ICS Series 5-15 Ton Indoor Ducted Air-Cooled Water … · 1 General Product Data Model ICS 060 ICS...

12
General Product Data Model ICS 060 ICS 120 ICS 180 Nominal Tons 5 10 15 Gross Cooling Capacity 58,000 Btuh 116,000 Btuh 174,000 Btuh Compressor(s) 1 Scroll 2 Scrolls 3 Scrolls Condenser Coil(s) (1) 46" x 20" (2) 46" x 20" (3) 46" x 20" Face Area (Sq. Ft.) 6.3 12.6 18.9 Rows / Fins Per Inch 4 / 14 4 / 14 4 / 14 Condenser Fan(s) (1) 15" x 10" FC (2) 15" x 12" FC (2) 15" x 15" FC Nominal Air Flow (CFM) 3,300 6,600 9,900 Standard Motor (HP) (1) 2 HP (1) 3 HP (1) 5 HP Motor Speed (RPM) 1750 RPM 1750 RPM 1750 RPM Drive Type V-Belt V-Belt V-Belt Evaporator(s) (1) SS Brazed Plate (2) SS Brazed Plate (3) SS Brazed Plate Refrigerant Circuit(s) 1 Circuit 2 Circuit 3 Circuit R22 Charge per Circuit (lbs.) 8.5 8.5 8.5 Steps of Unloading 100%-0 100%-50%-0 100%-66%-33%-0 Minumim Water Flow Rate (GPM) 6 12 18 Maximum Water Flow Rate (GPM) 18 36 54 Water Connection Nom (In.) 1" NFT 1-1/2" NFT 2" NFT Shipping Weight (lbs.) 540 950 1260 Note: Gross cooling capacity based on 54°F entering water temperature, 44°F leaving water temeprature and 95°F incoming condenser air (ambient) temperature. The SpacePak ICS series of air-cooled water chillers provide compact, efficient and reliable cooling in applications where placement of the air-cooled chiller outdoors is impractical or undesirable. Locating the chiller indoors and ducting the condenser air greatly minimizes the noise heard outside to the benefit of the building’s occupants and neighbors. SpacePak ICS series units are typically installed near an outside wall or converted window opening for access to outside air for the intergal air-cooled condenser. They are ideal for larger homes wanting multiple zones. Standard Features Less than 35" deep - fits through most doorways Less than 73" tall and 81" long - fits on most freight elevators High efficiency scroll compressor(s) Centrifical condenser fan capable up to 1.4" E.S.P. V-belt driven with variable pitch sheaves Plate-fin condenser coil Premium efficiency (E+ Type) condenser fan motor Stainless steel brazed plate evaporator(s) Nominal 5, 10 and 15 ton capacities Automatic refrigerant pump-down cycle Single phase 208 and 230 volt (all unit sizes) and three phase 208, 230 and 460 volt electrical service • Spacious galvanized steel cabinet with extruded aluminum framing insulated with 1" 1.5 lb. dual density matte-faced fiberglass insulation Refrigerant access valves and liquid line filter-driers Removable front and side panels with tooled access Front access panels for electrical controls and line power 24 volt electronic control system with LCD display ETL certified for indoor and outdoor installations Exceeds ASHRAE 90.1 requirements for energy efficiency ICS Series 5-15 Ton Indoor Ducted Air-Cooled Water Chillers ICSC-1

Transcript of ICS Series 5-15 Ton Indoor Ducted Air-Cooled Water … · 1 General Product Data Model ICS 060 ICS...

1

General Product DataModel

ICS 060 ICS 120 ICS 180Nominal Tons 5 10 15

Gross Cooling Capacity 58,000 Btuh 116,000 Btuh 174,000 Btuh

Compressor(s) 1 Scroll 2 Scrolls 3 Scrolls

Condenser Coil(s) (1) 46" x 20" (2) 46" x 20" (3) 46" x 20"

