Icm Rec670

download Icm Rec670

of 222

description

rec 670 relay module manual

Transcript of Icm Rec670

  • Innovation from ABB

    Installation and commissioning manualBay control IEDREC 670

  • Document ID: 1MRK511189-UENIssued: December 2007

    Revision: BIED product version: 1.1

    Copyright 2007 ABB. All rights reserved

  • COPYRIGHTWE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENTTHAT A PATENT IS ISSUED AND A DIFFERENT COMMERCIALPROPRIETARY RIGHT IS REGISTERED. IMPROPER USE, INPARTICULAR REPRODUCTION AND DISSEMINATION TO THIRDPARTIES, IS NOT PERMITTED.THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, INCASE ANY ERRORS ARE DETECTED, THE READER IS KINDLYREQUESTED TO NOTIFY THE MANUFACTURER AT THE ADDRESSBELOW.THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FORTHE CONCEPT OR PRODUCT DESCRIPTION AND IS NOT TO BEDEEMED TO BE A STATEMENT OF GUARANTEED PROPERTIES. INTHE INTEREST OF OUR CUSTOMERS, WE CONSTANTLY SEEK TOENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATESTTECHNOLOGICAL STANDARDS. AS A RESULT, IT IS POSSIBLE THATTHERE MAY BE SOME DIFFERENCES BETWEEN THE HW/SWPRODUCT AND THIS INFORMATION PRODUCT.Manufacturer:

    ABB ABSubstation Automation ProductsSE-721 59 VstersSwedenTelephone: +46 (0) 21 34 20 00Facsimile: +46 (0) 21 14 69 18www.abb.com/substationautomation

  • Table of contents

    Section 1 Introduction.....................................................................11Introduction to the installation and commissioning manual..............11

    About the complete set of manuals for an IED............................11About the installation and commissioning manual.......................12Intended audience.......................................................................13Related documents......................................................................13Revision notes.............................................................................14

    Section 2 Safety information..........................................................15Warning signs...................................................................................15Caution signs....................................................................................16Note signs.........................................................................................17

    Section 3 Overview........................................................................19Commissioning and installation overview.........................................19

    Section 4 Unpacking and checking the IED...................................21Taking delivery, unpacking and checking.........................................21

    Section 5 Installing the IED............................................................23Overview...........................................................................................23Dimensions.......................................................................................23

    Case without rear cover...............................................................23Case with rear cover....................................................................24Flush mounting dimensions.........................................................26Side-by-side flush mounting dimensions.....................................27Wall mounting dimensions...........................................................28

    Mounting methods and details..........................................................28Mounting the IED.........................................................................28Flush mounting............................................................................30

    Overview................................................................................30Mounting procedure for flush mounting..................................30

    19 panel rack mounting..............................................................31Overview................................................................................31Mounting procedure for 19 panel rack mounting...................32

    Wall mounting..............................................................................33Overview................................................................................33Mounting procedure for wall mounting...................................33How to reach the rear side of the IED....................................34

    Side-by-side 19 rack mounting...................................................35

    Table of contents

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 1

  • Overview................................................................................35Mounting procedure for side-by-side rack mounting..............36IED 670 mounted with a RHGS6 case...................................36

    Side-by-side flush mounting........................................................37Overview................................................................................37Mounting procedure for side-by-side flush mounting.............38

    Making the electrical connection......................................................39IED connectors............................................................................39

    Overview................................................................................39Front side connectors.............................................................40Rear side connectors.............................................................41Connection diagrams.............................................................45Connection examples.............................................................51

    Connecting to protective earth.....................................................54Connecting the power supply module.........................................55Configuration for analog CT inputs..............................................55Connecting to CT and VT circuits................................................55Connecting the binary input and output signals...........................55Making the screen connection.....................................................57

    Optical connections..........................................................................58Connecting station communication interfaces (OEM andSLM)............................................................................................58Connecting remote communication interfaces (LDCM)...............59

    Galvanic X.21 line data communication (X.21-LDCM).....................59Connecting Galvanic X.21 line data communication module(X.21 LDCM)................................................................................59

    Installing the serial communication cable for RS485........................61RS485 serial communication module..........................................61Installing the serial communication cable for RS485 SPA/IEC...............................................................................................65Data on RS485 serial communication module cable...................67

    Installing the GPS antenna...............................................................67Installing the GPS antenna..........................................................67

    Antenna installation................................................................67Electrical installation...............................................................68

    Section 6 Checking the external optical and electricalconnections....................................................................71Overview...........................................................................................71Checking the VT circuits...................................................................71Check of CT circuits.........................................................................72Checking the power supply..............................................................72Checking the binary I/O circuits........................................................72

    Binary input circuits.....................................................................73

    Table of contents

    2 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Binary output circuits...................................................................73Checking the optical connections.....................................................73

    Section 7 Energizing the IED.........................................................75Overview...........................................................................................75Energizing the IED............................................................................75Checking the self supervision signals...............................................77

    Reconfiguring the IED.................................................................77Setting the IED time.....................................................................77Checking the self supervision function........................................77

    Determine the cause of an internal failure..............................77Self supervision HMI data............................................................78

    Section 8 Set up PCM 600 communication link per IED................79Set up PCM 600 communication link per IED..................................79

    Section 9 Establishing connection and verifying the SPA/IEC-communication ..............................................................85Entering settings...............................................................................85

    Entering SPA settings..................................................................85Entering IEC settings...................................................................86

    Verifying the communication............................................................86Verifying SPA communication.....................................................86Verifying IEC communication......................................................87

    Fibre optic loop.................................................................................87Optical budget calculation for serial communication with SPA/IEC ...................................................................................................88

    Section 10 Establishing connection and verifying the LONcommunication ..............................................................89Communication via the rear ports ....................................................89

    LON communication....................................................................89The LON Protocol........................................................................90Hardware and software modules.................................................91

    Optical budget calculation for serial communication with LON ........93Section 11 Configuring the IED and changing settings....................95

    Overview...........................................................................................95Entering settings through the local HMI............................................96Analog input data..............................................................................96

    Configuration for analog CT inputs..............................................96Downloading settings and configuration from a PC..........................97

    Downloading the configuration and setting files..........................97Section 12 Verifying settings by secondary injection ......................99

    Overview...........................................................................................99

    Table of contents

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 3

  • Preparing for test............................................................................100Overview....................................................................................100Preparing the connection to the test equipment........................101Putting the IED into test mode...................................................101Connecting test equipment to the IED.......................................102Verifying the connections and the analog inputs.......................102Releasing the function(s) to be tested.......................................103Disturbance report.....................................................................104

    Introduction...........................................................................104Disturbance report settings..................................................104Disturbance recorder (DR)...................................................104Event recorder (ER).............................................................105

    Identifying the function to test in the technical referencemanual ......................................................................................105Exit test mode............................................................................105

    Basic IED functions........................................................................106Parameter setting groups (ACGR)............................................106

    Verifying the settings............................................................106Completing the test..............................................................106

    Differential protection......................................................................106High impedance differential protection (PDIF, 87).....................106

    Verifying the settings............................................................106Completing the test..............................................................107

    Current protection...........................................................................107Instantaneous phase overcurrent protection (PIOC, 50) ..........107

    Measuring the operate limit of set values.............................108Completing the test..............................................................108

    Four step phase overcurrent protection (PTOC, 51/67)............108Verifying the settings............................................................108Completing the test..............................................................110

    Instantaneous residual overcurrent protection (PIOC,50N) ..........................................................................................110

    Measuring the operate limit of set values.............................110Completing the test..............................................................110

    Four step residual overcurrent protection (PTOC, 51N/67N)...........................................................................................110

    Four step directional overcurrent protection.........................110Four step non-directional overcurrent protection..................111Completing the test..............................................................111

    Sensitive directional residual overcurrent and powerprotection (PSDE, 67N).............................................................111

    Measuring the operate and time limit for set values.............112Completing the test..............................................................116

    Table of contents

    4 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Thermal overload protection, one time constant (PTTR,26).............................................................................................116

    Measuring the operate and time limit of set values..............116Completing the test..............................................................117

    Thermal overload protection, two time constants (PTTR,49) ............................................................................................117

    Checking operate and reset values......................................117Completing the test..............................................................119

