IEEE_04039473
-
Upload
ramin-goudarzi -
Category
Documents
-
view
216 -
download
0
Transcript of IEEE_04039473
-
7/28/2019 IEEE_04039473
1/3
732 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007
Predictive Method for Improving SVC Speed inElectric Arc Furnace Compensation
Haidar Samet and Mostafa Parniani, Senior Member, IEEE
AbstractThe ability of static VAr compensators (SVC) to re-duce the flicker caused by electric arc furnaces and other variableVAr loads depends on their speed, which is limited by delays in re-active power measurement and thyristor ignition. In this paper, apredictive method is proposed to compensate the delay time and,hence, to improve the SVC performance. Previous samples of theload reactive power are used to predict its future values. PredictedVAr is then applied as a reference for reactive power compensa-tion.
Index TermsElectric arc furnace, flicker, prediction, static VArcompensator (SVC), variable reactive power.
I. INTRODUCTION
AN AC electric arc furnace is an unbalanced, nonlinear, and
time-varying load that can cause various power-quality
problems. Electric arc furnaces and other variable VAr loads
produce voltage fluctuation or flicker due to reactive power vari-
ation. A widely used method for flicker reduction is to em-
ploy static VAr compensators (SVCs) comprising thyristor-con-
trolled reactors (TCRs) or thyristor switched capacitors (TSCs)
[1]. However, the ability of SVCs in flicker reduction is lim-
ited by delays in reactive power measurement and thyristor ig-
nition [2]. The maximum ignition delay is a half cycle of line fre-
quency. Due to these inherent delays, the performance of SVC
in flicker reduction depends on the frequency of reactive powerchanges. With the load variation frequency of up to about 6 Hz,
its performance is very good, but at higher frequencies, it cannot
effectively compensate the load. The synchronous static com-
pensator (STATCOM) is a faster device to remedy this problem
[2]. It is, however, more expensive than SVCs. So, in this paper,
we offer a predictive method to compensate the delay time and,
hence, to improve performance of SVC in flicker reduction.
II. EFFECT OF COMPENSATOR DELAY TIME ON
ITS PERFORMANCE
The effect of delayed reactive power compensation can beshown using the following equations [3]:
(1)
(2)
(3)
Manuscript received June 1, 2006. Paper no. PESL-00035-2006.H. Samet is with the Electrical and Computer Engineering Department, Is-
fahan University of Technology, Isfahan 84156, Iran (e-mail: [email protected]).
M. Parniani is with the Department of Electrical Engineering, Sharif Univer-sity of Technology, Tehran, Iran (e-mail: [email protected]).
Digital Object Identifier 10.1109/TPWRD.2006.886768
where , , and are the load, compensator, and sourcereactive powers, respectively. is the frequency of reactive
power variation, and is the compensation delay. Then, the
variable VAr reduction factor is equal to
(4)
For an ideal compensator, is zero. With and in-
creasing, increases too, and above a specific frequency, this
factor becomes greater than one. In this case, the compensator
will have a negative impact on flicker, and causes it to grow.
The frequency limit is inversely proportional to the compensa-
tion delay time.
III. IMPROVING SVC PERFORMANCE WITH ESTIMATING LOAD
REACTIVE POWER IN FUTURE TIMES
To alleviate the negative impact of delay time, we use a
method to estimate the load reactive power in future times.
Predicted values will then be used as a reference for SVC, to
compensate the delay. VAr prediction is carried out using the
past samples of load reactive power. Laplace transform of the
lead time prediction function, can be approximated as
(5)
where s are constant coefficients to be calculated. One
simple way of calculating these coefficients is
(6)
It is straightforward to calculate s by expanding the right-
hand side (RHS) of (6), and approximating the series with its
first terms. Fig. 1 shows the amplitude and phase of the ap-
proximate functions for ms. In this figure, is shown
on each curve and the curve without any number is the exact
function. For , (6) is valid if
(7)
So, knowing the desired prediction horizon, the maximum
compensation frequency can be found from (7). For instance,
with ms, the maximum theoretical compensation fre-
quency is 16.6 Hz. A better approximation for to increase
this range is obtained as follows:
(8)
0885-8977/$20.00 2006 IEEE
-
7/28/2019 IEEE_04039473
2/3
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 733
Fig. 1. Amplitudeand phase of theapproximation functionswith a = 1 . (Colorversion available online at: http://ieeexplore.ieee.org).
Fig. 2. Amplitude of approximation functions for large frequencies with a =
1
.
Maximum compensation frequency with (8) is
(9)
A sufficiently large simplifies (9) to . In-
creasing the number of terms raises the accuracy of finite
approximation of(8). However, it has a negative impact in am-
plifying noise and harmonics at specific frequencies. This phe-nomenon is shown in Fig. 2 for and 10 ms. Studies
show that harmonic amplification tends to lessen with higher
values of .
Resonance may occur if the amplification frequency coin-
cides with the line frequency or its harmonics. In that case,
at the RHS of (5) needs to be replaced with . For ex-
ample, this is the case when using (8) with ms in a
50-Hz (314-rad/s) system (see Fig. 2 ). Choosing ms
then yields
(10)
Inspection of the frequency characteristics of (10) does not re-
veal any resonance condition.
IV. OPTIMUM APPROXIMATION
The approximation introduced in the last section is not nec-
essarily the optimum one. As already discussed, the sampling
delay time can be different with the prediction horizon. So with
the following general expression:
(11)
the optimum coefficients are found by solving
(12)
The choice of and depends on the desired compensa-
tion frequency range. Flicker frequency is normally between 4
Hz and 14 Hz. For convenience, let and .
Then, (12) can be rewritten as
(13)
Also, see (14)(15) at the bottom of the page.
The following set of equations needs to be solved to find the
optimum coefficients:
(16)
Table I shows constants for ms, ms, and
.
V. CONCLUSION
Inherent delays of SVCs limit their capability of compen-sating fast varying reactive loads and flicker reduction. To im-
prove the speed of compensation, a predictive method based on
the estimation of load reactive power in the future using its past
(14)
(15)
-
7/28/2019 IEEE_04039473
3/3
734 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007
TABLE I
OPTIMUM COEFFICIENTS FOR T = 1 0 ms AND T 1 = 1 4 ms.
samples was presented. It was shown how to choose the esti-
mation parameters to extend the compensation frequency and
to avoid resonance conditions. Optimum parameters were cal-
culated with due consideration of flicker frequency.
REFERENCES
[1] E. Acha, V. Agelidis, O. Anaya, and T. J. E. Miller, Power ElectronicControl in Electrical Systems. Oxford, U.K.: ButterworthHeine-
mann, 2002.[2] A. G. Cerrada et al., Comparison of thyristor-controlled reactors and
voltage-source inverters for compensation of flicker caused by arc fur-naces, IEEE Trans. Power Del., vol. 15, no. 4, pp. 12251231, Oct.2000.
[3] T. J. E. Miller, Reactive Power Control in Electrical Systems. NewYork: Wiley, 1982.