Face Area (Sq. Ft.) 6.3 12.6 18.9

Rows / Fins Per Inch 4 / 14 4 / 14 4 / 14

Condenser Fan(s) (1) 15" x 10" FC (2) 15" x 12" FC (2) 15" x 15" FC

Nominal Air Flow (CFM) 3,300 6,600 9,900

Standard Motor (HP) (1) 2 HP (1) 3 HP (1) 5 HP

Motor Speed (RPM) 1750 RPM 1750 RPM 1750 RPM

Drive Type V-Belt V-Belt V-Belt

Evaporator(s) (1) SS Brazed Plate (2) SS Brazed Plate (3) SS Brazed Plate

Refrigerant Circuit(s) 1 Circuit 2 Circuit 3 Circuit

R22 Charge per Circuit (lbs.) 8.5 8.5 8.5

Steps of Unloading 100%-0 100%-50%-0 100%-66%-33%-0

Minumim Water Flow Rate (GPM) 6 12 18

Maximum Water Flow Rate (GPM) 18 36 54

Water Connection Nom (In.) 1" NFT 1-1/2" NFT 2" NFT

Shipping Weight (lbs.) 540 950 1260

Note: Gross cooling capacity based on 54°F entering water temperature, 44°F leaving water temeprature and 95°Fincoming condenser air (ambient) temperature.

The SpacePak ICS series of air-cooled water chillers providecompact, efficient and reliable cooling in applicationswhere placement of the air-cooled chiller outdoors isimpractical or undesirable. Locating the chiller indoors andducting the condenser air greatly minimizes the noise heardoutside to the benefit of the building’s occupants andneighbors. SpacePak ICS series units are typically installednear an outside wall or converted window opening foraccess to outside air for the intergal air-cooled condenser.They are ideal for larger homes wanting multiple zones.

Standard Features• Less than 35" deep - fits through most doorways

• Less than 73" tall and 81" long - fits on most freightelevators

• High efficiency scroll compressor(s)

• Centrifical condenser fan capable up to 1.4" E.S.P. V-beltdriven with variable pitch sheaves

• Plate-fin condenser coil

• Premium efficiency (E+ Type) condenser fan motor

• Stainless steel brazed plate evaporator(s)

• Nominal 5, 10 and 15 ton capacities

• Automatic refrigerant pump-down cycle

• Single phase 208 and 230 volt (all unit sizes) and

three phase 208, 230 and 460 volt electrical service

• Spacious galvanized steel cabinet with extrudedaluminum framing insulated with 1" 1.5 lb. dual densitymatte-faced fiberglass insulation

• Refrigerant access valves and liquid line filter-driers

• Removable front and side panels with tooled access

• Front access panels for electrical controls and line power

• 24 volt electronic control system with LCD display

• ETL certified for indoor and outdoor installations

• Exceeds ASHRAE 90.1 requirements for energy efficiency

ICS Series 5-15 TonIndoor Ducted Air-Cooled Water Chillers

ICSC-1

2

ICS SeriesConfiguration

3

ICS SeriesTypical Condenser Air Ductwork Arrangement

Typical Water Piping Arrangement

Short Water Piping Loop ConsiderationsIn systems with relatively short water piping loops, the volume of the water in the system can be insufficient causingswings in water temperature and short cycling. In these cases a chilled water storage tank should be installed in thereturn water piping before the chiller. This will increase the volume of the water in the system thereby reducing thefluctuations in return water temperature and reduce compressor cycling. The use of three way valves at the evaporatorcoil (in lieu of 2-way valves) and hot gas bypass is also recommended. Typically allow a minimum of 5 GPM per ton ofchilled water storage.

4

ICS 060

ICS 120

ICS 180

0.20"

0.25"

0.30"

0.40"

0.60"

0.80"

1.00"

1.20"

1.40"

