IDA8 System
IDA8C
Networkable PAVA system Controller Unit
IDA8 is a third-generation modular
system that complies with current
architectural demands requiring
IP and/or fibreoptic networking to
allow for even the most complex of
system designs.
IDA8 responds to Public Address
and Voice Alarm requirements
as stated in EN54-16, ISO 7240-
16 and BS5839/8, with specific
attributes for compliance in large
installations.
Del iver ing Your Message
3
IDA8 system
IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
ConneCtivity:
The IDA8C Controller unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, with front panel access for a fully monitored fireman’s microphone and emergency message trigger buttons. IDA8C also supports amplifier monitoring with hot-swap amplifiers and loudspeaker line impedance monitoring. It can support up to four PSS-AS monitored microphone consoles and up to eight monitored amplifiers plus two back-up amplifiers, paging into 8 different zones per unit with A/B line detection according to BS5939 part 8. Two card slots are provided for either 4-channel 0dB audio input or 4-channel audio cards. Optional AES/EBU cards are also available.
Each IDA8C input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines. Up to 4 hours of digital messaging (WAV format) can be stored for live or pre-recorded playback. Digital audio files are uploaded from a computer to the IDA8S through the user-friendly ATEÏS Studio GUI. Several messages can be played simultaneously into different zones: up to 4 messages from a single IDA8C Controller or a total of 48 messages across an IDA8 system (controller with slaves). A built-in loudspeaker on the IDA8C allows selective feedback for all sources and 100V output signals.
IDA8S Slave units can extend the system configuration with an additional 8 inputs and 8 outputs and 2 back-up amplifiers. The slave units are available as single zone (IDA8S) or with A/B speaker line configurations (IDA8SAB), or for Low-impedance monitoring (IDA8SL).
The IDA8C Controller unit enables operators to see a detailed overview of the operational status of the entire PA system at the press of a button. It is able to run an impedance scan of all components connected to it, covering not only the input paging consoles but also connectors, cabling, processing blocks such as compressors and limiters, delay lines, the network and loudspeakers.
The IDA8C Controller operates either on mains power or on a 24V battery power supply for emergency back-up, with automatic switchover. Both power supplies are monitored. IDA8C is easily configured using the PC-based ATEÏS Studio global software. Once programmed, the system will operate independently (off-line) without a PC having to be connected.
SeCurity
In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally-generated pilot tone is available for monitoring impedance on the loudspeaker lines.
The system can handle 256 priorities for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements. The controller monitors the status of all the equipment in the system, reports status changes and logs the last 999 fault messages in the system. The log can be accessed on the front-panel IDA8C display or on a PC through ATEÏS Studio. The IDA8C system (controller and slaves) supports redundant network cabling, wired as a redundant loop.
Main CharaCteriStiCS
•Public address and emergency sound system control unit
•Fully digital with 8 audio inputs and 8 audio outputs
•4 dedicated and monitored PDC-ports for firemen’s microphones
•2 dedicated audio in and outputs for back-up amplifiers
•Enhanced loudspeaker line surveillance for AB-zoned installation
•Simultaneous control and routing of 48 audio channels over dedicated network
•Equiped as standard with RJ45 network cards (NET-C1) for links up to 100 m
• Optional Fibreoptic cards for links up to 20 km
•9 supervised control inputs and 8 control outputs
•Ethernet interface for configuration, control, diagnostics and logging
•Digital storage for up to 4 hours of prerecorded messages
• 4 message players
