Ice Thermal Storage Systems - Ashrae Bi-State

115
Ice Thermal Storage Systems Greg Henderson Director, Global Thermal Storage

Transcript of Ice Thermal Storage Systems - Ashrae Bi-State

Page 1: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage Systems

Greg Henderson

Director, Global Thermal Storage

Page 2: Ice Thermal Storage Systems - Ashrae Bi-State

Agenda

• Ice storage basics

• Ice storage design considerations

– Full and partial storage systems

– Internal and external melt systems

• Ice storage installations and applications

Page 3: Ice Thermal Storage Systems - Ashrae Bi-State
Page 4: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Build on Ice Coil Tube

Page 5: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Build on Ice Coil

Page 6: Ice Thermal Storage Systems - Ashrae Bi-State
Page 7: Ice Thermal Storage Systems - Ashrae Bi-State

What is Ice Storage?

• Ice Storage is the process of using a chiller or refrigeration plant to build ice during off-peak hours to serve part or all of the on-peak cooling requirement

Page 8: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage

How does it work?

Page 9: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

Typical Cooling Load Profile

Page 10: Ice Thermal Storage Systems - Ashrae Bi-State

Conventional System

Chiller

Cooling Load

Page 11: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage System

Ice Storage TankChiller

Cooling Load

Page 12: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

Ice Storage Cycle

Ice Storage

Cycle

Ice Storage

Cycle

Page 13: Ice Thermal Storage Systems - Ashrae Bi-State

Advantages of Thermal Energy Storage

• Reduced equipment costs

• Reduced energy and operating costs

• Increased flexibility to adapt to changing utility structures and requirements

• Reduces need for new power plants

Page 14: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Po

wer

(Meg

aw

att

s)

Typical Daily Utility Load Curve

Demand Charges

High Time of Day Rates

Total Utility Capacity

Page 15: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

Ice Storage Cycle

Ice Storage

Cycle

Ice Storage

Cycle

Demand Charges

High Time of Day Rates

Page 16: Ice Thermal Storage Systems - Ashrae Bi-State
Page 17: Ice Thermal Storage Systems - Ashrae Bi-State
Page 18: Ice Thermal Storage Systems - Ashrae Bi-State

0

20

40

60

80

100

M 2 4 6 8 10 N 14 16 18 20 22

Time of Day

% G

en

era

tio

n

0

20

40

60

80

100

M 2 4 6 8 10 N 14 16 18 20 22

Time of Day

% G

en

era

tio

nElectric Generation Fuel Sources

Hydro-electric 0.2¢/kWh

Nuclear 0.4¢/kWh

Coal-fired steam 2.5¢/kWh

Combined cycle 3.0¢/kWh

Oil-fired steam 3.5¢/kWh

Diesel 6.5¢/kWh

Comb. turbine 7.0¢/kWhThe

StorageShift

Page 19: Ice Thermal Storage Systems - Ashrae Bi-State

Thermal Storage System Environmental Advantages

• Require less kWh than conventional systems

• Utilize efficient power and produce fewer carbon dioxide emissions

• Energy line losses at night are 4% to 5% lower than during the daytime

Source: Source Energy and Environmental Impacts of Thermal Energy Storage, California Energy Commission - February 1996

Page 20: Ice Thermal Storage Systems - Ashrae Bi-State

Advantages of Ice Thermal Storage

• Reduced equipment costs

• Reduced energy and operating costs

• Colder supply water temperature

Page 21: Ice Thermal Storage Systems - Ashrae Bi-State

Advantages of Ice Thermal Storage

• Reduced equipment costs

– Only ~60% of chillers and heat rejection equipment required

– Requires only 1/4 to 1/6 of the space required for chilled water storage (~3Ft3/Ton-Hour)

– Requires less chiller plant plan area than instantaneous chiller system

Page 22: Ice Thermal Storage Systems - Ashrae Bi-State

30,000 RT Output

16,000 RT Heat Rejection

Page 23: Ice Thermal Storage Systems - Ashrae Bi-State

Advantages of Ice Thermal Storage

• Reduced equipment costs

• Reduced energy and operating costs

• Colder supply water temperature

Page 24: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal StorageUses Less Energy

• During daytime, chillers operate at higher supply temperatures and greater efficiency when piped upstream of the ice storage

• At night, chillers operate when ambient temperatures are lower

• Pump and fan energy can be less when colder system supply temperatures are used