    Breaker failure protection (RBRF, 50BF)...................................119Checking the phase current operate value, IP>...................120Checking the residual (EF) current operate value IN> setbelow IP>...........................................................................120Checking the re-trip and back-up times................................120Verifying the re-trip mode.....................................................121Verifying the back-up trip mode............................................121Verifying instantaneous back-up trip at CB faultycondition ..............................................................................123Verifying the case FunctionMode = Contact.........................123Verifying the function mode Curr&Cont Check..................123Completing the test..............................................................124

    Stub protection (PTOC, 50STB)................................................124Measuring the operate limit of set values.............................124Completing the test..............................................................125

    Pole discordance protection (RPLD, 52PD)..............................125Verifying the settings............................................................125Completing the test..............................................................126

    Directional underpower protection (PDUP) ..............................126Verifying the settings............................................................127Completing the test..............................................................128

    Directional overpower protection (PDOP) ................................128Verifying the settings............................................................128Completing the test..............................................................130

    Broken conductor check (BRC).................................................130Measuring the operate and time limit of set values..............130Completing the test..............................................................131

    Voltage protection...........................................................................131Two step undervoltage protection (PTUV, 27)..........................131

    Verifying the settings............................................................131Completing the test..............................................................132

    Two step overvoltage protection (PTOV, 59)............................132Verifying the settings............................................................132Completing the test..............................................................132

    Two step residual overvoltage protection (PTOV, 59N)............132Verifying the settings............................................................132

    Table of contents

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 5

  • Completing the test..............................................................133Voltage differential protection (PTOV, 60).................................133

    Check of undervoltage levels...............................................133Check of voltage differential trip and alarm levels................135Check of trip and trip reset timers........................................136Final adjustment of compensation for VT ratiodifferences ...........................................................................137Completing the test..............................................................137

    Loss of voltage check (LOV).....................................................137Measuring the operate limit of set values.............................138Completing the test..............................................................138

    Frequency protection......................................................................138Underfrequency protection (PTUF, 81).....................................138

    Verifying the settings............................................................139Completing the test..............................................................139

    Overfrequency protection (PTOF, 81).......................................140Verifying the settings............................................................140Completing the test..............................................................141

    Rate-of-change frequency protection (PFRC, 81).....................141Verifying the settings............................................................141Completing the test..............................................................141

    Multipurpose protection..................................................................142General current and voltage protection (GAPC)........................142

    Built-in overcurrent feature (non-directional)........................142Overcurrent feature with current restraint.............................143Overcurrent feature with voltage restraint............................143Overcurrent feature with directionality..................................143Over/Undervoltage feature...................................................144Completing the test..............................................................144

    Secondary system supervision.......................................................144Current circuit supervision (RDIF).............................................144

    Verifying the settings............................................................145Completing the test..............................................................145

    Fuse failure supervision (RFUF)................................................145Checking that the binary inputs and outputs operate asexpected ..............................................................................145Measuring the operate value for the negative sequencefunction ................................................................................146Measuring the operate value for the zero sequencefunction ................................................................................147Checking the operation of the duv/dt and di/dt basedfunction ................................................................................147Completing the test..............................................................148

    Control............................................................................................148

    Table of contents

    6 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Synchrocheck and energizing check (RSYN, 25)......................148Testing the synchronizing function.......................................150Testing the synchronism check............................................152Testing the energizing check................................................155Testing the voltage selection................................................156Completing the test..............................................................157

    Autorecloser (RREC, 79)...........................................................157Preparation of the verification ..............................................159Switching the auto-reclosing function On and Off................160Verifying the auto-reclosing function ...................................160Checking the reclosing conditions .......................................161Completing the test..............................................................163

    Apparatus control (APC)............................................................163Interlocking................................................................................163Voltage control (VCTR).............................................................163

    Secondary test.....................................................................165Check the activation of the Voltage Control Operation........165Check normal voltage regulation function............................166Check the setting of UVBlock...............................................167Check the setting of parameter UVmin and UVmax.............167Overcurrent blocking............................................................167Single transformer................................................................168Parallel voltage regulation....................................................169Completing the test..............................................................173

    Scheme communication.................................................................173Scheme communication logic for distance protection (PSCH,85) ............................................................................................173

    Testing permissive underreach............................................173Testing permissive overreach..............................................174Testing blocking scheme......................................................174Checking of unblocking logic................................................174Completing the test..............................................................175

    Current reversal and weak end infeed logic for distanceprotection (PSCH, 85) ..............................................................175

    Current reversal logic...........................................................175Weak end infeed logic..........................................................176Completing the test..............................................................177

    Local acceleration logic (PLAL).................................................177Verifying the settings............................................................177Completing the test..............................................................177

    Scheme communication logic for residual overcurrentprotection (PSCH, 85) ..............................................................177

    Testing the directional comparison logic function.................178Completing the test..............................................................179

    Table of contents

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 7

  • Current reversal and weak end infeed logic for residualovercurrent protection (PSCH, 85) ...........................................179

    Testing the current reversal logic.........................................179Testing the weak-end-infeed logic........................................180Completing the test..............................................................181

    Logic...............................................................................................181Tripping logic (PTRC, 94)..........................................................181

    Three phase operating mode...............................................1811ph/3ph operating mode......................................................1821ph/2ph/3ph operating mode...............................................183Circuit breaker lockout..........................................................184Completing the test..............................................................184

    Monitoring.......................................................................................184Event counter (GGIO)................................................................184Event function (EV)....................................................................185Fault locator (RFLO)..................................................................185

    Measuring the operate limit..................................................186Completing the test..............................................................187

    Metering..........................................................................................187Pulse counter logic (GGIO).......................................................187

    Station communication...................................................................187Multiple command and trasmit (CM, MT)..................................187Single command (CD)...............................................................187

    Remote communication..................................................................188Binary signal transfer to remote end..........................................188

    Section 13 Primary injection testing...............................................191Primary injection testing.................................................................191

    Voltage control (VCTR).............................................................191Load drop compensation function, LDC...............................191Testing the LDC function......................................................192Voltage control of Parallel Transformers..............................193Minimum Circulating Current (MCC) method.......................194Master Follower (MF) method..............................................196Completing the test..............................................................197

    Section 14 Commissioning and maintenance of the fault clearingsystem..........................................................................199Installation and commissioning.......................................................199Commissioning tests......................................................................200Periodic maintenance tests............................................................200

    Visual inspection........................................................................201Maintenance tests.....................................................................201

    Preparation...........................................................................202

    Table of contents

    8 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Recording.............................................................................202Secondary injection..............................................................202Alarm test.............................................................................202Self supervision check..........................................................202Trip circuit check..................................................................203Measurement of service currents.........................................203Restoring..............................................................................203

    Section 15 Fault tracing and repair................................................205Fault tracing....................................................................................205

    Information on the local HMI......................................................205Using front-connected PC or SMS............................................206

    Repair instruction............................................................................208Repair support................................................................................209Maintenance...................................................................................209

    Section 16 Glossary.......................................................................211Glossary.........................................................................................211

    Table of contents

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 9

  • 10

  • Section 1 Introduction

    About this chapterThis chapter introduces the user to the manual.

    1.1 Introduction to the installation andcommissioning manual

    1.1.1 About the complete set of manuals for an IEDThe users manual (UM) is a complete set of five different manuals:

    en06000097.vsd

    Applicationmanual

    Technicalreference

    manual

    Installation andcommissioning

    manual

    Operatorsmanual

    Engineeringguide

    The Application Manual (AM) contains application descriptions, setting guidelinesand setting parameters sorted per function. The application manual should be used tofind out when and for what purpose a typical protection function could be used. Themanual should also be used when calculating settings.The Technical Reference Manual (TRM) contains application and functionalitydescriptions and it lists function blocks, logic diagrams, input and output signals,setting parameters and technical data sorted per function. The technical referencemanual should be used as a technical reference during the engineering phase,installation and commissioning phase, and during normal service.The Installation and Commissioning Manual (ICM) contains instructions on howto install and commission the protection IED. The manual can also be used as areference during periodic testing. The manual covers procedures for mechanical andelectrical installation, energizing and checking of external circuitry, setting andconfiguration as well as verifying settings and performing directional tests. Thechapters are organized in the chronological order (indicated by chapter/sectionnumbers) in which the protection IED should be installed and commissioned.The Operators Manual (OM) contains instructions on how to operate the protectionIED during normal service once it has been commissioned. The operators manual

    Section 1Introduction

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 11

  • can be used to find out how to handle disturbances or how to view calculated andmeasured network data in order to determine the cause of a fault.The IED 670 Engineering guide (EG) contains instructions on how to engineer theIED 670 products. The manual guides to use the different tool components for IED670 engineering. It also guides how to handle the tool component available to readdisturbance files from the IEDs on the basis of the IEC 61850 definitions. The thirdpart is an introduction about the diagnostic tool components available for IED 670products and the PCM 600 tool.The IEC 61850 Station Engineering guide contains descriptions of IEC 61850station engineering and process signal routing. The manual presents the PCM 600and CCT tool used for station engineering. It describes the IEC 61850 attribute editorand how to set up projects and communication.

