Indian Electricity Rules

5
Indian Electricity Rules / Central Electricity Authority 1. Right of Way Clearance (As per GETCO Standard) 2. Minimum clearances between Electrical Lines crossing each other 3. Permissible Min ground Clearance of Electrical Line 4. Clearance for Telephone line Crossings Power Line 5. Vertical Clearance between Electrical Line and railway tracks 6. Clearance from Buildings to low, medium & high voltage lines 7. Clearance above ground at the lowest conductor 8. Vertical Clearance at Middle of Span 9. Safety Clearance from Live Part in Outdoor Substation 10. Lying of Telecommunication Cables with Power Cables (>33 kV) 11. Safe approach limits for people Code: Indian Electricity Rules / Central Electricity Authority Right of Way Clearance (As per GETCO Standard) KV Min ROW 66 KV 18 Meter 132 KV 27 Meter 220 KV 35 Meter 400KV 52 Meter (Single Circuit) 400 KV 48 Meter (Double Circuit) Go to Content Minimum clearances between Electrical Lines crossing each other Voltage 66 KV 132 KV 220 KV 400 KV 66 KV 2.4 Meter 3 Meter 4.5 Meter 5.4 Meter 132 KV 3 Meter 3 Meter 4.5 Meter 5.4 Meter 220 KV 4.5 Meter 4.5 Meter 4.5 Meter 5.4 Meter 400 KV 4.5 Meter 5.4 Meter 5.4 Meter 5.4 Meter

description

electricity

Transcript of Indian Electricity Rules

Page 1: Indian Electricity Rules

 Indian Electricity Rules / Central Electricity Authority1. Right of Way Clearance (As per GETCO Standard)

2. Minimum clearances between Electrical Lines crossing each other

3. Permissible Min ground Clearance of Electrical Line

4. Clearance for Telephone line Crossings Power Line

5. Vertical Clearance between Electrical Line and railway tracks

6. Clearance from Buildings to low, medium & high voltage lines

7. Clearance above ground at the lowest conductor

8. Vertical Clearance at Middle of Span

9. Safety Clearance from Live Part in Outdoor Substation

10. Lying of Telecommunication Cables with Power Cables (>33 kV)

11. Safe approach limits for people

Code: Indian Electricity Rules / Central Electricity Authority

Right of Way Clearance (As per GETCO Standard)

KV Min ROW

66 KV 18 Meter

132 KV 27 Meter

220 KV 35 Meter

400KV 52 Meter (Single Circuit)

400 KV 48 Meter (Double Circuit)

Go to Content   ↑

Minimum clearances between Electrical Lines crossing each other

Voltage 66 KV 132 KV 220 KV 400 KV

66 KV 2.4 Meter 3 Meter 4.5 Meter 5.4 Meter

132 KV 3 Meter 3 Meter 4.5 Meter 5.4 Meter

220 KV 4.5 Meter 4.5 Meter 4.5 Meter 5.4 Meter

400 KV 4.5 Meter 5.4 Meter 5.4 Meter 5.4 Meter

Go to Content   ↑

Permissible Min ground Clearance of Electrical Line

Page 2: Indian Electricity Rules

KV Ground Clearance Over National Highway

66 KV 6.1 Meter 8.0 Meter

132 KV 6.1 Meter 8.6 Meter

220 KV 7.0 Meter 9.8 Meter

400KV 8.8 Meter 10.8 Meter

Go to Content   ↑

Clearance for Telephone line Crossings Power Line

KV Clearance (Min)

66 KV 2.4 Meter

132 KV 2.7 Meter

220 KV 3.0 Meter

Go to Content   ↑

Vertical Clearance between Electrical Line and railway tracks

KV Clearance (Min)

66 KV 14 Meter

132 KV 14.6 Meter

220 KV 15.4 Meter

400 KV 17.9 Meter

Go to Content   ↑

Clearance from Buildings to low, medium and high voltage lines

Voltage Description Distance

Low & Medium

Voltage

Flat roof, open balcony, verandah roof ,When

the line passes above the building a vertical

2.5 Meter

Page 3: Indian Electricity Rules

clearance from the highest point

Low & Medium

Voltage

Line passes adjacent to the building a

horizontal clearance from the nearest point

1.2 Meter

Low & Medium

Voltage

Line passes above the building a vertical

clearance

2.5 Meter

Low & Medium

Voltage

Line passes adjacent the building a Horizontal

clearance

1.2 Meter

11 KV to 33 KV Line passes above or adjacent   to any

building or part of a building

3.7  Meter

Above 33 KV Line passes above or adjacent   to any

building or part of a building

3.7+(0.3 for every

additional 33 KV )

Up to 11 KV The horizontal clearance between the nearer

conductor and any part of such building

1.2 Meter

11 KV to 33 KV The horizontal clearance between the nearer

conductor and any part of such building

2.0 Meter

Above 33 KV The horizontal clearance between the nearer

conductor and any part ofsuch building

2.0 + (0.3 for every

additional 33 KV )

Go to Content   ↑

Clearance above ground at the lowest conductor

Voltage Description Distance

Low & Medium Voltage Across a street 5.8 Meter

High Voltage Across a street 6.1 Meter

Low & Medium Voltage Along a street 5.5 Meter

High Voltage Along a street 5.8 Meter

Low & Medium Voltage Elsewhere than along or across any

street

4.0 Meter

High Voltage Elsewhere than along or across any

street

5.2 Meter

33 KV & EHV Clearance above ground(Add 0.3 Meter

for every 33 KV Volts in 5.2 Meter)

Min 6.1 Meter

Go to Content   ↑

Page 4: Indian Electricity Rules

Vertical Clearance at Middle of Span

Span Vertical Clearance (At Middle of Span)

200 Meter 4.0 Meter

300 Meter 5.5 Meter

400 Meter 7.0 Meter

500 Meter 8.5 Meter

Go to Content   ↑

Safety Clearance from Live Part in Outdoor Substation

KV Safety Working Clearance

12 KV 2.6 Meter

36 KV 2.8 Meter

72.5 KV 3.1 Meter

145 KV 3.7 Meter

220 KV 4.3 Meter

400KV 6.4 Meter

800 KV 10.3 Meter

Go to Content   ↑

Lying of Telecommunication Cables with Power Cables (>33 kV)

Cable Min. Distance

Power cable of voltage exceeding 33 kV shall be laid Min 1.2 Meter depth

Underground telecommunication cable shall be with underground power

cable of voltage exceeding 33 kV.

Min 0.6 Meter

Separate from Power

Cable

Go to Content   ↑

Page 5: Indian Electricity Rules

Safe approach limits for people

Voltage 214V to

415 KV

11KV 33KV 66KV 132KV 275KV

Person using manually operated tool 1.3

Meter

2.0

Meter

3.0

Meter

4.0

Meter

5.0

Meter

6.0

Meter

Person using power operated tool 3.0

Meter

3.0

Meter

3.0

Meter

4.0

Meter

5.0

Meter

6.0

Meter