Page 25: Ice Thermal Storage Systems - Ashrae Bi-State

EER of Air Cooled Chillers*

6

8

10

12

14

16

20 25 30 35 40 45 50 55

Leaving CHW

EE

R

95 Air 85 Air 75 Air

* includes heat rejection

75

85

95

“Normal” Design Point Pre-cooling

Ice-Making

Page 26: Ice Thermal Storage Systems - Ashrae Bi-State

EER of Water Cooled Chillers*

10

12

14

16

18

20

20 25 30 35 40 45 50 55

Leaving CHW

EE

R

85 80 75

* excludes heat rejection

Pre-cooling“Normal”

Design Point

Ice-Making

75

80

85

Page 27: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage Reduces Operating Costs

• Reduces air conditioning kW demand by approximately 40%

• Reduces air conditioning kWh by up to approximately 15%

• Reduces electric utility costs

– Large percentage of energy usage is at night

– Daytime energy costs 2 to 5 times more than night time energy

Page 30: Ice Thermal Storage Systems - Ashrae Bi-State

LEED Criteria

• Sustainable sites (14 possible points)

• Water efficiency (5 possible points)

• Materials and resources (13 possible points)

• Energy and atmosphere (17 possible points)

– Ozone depletion

– Optimize energy performance• Cost based analysis vs. ASHRAE 90.1

• Indoor air quality (15 possible points)

• Innovation & design process (5 possible points)

Page 31: Ice Thermal Storage Systems - Ashrae Bi-State

Advantages of Ice Thermal Storage

• Reduced equipment costs

• Reduced energy and operating costs

• Colder supply water temperature

Page 32: Ice Thermal Storage Systems - Ashrae Bi-State

Advantages of Cold Supply Water Temperature

• Smaller distribution pumps and piping

• Reduced pumping power

• Allows for economical building isolation (indirect interface) with smaller heat exchangers

• Provides better dehumidification and indoor air quality(IAQ)– 78°F (25.5°C) at 40% RH is more comfortable

than 76°F (24.4°C) at 50% RH

• Cold air distribution

Page 33: Ice Thermal Storage Systems - Ashrae Bi-State
Page 34: Ice Thermal Storage Systems - Ashrae Bi-State

Burj Dubai Tower

• Will become world’s tallest building at over 180 floors

• Currently at 156 floors

• 41,600 ton-hours

Page 35: Ice Thermal Storage Systems - Ashrae Bi-State

Taipei 101

• Currently the world’s tallest building at 101 floors

• 36,400 ton-hours

Page 36: Ice Thermal Storage Systems - Ashrae Bi-State

7th & 8th floors

37.8 F (3 C)

42nd floor

39.2 F (4 C)

74th floor

41.0 F (5 C)

Taipei 101

Page 37: Ice Thermal Storage Systems - Ashrae Bi-State

Factors Favorable forIce Storage Systems

• Loads are of short duration

– Schools

• Loads occur infrequently

– Churches

– Sports venues

• Loads are cyclical in nature

– Process or batch cooling

Page 38: Ice Thermal Storage Systems - Ashrae Bi-State

Factors Favorable forIce Storage Systems

• Loads are not well matched to availability of the energy source

• Energy costs are time-dependent

– Time-of-use energy rates

• Energy supply is limited

– Demand charges for peak energy use

• Utility rebates, tax credits, or other economic incentives are provided for the use of load-shifting equipment

Page 39: Ice Thermal Storage Systems - Ashrae Bi-State

Potential Ice Storage Projects

• Commercial A/C and industrial

– Schools

– Hospitals

– Office buildings

– Internet data centers

– Hotels

– Airports

– Sports venues

– Manufacturing plants

Page 40: Ice Thermal Storage Systems - Ashrae Bi-State

Potential Ice Storage Projects

• Commercial A/C and industrial

• District cooling

– Colleges and universities

– Corporate campuses

– Hospitals

– Convention centers

– Sports arenas

– Utilities

Page 41: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage Systems

Design Considerations

Page 42: Ice Thermal Storage Systems - Ashrae Bi-State

Full Storage vs.

