In-Duct High Pressure Nozzle Humidification System - HP ... · 24 VAC Safety Loop Pump module...
Transcript of In-Duct High Pressure Nozzle Humidification System - HP ... · 24 VAC Safety Loop Pump module...
In-Duct High Pressure Nozzle HumidificationSystem - HP HVAC Series
Submittal Drawings
Walter Meier (Climate USA) Inc.826 Proctor Ave., Odgensburg, NY 13669 Tel: 315.425.1255 E-mail: [email protected]
Walter Meier (Climate Canada) Ltd.2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 613.822.0335 Fax: 613.822.7964
2560711-B l 04 OCT 2011
Date:
Job Name:
Contractor:
Contractor or Order No.:
Engineer:
Agent:
Agent P.O. No.:
Date Ordered:
Date Required:
1-866-NORTEC-1
HP HVACTypical InstallationJuly 21, 2008
- 2 -
Drain2” (5.1 cm)taller thanstatic pressure
Water Inlet3/4” NPT
Drain 1/4” NPT
1/2” NPTHigh-Pressure
Outlet
Humidistator BMS
Power Inlet
Air ProvingSwitch
High LimitHumidistat
Bottom of ductTo be slopedtowards drain
Stainlesssteel ductliner
Mist Eliminatoror Cooling Coil
Valve BlockAssembly
Drains
Nozzle ManifoldsAirflow
Valve Controller
Drain Pan
0-10V Signal
24 VAC Safety Loop
Pump module mounted remotely.Ensure high pressure line lengthis kept as short as possible.
Max Inlet Pressure:60 psig (Stainless steel pumps)90 psig (Brass pumps)
Use ½” stainless steel high pressurepiping. 3 feet of high pressureflexible hose is recommended atthe pump outlet and valve blockinlet to minimize vibrations.
- 3 -
Drain2” (5.1 cm)taller thanstatic pressure
Humidistator BMS
Air ProvingSwitch
High LimitHumidistat
Bottom of ductTo be slopedtowards drain
Stainlesssteel ductliner
Mist Eliminatoror Cooling Coil
Valve BlockAssembly
Drains
Nozzle ManifoldsAirflow
Valve Controller
Drain Pan
0-10V Signal
24 VAC Safety Loop
Pump module mounted remotely.Ensure high pressure line lengthis kept as short as possible.
Max Inlet Pressure:60 psig (Stainless steel pumps)90 psig (Brass pumps)
Use ½” stainless steel high pressurepiping. 3 feet of high pressureflexible hose is recommended atthe pump outlet and valve blockinlet to minimize vibrations.
Water Inlet3/4” NPT
Drain1/4” NPT
1/2” NPTHigh-PressureOutlet
PowerInlet
HP HVACTypical InstallationJuly 21, 2008
Pump Modules
- 4 -
Oil lubricated, triplex ceramic plunger pump no Variable Frequency DriveModel Pump Frame Volts Phase Hz Amps KW Max. Circ. ProtectionG500PM 120-1 Medium 120 1 60 13.6 0.75 20G500PM 230-1 Medium 230 1 60 6.8 0.75 15G500PM 230-3 Medium 230 3 60 4.2 0.75 15G500PM 460-3 Medium 460 3 60 1.8 0.75 15G500PM 575-3 Medium 575 3 60 3.35 2.24 15G850PM 120-1 Medium 120 1 60 24 1.49 35G850PM 230-1 Medium 230 1 60 12 1.49 20G850PM 230-3 Medium 230 3 60 6.8 1.49 15G850PM 460-3 Medium 460 3 60 3.4 1.49 15G850PM 575-3 Medium 575 3 60 3.35 2.24 15G1100PM 120-1 Medium 120 1 60 24 1.49 35G1100PM 230-1 Medium 230 1 60 12 1.49 20G1100PM 460-3 Medium 460 3 60 3.4 1.49 15G1100PM 575-3 Medium 575 3 60 3.35 2.24 15G1550PM 230-1 Medium 230 1 60 16.8 2.24 25G1550PM 230-3 Medium 230 3 60 8.8 