    1.1.2 About the installation and commissioning manualThe installation and commissioning manual contains the following chapters: The chapter Safety information presents warning and note signs, that the user

    should pay attention to. The chapter Overview is a summary of the major tasks faced when installing

    and commissioning an IED. The chapter Unpacking and checking the IED explains how to take delivery

    of the IED. The chapter Installing the IED explains how to install the IED. The chapter Checking the external optical and electrical connections explains

    how to check that the IED is properly connected to the protection system. The chapter Energizing the IED explains how to start the IED. The chapter Establishing connection and verifying the SPA/IEC-

    communication contains explains how to enter SPA/IEC settings and verifyingthe SPA/IEC communication.

    The chapter Establishing connection and verifying the LON communicationcontains a reference to another document.

    The chapter Configuring the IED and changing settings explains how todownload settings and configure the terminal.

    The chapter Verifying settings by secondary injection contains instructions onhow to verify that each included function operates correctly according to the setvalues.

    The chapter Commissioning and maintenance of the fault clearing systemdiscusses maintenance tests and other periodic maintenance measures.

    The chapter Fault tracing and repair explains how to troubleshoot. The chapter Glossary is a list of terms, acronyms and abbreviations used in

    ABB technical documentation.

    Section 1Introduction

    12 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 1.1.3 Intended audienceGeneralThe installation and commissioning manual addresses the personnel responsible forthe installation, commissioning, maintenance and taking the protection in and out ofnormal service.RequirementsThe installation and commissioning personnel must have a basic knowledge inhandling electronic equipment. The commissioning and maintenance personnel mustbe well experienced in using protection equipment, test equipment, protectionfunctions and the configured functional logics in the protection.

    1.1.4 Related documentsDocuments related to REC 670 Identity numberOperators manual 1MRK 511 188-UENInstallation and commissioning manual 1MRK 511 189-UENTechnical refernce manual 1MRK 511 187-UENApplication manual 1MRK 511 190-UENBuyers guide 1MRK 511 192-BENConnection diagram, Single breaker 1MRK 002 801-FAConnection diagram, Double breaker 1MRK 002 801-MAConnection diagram, 1 1/2 CB 1MRK 002 801-NAConfiguration diagram A, Single breaker arr. with single or double busbar 1MRK 004 500-90Configuration diagram B, Double breaker arrangements 1MRK 004 500-91Configuration diagram C, 1 1/2 breaker arr. for a full bay 1MRK 004 500-92

    Connection and Installation components 1MRK 013 003-BENTest system, COMBITEST 1MRK 512 001-BENAccessories for IED 670 1MRK 514 012-BENGetting started guide IED 670 1MRK 500 080-UENSPA and LON signal list for IED 670, ver. 1.1 1MRK 500 083-WENIEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WENGeneric IEC 61850 IED Connectivity package 1KHA001027-UENProtection and Control IED Manager PCM 600 Installation sheet 1MRS755552Engineering guide IED 670 products 1MRK 511 179-UEN

    Latest versions of the described documentation can be found on www.abb.com/substationautomation

    Section 1Introduction

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 13

  • 1.1.5 Revision notesRevision DescriptionB No functionality added. Minor changes made in content due to problem reports.

    Section 1Introduction

    14 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Section 2 Safety information

    About this chapterThis chapter contains safety information. Warning signs are presented which urge theuser to be careful during certain operations in order to avoid injuries to humans ordamage to equipment.

    2.1 Warning signs

    Strictly follow the company and country safety regulations. Workingin a high voltage environment requires serious approach to avoidhuman injuries and damage to equipment.

    Do not touch circuitry during operation. Potentially lethal voltagesand currents are present.

    Always avoid touching the circuitry when covers are removed. Theproduct contains electronic circuits which can be damaged if exposedto static electricity (ESD). Lethal high voltage circuits are alsoexposed when covers are removed.

    Always use suitable isolated test pins when measuring signals in opencircuitry. Potentially lethal voltages and currents are present.

    Never connect or disconnect a wire and/or a connector to or from aIED during normal operation. Hazardous voltages and currents arepresent that may be lethal. Operation may be disrupted and IED andmeasuring circuitry may be damaged.

    Always connect the IED to protective earth, regardless of theoperating conditions. This also applies to special occasions such asbench testing, demonstrations and off-site configuration. Operating

    Section 2Safety information

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 15

  • the IED without proper earthing may damage both IED and measuringcircuitry and may cause injuries in case of an accident.

    Never disconnect the secondary connection of current transformercircuit without short-circuiting the transformers secondary winding.Operating a current transformer with the secondary winding open willcause a massive potential build-up that may damage the transformerand may cause injuries to humans.

    Never remove any screw from a powered IED or from a IEDconnected to powered circuitry. Potentially lethal voltages andcurrents are present.

    Take adequate measures to protect the eyes. Never look into the laserbeam.

    2.2 Caution signs

    Always transport PCBs (modules) using certified conductive bags.Always handle modules using a conductive wrist strap connected toprotective ground and on a suitable antistatic surface. Electrostaticdischarge (ESD) may cause damage to the module since electroniccircuits are sensitive to this phenomena.

    Do not connect live wires to the IED. Internal circuitry may bedamaged

    Always use a conductive wrist strap connected to protective groundwhen replacing modules. Electrostatic discharge (ESD) may damagethe module and IED circuitry.

    Take care to avoid electrical shock if accessing wiring and connectionIEDs when installing and commissioning.

    Section 2Safety information

    16 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Changing the active setting group will inevitably change the IEDsoperation. Be careful and check regulations before making thechange.

    2.3 Note signs

    The protection assembly is designed for a maximum continuouscurrent of four times rated value.

    Section 2Safety information

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 17

  • 18

  • Section 3 Overview

    About this chapterThis chapter outlines the installation and commissioning of the IED.

    3.1 Commissioning and installation overviewThe settings for each function must be calculated before the commissioning task canstart. A configuration, done in the configuration and programming tool, must also beavailable if the IED does not have a factory configuration downloaded.The IED is unpacked and visually checked. It is preferably mounted in a cubicle oron a wall. The connection to the protection system has to be checked in order to verifythat the installation is successful.

    Section 3Overview

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 19

  • 20

  • Section 4 Unpacking and checking the IED

    About this chapterThis chapter describes the delivery and the unpacking of the IED

    4.1 Taking delivery, unpacking and checkingProcedure

    1. Remove the transport casing.2. Visually inspect the IED.3. Check that all items are included in accordance with the delivery documents.

    Once the IED has been started make sure that the software functions orderedhave been included in the delivery.

    4. Check for transport damages.If transport damage is discovered appropriate action must be taken against thelatest carrier and the nearest ABB office or representative should be informed.ABB should be notified immediately if there are any discrepancies in relationto the delivery documents.

    5. StorageIf the IED is to be stored before installation, this must be done in the originaltransport casing in a dry and dust free place. Observe the environmentalrequirements stated in the technical data.

    Section 4Unpacking and checking the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 21

  • 22

  • Section 5 Installing the IED

    About this chapterThis chapter describes how to install the IED.

    5.1 OverviewThe mechanical and electrical environmental conditions at the installation site mustbe within the limits described in the IED technical data. Dusty, damp places, placessusceptible to rapid temperature variations, powerful vibrations and shocks, surgevoltages of high amplitude and fast rise time, strong induced magnetic fields or similarextreme conditions should be avoided.Sufficient space must be available in front of and at the rear of the IED to allow accessfor maintenance and future modifications. Flush mounted IEDs should be mountedso that IED modules can be added and replaced without excessive dismantling.

