IEC Overload Relays Selection XX SIRIUS 3RB12 Solid State...
Transcript of IEC Overload Relays Selection XX SIRIUS 3RB12 Solid State...
XXIEC Overload RelaysSIRIUS 3RB12 Solid State Overload Relays
Selection
N C . ^ NO N£>--, Jr~^P
- ®®(g®O®®<x>®-
Front View 3RB12
1. Control supply voltage terminals A1/A2
2. Green "Ready" LED
3. Red "Ground Fault" LED
4. Red "Overload" LED
5. TEST/RESET button
6. 1 NO/1 NC for overload/thermistor trip
7. Terminals for thermistor T1/T2
8. Terminals for external summation current transformer C1/C2
9. Terminals for remote or auto RESET Y1/Y2
10. Current FLA dial
11. Trip Class dial
12. 1 NO/1 NC for ground fault trip or overload warning option
13. Analog output 4...20 mA
Ordering Information
>• Accessories see page 265.
> Dimensions see page 381.
> Wiring Diagram see page 381.
>• Technical Data see page 358.
> Application Data see page 261.
3RB12 Electronic Overload Relay
3RB1246
Selection and Ordering Data
Rated ControlSupply Voltage
24V DC
110-120V A C ( 1 )
220-240V AC
Setting RangeAmperage
1.25-6.36.3-2525-10050-205125-500200-820
1.25-6.36.3-2525-10050-205125-500200-820
1.25-6.36.3-2525-10050-205125-500200-820
Widthmm
707070
120145230707070
120145230707070120145230
ContactorFitting
single/panel mountsingle/panel mountsingle/panel mount3TF50/51/523TF53/54/55/56/573TF68/69
single/panel mpuntsingle/panel mountsingle/panel mount3TF50/51/523TF53/54/55/56/573TF68/69
single/panel mountsingle/panel mountsingle/panel mount3TF50/51/523TF53/54/55/56/573TF68/69
Catalog No
3RB1246-1PB3RB1246-1QB_3RB1246-1EB_3RB1253-OFB3RB1257-OKB3RB1262-OLB
3RB1246-1PG_3RB1246-1QG3RB1246-1EG3RB1253-OFG_3RB1257-OKG_3RB1262-OLG
3RB1246-1PIVL3RB1246-1QM3RB1246-1EM3RB1253-OFM_3RB1257-OKM3RB1262-OLM
PriceS
372.372.372.558.744.930.
372.372.372.558.744.930.
372.372.372.558.744.930.
oU
%Q
3RB1253
Order Options
VersionWithout internal summation current transformer for low-level ground-fault protection®for motors with 3 and 4-conductor connection (ground-fault protectionin the event of fault currents of U.3A, 0-5A, and 1A) with separate outputfor "ground-fault", next to the "overload/thermistor" output.
3RB1246-1PG
I i ,
Without internal summation current transformer for ground-fault protection®for motors with 3 and 4-conductor connection (ground-fault protectionin the event of fault currents of 0.3A, 0-5A and 1A) with separate output for"overload-warning", next to the "overload/thermistor"/"ground-fault" output.
With internal summation current transformer for ground-fault protection® formotors with 3-conductor connection (ground-fault detection in the event offault currents >30% from the set current...) with separate output for"ground-fault", next for the "overload/thermistor" output.
With internal summation current transformer for ground fault protection® for motorswith 3-conductor connection (ground-fault detection in the event of fault currents>30% from the set current...) with separate output for "overload-warning", nextto the "overload/thermistor"/"ground-fault" output.
Function of the outputs in the case of control-voltage failure:(For an explanation, see Table on page 41)
monostablebistable
PriceAdder
None
None
None
None
None155.
©Require external current transformer for low-leground-fault detection. See page 265.
©Can also be used with external transformer. Sepage 265.
©Switching statuses are retained.
Discount Code: Overload RelaysSiemens Industr ial Control Products
^yIEC Overload RelaysSIRIUS 3RB12 Solid State Overload Relays
General
Features• Ground Fault Protection: Equipment
or Low-level.• Overload Warning Contact Option.• Selectable Trip Class: 5, 10, 15, 20,
25, 30.• Three LED Displays: Ready, Ground
Fault, and Overload.• 2 NO/2 NC Electrically Isolated
Auxiliary Contacts are Standard.• Remote and Automatic Reset by
Means of External Wiring.• Combined Test/Reset button with
function test.• Monostable or Bistable Output
Versions Available.•_ Analog output versions available.
Self Monitoring.• UL Listed.• CSA Certified.
S«?««*4"«(| |
3 R B 1 2 So l i d -S ta te O v e r l o a d R e l a y
ApplicationThe 3RB12 solid state overload fea-tures adjustable trip class, groundfault protection, phase unbalance,and phase loss protection.
An optional overload warning contactprovides status from which to takeaction in advance of a shutdown.These and many other functionswere designed to meet the specificneeds of equipment protection.
Tripping CharacteristicsThe three phase trip curves (Figure 1)show the dependence of the trippingtime from a cold state on the multipleof the current setting. If the unit ispre-loaded with 100% of the current,the tripping times are shortened. Inthe event of a phase loss or a currentunbalance >40% of the current set-ting, the characteristic in phaseloss/unbalance trip curve (Figure 2)applies.
Mode of Operation
The motor current is detected ineach phase via current transformersand continuously monitored by amicroprocessor.
If an overload >110% of the currentsetting occurs, or if there is a current
unbalance >40%, or if a phase lossoccurs, then tripping is initiated bythe switching of two auxiliary con-tacts, 1 NO/1 NC, (Numeral 6 inFront View diagram on page 262).
Resetting is possible after a recoverytime of 5 minutes has elapsed, eitherby pressing the Test/Reset button onthe unit or by remote or automaticreset.
In the event of a ground-fault, theunit trips via separate (1 NO/1 NC)output without a time delay. (Numeral12 in Front View diagram on page262). Resetting after a ground faultis possible without a time delay.
A test of the unit's functions, namelycurrent detection, thermistor andground-fault input, and tripping func-tions of the auxiliary contacts can beinitiated by pressing the TEST/RESETbutton. A test of the unit's functionscan be carried out during operationwithout the contacts changing state.The test is verified by LED signals.
A self-monitoring feature causes theunit to trip when an internal faultoccurs.
E1
Q.•cH-
v><
120
50
20
10
5
2•• v
bO
20
10
5
2
0
-Cl
trSil\
C7
^
S3Tl 1ASS Y
LASS 30
/
</
^?sXl
^
/ 22
^̂v•x
5
D
-̂».
V
Sf
*̂»*»
-*.
5*»
**•
£
"|*
--
C'c {
I?H
(/> <
120100
50
20
10
5
2-. 1
bO
10
5
2
-CL!
k
\— *S
151 1C
VSS E
4̂</̂/
LASS 30,25y/™
m1x
x
•̂xs^V
V
$V
"Sfc
•s.
5>:•»
^
>s•>•«
, 6 1 2 5 10x1 e 0,6 1 2 5 10x1 eTripping current (mean values) Tripping current (mean values)
Figure 1 Figure 2
"hree Phase Trip Curves Trip Curves for Phase Loss/Unbalance
Function of the Output RelaysIn Case of:
Dropout of the control voltage without tripReturn of the control voltage without trip
Return of the control voltage after trip
Monostable3RB12...-...0
Unit trips
Unit resets
Bistable3RB12...-...1
No change in the switching state of the auxiliary contacts
Unit remains trippedResetting:
Overload trip, after 5 min.Thermistor trip when 5°K below the operating temperature.Ground-fault trip, immediately.
oo
Siemens Industrial Control Products