2.24 15G1550PM 460-3 Medium 460 3 60 4.4 2.24 15G1550PM 575-3 Medium 575 3 60 3.35 2.24 15G2300PM 230-3 Medium 230 3 60 13.4 3.73 20G2300PM 460-3 Medium 460 3 60 6.7 3.73 15G2300PM 575-3 Medium 575 3 60 5.2 3.73 15G3500PM 230-3 Large 230 3 60 20 5.6 35G3500PM 460-3 Large 460 3 60 10 5.6 15G5450PM 230-3 Large 230 3 60 26 7.46 40G5450PM 460-3 Large 460 3 60 13 7.46 20G5450PM 575-3 Large 575 3 60 10.4 7.46 15Oil lubricated, triplex ceramic plunger pump with Variable Frequency DriveGVFD950PM 230-3 Large 230 3 60 8.4 2.24 15GVFD950PM 460-3 Large 460 3 60 4.2 2.24 15GVFD950PM 575-3 Large 575 3 60 3.35 2.24 15GVFD1650PM 230-3 Large 230 3 60 8.4 2.24 15GVFD1650PM 460-3 Large 460 3 60 4.2 2.24 15GVFD1650PM 575-3 Large 575 3 60 3.35 2.24 15GVFD2100PM 230-3 Large 230 3 60 14 3.73 20GVFD2100PM 460-3 Large 460 3 60 7 3.73 15GVFD2100PM 575-3 Large 575 3 60 5.6 3.73 15GVFD3500PM 230-3 Large 230 3 60 21 5.6 35GVFD3500PM 460-3 Large 460 3 60 10.5 5.6 15GVFD3500PM 575-3 Large 575 3 60 8.4 5.6 15GVFD6500PM 230-3 Large 230 3 60 27 7.46 40GVFD6500PM 460-3 Large 460 3 60 13.5 7.46 20GVFD6500PM 575-3 Large 575 3 60 10.8 7.46 15Water lubricated, stainless steel pump with no Variable Frequency DriveD500PM 120-1 Medium 120 1 60 13.6 0.75 20D500PM 230-1 Medium 230 1 60 6.8 0.75 15D500PM 230-3 Medium 230 3 60 8.8 2.24 15D500PM 460-3 Medium 460 3 60 4.4 2.24 15D500PM 380-3 Medium 380 3 50 5.6 2.24 15D500PM 575-3 Medium 575 3 60 3.35 2.24 15D1100PM 120-1 Medium 120 1 60 24 1.49 35D1100PM 230-1 Medium 230 1 60 12 1.49 20D1100PM 230-3 Medium 230 3 60 8.8 2.24 15D1100PM 460-3 Medium 460 3 60 4.4 2.24 15D1100PM 380-3 Medium 380 3 50 5.6 2.24 15D1100PM 575-3 Medium 575 3 60 3.35 2.24 15D1800PM 230-1 Medium 230 1 60 16.8 2.24 25D1800PM 230-3 Medium 230 3 60 8.8 2.24 15D1800PM 460-3 Medium 460 3 60 4.4 2.24 15D1800PM 380-3 Medium 380 3 50 5.6 2.24 15D1800PM 575-3 Medium 575 3 60 3.35 2.24 15D2900PM 230-3 Large 230 3 60 13.4 3.73 20D2900PM 460-3 Large 460 3 60 6.7 3.73 15D2900PM 380-3 Large 380 3 50 8.2 3.73 15D2900PM 575-3 Large 575 3 60 5.2 3.73 15D3650PM 230-3 Large 230 3 60 20 5.6 35D3650PM 460-3 Large 460 3 60 10 5.6 15D3650PM 380-3 Large 380 3 50 12.1 5.6 20D3650PM 575-3 Large 575 3 60 8 5.6 15Water lubricated, stainless steel pump with Variable Frequency DriveDVFD500PM 230-3 Large 230 3 60 8.4 2.24 15DVFD500PM 460-3* Medium 460 3 60 1.8 1.1 15DVFD500PM 380-3* Medium 380 3 50 2.2 1.1 15DVFD500PM 575-3 Large 575 3 60 3.35 2.24 15DVFD1100PM 230-3 Large 230 3 60 8.4 2.24 15DVFD1100PM 460-3* Medium 460 3 60 2.6 1.5 15DVFD1100PM 380-3* Medium 380 3 50 3.3 1.5 15DVFD1100PM 575-3 Large 575 3 60 3.35 2.24 15DVFD1800PM 230-3 Large 230 3 60 14 3.73 20DVFD1800PM 460-3* Medium 460 3 60 3.7 2.2 15DVFD1800PM 380-3* Medium 380 3 50 4.7 2.2 15DVFD1800PM 575-3 Large 575 3 60 5.6 3.73 15DVFD2900PM 230-3 Large 230 3 60 21 5.6 35DVFD2900PM 460-3* Large 460 3 60 6.4 4 15DVFD2900PM 380-3* Large 380 3 50 7.9 4 15DVFD2900PM 575-3 Large 575 3 60 8.4 5.6 15DVFD3650PM 230-3 Large 230 3 60 27 7.46 40DVFD3650PM 460-3* Large 460 3 60 8.8 5.5 15DVFD3650PM 380-3* Large 380 3 50 11.1 5.5 15DVFD3650PM 575-3 Large 575 3 60 10.8 7.46 15*Requires DVDF Programming Kit. (One kit is interchangeable for multiple pumps)
