IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and...

24
Public Address - Voice Alarm Audio Distribution over IP Commercial Audio Intelligent Acoustic Solutions Intercommunication Loudspeakers IDA8 System IDA8C Networkable PAVA system Controller Unit IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240- 16 and BS5839/8, with specific attributes for compliance in large installations.

Transcript of IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and...

Page 1: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

Public Address - Voice Alarm

Audio Distribution over IP

Commercial Audio

Intelligent Acoustic Solutions

Intercommunication

Loudspeakers

IDA8 System

IDA8C

Networkable PAVA system Controller Unit

IDA8 is a third-generation modular

system that complies with current

architectural demands requiring

IP and/or fibreoptic networking to

allow for even the most complex of

system designs.

IDA8 responds to Public Address

and Voice Alarm requirements

as stated in EN54-16, ISO 7240-

16 and BS5839/8, with specific

attributes for compliance in large

installations.

Page 2: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

Del iver ing Your Message

Page 3: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

3

IDA8 system

IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.

ConneCtivity:

The IDA8C Controller unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, with front panel access for a fully monitored fireman’s microphone and emergency message trigger buttons. IDA8C also supports amplifier monitoring with hot-swap amplifiers and loudspeaker line impedance monitoring. It can support up to four PSS-AS monitored microphone consoles and up to eight monitored amplifiers plus two back-up amplifiers, paging into 8 different zones per unit with A/B line detection according to BS5939 part 8. Two card slots are provided for either 4-channel 0dB audio input or 4-channel audio cards. Optional AES/EBU cards are also available.

Each IDA8C input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines. Up to 4 hours of digital messaging (WAV format) can be stored for live or pre-recorded playback. Digital audio files are uploaded from a computer to the IDA8S through the user-friendly ATEÏS Studio GUI. Several messages can be played simultaneously into different zones: up to 4 messages from a single IDA8C Controller or a total of 48 messages across an IDA8 system (controller with slaves). A built-in loudspeaker on the IDA8C allows selective feedback for all sources and 100V output signals.

IDA8S Slave units can extend the system configuration with an additional 8 inputs and 8 outputs and 2 back-up amplifiers. The slave units are available as single zone (IDA8S) or with A/B speaker line configurations (IDA8SAB), or for Low-impedance monitoring (IDA8SL).

The IDA8C Controller unit enables operators to see a detailed overview of the operational status of the entire PA system at the press of a button. It is able to run an impedance scan of all components connected to it, covering not only the input paging consoles but also connectors, cabling, processing blocks such as compressors and limiters, delay lines, the network and loudspeakers.

The IDA8C Controller operates either on mains power or on a 24V battery power supply for emergency back-up, with automatic switchover. Both power supplies are monitored. IDA8C is easily configured using the PC-based ATEÏS Studio global software. Once programmed, the system will operate independently (off-line) without a PC having to be connected.

SeCurity

In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally-generated pilot tone is available for monitoring impedance on the loudspeaker lines.

The system can handle 256 priorities for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements. The controller monitors the status of all the equipment in the system, reports status changes and logs the last 999 fault messages in the system. The log can be accessed on the front-panel IDA8C display or on a PC through ATEÏS Studio. The IDA8C system (controller and slaves) supports redundant network cabling, wired as a redundant loop.

Main CharaCteriStiCS

•Public address and emergency sound system control unit

•Fully digital with 8 audio inputs and 8 audio outputs

•4 dedicated and monitored PDC-ports for firemen’s microphones

•2 dedicated audio in and outputs for back-up amplifiers

•Enhanced loudspeaker line surveillance for AB-zoned installation

•Simultaneous control and routing of 48 audio channels over dedicated network

•Equiped as standard with RJ45 network cards (NET-C1) for links up to 100 m

• Optional Fibreoptic cards for links up to 20 km

•9 supervised control inputs and 8 control outputs

•Ethernet interface for configuration, control, diagnostics and logging

•Digital storage for up to 4 hours of prerecorded messages

• 4 message players

• Stores the last 999 fault events

• EN54-16 certified

Networkable PaVa system – CoNtroller UNIt

IDA8C

Page 4: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

IDA8 system

4

inStallation noteS

Networkable PaVa system – CoNtroller UNIt

IDA8C

Page 5: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

5

IDA8 system

PartS inCluded

Quantities Components

1 IDA8Cxx Controller unit

1 Power cord

1 Set of mounting brackets for 19” rack

1 Set of connectors

1 Ateis Studio software GUI

teChniCal SPeCifiCationS

electrical

mains power supply

Voltage 115 or 230 VAC ±15%, 50/60 Hz

Power consumption 48 W

battery power supply

Voltage 18 - 26 VDC

Performance

Frequency response -3 dB @ 20 Hz and 20 kHz

line inputs (optional audio input card)