• Stores the last 999 fault events
• EN54-16 certified
Networkable PaVa system – CoNtroller UNIt
IDA8C
IDA8 system
4
inStallation noteS
Networkable PaVa system – CoNtroller UNIt
IDA8C
5
IDA8 system
PartS inCluded
Quantities Components
1 IDA8Cxx Controller unit
1 Power cord
1 Set of mounting brackets for 19” rack
1 Set of connectors
1 Ateis Studio software GUI
teChniCal SPeCifiCationS
electrical
mains power supply
Voltage 115 or 230 VAC ±15%, 50/60 Hz
Power consumption 48 W
battery power supply
Voltage 18 - 26 VDC
Performance
Frequency response -3 dB @ 20 Hz and 20 kHz
line inputs (optional audio input card)
Connector 3-pin phoenix
Frequency response -3 dB @ 20 Hz and 20 kHz
S/N >90 dBA
THD < 0,1% @ 1 kHz
Input sensivity 770 mV
Input impedance 20 kohm
line outputs (optional audio output card)
Connector 3-pin phoenix
S/N >-85 dBu
THD < 0,02% @ 1 kHz
Signal 770 mV
Output impedance <300 ohm
loudspeaker lines in 8 x 100 V
Rated load resistance 20 ohm (100 V)
Rated load capacitance 250 nF (100 V)
Rated output power(per channel)
500 W (cont. at 40°C)
loudspeaker lines out 8 x (a+b)
Rated load resistance 20 ohm (100 V)
Rated load capacitance 250 nF (100 V)
Rated output power(per channel) 500 W (cont. at 40°C)
mechanical
Dimensions (H x W x D)
With 19” rackmount brackets 88 x 483 x 305 mm
Weight 5.36 kg (11,8lb)
Mounting 19”-rackmount
Colour RAL7016
environmental
Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)
Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
ordering Information
IDa8C-C1-Io Controller with NET-C1 card & 4 audio inputs & 4 audio outputs
IDa8C-C1-2I Controller with NET-C1 card & 8 audio inputs
CertifiCationS and aPProvalS
inStallation/Configuration noteS
1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz
2
3
4
5
6
7
8
9
10
11
•
•
region CertifiCationS
Europe CE CE – 0359 (Intertek)
Immunity according to EN50103-4
PAVA EN54-16 certified 2012
ControlS and indiCatorS
Front
• 3,5” full colour touch-screen LCD display
• Zone selection buttons
• EVAC-start
• Fireman’s microphone
• Status indicators
rear
• Voltage selector
interConneCtionS
Front
• Firemen’s microphone
rear
• Mains input
• Battery backup input
• 9 control inputs
• 8 control outputs
• 4 analogue audio mic/line inputs
• 4 analogue audio line inputs
• Ethernet
• LOCAL network in/out card
• Free slot for GLOBAL-network card
• 8 amplifier in and outputs
• 2 connections for back-up amplifiers
• 4 monitored paging console inputs
Networkable PaVa system – CoNtroller UNIt
IDA8C
6
IDA8 system
1. Fireman microphone active
2. Fireman microphone input
3. Fireman microphone hook
4. Monitoring loudspeaker (Audible warning)
5. Bypass mode
6. General fault
7. System fault
8. Global EVAC
9. Bypass monitoring
10. 3.5” Touch screen
11. ESC - button
12. OK button
13. Up button
14. Down button
15. Plus button
16. Minus button
17. EVAC indicators
18. FAULT indicators
19. RESET button
20. Power
21. Network
22. EVAC button
1. Speaker zone outputs (A+B)
2. Back-up amplifiers (2x)
3. Amplifier 0dB line outputs
4. Bypass mode contact input
5. EVAC and GF output contact
6. PDC-ports for secured paging con-soles
7. Ethernet
8. Local network card
9. Global network card
10. Audio I/O
11. Telephone line input
12. Telephone controller
13. Bypass mode outputs
14. Contact outputs, 8x
15. Contact inputs, 9x
16. 24VDC slave output
17. 24VDC back-up input
18. AC power socket
Networkable PaVa system – CoNtroller UNIt
IDA8C
7
IDA8 system
IDA8 NetworkAble PAVA system – slAVe UNIt
IDA8S
IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
ConneCtivity:
The IDA8S Slave unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, along with amplifier monitoring for hot-swap amplifiers and loudspeaker line impedance monitoring. It can support up to two PSS-AS monitored microphone consoles and up to eight monitored amplifiers plus two backup amplifiers, paging into 8 different zones per unit with line detection. Two card slots can fitted with optional 4-channel analogue audio input/outputs cards or 4-channel audio AES/EBU cards (max two cards per device).