HP HVAC - Large Pump ModuleDimensional DrawingAugust 8, 2008
- 5 -
Detail View
This pump can either be a stainlesssteel pump (as shown) or a triplexceramic plunger pump.
Motor shown here is equippedwith an optional variablefrequency drive.
OptionalCover on
Large Pumps
HP Outlet1/2” NPT (m)
Drain1/4” NPT (m)
Water Inlet3/4” NPT (f)
25.40”(64.5 cm)
52.30”(132.8 cm)
43.20”
(109.7 cm)
HP HVAC - Medium Pump ModuleDimension DrawingAugust 8, 2008
- 6 -
This pump can either be a stainlesssteel pump (as shown) or a triplexceramic plunger pump.
Motor shown here is equippedwith an optional variablefrequency drive.
42.25”(107.3 cm)
16.64”(42.3 cm)
StandardCover
on MediumPumps
HP Outlet1/2” NPT (m)
Drain1/4” NPT (m)
Water Inlet3/4” NPT (f)
14.50”(36.8 cm)
3 2 1 Power
On/Off
3 StatusIights indicateActive valves.
Voltage: 120V/1ph/60HzFull load current: 2.7 AWeight: 15 lbs (6.8 kg)
0.78”(2.0 cm)
11.87”(30.1 cm)
KeyLock
Ø0.25”(0.635 cm)
9.87”(25.1 cm)
1.00”(2.5 cm)
8.00”(20.3 cm)
11.87”(30.1 cm)
Knock outs forControl / Power
Wiring
Valve Controller for HP HVAC Nozzle Applications
HP HVAC - Valve Controller1 Stage - Part 15066923 Stage - Part 15066916 Stage - Part 1506683April 9, 2010
- 7 -
Nortec HP HVAC Valve InstallationRev. A October 7, 2010
- 8 -
Valve Block Installation for HP HVAC Nozzle Applications
The NORTEC Valve block can be installed eitherinside the of duct or outside of the duct. It featuresbetween one, two, or three, 3-way valves, and aflush valve. All connections to the block arecompression type, and are clearly labeled on thevalve block. Refer to the installation drawingsprovided with each system to determine whichmanifolds should be connected to each valve.
Connections:Inlet:Drain:Valves:
½” O.D. compression½”O.D. compression3/8” O.D. Compression
Nortec HP HVAC1 Stage Valve AssemblyRev. A April 12, 2010
- 9 -
1 Stage Valve Assembly for HP HVAC Nozzle Systems
Voltage: 24VDCPower: 18 W per coil, 3 coils totalInlet Connection: ½” compression fittingDrain Connection: ½” compression fittingManifold Connection: 3/8” compression fittingMax. Pressure: 2000 psig (138 bar)Min. Flow: 0.3 gpm (1 Lpm)Max. Flow: 7.9 gpm (30 Lpm)Pressure Loss: 36 psig @ max flow (2.5 bar)Weight: 16 lbs (7 kg)Material: 304 stainless steel and plastic
1/2" Compression
3/8" Compression
8.0 in.( 203 mm )
4.0 in.( 102 mm )
1.4 in.( 34 mm )
2.6 in.( 66 mm )
8.4 in.( 214 mm )
8.0 in.( 203 mm )
4.5 in.( 114 mm )
3.6 in.( 92 mm )
6.8 in.( 171 mm)
6.6 in.( 168 mm )
2.5 in.( 63 mm )
Nortec HP HVAC3 Stage Valve AssemblyRev. B April 12, 2010
- 10 -
3 Stage Valve Assembly for HP HVAC Nozzle Systems
1/2" Compression
3/8" Compression
4.5 in.( 114 mm )
6.6 in.( 168 mm )
2.1 in.( 55 mm )
4.1 in.( 105 mm )
2.6 in.( 66 mm ) 8.0 in.