Connector 3-pin phoenix

Frequency response -3 dB @ 20 Hz and 20 kHz

S/N >90 dBA

THD < 0,1% @ 1 kHz

Input sensivity 770 mV

Input impedance 20 kohm

line outputs (optional audio output card)

Connector 3-pin phoenix

S/N >-85 dBu

THD < 0,02% @ 1 kHz

Signal 770 mV

Output impedance <300 ohm

loudspeaker lines in 8 x 100 V

Rated load resistance 20 ohm (100 V)

Rated load capacitance 250 nF (100 V)

Rated output power(per channel)

500 W (cont. at 40°C)

loudspeaker lines out 8 x (a+b)

Rated load resistance 20 ohm (100 V)

Rated load capacitance 250 nF (100 V)

Rated output power(per channel) 500 W (cont. at 40°C)

mechanical

Dimensions (H x W x D)

With 19” rackmount brackets 88 x 483 x 305 mm

Weight 5.36 kg (11,8lb)

Mounting 19”-rackmount

Colour RAL7016

environmental

Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)

Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)

Relative humidity 15% to 90%

Air pressure 600 to 1100 h Pa

ordering Information

IDa8C-C1-Io Controller with NET-C1 card & 4 audio inputs & 4 audio outputs

IDa8C-C1-2I Controller with NET-C1 card & 8 audio inputs

CertifiCationS and aPProvalS

inStallation/Configuration noteS

1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz

2

3

4

5

6

7

8

9

10

11

region CertifiCationS

Europe CE CE – 0359 (Intertek)

Immunity according to EN50103-4

PAVA EN54-16 certified 2012

ControlS and indiCatorS

Front

• 3,5” full colour touch-screen LCD display

• Zone selection buttons

• EVAC-start

• Fireman’s microphone

• Status indicators

rear

• Voltage selector

interConneCtionS

Front

• Firemen’s microphone

rear

• Mains input

• Battery backup input

• 9 control inputs

• 8 control outputs

• 4 analogue audio mic/line inputs

• 4 analogue audio line inputs

• Ethernet

• LOCAL network in/out card

• Free slot for GLOBAL-network card

• 8 amplifier in and outputs

• 2 connections for back-up amplifiers

• 4 monitored paging console inputs

Networkable PaVa system – CoNtroller UNIt

IDA8C

Page 6: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

6

IDA8 system

1. Fireman microphone active

2. Fireman microphone input

3. Fireman microphone hook

4. Monitoring loudspeaker (Audible warning)

5. Bypass mode

6. General fault

7. System fault

8. Global EVAC

9. Bypass monitoring

10. 3.5” Touch screen

11. ESC - button

12. OK button

13. Up button

14. Down button

15. Plus button

16. Minus button

17. EVAC indicators

18. FAULT indicators

19. RESET button

20. Power

21. Network

22. EVAC button

1. Speaker zone outputs (A+B)

2. Back-up amplifiers (2x)

3. Amplifier 0dB line outputs

4. Bypass mode contact input

5. EVAC and GF output contact

6. PDC-ports for secured paging con-soles

7. Ethernet

8. Local network card

9. Global network card

10. Audio I/O

11. Telephone line input

12. Telephone controller

13. Bypass mode outputs

14. Contact outputs, 8x

15. Contact inputs, 9x

16. 24VDC slave output

17. 24VDC back-up input

18. AC power socket

Networkable PaVa system – CoNtroller UNIt

IDA8C

Page 7: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

7

IDA8 system

IDA8 NetworkAble PAVA system – slAVe UNIt

IDA8S

IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.

ConneCtivity:

The IDA8S Slave unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, along with amplifier monitoring for hot-swap amplifiers and loudspeaker line impedance monitoring. It can support up to two PSS-AS monitored microphone consoles and up to eight monitored amplifiers plus two backup amplifiers, paging into 8 different zones per unit with line detection. Two card slots can fitted with optional 4-channel analogue audio input/outputs cards or 4-channel audio AES/EBU cards (max two cards per device).