IDA8S Slave units extend the IDA8 system configuration with an additional 8 output zones and 2 back-up amplifiers. Each input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines. Up to 4 hours of digital messaging (WAV format) can be stored for live or pre-recorded playback. Digital audio files are uploaded from a computer to the IDA8S through the user-friendly ATEÏS Studio GUI. Several messages can be played simultaneously into different zones: up to 4 messages from a single IDA8S Slave or a total of 48 messages across an IDA8 system (controller with slaves).
The IDA8S Slave operates either on mains power or on a 24V battery power supply for emergency back-up, with automatic switchover. Both power supplies are monitored. The IDA8S Slave also supports redundant loop network cabling. IDA8S is easily configured using the PC-based ATEÏS Studio global software. Once programmed, the system will operate independently (off-line) without a PC having to be connected.
SeCurity
In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally-generated pilot tone is available for monitoring impedance on the loudspeaker lines.
The system can handle 256 priorities for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements. The controller monitors the status of all the equipment in the system, reports status changes and logs error details. The log can be accessed on the front-panel IDA8C display or on a PC through ATEÏS Studio.
Main CharaCteriStiCS
•Public address and emergency sound system slave unit
•Fully digital with Optional: 8 audio inputs and 8 audio outputs
•2 dedicated audio in and outputs for back-up amplifiers
•2 dedicated and monitored PDC-ports for fireman’s microphones
•Enhanced loudspeaker line surveillance for zoned installations
•Simultaneous control and routing of 48 audio channels over dedicated network
•Equipped as standard with RJ45 network cards for links up to 100m
• Optional Fibreoptic cards for links up to 20 km
•9 supervised control inputs and 8 control outputs
•Ethernet interface for configuration, control, diagnostics and logging
•Digital storage for up to 4 hours of pre-recorded messages
• 4 message players
• EN54-16 certified
IDA8 system
8
IDA8 NetworkAble PAVA system – slAVe UNIt
IDA8S
inStallation noteS
9
IDA8 system
PartS inCluded
Quantities Components
1 IDA8Sxx Slave unit
1 Power cord
1 Set of mounting brackets for 19” rack
1 Set of connectors
1 Ateis Studio software GUI
teChniCal SPeCifiCationS
electrical
mains power supply
Voltage 115 or 230 VAC ±15%, 50/60 Hz
Power consumption 48 W
battery power supply
Voltage 18 - 26 VDC
Performance
Frequency response -3 dB @ 20 Hz and 20 kHz
line inputs (optional input card)
Connector 3-pin phoenix (electronically balanced)
Frequency response +/-3 dB @ 20 Hz and 20 kHz
S/N >90 dBA
THD < 0,1% @ 1 kHz
Input sensitivity 770 mV
Input impedance 20 kOhm
line outputs (optional output card)
Connector 3-pin phoenix
S/N >-85 dBu
THD < 0,02% @ 1 kHz
Signal 770 mV
Output impedance < 300 Ohm
loudspeaker lines in 8 x 100 V
Rated load resistance 20 ohm (100 V)
Rated load capacitance 250 nF (100 V)
Rated output power(per channel)
500 W (cont. at 40°C)
loudspeaker lines out 8 x
Rated load resistance 20 ohm (100 V)
Rated load capacitance 250 nF (100 V)
Rated output power(per channel) 500 W (cont. at 40°C)
IDA8 NetworkAble PAVA system – slAVe UNIt
IDA8S
mechanical
Dimensions (H x W x D)
for 19” rack use, with brackets
88 x 483 x 285 mm
Weight
IDA8s 4.2 kg (9.25 lb)
Mounting 19”-rackmount
Colour RAL7016
environmental
Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)
Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
ordering Information
IDA8s-C1 Slave with NET-C1 card
IDA8s-C1-Io Slave with NET-C1 card & 4 audio inputs & 4 audio outputs
IDA8s-C1-2I Slave with NET-C1 card & 8 audio inputs
IDA8s-C1-2o Slave with NET-C1 card & 8 audio outputs
CertifiCationS and aPProvalS
inStallation/Configuration noteS
1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz
2
3
4
5
6
7
8
9
10
11
•
•
region CertifiCationS
Europe CE CE – 0359 (Intertek)
Immunity according to EN50103-4
PAVA EN54-16 certified 2012
ControlS and indiCatorS
