DESIGN CONDITIONS INDOOR: 75F DB / 50% RH OUTDOOR: 95F DB / 80F WB SUMMER OUTDOOR: 25F DB WINTER INDOOR: 70F DB / 50% RH HVAC LEGEND AUTOMATIC BALANCING CONTROL VALVE SIDEWALL REGISTER LINEAR SIDEWALL REGISTER S.R. L.S.R. DOOR GRILLE MANUAL DAMPER FIRE DAMPER TURNING VANES FLEXIBLE DUCT CONNECTION D.G. M.D. F.D. DIRECTION OF PIPING FLOW PIPE CAP DRAIN VALVE W/ HOSE CONNECTION AUTOMATIC AIR VENT BASKET STRAINER RELIEF VALVE RINSE VALVE FLANGE CONNECTION FLANGED JOINT ELBOW UP ELBOW DOWN TEE UP TEE DOWN ELBOW SIDE TEE SIDE BUTTERFLY VALVE BALL VALVE CIRCUIT SETTER/ BALANCING VALVE PIPE WITH HEAT TRACING INSULATION AND JACKET S SOLENOID VALVE SWING CHECK VALVE PLUG VALVE CIRCUIT SENSOR BACKFLOW PREVENTER PRESSURE REDUCING VALVE UNION ECCENTRIC REDUCER/INCREASER CONCENTRIC REDUCER/INCREASER 3-WAY CONTROL VALVE 2-WAY CONTROL VALVE WAFER CHECK VALVE END SUCTION PUMP DOUBLE SUCTION PUMP WYE STRAINER WYE STRAINER W/BLOWDOWN BALL VALVE WITH HOSE CONNECTION GATE VALVE RETURN/EXHAUST/OUTSIDE AIR DUCT M CIRCUIT SETTER TRIPLE DUTY VALVE SUPPLY AIR DUCT EQUIPMENT CLEARANCE VARIABLE VOLUME TERMINAL UNIT VAV MOTORIZED BUTTERFLY VALVE BALL VALVE ROOF TOP UNIT MOTORIZED DAMPER M THERMOSTAT HUMIDISTAT SMOKE DETECTOR (DUCT MOUNTED) CARBON DIOXIDE SENSOR (DUCT MOUNTED) AIR TERMINAL DIFFUSER (CEILING MOUNTED) AIR TERMINAL RETURN GRILLE (CEILING MOUNTED) PREINSULATED FLEXIBLE DUCT CONNECTION TO EXISTING SYSTEM SD CD AIR TERMINAL EXHAUST GRILLE (CEILING MOUNTED) AIR TERMINAL TAG, X=TYPE MARK, Y=CFM AIR TERMINAL ROUND CONE DIFFUSER THERMOSTAT (DUCT MOUNTED) HUMIDISTAT (DUCT MOUNTED) X Y H H T T M MECHANICAL COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION IBC-2012 /ASCE 7-10 SEISMIC AND WIND REQUIREMENTS FOR MECHANICAL SYSTEMS COMPONENT IMPORTANCE FACTOR (Ip) Ip = 1.0 Ip = 1.5 RESTRAIN IF TOTAL WEIGHT OF DUCTS ON TRAPEZE > 10 LBS/FT 4 4 RESTRAIN IF TOTAL WEIGHT OF DUCTS ON TRAPEZE > 10 LBS/FT MULTIPLE DUCTS ON TRAPEZE 5 - 6 SQ.FT. AND LARGER RESTRAIN IF ANY PIPE ON TRAPEZE > 1" RESTRAIN IF TOTAL WEIGHT OF PIPES ON TRAPEZE > 10 LBS/FT 4 4 4 4 RESTRAIN ALL RESTRAIN IF ANY PIPE ON TRAPEZE > 3" RESTRAIN IF TOTAL WEIGHT OF PIPES ON TRAPEZE > 10 LBS/FT RESTRAIN ALL SUSPENDED PIPE ON TRAPEZE SUSPENDED NON DUCTILE PIPING (CAST IRON, PLASTIC, CERAMIC) NOTES: 1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT. 2. RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4 FT. OR LESS ABOVE A FLOOR, AND HAS FLEXIBLE CONNECTIONS BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT. 3. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY. 4. RESTRAINT IS NOT REQUIRED IF THE PIPING / DUCTWORK IS SUPPORTED BY HANGERS AND EACH HANGER IN THE PIPING RUN IS 12 IN. OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE SHALL BE SUPPORTED BY HANGERS HAVING A LENGTH OF 12 IN. OR LESS. WHERE ROD HANGERS ARE USED, THEY SHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENT BENDING IN THE ROD. 5. ALL DUCTWORK , REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES OR USED FOR SMOKE CONTROL MUST BE RESTRAINED. 6. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BY ENGINEER OF RECORD. A. PER SECTION 301.15 OF THE 2012 EDITION OF THE INTERNATIONAL MECHANICAL CODE, MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS (INCLUDING ROOF CURBS & ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINT IS REQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY. B. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR DESIGNATIONS. C. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT. D. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL. SUBMITTALS MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS. E. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF THE SEISMIC SUBMITTAL. F. SEISMIC RESTRAINTS FOR PIPING AND DUCTWORK MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS. NOTES 1.5 1.0 6 REQUIRED 6 NOT REQUIRED COMPONENT CERTIFICATION (SEE NOTE 6) 6 SQ.FT. AND LARGER DUCTWORK 4 >1" 4 >3" SUSPENDED DUCTILE PIPING (STEEL, ALUMINUM, COPPER, ETC.) - RESTRAIN ALL 1 RESTRAIN ALL NOT INLINE W/ DUCT/PIPE 3 RESTRAIN IF >75 LBS PROVIDE FLEX. CONN. 3 RESTRAIN IF >75 LBS PROVIDE FLEX. CONN. INLINE W/ DUCT SUSPENDED EQUIPMENT - RESTRAIN ALL 1 RESTRAIN ALL COMPONENT SUPPORTS - RESTRAIN ALL 1, 2 RESTRAIN ALL WALL MOUNTED - RESTRAIN ALL 1, 2 RESTRAIN ALL FLOOR MOUNTED - RESTRAIN ALL 1 RESTRAIN ALL ROOF MOUNTED SEISMIC RESTRAINT REQUIREMENT NOTES SEISMIC RESTRAINT REQUIREMENT COMPONENT IDENTIFICATION SEISMIC DESIGN CATEGORIES D,E,F ALL HVAC COMPONENTS EXCEPT AS NOTED IN Ip=1.5 GENERAL HVAC NOTES THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND LOCATION OF EQUIPMENT, DUCTWORK, PIPING, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE MECHANICAL INSTALLATION W/ THE STRUCTURE AND OTHER TRADES AND SHALL PROVIDE ADDITIONAL OFFSETS AND FITTINGS AS NECESSARY. COORDINATE WORK WITH OFFICE OF STATE ENGINEER (OSE). OSE SHALL ISSUE THE BUILDING / CONSTRUCTION PERMIT DIRECTLY TO THE OWNER, AND THE OWNER WILL PAY FOR INITIAL INSPECTIONS. PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTION AND ACCEPTANCE FROM OSE. THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS SHALL COMPLY WITH THE 2012 VERSION OF THE INTERNATIONAL MECHANICAL CODE, NFPA 90A, AND LOCAL CODE OFFICIAL REQUIREMENTS. IN THE EVENT OF A CONFLICT BETWEEN CODES, THE MOST STRINGENT SHALL ALWAYS GOVERN. DUCT DIMENSIONS ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. THE CONTRACTOR SHALL CHECK AND VERIFY ALL CLEARANCES PRIOR TO FABRICATION OR INSTALLATION OF EQUIPMENT, DUCTWORK, AND PIPING SYSTEMS. WHERE CONDITIONS REQUIRE A CHANGE IN DUCT OR PIPE ROUTING, NOTIFY THE ARCHITECT FOR AN ACCEPTABLE ALTERNATIVE METHOD. AVOID ROUTING DUCTWORK DIRECTLY OVER LIGHT FIXTURES, DIFFUSERS, AND OTHER CEILING MTD. DEVICES. LOCATE ALL MECHANICAL EQUIPMENT SO THAT FILTERS AND COMPONENTS REQUIRING ACCESS (SERVICE AND MAINTENANCE) ARE FULLY ACCESSIBLE. PROVIDE CURVED RADIUS ELBOW AT FIRST SUPPLY & RETURN FITTING FOR ALL HVAC UNITS. PROVIDE TURNING VANES IN ALL 90 DEGREE ELBOWS IN ALL RECTANGULAR SUPPLY/RETURN/EXHAUST DUCT SYSTEMS. ANY OFFSETS REQUIRED IN DUCT SYSTEMS SHALL BE INSTALLED PER SMACNA 2005 2ND EDITION MANUAL . SHARP ANGLED TRANSITIONS OR OFFSETS 'WILL NOT BE ALLOWED'. PROVIDE DUCT ACCESS DOORS AT LOCATIONS SPECIFIED. INSTALL ALL DUCT MOUNTED DEVICES (DAMPERS, ACCESS DOORS, ETC.) AND PIPING SPECIALTIES IN EASILY ACCESSIBLE LOCATIONS. ADVISE THE ARCHITECT IN ADVANCE OF INSTALLATION IF ACCESS WILL BE HINDERED SO AN ALTERNATE LOCATION CAN BE SELECTED. ALL DUCT TAKE-OFFS SHALL BE INSTALLED AS SHOWN BY DETAILS ON THE PLANS WITH A MANUAL BALANCING DAMPER AT EVERY TAKE-OFF. WHERE DUCT RUN-OUT SIZE IS NOT SHOWN PROVIDE DUCT SAME SIZE AS GRILLE NECK SIZE. PRE-INSULATED FLEXIBLE DUCT MAY BE USED FOR FINAL CONNECTION TO SUPPLY GRILLES (MAX. LENGTH 5'). ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS WITH PRESCRIBED CLEARANCES FOR SERVICE AND MAINTENANCE. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IF RECOMMENDED CLEARANCES ARE NOT POSSIBLE BEFORE INSTALLING EQUIPMENT. ALL ROTATING MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION. PROVIDE FLEXIBLE NEOPRENE DUCT CONNECTORS BETWEEN DUCTWORK AND ISOLATED MECHANICAL EQUIPMENT. THE CONTRACTOR SHALL FIRESTOP ALL PENETRATIONS OF FIRE RATED WALLS/FLOORS/CEILINGS BY DUCTWORK, PIPING, ETC., WITH U.L. LISTED FIRE STOPPING ASSEMBLY TO MAINTAIN FIRE RATING OF THE BARRIER. REFER TO ARCHITECTURAL PLANS FOR RATED ASSEMBLY LOCATIONS. SUBMIT UL LISTED ASSEMBLY MANUFACTURER INSTALLATION INSTRUCTIONS DURING SUBMITTAL PHASE FOR REVIEW BY ENGINEER OF RECORD, AND INSTALL ASSEMBLY PER MANUFACTURER RECOMMENDATIONS. SEISMIC PROTECTION OF EQUIPMENT, DUCTWORK, PIPING AND UTILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 16 OF THE INTERNATIONAL BUILDING CODE, 2012 EDITION. ALL SEISMIC RESTRAINT AND BRACING SHALL BE SUBSTANTIATED BY MANUFACTURER'S SUBMITTALS PER THE SPECIFICATIONS. FOR ADDITIONAL INFORMATION, SEE 'SEISMIC AND WIND REQUIREMENTS FOR MECHANICAL SYSTEMS' ON THIS SHEET. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING INSTALLATION OF SEISMIC BRACING DEVICES WITH THE OWNER'S SEISMIC SPECIAL INSPECTOR. PROVIDE A MINIMUM OF SEVEN DAYS ADVANCE NOTICE OF INSTALLATION. BALANCE ALL AIR DISTRIBUTION DEVICES, EXHAUST FANS, AND OUTSIDE AIR QUANTITIES AS SCHEDULED OR SHOWN ON THE DRAWINGS. PROVIDE MARKERS AT ALL DAMPER LOCATIONS SHOWING FULL OPEN/CLOSED POSITIONS AND DAMPER SETTING FOR REQUIRED AIRFLOW. PROVIDE FINAL TEST AND BALANCE REPORT ALONG W/ SCHEMATIC DRAWINGS SHOWING DIFFUSER LOCATION W/ DESIGN AND ACTUAL CFM. THE DIFFUSER TAGS ON THE DRAWINGS SHALL CORRESPOND TO THE DIFFUSER TAGS ON THE REPORT. THIS REPORT SHALL BE SUBMITTED BEFORE THE FINAL INSPECTION IS PERFORMED. SEE SPECIFICATIONS FOR FURTHER INFORMATION. ALL CONTROL WIRING, CONDUIT AND CONTROLS ACCESSORIES NECESSARY TO IMPLEMENT THE OUTLINED SEQUENCES OF OPERATION SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR. WIND LOAD PROTECTION OF ROOF MOUNTED EQUIPMENT AND DUCTWORK SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 16 OF THE INTERNATIONAL BUILDING CODE, 2012 EDITION. ALL WIND LOAD RESTRAINT AND BRACING SHALL BE SUBSTANTIATED BY MANUFACTURER'S SUBMITTALS PER THE SPECIFICATIONS. ALL EXPOSED PIPING AND DUCTWORK SHALL BE PAINTED. COORDINATE W/ ARCHITECTURAL PLANS/SPECIFICATIONS FOR EXPOSED LOCATIONS AND PAINTING REQUIREMENTS. SEE ARCHITECTURAL DOCUMENTS FOR ROOF PENETRATION AND FLASHING REQUIREMENTS. WHERE "APPROXIMATELY" IS USED TO DEFINE INSTALLATION LOCATIONS, CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES TO VERIFY THERE ARE NO CONFLICTS PRIOR TO INSTALLATION AT DIMENSION LISTED. FIRE DAMPERS SHALL BE INSTALLED PER MANUFACTURER'S INSTALLATION RECOMMENDATIONS. MANUFACTURER'S RECOMMENDATIONS SHALL BE PROVIDED FOR REVIEW DURING SUBMITTAL PROCESS. ALL ITEMS INSTALLED ABOVE THE CEILINGS SHALL BE PLENUM RATED. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. DESCRIPTION INTERNATIONAL BUILDING CODE INTERNATIONAL ENERGY CONSERVATION CODE INTERNATIONAL MECHANICAL CODE STANDARD FOR THE INSTALLATION AIR-CONDITIONING & VENTILATING SYSTEMS MANUAL FOR THE BALANCING & ADJUSTMENT OF AIR DISTRIBUTION SYSTEMS CODE IBC (2012) IECC (2009) IMC (2012) NFPA 90A (2015) SMACNA MECHANICAL CODES & STANDARDS DESCRIPTION EXISTING ADJUSTABLE ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AIR HANDLER AIR HANDLING UNIT BUILDING MANAGMENT SYSTEM BASIS OF DESIGN BOTTOM OF PIPE DOMESTIC COLD WATER SUPPLY CHEMICAL FEED CLEANOUT CENTRAL PLANT CONDENSER WATER RETURN CONDENSER WATER SUPPLY CONDENSING UNIT CHILLED WATER RETURN CHILLED WATER SUPPLY DOMESTIC COLD WATER DIRECT DIGITAL CONTROLS DIAMETER DRAIN EXHAUST AIR ELECTRICAL CONDUCTOR ELECTRICAL DUCT HEATER EXHAUST FAN ELECTRIC HEATER ENERGY MANAGEMENT CONTROL SYSTEM FLOOR DRAIN DOMESTIC HOT WATER SUPPLY HUB DRAIN HEAT PUMP DOMESTIC HOW WATER RETURN HEATING HOT WATER RETURN HEATING HOT WATER SUPPLY LEAVING AIR TEMPERATURE THOUSANDS OF BTU'S PER HOUR MECHANICAL CONTRACTOR NATURAL GAS PIPING NORMALLY OPEN OUTSIDE AIR OVER FLOW PLUMBING CONTRACTOR PIPE SUPPORT RETURN AIR REFRIGERANT RELATIVE HUMIDITY REMOTE MONITOR ROOF TOP UNIT RAIN WATER SUPPLY AIR SUPPLY FAN TRIPLE DUTY VALVE TYPICAL UNDERGROUND UNLESS OTHERWISE NOTED VARIABLE FREQUENCY DRIVE VENT WITH WIRE MESH SCREEN ABR (E) ADJ AFF AFG AH AHU BMS BOD BOP C CHF CO CP CR CS CU CHWR CHWS DCW DDC DIA DRN EA EC EDH EF EH EMCS FD H HD HP HR HWR HWS LAT MBH MC NG NO OA OF PC PS RA REFR RH RM RTU RW SA SF TDV TYP UG UNO VFD VNT W/ WMS ABBREVIATIONS PARTITION PLAN LEGEND 1 HR. RATED PARTITION TO DECK SEE SHEET A002 FOR CONSTRUCTION OF PARTITION TYPES. PARTITION KEY: EXISTING 1 HR. RATED PARTITION TO DECK. ENSURE SEALING TIGHT TO DECK WITH APPROVED SAFING MATERIAL. A M I L I L W B A D E N I A I I R L L D G No. T U D S I S R E T E A A 30241 R E G E E R I N E N L R C A H O R P S E F O L N S I O I N O C E R T I F I C A T E O F A U T H O R I Z A T I O N S O U T H C A R O L I N A CONSULTING ENGINEERS DWG, INC. No.C03649 CHECKED BY: DRAWN BY: DATE: PROJECT: REVISIONS: MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 1 A 2 3 4 5 6 B C D E COPYRIGHT 2015 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. WWW.LS3P.COM TEL. 843.577.4444 FAX 843.722.4789 205 1/2 KING ST. CHARLESTON SC 29401 H17-9548-PD 5/31/2016 11:15:30 AM C:\Users\mgallagher\Documents\MEP_CCU Smith Science [email protected] 11257 05/31/16 KTD WDB HVAC - NOTES & LEGENDS M-001 SCIENCE BUILDING RENOVATION BID CONSTRUCTION DOCUMENTS No. Description Date 1 OSE COMMENT REVISIONS 02/18/2016

