic unit consists of a frame with insulators and currentcarrying parts. Two different types of operating mechanisms: snap actionmechanism type K or stored spring energy mechanism type A, can bemounted on the frame. Fuse bases type F with tripping mechanism canalso be fitted. A triple pole earthing switch type EB with a snap actionmechanism and making capacity is also available. These differentmodules can be combined in various ways in order to meet your specificrequirements.Accessories such as shunt trip, under-voltage release, auxiliary switches,motor operation and various systems for manual operation can easilybe added.ABB’s switch disconnector type NAL and fuse switch disconnector typeNALF have primarily been developed for use within the following areas:- as line and transformer switches within distribution networks- as motor switches- as capacitor switchesBy combining NAL, which disconnects load currents and small fault currentscircuit, with a current limiting fuse (F), which breaks large short circuitcurrents, the result is an ideal combination. This combination (NALF)provides protection towards all types of faults in the network.ABB has been producing switch disconnectors for more than 50 years.The NAL was introduced in 1978 and has been undergoing continuosdevelopment to satisfy the users’ demands.More than 500 000 switches have been produced and are sold through-out the world.The switch disconnectors meet IEC Publication 60129, 60265, 60694,62271, GOST 1516.3-96, GOST 17717-79, ANSI Standard No. C37.20.4and CSA Standard No. C22.2, No. 193 concerning switches for general useand for safe co-operation between switch disconnector and fuse.Fig. 1 Fig. 2NAL in network NAL in cell

2. SHORT-CIRCUIT MAKING CAPACITYWith carefully designed contact geometry and high contact velocitiesthe NAL switches are able to close safely on short circuits of up to1550 MVA at 36 kV.

3. ENVIRONMENTAL WITHSTAND ABILITYThe switch disconnectors comply with IEC requirements for equipmentfor indoor use. The mechanisms are corrosion protected by zink platingand a supplementary chromate treatment, and the frames are paintedwith corroision resistant powder coating. In order to ensure a safeoperation even after years in service under all climatic conditions, themechanisms are generally fitted with plastic bearings.NAL switch disconnector is manufactured according to our strict qualityand environment procedures.Our ISO 9001 and ISO 14001 certifications assures the quality andenvironmental excellence.NAL switch disconnector is 98,64% recyclable.

4. FUNCTIONAL DESCRIPTIONTo ensure correct operation for all relevant currents, the switchdisconnector system NAL/NALF is equipped with a dual arc extinguishingsystem. When interrupting the current, the arc will be exposed to:a) A current independent air blast which automatically starts at the

correct time during the interrupting process. This is achieved bydesigning the insulators on the opening side as cylinders withpistons. The pistons are connected to the mechanism in thesame way as the moving contacts. The air blast therefore startssimultaneously with the contact movement (autopneumatic air blast).

b) A current dependent gas blast which occurs when the walls ofthe arcing nozzles are exposed to the hot arc.During this process, large volumes of gas are released and thearc is effectively cooled. The concentration of the developedgas increases with increasing current. The so called Hart gas effectis therefore most important at high currents.

Page 4: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB4

A well balanced utilization of these two effects has resulted in an arcextinguishing system with a high reliability for all relevant currents.Because of the autopneumatic air blast it will only be necessary to utilizethe Hart gas effect for the high currents. This gives an arcing system whichcan withstand a large number of operations without excessive wear.Consequently the NAL switches comply with highest electrical perfomanceclasses of IEC 60265-1 (for selected nominal voltages only).

5. STANDARD FEATURES

NALThe standard feature consists of chassis, insulators and currentcarrying parts with the following pole distance:

12 kV – pole distance 150 mm, 170 mm and 210 mm17,5 kV – pole distance 170 mm and 210 mm24 kV – pole distance 170 mm*, 235 mm and 275 mm36/40,5 kV – pole distance 360 mm* - with insulating barriers

Rated currents are 400, 630 and 1250 A up to 24 kVand 630/800 A for 36/40,5 kV

NALFIs delivered with the same pole distances as the standard feature.Fuse base type F is delivered for installation on both the openingside and the pivot side, with or without automatic tripping.Fuse base with 6 insulators can also be delivered separately withsignal at fuse blown, or for installation on the pivot side of the switch.

6. MECHANISMSA-MECHANISM – with two springs.The opening spring is always charged before the switch can be closed bymeans of the closing spring. This means that a closed switch always has theopening spring charged, and the switch can be tripped immediately by hand,electrically or by a fuse-link striker system.K-MECHANISM – with one spring

Closing or opening the switch is performed by charging the spring pastthe dead centre.KS-MECHANISMis a standard K-mechanism equipped with a latching mechanism typeS, which results in the latch being stopped past the dead centre.Thereby, the mechanism is ready for opening/closing by an operatingcoil or pneumatically by a pump.

NB!:- The switching operation can not be completed by the operating handle.- The spring must be charged before each operation.

The KS combination is suitable for remote operation in case where thespring mechanism can be charged manually.KS-mechanism can not be mechanically interlocked.

A and K mechanismsCan be equipped with motor operation. (KS on request)

Fig. 5A-mechanismFig. 6K-mechanismFig. 7KS-mechanism

Fig. 3

Fig. 4

Fig. 5

Fig. 7

Fig. 6

Page 5: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 5

7. EARTHING SWITCH

EARTHING SWITCH TYPE E – with snap action spring mechanism

The earthing switch can be mounted on the pivot side of the switchand on the fuse base when the latter is on the pivot side of theswitch.

EARTHING SWITCH TYPE EB – can be delivered for separateinstallation.

FUSE BASES TYPE Fwith or without automatic tripping of the switch by the fuse-link strikersystem. The fuse base can be mounted on both sides (i.e. openingside or pivot side of the switch).

Fig. 8Type E

Fig. 9Type EB

8. MOTOR OPERATION

The motor operation is very flexible when it comes to installation. Itcan be installed at the switch axle’s right or left side, directly on theswitch or on the axle’s extension.Can be delivered for all normed voltages.

If motor operation is desired mounted on the front panel,UEMC40A2 can be used.Can be delivered for all normed voltages.

Fig. 11Motor operation mounted in cell front type UEMC 40 A2

Fig. 10Motor operation mounted on switch type UEMC 40 K3/NM

Fig. 8

Fig. 9

Fig. 11

Fig. 10

Page 6: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB6

Switch disconnector,with integrated fuse base 1)

Rated voltage 12 kVRated voltage 17,5 kVRated voltage 24 kVRated voltage 36 kVRated voltage 40,5 kVRated current 400 ARated current 630 ARated current 800 ARated current 1250 Awithout mechanismSnap action mechanismStored spring energy mechanismLatched snap action mechanism 4)

Pole distance 12 kVPole distance 12 kV, 17,5 kV and 24 kVPole distance 12 kV and 17,5 kVPole distance 24 kVPole distance 24 kVPole distance 36/40,5 kVRight hand side operationLeft hand side operation 5)

Quick -make earthing switch 6)

NALF

12172436

40,5 43)

682)

123)

KA

KS150170210235275360

RL

E

9. ORDERING CODES

Index explanations

1) additional information needed when placing the order:the length of fuse linkmounting side - pivot or openingwith or withour fuse tripping

2) for 36/40,5 kV only3) up to 24 kV only4) closing or opening of switch disconnector must be carried by a coil5) for left hand operation shaft extension must be used6) the earthing switch is normally delivered without mechanical

interlocking that must be spefified seperatelly. For 36/40,5 kVearthing switch is provided as self standing only type EB.