( 203 mm )
6.0 in.( 152 mm )
2.3 in.( 57 mm )
3.2 in.( 80 mm )
1.4 in.( 34 mm )
4.0 in.( 100 mm )
6.0 in.( 152 mm )
8.4 in.( 214 mm )
O 0.4 in.( 10 mm )
2.3 in.( 57 mm )
1.5 in.( 39 mm )
3.6 in.( 92 mm )
1.5 in.( 39 mm )
3.0 in.( 75 mm )
6.8 in.( 171 mm )
Voltage: 24VDCPower: 18 W per coil, 5 coils totalInlet Connection: ½” compression fittingDrain Connection: ½” compression fittingManifold Connection: 3/8” compression fittingMax. Pressure: 2000 psig (138 bar)Min. Flow: 0.3 gpm (1 Lpm)Max. Flow: 7.9 gpm (30 Lpm)Pressure Loss: 36 psig @ max flow (2.5 bar)Weight: 28 lbs (13 kg)Material: 304 stainless steel and plastic
Nortec HP HVAC6 Stage Valve AssemblyRev. B April 12, 2010
- 11 -
6 Stage Valve Assembly for HP HVAC Nozzle Systems
3/8" Compression
1/2" Compression
6.8 in.( 171 mm)3.6 in.
( 92 mm )
4.5 in.( 114 mm )
0.9 in.( 24 mm )
2.9 in.( 74 mm )
4.9 in.( 123 mm )
O 0.4 in.( 10 mm )
6.6 in.( 168 mm )
1.5 in.( 39 mm )
3.0 in.( 75 mm )
1.5 in.( 39 mm )
2.3 in.( 57 mm )
2.6 in.( 66 mm )
8.0 in.( 203 mm )
8.0 in.( 202 mm )
2.3 in.( 57 mm )1.4 in.
( 34 mm )
3.2 in.( 80 mm )
4.0 in.( 100 mm )
6.0 in.( 152 mm )
8.4 in.( 214 mm )
Voltage: 24VDCPower: 18 W per coil, 7 coils totalInlet Connection: ½” compression fittingDrain Connection: ½” compression fittingManifold Connection: 3/8” compression fittingMax. Pressure: 2000 psig (138 bar)Min. Flow: 0.3 gpm (1 Lpm)Max. Flow: 7.9 gpm (30 Lpm)Pressure Loss: 36 psig @ max flow (2.5 bar)Weight: 38 lbs (17kg)Material: 304 stainless steel and plastic
Nortec HP HVAC3 Stage & 6 Stage Nozzle ManifoldsSeptember 18, 2003
- 12 -
* For 1 Stage Systems (On/Off) connect all manifolds together (not shown).
