IEC 60870-5-101 Requirement for RLDC

1
IEC 60870-5-101 Interoperability profile for NRLDC, NERLDC , ERLDC (ALSTOM EMS/SCADA system) Page 9 of 10 Rev.1 2. ADDITIONAL INFORMATION ON IEC 60870-5-101 FOR NRLDC, NERLDC AND ERLDC A. Telemetred Data and ASDU mapping The following table explains the type of the telemetered data and corresponding ASDUs used to transmit this data as per IEC 60870-5-101 protocol. These are same for all the above three RLDCs. Type of Data Data Unit type as per IEC Description as per IEC Data polling method Interro gation group Transmitt ed after Class-X request Info Obj. Address range Analog inputs (P,Q, V, f) ASDU-11 Measured value scaled value As cyclic data on Class 2 polls Class 2 8848- ASDU-1 Single point information By exception (spontaneou s) and on periodic Group scan Group-1 Class 1 after exception, Class 1 after Group 1 scan 392- Digital inputs – Single status (Isolators, Protection signals) ASDU- 2 (for SOE) Single point information with time tag By exception (spontaneou s) and on periodic Group scan Group-1 Class 1 after exception, Class 1 after Group 1 scan Digital inputs – Double status (Circuit breakers) ASDU-4 Double point information with time tag By exception (spontaneou s) and on periodic Group scan Group-1 Class 1 after exception, Class 1 after Group 1 scan 256- Pulse accumulators ASDU-15 Integrated totals By periodic counter interrogatio n Group-1 (counter interrog ation) Class 2 12544- Analog Outputs (Setpoint) ASDU-48 Set point command Normalized value 37120 Digital Control command (CB ASDU 46 Double command 33024-

description

Protocol Requirement for connection to Grid

Transcript of IEC 60870-5-101 Requirement for RLDC

Page 1: IEC 60870-5-101 Requirement for RLDC

IEC 60870-5-101 Interoperability profile for NRLDC, NERLDC , ERLDC (ALSTOM EMS/SCADA system)

Page 9 of 10 Rev.1

2. ADDITIONAL INFORMATION ON IEC 60870-5-101 FOR NRLDC, NERLDC AND ERLDC

A. Telemetred Data and ASDU mapping

The following table explains the type of the telemetered data and corresponding ASDUs used to transmit this data as per IEC 60870-5-101 protocol. These are same for all the above three RLDCs.

Type of Data Data Unit type as per IEC

Description as per IEC

Data polling method

Interrogation group

Transmitted after Class-X request

Info Obj. Addressrange

Analog inputs (P,Q, V, f)

ASDU-11 Measured value scaled value

As cyclic data on Class 2 polls

Class 2 8848-

ASDU-1 Single point information

By exception (spontaneous) and on periodic Group scan

Group-1 Class 1 after exception, Class 1 after Group 1 scan

392- Digital inputs –Single status (Isolators, Protection signals)

ASDU- 2 (for SOE)

Single point information with time tag

By exception (spontaneous) and on periodic Group scan

Group-1 Class 1 after exception, Class 1 after Group 1 scan

Digital inputs –Double status (Circuit breakers)

ASDU-4 Double point information with time tag

By exception (spontaneous) and on periodic Group scan

Group-1 Class 1 after exception, Class 1 after Group 1 scan

256-

Pulse accumulators ASDU-15 Integrated totals By periodic counter interrogation

Group-1 (counter interrogation)

Class 2 12544-

Analog Outputs (Setpoint)

ASDU-48 Set point command Normalized value

37120

Digital Control command (CB

ASDU 46 Double command 33024-