    5.2 Dimensions5.2.1 Case without rear cover

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 23

  • xx04000448.vsd

    CB

    D

    E

    A

    Figure 1: Case without rear cover xx04000464.vsd

    JG

    F

    K

    H

    Figure 2: Case without rear coverwith 19 rack mounting kit

    Case size (mm) A B C D E F G H J K6U, 1/2 x 19 265.9 223.7 201.1 252.9 205.7 190.5 203.7 - 187.6 -6U, 3/4 x 19 265.9 336.0 201.1 252.9 318.0 190.5 316.0 - 187.6 -6U, 1/1 x 19 265.9 448.3 201.1 252.9 430.3 190.5 428.3 465.1 187.6 482.6The H and K dimensions are defined by the 19 rack mounting kit

    5.2.2 Case with rear cover

    Section 5Installing the IED

    24 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • xx05000501.vsd

    B

    D

    E

    A

    C

    Figure 3: Case with rear cover.

    xx05000502.vsd

    JG

    F

    K

    H

    Figure 4: Case with rear coverand 19 rack mountingkit.

    xx05000503.vsd

    Figure 5: Rear cover case withdetails.

    Case size (mm) A B C D E F G H J K6U, 1/2 x 19 265.9 223.7 242.1 255.8 205.7 190.5 203.7 - 228.6 -6U, 3/4 x 19 265.9 336.0 242.1 255.8 318.0 190.5 316.0 - 228.6 -6U, 1/1 x 19 265.9 448.3 242.1 255.8 430.3 190.5 428.3 465.1 228.6 482.6The H and K dimensions are defined by the 19 rack mounting kit.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 25

  • Case size(inches)

    A B C D E F G H J K

    6U, 1/2 x 19 10.47 8.81 9.53 10.07 8.10 7.50 8.02 - 9.00 -6U, 3/4 x 19 10.47 13.23 9.53 10.07 12.52 7.50 12.4 - 9.00 -6U, 1/1 x 19 10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00 19.00The H and K dimensions are defined by the 19 rack mounting kit.

    5.2.3 Flush mounting dimensions

    CA

    B

    ED

    xx04000465.vsd

    Figure 6: Flush mounting

    Case sizeTolerance

    Cut-out dimensions (mm)A+/-1

    B+/-1

    C D

    6U, 1/2 x 19" 210.1 254.3 4.0-10.0 12.56U, 3/4 x 19" 322.4 254.3 4.0-10.0 12.56U, 1/1 x 19" 434.7 254.3 4.0-10.0 12.5E = 188.6 mm without rear protection cover, 229.6 mm with rear protection cover

    Section 5Installing the IED

    26 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 5.2.4 Side-by-side flush mounting dimensions

    xx06000182.vsd

    Figure 7: A 1/2 x 19 size IED 670 side-by-side with RHGS6.

    xx05000505.vsd

    B

    A

    C

    GD

    E

    F

    Figure 8: Panel-cut out dimensions for side-by-side flush mounting

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 27

  • 5.2.5 Wall mounting dimensions

    en04000471.vsd

    E

    A

    B

    CD

    Figure 9: Wall mounting

    Case size (mm) A B C D E6U, 1/2 x 19 292.0 267.1 272.8 390.0 243.06U, 3/4 x 19 404.3 379.4 272.8 390.0 243.06U, 1/1 x 19 516.0 491.1 272.8 390.0 243.0

    5.3 Mounting methods and details5.3.1 Mounting the IED

    Most of the IED 670s can be rack, flush or wall mounted with the use of differentmounting kits, see figure10. An additional box of type RHGS can be mounted to oneside of a 1/2 or 3/4 IED.

    Section 5Installing the IED

    28 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • The different mounting kits contain all parts needed including screws and assemblyinstructions. The following mounting kits are available: Flush mounting kit 19 Panel (rack) mounting kit Wall mounting kit Side-by-side mounting kit

    The same mounting kit is used for side-by-side rack mounting and side-by-side flushmounting.

    The mounting kits must be ordered separately when ordering an IED.They are available as options on the ordering sheet in Accessoriesfor IED 670, see section 0.

    Generally, all the screws included in delivered mounting kits are of Torx type and ascrewdriver of the same type is needed (Tx10, Tx15, Tx20 and Tx25).

    If other type of screws are to be used, be sure to use the dimensionsof the screws that are given in this guide.

    A B C D

    Figure 10: Different mounting methods for IED 670 DescriptionA Flush mountingB 19 Panel rack mountingC Wall mountingD Side-by-side rack or flush mounting

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 29

  • 5.3.2 Flush mounting5.3.2.1 Overview

    All IED sizes, 1/2 x 19, 3/4 x 19 and 1/1 x 19 and RHGS6 6U 1/4 x 19, cases,can be flush mounted. Only a single case can be mounted in each cut-out on the cubiclepanel, for class IP54 protection.The flush mounting kit are utilized for IEDs of sizes: 1/2 x 19, 3/4 x 19 and 1/1 x19 and are also suitable for mounting of RHGS6, 6U 1/4 x 19 cases.

    Flush mounting cannot be used for side-by-side mounted IEDs whenIP54 class must be fulfilled. Only IP20 class can be obtained whenmounting two cases side-by-side in one (1) cut-out.

    To obtain IP54 class protection, an additional factory mounted sealingmust be ordered when ordering the IED.

    5.3.2.2 Mounting procedure for flush mounting

    1

    35

    xx06000246.vsd

    4

    26

    7

    Figure 11: Flush mounting details.

    Section 5Installing the IED

    30 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • PosNo Description Quantity Type1 Sealing strip, used to

    obtain IP54 class. Thesealing strip is factorymounted between thecase and front plate.

    - -

    2 Fastener 4 -3 Groove - -4 Screw, self tapping 4 2,9x9,5 mm5 Joining point of sealing

    strip (rear view)- -

    6 Panel - -7 Screw 4 M5x25

    Procedure

    1. Cut an opening in the panel.See section "Flush mounting dimensions" regarding dimensions.

    2. Carefully press the sealing strip around the IEDs collar. Cut the end of thesealing strip a few mm to long to make the joining point (5) tight.The sealing strip is delivered with the mounting kit. The strip is long enoughfor the largest available IED.

    3. Insert the IED into the opening (cut-out) in the panel.4. Attach the fasteners to the IED.

    Insert the panel end of the fastener in the gap between the IED and the panel.Insert the rear end of the fastener into the groove. Insert from the rear side andlightly tighten the screw (4)Repeat this with the remaining fasteners.

    5. Fix the IED by tightening all four (7) screws against the panel.

    5.3.3 19 panel rack mounting5.3.3.1 Overview

    All IED sizes can be mounted in a standard 19 cubicle rack by using the for eachsize suited mounting kit which consists of two mounting angles and fastening screwsfor the angles. The mounting angles are reversible which enables mounting of IEDsize 1/2 x 19 or 3/4 x 19 either to the left or right side of the cubicle.

    Please note that the separately ordered rack mounting kit for side-by-side mounted IEDs, or IEDs together with RHGS cases, is to beselected so that the total size equals 19.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 31

  • When mounting the mounting angles, be sure to use screws thatfollows the recommended dimensions. Using screws with otherdimensions than the original may damage the PCBs inside the IED.

    5.3.3.2 Mounting procedure for 19 panel rack mounting

    xx04000452.vsd

    1a

    2

    1b

    Figure 12: 19 panel rack mounting details

    PosNo Description Quantity Type1a, 1b Mounting angels, which can be mounted, either to the

    left or right side of the case.2 -

    2 Screw 8 M4x6

    Procedure

    1. Carefully fasten the mounting angles (1a, 1b) to the sides of the IED.Use the screws (2) supplied in the mounting kit.

    2. Place the IED assembly in the 19 panel.3. Fasten the mounting angles with appropriate screws.

    Section 5Installing the IED

    32 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 5.3.4 Wall mounting5.3.4.1 Overview

    All case sizes, 1/2 x 19, 3/4 x 19 and 1/1 x 19, can be wall mounted. It is alsopossible to mount the IED on a panel or in a cubicle.