Transcript of IBC-2012 /ASCE 7-10 · 2016. 6. 2. · turning vanes flexible duct connection d.g. m.d. f.d....

  • DESIGN CONDITIONS

    INDOOR: 75F DB / 50% RH

    OUTDOOR: 95F DB / 80F WBSUMMER

    OUTDOOR: 25F DBWINTER

    INDOOR: 70F DB / 50% RH

    HVAC LEGEND

    AUTOMATIC BALANCING CONTROL VALVE

    SIDEWALL REGISTER

    LINEAR SIDEWALL REGISTER

    S.R.

    L.S.R.

    DOOR GRILLE

    MANUAL DAMPER

    FIRE DAMPER

    TURNING VANES

    FLEXIBLE DUCT CONNECTION

    D.G.

    M.D.

    F.D.

    DIRECTION OF PIPING FLOW

    PIPE CAP

    DRAIN VALVE W/ HOSE CONNECTION

    AUTOMATIC AIR VENT

    BASKET STRAINER

    RELIEF VALVE

    RINSE VALVE

    FLANGE CONNECTION

    FLANGED JOINT

    ELBOW UP

    ELBOW DOWN

    TEE UP

    TEE DOWN

    ELBOW SIDE

    TEE SIDE

    BUTTERFLY VALVE

    BALL VALVE

    CIRCUIT SETTER/BALANCING VALVE

    PIPE WITH HEAT TRACING

    INSULATION AND JACKET

    SSOLENOID VALVE

    SWING CHECK VALVE

    PLUG VALVE

    CIRCUIT SENSOR

    BACKFLOW PREVENTER

    PRESSURE REDUCING VALVE

    UNION

    ECCENTRIC REDUCER/INCREASER

    CONCENTRIC REDUCER/INCREASER

    3-WAY CONTROL VALVE

    2-WAY CONTROL VALVE

    WAFER CHECK VALVE

    END SUCTION PUMP

    DOUBLE SUCTION PUMP

    WYE STRAINER

    WYE STRAINER W/BLOWDOWN BALL VALVE WITH HOSECONNECTION

    GATE VALVE

    RETURN/EXHAUST/OUTSIDE AIR DUCT

    M

    CIRCUIT SETTER

    TRIPLE DUTY VALVE

    SUPPLY AIR DUCT

    EQUIPMENT CLEARANCE

    VARIABLE VOLUME TERMINAL UNITVAV

    MOTORIZEDBUTTERFLY VALVE

    BALL VALVE

    ROOF TOP UNIT

    MOTORIZED DAMPER

    M

    THERMOSTAT

    HUMIDISTAT

    SMOKE DETECTOR (DUCT MOUNTED)

    CARBON DIOXIDE SENSOR (DUCT MOUNTED)

    AIR TERMINAL DIFFUSER(CEILING MOUNTED)

    AIR TERMINAL RETURNGRILLE (CEILING MOUNTED)

    PREINSULATED FLEXIBLE DUCT

    CONNECTION TO EXISTING SYSTEM

    SD

    CD

    AIR TERMINAL EXHAUSTGRILLE (CEILING MOUNTED)

    AIR TERMINAL TAG, X=TYPE MARK, Y=CFM

    AIR TERMINAL ROUND CONE DIFFUSER

    THERMOSTAT (DUCT MOUNTED)

    HUMIDISTAT (DUCT MOUNTED)

    XY

    H

    H

    T

    T

    M

    MECHANICAL COMPONENT IMPORTANCE FACTOR (Ip) DESIGNATION

    IBC-2012 /ASCE 7-10

    SEISMIC AND WIND REQUIREMENTSFOR MECHANICAL SYSTEMS

    COMPONENT IMPORTANCE FACTOR (Ip)

    Ip = 1.0 Ip = 1.5

    RESTRAIN IF TOTAL WEIGHT OF DUCTS

    ON TRAPEZE > 10 LBS/FT44

    RESTRAIN IF TOTAL WEIGHT OF DUCTS

    ON TRAPEZE > 10 LBS/FTMULTIPLE DUCTS ON TRAPEZE

    5- 6 SQ.FT. AND LARGER

    RESTRAIN IF ANY PIPE

    ON TRAPEZE > 1"

    RESTRAIN IF TOTAL WEIGHT OF PIPES

    ON TRAPEZE > 10 LBS/FT

    4

    4

    4

    4 RESTRAIN ALL

    RESTRAIN IF ANY PIPE

    ON TRAPEZE > 3"

    RESTRAIN IF TOTAL WEIGHT OF PIPES

    ON TRAPEZE > 10 LBS/FT

    RESTRAIN ALL

    SUSPENDED PIPE ON TRAPEZE

    SUSPENDED NON DUCTILE PIPING

    (CAST IRON, PLASTIC, CERAMIC)

    NOTES:

    1. EQUIPMENT 20 LBS. OR LESS IS EXEMPT IF FLEXIBLE CONNECTIONS ARE PROVIDED BETWEEN THE COMPONENT AND ASSOCIATEDDUCTWORK, PIPING, AND CONDUIT.

    2. RESTRAINTS ARE NOT REQUIRED IF THE COMPONENT WEIGHS 400 LBS. OR LESS, IS MOUNTED AT 4 FT. OR LESS ABOVE A FLOOR,AND HAS FLEXIBLE CONNECTIONS BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.

    3. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY.4. RESTRAINT IS NOT REQUIRED IF THE PIPING / DUCTWORK IS SUPPORTED BY HANGERS AND EACH HANGER IN THE PIPING RUN IS 12 IN.

    OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE SUPPORTING STRUCTURE. WHERE PIPES ARE SUPPORTED ON A TRAPEZE,THE TRAPEZE SHALL BE SUPPORTED BY HANGERS HAVING A LENGTH OF 12 IN. OR LESS. WHERE ROD HANGERS ARE USED, THEYSHALL BE EQUIPPED WITH SWIVELS, EYE NUTS OR OTHER DEVICES TO PREVENT BENDING IN THE ROD.

    5. ALL DUCTWORK , REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES OR USED FOR SMOKECONTROL MUST BE RESTRAINED.

    6. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT TIME OF SUBMITTAL FOR REVIEW BYENGINEER OF RECORD.

    A. PER SECTION 301.15 OF THE 2012 EDITION OF THE INTERNATIONAL MECHANICAL CODE, MECHANICAL EQUIPMENT, APPLIANCESAND SUPPORTS (INCLUDING ROOF CURBS & ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESISTTHE WIND PRESSURES DETERMINED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. WHERE SEISMIC RESTRAINTIS REQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED INTHE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN CATEGORY.

    B. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR DESIGNATIONS.C. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH MECHANICAL COMPONENT.D. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS SHALL BE DESIGNED

    BY A REGISTERED DESIGN PROFESSIONAL. SUBMITTALS MUST INCLUDE STAMPED AND SIGNED DRAWINGS AND CALCULATIONS.E. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS

    CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPTOF THE SEISMIC SUBMITTAL.

    F. SEISMIC RESTRAINTS FOR PIPING AND DUCTWORK MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINTLOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS.

    NOTES

    1.51.0

    6REQUIRED6NOT REQUIREDCOMPONENT CERTIFICATION

    (SEE NOTE 6)

    6 SQ.FT. AND LARGERDUCTWORK

    4>1"4>3"SUSPENDED DUCTILE PIPING

    (STEEL, ALUMINUM, COPPER, ETC.)

    -RESTRAIN ALL1RESTRAIN ALLNOT INLINE W/

    DUCT/PIPE

    3RESTRAIN IF >75 LBS

    PROVIDE FLEX. CONN.3RESTRAIN IF >75 LBS

    PROVIDE FLEX. CONN.INLINE W/ DUCT

    SUSPENDED

    EQUIPMENT

    -RESTRAIN ALL1RESTRAIN ALLCOMPONENT SUPPORTS

    -RESTRAIN ALL1, 2RESTRAIN ALLWALL MOUNTED

    -RESTRAIN ALL1, 2RESTRAIN ALLFLOOR MOUNTED

    -RESTRAIN ALL1RESTRAIN ALLROOF MOUNTED

    SEISMIC RESTRAINT

    REQUIREMENTNOTES

    SEISMIC RESTRAINT

    REQUIREMENTCOMPONENT IDENTIFICATION

    SEISMIC DESIGN CATEGORIES D,E,F

    ALL HVAC COMPONENTS EXCEPT AS NOTED IN Ip=1.5

    GENERAL HVAC NOTES

    THE DRAWINGS SHOW THE GENERAL ARRANGEMENT AND LOCATION OF EQUIPMENT, DUCTWORK, PIPING, ETC. THE CONTRACTORSHALL BE RESPONSIBLE FOR COORDINATING THE MECHANICAL INSTALLATION W/ THE STRUCTURE AND OTHER TRADES AND SHALLPROVIDE ADDITIONAL OFFSETS AND FITTINGS AS NECESSARY.

    COORDINATE WORK WITH OFFICE OF STATE ENGINEER (OSE). OSE SHALL ISSUE THE BUILDING / CONSTRUCTION PERMIT DIRECTLYTO THE OWNER, AND THE OWNER WILL PAY FOR INITIAL INSPECTIONS.

    PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTION AND ACCEPTANCE FROM OSE.

    THE HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS SHALL COMPLY WITH THE 2012 VERSION OF THE INTERNATIONALMECHANICAL CODE, NFPA 90A, AND LOCAL CODE OFFICIAL REQUIREMENTS. IN THE EVENT OF A CONFLICT BETWEEN CODES, THEMOST STRINGENT SHALL ALWAYS GOVERN.

    DUCT DIMENSIONS ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.

    THE CONTRACTOR SHALL CHECK AND VERIFY ALL CLEARANCES PRIOR TO FABRICATION OR INSTALLATION OF EQUIPMENT,DUCTWORK, AND PIPING SYSTEMS. WHERE CONDITIONS REQUIRE A CHANGE IN DUCT OR PIPE ROUTING, NOTIFY THE ARCHITECTFOR AN ACCEPTABLE ALTERNATIVE METHOD. AVOID ROUTING DUCTWORK DIRECTLY OVER LIGHT FIXTURES, DIFFUSERS, ANDOTHER CEILING MTD. DEVICES. LOCATE ALL MECHANICAL EQUIPMENT SO THAT FILTERS AND COMPONENTS REQUIRING ACCESS(SERVICE AND MAINTENANCE) ARE FULLY ACCESSIBLE.

    PROVIDE CURVED RADIUS ELBOW AT FIRST SUPPLY & RETURN FITTING FOR ALL HVAC UNITS. PROVIDE TURNING VANES IN ALL 90DEGREE ELBOWS IN ALL RECTANGULAR SUPPLY/RETURN/EXHAUST DUCT SYSTEMS. ANY OFFSETS REQUIRED IN DUCT SYSTEMSSHALL BE INSTALLED PER SMACNA 2005 2ND EDITION MANUAL . SHARP ANGLED TRANSITIONS OR OFFSETS 'WILL NOT BEALLOWED'. PROVIDE DUCT ACCESS DOORS AT LOCATIONS SPECIFIED.

    INSTALL ALL DUCT MOUNTED DEVICES (DAMPERS, ACCESS DOORS, ETC.) AND PIPING SPECIALTIES IN EASILY ACCESSIBLELOCATIONS. ADVISE THE ARCHITECT IN ADVANCE OF INSTALLATION IF ACCESS WILL BE HINDERED SO AN ALTERNATE LOCATIONCAN BE SELECTED.

    ALL DUCT TAKE-OFFS SHALL BE INSTALLED AS SHOWN BY DETAILS ON THE PLANS WITH A MANUAL BALANCING DAMPER AT EVERYTAKE-OFF. WHERE DUCT RUN-OUT SIZE IS NOT SHOWN PROVIDE DUCT SAME SIZE AS GRILLE NECK SIZE. PRE-INSULATED FLEXIBLEDUCT MAY BE USED FOR FINAL CONNECTION TO SUPPLY GRILLES (MAX. LENGTH 5').

    ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONSWITH PRESCRIBED CLEARANCES FOR SERVICE AND MAINTENANCE. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IFRECOMMENDED CLEARANCES ARE NOT POSSIBLE BEFORE INSTALLING EQUIPMENT.

    ALL ROTATING MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH VIBRATION ISOLATION. PROVIDE FLEXIBLE NEOPRENE DUCTCONNECTORS BETWEEN DUCTWORK AND ISOLATED MECHANICAL EQUIPMENT.

    THE CONTRACTOR SHALL FIRESTOP ALL PENETRATIONS OF FIRE RATED WALLS/FLOORS/CEILINGS BY DUCTWORK, PIPING, ETC.,WITH U.L. LISTED FIRE STOPPING ASSEMBLY TO MAINTAIN FIRE RATING OF THE BARRIER. REFER TO ARCHITECTURAL PLANS FORRATED ASSEMBLY LOCATIONS. SUBMIT UL LISTED ASSEMBLY MANUFACTURER INSTALLATION INSTRUCTIONS DURING SUBMITTALPHASE FOR REVIEW BY ENGINEER OF RECORD, AND INSTALL ASSEMBLY PER MANUFACTURER RECOMMENDATIONS.

    SEISMIC PROTECTION OF EQUIPMENT, DUCTWORK, PIPING AND UTILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 16 OFTHE INTERNATIONAL BUILDING CODE, 2012 EDITION. ALL SEISMIC RESTRAINT AND BRACING SHALL BE SUBSTANTIATED BYMANUFACTURER'S SUBMITTALS PER THE SPECIFICATIONS. FOR ADDITIONAL INFORMATION, SEE 'SEISMIC AND WIND REQUIREMENTSFOR MECHANICAL SYSTEMS' ON THIS SHEET. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING INSTALLATION OF SEISMICBRACING DEVICES WITH THE OWNER'S SEISMIC SPECIAL INSPECTOR. PROVIDE A MINIMUM OF SEVEN DAYS ADVANCE NOTICE OFINSTALLATION.

    BALANCE ALL AIR DISTRIBUTION DEVICES, EXHAUST FANS, AND OUTSIDE AIR QUANTITIES AS SCHEDULED OR SHOWN ON THEDRAWINGS. PROVIDE MARKERS AT ALL DAMPER LOCATIONS SHOWING FULL OPEN/CLOSED POSITIONS AND DAMPER SETTING FORREQUIRED AIRFLOW. PROVIDE FINAL TEST AND BALANCE REPORT ALONG W/ SCHEMATIC DRAWINGS SHOWING DIFFUSER LOCATIONW/ DESIGN AND ACTUAL CFM. THE DIFFUSER TAGS ON THE DRAWINGS SHALL CORRESPOND TO THE DIFFUSER TAGS ON THEREPORT. THIS REPORT SHALL BE SUBMITTED BEFORE THE FINAL INSPECTION IS PERFORMED. SEE SPECIFICATIONS FOR FURTHERINFORMATION.

    ALL CONTROL WIRING, CONDUIT AND CONTROLS ACCESSORIES NECESSARY TO IMPLEMENT THE OUTLINED SEQUENCES OFOPERATION SHALL BE PROVIDED BY THE CONTROLS CONTRACTOR.

    WIND LOAD PROTECTION OF ROOF MOUNTED EQUIPMENT AND DUCTWORK SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 16OF THE INTERNATIONAL BUILDING CODE, 2012 EDITION. ALL WIND LOAD RESTRAINT AND BRACING SHALL BE SUBSTANTIATED BYMANUFACTURER'S SUBMITTALS PER THE SPECIFICATIONS.

    ALL EXPOSED PIPING AND DUCTWORK SHALL BE PAINTED. COORDINATE W/ ARCHITECTURAL PLANS/SPECIFICATIONS FOR EXPOSEDLOCATIONS AND PAINTING REQUIREMENTS.

    SEE ARCHITECTURAL DOCUMENTS FOR ROOF PENETRATION AND FLASHING REQUIREMENTS.

    WHERE "APPROXIMATELY" IS USED TO DEFINE INSTALLATION LOCATIONS, CONTRACTOR SHALL COORDINATE WITH ALL OTHERTRADES TO VERIFY THERE ARE NO CONFLICTS PRIOR TO INSTALLATION AT DIMENSION LISTED.

    FIRE DAMPERS SHALL BE INSTALLED PER MANUFACTURER'S INSTALLATION RECOMMENDATIONS. MANUFACTURER'SRECOMMENDATIONS SHALL BE PROVIDED FOR REVIEW DURING SUBMITTAL PROCESS.

    ALL ITEMS INSTALLED ABOVE THE CEILINGS SHALL BE PLENUM RATED.

    1.

    2.

    3.

    4.

    5.

    6.

    7.

    8.

    9.

    10.

    11.

    12.

    13.

    14.

    15.

    16.

    17.

    18.

    19.

    20.

    21.

    DESCRIPTIONINTERNATIONAL BUILDING CODEINTERNATIONAL ENERGY CONSERVATION CODEINTERNATIONAL MECHANICAL CODESTANDARD FOR THE INSTALLATION AIR-CONDITIONING &VENTILATING SYSTEMSMANUAL FOR THE BALANCING & ADJUSTMENT OF AIRDISTRIBUTION SYSTEMS

    CODEIBC (2012)

    IECC (2009)IMC (2012)

    NFPA 90A (2015)

    SMACNA

    MECHANICAL CODES & STANDARDS

    DESCRIPTIONEXISTINGADJUSTABLEABOVE FINISHED FLOORABOVE FINISHED GRADEAIR HANDLERAIR HANDLING UNITBUILDING MANAGMENT SYSTEMBASIS OF DESIGNBOTTOM OF PIPEDOMESTIC COLD WATER SUPPLYCHEMICAL FEEDCLEANOUTCENTRAL PLANTCONDENSER WATER RETURNCONDENSER WATER SUPPLYCONDENSING UNITCHILLED WATER RETURNCHILLED WATER SUPPLYDOMESTIC COLD WATERDIRECT DIGITAL CONTROLSDIAMETERDRAINEXHAUST AIRELECTRICAL CONDUCTORELECTRICAL DUCT HEATEREXHAUST FANELECTRIC HEATERENERGY MANAGEMENT CONTROL SYSTEMFLOOR DRAINDOMESTIC HOT WATER SUPPLYHUB DRAINHEAT PUMPDOMESTIC HOW WATER RETURNHEATING HOT WATER RETURNHEATING HOT WATER SUPPLYLEAVING AIR TEMPERATURETHOUSANDS OF BTU'S PER HOURMECHANICAL CONTRACTORNATURAL GAS PIPINGNORMALLY OPENOUTSIDE AIROVER FLOWPLUMBING CONTRACTORPIPE SUPPORTRETURN AIRREFRIGERANTRELATIVE HUMIDITYREMOTE MONITORROOF TOP UNITRAIN WATERSUPPLY AIRSUPPLY FANTRIPLE DUTY VALVETYPICALUNDERGROUNDUNLESS OTHERWISE NOTEDVARIABLE FREQUENCY DRIVEVENTWITHWIRE MESH SCREEN

    ABR(E)

    ADJAFFAFGAH

    AHUBMSBODBOP

    CCHFCOCPCRCSCU

    CHWRCHWSDCWDDCDIADRNEAEC

    EDHEFEH

    EMCSFDH

    HDHPHR

    HWRHWSLATMBHMCNGNOOAOFPCPSRA

    REFRRHRMRTURWSASF

    TDVTYPUG

    UNOVFDVNTW/

    WMS

    ABBREVIATIONS

    PARTITION PLAN LEGEND

    1 HR. RATED PARTITION TO DECK

    SEE SHEET A002 FOR CONSTRUCTION OF PARTITION TYPES.PARTITION KEY:

    EXISTING 1 HR. RATED PARTITION TO DECK. ENSURE SEALING TIGHTTO DECK WITH APPROVED SAFING MATERIAL.

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    5/3

    1/2

    016 1

    1:1

    5:3

    0 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    KTD

    WDB

    HVAC - NOTES& LEGENDS

    M-001

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    No. Description Date

    1 OSE COMMENTREVISIONS

    02/18/2016

  • EXISTINGLOUVER

    EXISTING EXTERIORWALL

    PLENUM, SEAL ANDINSULATE BACK WITH 1"FLEXIBLE ELASTOMERICINSULATION

    EXISTINGLOUVER

    EXISTING EXTERIORWALL

    MOTOR ACTUATEDDAMPER

    INSECT SCREEN

    PLENUM, SEAL AND INSULATEBACK WITH 1" FLEXIBLEELASTOMERIC INSULATION

    INTAKE DUCT,SEE PLANSFOR SIZES

    FACTORY BUILT CURB

    ROOFING MATERIAL

    HOOD COVER

    COORDINATE ROOF WORK

    WITH ARCHITECTURAL PLANS

    AND ROOFING CONTRACTOR.

    ATTACH DUCTAT ROOF CURB

    SECURE HOOD TO

    CURB WITH CADMIUM

    PLATED STEEL SCREWS

    AT EACH CORNER

    INSECT SCREEN ALL

    AROUND

    FLASHING AND

    COUNTERFLASHING

    BAROMETRICRELIEF DAMPER

    STUB DUCT INTORETURN PLENUMCHASE

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    5/3

    1/2

    016 1

    1:1

    5:3

    5 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    KTD

    WDB

    HVACSCHEDULES

    M-002

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    FAN COIL UNIT SCHEDULE

    INDOORMARK

    COOLINGMBH

    SENSIBLEMBH EAT DB EAT WB LAT DB LAT WB

    CHILLED WATER

    MANUFACTURER MODELFLOW RATE

    (GPM) EWT °F LWT °FPRESSURE DROP

    AT MAX FLOWFCU-1 18.1 14.9 75°F 63°F 58°F 57°F 3.6 42°F 54°F 6.4 FT MITSUBISHI PKA-A18HA

    FCU-2 18.1 14.9 75°F 63°F 58°F 57°F 3.6 42°F 54°F 6.4 FT MITSUBISHI PKA-A18HA

    FCU-3 18.1 14.9 75°F 63°F 58°F 57°F 3.6 42°F 54°F 6.4 FT MITSUBISHI PKA-A18HA

    FCU-4 18.1 14.9 75°F 63°F 58°F 57°F 3.6 42°F 54°F 6.4 FT MITSUBISHI PKA-A18HA

    FCU-5 18.1 14.9 75°F 63°F 58°F 57°F 3.6 42°F 54°F 6.4 FT MITSUBISHI PKA-A18HA

    EXHAUST FAN SCHEDULE

    MARK CFM TOTAL SPNOISE

    CRITERIA MANUFACTURER MODELEF-1 500 0.70 in-wg 9.1 SONES GREENHECK G-098-VG

    EF-2 300 0.50 in-wg 7.6 SONES GREENHECK G-085-D

    EF-3 375 0.60 in-wg 7.6 SONES GREENHECK G-090-D

    LAB EXHAUST FAN SCHEDULE

    MARK CFM INLET SIZE AIR P.D.

    NOISECRITERIA@ INLET MANUFACTURER MODEL

    LEF-1 515 5" 3" W.G. 79 dB GREENHECK VK-H-10-5

    LEF-2 515 5" 3" W.G. 79 dB GREENHECK VK-H-10-5

    VAV SCHEDULE

    MARK INLET SIZEDESIGN

    CFM

    MINIMUMCOOLING

    CFM

    MAX AIRPD (IN.W.G.)

    HEATINGCFM EAT °F LAT °F GPM EWT °F LWT °F

    MAX COILPD (FT) MANUFACTURER MODEL

    VAV-100 10" 925 310 0.3 505 55.0 95.0 1.5 150 120 1.93 TRANE VCWF10

    VAV-101C 6" 425 140 0.3 140 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-102 8" 800 265 0.3 265 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    VAV-102C 4" 110 35 0.3 50 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-104 8" 800 265 0.3 265 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    VAV-105 6" 470 155 0.3 155 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-107 8" 650 215 0.3 215 55.0 95.0 0.50 150 120 0.67 TRANE VCWF08

    VAV-108 5" 325 110 0.3 110 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-109 8" 540 180 0.3 220 55.0 95.0 1.0 150 120 0.50 TRANE VCWF08

    VAV-110 6" 475 160 0.3 160 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-111 6" 440 145 0.3 155 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-112 10" 950 315 0.3 315 55.0 95.0 1.0 150 120 0.73 TRANE VCWF10

    VAV-113 8" 875 290 0.3 420 55.0 95.0 1.5 150 120 0.92 TRANE VCWF08

    VAV-114A 5" 260 85 0.3 105 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-114B 8" 500 165 0.3 235 55.0 95.0 1.0 150 120 0.51 TRANE VCWF08

    VAV-117 8" 850 285 0.3 285 55.0 95.0 1.0 150 120 0.68 TRANE VCWF08

    VAV-119 5" 270 90 0.3 115 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-120 5" 250 85 0.3 85 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-121 6" 485 160 0.3 245 55.0 95.0 1.0 150 120 0.51 TRANE VCWF06

    VAV-122 8" 850 285 0.3 285 55.0 95.0 1.0 150 120 0.68 TRANE VCWF08

    VAV-123A 4" 85 30 0.3 30 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-123B 8" 790 265 0.3 360 55.0 95.0 1.0 150 120 1.28 TRANE VCWF08

    VAV-123C 4" 175 60 0.3 60 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-124 8" 810 270 0.3 340 55.0 95.0 1.0 150 120 0.90 TRANE VCWF08

    VAV-125 10" 930 930 0.3 930 55.0 95.0 3.0 150 120 8.0 TRANE VCWF10

    VAV-126 5" 290 95 0.3 235 55.0 95.0 1.0 150 120 0.50 TRANE VCWF05

    VAV-201A 8" 600 200 0.3 200 55.0 95.0 1.0 150 120 0.50 TRANE VCWF06

    VAV-201B 8" 600 200 0.3 205 55.0 95.0 1.0 150 120 0.50 TRANE VCWF06

    VAV-202 4" 210 70 0.3 70 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-205A 8" 575 190 0.3 215 55.0 95.0 1.0 150 120 0.51 TRANE VCWF08

    VAV-205B 5" 265 90 0.3 135 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-206 8" 550 185 0.3 205 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    VAV-207A 8" 675 225 0.3 225 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    VAV-207B 4" 95 30 0.3 65 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-207C 8" 500 165 0.3 200 55.0 95.0 1.0 150 120 0.51 TRANE VCWF08

    VAV-207D 8" 525 175 0.3 235 55.0 95.0 1.0 150 120 0.51 TRANE VCWF08

    VAV-207E 4" 95 30 0.3 65 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-208 8" 530 175 0.3 205 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    VAV-210A 4" 160 55 0.3 55 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-210B 6" 440 145 0.3 190 55.0 95.0 1.0 150 120 0.50 TRANE VCWF06