RPM 762

776

789

815

866

915

963

1008

1052

BHP1.24

1.27

1.31

1.38

1.54

1.70

1.87

2.04

2.21

EER 6.6

7.1

7.6

6.6

7.1

7.6

6.7

7.0

7.5

ICS SeriesPerformance

LeavingWater

Temp. °FModel KW 7.2

7.4

7.5

14.5

14.8

15.1

21.7

22.2

22.6

Mbh 48.2

52.7

57.3

96.4

105.4

114.6

144.6

158.0

171.9

EER 7.7

8.3

8.8

7.7

8.2

8.7

7.7

8.3

8.8

KW 6.6

6.7

6.9

13.2

13.4

13.7

19.7

20.2

20.6

Mbh 50.9

55.5

60.2

101.8

111.0

120.4

152.7

166.5

180.7

EER10.3

11.0

11.6

10.3

11.0

11.6

10.2

11.1

11.7

KW 5.5

5.6

5.7

10.9

11.2

11.5

16.4

16.8

17.2

Mbh 56.5

61.3

66.3

112.9

122.6

132.6

169.4

183.9

198.9

EER 9.0

9.6

10.2

9.0

9.5

10.2

9.1

9.6

10.1

KW 6.0

6.1

6.2

12.0

12.2

12.5

18.0

18.3

18.7

Mbh 53.8

58.6

63.5

107.7

117.2

127.0

161.5

175.8

190.4

40

45

50

40

45

50

40

45

50

95°F Ambient AirTemperature

105°F Ambient AirTemperature

85°F Ambient AirTemperature

115°F Ambient AirTemperature

Cooling Performance Data

Note:• Cooling capacities based on 10°F

water temperature drop operatingat sea level.

• Refer to performance adjustmentfactors to reflect operation withethylene glycol solution andaltitudes above sea level.

• KW and EER ratings are for entireunit.

• Minimum incoming condenserair (ambient) temperature forproper operation is 55°F. Forambient temperatures below 55°F,use the low ambient head pressurecontrol accessory.

• Minimum water temperature dropis 8°F, maximum water temperaturedrop is 12°F.

• Water f low (GPM) is coolingcapacity (Btuh) divided by 500times the water temperaturedrop (°F).

BHP4.47

4.58

4.69

4.90

5.33

5.77

6.22

6.80

7.16

E.S.P.In. W.G.

RPM 800

813

827

853

903

952

999

1044

1089

BHP2.51

2.59

2.66

2.81

3.30

3.40

3.50

3.65

3.80

RPM 784

797

809

835

881

943

976

1035

1068

ICS 1206600 CFM

ICS 1809900 CFM

ICS 0603300 CFM

Condenser Fan Data

3

5

10

12

15

20

2.3

3.5

4.9

6.9

8.4

14.7

Water PressureDrop (Ft.)

0.4

1.2

4.7

6.7

10.1

17.4

20

25

30

36

40

50

6

10

20

25

30

40

0.4

1.2

4.8

7.4

10.4

17.8

ICS 180

Evaporator Data

Water Flow(GPM)

Water PressureDrop (Ft.)

Water Flow(GPM)

ICS 120

Water PressureDrop (Ft.)

Water Flow(GPM)

ICS 060

5

RLA20.7

10.0

32.1

20.7

10.0

32.1

20.7

10.0

32.1

20.7

10.0

32.1

20.7

10.0

32.1

20.7

10.0

208-230/60/3

460/60/3

208-230/60/1

208-230/60/3

460/60/3

208-230/60/1

208-230/60/3

460/60/3

208-230/60/1

208-230/60/3

460/60/3

208-230/60/1

208-230/60/3

460/60/3

208-230/60/1

Circuit 1

Circuit 2

208-230/60/3

460/60/3

FLA 5.9/5.4

2.7

19.4/17.6

9.1/8.2

4.1

13.0/11.8

9.1/8.2

4.1

13.0/11.8

14.1/12.8

6.4

21.1/19.1

14.1/12.8

6.4

21.1/19.1

22.1/20.0

10.0

31.3

15.2

57.7

34.1

16.6

51.9

54.8

26.6

84.0

59.4

28.9

91.3

80.1

38.9

59.2

72.2

87.3

42.5

52.0

25.2

89.8

54.8

26.6

84.0

75.5

36.6

116.1

80.1

38.9

123.4

100.8

48.9

91.3

104.3

108.0

52.5

45

20

75

45

20

75

60

30

100

70

35

110

90

45

75

90

100

45

ICS 060

ICS 120

ICS 180

HP2.0

2.0

2.0

3.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

5.0

7.5

7.5

Rec.Fuse

ElectricalLine PowerModel LRA

156.0

75.0

176.0

156.0

75.0

176.0

156.0

75.0

176.0

156.0

75.0

176.0

156.0

75.0

176.0

156.0

75.0

CondenserFan MotorCompressor (each)

Electrical Data

Max.Fuse

Note:• All 5 and 10 ton 1-phase and 3-phase units and 15 ton 3-phase units have single point line power connection.

Single phase 15 ton units have dual point line power connections.

• Minimum circuit ampacity calculated per UL formula: MCA = (1.25 x largest load) + the sum of other loads.