    When mounting the side plates, be sure to use screws that follows therecommended dimensions. Using screws with other dimensions thanthe original may damage the PCBs inside the IED.

    If fiber cables are bent too much, the signal can be weakened. Wallmounting is therefore not recommended for communication moduleswith fiber connection; Serial SPA/IEC 60870-5-103 and LONcommunication module (SLM), Optical Ethernet module (OEM) andLine data communication module (LDCM).

    5.3.4.2 Mounting procedure for wall mounting

    xx04000453.vsd

    1

    2

    34

    5

    6

    Figure 13: Wall mounting details.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 33

  • PosNo Description Quantity Type1 Bushing 4 -2 Screw 8 M4x103 Screw 4 M6x12 or

    corresponding4 Mounting bar 2 -5 Screw 6 M5x86 Side plate 2 -

    Procedure

    1. Mount the mounting bars onto the wall (4).See section "Wall mounting dimensions" for mounting dimensions.Depending on the wall different preparations may be needed like drilling andinserting plastic or expander plugs (concrete/plasterboard walls) or threading(metal sheet wall).

    2. Make all electrical connections to the IED terminal.It is much easier to do this without the unit in place.

    3. Mount the side plates to the IED.4. Mount the IED to the mounting bars.

    5.3.4.3 How to reach the rear side of the IEDThe IED can be equipped with a rear protection cover which is recommended to usewith this type of mounting. See figure 14.To reach the rear side of the IED, a free space of 80 mmis required on the unhingedside.

    Section 5Installing the IED

    34 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 80 mm

    View from above

    1

    en06000135.vsd

    3

    2

    Figure 14: How to reach the connectors on the rear side of the IED.

    PosNo Description Type1 Screw M4x102 Screw M5x83 Rear protection cover -

    Procedure

    1. Remove the inner screws (1), upper and lower on one side.2. Remove all three fixing screws (2), on the opposite side, from wall support.3. The IED can now be swung out for access to the connectors, after removing any

    rear protection.

    5.3.5 Side-by-side 19 rack mounting5.3.5.1 Overview

    IED case sizes, 1/2 x 19 or 3/4 x 19 and RHGS cases, can be mounted side-by-sideup to a maximum size of 19. For side-by-side rack mounting, the side-by-sidemounting kit together with the 19 rack panel mounting kit must be used. Themounting kit has to be ordered separately.

    When mounting the plates and the angles on the IED, be sure to usescrews that follows the recommended dimensions. Using screws withother dimensions than the original may damage the PCBs inside theIED.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 35

  • 5.3.5.2 Mounting procedure for side-by-side rack mounting

    xx04000456.vsd

    3

    4

    12

    Figure 15: Side-by-side rack mounting details.

    PosNo Description Quantity Type1 Mounting plate 2 -2, 3 Screw 16 M4x64 Mounting angle 2 -

    Procedure

    1. Place the two IEDs next to each other on a flat surface.2. Fasten a side-by-side mounting plate (1).

    Use four of the delivered screws (2, 3).3. Carefully turn the two IEDs up-side down.4. Fasten the second side-by-side mounting plate.

    Use the remaining four screws.5. Carefully fasten the mounting angles (4) to the sides of the IED.

    Use the screws available in the mounting kit.6. Place the IED assembly in the rack.7. Fasten the mounting angles with appropriate screws.

    5.3.5.3 IED 670 mounted with a RHGS6 caseAn 1/2 x 19 or 3/4 x 19 size IED can be mounted with a RHGS (6 or 12 dependingon IED size) case. The RHGS case can be used for mounting a test switch of typeRTXP 24. It also has enough space for a terminal base of RX 2 type for mounting of,for example, a DC-switch or two trip relays.

    Section 5Installing the IED

    36 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • xx06000180.vsd

    8 88

    7

    5

    6

    3

    4

    2

    7

    5

    6

    7

    5

    6

    3

    4

    2

    3

    4

    2

    1

    1

    1

    2

    1 1

    1

    8

    7

    5

    6

    3

    4

    2

    2

    2

    1

    Figure 16: IED 670 (1/2 x 19) mounted with a RHGS6 case containing a testswitch module equipped with only a test switch and a RX2 terminalbase.

    5.3.6 Side-by-side flush mounting5.3.6.1 Overview

    It is not recommended to flush mount side by side mounted cases if IP54 is required.If your application demands side-by-side flush mounting, the side-by-side mountingdetails kit and the 19 panel rack mounting kit must be used. The mounting kit hasto be ordered separately. The maximum size of the panel cut out is 19.

    With side-by-side flush mounting installation, only IP class 20 isobtained. To reach IP class 54, it is recommended to mount the IEDsseparately. For cut out dimensions of separately mounted IEDs, seesection "Flush mounting".

    When mounting the plates and the angles on the IED, be sure to usescrews that follows the recommended dimensions. Using screws withother dimensions than the original may damage the PCBs inside theIED.

    Please contact factory for special add on plates for mounting FTswitches on the side (for 1/2 19" case) or bottom of the relay.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 37

  • 5.3.6.2 Mounting procedure for side-by-side flush mounting

    xx06000181.vsd

    1 2

    3

    4

    Figure 17: Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x19 IED).

    PosNo Description Quantity Type1 Mounting plate 2 -2, 3 Screw 16 M4x64 Mounting angle 2 -

    Procedure

    1. Make a panel cut-out.For panel cut out dimension, see section "Side-by-side flush mountingdimensions".

    2. Carefully press the sealing strip around the IED collar. Cut the end of the sealingstrip a few mm to long to make the joining point tight.Repeat the same procedure with the second case.The sealing strip is delivered with the mounting kit. The strip is long enoughfor the largest available IED.

    3. Place the two IEDs next to each other on a flat surface.4. Fasten a side-by-side mounting plate (1).

    Use four of the delivered screws (2, 3).5. Carefully turn the two IEDs up-side down.6. Fasten the second side-by-side mounting plate.

    Use the remaining four screws.7. Carefully fasten the mounting angles (4) to the sides of the IED.

    Section 5Installing the IED

    38 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Use the fixing screws available in the mounting kit.8. Insert the IED into the cut-out.9. Fasten the mounting angles with appropriate screws.

    5.4 Making the electrical connection5.4.1 IED connectors5.4.1.1 Overview

    The quantity and designation of connectors depend upon the type and size of the IED.The rear cover plates are prepared with space for the maximum of HW options foreach case size and the cut-outs that are not in use are covered with a plate from factory.

    Table 1: Basic modules, always includedModule DescriptionCombined backplane module (CBM) A backplane PCB that carries all internal signals

    between modules in an IED. Only the TRM is notconnected directly to this board.

    Universal backplane module (UBM) A backplane PCB that forms part of the IEDbackplane with connectors for TRM, ADM etc.

    Power supply module (PSM) Including a regulated DC/DC converter thatsupplies auxiliary voltage to all static circuits. An internal fail alarm output is available.

    Numerical module (NUM) Module for overall application control. Allinformation is processed or passed through thismodule, such as configuration, settings andcommunication.

    Local Human machine interface (LHMI) The module consists of LED:s, an LCD, a pushbutton keyboard and an ethernet connector used toconnect a PC to the IED.

    Transformer input module (TRM) Transformer module that galvanically separates theinternal circuits from the VT and CT circuits. It has12 analog inputs.

    Analog digital conversion module (ADM) Slot mounted PCB with A/D conversion.

    Table 2: Application specific modulesModule DescriptionBinary input module (BIM) Module with 16 optically isolated binary inputsBinary output module (BOM) Module with 24 single outputs or 12 double-pole

    command outputs including supervision functionBinary I/O module (IOM) Module with 8 optically isolated binary inputs, 10

    outputs and 2 fast signalling outputs.Table continued on next page

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 39

  • Module DescriptionLine data communication modules (LDCM) (shortrange, medium range, long range, X21)

    Modules used for digital communication to remoteterminal.