    VAV-210C 6" 475 160 0.3 185 55.0 95.0 1.0 150 120 0.51 TRANE VCWF06

    VAV-211 5" 275 90 0.3 105 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-215 6" 425 140 0.3 175 55.0 95.0 1.0 150 120 0.50 TRANE VCWF05

    VAV-216A 8" 650 215 0.3 215 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    VAV-216B 5" 300 100 0.3 120 55.0 95.0 0.50 150 120 0.50 TRANE VCWF05

    VAV-216C 6" 350 115 0.3 115 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-217A 6" 425 140 0.3 150 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-217B 4" 200 65 0.3 65 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-217C 8" 525 175 0.3 225 55.0 95.0 1.0 150 120 0.51 TRANE VCWF08

    VAV-217D 6" 385 130 0.3 130 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-218A 8" 525 175 0.3 175 55.0 95.0 0.50 150 120 0.50 TRANE VCWF08

    VAV-218B 4" 190 65 0.3 65 55.0 95.0 0.50 150 120 0.50 TRANE VCWF04

    VAV-218C 6" 425 140 0.3 225 55.0 95.0 1.0 150 120 0.51 TRANE VCWF06

    VAV-218D 6" 475 160 0.3 160 55.0 95.0 0.50 150 120 0.50 TRANE VCWF06

    VAV-218E 6" 350 115 0.3 165 55.0 95.0 0.50 150 120 0.51 TRANE VCWF06

    VAV-218F 8" 525 175 0.3 200 55.0 95.0 1.0 150 120 0.51 TRANE VCWF08

    VAV-218G 8" 615 205 0.3 275 55.0 95.0 1.0 150 120 0.58 TRANE VCWF08

    VAV-218H 6" 445 150 0.3 185 55.0 95.0 1.0 150 120 0.51 TRANE VCWF06

    VAV-219 8" 820 275 0.3 275 55.0 95.0 1.0 150 120 0.67 TRANE VCWF08

    AIR HANDLING UNIT SCHEDULE

    MARK

    AIR CAPACITY

    EXTERNALSTATIC

    TOTALSTATIC

    COOLING COIL PREHEAT COIL

    MANUFACTURER MODELDESIGN

    CFMMAX OA

    CFMMIN OA

    CFM TOTAL MBHSENSIBLE

    MBH EAT DB EAT WB LAT DB LAT WB GPM EWT LWT COIL PDSENSIBLE

    MBH EAT DB LAT DB EWT LWT GPM COIL WPD(E) AH-1 9100 1700 535 3 4.5 374 258 80.0 °F 67.0 °F 54.3 °F 53.6 °F 62 42.0 °F 54.0 °F 2.80 FT 100 40.0 °F 55.0 °F 150.0 °F 120.0 °F 8 6.91 TRANE MCCB

    (E) AH-2 9100 1400 625 3 4.5 386 266 80.0 °F 67.0 °F 53.5 °F 53.1°F 64 42.0 °F 54.0 °F 4.2 FT 100 40.0 °F 55.0 °F 150.0 °F 120.0 °F 3 8.26 TRANE MCCB

    (E) AH-4 10330 3140 1400 2.3 3 516 309 82.0 °F 70.0 °F 55.0 °F 54.4 °F 86 42.0 °F 54.0 °F 16.4 FT 75 25.0 °F 40.0 °F 150.0 °F 120.0 °F 5 3.82 TRANE CSOA017

    PUMP SCHEDULE

    MARK GPMPUMPHEAD MOTOR HP RPM TYPE VFD MANUFACTURER MODEL

    BP-1 25 30' 2/5 3250 IN-LINE NO BELL & GOSSETT PL-55

    BP-2 25 30' 2/5 3250 IN-LINE NO BELL & GOSSETT PL-55

    CWP-1 215 80' 7.5 1750 END SUCTION YES BELL & GOSSETT E1510 MODEL 2BD

    CWP-2 215 80' 7.5 1750 END SUCTION YES BELL & GOSSETT E1510 MODEL 2BD

    HWP-1 60 60' 5 1750 END SUCTION YES BELL & GOSSETT E1510

    HWP-2 60 60' 5 1750 END SUCTION YES BELL & GOSSETT E1510

    BOILER SCHEDULE

    MARK CAPACITYFLOWRATE

    FLUID TEMPERATURE

    MANUFACTURER MODELENTERING LEAVINGB-1 399000 BTUH 21 GPM 120 150 LOCHINVAR KBN400

    B-2 399000 BTUH 21 GPM 120 150 LOCHINVAR KBN400

    AIR DISTRIBUTION SCHEDULE

    MARK DESCRIPTIONFACE SIZE

    HFACE SIZE

    W NECK SIZE MANUFACTURER MODELSupply Air

    PD106 SQUARE PLAQUE 12" 12" 6" PRICE ASPD

    PD206 SQUARE PLAQUE 24" 24" 6" PRICE ASPD

    PD208 SQUARE PLAQUE 24" 24" PRICE ASPD

    PD210 SQUARE PLAQUE 24" 24" PRICE ASPD

    PD212 SQUARE PLAQUE 24" 24" PRICE ASPD

    SDS50 LINEAR SLOT DIFFUSER 4' LONG 2 SLOT 6" PRICE SDS50 WITH SDB1FACTORY PLENUM

    SDS75 LINEAR SLOT DIFFUSER 4' LONG 2 SLOT 6" PRICE SDS75 WITH SDB1FACTORY PLENUM

    SWS1 LOUVERED SIDEWALL 6" 12" 10" PRICE 620DAL

    SWS2 LOUVERED SIDEWALL 4" 10" 6" PRICE 620DAL

    Return Air

    LF222 PRICE 630DAL

    SDR75 LINEAR SLOT RETURN 4' LONG 2 SLOT NONE PRICE SDR75

    Exhaust Air

    LF111 LOUVERED FACEEXHAUST

    12" 12" 10"x10" PRICE 630DAL

    LF222 LOUVERED FACEEXHAUST

    24" 24" 22"x22" PRICE 630DAL

    NOTES:

    1.2.

    SEE ELECTRICAL EQUIPMENT CONNECTION SCHEDULE FOR VOLTAGE INFORMATION.SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

    NOTES:

    1.2.3.

    SEE ELECTRICAL EQUIPMENT CONNECTION SCHEDULE FOR VOLTAGE INFORMATION.SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.EXHAUST FANS SHALL OPERATE ON TIMECLOCK DURING HOURS OF OPERATION.

    NOTES:

    1.2.3.4.5.

    SEE ELECTRICAL EQUIPMENT CONNECTION SCHEDULE FOR VOLTAGE INFORMATION.SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.SEISMIC VIBRATION ISOLATION CURB SHALL BE PROVIDED WITH EACH FAN.LAB EXHAUST FANS SHALL OPERATE CONTINUALLY.PROVIDE WITH BACNET INTERFACE FOR MONITORING BY CONTROLS SYSTEM.

    NOTES:

    1.2.3.

    SEE ELECTRICAL EQUIPMENT CONNECTION SCHEDULE FOR VOLTAGE INFORMATION.SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.INLET DUCT SHALL BE SAME SIZE AS LISTED VAV TERMINAL INLET.

    NOTES:

    1. UNITS INDICATED ABOVE ARE EXISTING TO REMAIN.2. SEE ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.3. TEST AND BALANCE CONTRACTOR SHALL MEASURE AND RECORD CHILLED AND HYDRONIC HEATING WATER FLOW TO UNITS PRIOR TO START OF RENOVATION FOR COMPARISON AT CONCLUSION OF WORK.4. CONTRACTOR SHALL PROVIDE AND INSTALL THE FOLLOWING FOR THE EXISTING AIR HANDLERS:

    NOTES:

    1. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES.2. COORDINATE MOUNTING TYPE AND ACCESSORIES WITH ARCHITECTURAL CEILING GRID.3. COORDINATE AIR DISTRIBUTION LOCATIONS WITH ALL OTHER TRADES.4. ALL AIR DISTRIBUTION SHALL BE ALUMINUM CONSTRUCTION WITH BAKED ENAMEL "OFF-WHITE" FINISH.5. SURFACE MOUNTED AIR DISTRIBUTION DEVICES SHALL BE MOUNTED WITHOUT VISIBLE FASTENERS.6. ALL CEILING DIFFUSERS SHALL BE 4-WAY BLOW.

    AIR SEPARATOR SCHEDULE

    MARKSYSTEM

    CONNECTION GPM

    PRESSUREDROP AT MAX

    FLOW MANUFACTURER MODELAS-1 HOT WATER 60 1.8 FT BELL & GOSSETT RL-3

    AS-2 CHILLED WATER 160 4.4 FT BELL & GOSSETT RL-4

    EXPANSION TANK SCHEDULE

    MARK SYSTEMTANK VOLUME

    (GALLONS)

    ACCEPTANCEVOLUME

    (GALLONS) MANUFACTURER MODELET-1 HOT WATER 44.0 34.0 BELL & GOSSETT HFT-90V

    ET-2 CHILLED WATER 30.0 30.0 BELL & GOSSETT ATF-12

    NOTES:

    1. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

    NOTES:

    1. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

    NOTES:

    1. SEE ELECTRICAL EQUIPMENT CONNECTION SCHEDULE FOR VOLTAGE INFORMATION.2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.3. PROVIDE WITH CONDENSATE NEUTRALIZER KIT FOR DISCHARGE INTO FLOOR DRAIN.4. PROVIDE WITH MANUFACTURER PROVIDED CONCENTRIC VENT KIT FOR DIRECT VENT INTAKE AND FLUE

    PENETRATIONS THROUGH WALL.5. PROVIDE WITH FACTORY MOUNTED CONTROL PANEL WITH INTEGRAL SEQUENCES TO CONTROL BOILER,

    BOILER PUMP, EMERGENCY SHUTOFF, ETC. PANEL SHALL BE BACNET COMPLIANT FOR CONNECTION BYCONTROLS SYSTEM.

    GRAVITY VENTILATOR SCHEDULE

    MARK CFM MANUFACTURER MODELGV-1 4600 GREENHECK FGR

    GV-2 3000 GREENHECK FGR

    NOTES:

    1. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.2. REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.3. PROVIDE UNIT HEATERS WITH FIELD INSTALLED DISCONNECT

    SWITCH.

    No. Description Date

    1 OSE COMMENTREVISIONS

    02/18/2016

    UNIT HEATER SCHEDULE

    MARK TOTAL KW MANUFACTURER MODELUH-1 1.8 MARKEL 5600

    UH-2 1.8 MARKEL 5600

    NOT TO SCALEM-002

    1 INTAKE LOUVER CAP INSTALLATION DETAIL

    NOT TO SCALEM-002

    2 INTAKE LOUVER INSTALLATION DETAIL

    NOT TO SCALEM-002

    3 GRAVITY VENTILATOR INSTALLATION DETAIL

    NOTES:

    1. ALUMINUM CONSTRUCTION WITH ALUMINUM INSECT SCREEN.

    a. NEW FILTERS PRIOR TO FINAL COMPLETION.b. INSTALL COMPONENTS AND CONTROLS NECESSARY FOR DEMAND CONTROL VENTILATION INCLUDING CO2 SENSORS. SEE SCHEMATIC FOR ADDITIONAL INFORMATION.c. REHEAT COILS SHALL BE REMOVED FROM UNITS, PIPE PENETRATIONS AND UNIT CASING SHALL BE SEALED.d. INSTALL MOTORIZED DAMPERS IN OUTSIDE AIR AND RETURN AIR STREAMS.e. INSTALL COMPONENTS AND CONTROLS NECESSARY FOR DRY BULB ECONOMIZER CONTROL.f. INSTALL DUCT MOUNTED SMOKE DETECTORS IN SUPPLY AND RETURN DUCTS.g. PROVIDE AND INSTALL EBTRON GTx116-P+ OUTSIDE AIR MONITORING STATIONS, FIELD INSTALL IN THE UNIT INTAKE HOODS OR DUCT AS APPROPRIATE.h. FAN MOTORS SHALL BE REPLACED WITH INVERTER DUTY TYPE, ALLOWING VARIABLE SPEED OPERATION. VERIFY SIZE AND HP TO BE INSTALLED IN EXISTING CABINETi. (E) AH-4 COOLING COIL SHALL BE REPLACED WITH TRANE DUWB40, 8-ROW, UW, DELTA FLO E COIL MATCHING CAPACITIES INDICATED ABOVE, SIZED TO FIT IN EXISTING AIR HANDLER. FIELD VERIFY BEFORE ORDERING.j. (E) AH-1 COOLING COIL SHALL BE REPLACED WITH TRANE DW0B48, 6-ROW, W, PRIMA-FLO E COIL MATCHING CAPACITIES INDICATED ABOVE, SIZED TO FIT IN EXISTING AIR HANDLER. FIELD VERIFY BEFORE ORDERING.k. (E) AH-2 COOLING COIL SHALL BE REPLACED WITH TRANE DW0B36, 6-ROW, W, PRIMA-FLO E COIL MATCHING CAPACITIES INDICATED ABOVE, SIZED TO FIT IN EXISTING AIR HANDLER. FIELD VERIFY BEFORE ORDERING.

    NOTES:

    1. SEE ELECTRICAL EQUIPMENT CONNECTION SCHEDULE FOR VOLTAGE INFORMATION.2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.3. VFD'S SHALL BE FURNISHED BY CONTROL'S CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR.4. HWP AND CWP PUMP MOTORS SHALL BE INVERTER DUTY RATED.

  • NOTES:

    H = FAN STATIC PRESSURE (IN. W.C.) + 1"3.

    J"

    ACCESSIBLE FOR CLEANING.

    2. "RUNNING" TYPE TRAPS SHALL BE UNACCEPTABLE.

    1. LOCATE TRAPS SO AS TO BE

    PIPE FULL SIZE OFUNIT DRAIN

    H"

    UNIT CASING

    SCREWED CAP

    OPEN END (VENT)

    J = H/2 (MINIMUM)

    45° "Y" TEE

    2-WAY 45° "Y" TEE

    90° CONICAL TEE

    90° TEE WITH 45° TAKE-OFF

    DIRECTIONOF AIRFLOW

    DIRECTIONOF AIRFLOW

    1-1/2 D

    D

    1-1/2 D

    D

    BRANCH DUCT

    BRANCH DUCT

    BRANCH DUCT

    TRUNK

    DUCT

    TRUNK DUCT

    DIRECTION OF

    AIR FLOW

    DIRECTIONOF AIRFLOW

    BRANCH DUCT

    TRUNK

    DUCT TRUNK

    DUCT

    ROUND METAL BRANCH DUCTSAME SIZE AS VAV CONNECTIONUNLESS NOTED OTHERWISE

    HANGER RODS ORSTRAPS UP TOSTRUCTURE

    AIR TERMINAL UNIT

    HOT WATER COIL

    TAKE-OFF FITTING

    EXISTING SUPPLYAIR TRUNK

    4'-0"(MIN & MAX)STRAIGHT RUN OR ASDICTATED BY MANUFACTURER'S WRITTENINSTALLATION INSTRUCTIONS.