Ordering example A:Switch disconnector for 17,5kV / 1250A with latched snap actionmechanism, pole distance 170 mm. The switch disconnector is left-hand operated and equipped with quick-make earthing switch.

Ordering example B:Switch disconnector for 24kV / 630A with stored spring energymechanism type A, equipped with fuse-base on the pivot side, withfuse-tripping device, pole distance 235mm, right-hand operated.

1) Normally, the switch disconnector is delivered with fuse base forpivot side mounting. Fuse base for opening side mounting mustbe specified in the order.

2) Closing or opening of the switch disconnector must be carriedout by a coil by operating coil. Additional charge.

3) For left-hand operation, a shaft extension must be used.Additional charge.

4) The earthing switch is normally delivered without mechanicalinterlocking. Additional charge for interlocking.

Page 7: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 7

10. OPTIONS

AUXILIARY SWITCH can be mounted on all switch disconnectors, max.8NO and 8NC and on all earthing switches, max. 4NO + 4NC (fig. 21).

Fig. 21

Fig. 12

Fig. 16

AUXILIARY SWITCH for blown fuse (fig. 12).

SHAFT EXTENSION with joint link, 380/470 mm (fig. 13).+ connection kit for assembling

SHAFT EXTENSION for left-hand operation of switch (fig. 14).

LEVER for switchchrod operation (fig. 15).

TEST FUSE LINK - adjustable (fig. 16).

Fig. 19

Fig. 18

Fig. 13

Fig. 17

(a)

(b)

(c)

OPERATION

Manual operation of HE consists of (fig. 17):- lower part (a)- upper part (b)- shaft- connection rod (c)

Lower part for HE can be equipped with blocking coil for all normedvoltages (fig. 18).

MANUAL OPERATION TYPE HEPlease observe! The mechanism shaft does not pass through theswitch from the mechanism on the right-hand side to the left side,special extension shaft is needed for operation of the mechanismfrom the left-hand side.

SHUNT TRIP can be mounted on all A-mechanisms. Shunt trip coilis available for following voltages: 24,48, 110, 220 V DC and 110,220 V AC. The shunt trip coil shall always be connected in serieswith an auxiliary switch, disconnecting the shunt trip coil when theswitch is open.

MECHANICAL INTERLOCKING BETWEEN SWITCH ANDEARTHING SWITCHAt earth on fuse base, the interlocking design depends upon thelength of the fuse. Therefore, the fuse size must be stated.KS-mechansism can not be interlocked to earthing switch (fig. 20).

Fig. 15

Fig. 14

Fig. 20

Page 8: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB8

11. EXAMPLE OF MOUNTING OF SWITCH

Auxiliary switch

Shaft extension forleft-hand operation

Mechanical interlocking

Earthing switch type E

NALF

Mechanisms

Lever for switchrod operation

HE-operation– lower part (mounted in cell front)

Shunt trip

Auxiliarty switchat blown fuse

HE-operation– upper part

Motoroperation

Page 9: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 9

12. TECHNICAL SPECIFICATIONS

Switch disconnector type NALThe switch disconnector complies with IEC publications 129, 254 and 694 concerning general purpose switches, IEC publication 420regarding correct co-operation between switch disconnector and fuse.

Rated voltage Un kV 12 kV 17,5 kV 24 kV 36 kV 40,5 kVRated current In A 400 630 1250 400 630 1250 400 630 1250 630 800 630 800Max. rated current I A 400 630 1150 400 630 1150 400 630 1150 630 800 630 800Short circuit making capacity Ima kA peak 67 67 67 50 50 50 50 50 50 50 50 50 50Peak withstand current Idyn kA peak 82 82 82 82 82 82 62,5 62,5 82 66 66 66 66Short time current 1 sec. Ith kA eff 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5

2 sec. " " 25 25 25 25 25 25 25 25 25 25 25 25 253 sec. " " 20 20 20 16 16 16

Mainly active load breaking capacity 2)

(test duty 1 and 2, IEC 265) I A 400 630 1250 400 630 1250 400 630 1250 630 800 630 800Mainly capacitive breaking capacity(test duty 4, IEC 265) I A 150 150 150 45 45 45 80 80 80 50 50 50 50Mainly inductive breaking capacitycos ϕ = 0,15 A 16 16 16 16 16 16 16 16 16 165) 165) 165) 165)

Rated earth fault breaking capacity, IEC 265Earth fault breaking capacity, fig. 6 I A 150 150 150 70 70 70 75 75 75Capacitive breaking capacity, fig. 7 I A 90 90 90 40 40 40 31,5 31,5 31,5 50 50 50 50Max. breaking capacity in co-operation withfuses (IEC 420 1990-11) A 1600 1600 1600 1600 900 900 300 300 300 300Max. fuse size 4) In A 125 125 125 125 80 80 40 40 40 40Power frequency withstand voltage 50 Hz 1 min.- to earth and between poles kV 42 45 55 80 95- across isolating distance kV 48 60 70 88 120Impulse withstand voltage 1,2/50 us.- to earth and between poles kV 75 95 125 170 190- across isolating distance kV 85 110 145 195 220Pole distance P mm 150, 170 and 210 170 and 210 1706), 235 and 275 360Max. operating torque at:- closing K/A mech. Nm 115 - 120 Nm 80 - 100 Nm- opening K/A mech. Nm K-mech. 120 Nm / A-mech. 3 Nm K-mech 80 - 100 NmOperating angle on the shaft degrees 130 120Opening time ms 40 - 60 60Arc time ms 10 - 20 35

Earthing switch type E 1) for NAL/NALF and type EBRated voltage Un kV 12 17,5 24 36Peak withstand current3) Idyn. kA peak 62/82 40/82 38/82 66Short time current 1 sec. Ith kA eff 31,5 31,5 31,5

2 sec. " " 25 25 253 sec. " " 20 16

Short circuit making capacity 3) Ima kA peak 62/67 40/62,5 38/50 50Test voltage 50 Hz 1 min. kV 42 45 55 80Power frequency withstand voltage 1,2 / 50 us. kV 82 95 125 170Pole distance P mm 175 and 210 170 and 210 170, 235 and 275 3601) Mechanical interlocking can be fitted, but not for KS-mechanism.2) At In = 630 A, 100 x CO. At In = 1250 A, 20 x CO.3) When fed from switch disconnector/earthing switch side.4) Max. fuse size is ref. to time current characteristics for CEF.5) Power factor =0,16) With insulating barriers

TABLE I

Page 10: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB10

TABLE II according to CSA -C22.2

Rated Nominal Voltage kV 4,16 13,8 27,6 34,5Rated Maximum Voltage kV 4,76 15 29,8 38Rated Current A 600/1200 600/1200 600/1200 600/800Impulse Test Voltage kV 60 95 125 150Power Frequency Withstand Voltage kV 28 38 60 70Pole Spacing mm/inches 150/5,9 170/6,69 235/9,25 360/14,1

210/8,25 210/8,25 275/10,8235/9,25

Momentary Rating Current kA asym. 40 40 40 40Fault-Closing Rating Current kA asym. 40 40 40 30Short Time Current kA sym.-2s 25 25 25 25