    Serial SPA/LON/IEC 60870-5-103communication modules (SLM)

    Used for SPA/LON/IEC 608705103communication

    Optical ethernet module (OEM) PMC board for IEC 61850 based communication.mA input module (MIM) Analog input module with 6 independent,

    galvanically separated channels.GPS time synchronization module (GSM) Used to provide the IED with GPS time

    synchronization.Static output module (SOM) Module with 6 fast static outputs and 6 change over

    output relays.IRIG-B Time synchronization module Module with 2 inputs. One is used for handling both

    pulse-width modulated signals and amplitudemodulated signals and one is used for optical inputtype ST for PPS time synchronization.

    5.4.1.2 Front side connectors

    Figure 18: IED front side connectorPosNo Description1 IED serial communication port with RJ45 connector2 Ethernet cable with RJ45 connectors

    Section 5Installing the IED

    40 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • The cable between PC and the IED serial communication port shallbe a crossed-over Ethernet cable with RJ45 connectors. If theconnection are made via a hub or switch, a standard Ethernet cablecan be used.

    5.4.1.3 Rear side connectors

    Table 3: Designations for 1/2 x 19 casing with 1 TRM slot

    Module Rear Positions PSM X11 BIM, BOM, SOM or IOM X31 and X32 etc. to X51 and

    X52

    BIM, BOM, SOM, IOM orGSM

    X51, X52

    SLM X301:A, B, C, D IRIG-B 1) X302 OEM X311:A, B, C, D RS485 or LDCM 2) 3) X312 LDCM 2) X313 TRM X401 1) IRIG-B installation, when included in seat P30:2

    2) LDCM installation sequence: P31:2 or P31:33) RS485 installation, when included in seat P31:2Note!1 One LDCM can be included depending of availability ofIRIG-B respective RS485 modules.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 41

  • Table 4: Designations for 3/4 x 19 casing with 1 TRM slot

    Module Rear Positions PSM X11 BIM, BOM, SOM, IOM or

    MIMX31 and X32 etc. toX101 and X102

    BIM, BOM, SOM, IOM,MIM or GSM

    X101, X102

    SLM X301:A, B, C, D IRIG-B or LDCM 1) 2) X302 LDCM 2) X303 OEM X311:A, B, C, D RS485 or LDCM 2) 3) X312 LDCM 2) X313 TRM X401 1) IRIG-B installation, when included in seat P30:2

    2) LDCM installation sequence: P31:2, P31:3, P30:2and P30:33) RS482 installation, when included in seat P31:2Note!2-4 LDCM can be included depending of availabilityof IRIG-B respective RS485 modules.

    Section 5Installing the IED

    42 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Table 5: Designations for 3/4 x 19 casing with 2 TRM slot

    Module Rear Positions PSM X11 BIM, BOM, SOM, IOM or

    MIMX31 and X32 etc. to X71 andX72

    BIM, BOM, SOM, IOM,MIM or GSM

    X71, X72

    SLM X301:A, B, C, D IRIG-B or LDCM 1,2) X302 LDCM 2) X303 OEM X311:A, B, C, D RS485 or LDCM 2) 3) X312 LDCM 2) X313 LDCM 2) X322 LDCM 2) X323 TRM 1 X401 TRM 2 X411 1) IRIG-B installation, when included in seat P30:2

    2) LDCM installation sequence: P31:2, P31:3, P32:2, P32:3,P30:2 and P30:33) RS485 installation, when included in seat P31:2Note!2-4 LDCM can be included depending of availability of IRIG-B respective RS485 modules.

    Table 6: Designations for 1/1 x 19 casing with 1 TRM slot

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 43

  • Module Rear Positions PSM X11 BIM, BOM, SOM,

    IOM or MIMX31 and X32 etc. to X161 andX162

    BIM, BOM, SOM,IOM, MIM or GSM

    X161, X162

    SLM X301:A, B, C, D IRIG-B or LDCM

    1,2)X302

    LDCM 2) X303 OEM X311:A, B, C, D RS485 or LDCM 2)

    3)X312

    LDCM 2) X313 TRM X401 1) IRIG-B installation, when included in seat P30:2

    2) LDCM installation sequence: P31:2, P31:3, P30:2and P30:33) RS485 installation, when included in seat P31:2Note!2-4 LDCM can be included depending of availabilityof IRIG-B respective RS485 modules.

    Section 5Installing the IED

    44 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Table 7: Designations for 1/1 x 19 casing with 2 TRM slots

    Module Rear Positions PSM X11 BIM, BOM, SOM,

    IOM or MIMX31 and X32 etc. to X131 andX132

    BIM, BOM, SOM,IOM, MIM or GSM

    X131, X132

    SLM X301:A, B, C, D IRIG-B or LDCM

    1,2)X302

    LDCM 2) X303 OEM X311:A, B, C, D RS485 or LDCM 2)

    3)X312

    LDCM 2) X313 LDCM 2) X322 LDCM 2) X323 TRM 1 X401 TRM 2 X411 1) IRIG-B installation, when included in seat P30:2

    2) LDCM installation sequence: P31:2, P31:3, P32:2,P32:3, P30:2 and P30:33) RS485 installation, when included in seat P31:2Note!2-4 LDCM can be included depending of availabilityof IRIG-B respective RS485 modules.

    5.4.1.4 Connection diagrams

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 45

  • Figure 19: Transformerinputmodule(TRM)

    CT/VT-input designation according to figure 19 Current/voltage

    configuration(50/60 Hz)

    AI01

    AI02

    AI03

    AI04

    AI05

    AI06

    AI07 AI08 AI09 AI10 AI11 AI12

    12I (1A) 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 12I (5A) 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 9I (1A) and 3U 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-22

    0V110-220V

    110-220V

    9I (5A) and 3U 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V

    110-220V

    110-220V

    5I (1A) and 4I (5A)and 3U

    1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V

    110-220V

    110-220V

    7I (1A) and 5U 1A 1A 1A 1A 1A 1A 1A 110-220V

    110-220V

    110-220V

    110-220V

    110-220V

    7I (5A) and 5U 5A 5A 5A 5A 5A 5A 5A 110-220V

    110-220V

    110-220V

    110-220V

    110-220V

    6I (1A) and 6U 1A 1A 1A 1A 1A 1A 110-220V

    110-220V

    110-220V

    110-220V

    110-220V

    110-220V

    6I (5A) and 6U 5A 5A 5A 5A 5A 5A 110-220V

    110-220V

    110-220V

    110-220V

    110-220V

    110-220V

    6I (1A) 1A 1A 1A 1A 1A 1A - - - - - - 6I (5A) 5A 5A 5A 5A 5A 5A - - - - - -

    Section 5Installing the IED

    46 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Figure 20: Binary input module (BIM).Input contacts named XAcorresponds to rear positionX31, X41, etc. and inputcontacts named XB to rearposition X32, X42, etc.

    Figure 21: mA input module (MIM)

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 47

  • Figure 22: Communication interfaces (OEM, LDCM, SLM and HMI)Note to figure 221) Rear communication port SPA/IEC 61850-5-103, ST-connector for glass alt. HFBR Snap-in connector for plastic as ordered2) Rear communication port LON, ST connector for glass alt. HFBR Snap-in connector for plastic as ordered3) Rear communication port RS485, terminal block4) Time synchronization port IRIG-B, BNC-connector5) Time synchronization port PPS or Optical IRIG-B, ST-connector6) Rear communication prot IEC 61850, ST-connector7) Rear communication port C37.94, ST-connector8) Front communication port Ethernet, RJ45 connector9) Rear communication port 15-pole female micro D-sub, 1.27 mm (0.050") pitch10) Rear communication port, terminal block

    Section 5Installing the IED

    48 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Figure 23: Power supply module (PSM)

    Figure 24: GPS time synchronization module(GSM)

    Figure 25: Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41,etc. and output contacts named XB to rear position X32, X42, etc.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 49

  • Figure 26: Static output module (SOM)

    Figure 27: Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, etc.and output contacts named XB to rear position X32, X42, etc.

    Section 5Installing the IED

    50 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 5.4.1.5 Connection examplesWARNING! USE EXTREME CAUTION! Dangerously highvoltages might be present on this equipment, especially on the platewith resistors. Do any maintenance ONLY if the primary objectprotected with this equipment is de-energized. If required by nationallow/standard enclose the plate with resistors with a protective coveror in a separate box!