Partial Storage

Page 43: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Batch Cooling or Process Load Profile

Page 44: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Full Ice StorageBatch Cooling or Process Application

Ice Charge Ice Discharge

Page 45: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Air Conditioning Load Profile

Page 46: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Full Ice StorageAir Conditioning Application

Ice Charge Ice Discharge

Page 47: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage System DesignFull Ice Storage

Advantages

• Best suited for short, peak demand periods and/or high, peak loads

• Shifts largest electrical demand that provides the lowest operating cost

• Provides system standby capability and operating flexibility

Disadvantages

• Largest storage volume required

• Larger chiller required

• Most expensive thermal storage design

Page 48: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Partial Ice StorageAir Conditioning Application

Ice Charge Chiller

Ice Discharge

Page 49: Ice Thermal Storage Systems - Ashrae Bi-State

Partial Ice StorageAir Conditioning Application

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Ice Charge Chiller

Ice Discharge

Page 50: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Partial Ice StorageAir Conditioning Application

Ice Charge Chiller

Ice Discharge

Page 51: Ice Thermal Storage Systems - Ashrae Bi-State

0 2 4 6 8 10 12 14 16 18 20 22

Time of Day

Co

oli

ng

Lo

ad

(T

on

s)

Ice Charge Chiller

Ice Discharge

Base Chiller

Page 52: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage System DesignPartial Ice Storage

Advantages

• Best suited for long cooling periods

• Lower first cost due to reduced storage volume and smaller chiller

• Provides system operating flexibility

Disadvantages

• Less standby capability

• Less electrical demand shifted to off-peak

Page 53: Ice Thermal Storage Systems - Ashrae Bi-State

Internal Melt vs.

External Melt

Indirect vs. Direct

Contact Cooling

Page 54: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage System Types

Direct Contact Cooling Indirect Contact Cooling

Page 55: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage Ice-on-Coil Technology

Page 56: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage System DesignIce on Coil - Internal Melt

• Cold glycol solution is circulated through the coil to the A/C system

• Warm glycol solution, circulating through the coil, is cooled indirectly by the melting ice

ICE

ICE ON COIL

WARM

GLYCOL

IN

COLD

GLYCOL

OUT

WARM

GLYCOL

MELTING OCCURS

FROM INSIDE

Indirect

Page 57: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignInternal Melt (Indirect Contact)

Page 58: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignInternal Melt Performance*

32

34

36

38

40

42

44

46

0 10 20 30 40 50 60 70 80 90 100

% Ice Meltout

Le

av

ing

Te

mp

era

ture

0

1

2

3

4

5

6

7

(°F) (°C)

*10 hour, constant load

w/o air agitation

Page 59: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignInternal Melt (Indirect Contact)

Advantages

• Simple to design and operate– simple controls for various operating modes

– closed, pressurized loop

• Stable, cold discharge temperatures– 36°F to 38°F (2.2°C to 3.3°C) typical

• Durable steel construction– 150 to 300 psi (10.3 to 20.7 bar) design pressure

rating

– tested at 190 to 375 psi (13.1 to 25.8 bar)

• Flexible layout (modular tanks or vault design)

Page 60: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage TankChiller

Heat Exchanger

OptionalBase Chiller

Cooling Load

System Schematic

Page 61: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignInternal Melt (Indirect Contact)

Disadvantages

• Heat exchanger required for chilled water in building loop

• Not able to discharge as quickly as direct contact cooling

– ice melt limited by flow through coil

Page 62: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage System DesignIce on Coil - External Melt

• Ice water is circulated through the ice storage tank to the A/C system

• Warm return water, circulating through the tank, is cooled via direct contact with the ice

Direct

ICE

ICE ON COIL

REFRIGERANT

OR GLYCOL

MELTING OCCURS

FROM OUTSIDE

WATERIN

WATEROUT

AIR

WARM

WATER

Page 63: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignExternal Melt (Direct Contact)

Page 64: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignExternal Melt Performance*

32

34

36

38

40

42

44

46

0 10 20 30 40 50 60 70 80 90 100

% Ice Meltout

Le

av

ing

Te

mp

era

ture

0

1

2

3

4

5

6

7

(°F) (°C)

*10 hour, constant load

Page 65: Ice Thermal Storage Systems - Ashrae Bi-State

External Melt Supply Temperatures

0102030405060708090100

% Ice Remaining

32

33

34

35

36

37

38

39

40

Leavin

g W

ate

r T

em

p.