    5 FT

    7

    6 8 10

    9 1110 12

    1312 14 16

    1614 17 19

    864 532 2 1/21 1/21 1 1/4THRU 3/4

    7 7

    7 98

    SIDE VIEW TRAPEZE HANGER FOR UPTO 1000 LB. UNIFORM LOAD

    ADJUSTABLE CLEVIS HANGER

    TYPE 1 - SEE SPECIFICATIONS

    ADJUSTABLE CLEVIS HANGER

    TYPE 43 - SEE SPECIFICATIONS

    PROVIDE INSULATION SHIELD& INSERT FOR ALL PIPING (8" MIN.)

    BAND

    1-5/8" 12 GAUGECHANNEL OR2"x2"x1/4" ANGLE

    1/2" DIA. HANGER RODSWITH 36" MAX. SPACINGON EACH CHANNEL

    WELD

    SADDLE

    INSULATION SHIELDAT HANGER

    PROVIDE HIGHCOMPRESSIVE STRENGTHINSULATION (9 PSF MIN.DENSITY) UNDERINSULATION SHIELD

    INSULATION (VAPORBARRIER TYPE ISREQUIRED FOR LOWTEMPERATURE PIPE)

    THREADED HANGER ROD

    MAXIMUM PIPE/TUBING SUPPORT SPACING

    NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

    NOM. SIZE

    PIPE

    TUBING

    IN.

    FT.

    FT.

    1" MAX.

    NOTES:SEE SPECIFICATIONS FORDETAILED HANGER REQUIREMENTS

    NOTES:

    OTHER OBSTACLE

    DUCT SEALANT

    DUCT CLAMP

    FLEXIBLE DUCTWORK

    SUSPENDED CEILING

    DUCTWORK OR

    SLAB

    FLAT OVAL CONNECTION

    SQUARE CEILING

    DIFFUSER

    SUPPLY AIRPLENUM

    1. THIS DETAIL SHALL APPLY TO CEILING OUTLETS AND INLETS THAT ARE LOCATEDBELOW DUCTWORK OR OTHER OBSTACLES WHERE CLEARANCES ARE MINIMAL.

    2. THE SIZE OF THE SUPPLY AIR PLENUM SHALL BE A MINIMUM OF 1" LARGER IN HEIGHTAND WIDTH THAN THE FLAT OVAL DUCTWORK CONNECTION.

    3. THE SUPPLY AIR PLENUM IS REQUIRED TO BE INSULATED. THE PLENUM/DIFFUSERCONNECTION SHALL BE SEALED WITH AN APPROVED DUCTWORK SEALANT.

    4. PROVIDE A ROUND TO FLAT OVAL TRANSITION SECTION OF DUCTWORK AS REQUIRED.5. THE FOLLOWING SCHEDULE SHALL BE USED FOR ROUND TO FLAT OVAL DUCTWORK

    SIZE EQUIVALENTS:

    ROUND (INCHES) FLAT OVAL (HxW INCHES)

    3x11, 4x9, 5x84x15, 5x12, 6x116x15, 7x13, 8x11, 9x127x20, 8x17, 9x15, 10x139x20, 10x18, 11x17, 12x1510x23, 8x30, 6x4410x30, 12x26, 14x2212x32, 14x28, 16x2412x38, 14x32, 18x3014x38, 16x34, 18x3016x38, 18x34, 20x32

    68101214161820222426

    NOTES:

    MANUAL

    3. SPIN-IN FITTINGS WITH INTEGRAL SCOOP AND DAMPER SHALL ONLY BE USED ON LOW PRESSURE DUCT.2. TAKE-OFFS IN MEDIUM PRESSURE DUCT SHALL HAVE AN OVERSIZED INTAKE.

    1. CONTRACTOR MAY SUBSTITUTE A MANUFACTURED FITTING FOR THE DETAILED TAKE-OFF ABOVE.

    ELEVATION

    1" MIN

    ROUND BRANCHDUCT

    PLAN

    DAMPER

    RECTANGULAR

    BRANCH DUCT

    1" MIN

    ELEVATION

    PLAN

    6"

    DAMPER

    60°

    6"

    MAIN DUCT

    AIRFLOW

    MAIN DUCT

    SUPPLY

    RETURN OR EXHAUST

    45°

    MANUAL

    6"

    4. FITTINGS SHALL BE SCREWED TO THE TRUNK DUCT AND SEALED WITH MASTIC. MASTIC TAPE IS NOT ACCEPTABLE, SEE SPECIFICATIONS.5. IF VAV BOX IS LOCATED IN BRANCH DUCT, BALANCE DAMPER SHALL NOT BE INSTALLED IN TAKOFF FROM MAIN TRUNK DUCT.

    NOTES:

    RETURN AIR BOX SHALL BE MINIMUM 12" HIGH. RETURN DUCT MAYTAP INTO THE SIDE OF THE BOX A MINIMUM OF 6" ABOVE GRILLE.

    NYLONCLAMP

    NYLON CLAMP

    DUCT WRAP OVERENTIRE DIFFUSER

    LAY-IN CEILINGSUPPLY DIFFUSER

    PREINSULATEDFLEX. DUCT

    DUCT WRAP (TYP.)

    OPPOSED BLADEDAMPER

    NYLON CLAMP

    LAY-IN RETURNAIR GRILLE

    RETURN AIRBOX W/LINER

    NYLON CLAMP

    PREINSULATEDFLEX. DUCT

    DUCT WRAP (TYP.)

    MANUAL DAMPER

    ROUND METAL DUCT

    TAKE-OFF FITTING

    SUPPLY DUCTW/ WRAP

    METAL COLLAR

    RETURN DUCTW/ WRAP

    INSTALL NYLON CLAMPS ON INNER FLEX DUCT LINER AND OUTER JACKET. TAPE ENDS OFPREINSULATED FLEX. DUCT AT THE DIFFUSER AND THE BRANCH DUCT CONNECTION.

    RETURN AIR BOX SHALL BE MINIMUM 12" HIGH. RETURN DUCT MAY TAP INTO THE SIDE OFTHE BOX A MINIMUM OF 6" ABOVE GRILLE.

    1.

    2.

    MANUAL DAMPER

    PROVIDE YOUNG REGULATOR REMOTE DAMPER CONTROLLER FOR EACH DIFFUSER AND GRILLELOCATED IN AREAS WITH INACCESSIBLE CEILINGS. LOCATE CONTROLLER IN A CONCEALED,ACCESSIBLE LOCATION.

    3.

    MOTOR ACCESS AND AIRENTRAINMENT OPENING

    BOLTED ANDGASKETEDACCESS PANEL

    ISOLATIONDAMPER

    LIFT LUG

    DRAIN HOLE1"COUPLING

    SEISMIC/WIND LOADAND VIBRATION ISOLATIONENGINEERED ROOF CURB

    WEATHERHOODAND DAMPER

    ACTUATOR COVERWITH BIRDSCREEN

    DRAIN CONNECTION1"COUPLING

    ROOF LINE

    BYPASSDAMPER

    PRIMARYAIR

    BYPASS AIR

    CHEMICAL RESISTANTFLEXIBLE CONNECTOR

    TRANSITION ASREQUIRED

    WELDED STAINLESSSTEEL EXHAUST DUCTFROM ASSOCIATEDFUME HOOD, SEEDRAWINGS

    MECHANICALLY FASTEN ROOFCURB TO STRUCTURE PERSEISMIC RECOMMENDATIONS

    LOCATE AIRFLOWMONITORINGSTATION CLOSE TO LABHOOD AS INDICATEDON HVAC PLANS,ACCESSIBLE FROMABOVE LAB CEILING

    PROVIDE SEISMIC BRACING ASRECOMMENDED BY SEISMICENGINEER. SEE SEISMICCHART, M001, FOR MOREINFORMATION.

    SUPPLY WATER

    G

    BOILER PUMPASSEMBLY SEEDETAIL (TYP)

    6" CONCRETE PAD, TYP.

    GROUND JOINT UNION

    B-1

    THERMOMETER TYP.

    G

    3"

    B-2

    FROMSYSTEM

    RETURN WATER

    3"

    2"

    CHECKVALVE (TYP)

    LOW WATER CUT-OFF

    SWITCH, TYP.

    PRESSURE TEMPERATURE

    GAUGE TYP.

    STRAINER TYP.

    FOR CONT.

    SEE PLUMBING PLANS.

    6" DIRT LEG,(TYP)

    PIPE RELIEF VALVE

    DISCHARGE FULL SIZE

    TO FLOOR DRAIN,

    TYP.

    SHUTOFF VALVE(TYP)

    PVC GASVENT THRU SIDEWALL,TYP. SEE PLANS.

    P&T

    P&T

    NOTES:

    1. FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER, SEE APPROPRIATE DIMENSIONAL DRAWING.2. SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY, BY GRAVITY, TO A CONVENIENT FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT 18"ABOVE FLOOR.3. LOCATE WATER INLET AND OUTLET FITTINGS (i.e. UNIONS, ELBOWS, ETC.) A MINIMUM OF 6" FROM BOILER FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS. ALL PIPING AND ELECTRICCONNECTIONS (SERVICE SWITCHES, CONDUIT BOXES) SHOULD LIKEWISE BE 6" AWAY FROM SIDE PANELS.4. REFRENCE PLUMBING DOCUMENTS FOR NATURAL GAS PIPING DIAMETER, ROUTING AND REQUIREMENTS. COORDINATE WITH PC.

    MAX LENGTH OF 12"

    MANUAL GAS SHUTOFF VALVE W/1/8" NPT PLUGGED TAPPING, TYP.

    GAS PRESSUREREGULATOR TOMAINTAIN 4" WC,(TYP).

    TO PUMP SUCTION

    2"

    NOTES:

    1. CHEMICAL SHOT FEEDER SHALL BE 2'-0" AFF MIN.

    2. SEE SPECIFICATIONS FOR FURTHER INFORMATION.COORDINATE WITH CHEMICAL TREATMENT PROVIDER.

    3/4" PIPING ROUTED TO WATERLOOP. CONNECT TODISCHARGE SIDE OF PUMPS.

    3/4" PIPING ROUTED TO WATERLOOP. CONNECT TO SUCTION SIDEOF PUMPS UPSTREAM OF AIRSEPERATOR.

    CHECK VALVE

    BALL VALVE(TYP.)

    1/2" DRAINVALVE

    FINISHED FLOOR

    HOSE CONNECTION

    CHEMICAL SHOT FEEDER

    MANUFACTURER'S STANDARDSUPPORT LEG, BOLTED DOWNTO FLOOR (TYPICAL 3X)

    MULTIPORT PRESSUREINDICATOR (4-PORT)

    1/4" O.D. COPPER TUBINGW/ COMP. FITTINGS

    DRAIN: TERMINATENEAR F.D.TRANSITION TO LINE

    SIZE AS INDICATED ONPLANS DIRECTLY OFFCONNECTION TO PUMP(TYPICAL)

    TO SYSTEM

    WHERE REQ'D AN ADDITIONAL PUMP SUPPORTBRACKET MAY BE PROVIDED. PUMP SUPPORTSMUST BE INSTALLED IN SUCH A WAY AS TO NOTCREATE ANY STRESSES ON PUMP COMPONENTS.PUMP SUPPORTS SHALL NOT BE SO RIGIDLYMOUNTED THAT IT LIMITS THE PUMPS ABILITY TOMOVE WITH PIPE EXPANSION MOVEMENT.

    VERTICAL INLINE PUMP

    9" INDUSTRIAL THERMOMETER W 3/4"NPT COPPER WELL

    INSTALLER IS RESPONSIBLE FORINSTALLING AND SUPPORTING THEVERTICAL INLINE PUMP PER THEMANUFACTURER'S RECOMMENDEDINSTALLATION INSTRUCTIONS.

    TRIPLE DUTY VALVE

    DOUBLE SPHERE EPDMFLEXIBLE PIPECONNECTOR (TYPICAL)

    FROM SYSTEM

    PIPE HANGERS (SPRING

    & NEOPRENE TYPE)

    STRAINER (LINE SIZE) W/HOSE ENDED BLOWDOWNVALVE / DRAIN

    ISOLATION VALVE

    SPRING TYPE PIPEHANGERS, SECURETO STRUCTURE

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    5/3

    1/2

    016 1

    1:1

    5:3

    7 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    KTD

    WDB

    HVAC DETAILS

    M-003

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    NOT TO SCALEM-003

    6 CONDENSATE DRAIN TRAP INSTALLATION DETAIL

    NOT TO SCALEM-003

    1 ROUND DUCT BRANCH TAKE OFF DETAIL

    NOT TO SCALEM-003

    7 TYPICAL VAV INSTALLATION DETAIL

    NOT TO SCALEM-003

    4 MECHANICAL PIPE SUPPORT DETAIL

    NOT TO SCALEM-003

    5 CEILING DIFFUSER/GRILLE & DUCT OBSTRUCTION DETAIL

    NOT TO SCALEM-003

    2 TYPICAL DUCT TAKE OFF INSTALLATION DETAILNOT TO SCALE

    M-003

    3 TYPICAL DIFFUSER/GRILLE INSTALLATION DETAIL

    NOT TO SCALEM-003

    10 LAB EXHAUST FAN INSTALLATION DETAILNOT TO SCALE

    M-003

    9 BOILER PIPING DETAILNOT TO SCALEM-003

    8 CHEMICAL TREATMENT INSTALLATION DETAIL

    No. Description Date

    1 OSE COMMENTREVISIONS

    02/18/2016

    NOT TO SCALEM-003

    11 PUMP_INLINE PUMP DETAIL

  • NOTES:

    24" DIA. MIN.

    GRADE

    1. COVER WITH LANDSCAPE AFTER INSPECTION IS COMPLETED.

    CONDENSATE DRAIN LINE

    HOLE IN GROUND24" DIAMETER MIN.BY 24" DEEP MIN.FILLED WITH CRUSHEDSTONE 1/2" TO1 1/2" SIZE.

    2. CONTRACTOR SHALL VERIFY THAT THE PRIMARY CONDENSATE DRAIN LINE IS IN WORKINGORDER BY RUNNING WATER DOWN THRU THE DRAIN LINE FROM THE POINT OF THE COILCONNECTION.

    3. DRAIN LINE SHALL TERMINATE 6" ABOVE FINISHED GRADE OVER TOP OF THE DRAIN PIT.

    TABLE 4-1 RECTANGULAR DUCT HANGERS MINIMUM SIZE

    1-1/2"X16GA.

    1-1/2"X16GA.

    3/4"-3000 LBS.5/8"-2000 LBS.1/2"-1250 LBS.

    1/4"-270 LBS.3/8"-680 LBS.

    1-1/2 " X 16 GA. - 1100 LBS.

    1" X 22 GA. - 260 LBS.1" X 20 GA. - 320 LBS.

    1" X 16 GA. - 700 LBS.1" X 18 GA. - 420 LBS.

    1-1/2" X 16 GA. -TWO 3/8" DIA.PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE.