    Connections for three-phase high impedance differential protectionGenerator, reactor or busbar differential protection is a typical application for three-phase high impedance differential protection. Typical CT connections for three-phasehigh impedance differential protection scheme with 670 series are shown in figureCT connections for High Impedance Differential Protection

    L1(A)

    L2(B)

    L3(C)

    Protected Object

    CT 1200/1Star/Wye

    Connected

    L1(A)

    L2(B)

    L3(C)

    CT 1200/1Star/Wye

    Connected

    789

    101112

    123456

    AI01 (I)

    AI02 (I)

    AI03 (I)

    AI04 (I)

    AI05 (I)

    AI06 (I)

    78

    6

    9

    IED 670

    X1

    R4 R5 R6

    12

    12

    12

    11 12 13 14

    U U U R11

    342

    13R2

    2 4

    13R3

    2 41 2 3 4 5 6 7

    L1 (A)L2 (B)L3 (C)N

    3-Ph Plate with Metrosils and Resistors

    23

    5

    4

    10

    X X

    L1 (A)L2 (B)L3 (C)N

    1

    Figure 28: CT connections for High Impedance Differential Protection

    Number 1 shows the scheme earthing point. Note that it is of outmost importanceto insure that only one earthing point exist in such scheme.

    Number 2 shows the three-phase plate with setting resistors and metrosils. Number 3 shows the necessary connection for three-phase metrosil set. Shown

    connections are applicable for both types of three-phase plate. Number 4 shows the position of optional test switch for secondary injection into

    the high impedance differential relay. Number 5 shows the necessary connection for setting resistors. Shown

    connections are applicable for both types of three-phase plate.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 51

  • Number 6 shows that the factory made star point on a three-phase setting resistorset shall be removed for installations with 670 series. This star point is requiredfor RADHA schemes only!

    Number 7 shows how to connect three individual phase currents for highimpedance scheme to three CT inputs in IED 670.

    Number 8 shows a TRM module where these current inputs are located. Notethat the CT ratio for high impedance differential protection application must beset as one! Thus for main CTs with 1A secondary rating the following settingvalues shall be entered: CTprim=1A and CTsec=1A; while for main CTs with5A secondary rating the following setting values shall be entered: CTprim=5Aand CTsec=5A. The parameter CTStarPoint shall be always left to the defaultvalue ToObject.

    Number 9 shows three connections made in Signal Matrix Tool (i.e. SMT) whichconnect these three current inputs to first three input channels of thepreprocessing function block (10). For high impedance differential protectionpreprocessing function block in 3ms task shall be used.

    Number 10 shows the preprocessing block which has a task to digitally filter theconnected analogue inputs. Preprocessing block outputs AI1, AI2 and AI3 shallbe connected to three instances of high impedance differential protectionfunction blocks (e.g. HZD1, HZD2 and HZD3 function blocks in theconfiguration tool).

    Connections for three-phase high impedance differential protectionRestricted earth fault (REF) protection is a typical application for one-phase highimpedance differential protection. Typical CT connections for high impedance basedREF protection scheme with 670 series are shown in figure CT connections forRestricted Earth Fault Protection

    Section 5Installing the IED

    52 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • L1(A)

    L2(B)

    L3(C)

    Protected Object

    CT 1500/5Star/Wye

    Connected

    789

    101112

    123456

    AI01 (I)

    AI02 (I)

    AI03 (I)

    AI04 (I)

    AI05 (I)

    AI06 (I)

    6

    7

    8

    IED 670

    X1

    R11

    2

    4 5

    U R21

    342

    1 2 3

    N

    1-Ph Plate with Metrosil and Resistor

    23

    5

    4

    9

    N

    L1(A)

    L2(B)

    L3(C)

    CT 15

    00/5

    1

    en07000194.vsd

    Figure 29: CT connections for Restricted Earth Fault Protection

    Number 1 shows the scheme earthing point. Note that it is of outmost importanceto insure that only one earthing point exist in such scheme.

    Number 2 shows the one-phase plate with setting resistor and metrosil. Number 3 shows the necessary connection for the metrosil. Shown connections

    are applicable for both types of one-phase plate. Number 4 shows the positionof optional test switch for secondary injection into the high impedancedifferential relay.

    Number 4 shows the position of optional test switch for secondary injection intothe high impedance differential relay.

    Number 5 shows the necessary connection for setting resistor. Shownconnections are applicable for both types of one-phase plate.

    Number 6 shows how to connect the REF high impedance scheme to one CTinput in IED 670.

    Number 7 shows a TRM module where this current input is located. Note thatthe CT ratio for high impedance differential protection application must be setas one! Thus for main CTs with 1A secondary rating the following setting valuesshall be entered: CTprim=1A and CTsec=1A; while for main CTs with 5Asecondary rating the following setting values shall be entered: CTprim=5A andCTsec=5A. The parameter CTStarPoint shall be always left to the default valueToObject.

    Number 8 shows a connection made in Signal Matrix Tool (i.e. SMT) whichconnects this current input to first input channel of the preprocessing functionblock (10). For high impedance differential protection preprocessing functionblock in 3ms task shall be used.

    Number 9 shows the preprocessing block which has a task to digitally filter theconnected analogue inputs. Preprocessing block output AI1 shall be connected

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 53

  • to one instances of high impedance differential protection function block (e.g.HZD1 function block in the configuration tool).

    5.4.2 Connecting to protective earthConnect the earthing screw (pos 1 in figure 30) on the rear of the IED unit to theclosest possible earthing point in the cubicle. Electrical codes and standards requirethat protective earth cables are green/yellow conductors with a cross section area ofat least 2.5 mm2 (AWG14). There are several protective earthing screws on an IED.The Power supply module (PSM), Transformer input modules (TRM) and theenclosure are all separately earthed, see figure 30 below.The cubicle must be properly connected to the station earthing system. Use aconductor with a core cross section area of at least 4 mm2 (AWG 12).

    1

    en05000509.vsd

    3

    2

    Figure 30: Rear view of IED with one TRM showing earthing points.PosNo Description1 Main protective earth to chassis2 Earthing screw to Power supply module (PSM)3 Earthing screw to Transformer input module (TRM). (There is one earth connection per TRM)

    Use the main protective earth screw (1) for connection to the stationsearthing system. Earthing screws for PSM module (2) and TRMmodule (3) must be fully tightened to secure protective earthconnection of these modules.

    Section 5Installing the IED

    54 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 5.4.3 Connecting the power supply moduleThe wiring from the cubicle terminal block to the IED terminals (see figure 23 forPSM connection diagram) must be made in accordance with the establishedguidelines for this type of equipment. The wires from binary inputs and outputs andthe auxiliary supply must be routed separated from the current transformer cablesbetween the terminal blocks of the cubicle and the IEDs connections. The connectionsare made on connector X11. For location of connector X11, refer to section "Rearside connectors".

    5.4.4 Configuration for analog CT inputsThe secondary rated current of the CT (i.e. 1A or 5A) determines the choice of TRMin the IED. Two TRMs are available, One is dimensioned for an input current of 5Aand the other for an input of 1A. If the CT rated secondary current does not matchthe TRM input current rating adjustments can be made in settings depending on thetolerance of the TRM.

    5.4.5 Connecting to CT and VT circuitsCTs and VTs are connected to the 24pole connector of the Transformer input module(TRM) on the rear side of the IED. Connection diagram for TRM is shown infigure 19.

    Use a solid conductor with a cross section area between 2.5-6 mm2 (AWG14-10) ora stranded conductor with a cross section area between 2.5-4 mm2 (AWG14-12).If the IED is equipped with a test-switch of type RTXP 24 COMBIFLEX wires with20 A sockets must be used to connect the CT and VT circuits.Connectors X401 and X402 (for location see section "Rear side connectors") forcurrent and voltage transformer circuits are so called feed-through terminal blocksand are designed for conductors with cross sectional area up to 4 mm2 (AWG 12).The screws used to fasten the conductors should be tightened with a torque of 1Nm.