IDA8S Slave units extend the IDA8 system configuration with an additional 8 output zones and 2 back-up amplifiers. Each input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines. Up to 4 hours of digital messaging (WAV format) can be stored for live or pre-recorded playback. Digital audio files are uploaded from a computer to the IDA8S through the user-friendly ATEÏS Studio GUI. Several messages can be played simultaneously into different zones: up to 4 messages from a single IDA8S Slave or a total of 48 messages across an IDA8 system (controller with slaves).

The IDA8S Slave operates either on mains power or on a 24V battery power supply for emergency back-up, with automatic switchover. Both power supplies are monitored. The IDA8S Slave also supports redundant loop network cabling. IDA8S is easily configured using the PC-based ATEÏS Studio global software. Once programmed, the system will operate independently (off-line) without a PC having to be connected.

SeCurity

In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally-generated pilot tone is available for monitoring impedance on the loudspeaker lines.

The system can handle 256 priorities for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements. The controller monitors the status of all the equipment in the system, reports status changes and logs error details. The log can be accessed on the front-panel IDA8C display or on a PC through ATEÏS Studio.

Main CharaCteriStiCS

•Public address and emergency sound system slave unit

•Fully digital with Optional: 8 audio inputs and 8 audio outputs

•2 dedicated audio in and outputs for back-up amplifiers

•2 dedicated and monitored PDC-ports for fireman’s microphones

•Enhanced loudspeaker line surveillance for zoned installations

•Simultaneous control and routing of 48 audio channels over dedicated network

•Equipped as standard with RJ45 network cards for links up to 100m

• Optional Fibreoptic cards for links up to 20 km

•9 supervised control inputs and 8 control outputs

•Ethernet interface for configuration, control, diagnostics and logging

•Digital storage for up to 4 hours of pre-recorded messages

• 4 message players

• EN54-16 certified

Page 8: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

IDA8 system

8

IDA8 NetworkAble PAVA system – slAVe UNIt

IDA8S

inStallation noteS

Page 9: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

9

IDA8 system

PartS inCluded

Quantities Components

1 IDA8Sxx Slave unit

1 Power cord

1 Set of mounting brackets for 19” rack

1 Set of connectors

1 Ateis Studio software GUI

teChniCal SPeCifiCationS

electrical

mains power supply

Voltage 115 or 230 VAC ±15%, 50/60 Hz

Power consumption 48 W

battery power supply

Voltage 18 - 26 VDC

Performance

Frequency response -3 dB @ 20 Hz and 20 kHz

line inputs (optional input card)

Connector 3-pin phoenix (electronically balanced)

Frequency response +/-3 dB @ 20 Hz and 20 kHz

S/N >90 dBA

THD < 0,1% @ 1 kHz

Input sensitivity 770 mV

Input impedance 20 kOhm

line outputs (optional output card)

Connector 3-pin phoenix

S/N >-85 dBu

THD < 0,02% @ 1 kHz

Signal 770 mV

Output impedance < 300 Ohm

loudspeaker lines in 8 x 100 V

Rated load resistance 20 ohm (100 V)

Rated load capacitance 250 nF (100 V)

Rated output power(per channel)

500 W (cont. at 40°C)

loudspeaker lines out 8 x

Rated load resistance 20 ohm (100 V)

Rated load capacitance 250 nF (100 V)

Rated output power(per channel) 500 W (cont. at 40°C)

IDA8 NetworkAble PAVA system – slAVe UNIt

IDA8S

mechanical

Dimensions (H x W x D)

for 19” rack use, with brackets

88 x 483 x 285 mm

Weight

IDA8s 4.2 kg (9.25 lb)

Mounting 19”-rackmount

Colour RAL7016

environmental

Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)

Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)

Relative humidity 15% to 90%

Air pressure 600 to 1100 h Pa

ordering Information

IDA8s-C1 Slave with NET-C1 card

IDA8s-C1-Io Slave with NET-C1 card & 4 audio inputs & 4 audio outputs

IDA8s-C1-2I Slave with NET-C1 card & 8 audio inputs

IDA8s-C1-2o Slave with NET-C1 card & 8 audio outputs

CertifiCationS and aPProvalS

inStallation/Configuration noteS

1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz

2

3

4

5

6

7

8

9

10

11

region CertifiCationS

Europe CE CE – 0359 (Intertek)