Front
• Status LEDs
• Zone LEDs
• Power LEDs
rear
• Voltage selector
interConneCtionS
rear
• Mains input
• Battery backup input
• 9 control inputs
• 8 control outputs
• Optional 4 analogue audio mic/line inputs
• Optional 4 analogue line audio inputs
• 2 system LOCAL-network connections
• 8 amplifier in and outputs
• 2 connections for back-up amplifiers
10
IDA8 system
1. System fault
2. General fault
3. Bypass mode
4. Bypass monitoring
5. Global EVAC
6. EVAC indicators
7. Power
8. Network
9. FAULT indicators
1. Speaker zone outputs (8x)
2. Back-up amplifiers (2x)
3. Amplifier 0dB line outputs
4. Bypass mode outputs
5. PDC-ports for secured paging consoles
6. Local network card
7. Audio I/O (Optional)
8. 8 Contact outputs
9. 9 Contact inputs
10. 24 VDC input
11. 24 VDC back-up input
IDA8 NetworkAble PAVA system – slAVe UNIt
IDA8S
11
IDA8 system
IDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg
IDA8SAB
IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
ConneCtivity:
The IDA8SAB Slave unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, along with amplifier monitoring with hot-swap amplifiers and loudspeaker line-impedance line monitoring. It can support up to two PSS-AS monitored microphone consoles, up to eight monitored amplifiers plus two backup amplifiers and paging into 8 different zones per unit with A/B line detection according to the BS 5939-part 8. Two rear card slots can be fitted with optional 4-channel analogue audio in/output cards 4 channel AES/EBU cards for digital audio in/out.
IDA8SAB Slave units can extend the IDA8 system configuration with an additional 8 output zones and 2 back-up amplifiers. Up to 4 hours of digital messaging can be stored in the unit for live or scheduled playback. Files are uploaded in WAV format from a computer using the ATEÏS Studio system GUI. Several messages can be played simultaneously into different zones: up to 4 from a single IDA8SAB or a total of 48 messages across a full IDA8 system with slaves.
Each input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines.
IDA8SAB is easily configured with PC-based ATEÏS Studio global software. Once programmed, the system will run independently without a PC connected. The IDA8SAB Slave operates either on AC mains power or on a 24V DC battery power supply for emergency back-up, with automatic switchover. Both of the power supplies are monitored
SeCurity
In accordance with EN54-16, ISO 7240-16 and BS5839:pt8, all system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally generated pilot tone is available for monitoring impedance on the loudspeaker lines. The IDA8SL Slave supports redundant network cabling as a redundant loop. The system can handle 256 priorities, for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements.
Main CharaCteriStiCS
•Public address and emergency sound system slave unit
•Fully digital with up to 8 audio inputs and outputs (optional)
•2 dedicated and monitored PDC-ports for fire-man’s microphones
•2 dedicated audio in and outputs for back-up amplifiers
•Enhanced loudspeaker line surveillance for AB-zoned installations
•Simultaneous control and routing of 48 audio channels over dedicated network
•Equipped as standard with RJ45 network cards for links up to 100 m
• Optional fibreoptic cards for links up to 20 km
• 9 supervised control inputs and 8 control outputs
•Ethernet interface for configuration, control, diagnostics and logging
•Digital storage for up to 4 hours of pre-recorded messages
• 4 message players
• EN54-16 certified
IDA8 system
12
inStallation noteS
IDA8SABIDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg
13
IDA8 system
PartS inCluded
Quantities Components
1 IDA8SAB Slave unit
1 Power cord
1 Set of mounting brackets for 19” rack
1 Set of connectors
1 Ateis Studio software GUI
teChniCal SPeCifiCationS
electrical
mains power supply
Voltage 115 or 230 VAC ±15%, 50/60 Hz
Power consumption 48 W
battery power supply
Voltage 18 - 26 VDC
Performance
Frequency response -3 dB @ 20 Hz and 20 kHz
line inputs (oPtIoNAl)
Connector 3-pin phoenix (electronically balanced)
Frequency response +/-3 dB @ 20 Hz and 20 kHz