• Maximum fuse size is calculated per UL formula: Max. Fuse = (2.25 x largest load) + the sum of all other loads.

• Time delay fuses and circuit breakers are recommended.

MCA

1.00

0.99

0.98

0.98

0.97

1.00

0.98

0.97

0.95

0.94

1.02

1.04

1.07

1.10

1.14

ICS SeriesPerformance

.0005

.0010

.0020

1.01

1.02

1.04

CompressorInput

(KW) PAF

0.98

0.96

0.90

0.98

0.94

0.89

0.99

0.98

0.94

2000

4000

6000

Fouling Factor and Elevation Performance Adjustment Factors

CoolingCapacity

(Btuh) PAFElevation (Ft.)

Above Sea Level

CompressorInput

(KW) PAF

CoolingCapacity

(Btuh) PAFFoulingFactor

10%

20%

30%

40%

50%

25°F

17°F

5°F

-12°F

-32°F

Ethylene Glycol Performance Adjustment Factors

CompressorInput

(KW) PAF

CoolingCapacity

(Btuh) PAFWater Flow(GPM) PAF

FreezingTemperature

(°F)% Glycol

by Weight

6

ICS SeriesDimensions

A B C D E F G H J K L M N P

ICS060

ICS120

ICS180

72.06 34.00 27.74 4.00 20.47 48.00 25.09 1.19 4.50 4.39 23.20 43.75 46.75 3.72

72.06 34.00 54.10 4.00 20.47 48.00 51.34 1.19 4.28 4.39 23.20 43.75 46.75 3.72

72.06 34.00 80.22 4.00 20.47 48.00 77.60 1.19 3.94 4.39 23.20 43.75 46.75 3.72

SpacePak ICS WATER CHILLER - PHYSICAL DIMENSIONS (INCHES)

SPACEPAK RESERVES THE RIGHT TO MAKE CHANGES AND IMPROVEMENTS WITHOUT NOTICE. CONTACT FACTORY AT TIME OF ORDER FOR CERTIFIED DRAWINGS.

MODELOVERALL DIM’S DUCT DIM’S ELEC. CONN.WATER CONN.

7

All Field Installed Accessories are to be ordered as aseparate line items.

FIELD INSTALLED ACCESSORIESAC-A1 - Water Flow SwitchAC-A2 - 1" Fine Mesh Fluid StrainerAC-A3 - 11/2" Fine Mesh Fluid StrainerAC-A4 - 2" Fine Mesh Fluid StrainerAC-B1 - 30 Amp Non-Fused DisconnectAC-B2 - 60 Amp Non-Fused DisconnectAC-B3 - 100 Amp Non-Fused DisconnectAC-B4 - 30 Amp Fused DisconnectAC-B5 - 60 Amp Fused DisconnectAC-B6 - 100 Amp Fused DisconnectAC-C1 - Rubber-in-shear Vibration Isolation PackageAC-C2 - 4" Caster Kit (4) - Requires Fork Lift compatible baseAC-D1 - 30 Gallon Insulated Chilled Water Storage TankAC-D2 - 60 Gallon Insulated Chilled Water Storage TankAC-D3 - 90 Gallon Insulated Chilled Water Storage TankAC-D4 - 30 psi Water Pressure Relief ValveAC-D5 - 100 psi Water Pressure Relief ValveOP-D5 - Low Ambient Head Pressure Control KitAC-E5 - 5 TonAC-E6 - 10 TonAC-E7 - 15 TonOP-E3 - Condenser Duct Connection Kit with Access CoversAC-H5 - 5 TonAC-H6 - 10 TonAC-H7 - 15 TonOP-G3 - Wall Louver and SleeveAC-J5 - 5 TonAC-J6 - 10 TonAC-J7 - 15 TonOP-H1 - Condenser 2" Filter RackAC-K9 - 5 TonAC-K10 - 10 TonAC-K11 - 15 Ton 2" Throw-away Filter Set for Condenser Filter RackAC-K12 - 5 TonAC-K13 - 10 TonAC-K14- 15 Ton

Note: Specials in any digit in the model number aredesignated with a “Z”.