3 STAGES
6 STAGESHigh-PressureWater Inlet
Drain
High-PressureWater Inlet
Drain
Nortec HP HVACVibration ClampRev. A April 9, 2010
- 13 -
Vibration Clamp for HP HVAC Nozzle Applications
3/8" OD
1.2 in.( 30 mm )
1.1 in.( 28 mm )
1.4 in.( 34 mm )
Nortec HP HVACMounting Rail KitRev. A April 9, 2010
- 14 -
Mounting Rail Kit for HP HVAC Nozzle Applications
Note: Kit also includes 4x 1506296 (1/4” Bolt) and 4x 1493027 (1/4” Locknut)
3.1 in.( 78 mm )
1.2 in.( 31 mm )
D 0.3 in.( 8 mm )
6.1 in.( 154 mm )
D 0.3 in.( 8 mm )
96.0 in.( 2438 mm )
1.2 in.( 31 mm )
1.1 in.( 29 mm )
0.4 in.( 11 mm )
0.2 in.( 6 mm )
2.5 in.( 64 mm )
1507296 - Mounting RailQTY: 1
1507297 - Mounting Rail GussetQTY: 2
Nortec HP HVACMounting Rail InstallationRev. A April 9, 2010
- 15 -
Mounting Rail Installation for HP HVAC Nozzle Applications
1510135HP Mounting Rail Extension KitRev. A May 3, 2010
- 16 -
1510135 - Mounting Rail Extension Kit
Material Specifications:Rail: 304 Stainless steel, 16 gauge
Kit Includes:1x 1507296 - HP Mounting Rail4x 1506296 - Bolt, 1/4”-20 UNC x 1.75”4x 1493027 - Lock Nut, 1/4”-20 UNC
1506296
1493027
1507296
Part Numbers 1507139, 1507140HP HVAC NozzleApril 12, 2010
- 17 -
2"
2"
O -R ING
A NT I-D R IPSPR ING
A N TI-D R IPC H E C K B A L L
AN TI-D R IPB O D Y
O-R IN G
Specifications
Flow Rate
Insert Length: 0.1950” - 0.2010” (4.95 mm - 5.11 mm)Insert Diameter: 0.1880” - 0.1885” (4.78 mm - 4.79 mm)Wall Thickness: 0.0875” - 0.0890” (2.22 mm - 2.26 mm)Thread Pitch 12/24 NC
.008” (0.020 cm) orifice .025 GPM (0.45 Lpm) or 12 lbs/hr (5.4 kg/hr) at 1000 PSI (68.9 Bar)
.005” (0.013 cm) orifice .015 GPM (0.57 Lpm) or 5 lbs/hr (2.3 kg/hr) at 1000 PSI (68.9 Bar)
Nortec HP HVACNozzle Specification Data Sheet
Proper Spray Pattern
Nozzle Anti-Drip Assembly
NOZZLE
(5.1 cm)
(5.1 cm)
Nortec HP HVAC nozzles are impeller-type nozzles and produce a very fine mist without the use
of impingement pins or compressed air. Water at 1000psig is sprayed though a 0.008”
(0.20 mm) or 0.005" (0.13 mm) orifice producing droplets between 10 and 40 microns in size,
with 95% of the droplets at 15 microns. The nozzle and impeller are constructed from 316 stainless
steel for long life. A raised impeller insert helps shed water after the nozzle has stopped fogging,
which will reduce possible nozzle blockage. A Viton o-ring is used to create a leak free seal, and
allows nozzles to be installed or removed without tools. To prevent dripping after the system has
shut down, the nozzles are screwed into anti-drip check valves.
The nozzles are made in the USA to tolerances of 0.00010” (0.00254 mm), and tested for
quality prior to shipping.
HP HVACMist EliminatorSeptember 18, 2003
- 18 -
Mist Eliminator for HP HVAC Nozzle Applications
The NORTEC Mist Eliminator is a single bankdroplet removal system, designed to capturewater within its media. Entrained water iseither evaporated by the passing airflow,increasing water efficiency, or flows downtowards the drain pan at the bottom of theduct section.
The Mist Eliminator is commonly installedat a slight upstream angle (10° - 30°). Wheninstalled in this way, the top of the MistEliminator is farther upstream than thebottom, and airflow drives the waterdownwards to the drains.
Media Specifications:White
AntimicrobialCompatible with UV duct sterilization
1” nominal0.21 @ 300 fpm
1 oz. per square footClass 2
Color:Coatings:UV:Thickness:Initial Resistance:Basis Weight:UL Rating:
For duct sizes in between the standardsizes, the next largest Mist Eliminator isordered and trimmed to fit during installation.