(°F)

Hours

1

2

4

12

6

Page 66: Ice Thermal Storage Systems - Ashrae Bi-State

6000 Ton-HoursIce Storage

6000 Ton-HoursIce Storage

375 TRWater Chiller

375 TRWater Chiller

375 TRWater Chiller

(Spare)

34°FCWS

54°FCWR

42°FCWS

250 TRGlycol Chiller

250 TRGlycol Chiller

250 TRGlycol Chiller

(Spare)

21.4°FCGS

27.8°FCGR

2000 GPM

1500 GPM

External MeltSystem Schematic

Page 67: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignExternal Melt (Direct Contact)

Advantages

• Lowest chilled water supply temperatures

• Quickest discharge capability

• Eliminates glycol from chilled water loop

Page 68: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Storage DesignExternal Melt (Direct Contact)

Disadvantages

• Chiller with lower temperature capability generally required

• Glycol control valves required on larger systems

• Heat exchanger may require to manage static head of open system

• More difficult to monitor amount of ice in inventory

Page 69: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage SystemsExternal Melt vs. Internal Melt

External Melt

• Project requires a constant, cold supply water temperature of 34°F (1°C) or quick discharge periods

• Trained operating staff available

• Large savings in distribution piping system

• Highest energy efficiency

Internal Melt

• Project does not require coldest possible supply temperature

• Simpler design and operation

• Individual buildings

• Energy efficiency is less critical (extra heat transfer step required)

Page 70: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage SystemsExternal Melt vs. Internal Melt

• Most air conditioning applications use internal melt

• Most process and district cooling systems use external melt

Page 71: Ice Thermal Storage Systems - Ashrae Bi-State
Page 72: Ice Thermal Storage Systems - Ashrae Bi-State
Page 73: Ice Thermal Storage Systems - Ashrae Bi-State

Maryknoll Grade SchoolHonolulu, Hawaii

Below-Grade Concrete Tank

2,000 Ton-Hours Ice Storage

District Cooling Retrofit

Page 74: Ice Thermal Storage Systems - Ashrae Bi-State
Page 75: Ice Thermal Storage Systems - Ashrae Bi-State
Page 76: Ice Thermal Storage Systems - Ashrae Bi-State
Page 77: Ice Thermal Storage Systems - Ashrae Bi-State
Page 78: Ice Thermal Storage Systems - Ashrae Bi-State
Page 79: Ice Thermal Storage Systems - Ashrae Bi-State
Page 80: Ice Thermal Storage Systems - Ashrae Bi-State
Page 81: Ice Thermal Storage Systems - Ashrae Bi-State
Page 82: Ice Thermal Storage Systems - Ashrae Bi-State
Page 83: Ice Thermal Storage Systems - Ashrae Bi-State

Maryland Stadium AuthorityOriole Park at Camden YardsRavens Stadium at Camden

Yards Baltimore, Maryland

Buried Concrete Tank

13,000 Ton-Hours Ice Storage

Page 84: Ice Thermal Storage Systems - Ashrae Bi-State
Page 85: Ice Thermal Storage Systems - Ashrae Bi-State
Page 86: Ice Thermal Storage Systems - Ashrae Bi-State
Page 87: Ice Thermal Storage Systems - Ashrae Bi-State
Page 88: Ice Thermal Storage Systems - Ashrae Bi-State
Page 89: Ice Thermal Storage Systems - Ashrae Bi-State
Page 90: Ice Thermal Storage Systems - Ashrae Bi-State
Page 91: Ice Thermal Storage Systems - Ashrae Bi-State
Page 92: Ice Thermal Storage Systems - Ashrae Bi-State
Page 93: Ice Thermal Storage Systems - Ashrae Bi-State
Page 94: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link District CoolingBaltimore, Maryland USA

• 32,000 TR peak system capacity

• 21,650 TR chiller capacity

• 75,000 TH ice storage

• 10 miles+ of distribution system piping

• Chilled water distributed at 37°F (2.8°C)

• 50+ customers

– commercial and government office, hospital, data center, hotel, residential, convention center, entertainment and retail space

Page 95: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Plant #2Saratoga and Eutaw Streets

Baltimore, Maryland

Above-Grade Steel Tanks

27,000 Ton-Hours Ice Storage

Page 96: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 97: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 98: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 99: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 100: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 101: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 102: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Construction (1999)

Page 103: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link Market Center Chilling Station – Completion (1999)

Page 104: Ice Thermal Storage Systems - Ashrae Bi-State
Page 105: Ice Thermal Storage Systems - Ashrae Bi-State

Comfort Link District CoolingBaltimore, Maryland USA

• Operations began in 1996 with traditional electric tariff– 10:00 AM to 8:00 PM peak window

– Fixed peak demand charge

– Time of day energy rates

• Began purchase of electricity through independent suppliers in June, 2002

• System flexibility allows daily changes to operating schedules to minimize spot market consumption and capacity charges

Page 106: Ice Thermal Storage Systems - Ashrae Bi-State

Electric Cost Components - Typical UserSRC Current Market Estimate - PJM Mid-Atlantic