    5.4.6 Connecting the binary input and output signalsAuxiliary power and signals are connected using voltage connectors. Signal wires areconnected to a female connector, see figure 31, which is then plugged into thecorresponding male connector, see figure 32, located at the rear of the IED. Forlocation of BIM, BOM, IOM and SOM refer to section "Rear side connectors".Connection diagrams for BIM, BOM, IOM and SOM are shown in figure 20,figure 25, figure26 and figure 27.If the IED is equipped with a test-switch of type RTXP 24 COMBIFLEX wires with20 A sockets, 1.5mm (AWG16) conductor area must be used to connect the auxiliarypower.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 55

  • Procedure

    1. Connect signals to the female connectorAll wiring to the female connector should be done before it is plugged into themale part and screwed to the case. The conductors can be of rigid type (solid,stranded) or of flexible type.The female connectors accept conductors with a cross section area of 0.2-2.5mm2 (AWG 24-14). If two conductors are used in the same terminal, themaximum permissible cross section area is 0.2-1 mm2 (AWG 24-18 each).If two conductors, each with area 1.5 mm2 (AWG 16) need to be connected tothe same terminal, a ferrule must be used, see figure 33. This ferrule, is appliedwith the by Phoenix recommended crimping tool, see figure "". No solderingis needed. Wires with a smaller gauge can be inserted directly into the femaleconnector receptacle and the fastening screw shall be tightened with a torque of0.4 Nm (This torque applies to all binary connectors).

    2. Plug the connector to the corresponding back-side mounted male connector3. Lock the connector by fastening the lock screws

    xx02000742.vsd

    Figure 31: A female connector

    Figure 32: Board with male connectors

    Section 5Installing the IED

    56 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • 12

    1

    xx06000168.vsd

    Figure 33: Cable connectorsPosNo Description1 Is ferrule,2 A bridge connector, is used to jump terminal points in a connector.

    5.4.7 Making the screen connectionWhen using screened cables always make sure screens are earthed and connectedaccording to applicable engineering methods. This may include checking forappropriate earthing points near the IED, for instance, in the cubicle and/or near thesource of measuring. Ensure that earth connections are made with short (max. 10 cm)conductors of an adequate cross section, at least 6 mm2 (AWG10) for single screenconnections.

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 57

  • en06000190.vsd

    Rx

    TxSc

    Lc

    Tx

    RxSc

    LcCc

    IED ExternalEquipment

    1

    3

    22

    Figure 34: Communication cable installation.PosNo Description1 Outer shield2 Protective earth screw3 Inner shield

    Inner shielding of the cable shall be grounded at the externalequipment end only. At the Relay terminal end, the inner shield mustbe isolated from protective ground.

    5.5 Optical connections5.5.1 Connecting station communication interfaces (OEM and

    SLM)The IED can, if ordered accordingly, be equipped with an optical ethernet module(OEM, see figure 22), needed for IEC 61850 communication and a serialcommunication module (SLM, see figure 22) for LON, SPA and IEC 608705103communication. In such cases optical ports are provided on the rear side of the casefor connection of the optical fibers. For location of OEM and SLM, refer tosection "Rear side connectors". Optical ports X311: A, B (Tx, Rx) and X311: C, D (Tx, Rx) on the OEM module

    are used for IEC 61850 communication. Connectors are of ST type. When the

    Section 5Installing the IED

    58 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • optical ethernet module is used, the protection plate for the galvanic connectionmust not be removed.

    Optical port X301: A, B (Tx, Rx) on the SLM module is used for SPA or IEC60870-5-103 communication. Connectors are of ST type (glass) or HFBR Snapin (plastic).

    Optical port X301: C, D (Tx, Rx) on the SLM module is used for LONcommunication. Connectors are of ST type (glass) or HFBR Snap in (plastic).

    Connectors are generally color coded; connect blue or dark grey cable connectors toblue or dark grey (receive) back-side connectors. Connect black or grey cableconnectors to black or grey (transmit) back-side connectors.

    The fiber optical cables are very sensitive to handling. Do not bendtoo sharply. The minimum curvature radius is 15 cm for the plasticfiber cables and 25 cm for the glass fiber cables. If cable straps areused to fix the cables, apply with loose fit.Always hold the connector, never the cable, when connecting ordisconnecting optical fibers. Do not twist, pull or bend the fiber.Invisible damage may increase fiber attenuation thus makingcommunication impossible.

    Please, strictly follow the instructions from the manufacturer for eachtype of optical cables/connectors.

    5.5.2 Connecting remote communication interfaces (LDCM)The Line Data Communication Module (LDCM, see figure 22) is the hardware usedfor the transfer of binary and analog signal data between IEDs in different protectionschemes on the IEEE/ANSI C37.94 protocol. The optical ports on the rear side of theIED are X302, X303, X312 and X313. For location of LDCM module, refer tosection "Rear side connectors".

    5.6 Galvanic X.21 line data communication (X.21-LDCM)

    5.6.1 Connecting Galvanic X.21 line data communication module(X.21 LDCM)The Galvanic X.21 line data communication module (X.21 LDCM, see figure 22) isthe hardware used for the transfer of binary and analog signal data between IEDs indifferent protection schemes via telecommunication equipment, for example leased

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 59

  • telephone lines. For location of X-21 LDCM module, refer to section "Rear sideconnectors".The galvanic X.21 line data communication module uses a ABB specific PC*MIPType II format.

    C

    en07000196.vsd

    Figure 35: Overview of the X.21 LDCM module

    1 3

    2 en07000195.vsd

    Figure 36: The X.21 LDCM module external connectors

    1. Ground selection connector for IO, screw terminals, 2-pole2. Ground pin3. X.21: Micro D-sub 15 pole female connector according to the V11 (X.27)

    balanced version

    Soft groundTo avoid ground loops when the grounds are connected, a soft ground connection forthe IO-ground can be used. This is handled in the ground selection connector.

    Section 5Installing the IED

    60 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • Three different kinds of grounding principles can be set:1. No ground - leave the connector without any connection2. Direct ground - connect the ground pin directly to earth3. Soft ground - connect the two pins to each other

    X.21 connectorTable 8: Pinout for the X.21 communication connector

    Pin number Signal1 Shield (ground)2 TXD A3 Control A4 RXD A6 Signal timing A8 Ground9 TXD B10 Control B11 RXD B13 Signal timing B5,7,12,14,15 Not used

    5.7 Installing the serial communication cable forRS485

    5.7.1 RS485 serial communication module

    RS485PWBScrew

    terminalX1

    Backplate

    Screwterminal

    X3

    Anglebracket

    12456

    3

    12

    en07000140.vsd

    Figure 37: The connection plate to the backplate with connectors and screws.This figure also shows the pin numbering from the component side

    Section 5Installing the IED

    REC 670 Installation and commissioning manual1MRK511189-UEN rev. B 61

  • Pin Name 2-wire Name 4-wire Descriptionx3:1 soft groundx3:2 soft groundx1:1 RS485 + TX+ Receive/transmit high

    or transmit highx1:2 RS485 TX- Receive/transmit low or

    transmit lowx1:3 Term T-Term Termination resistor for

    transmitter (andreceiver in 2-wire case)(connect to TX+)

    x1:4 reserved R-Term Termination resistor forreceiver (connect to RX+)

    x1:5 reserved RX- Receive lowx1:6 reserved RX+ Receive high2wire: Connect pin X1:1 to pin

    X1:6 and pin X1:2 to pinX1:5.

    Termination (2-wire): Connect pin X1:1 to pinX1:3

    Termination (4-wire): Connect pin X1:1 to pinX1:3 and pin X1:4 to pinX1:6

    The distance between earth points should be < 1200 m (3000 ft), see figure 38 and39. Only the outer shielding is connected to the protective earth at the terminal. Theinner and outer shieldings are connected to the protective earth at the externalequipment. Use insulating tape for the inner shield to prevent contact with theprotective earth. Make sure that the terminals are properly earthed with as shortconnections as possible from the earth screw, for example to an earthed frame.The terminal and the external equipment should preferably be connected to the samebattery.

    Section 5Installing the IED

    62 Installation and commissioning manual1MRK511189-UEN rev. B REC 670

  • en07000141.vsd

    Cc Cc1)

    ExternalEquipment (PC)

    PE 1) 3)

    2)

    PE

    IED

    X11 65432

    IED

    1 65432X1

    PEPE

    Figure 38: Communication cable installation, 2-wire.Where:1 The inner shields shall be connected together (with an isolated terminal block) and only have

    one earthing point in the whole system, preferably at the external equipment (PC).The outer shield shall be connected to Protective Earth (PE) in every cable end i.e. to PE atall relay terminals and to PE at External equipment (PC). The first