    1" X 16 GA. - TWO 1/4" DIA.1" X 18,20,22 GA. - TWO #10 OR ONE 1/4" BOLT

    WIRE OR ROD (DIA.)STRAP

    SINGLE HANGER MAXIMUM ALLOWABLE LOADWHEN STRAPS ARE LAP JOINEDUSE THESE MINIMUM FASTENERS

    SPECIAL ANALYSIS REQUIRED

    1/4"

    1/4"

    1" X 18 GA.

    1" X 16 GA.

    1" X 20 GA.

    1" X 22 GA.

    12 GA. (.106")1" X 22 GA.

    1/4"1" X 22 GA.

    3/8"

    3/8"3/8"

    3/8"

    3/8"

    1" X 22 GA.

    3/8"

    1/4"

    1" X 22 GA. 12 GA. (.106")

    1" X 20 GA.

    1" X 18 GA.

    1" X 16 GA.

    1" X 16 GA.

    3/8"1" X 16 GA.

    3/8"

    1/2"

    1" X 18 GA.

    1/2"

    1/4"1" X 20 GA.

    10 GA. (.135")1" X 22 GA.

    1/2"

    1-1/2"X16GA.

    NOT GIVEN

    1-1/2"X16GA.

    1" X 16 GA.

    1" X 18 GA.

    WIRE/RODSTRAPWIRE/RODSTRAPWIRE/RODSTRAPWIRE/RODSTRAP

    PAIR AT 4FT. SPACINGPAIR AT 5 FT. SPACINGPAIR AT 8 FT. SPACINGPAIR AT 10 FT. SPACING

    P/2= 192"

    P/2=193" UP

    1/2"P/2= 168"

    P/2= 30"10 GA. (.135")1" X 22 GA.

    P/2= 72" 3/8"

    1/2"P/2= 120"

    P/2= 96" 3/8"

    HANGERSTRAPS

    60" MAX.

    SCREWS

    SCREWS MAY BEOMITTED IF HANGER LOOPS

    1" MIN.

    MAXIMUMHALF OF

    DUCTPERIMETER

    INTEGRAL 1" 14 GAUGEGALVANIZED LIPPED STEELMOUNTING CHANNEL

    PIPE CLAMP. SIZEAS REQUIRED

    REFER TO PLANS FORQUANTITY & SIZE OF PIPES

    GALVANIZEDTHREADED ROD, (TYP)

    UV-INHIBITED RUBBER BLOCK,LENGTH AS REQUIRED

    LOCKING SQUAREWASHER & LOCKNUT

    NOTE:

    1. NO ROOFING PENETRATIONS SHALL BE REQUIRED.

    LINING (1 PCF DENSITY)1" INTERIOR ACOUSTICAL

    LAY-INRETURN REGISTER

    CEILING T-BAR

    DUCT SIZE SAMEAS TERMINAL

    CEILING TILE

    16"

    OR OTHER OBSTRUCTIONSTO CLEAR LIGHTS, PIPING3" OR HEIGHT REQUIRED

    CONNECTION

    2'-0" (MIN)

    RETURN GRILLEDEPTH SAME AS

    22 GAUGE (MIN)SHEETMETAL

    SKIN

    CEILING TILE

    SUPPORT FROM STRUCTURE

    WITH SHEETMETAL STRAPS

    (TYP)

    DUCT IS OPEN TO

    ABOVE CEILING

    PLENUM SPACE

    BUILT UP ROOFING

    SECURE ROOF RAIL TO STRUCTURE

    PER SEISMIC SUBMITTAL

    PRESSURE TREATED WOOD NAILER.

    ROOF RAIL SHALL EXTEND

    8" MINIMUM ABOVE FINISHED ROOF.

    SUPPORTED EQUIPMENT

    SECURE ROOFTOP

    EQUIPMENT TO RAIL PER

    SUBMITTAL REQUIREMENTS.

    ROOF RAIL SHALL BE CERTIFIED BY SEISMIC ENGINEER.

    ROOF RAIL SHALL BE SEISMIC / WIND RATED

    DRAIN VALVE

    TO DDC CONTROL SYSTEM

    WATER COIL

    ISOLATION VALVE

    (TYP.)

    MOTORIZED MODULATING

    2-WAY CONTROL VALVE (BY

    CONTROLS CONTRACTOR)

    AUTOMATIC FLOW CONTROLSVALVE WITH TEST PORTS

    FITTING WITH PRESSURE/

    TEMPERATURE TEST PLUG

    (TYPICAL)

    STRAINER

    W/BLOWDOWN

    VALVE & CAP

    PROVIDE BYPASS LINE WITHVALVE FOR FLUSHING SYSTEM.VALVE SHALL BE CLOSED ANDHANDLE REMOVED ATCONCLUSION OF FLUSHING

    NOTE:INSTALL AN ISOLATION VALVE AT EACHCONNECTION TO COIL FOR MULTIPLECOIL CONNECTIONS

    FLEXIBLE CONNECTIONS

    790-100

    107A

    PRESSURE RELIEF VALVE

    AIR VENT

    SUCTION

    TO PUMP

    FROM SYSTEM

    TAG

    1

    1

    MANUF

    B&G

    B&G

    MODEL

    NUMBERDESCRIPTION

    LOW CAPACITYAIR VENT

    PRESSURE GAUGEW/NEEDLE VALVE

    AIR CHARGING VALVE -PRESSURIZE DRY TANKEQUAL TO FILL VALVEPRESSURE

    EXPANSIONTANK

    RELIEF VALVE - (WHENNOT PROVIDED ON HEATTRANSFER DEVICE) PIPEDTO FLOOR DRAIN

    DRAIN BALL VALVE W/HOSE CONNECTION

    UNDERSLUNG CONNECTION CREATESTHERMAL TRAP (12" MIN. DROP)

    SYSTEM CONNECTION -(CONNECT TO SIDE ORBOTTOM OF MAIN HEADER)

    BRACKET SUPPORTS WITHOVERHEAD SUPPORTS

    SHUT-OFF VALVES

    FLANGEDCONNECTION

    (TYPICAL)

    AIR SEPARATOR

    TIE IN MAKE-UP WATER LINEFROM DOMESTIC WATERSERVICE AND PRESSUREREDUCING VALVE

    BLOWDOWN & DRAIN VALVEWITH HOSE CONNECTION

    3/4

    " C

    6" THICK

    CLEARANCE

    1" OPERATING

    CONCRETE PAD

    FILL BASE WITH 3500 PSICONCRETE

    EQUIPMENT ANCHORBOLT TEMPLATE

    CHANNEL PERIMETERFRAME

    ISOLATOR SUPPORT CLIP

    STABLE SPRING ISOLATOR

    HOOKS AND REINFORCINGAS REQUIRED

    CONTINUOUS THREADED ROD

    HEIGHT ADJUST

    LATERAL ADJUST SPACER BRACKET

    STEEL SLIDE CHANNEL

    DUCT SLIDE ASSEMBLY

    SUPPORT BRACKET(WELDED TO CHANNEL)

    LAG BOLT

    RECTANGULAR DUCT SUPPORT

    PROVIDE STRAPS AS NEEDED BYWIND CALCULATIONS

    WIND RATED ROOF RAIL

    GALVANIZEDSUPPLY/RETURN DUCT

    2"x18 GA DUCT STRAP

    SEE ARCHITECTURALDRAWINGS FOR FLASHINGREQUIREMENTS

    1.5" PHENOLIC FOAMINSULATION 2.5 LB./CU. FT.

    ALUMINUM JACKET OVERLAPSEAMS BY 6"

    NOTES:1. MULTIPLE DUCTS MAY BE SUPPORTED BY SINGLE RAIL.2. STRAP DUCT/INSULATION ASSEMBLY TO TUBE SUPPORT PER WIND LOAD ENGINEERING CALCULATIONS.3. ENCLOSE ASSEMBLY WITH ALUMINUM JACKET. SECURE JACKET WITH STAINLESS STEEL SCREWS. LOCATE

    LONGITUDINAL SEAMS ALONG THE BOTTOM OF THE DUCT ASSEMBLY. CAULK ALL JOINTS WITH CLEAR SILICONE CAULK.

    ELECTRIC CONDUIT

    BACK DRAFT DAMPER

    VIBRATION ISOLATOR

    ROOF CRICKET

    NONFUSEDDISCONNECT SWITCH

    SECURE FAN TO CURBWITH CADMIUM PLATEDSTEEL SCREWS AT EACHCORNER

    FOAM RUBBER GASKETAPPLIED TOUNDERSIDE OF FANCURB CAP

    SEISMIC / WIND CURB TO MATCHROOF SLOPE. INSTALL CURBIN ACCORDANCE WITHINSTRUCTIONS.

    ATTACH DUCT TO ROOF CURB WITHGALVANIZED SCREWS 6" ON CENTERS

    STEEL SUPPORTS

    NOTE:

    1. COORDINATE ROOF WORK WITH ARCHITECTURAL PLANS AND ROOFINGCONTRACTOR.

    2. COORDINATE ROOF SLOPE WITH ARCHITECTURAL PLANS AND FIELD VERIFY.3. BACKDRAFT DAMPERS SHALL BE INSTALLED SUCH THAT DAMPERS OPEN ONLY ONCE

    FAN IS ENERGIZED.

    ROOF DECK

    FLASHING AND COUNTER FLASHING

    1" OPER.

    CLEARANCE.

    TO SYSTEM

    FROM SYSTEM

    PIPE HANGERS(SPRING &NEOPRENE TYPE)

    ISOLATION VALVE

    WAFER STYLE SWING CHECK VALVE

    9" INDUSTRIAL THERMOMETERW/ 3/4" NPT COPPER WELL

    1/4" O.D. COPPER TUBINGW/COMP. FITTINGS

    SUCTION DIFFUSER WITH STRAINER

    FIELD FABRICATED SUPPORT LEG

    DRAIN: TERMINATE NEAR F.D.

    CONCRETE INERTIA VIBRATIONPUMP BASE W/ SPRING ISOLATORS

    6" THICK CONCRETE HOUSEKEEPING PAD W/ CHAMFEREDEDGES TO EXTEND 6" PAST ALLSIDES OF PUMP BASE.

    FINISH FLOOR

    GROUTABLE FABRICATEDSTEEL BASE PLATE

    BASE MOUNTED ENDSUCTION PUMP (LONGCOUPLED)

    OSHA/ANSI COUPLER GUARD

    MULTIPORT PRESSUREINDICATOR (4-PORT)

    ISOLATION VAVE(BUTTERFLY VALVE TYP.)

    DOUBLE SPHERE EPDM FLEXIBLEPIPE CONNECTOR (TYPICAL)

    TRANSITION TO LINE SIZE ASINDICATED ON PLANS DIRECTLY OFFCONNECTION TO PUMP (TYPICAL)

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    5/3

    1/2

    016 1

    1:1

    5:3

    9 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    KTD

    WDB

    HVAC DETAILS

    M-004

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    NOT TO SCALEM-004

    1 DRAIN PIT DETAILNOT TO SCALE

    M-004

    2 SUPPORT DETAIL

    NOT TO SCALEM-004

    10 ROOF PIPING SUPPORT DETAIL

    NOT TO SCALEM-004

    6 RETURN REGISTER INSTALLATION DETAIL

    NOT TO SCALEM-004

    11 ROOF RAIL DETAILNOT TO SCALE

    M-004

    8 AHU & VAV COIL PIPING DETAIL

    NOT TO SCALEM-004

    5 AIR SEPARATOR AND EXPANSION TANK PIPING DETAIL

    NOT TO SCALEM-004

    9 INERTIA BASE DETAIL

    NOT TO SCALEM-004

    3 ROOF MOUNTED DUCT SUPPORT/INSULATION DETAIL

    No. Description Date

    1 OSE COMMENTREVISIONS

    02/18/2016

    SCALE: NOT TO SCALEM-004

    7 ROOF EXHAUST FAN INSTALLATION DETAIL

    NOT TO SCALEM-004

    4 END SUCTION PUMP DETAIL

  • T

    T P

    P CHS

    CHR

    M

    TS

    VAV POINTS LISTAHU POINTS LIST

    LEGEND SEQUENCE OF OPERATION: VARIABLE AIR VOLUME (VAV)TERMINAL UNITS

    SEQUENCE OF OPERATION: AIR HANDLING UNIT

    VAV BOX WITH HOT WATER REHEAT COIL:

    A DEDICATED UNIT MOUNTED VAV CONTROLLER WILL CONTROL EACH UNIT.

    UNOCCUPIED MODE :

    NIGHT SET-BACK OPERATION:

    IN UNOCCUPIED MODE THE PRIMARY AIR DAMPER WILL REMAIN CLOSED. UPON A DROP IN SPACE

    TEMPERATURE BELOW NIGHT LOW LIMIT SETPOINT (ADJ.), THE VAV CONTROLLER WILL REQUEST AHU FAN

    OPERATION. UPON PROOF OF AHU OPERATION, VAV HEATING SHALL BE ENABLED AND VAV BOX PRIMARY AIR

    DAMPER SHALL MODULATE OPEN TO MAINTAIN HEATING CFM SETPOINT (ADJ.) AND HEATING SHALL BE

    ADJUSTED AS REQUIRED TO MAINTAIN THE SPACE NIGHT LOW LIMIT SETPOINT. ON A RISE IN SPACE

    TEMPERATURE, THE REVERSE WILL OCCUR

    AFTER HOURS OPERATION:

    EACH VAV ZONE MAY BE OVERRIDDEN INTO OCCUPIED MODE. DURING AFTER HOURS OPERATION, VAV BOX

    SHALL MAINTAIN OCCUPIED HEATING AND COOLING SETPOINTS.

    OCCUPIED MODE :

    IN OCCUPIED MODE, THE PRIMARY AIR DAMPER WILL BE ENABLED TO MODULATE TO MAINTAIN MINIMUM

    COOLING CFM SETPOINT (ADJ.). WHEN THE SPACE TEMPERATURE RISES ABOVE THE COOLING SETPOINT (ADJ.),

    THE PRIMARY AIR DAMPER WILL MODULATE OPEN TOWARDS MAXIMUM AIRFLOW SETPOINT (ADJ.). THE

    CONTROLLER WILL COMPARE THE COOLING SETPOINT WITH THE SPACE TEMPERATURE AND DETERMINE THE

    DESIRED AIRFLOW QUANTITY BETWEEN MAXIMUM AND MINIMUM AIRFLOW SETTINGS. ON A FALL IN SPACE

    TEMPERATURE, THE PRIMARY AIR DAMPER WILL MODULATE CLOSED TO MAINTAIN MINIMUM COOLING CFM

    SETPOINT. IF SPACE TEMPERATURE CONTINUES TO FALL BELOW SPACE HEATING SETPOINT (ADJ.), THE

    PRIMARY AIR DAMPER SHALL MODULATE TO MAINTAIN HEATING CFM SETPOINT (ADJ.) AND THE HOT WATER RE-HEAT

    COIL WILL BE INDEXED AS REQUIRED TO MAINTAIN HEATING SETPOINT. ON A RISE IN SPACE TEMPERATURE,

    THE REVERSE WILL OCCUR

    VAV AIR HANDLING UNIT

    PROVIDE UNIT WITH A MICROPROCESSOR BASED PROGRAMMABLE CONTROLLER CAPABLE OF

    STANDALONE OPERATION OR AS DIRECTED BY THE ENERGY MANAGEMENT SYSTEM (EMS). THE UNIT MOUNTED

    CONTROLLER SHALL MONITOR AND CONTROL THE UNIT. THE CONTROLLER SHALL HAVE A HUMAN INTERFACE

    PANEL CONSISTING OF 2-LINE LCD DISPLAY SCREEN AND A MULTI-BUTTON KEYPAD FOR MONITORING, SETTING,

    EDITING, AND CONTROLLING THE UNIT.