1 2 3 4 5 6 7 8 9 10 11 12 13 14+

UT CP CA PL CC RT SV CB CM OP

(Internal use Only)

Sterling AquaKing™ ChillerModel Number Description

1, 2, 3 - Unit Type [UT]ICS - Indoor Ducted Water Chiller

4 - Number of Circuits/Compressors [CP]S - Single (5 Tons)D - Dual (10 Tons)T - Triple (15 Tons)

5, 6, 7 - Nominal Cooling Capacity [CA]060 - 60,000 Btuh (5 Tons)120 - 120,000 Btuh (10 Tons)180 - 180,000 Btuh (15 Tons)

8 - Piping Location [PL] (Facing Front of Unit)A - Left Hand (Standard)B - Right Hand

9 - Cabinet Construction [CC]1 - Galvanized Steel2 - Painted Steel3 - Stainless Steel

10 - Refrigerant Type [RT]A - R22

11 - Supply Voltage [SV]2 - 208/1/603 - 230/1/604 - 208/3/605 - 230/3/606 - 460/3/60

12 - Condenser Blower Type [CB]B - Forward Curved Belt Drive

13 - Condenser Fan Motor Size and Type [CM]1 - 2 HP Open Drip-proof2 - 3 HP Open Drip-proof3 - 5 HP Open Drip-proof4 -7-1/2 HP Open Drip-proof5 - 2 HP Totally Enclosed6 - 3 HP Totally Enclosed7 - 5 HP Totally Enclosed8 - 7-1/2 HP Totally Enclosed

14 - Factory Installed Options [OP] - All Factory InstalledOptions are to be entered in the model number Digit#14+.R - Refrigerant Pressure Relief Valve(s) - Chicago CodeH - Hot Gas Bypass (One Circuit Only)E - Epoxy Coated Condenser Coil(s)B - Fork Lift Compatible BaseP - Freeze Protection

(Heaters on Evaporator and Internal Water Piping)W - Water Flow SwitchS - Fluid StrainerL - Low Ambient Head Pressure Control

New York City MEA Listed

8

ICS SeriesSuggested Mounting Methods

VIBRATION ISOLATOR

NUT & LOCK WASHER

3/4" NUT &LOCK WASHER

3/4" LOCK WASHER

3/4" NUT

TYPICAL MOUNTING HARDWARE : (4) FLOOR ANCHORS(4) LEGS (6 TO 72")(4) VIBRATION ISOLATORS(10) LEVELING SHIMS(8) 3/4" NUTS(8) 3/4" LOCK WASHERSCROSS BRACING OVER 24"

TYPICAL MOUNTING HARDWARE :

(4) 3/4" FLOOR ANCHORS(4) 3/4" NUTS & LOCK WASHERS(4) VIBRATION ISOLATORS(10) LEVELING SHIMS

3" DIA. LEG

OVER 24" IN HEIGHTCROSS BRACE

FLOOR ANCHOR

CONCRETE FLOOR

F L O OR MOUNT

E L E VA TE D F L OO R MOUNT

CONCRETE FLOORVIBRATION ISOLATORS

FLOOR ANCHOR

9

ICS SeriesTypical Wiring

10

ICS SeriesSpecifications

CabinetThe cabinet is constructed from heavy gauge galvanizedsteel panels with extruded aluminum framing insulatedwith 1" 1.5 lb. dual density matte-faced fiberglassinsulation. Easy service access is provided through panelsat each side and front with tooled access. A convenientcontrol box access panel allows the unit to be operatingwhile the controls are accessible.

Compressor(s)Individually circuited compressors are high efficiencyhermetic scroll with internal thermal overload protection,internal suspension system, centrifugal oil pump andcrankcase heater.

Condenser Fan MotorBall bearing open drip-proof premium efficiency (E+ Type)condenser fan motor with thermal overload protection.

Condenser Fan(s)Fans are forward curve centrifugal fans. The fan wheels arestatically and dynamically balanced. Dual condenser fansare driven by a common motor. Shaft bearings arepermanently lubricated. V-belt drives include a blowerpulley, adjustable pitch motor sheave and V-belt.

Condenser Coil(s)Coils are constructed from 3/8" OD seamless, internallyenhanced copper tube of not less than .012" wallthickness. Aluminum fins are of a die formed, enhancedlouver design no less than .0045" thick. Tubes shall bemechanically expanded to assure a good mechanical bondbetween the tube and fin. Coil manifolds are Type “L”seamless copper tubing.