Immunity according to EN50103-4

PAVA EN54-16 certified 2012

ControlS and indiCatorS

Front

• Status LEDs

• Zone LEDs

• Power LEDs

rear

• Voltage selector

interConneCtionS

rear

• Mains input

• Battery backup input

• 9 control inputs

• 8 control outputs

• Optional 4 analogue audio mic/line inputs

• Optional 4 analogue line audio inputs

• 2 system LOCAL-network connections

• 8 amplifier in and outputs

• 2 connections for back-up amplifiers

Page 10: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

10

IDA8 system

1. System fault

2. General fault

3. Bypass mode

4. Bypass monitoring

5. Global EVAC

6. EVAC indicators

7. Power

8. Network

9. FAULT indicators

1. Speaker zone outputs (8x)

2. Back-up amplifiers (2x)

3. Amplifier 0dB line outputs

4. Bypass mode outputs

5. PDC-ports for secured paging consoles

6. Local network card

7. Audio I/O (Optional)

8. 8 Contact outputs

9. 9 Contact inputs

10. 24 VDC input

11. 24 VDC back-up input

IDA8 NetworkAble PAVA system – slAVe UNIt

IDA8S

Page 11: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

11

IDA8 system

IDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg

IDA8SAB

IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.

ConneCtivity:

The IDA8SAB Slave unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, along with amplifier monitoring with hot-swap amplifiers and loudspeaker line-impedance line monitoring. It can support up to two PSS-AS monitored microphone consoles, up to eight monitored amplifiers plus two backup amplifiers and paging into 8 different zones per unit with A/B line detection according to the BS 5939-part 8. Two rear card slots can be fitted with optional 4-channel analogue audio in/output cards 4 channel AES/EBU cards for digital audio in/out.

IDA8SAB Slave units can extend the IDA8 system configuration with an additional 8 output zones and 2 back-up amplifiers. Up to 4 hours of digital messaging can be stored in the unit for live or scheduled playback. Files are uploaded in WAV format from a computer using the ATEÏS Studio system GUI. Several messages can be played simultaneously into different zones: up to 4 from a single IDA8SAB or a total of 48 messages across a full IDA8 system with slaves.

Each input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines.

IDA8SAB is easily configured with PC-based ATEÏS Studio global software. Once programmed, the system will run independently without a PC connected. The IDA8SAB Slave operates either on AC mains power or on a 24V DC battery power supply for emergency back-up, with automatic switchover. Both of the power supplies are monitored

SeCurity

In accordance with EN54-16, ISO 7240-16 and BS5839:pt8, all system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally generated pilot tone is available for monitoring impedance on the loudspeaker lines. The IDA8SL Slave supports redundant network cabling as a redundant loop. The system can handle 256 priorities, for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements.

Main CharaCteriStiCS

•Public address and emergency sound system slave unit

•Fully digital with up to 8 audio inputs and outputs (optional)

•2 dedicated and monitored PDC-ports for fire-man’s microphones

•2 dedicated audio in and outputs for back-up amplifiers

•Enhanced loudspeaker line surveillance for AB-zoned installations

•Simultaneous control and routing of 48 audio channels over dedicated network

•Equipped as standard with RJ45 network cards for links up to 100 m

• Optional fibreoptic cards for links up to 20 km

• 9 supervised control inputs and 8 control outputs

•Ethernet interface for configuration, control, diagnostics and logging

•Digital storage for up to 4 hours of pre-recorded messages

• 4 message players

• EN54-16 certified

Page 12: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

IDA8 system

12

inStallation noteS

IDA8SABIDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg

Page 13: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

13

IDA8 system

PartS inCluded

Quantities Components

1 IDA8SAB Slave unit

1 Power cord

1 Set of mounting brackets for 19” rack

1 Set of connectors

1 Ateis Studio software GUI

teChniCal SPeCifiCationS

electrical

mains power supply

Voltage 115 or 230 VAC ±15%, 50/60 Hz

Power consumption 48 W

battery power supply

Voltage 18 - 26 VDC

Performance

Frequency response -3 dB @ 20 Hz and 20 kHz

line inputs (oPtIoNAl)

Connector 3-pin phoenix (electronically balanced)

Frequency response +/-3 dB @ 20 Hz and 20 kHz

S/N > 90 dBA

THD < 0,1% @ 1 kHz

Input sensitivity 770 mV

Input impedance 20 kohm

line outputs (oPtIoNAl)

Connector 3-pin phoenix

S/N > -85 dBu

THD < 0,02% @ 1 kHz

Signal 770 mV

Output impedance < 300 Ohm

loudspeaker lines in 8 x 100 V

Rated load resistance 20 ohm (100 V)