    SUPPLY FAN CONTROL (GENERAL) : THE SUPPLY FAN WILL BE CONTROLLED THROUGH A HAND-OFF-AUTO

    (H-O-A) SWITCH INTEGRAL WITH THE VARIABLE FREQUENCY DRIVE (VFD). WHEN THE SWITCH IS IN THE

    "AUTO" POSITION, THE SUPPLY FAN WILL BE STARTED AND STOPPED AND FAN SPEED WILL BE CONTROLLED

    THROUGH THE EMS. WHEN THE SWITCH IS IN THE "HAND" POSITION, THE SUPPLY FAN WILL RUN AND THE

    FAN SPEED WILL BE CONTROLLED THROUGH A MANUAL SPEED ADJUSTMENT INTEGRAL TO THE VFD. WHEN

    THE SWITCH IS IN THE "OFF" POSITION, THE SUPPLY FAN AND DRIVE WILL REMAIN OFF. WHEN THE STARTING

    CIRCUIT IS ACTIVATED BY THE EMS OR BY PLACING THE SELECTOR SWITCH IN "HAND" POSITION, THE VFD

    WILL START UNLOADED AND WILL RAMP UP TO SPEED AS PROGRAMMED INTO THE VFD'S SAFETY CIRCUIT.

    UNOCCUPIED MODE : IN UNOCCUPIED MODE, UNIT SUPPLY FANS WILL BE INDEXED OFF AND WILL

    REMAIN OFF UNTIL THE START OF AN OCCUPIED CYCLE OR A CALL FROM THE VAV ZONES FOR NIGHT SET-UP

    OR SET-BACK OPERATION. THE OUTSIDE AIR CONTROL DAMPER WILL REMAIN CLOSED TO OUTSIDE AIR DURING

    UNOCCUPIED, NIGHT SET-UP AND SET-BACK OPERATION. DURING NIGHT SET-BACK OPERATION THE

    DISCHARGE AIR TEMPERATURE SHALL BE SET AT 60 DEGREES F (ADJ.). ALL FURTHER SPACE HEATING SHALL

    BE ACCOMPLISHED LOCALLY WITH THE VAV BOX REHEAT. UPON A CALL FOR NIGHT SET-UP OPERATION,

    DISCHARGE AIR TEMPERATURE CONTROL SHALL BE AS DURING OCCUPIED MODE.

    AFTER HOURS OPERATION : UPON A CALL FOR AFTER HOURS OPERATION FROM VAV ZONES, AHU SHALL

    OPERATE IN THE OCCUPIED MODE FOR 4 HOURS.

    OCCUPIED MODE : IN OCCUPIED MODE, THE SUPPLY FAN WILL BE ENABLED TO RUN THROUGH THE VARIABLE

    FREQUENCY DRIVE (VFD); WILL RUN CONTINUOUSLY AND; THE OUTSIDE AIR CONTROL DAMPER WILL BE ENABLED.

    OUTSIDE AIR DAMPER CONTROL : OUTSIDE AIRFLOW SHALL BE MONITORED BY THE AIRFLOW

    MONITORING STATION. IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER WILL BE MODULATED TO MAINTAIN

    RETURN AIR CO2 SETPOINT AS SENSED BY THE DUCT MOUNTED CO2 MONITOR. WHEN THE CO2 SENSOR

    SENSES A CO2 CONCENTRATION OF 400 PPM, THE OUTDOOR AIR DAMPER SHALL BE AT THE MINIMUM

    POSITION. AS CO2 CONCENTRATION LEVELS RISE, THE DAMPER SHALL MODULATE OPEN. THE DAMPER SHALL

    BE AT THE FULL OPEN POSITION WHEN CO2 LEVELS EQUAL 1100 PPM. MINIMUM OUTSIDE AIR DAMPER

    POSITION SHALL BE ESTABLISHED DURING SYSTEM AIR BALANCE.

    DISCHARGE AIR TEMPERATURE CONTROL (RESET PROGRAM) : DISCHARGE AIR TEMPERATURE FROM THE UNIT WILL

    BE RESET IN ACCORDANCE WITH THE RESET SCHEDULE. THE CONTROLLER WILL MODULATE FLOW OF

    CHILLED WATER TO MAINTAIN THE TEMPERATURE OF THE AIR LEAVING THE COIL AT THE SETPOINT DETERMINED BY

    THE RESET SCHEDULE. DISCHARGE AIR TEMPERATURE SETPOINT WILL VARY BETWEEN A MINIMUM OF 50° F

    (ADJ.) AND A MAXIMUM OF 60° F (ADJ.). RESET OF DISCHARGE AIR SETPOINT SHALL BE BASED UPON

    COOLING DEMAND FROM VAV ZONES ASSOCIATED WITH EACH AHU.

    SUPPLY DUCT STATIC PRESSURE CONTROL : THE SUPPLY FAN VFD WILL BE MODULATED TO MAINTAIN THE

    SUPPLY DUCT STATIC PRESSURE SETPOINT AS SENSED BY DUCT STATIC PRESSURE SENSOR LOCATED

    DOWNSTREAM IN THE SUPPLY MAIN. UPON STARTUP, THE VFD WILL BE IN THE "UNLOADED" POSITION. THE

    VFD SPEED WILL BE ADJUSTED THROUGH A CONTROL LOOP IN RESPONSE TO THE DUCT STATIC PRESSURE

    SETPOINT. AS THE DUCT STATIC PRESSURE RISES ABOVE SETPOINT, THE FAN SPEED WILL BE REDUCED

    THROUGH THE VFD SPEED SIGNAL CONTROLLER DOWN TO THE PROGRAMMED MINIMUM SPEED (ADJ.). AS THE

    STATIC PRESSURE INCREASES ABOVE THE ACTIVE SETPOINT, THE FAN SPEED WILL BE INCREASED. DUCT

    STATIC PRESSURE SETPOINT SHALL RESET BETWEEN AN ADJUSTABLE MINIMUM AND MAXIMUM SETPOINT. RESET

    OF STATIC PRESSURE SETPOINT SHALL BE BASED UPON AIRFLOW DEMANDS FROM VAV ZONES. IF THE FAN

    SPEED IS AT 100 PERCENT AND THE SUPPLY DUCT STATIC PRESSURE IS STILL BELOW SETPOINT, THE

    DISCHARGE AIR TEMPERATURE RESET CONTROL LOOP WILL BE OVERRIDDEN TO DECREASE THE ACTIVE

    DISCHARGE AIR TEMPERATURE SETOINT UNTIL THE STATIC PRESSURE SETPOINT IS SATISFIED.

    MORNING WARM-UP CYCLE : IN THE MORNING WARM-UP CYCLE, THE AHU SUPPLY FAN SHALL START, THE

    OUTSIDE AIR DAMPERS WILL REMAIN CLOSED, AND UNIT COOLING SHALL BE DISABLED. ALL BUILDING HEATING

    WILL BE ACCOMPLISHED LOCALLLY AT THE REHEAT VAV TERMINAL UNITS. MORNING WARM-UP CYCLE SHALL

    BE INITIATATED FROM VAV ZONES AS REQUIRED. AN ADJUSTABLE MINIMUM NUMBER OF VAV ZONES SHALL

    REQUIRE MORNING WARM-UP BEFORE AHU SHALL BE STARTED.

    MORNING COOL-DOWN CYCLE : IN THE MORNING COOL-DOWN CYCLE, THE AHU SUPPLY FAN START, OUTSIDE

    AIR DAMPERS WILL REMAIN CLOSED, AND UNIT COOLING SHALL BE ENABLED. MORNING COOL-DOWN CYCLE

    SHALL BE INITIATATED FROM VAV ZONES AS REQUIRED. AN ADJUSTABLE MINIMUM NUMBER OF VAV ZONES

    SHALL REQUIRE MORNING COOL-DOWN BEFORE AHU SHALL BE STARTED. DISCHARGE AIR TEMPERATURE

    CONTROL SHALL BE AS IN OCCUPIED MODE.

    SENSORS : A DRY CONTACT FROM THE VFD CONTROLLER WILL PROVIDE FAN STATUS FOR UNIT SUPPLY FAN.

    AN ALARM WILL BE INITIATED WHENEVER THE FAN COMMAND AND STATUS DO NOT MATCH. A FAULT CONTACT

    WILL BE INPUT TO THE CONTROLLER TO INDICATE AN INTERNAL PROBLEM WITH THE SUPPLY FAN VFD. A

    DUCT TEMPERATURE SENSOR DOWNSTREAM OF THE COOLING COIL SECTION WILL MONITOR SUPPLY AIR

    TEMPERATURE FROM THE UNIT. A DUCT TEMPERATURE SENSOR IN THE MIXED AIR STREAM WILL MONITOR THE

    MIXED AIR CONDITION UPSTREAM OF THE COIL.

    SAFETIES: UPON A SIGNAL FROM THE DUCT-MOUTNED SMOKE DETECTOR, THE SUPPLY FAN WILL BE DE-ENERGIZED (HARDWIRED INTERLOCK), THE OUTSIDE AIR DAMPER WILL BE CLOSED, AN ALARM WILL BE DISPLAYEDAT THE OPERATOR'S WORKSTATION, AND THE FIRE ALARM SHALL BE ACTIVATED.

    RETURNAHU

    AIR

    CHILLEDWATER

    COOLINGCOIL

    MIXINGBOX

    M

    M

    FILTER

    VFD

    FANC

    EMCS

    OUTSIDE

    P

    M

    SUPPLYAHU

    EMCS

    SPACE

    T

    ENERGY MANAGEMENT CONTROL SYSTEM UNIT CONTROLLER

    MOTORIZED ACTUATOR

    EMCS

    M

    TEMPERATURE SENSOR

    CURRENT SWITCHC

    T

    T

    VAV

    BOX

    FLOW RING SENSOR(BY VAV BOX MANUFACTURER)

    VARIABLE FREQUENCY DRIVEVFD

    HOT WATERREHEAT COIL

    CO2 SENSORO

    T

    LOCATE 2/3OF THE WAYDOWN THELENGTH OFDUCT.

    O

    FIRE ALARMPANEL

    PRESSURE SENSORP

    T

    STATIONAIR MONITORING

    AI-1 AIR FLOW SENSOR

    AI-2 SPACE TEMP SENSOR

    AI-3 DAMPER POSITION

    AI-4 SPACE CO2 SENSOR (SEE DRAWINGS FOR LOCATIONS)

    AI-5 MINIMUM CFM

    AI-6 MAXIMUM CFM

    AO-1 DAMPER CONTROL

    DO-1 ELECTRIC HEAT (AHU-2)

    DI-1 AHU FAN STATUS (CURRENT)

    AI-2 DISCHARGE AIR TEMP

    AI-3 DUCT STATIC PRESSURE

    DI-2 FIRE ALARM PANEL CONTACT

    AI-1 MIXED AIR TEMP

    AO-5 VARIABLE FREQUENCY DRIVE

    DO-1 START/STOP AHU

    AO-1 DISCHARGE STATIC PRESSURE SETPOINT

    AO-2 SUPPLY AIR TEMP SETPOINT

    AO-3 OA MOTORIZED DAMPER

    AO-4 RA MOTORIZED DAMPER

    AI-4 OUTDOOR AIR FLOWRATE (CFM)

    HWS

    HWR

    M

    HOTWATER

    PRE-HEATCOIL

    M

    ECONOMIZER: THE CONTROLLER SHALL MEASURE THE RETURN AND OUTDOOR AIR DRY BULB TEMPERATUREREADINGS, AND SHALL MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT THATHAS LOWER OR EQUAL TEMPERATURE THAN THE SUPPLY AIR SETPOINT. THE OUTSIDE AIR DAMPERS SHALLMAINTAIN A MINIMUM POSITION AS INDICATED ON THE EQUIPMENT SCHEDULE.

    THE ECONOMIZER SHALL BE ENABLED WHENEVER ALL OF THE FOLLOWING CONDITIONS HAVE BEEN MET:OUTSIDE AIR TEMPERATURE IN LESS THAN 55°F, OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIRTEMPERATURE, AND THE SUPPLY FAN STATUS IS ON.

    THE OUTSIDE AIR INTAKE DAMPER SHALL CLOSE WHENEVER ANY OF THE FOLLOWING OCCURS: THEFREEZESTAT IS ON, OR THE SUPPLY FAN STATUS IS OFF. THE OUTSIDE AND EXHAUST AIR DAMPERS SHALLCLOSE, AND THE RETURN AIR DAMPER SHALL OPEN WHEN THE UNIT IS OFF.

    BAROMETRIC DAMPER SHALL BE SET DURING TEST AND BALANCING TO OPEN WHEN BUILDING BECOMESPRESSURIZED DURING ECONOMIZER MODE.

    FREEZE STATF

    F

    FREEZESTAT

    T

    AMBIENT

    HOT WATER RE-HEAT COILSHALL BE DISCONECTED,REMOVED, AND SEALED

    FAN MOTOR SHALL BEREPLACED WITH INVERTERDUTY, ALLOWING VARIABLESPEED OPERATION. VERIFYSIZE AND HP TO BEINSTALLED IN EXISTINGCABINET

    EXISTING AIR HANDLER

    RELIEFAHU

    DUCT MOUNTED SMOKE DETECTORS

    BAROMETRIC DAMPER

    S

    FIRE ALARMPANEL

    ADDITIONAL POINTS MONITORED BY THE BMS:• WATER HEATER WH-1, ALARM AND MONITORING• CIRCULATING PUMP HWC-1, CONTROL AND MONITORING• ELEVATOR SUMP PUMP SP-1, ALARM AND MONITORING

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    5/3

    1/2

    016 1

    1:1

    5:4

    0 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    WDB

    MAU

    HVACCONTROLSDIAGRAMS

    M-005

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    NOT TO SCALEM-005

    1 AHU SCHEMATIC DIAGRAM AND SEQUENCE OF OPERATION

    No. Description Date

    1 OSE COMMENTREVISIONS

    02/18/2016

  • 3/4

    "-D

    RN

    4"-

    HW

    S

    M

    M

    VFD---

    VFD---

    M

    0-100

    AFV

    0-100

    HDSS

    HDSS

    INSIDEOUTSIDE

    BY MCBY PC

    SEE PLUMBING PLANS1"-DCW

    B&G

    MODEL 7

    (SET @ 45

    PSIG)

    1"-NC BYPASS

    0-100HIGH

    CAPACITY

    AIR VENT

    0-100

    LOW CAPACITY

    AIR VENT

    HDSS

    B&G

    MODEL 1170-75

    (SET @ 75 PSIG)

    FLEX-HOSE CO.