TABLE III according to ANSI C 37.20.4

Rated Nominal Voltage kV 4,73 12-13,8 12-16,8 22,9-24,9 34,5Rated Maximum Voltage kV 8,25 15 17 27 38Rated Current A 200/600/1200 200/600/1200 200/600/1200 200/600/1200 600/800Impulse Test Voltage kV 75 95 110 125 150Power Frequency Withstand Voltage kV 26 36 50 60 80Pole Spacing mm/inches 210/8,25 170/6,69 235/9,25 275/10,8 360/14,1Momentary Rating Current kA asym. 40 40 40 40 40Fault-Closing Rating Current kA asym. 40 40 40 40 30Short Time Current kA sym.-2s 25 25 25 25 25

Other technical specification see Table I

Page 11: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 11

NAL 12-4K150R 12 400 150 1YMX054010M0001 30NAL 12-4K170R 12 400 170 1YMX065170M0001 30NAL 12-4K210R 12 400 210 1YMX054910M0001 30NAL 12-6K150R 12 630 150 1YMX054011M0001 30NAL 12-6K170R 12 630 170 1YMX065170M0002 30NAL 12-6K210R 12 630 210 1YMX054911M0001 30NAL 12-12K150R 12 1250 150 1YMX054012M0001 31NAL 12-12K170R 12 1250 170 1YMX065170M0003 31NAL 12-12K210R 12 1250 210 1YMX054912M0001 31NAL 17-4K170R 17,5 400 170 1YMX054013M0001 32NAL 17-4K210R 17,5 400 210 1YMX065210M0001 32NAL 17-6K170R 17,5 630 170 1YMX054014M0001 32NAL 17-6K210R 17,5 630 210 1YMX065210M0002 32NAL 17-12K170R 17,5 1250 170 1YMX054015M0001 33NAL 17-12K210R 17,5 1250 210 1YMX065210M0003 33NAL 24-4K170R 24 400 170 1YMX065171M0001 40NAL 24-4K235R 24 400 235 1YMX054016M0001 40NAL 24-4K275R 24 400 275 1YMX054410M0001 40NAL 24-6K170R 24 630 170 1YMX065171M0002 40NAL 24-6K235R 24 630 235 1YMX054017M0001 40NAL 24-6K275R 24 630 275 1YMX054411M0001 40NAL 24-12K170R 24 1250 170 1YMX065171M0003 41NAL 24-12K235R 24 1250 235 1YMX054018M0001 41NAL 24-12K275R 24 1250 275 1YMX054412M0001 41NAL 36-6K360R 36 630 360 1YMX054363M0001 67NAL 36-8K360R 36 800 360 1YMX054314M0001 67NAL 40-6K360R 40,5 630 360 1YMX065363M0001 68NAL 40-8K360R 40,5 800 360 1YMX065314M0001 68

NAL 12-4KS150R 12 400 150 1YMX054025M0001 32NAL 12-4KS170R 12 400 170 1YMX066170M0001 32NAL 12-4KS210R 12 400 210 1YMX054915M0001 32NAL 12-6KS150R 12 630 150 1YMX054026M0001 32NAL 12-6KS170R 12 630 170 1YMX066170M0002 32NAL 12-6KS210R 12 630 210 1YMX054916M0001 32NAL 12-12KS150R 12 1250 150 1YMX054027M0001 33NAL 12-12KS170R 12 1250 170 1YMX066170M0003 33NAL 12-12KS210R 12 1250 210 1YMX054917M0001 33NAL 17-4KS170R 17,5 400 170 1YMX054028M0001 34NAL 17-4KS210R 17,5 400 210 1YMX066210M0001 34NAL 17-6KS170R 17,5 630 170 1YMX054029M0001 34NAL 17-6KS210R 17,5 630 210 1YMX066210M0002 34NAL 17-12KS170R 17,5 1250 170 1YMX054030M0001 35NAL 17-12KS210R 17,5 1250 210 1YMX066210M0003 35NAL 24-4KS170R 24 400 170 1YMX066171M0001 40NAL 24-4KS235 24 400 235 1YMX054031M0001 40NAL 24-4KS275R 24 400 275 1YMX054415M0001 40NAL 24-6KS170R 24 630 170 1YMX066171M0002 40NAL 24-6KS235R 24 630 235 1YMX054032M0001 40NAL 24-6KS275R 24 630 275 1YMX054416M0001 40NAL 24-12KS170R 24 1250 170 1YMX066171M0003 41NAL 24-12KS235R 24 1250 235 1YMX054033M0001 41NAL 24-12KS275R 24 1250 275 1YMX054417M0001 41NAL 36-6KS360R 36 630 360 1YMX054316M0001 67NAL 36-8KS360R 36 800 360 1YMX054317M0001 67NAL 40-6KS360R 40,5 630 360 1YMX066316M0001 68NAL 40-8KS360R 40,5 800 360 1YMX066317M0001 68

NAL 12-4A150R 12 400 150 1YMX054040M0001 32NAL 12-4A170R 12 400 170 1YMX067170M0001 32NAL 12-4A210R 12 400 210 1YMX054920M0001 32NAL 12-6A150R 12 630 150 1YMX054041M0001 32NAL 12-6A170R 12 630 170 1YMX067170M0002 32NAL 12-6A210R 12 630 210 1YMX054921M0001 32NAL 12-12A150R 12 1250 150 1YMX054042M0001 33NAL 12-12A170R 12 1250 170 1YMX067170M0003 33NAL 12-12A210R 12 1250 210 1YMX054922M0001 33NAL 17-4A170R 17,5 400 170 1YMX054043M0001 34NAL 17-4A210R 17,5 400 210 1YMX067210M0001 34NAL 17-6A170R 17,5 630 170 1YMX054044M0001 34NAL 17-6A210R 17,5 630 210 1YMX067210M0002 34NAL 17-12A170R 17,5 1250 170 1YMX054045M0001 35NAL 17-12A210R 17,5 1250 210 1YMX067210M0003 35NAL 24-4A170R 24 400 170 1YMX067171M0001 42NAL 24-4A235R 24 400 235 1YMX054046M0001 42NAL 24-4A275R 24 400 275 1YMX054420M0001 42NAL 24-6A170R 24 630 170 1YMX067171M0002 42NAL 24-6A235R 24 630 235 1YMX054047M0001 42NAL 24-6A275R 24 630 275 1YMX054421M0001 42NAL 24-12A170R 24 1250 170 1YMX067171M0003 43NAL 24-12A235R 24 1250 235 1YMX054048M0001 43NAL 24-12A275R 24 1250 275 1YMX054422M0001 43NAL 36-6A360R 36 630 360 1YMX054319M0001 68NAL 36-8A360 36 800 360 1YMX054320M0001 68NAL 40-6A360R 40,5 630 360 1YMX067319M0001 69NAL 40-8A360R 40,5 800 360 1YMX067320M0001 69