72%

5%

4%

19% Market - Energy Cost

Market - Capacity Cost

Market - Other Costs

Local Delivery / Utility

Current Market Supply Estimate, 1 Year:

$85-$88/MWh

Page 107: Ice Thermal Storage Systems - Ashrae Bi-State

Electric Cost Components

• Energy– Based on prevailing market prices

– Daytime energy costs average twice nighttime energy costs

• Capacity– UCAP (generation capacity charge)

• Highest system load hour on each of 5 highest load days (not customer)

– Transmission

– More than $60/kW/year

Page 108: Ice Thermal Storage Systems - Ashrae Bi-State

Energy Cost Operating Strategy

0

2000

4000

6000

8000

10000

12000

14000

16000

7/3/03

12:00 AM

7/3/03

6:00 AM

7/3/03

12:00 PM

7/3/03

6:00 PM

7/4/03

12:00 AM

7/4/03

6:00 AM

7/4/03

12:00 PM

7/4/03

6:00 PM

7/5/03

12:00 AM

7/5/03

6:00 AM

7/5/03

12:00 PM

Co

mfo

rt L

ink

kW

0

20

40

60

80

100

120

140

160

PJ

M IS

O P

ric

e (

$/m

W)

Chart courtesy of Comfort Link

Page 109: Ice Thermal Storage Systems - Ashrae Bi-State

Energy Cost Operating Strategy

0

2000

4000

6000

8000

10000

12000

14000

16000

7/3/03

12:00 AM

7/3/03

6:00 AM

7/3/03

12:00 PM

7/3/03

6:00 PM

7/4/03

12:00 AM

7/4/03

6:00 AM

7/4/03

12:00 PM

7/4/03

6:00 PM

7/5/03

12:00 AM

7/5/03

6:00 AM

7/5/03

12:00 PM

Co

mfo

rt L

ink

kW

0

20

40

60

80

100

120

140

160

PJ

M IS

O P

ric

e (

$/m

W)

Chart courtesy of Comfort Link

Page 110: Ice Thermal Storage Systems - Ashrae Bi-State

Energy Cost Operating Strategy

0

2000

4000

6000

8000

10000

12000

14000

16000

7/3/03

12:00 AM

7/3/03

6:00 AM

7/3/03

12:00 PM

7/3/03

6:00 PM

7/4/03

12:00 AM

7/4/03

6:00 AM

7/4/03

12:00 PM

7/4/03

6:00 PM

7/5/03

12:00 AM

7/5/03

6:00 AM

7/5/03

12:00 PM

Co

mfo

rt L

ink

kW

0

20

40

60

80

100

120

140

160

PJ

M IS

O P

ric

e (

$/m

W)

Chart courtesy of Comfort Link

Page 111: Ice Thermal Storage Systems - Ashrae Bi-State

Demand Limiting Operating Strategy

0

5

10

15

20

25

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Hour

To

tal

Syste

m T

on

s (

000)

Chiller Ice

Chart courtesy of Comfort Link

June 27, 2007

High of 100°F (37.8°C)

Low of 80°F (26.7°C)

12 mW

Demand Shift

Page 112: Ice Thermal Storage Systems - Ashrae Bi-State

Record Heat and Record Loads

0

5

10

15

20

25

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Hour

To

tal

Syste

m T

on

s (

000)

Chiller

Chart courtesy of Comfort Link

August 8, 2007

High of 108°F (42.2°C)

Low of 86°F (30.0°C)

(1) 1750 TR chiller out of service

Load Leveling Operating Strategy

Page 113: Ice Thermal Storage Systems - Ashrae Bi-State

Load Leveling Operating Strategy

0

5

10

15

20

25

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Hour

To

tal

Syste

m T

on

s (

000)

Chiller Ice

Chart courtesy of Comfort Link

August 8, 2007

High of 108°F (42.2°C)

Low of 86°F (30.0°C)

(1) 1750 TR chiller out of service

6 mW

Demand Shift

Page 114: Ice Thermal Storage Systems - Ashrae Bi-State

Demand Limiting Operating Strategy

0

5

10

15

20

25

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Hour

To

tal

Syste

m T

on

s (

000)

Chiller Ice

Chart courtesy of Comfort Link

August 8, 2007

High of 108°F (42.2°C)

Low of 86°F (30.0°C)

11 mW

Demand Shift

Predicted performance with all chillers in service

Page 115: Ice Thermal Storage Systems - Ashrae Bi-State

Ice Thermal Storage Systems

Greg Henderson

Director, Global Thermal Storage