S/N > 90 dBA
THD < 0,1% @ 1 kHz
Input sensitivity 770 mV
Input impedance 20 kohm
line outputs (oPtIoNAl)
Connector 3-pin phoenix
S/N > -85 dBu
THD < 0,02% @ 1 kHz
Signal 770 mV
Output impedance < 300 Ohm
loudspeaker lines in 8 x 100 V
Rated load resistance 20 ohm (100 V)
Rated load capacitance 250 nF (100 V)
Rated output power(per channel)
500 W (cont. at 40°C)
loudspeaker lines out 8x (A+b)
Rated load resistance 20 ohm (100 V)
Rated load capacitance 250 nF (100 V)
Rated output power(per channel) 500 W (cont. at 40°C)
mechanical
Dimensions (H x W x D)
(including rackmount brackets) 2U, 88 x 483 x 289 mm
Weight
IDA8sAb 5 kg (11 lb)
Mounting 19”-rackmount
Colour RAL7016
environmental
Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)
Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
ordering Information
IDA8sAb-C1 Slave with NET-C1 card
IDA8sAb-C1-Io Slave with NET-C1 card & 4 audio inputs & 4 audio outputs
IDA8sAb-C1-2I Slave with NET-C1 card & 8 audio inputs
IDA8sAb-C1-2o Slave with NET-C1 card & 8 audio outputs
CertifiCationS and aPProvalS
inStallation/Configuration noteS
1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz
2
3
4
5
6
7
8
9
10
11
•
•
region CertifiCationS
Europe CE CE – 0359 (Intertek)
Immunity according to EN50103-4
PAVA EN54-16 certified 2012
ControlS and indiCatorS
Front
• Status LEDs
• Zone LEDs
• Power LEDs
rear
• Voltage selector
interConneCtionS
rear
• Mains input
• Battery backup input
• 9 control inputs
• 8 control outputs
• 4 analogue audio mic/line inputs (optional)
• 4 analogue audio line inputs (optional)
• 2 system LOCAL-network connections
• 8 amplifier in and outputs
• 2 connections for back-up amplifiers
• 2 monitored paging console inputs
IDA8SABIDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg
14
IDA8 system
1. System fault
2. General fault
3. Bypass mode
4. Bypass monitoring
5. Global EVAC
6. EVAC indicators
7. Power
8. Network
9. FAULT indicators
1. Speaker zone outputs (A+B)
2. 2 Back-up amplifier outputs
3. Amplifier 0dB line outputs
4. Bypass mode outputs
5. PDC-ports for secured paging consoles
6. Local network card
7. Audio I/O (optional)
8. Telephone line input
9. Telephone controller
10. 8 Contact outputs
11. 9 Contact inputs
12. 24 VDC slave output
13. 24 VDC back-up input
14. AC power socket
IDA8SABIDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg
15
IDA8 system
IDA8 NetworkAble PAVA system – low Impedance slave unit
IDA8SL
IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
ConneCtivity:
The IDA8SL Low-Impedance Slave unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, along with amplifier monitoring with hot-swap amplifiers and low-impedance line monitoring. It can support up to two PSS-AS monitored microphone consoles, up to four monitored amplifiers plus two backup amplifiers and paging into 4 different zones per unit with line detection. Each input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines.
IDA8SL Slave units can extend the IDA8 system configuration with an additional 4 output zones and 2 back-up amplifiers. Up to 4 hours of digital messaging can be stored in the unit for live or scheduled playback. Files are uploaded in WAV format from a computer using the ATEÏS Studio system GUI. Several messages can be played simultaneously into different zones: up to 4 from a single IDA8SL or a total of 48 messages across a full IDA8 system with slaves.
IDA8SL is easily configured with PC-based ATEÏS Studio global software. Once programmed, the system will run independently without a PC connected. The IDA8SL-Slave operates either on AC mains power or on a 24V DC battery power supply for emergency back-up, with automatic switchover. Both of the power supplies are monitored.
SeCurity
In accordance with EN54-16, ISO 7240-16 and BS5839:pt8, all system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally generated pilot tone is available for monitoring impedance on the loudspeaker lines. The IDA8SL Slave supports redundant network cabling as a redundant loop. The system can handle 256 priorities, for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements.