13. ORDERING INFORMATION

Type Rated Rated Pole dist- Ident. Weight,voltage current ance mm no. kg

NAL12-4 12 400 150 1YMX054150M0001 25NAL 12-4 12 400 170 1YMX064170M0001 25NAL 12-4 12 400 210 1YMX054950M0001 25NAL 12-6 12 630 150 1YMX054141M0001 25NAL 12-6 12 630 170 1YMX064170M0002 25NAL 12-6 12 630 210 1YMX054971M0001 25NAl 12-12 12 1250 150 1YMX054152M0001 26NAL 12-12 12 1250 170 1YMX064170M0003 26NAL 12-12 12 1250 210 1YMX054952M0001 26NAL 17-4 17,5 400 170 1YMX054153M0001 27NAL 17-4 17,5 400 210 1YMX064210M0001 27NAL 17-6 17,5 630 170 1YMX054144M0001 27NAL 17-6 17,5 630 210 1YMX064210M0002 27NAL 17-12 17,5 1250 170 1YMX054155M0001 28NAL 17-12 17,5 1250 210 1YMX064210M0003 28NAL 24-4 24 400 170 1YMX064171M0001 35NAL 24-4 24 400 235 1YMX054156M0001 35NAL 24-4 24 400 275 1YMX054456M0001 35NAL 24-6 24 630 170 1YMX064171M0002 35NAL 24-6 24 630 235 1YMX054147M0001 35NAL 24-6 24 630 275 1YMX054467M0001 35NAL 24-12 24 1250 170 1YMX064171M0003 36NAL 24-12 24 1250 235 1YMX054158M0001 36NAL 24-12 24 1250 275 1YMX054458M0001 36NAL 36-6 36 630 360 1YMX054310M0001 62NAL 36-8 36 800 360 1YMX054311M0001 62NAL 40-6 40,5 630 360 1YMX064310M0001 63NAL 40-8 40,5 800 360 1YMX064311M0001 63

Fig. 23

Fig. 22

Main switch with snap action mechanism(K-mechanism)

Main switch with stored spring energy mechanism(A-mechanism)

Main switch with latched snap action mechanism(KS-mechanism)

Main switch without mechanism

Fig. 24

Page 12: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB12

Fig. 25

Main switch with fuse base and snap action mechanism,without fuse tripping

Type Rated Rated Pole dist- Ident. Weightvoltage current ance mm no. kg

NALF 12-4K150R 12 400 150 1YMX054070M0001 39NALF 12-4K170R 12 400 170 1YMX068170M0001 39NALF 12-4K210R 12 400 210 1YMX054925M0001 39NALF 12-6K150R 12 630 150 1YMX054071M0001 39NALF 12-6K170R 12 630 170 1YMX068170M0002 39NALF 12-6K210R 12 630 210 1YMX054926M0001 39NALF 17-4K170R 17,5 400 170 1YMX054072M0001 42NALF 17-4K210R 17,5 400 210 1YMX068210M0001 42NALF 17-6K170R 17,5 630 170 1YMX054073M0001 42NALF 17-6K210R 17,5 630 210 1YMX068210M0002 42NALF 24-4K170R 24 400 170 1YMX068171M0001 51NALF 24-4K235R 24 400 235 1YMX054074M0001 51NALF 24-4K275R 24 400 275 1YMX054425M0001 51NALF 24-4K170R 24 630 170 1YMX068171M0002 51NALF 24-6K235R 24 630 235 1YMX054075M0001 51NALF 24-6K275R 24 630 275 1YMX054426M0001 51NALF 36-6K360R 36 630 360 1YMX054322M0001 68NALF 36-8K360R 36 800 360 1YMX054323M0001 68NALF 40-6K360R 40,5 630 360 1YMX068322M0001 69NALF 40-8K360R 40,5 800 360 1YMX068323M0001 69Main switch with fuse base and latched snap actionmechanism, with fuse trippingNALF 12-4KS150R 12 400 150 1YMX054080M0001 41NALF 12-4KS170R 12 400 170 1YMX069170M0001 41NALF 12-4KS210R 12 400 210 1YMX054930M0001 41NALF 12-6KS150R 12 630 150 1YMX054081M0001 41NALF 12-6KS170R 12 630 170 1YMX069170M0001 41NALF 12-6KS210R 12 630 210 1YMX054931M0001 41NALF 17-4KS170R 17,5 400 170 1YMX054082M0001 44NALF 17-4KS210R 17,5 400 210 1YMX069210M0001 44NALF 17-6KS170R 17,5 630 170 1YMX054083M0001 44NALF 17-6KS210R 17,5 630 210 1YMX069210M0002 44NALF 24-4KS170R 24 400 170 1YMX069171M0001 53NALF 24-4KS235R 24 400 235 1YMX054084M0001 53NALF 24-4KS275R 24 400 275 1YMX054430M0001 53NALF 24-6KS170R 24 630 170 1YMX069171M0002 53NALF 24-6KS235R 24 630 235 1YMX054085M0001 53NALF 24-6KS275R 24 630 275 1YMX054431M0001 53NALF 36-6KS360R 36 630 360 1YMX054325M0001 70NALF 36-8KS360R 36 800 360 1YMX054326M0001 70NALF 40-6KS360R 40,5 630 360 1YMX069325M0001 71NALF 40-8KS360R 40,5 800 360 1YMX069326M0001 71

NALF 12-4A150R 12 400 150 1YMX054090M0001 41NALF 12-4A170R 12 400 170 1YMX070170M0001 41NALF 12-4A210R 12 400 210 1YMX054935M0001 41NALF 12-6A150R 12 630 150 1YMX054091M0001 41NALF 12-6A170R 12 630 170 1YMX070170M0002 41NALF 12-6A210R 12 630 210 1YMX054936M0001 41NALF 17-4A170R 17,5 400 170 1YMX054092M0001 44NALF 17-4A210R 17,5 400 210 1YMX070210M0001 44NALF 17-6A170R 17,5 630 170 1YMX054093M0001 44NALF 17-6A210R 17,5 630 210 1YMX070210M0002 44NALF 24-4A170R 24 400 170 1YMX070171M0001 53NALF 24-4A235R 24 400 235 1YMX054094M0001 53NALF 24-4A275R 24 400 275 1YMX054435M0001 53NALF 24-6A170 24 630 170 1YMX070171M0002 53NALF 24-6A235R 24 630 235 1YMX054095M0001 53NALF 24-6A275R 24 630 275 1YMX054436M0001 53NALF 36-6A360R 36 630 360 1YMX054328M0001 70NALF 36-8A360R 36 800 360 1YMX054329M0001 70NALF 40-6A360R 40,5 630 360 1YMX070328M0001 71NALF 40-8A360R 40,5 800 360 1YMX070329M0001 71CSA Main switch without mechanismNAL 4-6 150 4,16 600 150 1YMX084141M0001 25NAL 4-12 150 4,16 1200 150 1YMX084152M0001 26NAL 4-6 210 4,16 600 210 1YMX084971M0001 25NAL 4-12 210 4,16 1200 210 1YMX089952M0001 26NAL 13-6 170 13,8 600 170 1YMX084144M0001 27NAL 13-12 170 13,8 1200 170 1YMX084155M0001 28NAL 13-6 210 13,8 600 210 1YMX084210M0002 27NAL 13-12 210 13,8 1200 210 1YMX084210M0003 28NAL 13-6 235 13,8 600 235 1YMX084147M0001 35NAL 13-12 235 13,8 1200 235 1YMX084158M0001 36NAL 27-6 235 27,6 600 235 1YMX184147M0001 35NAL 27-12 235 27,6 1200 235 1YMX184158M0001 36NAL 27-6 275 27,6 600 275 1YMX084467M0001 35NAL 27-12 275 27,6 1200 275 1YMX084458M0001 36NAL 34-6 360 34,5 600 360 1YMX084310M0001 62NAL 34-8 360 34,5 800 360 1YMX084311M0001 62