Rated load capacitance 250 nF (100 V)

Rated output power(per channel)

500 W (cont. at 40°C)

loudspeaker lines out 8x (A+b)

Rated load resistance 20 ohm (100 V)

Rated load capacitance 250 nF (100 V)

Rated output power(per channel) 500 W (cont. at 40°C)

mechanical

Dimensions (H x W x D)

(including rackmount brackets) 2U, 88 x 483 x 289 mm

Weight

IDA8sAb 5 kg (11 lb)

Mounting 19”-rackmount

Colour RAL7016

environmental

Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)

Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)

Relative humidity 15% to 90%

Air pressure 600 to 1100 h Pa

ordering Information

IDA8sAb-C1 Slave with NET-C1 card

IDA8sAb-C1-Io Slave with NET-C1 card & 4 audio inputs & 4 audio outputs

IDA8sAb-C1-2I Slave with NET-C1 card & 8 audio inputs

IDA8sAb-C1-2o Slave with NET-C1 card & 8 audio outputs

CertifiCationS and aPProvalS

inStallation/Configuration noteS

1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz

2

3

4

5

6

7

8

9

10

11

region CertifiCationS

Europe CE CE – 0359 (Intertek)

Immunity according to EN50103-4

PAVA EN54-16 certified 2012

ControlS and indiCatorS

Front

• Status LEDs

• Zone LEDs

• Power LEDs

rear

• Voltage selector

interConneCtionS

rear

• Mains input

• Battery backup input

• 9 control inputs

• 8 control outputs

• 4 analogue audio mic/line inputs (optional)

• 4 analogue audio line inputs (optional)

• 2 system LOCAL-network connections

• 8 amplifier in and outputs

• 2 connections for back-up amplifiers

• 2 monitored paging console inputs

IDA8SABIDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg

Page 14: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

14

IDA8 system

1. System fault

2. General fault

3. Bypass mode

4. Bypass monitoring

5. Global EVAC

6. EVAC indicators

7. Power

8. Network

9. FAULT indicators

1. Speaker zone outputs (A+B)

2. 2 Back-up amplifier outputs

3. Amplifier 0dB line outputs

4. Bypass mode outputs

5. PDC-ports for secured paging consoles

6. Local network card

7. Audio I/O (optional)

8. Telephone line input

9. Telephone controller

10. 8 Contact outputs

11. 9 Contact inputs

12. 24 VDC slave output

13. 24 VDC back-up input

14. AC power socket

IDA8SABIDA8 NetworkAble PAVA system – slAVe UNIt – A/b zoNINg

Page 15: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

15

IDA8 system

IDA8 NetworkAble PAVA system – low Impedance slave unit

IDA8SL

IDA8 is a third-generation modular system that complies with current architectural demands requiring IP and/or fibreoptic networking to allow for even the most complex of system designs. IDA8 responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.

ConneCtivity:

The IDA8SL Low-Impedance Slave unit houses advanced audio digital signal processing (DSP), matrix control functions and a digital message player, along with amplifier monitoring with hot-swap amplifiers and low-impedance line monitoring. It can support up to two PSS-AS monitored microphone consoles, up to four monitored amplifiers plus two backup amplifiers and paging into 4 different zones per unit with line detection. Each input and output channel is fitted with a wide range of pre-and post-processing devices such as volume controllers, routing mixers and switches, priority and paging components, equalisers, compressors, limiters and delay-lines.

IDA8SL Slave units can extend the IDA8 system configuration with an additional 4 output zones and 2 back-up amplifiers. Up to 4 hours of digital messaging can be stored in the unit for live or scheduled playback. Files are uploaded in WAV format from a computer using the ATEÏS Studio system GUI. Several messages can be played simultaneously into different zones: up to 4 from a single IDA8SL or a total of 48 messages across a full IDA8 system with slaves.

IDA8SL is easily configured with PC-based ATEÏS Studio global software. Once programmed, the system will run independently without a PC connected. The IDA8SL-Slave operates either on AC mains power or on a 24V DC battery power supply for emergency back-up, with automatic switchover. Both of the power supplies are monitored.

SeCurity

In accordance with EN54-16, ISO 7240-16 and BS5839:pt8, all system components and peripherals are monitored. This monitoring extends from the capsule of a paging station microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally generated pilot tone is available for monitoring impedance on the loudspeaker lines. The IDA8SL Slave supports redundant network cabling as a redundant loop. The system can handle 256 priorities, for calls to hundreds of zones, satisfying even the most complex public address and emergency requirements.