Main CharaCteriStiCS
•Public address and emergency sound system slave unit
•Fully digital with: 8 audio inputs and 8 audio outputs
•Two dedicated and monitored PDC-ports for firemen’s microphones
•2 dedicated audio in and outputs for back-up amplifiers
•Enhanced loudspeaker line surveillance for low-impedance installations
•Simultaneous control and routing of 48 audio channels over dedicated network
•Equipped as standard with RJ45 network cards for links up to 100 m
• Optional Fiberoptic cards for links up to 20 km
•9 supervised control inputs and 8 control outputs
•Ethernet interface for configuration, control, diagnostics and logging
•Digital storage for up to 4 hours of pre-recorded messages
• 4 message players
• EN54-16 certified
IDA8 system
16
inStallation noteS
IDA8 NetworkAble PAVA system – low Impedance slave unit
IDA8SL
17
IDA8 system
PartS inCluded
Quantities Components
1 IDA8SLxx Slave unit
1 Power cord
1 Set of mounting brackets for 19” rack
1 Set of connectors
1 Ateis Studio software GUI
teChniCal SPeCifiCationS
electrical
mains power supply
Voltage 115 or 230 VAC ±15%, 50/60 Hz
Power consumption 48 W
battery power supply
Voltage 18 - 26 VDC
Performance
Frequency response -3 dB @ 20 Hz and 20 kHz
line inputs
Connector SPEAKON(electronically balanced)
Frequency response -3 dB @ 20 Hz and 20 kHz
S/N > 90 dBA
THD < 0,1% @ 1 kHz
Input sensitivity 770 mV
Input impedance 20 kOhm
line outputs
Connector SPEAKON
S/N >-85 dBu
THD < 0,02% @ 1 kHz
Signal 770 m V
Output impedance < 300 Ohm
loudspeaker lines in 4 x
Rated load resistance 8 Ohm (100 W) RMS
Rated load capacitance 250 nF (100 V)
Rated output power(per channel)
100 W (cont. at 40°C) 1500 W Piek
loudspeaker lines out 4 x
Rated load resistance 8 Ohm (100 W) RMS
Rated output power(per channel)
100 W (cont. at 40°C) 1500 W Piek
mechanical
Dimensions (H x W x D)
for 19” rack use, with brackets
88 x 483 x 300 mm
19” ‘in-front’ brackets 40 mm
Weight
IDA8sl 4.2 kg (9.25 lb)
Mounting 19”- rackmount
Colour RAL7016
environmental
Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)
Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
ordering Information
IDA8sl-C1 Slave with NET-C1 card
IDA8sl-C1-Io Slave with NET-C1 card & 4 audio inputs & 4 audio outputs
IDA8sl-C1-2I Slave with NET-C1 card& 8 audio inputs
IDA8sl-C1-2o Slave with NET-C1 card & 8 audio outputs
CertifiCationS and aPProvalS
inStallation/Configuration noteS
1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz
2
3
4
5
6
7
8
9
10
11
•
•
region CertifiCationS
Europe CE
Immunity according to EN50103-4
PAVA EN54-16 certified 2012
ControlS and indiCatorS
Front
• Status LEDs
• Zone LEDs
• Power LEDs
rear
• Voltage selector
interConneCtionS
rear
• Mains input
• Battery backup input
• 9 control inputs
• 8 control outputs
• Optional: 4 analogue audio mic/line inputs
• Optional: 4 analogue audio line inputs
• 2 system LOCAL-network connections
• 4 low-impedance amplifier in and outputs
• 1 connection for back-up amplifiers
• 2 monitored paging console inputs
• 2 connections for back-up amplifiers
IDA8 NetworkAble PAVA system – low Impedance slave unit
IDA8SL
18
IDA8 system
1. System fault
2. General fault
3. Bypass mode
4. Bypass monitoring
5. Global EVAC
6. EVAC indicators
7. Power
8. Network
9. FAULT indicators
1. Backup amplifier output
2. Bypass mode outputs
3. PDC-ports for secured paging consoles
4. Local network card
5. Zone 1 Speaker line output
6. Zone 1 Amplifier output
7. Zone 1 amplifier input
8. Backup amplifier input
9. 8 Contact outputs
10. 9 Contact inputs
11. 24 VDC slave output
12. 24 VDC back-up input
13. AC power socket
IDA8 NetworkAble PAVA system – low Impedance slave unit
IDA8SL
IDA8 system
19
ATEIS NET SEcurEd AudIo NETwork cArd
NET-CX
ATEÏS Net™ is a secured (monitored) audio network developed for fast and low-latency audio and data transport over a redundant copper (CAT-5) or fibreoptic network ring. ATEÏS Net™ has an open-architec-ture design and interfaces with remote devices such as paging consoles, audio break-in and break-out convertors and room controllers. It is best suited to medium to large-scale installations, such as shop¬ping malls, retail stores, train stations and airports.