Main switch with fuse base and stored spring energymechanism, with fuse tripping

Fig. 26

Page 13: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 13

CSA Main switch with snap action mechanism(K-mechanism)

NAL 4-6 150KR 4,16 600 150 1YMX084011M0001 30NAL 4-12 150KR 4,16 1200 150 1YMX084012M0001 31NAL 4-6 210KR 4,16 600 210 1YMX084911M0001 30NAL 4-12 210KR 4,16 1200 210 1YMX084912M0001 31NAL 13-6 170K17R 13,8 600 170 1YMX084014M0001 32NAL 13-12 170K17R 13,8 1200 170 1YMX084015M0001 33NAL 13-6 170K24R 13,8 600 170 1YMX084014M0002 32NAL 13-12 170K24R 13,8 1200 170 1YMX084015M0002 33NAL 13-6 210K17R 13,8 600 210 1YMX085210M0002 32NAL 13-12 210K17R 13,8 1200 210 1YMX085210M0003 33NAL 13-6 210K24R 13,8 600 210 1YMX085210M0004 32NAL 13-12 210K24R 13,8 1200 210 1YMX085210M0005 33NAL 13-6 235K17R 13,8 600 235 1YMX084017M0001 40NAL 13-12 235K17R 13,8 1200 235 1YMX084018M0001 41NAL 13-6 235K24R 13,8 600 235 1YMX084017M0002 40NAL 13-12 235K24R 13,8 1200 235 1YMX084018M0002 41NAL 27-6 235K24R 27,6 600 235 1YMX184017M0001 40NAL 27-12 235K24R 27,6 1200 235 1YMX184018M0001 41NAL 27-6 275K24R 27,6 600 275 1YMX084411M0001 40NAL 27-12 275K24R 27,6 1200 275 1YMX084412M0001 41NAL 34-6 360KR 34,5 600 360 1YMX084363M0001 67NAL 34-8 360KR 34,5 800 360 1YMX084314M0001 67CSA Main switch with latched snap action mechanism(KS-mechanism)NAL 4-6 150KSR 4,16 600 150 1YMX084026M0001 32NAL 4-12 150KSR 4,16 1200 150 1YMX084027M0001 33NAL 4-6 210KSR 4,16 600 210 1YMX084916M0001 32NAL 4-12 210KSR 4,16 1200 210 1YMX084917M0001 33NAL 13-6 170KSR 13,8 600 170 1YMX084029M0001 34NAL 13-12 170KSR 13,8 1200 170 1YMX084030M0001 35NAL 13-6 210KSR 13,8 600 210 1YMX086210M0002 34NAL 13-12 210KSR 13,8 1200 210 1YMX086210M0003 35NAL 13-6 235KSR 13,8 600 235 1YMX084032M0001 40NAL 13-12 235KSR 13,8 1200 235 1YMX084033M0001 41NAL 27-6 235KSR 27,6 600 235 1YMX184032M0001 40NAL 27-12 235KSR 27,6 1200 235 1YMX184033M0001 41NAL 27-6 275KSR 27,6 600 275 1YMX084416M0001 40NAL 27-12 275KSR 27,6 1200 275 1YMX084417M0001 41NAL 34-6 360KSR 34,5 600 360 1YMX054316M0001 67NAL 34-8 360KSR 34,5 800 360 1YMX054317M0001 67CSA Main switch with stored spring energy mechanism(A-mechanism)NAL 4-6 150AR 4,16 600 150 1YMX084041M0001 32NAL 4-12 150AR 4,16 1200 150 1YMX084042M0001 33NAL 4-6 210AR 4,16 600 210 1YMX084921M0001 32NAL 4-12 210AR 4,16 1200 210 1YMX084922M0001 33NAL 13-6 170A17R 13,8 600 170 1YMX084404M0001 34NAL 13-12 170A17R 13,8 1200 170 1YMX084045M0001 35NAL 13-6 170A24R 13,8 600 170 1YMX084404M0002 34NAL 13-12 170A24R 13,8 1200 170 1YMX084045M0002 35NAL 13-6 210A17R 13,8 600 210 1YMX087210M0002 34NAL 13-12 210A17R 13,8 1200 210 1YMX087210M0003 35NAL 13-6 210A24R 13,8 600 210 1YMX087210M0004 34NAL 13-12 210A24R 13,8 1200 210 1YMX087210M0005 35NAL 13-6 235A17R 13,8 600 235 1YMX084047M0001 42NAL 13-12 235A17R 13,8 1200 235 1YMX084048M0001 43NAL 13-6 235A24R 13,8 600 235 1YMX084047M0002 42NAL 13-12 235A24R 13,8 1200 235 1YMX084048M0002 43NAL 27-6 235A24R 27,6 600 235 1YMX184047M0001 42NAL 27-12 235A24R 27,6 1200 235 1YMX184048M0001 43NAL 27-6 275A24R 27,6 600 275 1YMX084421M0001 42NAL 27-12 275A24R 27,6 1200 275 1YMX084422M0001 43NAL 34-6 360AR 34,5 600 360 1YMX084319M0001 68NAL 34-8 360AR 34,5 800 360 1YMX084320M0001 68

Type Rated Rated Pole dist- Ident. Weightvoltage current ance mm no. kg

CSA Main switch with fuse base and snap actionmechanismwithout fuse trippingNALF 4-6 150KR 4,16 600 150 1YMX084071M0001 39NALF 4-6 210KR 4,16 600 210 1YMX084926M0001 39NALF 13-6 170K17R 13,8 600 170 1YMX084073M0002 42NALF 13-6 170K24R 13,8 600 170 1YMX084073M0001 42NALF 13-6 210K17R 13,8 600 210 1YMX088210M0002 42NALF 13-6 210K24R 13,8 600 210 1YMX088210M0003 42NALF 13-6 235K17R 13,8 600 235 1YMX084075M0001 51NALF 13-6 235K24R 13,8 600 235 1YMX084075M0002 51NALF 27-6 235K24R 27,6 600 235 1YMX184075M0001 51NALF 27-6 275K24R 27,6 600 275 1YMX084426M0001 51NALF 34-6 360KR 34,5 600 360 1YMX084322M0001 68NALF 34-8 360KR 34,5 800 360 1YMX084323M0001 68CSA Main switch with fuse base and latched snap actionmechanism, with fuse trippingNALF 4-6 150KSR 4,16 600 150 1YMX084081M0001 41NALF 4-6 210KSR 4,16 600 210 1YMX084931M0001 41NALF 13-6 170KSR 13,8 600 170 1YMX084083M0001 44NALF 13-6 210KSR 13,8 600 210 1YMX089210M0002 44NALF 13-6 235KSR 13,8 600 235 1YMX084085M0001 53NALF 27-6 235KSR 27,6 600 235 1YMX184085M0001 53NALF 27-6 275KSR 27,6 600 275 1YMX084431M0001 53NALF 34-6 360KSR 34,5 600 360 1YMX084325M0001 70NALF 34-8 360KSR 34,5 800 360 1YMX084326M0001 70CSA Main switch with fuse base and stored spring energymechanism, with fuse trippingNALF 4-6 150AR 4,16 600 150 1YMX084091M0001 41NALF 4-6 210AR 4,16 600 210 1YMX084936M0001 41NALF 13-6 170A17R 13,8 600 170 1YMX084093M0001 44NALF 13-6 170A24R 13,8 600 170 1YMX084093M0002 44NALF 13-6 210A17R 13,8 600 210 1YMX080210M0002 44NALF 13-6 210A24R 13,8 600 210 1YMX080210M0003 44NALF 13-6 235A17R 13,8 600 235 1YMX084095M0001 53NALF 13-6 235A24R 13,8 600 235 1YMX084095M0002 53NALF 27-6 235A24R 27,6 600 235 1YMX184095M0001 53NALF 27-6 275A24R 27,6 600 275 1YMX084436M0001 53NALF 34-6 360AR 34,5 600 360 1YMX084328M0001 70NALF 34-8 360AR 34,5 800 360 1YMX084329M0001 70