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
250 300 350 400 450 500 550 600 650 700 750
Air Velocity (FPM)
Pressure Drop Across Wet Mist Eliminator (in. H 2O)
Part Number Width Height
2529872 4 4
2529869 4 8
2529864 4 12
2529871 8 4
2529868 8 8
2529863 8 12
2529870 12 4
2529867 12 8
2529862 12 12
2529866 16 8
2529861 16 12
2529865 20 8
2529860 20 12
Size (ft)
HP HVACMist Eliminator - Typical InstallationJanuary 2, 2008
- 19 -
Pump ControlWD 1506681 Rev. F08/19/09
- 20 -
L1
L2
L3 T3
T2
T1
MOTOR
24VACContactor
3 Amps
L1 L2 L3
L1
L2
L3
AUTO
Manual
Off/Auto/Manual SW
G
G
Humid ONIndicator Lamp
NO
NC
COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Y
Overload RelayContactor
Humid ActiveIndicator Lamp
Humid ServiceIndicator Lamp
24vac
24vac COM.Connected toCabinet GND
PrimaryLine Voltage
Water PressureSwitch
ThermostaticSensor
Warm WaterRelief Valve
L1 N I1 I2 I3 I4 I5 I6
Q1 Q2 Q3 Q4
R
Humid FaultIndicator Lamp
(Make connectionto force shutdown100 hours aftermaintenancewarning)
3 1
56 4
2
Push to resethour counter
R
W Bk
24 VAC Cooling Fanfor Totally Enclose Model only
}
ManifoldControlConnection
Humid
Service
}}} }
Humid
Fault
Humid
Active
Humid
ON
COMN/O N/C
Humid ONRelay
Humid ActiveRelay
Humid ServiceRelay
Humid FaultRelay
97 98
Pump Controller with Danfoss VLT 2800or VLT Aqua FC 200WD 1506682 Rev. G03/07/11
- 21 -
L1
L2
L3 L3 VT3
L2 WT2
L1 UT1
MOTOR
24VACContactor
3 Amp s
L1 L2 L3
L1
L2
L3
Variable Speed Controller
AUTO
Manual
Off/Auto/Manual SW
G
G
Humid ONIndicator Lamp
NO
NC
COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Y
Digital input (other)
Com. Analog output
Com. Analog input
Star/Stop
54
39
18
27
12
Pressure Transmitter(4-20 mA)
1 2-+
Overload RelayContactor
Humid ActiveIndicator Lamp
Humid ServiceIndicator Lamp
24vac
24vac COM.Connected toCabinet GND
PrimaryLine Voltage
Water PressureSwitch
ThermostaticSensor
Warm WaterRelief Valve
L1 N I1 I2 I3 I4 I5 I6
Q1 Q2 Q3 Q4
R
Humid FaultIndicator Lamp
- VDC
10 VDC Supply
3 1
56 4
2
Push to resethour counter
55
13
20
50
Analog input (0-20mA)
24 vdc Supply
R
W Bk
24 VAC Cooling Fanfor Totally Enclose Model only
}
ManifoldControlConnection
Humid Service
}}} }
Humid Fault
Humid
Active
Humid O
N
COMN/O N/C
Humid ONRelay
Humid ActiveRelay
Humid ServiceRelay
Humid FaultRelay
}
97 98
60 [ VLT 2800 only ]
[ VLT FC 200 only ]
Analog input (0-20mA)
s s1 Amp 1 Amp
Pump Controller with Danfoss Integrated VFDWD1506708 Rev. DAugust 19, 2009
- 26 -
L1
L2
L3 L3 T3T3
L2 T2T2
L1 T1T1
MOTOR
24VACContactor
3 Amp s
L1 L2 L3
L1
L2
L3
Variable Speed Controller
AUTO
Manual
Off/Auto/Manual SW
G
G
Humid ONIndicator Lamp
NO
NC
COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Y
Digital iput (other)
Analog input (0-10 V)