Main CharaCteriStiCS

•Public address and emergency sound system slave unit

•Fully digital with: 8 audio inputs and 8 audio outputs

•Two dedicated and monitored PDC-ports for firemen’s microphones

•2 dedicated audio in and outputs for back-up amplifiers

•Enhanced loudspeaker line surveillance for low-impedance installations

•Simultaneous control and routing of 48 audio channels over dedicated network

•Equipped as standard with RJ45 network cards for links up to 100 m

• Optional Fiberoptic cards for links up to 20 km

•9 supervised control inputs and 8 control outputs

•Ethernet interface for configuration, control, diagnostics and logging

•Digital storage for up to 4 hours of pre-recorded messages

• 4 message players

• EN54-16 certified

Page 16: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

IDA8 system

16

inStallation noteS

IDA8 NetworkAble PAVA system – low Impedance slave unit

IDA8SL

Page 17: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

17

IDA8 system

PartS inCluded

Quantities Components

1 IDA8SLxx Slave unit

1 Power cord

1 Set of mounting brackets for 19” rack

1 Set of connectors

1 Ateis Studio software GUI

teChniCal SPeCifiCationS

electrical

mains power supply

Voltage 115 or 230 VAC ±15%, 50/60 Hz

Power consumption 48 W

battery power supply

Voltage 18 - 26 VDC

Performance

Frequency response -3 dB @ 20 Hz and 20 kHz

line inputs

Connector SPEAKON(electronically balanced)

Frequency response -3 dB @ 20 Hz and 20 kHz

S/N > 90 dBA

THD < 0,1% @ 1 kHz

Input sensitivity 770 mV

Input impedance 20 kOhm

line outputs

Connector SPEAKON

S/N >-85 dBu

THD < 0,02% @ 1 kHz

Signal 770 m V

Output impedance < 300 Ohm

loudspeaker lines in 4 x

Rated load resistance 8 Ohm (100 W) RMS

Rated load capacitance 250 nF (100 V)

Rated output power(per channel)

100 W (cont. at 40°C) 1500 W Piek

loudspeaker lines out 4 x

Rated load resistance 8 Ohm (100 W) RMS

Rated output power(per channel)

100 W (cont. at 40°C) 1500 W Piek

mechanical

Dimensions (H x W x D)

for 19” rack use, with brackets

88 x 483 x 300 mm

19” ‘in-front’ brackets 40 mm

Weight

IDA8sl 4.2 kg (9.25 lb)

Mounting 19”- rackmount

Colour RAL7016

environmental

Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)

Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)