Fuse base type F for A/KS mechanism with fuse trippingMounted on the pivot sideF 12 12 400/630 150 1YMX054195M0001 7F 12 12 400/630 170 1YMX064195M0001 7F 12 12 400/630 210 1YMX054976M0001 7F 17 17 400/630 170 1YMX054196M0001 8F 17 17 400/630 210 1YMX064196M0001 8F 24 24 400/630 170 1YMX064197M0001 15F 24 24 400/630 235 1YMX054197M0001 13F 24 24 400/630 275 1YMX054476M0001 13F 36 36 630/800 360 1YMX054335M0001 17F 40 40,5 630/800 360 1YMX064335M0001 17Mounted on the opening sideF 12 12 400/630 150 1YMX054200M0001 7F 12 12 400/630 170 1YMX064200M0001 7F 12 12 400/630 210 1YMX054978M0001 7F 17 17 400/630 170 1YMX054201M0001 8F 17 17 400/630 210 1YMX064201M0001 8F 24 24 400/630 170 1YMX064202M0001 13F 24 24 400/630 235 1YMX054202M0001 13F 24 24 400/630 275 1YMX054478M0001 13

Type Rated Rated Pole dist- Ident. Weightvoltage current ance mm no. kg

Page 14: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB14

For switch disconnector type NALE 12 12 400/630 150 1YMX054235M0001 7E 12 12 400/630 170 1YMX064235M0001 7E 12 12 400/630 210 1YMX054983M0001 7E 12 12 1250 150 1YMX054214M0001 7E 12 12 1250 170 1YMX064235M0002 7E 12 12 1250 210 1YMX054989M0001 7E 17 17,5 400/630 170 1YMX054236M0001 8E 17 17,5 400/630 210 1YMX064236M0001 8E 17 17,5 1250 170 1YMX054218M0001 8E 17 17,5 1250 210 1YMX064236M0002 8E 24 24 400/630 170 1YMX064237M0001 9E 24 24 400/630 235 1YMX054237M0001 9E 24 24 400/630 275 1YMX054483M0001 9E 24 24 1250 170 1YMX064237M0002 9E 24 24 1250 235 1YMX054219M0001 9E 24 24 1250 275 1YMX054489M0001 9For fuse base NALFE 12 12 400/630 150 1YMX054225M0001 7E 12 12 400/630 170 1YMX064225M0001 7E 12 12 400/630 210 1YMX054988M0001 7E 17 17,5 400/630 170 1YMX054226M0001 8E 17 17,5 400/630 210 1YMX064226M0001 8E 24 24 400/630 170 1YMX064227M0001 9E 24 24 400/630 235 1YMX054227M0001 9E 24 24 400/630 275 1YMX054488M0001 9

EB 12 12 1250 150 1YMX054270M0001 17,5EB 12 12 1250 170 1YMX064270M0001 17,5EB 12 12 1250 210 1YMX054271M0001 17,5EB 17 17,5 1250 170 1YMX054272M0001 19EB 17 17,5 1250 210 1YMX064272M0001 19EB 24 24 1250 235 1YMX054273M0001 24EB 24 24 1250 170 1YMX064273M0001 24EB 24 24 1250 275 1YMX054274M0001 24EB 36 36 800 360 1YMX054288M0001 30EB 36 Pivot s. NAL 36 630/800 360 1YMX344033M0001 30EB 36 Open s. NAL 36 630/800 360 1YMX344034M0001 30EB 36 Pivot s. NALF 36 630/800 360 1YMX344035M0001 30EB 36 Open s. NALF 36 630/800 360 1YMX344036M0001 30

Type Rated Rated Pole dist- Ident. Weight,voltage kV current A ance mm no. kg

Mounted on the pivot sideF 12 12 400/630 150 1YMX054181M0001 7F 12 12 400/630 170 1YMX064181M0001 7F 12 12 400/630 210 1YMX054960M0001 7F 17 17,5 400/630 170 1YMX054182M0001 8F 17 17,5 400/630 210 1YMX064182M0001 8F 24 24 400/630 170 1YMX064183M0001 13F 24 24 400/630 235 1YMX054183M0001 13F 24 24 400/630 275 1YMX054460M0001 13F 36 36 630/800 360 1YMX054337M0001 17F 40 40,5 630/800 360 1YMX064337M0001 17Mounted on the opening sideF 12 12 400/630 150 1YMX054190M0001 7F 12 12 400/630 170 1YMX064190M0001 7F 12 12 400/630 210 1YMX054961M0001 7F 17 17,5 400/630 170 1YMX054191M0001 8F 17 17,5 400/630 210 1YMX064191M0001 8F 24 24 400/630 170 1YMX064193M0001 13F 24 24 400/630 235 1YMX054193M0001 13F 24 24 400/630 275 1YMX054461M0001 13F 36 36 630/800 360 1YMX054337M0001 17F 40 40,5 630/800 360 1YMX064337M0001 17

Type Rated Rated Pole dist- Ident. Weight,voltage kV current A ance mm no. kg

12 400/630/1250 150 1YMX054205M000112 400/630/1250 170 1YMX064205M000112 400/630/1250 210 1YMX054974M0001

17,5 400/630/1250 170 1YMX054206M000117,5 400/630/1250 210 1YMX064206M000124 400/630/1250 170 1YMX064207M000124 400/630/1250 235 1YMX054207M000124 400/630/1250 275 1YMX054474M0001

12 400/630/1250 150 1YMX054185M000112 400/630/1250 170 1YMX064185M000112 400/630/1250 210 1YMX054972M0001

17,5 400/630/1250 170 1YMX054418M000117,5 400/630/1250 210 1YMX064418M000124 400/630/1250 170 1YMX064187M000124 400/630/1250 235 1YMX054187M000124 400/630/1250 275 1YMX054472M0001

Fig. 27

Fig. 28

Fuse base with 6 insulators for A/KS-mechanism incl.fuse tripping

Earthing switch type E for NAL without mechanicalinterlocking

Earthing switch type EB for separate installation

Fuse base with 6 insulators for A/KS-mechanism excl.fuse tripping

Fuse base type F for K/A/KS mechanism withoutfuse tripping

Fuse base with 6 insulations with double fuses12 400/630/1250 150 1YMX343555M000112 400/630/1250 210 1YMX343555M0004