Evaporator(s)Stainless steel brazed plate heat exchangers with workingpressures to 450 psig. Evaporator and water lines insulatedwith closed-cell insulation. Drain plug provided for thewater piping.

ElectricalETL certified for indoor or outdoor use. Control systemshall be 24-volt electronic temperature control with LCDdisplay, compressor contactors, high/low pressure safetycontrols and line voltage-24 volt control transformer. Anti-recycle function standard on all units and automaticcompressor lead-lag function standard on all units (excepton units with hot gas bypass option). Electronic controlsystem consists of a fully configurable and programmableelectronic microprocessor, adaptable to standard LON,N2Open, and BACnet MSTP Building Automation Systemprotocols. Controller shall have capabilities to provide bothlocal (unit mounted) and remotely mounted User Interfacemodules to distances up to 300 meters. User Interfacemodule shall have a 4 x 20 backlit LCD, IP54 display withan extended operating range from -20°C to +50°C. All unitsexceed Ashrae 90.1 requirements for energy efficiency.

Refrigerant Circuit(s)Each refrigerant circuit includes thermostatic expansionvalve, refrigerant access valves, liquid line filter-dryer andshipped with an operating charge of R22. Automaticrefrigerant pump-down cycle with solenoid valves on eachcircuit.

FACTORY INSTALLED OPTIONS

Painted CabinetSame specifications as the standard cabinet, except theexterior of the cabinet is painted in gray color.

Stainless Steel CabinetSame specifications as the standard cabinet, except theexterior panels and bottom base pan are constructed of430 alloy stainless steel for corrosion resistance withextruded aluminum framing.

Fork Lift Compatible BaseThe units base has fork lift tine openings for handling fromany side.

Refrigerant Relief Valve(s)Relief valves for each refrigerant circuit installed on thedischarge lines and terminated in a 1/2" male fitting forpiping to outside of building.

Hot Gas BypassHot gas bypass valve to modulate the cooling capacitybelow the minimum step of unloading on one circuit.

Epoxy Coated Condenser Coil(s)Same specifications as the standard coils, except the coil iscoated with an epoxy type electro-deposition coatinghighly resistant to corrosive environments. The thicknessof the coating is computer controlled at 0.001" (+/-0.0002"). The coating has a thermal heat transfer reductionof less than 1%.

Low Ambient Freeze ProtectionThermostatically controlled electric heat tape for freezeprotection of the evaporator and water piping.

Totally Enclosed Condenser Fan MotorBall bearing totally enclosed premium efficiency condenserfan motor with thermal overload protection.

Fluid StrainerFine mesh fluid strainer for the water piping.(Also available as a field installed accessory.)

Water Flow SwitchAn interlocking flow switch in the evaporator water pipingis required to prevent unit operation without water flow.(Also available as a field installed accessory.)

11

ICS SeriesSpecifications

FACTORY INSTALLED OPTIONS(CONTINUED)

Low Ambient Head Pressure ControlA variable frequency drive on the condenser fan thatregulates head pressure to allow operation at low outdoorambient temperatures down to 0° F (recommended whenambient temperatures fall below 55° F). Includes anti-recycle and bypass timers.(Also available as a field installed accessory kit.)

FIELD INSTALLED ACCESSORIES(SHIPPED SEPARATELY)

Electrical Disconnect SwitchesFused or non-fused electrical disconnect switches for theline power.

Wall Louver and SleeveArchitectural galvaneal wall louver with screen for thecondenser air opening in a wall suitable for painting.

Condenser Duct Connection Kitwith Access CoversA knocked-down ductwork kit with access covers and flexconnectors to connect to the condenser air opening tothe wall sleeve, while providing access for cleaning thecondenser coil.

CastersHeavy duty, large diameter, locking casters to provideportability and ease installations in tight retrofit applications(requires fork lift compatible base option).

Vibration Isolation PackageRubber-in-shear isolation package.

Chilled Water Storage TanksInsulated 30, 60 or 90 gallon chilled water storage tankwith suitable tappings to serve as a buffer with fluidtappings.

Water Pressure Relief Valve30 or 100 PSI water relief valve.

Condenser Air 2" Filter RackCondenser Air inlet filter rack.

Condenser Air Filters2" pleated throw-away filters for the condenser air filterrack.