ATEÏS Net™ secured audio network responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.
funCtionS
ATEÏS Net™ is able to simultaneously transport 48 audio channels (32 bit, 48 kHz sampling rate) with a latency <1ms together with the necessary control data over a CAT-5 or fibreoptic dedicated network. For LOCAL and GLOBAL system networking, optional ATEÏS Net™ networking cards can be installed into the IDA8 Controller and Slave units. Thanks to its loop architecture, the ATEÏS Net™ audio network is fully redundant. If a problem (line open or shorted) occurs on a loop segment, it will be automatically isolated without affecting system functionality. One IDA8C Controller and up to 31 IDA8S Slaves can be connected together onto one LOCAL network. For systems of more than 32 units, or to link LOCAL networks, the GLOBAL network is used. Up to 32 IDA8C Controllers can be connected on the same GLOBAL network.
As network addresses are auto negotiated, network setup is very easy. Once programmed, the system will function independently without a PC having to be connected. IDA8C Controller units can be equipped with both LOCAL and GLOBAL network cards the communication network to be expanded up to 32 x 32 nodes.
NET-C1 cards (RJ45 to RJ45) are suitable for installation distances of up to 100m between Controller and Slave and/or Slave and Slave. For longer installation distances, optional NET-C2, C3 or C4 can be used to extend distances up to 2 km between units in multi-mode or 20 km in single-mode.
Main CharaCteriStiCS
• Ateis Net™ audio and data secured network
• Local-net & Global-net
• 32 x 32 - nodes in a combined network
• Low-latency <1ms
• 48-audio channels
• Redundant loop architecture
• 32 bit, 48 kHz sampling
• CAT-5 for up to 100 m
• Fibreoptic dual-mode for up to 2 km
• Fibreoptic single-mode for up to 20 km
• Dedicated network
• EN54-16 certified
NET-c1, 2x rJ45 Port A & Port B NET-c2, 1x rJ45 Port B & 1x fibre Port A
NET-c3, 2x fibre Port A & Port B
NET-c4, 1x fibre Port B & 1x rJ45 Port A
NotePort A = network INPort B = network OUT
IDA8 system
20
PartS inCluded
Quantities components
1Ateis Net™ secured audio network card
1Set of interconnecting ribbon cables
1 Set of mounting pillars
teChniCal SPeCifiCationS
Electrical
Battery power supply
Voltage Internal multi-power socket
Power consumption 5 W
Audio transport 48 channels
Performance
Frequency response -3 dB @ 20 Hz and 22 kHz
Sampling rate 32 bit / 48 kHz
Latency < 1 ms
Integrity assurance Watchdog
Indicators
LED Network active
LED Network present
Mechanical
Dimensions (H x W x D) 18 x 100 x 150 mm
Environmental
Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)
Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity 15% to 90%
Air pressure 600 to 1100 h Pa
ordering information
NET-c1, RJ45(A)/RJ45(B) (supplied as standard with IDA8 models)
NET-c2, ST Multi-mode Fibre (A)/RJ45(B) (Surcharge)
NET-c3, ST Multi-mode Fibre(A)/(B) (Surcharge)
NET-c4, RJ45(A)/ST Multi-mode Fibre(B) (Surcharge)
NET-c3S, ST Single-mode Fibre(A)/(B) (Surcharge)
SeCurity
In accordance with EN54-16, ISO 7240-16 and BS5839:pt8, all IDA8 system components and peripherals on the ATEÏS Net™ secured audio network are monitored and reports stored in the IDA8C system controller. The controller monitors the status of all the equipment in the system, reports status changes and stores fault messages for recall either on the controller front-panel display or through the ATEÏS Studio PC-based software.