17,5 400/630/1250 170 1YMX343555M000224 400/630/1250 235 1YMX343555M000324 400/630/1250 245 1YMX343555M0005

Page 15: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 15

Description Type Ident. Wt,no. kg

Hand operating mechanism type HE with accessoriesFront bearing for HE, with cardanic joint 1YMX053233M0001 1.6Front bearing for HE, without cardanic joint 1YMX053233M0002 0.8Front bearing for HE, for motor operating 1YMX042249M0004 1,6Bevel gear for HE 1YMX053362M0001 1.4Operating handle for HE 1YMX053235M0001 0.6Operating handle for HE, armoured 1YMX053235M0004 1,8Front bearing for HE, with blocking coil, 220 V AC 1YMX053393M0001 2.1Front bearing for HE, with blocking coil, 110 V AC 1YMX053394M0001 2.1Front bearing for HE, with blocking coil, 220 V DC 1YMX053395M0001 2.1Front bearing for HE, with blocking coil, 110 V DC 1YMX053396M0001 2.1Front bearing for HE, with blocking coil, 48 V DC 1YMX053397M0001 2.1Front bearing for HE, with blocking coil, 24 V DC 1YMX053398M0001 2.1Shaft extension for left-hand side operation:– for pole distance 150 mm 1YMX054357M0001 1.9– for pole distance 210 mm 1YMX054353M0001 2.3– for pole distance 170 mm (12 kV) 1YMX054358M0002 2.1– for pole distance 170 mm (17,5 and 24 kV) 1YMX054358M0001 2.1– for pole distance 235 mm 1YMX054359M0001 2.6– for pole distance 275 mm 1YMX054355M0001 3.1– for pole distance 360 mm 1YMX343226M0004 4.0Connection kit for shaft extension assembing 1YMX000054M0001 0,1Connection rod 490 mm 1YMX053346M0008 0,8Connection rod 550 mm 1YMX053346M0009 0,9Connection rod 570 mm 1YMX053346M0010 1,0Connection rod 1300 mm 1YMX053346M0002 1,9Connection rod 2000 mm 1YMX053347M0001 2,9Connection rod 1300 mm, insulated 1YMX000012M0001 2,1Connection rod 2000 mm, insulated 1YMX000012M0002 3,1Connection rod 1300 mm, armoured and insulated 1YMX000012M0003 2,9Connection rod 2000 mm, armoured and insulated 1YMX000012M0004 4,2Connection rod 668 mm, insulated CZ 1YMX000012M0005 1,2Connection rod 738 mm, insulated CZ 1YMX000012M0006 1,3Connection rod 1300 mm, armoured and insulated CZ 1YMX000012M0007 2,9Connection rod 2000 mm, armoured and insulated CZ 1YMX000012M0008 4,2Connection rod 1300 mm, armoured 1YMX000004M0003 2,7Connection rod 2000 mm, armoured 1YMX000004M0004 4,0Connection rod 1300 mm, armoured CZ 1YMX000004M0007 2,7Connection rod 2000 mm, armoured CZ 1YMX000004M0008 4,0Crank arm 1YMX053225M0001Operating rod 1YMX053001M0001 0.7Shaft extension 470 mm 1YMX053348M0001 1.7Shaft extension 380 mm 1YMX053349M0001 1.4Joint link for shaft extension 1YMX053350M0001 0.2Support bearing for NAL/NALF 12 1YMX053351M0001 1.8Support bearing for NAL/NALF 17/24 1YMX053352M0001 1.9Support bearing for NAL 12 with E 12 1YMX053353M0001 2.2Support bearing for NAL 17/24 with E 17/24 1YMX053354M0001 2.8Support bearing for F 12 with E 12 1YMX053355M0001 1.3Support bearing for F 17/24 with E 17/24 1YMX053356M0001 1.4Test fuseAdjustable length 3, 6/36 kV with striker pin 1YMX300062M0001Mechanical interlocking for earthing switch *)– on NAL 12 1YMX054275M0001 2,5– on NAL 17/24 1YMX054276M0001 3,1– on NALF 12 Fuse length dim. e = 292 mm 1YMX054277M0001 5,7– on NALF 12 Fuse length dim. e = 192 mm 1YMX054278M0001 5,0– on NALF 12 Fuse length dim. e = 442 mm 1YMX054279M0001 6,4– on NALF 17 Fuse length dim. e = 292 mm 1YMX054280M0001 6,3– on NALF 17 Fuse length dim. e = 442 mm 1YMX054281M0001 7,0– on NALF 24 Fuse length dim. e = 442 mm 1YMX054282M0001 6,5– on NALF 24 Fuse length dim. e = 537 mm 1YMX054283M0001 7,3– on NAL 36/40 RB on pivot side 1YMX343986M0002 5,4– on NAL 36/40 RB on opening side 1YMX343986M0001 3,3– on NALF 36/40 RB on pivot side 1YMX343986M0003 9,4– on Nale 36/40 RB on opening side 1YMX343986M0004 7,6

*) Normally, interlocking is mounted on the left hand side of the switch andtherefore a shaft for left hand operation is needed.

Fig. 29 A-mechanismFig. 30 K-mechanismFig. 31 KS-mechanismFig. 32 Front bearing for HE

Fig. 29

Fig. 30

Fig. 31

Fig. 32

Fig. 33

Fig. 35

Fig. 34

Fig. Bevel gear for HEFig. 34 Mechanical interlockingFig. 35 Auxiliary switch

Description Type Ident. Wt,no. kg

MechanismsK-mechanism K 12 1YMX054165M0001 5K-mechanism K 17 1YMX038658M0001 5K-mechanism K 24 1YMX054167M0001 5K-mechanism K 36 1YMX054340M0001 5K-mechanism K 40 1YMX054340M0001 5A-mechanism A 12 1YMX054173M0001 7A-mechanism A 17 1YMX054174M0001 7A-mechanism A 24 1YMX054175M0001 7A-mechanism A 36 1YMX051341M0001 7A-mechanism A 40 1YMX051341M0001 7KS-mechanism*) KS 12/17 1YMX054168M0001 6KS-mechanism*) KS 24 1YMX054171M0001 6KS-mechanism KS 36 1YMX054342M0001 6KS-mechanism KS 40 1YMX054342M0001 6Plastic cover for A-mechanism 1YMX241351M0001 0,2

14. OPERATING EQUIPMENT AND OPTIONS

Page 16: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB16

Description Ident. Weight,no. kg

Auxiliary switch for switch and earthing switchAuxiliary switch 2no + 2nc for NAL/NALF 12-24 1YMX054713M0001 0.9Auxiliary switch 4no + 4nc for NAL/NALF 12-24 1YMX054714M0001 1.0Auxiliary switch 8no + 8nc for NAL/NALF 12-24 1YMX054715M0001 1.1Auxiliary switch 2no + 2nc for E/EB 12-24 1YMX054716M0001 0.9Auxiliary switch 2no + 2nc for E/EB 36 1YMX054716M0002 0.9Auxiliary switch 4no + 4nc for E/EB 12-24 1YMX054717M0001 1.0Auxiliary switch 4no + 4nc for E/EB 36 1YMX054717M0002 1.0Auxiliary switch 2no + 2nc for NAL/NALF 36 1YMX240807M0005 0.9Auxiliary switch 4no + 4nc for NAL/NALF 36 1YMX240807M0006 1.0Auxiliary switch 8no + 8nc for NAL/NALF 36 1YMX054715M0001 1.1Fixing materials for NAL/NALF 36 1YMX240807M0004 0.1Auxiliary switch at fuse blown 1YMX053390M0001 0.1

Shunt trip for A-mechanism incl. mounting materialsCoil 220 V AC without auxiliary switch 1YMX054740M0001 0.6Coil 110 V AC without auxiliary switch 1YMX054741M0001 0.6Coil 220 V DC without auxiliary switch 1YMX054742M0001 0.6Coil 110 V DC without auxiliary switch 1YMX054743M0001 0.6Coil 48 V DC without auxiliary switch 1YMX054744M0001 0.6Coil 24 V DC without auxiliary switch 1YMX054745M0001 0.6

NOTE: In connection with shunt trip, auxiliary switch with indent no.1YMX054713/54715 must be used.