Digital input
Star/Stop
1
2
4
5
6
X101Pressure Transmitter
(4-20 mA)1 2
-+
Overload RelayContactor
Humid ActiveIndicator Lamp
Humid ServiceIndicator Lamp
24vac
24vac COM.Connected toCabinet GND
PrimaryLine Voltage
Water PressureSwitch
ThermostaticSensor
Warm WaterRelief Valve
L1 N I1 I2 I3 I4 I5 I6
Q1 Q2 Q3 Q4
R
Humid FaultIndicator Lamp
(Make connectionto force shutdown100 hours aftermaintenancewarning)
0 V for terminals 1-7 and 9
Analog (0-20 mA) output
3 1
56 4
2
Push to resethour counter
3
7
8
9
Analog input (0-20mA)
24 vdc Supply
10 vdc Supply
R
W Bk
24 VAC Cooling Fanfor Totally Enclose Model only
}
ManifoldControlConnection
Humid
Service
}}} }
Humid
Fault
Humid
Active
Humid
ON
COMN/O N/C
Humid ONRelay
Humid ActiveRelay
Humid ServiceRelay
Humid FaultRelay
97 98
1 Stage Valve ControllerWD1506692 Rev. DJune 25, 2009
- 27 -
24VdcPowerSupply
N L
VV +_
24Vdc output
N L
PLC UNIT #1
L+ M I-1 I-2 I-3 I-4 I-6 I-7 I-8I-5
Q1
1 2
Q2
1 2
Q3
1 2
Q4
1 2
1 2 3 4 5 96 107 11 14
NOTE:Valve Voltage: 24 VdcValve Power Consumption: 18 W each
24 Vdc
Input Voltage120Vac 60Hz 2.7A
Power OnGreen 24 V
Valve # 1 OnYellow 24 V
Pump Control
8 12 1513 16
ON/OFFLOOP
INTERNAL INTERNAL
EXTERNAL EXTERNAL
V1N/C
V1N/O FLUSH
+ +
+
2/6 1/3
1/22/5ON/OFF Power Switch
+_
0-10Vdc *
* For time proportioning control, connect 0-10 Vdchumidistat.For on/off control, jumper between 1 and 4and put humidistat on 1 and 2 ON/OFF loop
3 Stage Valve ControllerWiring Diagram No. 1506691 REV. DJune 25, 2009
- 28 -
24VdcPowerSupply
N L
VV +_
24Vdc output
N L
PLC UNIT #2
Q11 2
Q21 2
Q31 2
Q41 2
PLC UNIT #1
L+ L+M MI-1 I-1I-2 I-2I-3 I-3I-4 I-4I-6 I-6I-7 I-7I-8 I-8I-5 I-5
Q11 2
Q21 2
Q31 2
Q41 2
Va
lve
#1
Va
lve
#2
Va
lve
#3
Va
lve
#4
Va
lve
#5
1 2 3 4 5 96 107 11 14
0-10Vdc
+
NOTE:Valve Voltage: 24 VdcValve Power Consumption: 18 W each
24 Vdc
Input Voltage120Vac 60Hz 2.7A
Power OnGreen 24 V
Valve # 2 OnYellow 24 V
Valve # 1 OnYellow 24 V
Pump Control
8 12 1513 16
ON/OFFLOOP
INTERNAL INTERNAL
EXTERNAL EXTERNAL
V1N/C FLUSH
+ + + +
+
2/6 1/3
1/22/5ON/OFF Power Switch
-
V1N/O
V2N/C
V2N/O
- --
6 Stage Valve ControllerWiring Diagram No. 1506683 REV. CJune 25, 2009
- 29 -
24VdcPowerSupply
N L
VV +_
24Vdc output
N L
PLC UNIT #2
Q11 2
Q21 2
Q31 2
Q41 2
PLC UNIT #1
L+ L+M MI-1 I-1I-2 I-2I-3 I-3I-4 I-4I-6 I-6I-7 I-7I-8 I-8I-5 I-5
Q11 2
Q21 2
Q31 2
Q41 2
1 2 3 4 5 96 107 11 14
0-10Vdc
+
NOTE:Valve Voltage: 24 VdcValve Power Consumption: 18 W each
24 Vdc
Input Voltage120Vac 60Hz 2.7A
Power OnGreen 24 V
Valve # 3 OnYellow 24 V
Valve # 2 OnYellow 24 V
Valve # 1 OnYellow 24 V
Pump Control
8 12 1513 16
ON/OFFLOOP
INTERNAL INTERNAL
EXTERNAL EXTERNAL
V1N/C FLUSH
+ + + + + ++
2/6 1/3
1/22/5ON/OFF Power Switch
--
V1N/O
V2N/C
V2N/O
--V3
N/CV3
N/O