Relative humidity 15% to 90%

Air pressure 600 to 1100 h Pa

ordering Information

IDA8sl-C1 Slave with NET-C1 card

IDA8sl-C1-Io Slave with NET-C1 card & 4 audio inputs & 4 audio outputs

IDA8sl-C1-2I Slave with NET-C1 card& 8 audio inputs

IDA8sl-C1-2o Slave with NET-C1 card & 8 audio outputs

CertifiCationS and aPProvalS

inStallation/Configuration noteS

1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz

2

3

4

5

6

7

8

9

10

11

region CertifiCationS

Europe CE

Immunity according to EN50103-4

PAVA EN54-16 certified 2012

ControlS and indiCatorS

Front

• Status LEDs

• Zone LEDs

• Power LEDs

rear

• Voltage selector

interConneCtionS

rear

• Mains input

• Battery backup input

• 9 control inputs

• 8 control outputs

• Optional: 4 analogue audio mic/line inputs

• Optional: 4 analogue audio line inputs

• 2 system LOCAL-network connections

• 4 low-impedance amplifier in and outputs

• 1 connection for back-up amplifiers

• 2 monitored paging console inputs

• 2 connections for back-up amplifiers

IDA8 NetworkAble PAVA system – low Impedance slave unit

IDA8SL

Page 18: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

18

IDA8 system

1. System fault

2. General fault

3. Bypass mode

4. Bypass monitoring

5. Global EVAC

6. EVAC indicators

7. Power

8. Network

9. FAULT indicators

1. Backup amplifier output

2. Bypass mode outputs

3. PDC-ports for secured paging consoles

4. Local network card

5. Zone 1 Speaker line output

6. Zone 1 Amplifier output

7. Zone 1 amplifier input

8. Backup amplifier input

9. 8 Contact outputs

10. 9 Contact inputs

11. 24 VDC slave output

12. 24 VDC back-up input

13. AC power socket

IDA8 NetworkAble PAVA system – low Impedance slave unit

IDA8SL

Page 19: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

IDA8 system

19

ATEIS NET SEcurEd AudIo NETwork cArd

NET-CX

ATEÏS Net™ is a secured (monitored) audio network developed for fast and low-latency audio and data transport over a redundant copper (CAT-5) or fibreoptic network ring. ATEÏS Net™ has an open-architec-ture design and interfaces with remote devices such as paging consoles, audio break-in and break-out convertors and room controllers. It is best suited to medium to large-scale installations, such as shop¬ping malls, retail stores, train stations and airports.

ATEÏS Net™ secured audio network responds to Public Address and Voice Alarm requirements as stated in EN54-16, ISO 7240-16 and BS5839/8, with specific attributes for compliance in large installations.

funCtionS

ATEÏS Net™ is able to simultaneously transport 48 audio channels (32 bit, 48 kHz sampling rate) with a latency <1ms together with the necessary control data over a CAT-5 or fibreoptic dedicated network. For LOCAL and GLOBAL system networking, optional ATEÏS Net™ networking cards can be installed into the IDA8 Controller and Slave units. Thanks to its loop architecture, the ATEÏS Net™ audio network is fully redundant. If a problem (line open or shorted) occurs on a loop segment, it will be automatically isolated without affecting system functionality. One IDA8C Controller and up to 31 IDA8S Slaves can be connected together onto one LOCAL network. For systems of more than 32 units, or to link LOCAL networks, the GLOBAL network is used. Up to 32 IDA8C Controllers can be connected on the same GLOBAL network.

As network addresses are auto negotiated, network setup is very easy. Once programmed, the system will function independently without a PC having to be connected. IDA8C Controller units can be equipped with both LOCAL and GLOBAL network cards the communication network to be expanded up to 32 x 32 nodes.

NET-C1 cards (RJ45 to RJ45) are suitable for installation distances of up to 100m between Controller and Slave and/or Slave and Slave. For longer installation distances, optional NET-C2, C3 or C4 can be used to extend distances up to 2 km between units in multi-mode or 20 km in single-mode.

Main CharaCteriStiCS

• Ateis Net™ audio and data secured network

• Local-net & Global-net

• 32 x 32 - nodes in a combined network

• Low-latency <1ms

• 48-audio channels

• Redundant loop architecture

• 32 bit, 48 kHz sampling

• CAT-5 for up to 100 m

• Fibreoptic dual-mode for up to 2 km

• Fibreoptic single-mode for up to 20 km

• Dedicated network

• EN54-16 certified

NET-c1, 2x rJ45 Port A & Port B NET-c2, 1x rJ45 Port B & 1x fibre Port A

NET-c3, 2x fibre Port A & Port B

NET-c4, 1x fibre Port B & 1x rJ45 Port A

NotePort A = network INPort B = network OUT

Page 20: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

IDA8 system

20

PartS inCluded

Quantities components

1Ateis Net™ secured audio network card

1Set of interconnecting ribbon cables

1 Set of mounting pillars

teChniCal SPeCifiCationS

Electrical

Battery power supply

Voltage Internal multi-power socket

Power consumption 5 W

Audio transport 48 channels

Performance

Frequency response -3 dB @ 20 Hz and 22 kHz

Sampling rate 32 bit / 48 kHz

Latency < 1 ms

Integrity assurance Watchdog

Indicators

LED Network active

LED Network present

Mechanical

Dimensions (H x W x D) 18 x 100 x 150 mm

Environmental

Operating temperature -5 ºC to +55 ºC (+23 ºF to +131 ºF)

Storage temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)

Relative humidity 15% to 90%

Air pressure 600 to 1100 h Pa

ordering information

NET-c1, RJ45(A)/RJ45(B) (supplied as standard with IDA8 models)

NET-c2, ST Multi-mode Fibre (A)/RJ45(B) (Surcharge)

NET-c3, ST Multi-mode Fibre(A)/(B) (Surcharge)

NET-c4, RJ45(A)/ST Multi-mode Fibre(B) (Surcharge)

NET-c3S, ST Single-mode Fibre(A)/(B) (Surcharge)