Spare coil for shunt trip for A-mechanism and coil for operating coilfor KS-mechanism.Coil 220 V AC 1YMX054250M0001 0.4Coil 110 V AC 1YMX054251M0001 0.4Coil 220 V DC 1YMX054252M0001 0.4Coil 110 V DC 1YMX054253M0001 0.4Coil 48 V DC 1YMX054254M0001 0.4Coil 24 V DC 1YMX054255M0001 0.4Common separator for KS-mechanism 1YMX054257M0001 0.1

Fig. 36

Fig. 36 Shunt trip

Page 17: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 17

Type A A1 A2 A3 B H H1 H2 K K1 M N N1 P R S U V

NAL 12-A/K/KS, P=150 166 320 362 394 90 422 428 510 315 58 412 122 164 150 375 350 75 33NAL 12-A/K/KS, P=170 166 320 362 394 90 422 428 510 315 58 452 122 164 170 375 390 75 33NAL 12-A/K/KS, P=210 166 320 362 394 90 422 428 510 315 58 532 122 164 210 375 470 75 33

NAL 17,5 A/K/KS, P=170 225 375 418 511 98 534 577 600 441 87 452 122 164 170 500 395 90 18

NAL 17,5-A/K/KS, P=210 225 375 418 511 98 534 577 600 441 87 532 122 164 210 500 470 90 18

NAL 24-A/K/KS, P=170 225 375 418 511 98 534 577 600 441 87 452 186 202 170 500 395 90 18

NAL 24 A/K/KS, P=235 225 375 418 511 98 534 577 600 441 87 582 186 202 235 500 525 90 18

NAL 24 A/K/KS, P=275 225 375 418 511 98 534 577 600 441 87 662 186 202 275 500 605 90 18* 1250 A: A + 2 mm

Switch disconnectortype NAL 12, 17,5 and 24 kVwith mechansim

Fuses H1 H4 K2 K4 R1 R2 kV Length3,6/7,2 192 848 710 722 598 275 50

292948 810 822 698 375 150

12292442 1098 960 972 848 525 300

Fuse switch disconnectortype NALF 12 kV with mechanism

15. DIMENSIONAL DRAWING

Type M SNALF 12, P=150 412 350NALF 12, P=170 452 390NALF 12, P=210 532 470

36

36

Page 18: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB18

Fuses H1 H4 K2 K4 R1 R2 kV Length 442 1194 1045 986 978 425 275

537 1284 1140 1090 1073 525 370

Fuse switch disconnectortype NALF 24 kV withmechanism

Type M SNALF 24, P=170 452 395NALF 24, P=235 582 525NALF 24, P=275 662 605

Fuse switch disconnectortype NALF 17,5 kV with mechanism

Type M SNALF 17, P=170 452 395NALF 17, P=210 532 470

Fuses H1 H4 K2 K4 R1 R2 kV Length

17,5 292 1060 895 925 828 375 125442 1210 1045 1075 978 525 275

24

Page 19: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 19

Fuses H5 kV Length

3,6/7,2 192 462292 562

12 292 562442 704

17,5 292 563442 706

24 442 706537 801

Type A5 A7 P

NALF 12 – P = 150 173 430 150NALF 12 – P = 170 173 430 170NALF 17,5 – P = 170 243 500 170NALF 24 – P = 170 243 500 170NALF 17,5 – P = 210 243 500 210NALF 12 – P = 210 173 430 210NALF 24 – P = 235 243 500 235NALF 24 – P = 275 243 500 275

Fuse switch disconnectortype NALF 12, 17,5 and 24 kVFuse base with 6 insulators

Earthing switch with makingcapacitiy type E 12mounted on fuse base F 12

Earthing switch with makingcapacity type E 12mounted on NAL 12

Type M1 M2 SE12, P=150 681 428 350E12, P=170 721 468 390E12, P=210 801 548 470

Page 20: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB20

Earthing switch with makingcapacity type E 17,5 mounted onfuse base F 17,5.

Earthing switch with makingcapacity type E 17,5 mounted onNAL 17,5 kV

Type H2 H3 K3 M1 M2 N2 N3 P S T WE 12 P = 150 208 393 100 681 428 112 139 150 350 375 60E 12 P = 170 208 393 100 721 468 112 139 170 390 375 60E 17,5 P = 170 208 393 100 721 468 112 139 170 395 375 60E 24 P = 170 208 432 100 721 468 112 139 170 395 375 60E 17,5 P = 210 208 432 100 801 548 112 139 210 395 375 60E 24 P = 235 351 575 100 933 598 161 174 235 525 500 120E 24 P = 275 351 575 100 1013 678 161 174 275 605 500 120

Earthing switch with making capacitytype E 12, E 17,5 and E 24 mounted onfuse base with 6 insulators

Earthing switch with makingcapacity type E 24 mounted onfuse base F 24

Earthing switch with makingcapacity type E 24 mounted onNAL 24 kV

E 17,5 M1 M2 SP 170 721 468 395P 210 801 548 475

E 24 M1 M2 S N2 N3P=170 721 468 395 114 139P=235 933 598 525 161 174P=275 1013 678 605 163 174

Page 21: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 21

Type A H K R U

EB 12 245 231 115 200 46EB 17,5-24 310 245 90 175 21

Separately mounted earthing switch with making capacity type EB

Manual operation type HE

Recess in front

Operating angle 180°

for A/K mech

for aplication with k mechanism only

1YMX053302M00021YMX343036M0001

1YMX400840M0001

1YMX053362M0002

1YMX053233M0001

Connection rod

Transmission

46 46

100

90°

1YMX000129M0005

Page 22: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB22

NAL 36

NAL 40,5

Fuse H1 H2 H3 K2 R1

kV Length e

192 192 848 772 1063 722 275

292 292 948 872 1163 822 375

292 292 948 872 1163 822 375

442 1098 1098 1022 1313 972 525

7,2

12

Page 23: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB 23

EB 36

NAL 36+EB 36

NALF 36 + EB

Page 24: Indoor Air Switch Disconnector, NAL Indoor Air Switch ... Chave Seccionadora NAL(F) 12-40... · Indoor Air Switch Disconnector, ... 12 kV – pole distance 150 mm, ... For 36/40,5

Triple-pole switch disconnectortype NALFuse switch disconnectortype NALF

ABB24

NALF 36 + EB

ABB Sp. z o.o.Power Products divisionul. Leszno 5906-300 Przasnysz, PolandPhone: (+48 22) 51 52 838, 51 52 831

(+48 29) 75 33 233, 75 33 240Fax: +48 22 51 52 659, +48 29 75 33 327e-mail: [email protected]