inStallation noteS
ATEIS NET SEcurEd AudIo NETwork cArd
NET-CX
ControlS and indiCatorS
Front
• Data running indicator
• Net-work present indicator
interConneCtionS
Front
•Two system network connections either CAT5 or Fiber-optic or a combination
CertifiCationS and aPProvalS
inStallation/Configuration noteS
1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz
2
3
4
5
6
7
8
9
10
11
•
•
region CertifiCationS
Europe Certification CE – 0359 (Intertek)
Immunity according to EN50103-4
PAVA EN54-16 certified 2012
ATEÏS Studio
21
integrated operation software
ATEÏS Studio
ATEÏS Studio is a user-friendly graphic user interface designed for intuitive system setup. The PC-based software allows hardware updating, full system configuration and generates the user interface for day-to-day system operation.
graPhiCal uSer interfaCe
ATEÏS Studio allows complete PAVA/audio systems incorporating a range of devices to be configured, monitored and controlled centrally from a single user interface. ATEÏS Studio supports all IP-based products within the ATEÏS product family such as IDA8, LAP-AS and ECS. The software enables a comprehensive overview of the system and its virtual connections and also offers control and configuration for power amplifiers, paging consoles and remote controllers such as PSS-AS, CD16-AS and URC-AS devices.
diagnoSting
ATEÏS Studio monitors, controls, logs and reports a range of events. The whole system configuration preset can be stored and reloaded at the press of a button, depending on application. Users can tailor design elements of the graphic user interface or control panels, as well as program automatic sequences of events and create different levels of user access for security and rights management.
Building
ATEÏS Studio provides a complete set of tools and building blocks for real-time control, monitoring and design of an audio system or Voice Evacuation system from paging console to loudspeaker. Detailed information such as signal levels, loudspeaker impedance, pre-recorded messages, amplifier conditions and other parameters can be monitored in real-time.
A comprehensive library of tools, control and monitoring elements is provided along with the GUI, including items such as volume control faders, metering, high-level EQ, compression, limiting, auto-gain, noise sensing, mixing, shortcut buttons and display elements. Element behaviour can be fully tailored to suit each application. Built-in file transfer software transfers both data and audio files from the PC to the network controller.
Configuration Software
• Runs on Windows
• Assignable access levels with rights management
• All system and unit parameters can be configured
• Easy navigation
diagnoStiC and logging Software
• Call, fault and general event logging
• On-line logging function
• Historical logging
• Event display priority can be changed
• Password-protected
file tranSfer Software
• PC-based application
• Supplied together with the network controller
• Creation of message sets
• Off-line configuration
ATEÏS Studio
22
aCCeSS levelS
Additional security can be added to the software with password-protected layers according to EN 54-16. Multiple users can be created and assigned, each with a unique password and access to specific layers of the GUI. This creates a control surface specific to the needs of system designers and operators at multiple levels.
integrated operation software
ATEÏS Studio
Del iver ing Your Message
Public Address - Voice Alarm
Audio Distribution over IP
Commercial Audio
Intelligent Acoustic Solutions
Intercommunication
Loudspeakers
ATEÏS Europe B.V. Sydneystraat 42 - 3047 BP - ROTTERDAM - NETHERLANDS
Phone: +31 (0)10 2088690 - Fax: +31 (0)10 [email protected]
ATEÏ
S re
serv
e th
e rig
ht to
cha
nge
spec
ifica
tions
with
out n
otic
eHE
LPRO
D.CO
M -
Pro
duct
pic
ture
s, R
ober
t Pee
k Fo
togr
afie
- F
otol
ia
IDA8S
Networkable PAVA system Slave Unit
IDA8SAB
Networkable PAVA system Slave Unit – A/B-zoning
IDA8SL
Networkable PAVA system Low impedance Slave Unit