SeCurity

In accordance with EN54-16, ISO 7240-16 and BS5839:pt8, all IDA8 system components and peripherals on the ATEÏS Net™ secured audio network are monitored and reports stored in the IDA8C system controller. The controller monitors the status of all the equipment in the system, reports status changes and stores fault messages for recall either on the controller front-panel display or through the ATEÏS Studio PC-based software.

inStallation noteS

ATEIS NET SEcurEd AudIo NETwork cArd

NET-CX

ControlS and indiCatorS

Front

• Data running indicator

• Net-work present indicator

interConneCtionS

Front

•Two system network connections either CAT5 or Fiber-optic or a combination

CertifiCationS and aPProvalS

inStallation/Configuration noteS

1Audio outputs: maximum level + 5 dB, bandwidth 20 Hz - 20 kHz

2

3

4

5

6

7

8

9

10

11

region CertifiCationS

Europe Certification CE – 0359 (Intertek)

Immunity according to EN50103-4

PAVA EN54-16 certified 2012

Page 21: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

ATEÏS Studio

21

integrated operation software

ATEÏS Studio

ATEÏS Studio is a user-friendly graphic user interface designed for intuitive system setup. The PC-based software allows hardware updating, full system configuration and generates the user interface for day-to-day system operation.

graPhiCal uSer interfaCe

ATEÏS Studio allows complete PAVA/audio systems incorporating a range of devices to be configured, monitored and controlled centrally from a single user interface. ATEÏS Studio supports all IP-based products within the ATEÏS product family such as IDA8, LAP-AS and ECS. The software enables a comprehensive overview of the system and its virtual connections and also offers control and configuration for power amplifiers, paging consoles and remote controllers such as PSS-AS, CD16-AS and URC-AS devices.

diagnoSting

ATEÏS Studio monitors, controls, logs and reports a range of events. The whole system configuration preset can be stored and reloaded at the press of a button, depending on application. Users can tailor design elements of the graphic user interface or control panels, as well as program automatic sequences of events and create different levels of user access for security and rights management.

Building

ATEÏS Studio provides a complete set of tools and building blocks for real-time control, monitoring and design of an audio system or Voice Evacuation system from paging console to loudspeaker. Detailed information such as signal levels, loudspeaker impedance, pre-recorded messages, amplifier conditions and other parameters can be monitored in real-time.

A comprehensive library of tools, control and monitoring elements is provided along with the GUI, including items such as volume control faders, metering, high-level EQ, compression, limiting, auto-gain, noise sensing, mixing, shortcut buttons and display elements. Element behaviour can be fully tailored to suit each application. Built-in file transfer software transfers both data and audio files from the PC to the network controller.

Configuration Software

• Runs on Windows

• Assignable access levels with rights management

• All system and unit parameters can be configured

• Easy navigation

diagnoStiC and logging Software

• Call, fault and general event logging

• On-line logging function

• Historical logging

• Event display priority can be changed

• Password-protected

file tranSfer Software

• PC-based application

• Supplied together with the network controller

• Creation of message sets

• Off-line configuration

Page 22: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

ATEÏS Studio

22

aCCeSS levelS

Additional security can be added to the software with password-protected layers according to EN 54-16. Multiple users can be created and assigned, each with a unique password and access to specific layers of the GUI. This creates a control surface specific to the needs of system designers and operators at multiple levels.

integrated operation software

ATEÏS Studio

Page 23: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

Del iver ing Your Message

Page 24: IDA8 System · In accordance with EN54-16, ISO 7240-16 and BS5839/8, all IDA8 system components and peripherals are monitored. This monitoring extends from the capsule of a paging

Public Address - Voice Alarm

Audio Distribution over IP

Commercial Audio

Intelligent Acoustic Solutions

Intercommunication

Loudspeakers

ATEÏS Europe B.V. Sydneystraat 42 - 3047 BP - ROTTERDAM - NETHERLANDS

Phone: +31 (0)10 2088690 - Fax: +31 (0)10 [email protected]

ATEÏ

S re

serv

e th

e rig

ht to

cha

nge

spec

ifica

tions

with

out n

otic

eHE

LPRO

D.CO

M -

Pro

duct

pic

ture

s, R

ober

t Pee

k Fo

togr

afie

- F

otol

ia

IDA8S

Networkable PAVA system Slave Unit

IDA8SAB

Networkable PAVA system Slave Unit – A/B-zoning

IDA8SL

Networkable PAVA system Low impedance Slave Unit