    MODEL NNS

    (TYP THIS DWG)

    3/4"-DRN

    SS FD

    3"-

    HW

    S

    HWP-1

    HOT WATER PUMP

    (OPERATING)

    0-100

    CMI

    PSD

    3"-

    HW

    S

    SS

    PIPE ALL PSD DRAINS TO

    FLOOR DRAIN LOCATED AT

    EACH PUMP (TYPICAL)

    FD

    3"-

    HW

    S

    HWP-2

    HOT WATER PUMP

    (STANDBY)

    0-100

    CMI

    PSD

    3"-

    HW

    S

    SS FD

    3/4

    "-C

    HF

    HOT WATER

    SHOT FEEDER

    (5 GALLONS)

    HSF-1

    8" COMBUSTION

    AIR INTAKE (TYP)

    8" FLUE

    GAS

    EXHAUST

    0-100

    0-100

    1-1

    /2"-

    DR

    N

    1-1

    /2"-

    DR

    N

    BY BOILER

    MANUFACTURER.

    AFV

    12"

    (MAX)

    3/4

    "-D

    RN

    EXPANSION TANK

    3"-HWS

    2"-GAS

    (PROVIDE MIN. 10' LENGTH

    BETWEEN PRV & BOILER-TYP)

    3"-HWR

    2"-

    HW

    R

    2"-

    HW

    S

    3"-HWR

    BOILER

    CIRCULATING

    PUMP BP-2

    BOILER

    CONTROL

    PANEL

    BCP-2

    3"-HWS

    BOILER

    (LAG)

    B-2

    BOILER

    CIRCULATING

    PUMP BP-1

    NORTH WALL INSIDEOUTSIDE

    8" FLUE

    GAS

    EXHAUST

    SLEEVE &

    LINK SEAL

    8" COMBUSTION

    AIR INTAKE (TYP)

    3/4

    "-D

    RN

    EARTHQUAKE VALVE

    BY BOILERMANUFACTURER

    BY BOILERMFR. PROVIDEBACNET I/FACETO BMS

    TO LOCAL DDC PANEL

    OUTSIDE ABV GRADE

    OA TEMPRESET

    BOILER EMERGENCY

    SHUTDOWN SWITCHBOILER

    CONTROL

    PANEL

    BCP-1

    1"-

    DR

    N

    1-1

    /2"-

    DR

    N

    1-1

    /2"-

    DR

    N2"-GAS

    2"-

    HW

    R

    2"-

    HW

    S

    BOILER

    (LEAD)

    B-1

    3"-HWS

    3/4"-CHF

    3"-HWS

    INSIDE

    OUTSIDE BELOW

    GRADE

    OUTSIDE

    IN-LINE AIR

    SEPARATOR

    NATURAL GAS DISTRIBUTION

    GAS PIPING, SEE PLUMBING

    D

    FSTI

    TI

    PI

    PITIPI

    FSTIPI

    PRV

    PRV

    ES

    TT

    RV

    PRV

    RV

    PI PI

    PIPRV

    PI

    AAVAAV

    RVTE

    TT

    TERMINAL UNIT HOTWATER COIL TYPICAL THISDRAWING

    PIPE ALL INDICATED DRAINSTO HUB DRAIN (SEE PLANS)

    CONTROLS CONTRACTOR SHALLPROVIDE DIFFERENTIAL PRESSURETRANSMITTER IN SYSTEM DISTRIBUTIONPIPING APPROX. 2/3 DISTANCE OF THELONGEST PIPE RUN.

    AH

    U P

    RE

    -HE

    AT

    CO

    IL

    GENERAL NOTES:1. THE WORK FOR THE HVAC CONTROLS SYSTEM WILL BEPERFORMED BY SIEMENS BUILDING TECHNOLOGIES UNDER DIRECTCONTRACT WITH COASTAL CAROLINA UNIVERSITY.

    2. SEE SPECIFICATION SECTION 23 09 23 FOR DELINEATION OF WORK.

    3. PROVIDE INSULATION AND JACKETING ON ALL EQUIPMENT.

    BYPASS WITH PRESSURERELIEF VALVE SET TO 35% OFMAXIMUM PUMP FLOW (ADJ.).

    M

    VA

    V R

    E-H

    EA

    T C

    OIL

    MM

    1"-

    CW

    S

    3/4

    "-D

    RN

    1"-DCW

    1"-NC BYPASS

    4"-

    CH

    WS

    4"-

    CH

    WS

    1"-

    DR

    N

    CWP-1

    CHILLED

    WATER PUMP

    (OPERATING)SS

    PSD

    FD

    3/4

    "-D

    RN

    0-100

    FLEX-HOSE CO.

    MODEL NNS

    (TYP THIS DWG)

    B&G

    MODEL 7

    (SET @ 45

    PSIG)

    B&G

    MODEL 1170-75

    (SET @ 75 PSIG)

    HIGH

    CAPACITY

    AIR VENT

    SEE PLUMBING PLANS

    HDPIPE ALL PSD

    DRAINS TO

    FLOOR DRAIN

    LOCATED AT

    EACH PUMP

    TYP.

    SS

    M M

    LOW CAPACITY

    AIR VENT

    EXPANSION TANK0-100

    3/4

    "-D

    RN

    4"CHWR

    4"CHWS4"CHWS

    4"CHWS

    BY PC BY MC

    CWP-2

    CHILLED

    WATER PUMP

    (STANDBY)

    4"-

    CH

    WS

    4"-

    CH

    WS

    PSD

    FD

    CMI

    VFD---

    SS

    CMI

    VFD---

    0-100

    0-100

    3/4"-DRN

    D

    RV

    TT TTFE

    BTU METER

    T3

    1/2" CIRCUIT SETTER BYPASS TO ALLOWMINIMUM FLOW AT ALL TIMES TO ALLOWT3 TEMPERATURE READING

    NORMALLY CLOSED BYPASS

    DP

    40ºF 56ºF

    CHWSFROMCAMPUSCEP

    CHWRBACK TOCAMPUSCEP

    T IN=42ºF

    T OUT=54ºF

    OUTSIDE INSIDE

    FULL SIZE BYPASS

    CONTROLS TOLOCAL DDCCONTROLLER

    DDC

    BUILDING LOOP DP TOCAMPUS CEP FOR MAINDISTRIBUTION UFDCONTROL

    PRV PI

    AAV

    PI

    AAV

    PI PI

    TO LOCAL DDC CONTROL PANEL

    PIPE ALL INDICATED DRAINSTO HUB DRAIN (SEE PLANS)

    CONTROL VALVE

    TO LOCAL DDC PANEL

    TYP.

    CH

    ILLE

    D W

    AT

    ER

    CO

    IL

    AH

    U-3

    CH

    ILLE

    D

    WA

    TE

    R C

    OIL

    INLINE AIRSEPARATOR

    M

    BYPASS WITH PRESSURERELIEF VALVE SET TO 35% OFMAXIMUM PUMP FLOW (ADJ.).

    CONTROLS CONTRACTOR SHALLPROVIDE DIFFERENTIAL PRESSURETRANSMITTER IN SYSTEM DISTRIBUTIONPIPING APPROX. 2/3 DISTANCE OF THELONGEST PIPE RUN.

    CHILLED WATER AND HEATING HOT WATER SEQUENCE OF OPERATIONS:

    CHILLED WATER:

    THE CHILLED WATER SYSTEM PUMPS SHALL BE ENERGIZED THROUGH THE DDC CONTROLLER VIAOCCUPIED/UNOCCUPIED MODE THROUGH THE BUILDING ECMS. THE CHILLED WATER PUMPS AREREDUNDANT AND SHOULD NOT OPERATE AT THE SAME TIME. THE ECMS SHALL SCHEDULE/ROTATE THEPRIMARY PUMP AND STAND-BY PUMP ON A MONTHLY BASIS TO EQUALIZE RUN TIME HOURS.

    THE CHILLED WATER PUMP SPEED SHALL BE CONTROLLED THROUGH THE VFD BASED ON THEDIFFERENTIAL PRESSURE SENSOR LOCATED IN THE CHILLED WATER DISTRIBUTION SYSTEM.

    IN THE EVENT OF THE PRIMARY CHILLED WATER PUMP FAILURE THE ECMS SHALL ENERGIZE THE STAND-BYCHILLED WATER PUMP AND GENERATE AN ALARM AT THE OPERATOR'S WORKSTATION. THE CHILLEDWATER PUMPS SHALL PROVIDE PROOF OF OPERATION AT THE OPERATOR'S WORKSTATION THROUGH THEUSE OF A CURRENT SWITCH.

    HOT WATER:

    THE HOT WATER SYSTEM PUMPS AND BOILERS SHALL BE ENERGIZED TO PROVIDE HEATING TO SUPPLYAIR TERMINAL UNITS (VAVS) REHEAT COILS, FAN-COIL UNIT HEATING COILS, UNIT HEATER HEATING COILSAND AIR HANDLING UNIT PREHEAT COILS.

    THE ECMS SYSTEM SHALL INTERFACE TO THE BOILER SYSTEM CONTROL UTILZING BACNET. THE ECMSSHALL ENABLE THE BOILER SYSTEM CONTROLLER. THE BOILER SYSTEM CONTROLLER SHALL CONTROLRESPECTIVE BOILER CIRCULATION PUMPS AND ALSO SHALL PROVIDE STAGING OF THE HEATING BASED ONBUILDING HOT WATER SUPPLY TEMPERATURE. A CONTROL VALVE LOCATED ON THE RETURN LINE OFEACH BOILER SHALL BE INTERLINKED WITH THE BOILER STAGING TO ISOLATE THE BOILER NOT INOPERATION (LAG BOILER). OUTDOOR TEMPERATURE RESET SCHEDULE SHALL BE CONTROLLED THROUGHTHE ECMS. THE ECMS SHALL MONITOR THE SYSTEM BOILER ALARMS AND RELAY/GENERATE ANY AND ALLSYSTEM ALARMS AT THE OPERATOR'S WORKSTATION.

    THE SECONDARY BUILDING HOT WATER PUMPS SHALL BE CONTROLLED THROUGH THE ECMS. THE ECMSSHALL ROTATE THE PRIMARY AND STAND-BY HOT WATER PUMPS ON A MONTHLY BASIS TO EQUALIZE RUN-TIME HOURS. IN THE EVENT OF THE PRIMARY HOT WATER PUMP FAILURE THE ECMS SHALL ENERGIZE THESTAND-BY HOT WATER PUMP AND GENERATE AN ALARM AT THE OPERATOR'S WORKSTATION. THE HOTWATER PUMPS SHALL PROVIDE PROOF OF OPERATION AT THE OPERATOR'S WORKSTATION THROUGH THEUSE OF A CURRENT SWITCH.

    THE HOT WATER PUMP SPEED SHALL BE CONTROLLED THROUGH THE VFD BASED ON THE DIFFERENTIALPRESSURE SENSOR LOCATED IN THE CHILLED WATER DISTRIBUTION SYSTEM.

    A BOILER EMERGENCY SHUTDOWN SWITCH SHALL BE LOCATED AT EACH ENTRANCE TO THE MECHANICALSPACE ROOM.

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    5/3

    1/2

    016 1

    1:1

    5:4

    1 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    WDB

    MAU

    HVACCONTROLSDIAGRAMS

    M-006

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    NOT TO SCALEM-006

    1 HEATING HOT WATER SYSTEM FLOW DIAGRAM

    NOT TO SCALEM-006

    2 CHILLED WATER SYSTEM FLOW DIAGRAM

    No. Description Date

  • 1

    (E) AH-1

    (E) AH-2

    (E) AH-4

    1

    1

    2

    3

    4

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    0

    N

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    8 16 24 32

    SCALE: 1/8" = 1'-0"5/31/2

    016 1

    1:1

    5:4

    2 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    KTD

    WDB

    ROOF HVACDEMO PLAN

    M-031

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    SCALE: 1/8" = 1'-0"M-031

    1 ROOF HVAC DEMO PLAN

    1

    DEMOLITION KEYED NOTES

    EXISTING AIR HANDLING UNITS AH-1, AH-2 AND AH-4 SHALL REMAIN. ALL ASSOCIATEDDUCT AND ACCESSORIES SHALL BE DEMOLISHED.

    EXISTING EXHAUST FAN TO BE DEMOLISHED. (TYP.)

    EXISTING ROOFTOP HVAC EQUIPMENT TO BE DEMOLISHED. (TYP.)

    EXISTING DUCTWORK TO BE DEMOLISHED. (TYP.)

    GENERAL DEMOLITION NOTES

    1. UNLESS NOTED OTHERWISE, ALL EXISTING ROOFTOP EQUIPMENT, INCLUDINGMAKE-UP AIR UNITS, EXHAUST FANS, AIR-HANDLING UNITS, AND CONDENSINGUNITS, AND ALL ASSOCIATED DUCTWORK, CURBS AND ACCESSORIES SHALL BEDEMOLISHED. ALL EXISTING OPENINGS NOT BEING REUSED SHALL BE REPAIRED TOMATCH EXISTING ROOF.

    2. WHILE ONLY THE ROOF PLAN IS INDICATED ABOVE, EXCEPT NOTED OTHERWISE,ALL MECHANICAL COMPONENTS ON THE FIRST AND SECOND FLOOR PLANS SHALLBE REMOVED. REFERENCE EXISTING ARCHITECTURAL FLOOR PLANS.

    3. WHERE ROOFTOP EQUIPMENT IS BEING DEMOLISHED, CONTRACTOR SHALLPROVIDE MOISTURE-TIGHT SEALS ON CURBS AND ANY OTHER ROOFPENETRATIONS.

    4. (2) FIRST FLOOR CHILLED WATER PUMPS AND ASSOCIATED VIBRATION ISOLATIONBASES SHALL BE SALVAGED AND TURNED OVER TO THE OWNER.

    2

    3

    4

    NOT TO SCALEM-031

    2 EXISTING ROOF EQUIPMENT - 1

    NOT TO SCALEM-031

    3 EXISTING ROOF EQUIPMENT - 2

    NOT TO SCALEM-031

    4 EXISTING ROOF EQUIPMENT - 3

    No. Description Date

  • DN

    DN

    DN

    DN

    UP

    DN

    DN

    GENERALCLASSROOM 1

    102

    GENERALCLASSROOM 2

    104

    PHYS. LAB &CREATE STORAGE

    120

    MECH. PUMP ROOM

    126

    PHYSICSENGINEERING

    DESIGN RESEARCHLAB

    124

    PHYSICS FTFACULTY OFFICE 1

    123D

    PHYSICS FTFACULTY OFFICE 2

    123E

    PHYSICS FTFACULTY OFFICE 3

    123F

    PHYSICS FTFACULTY OFFICE 4

    123A

    PHYSICS FTFACULTY OFFICE 5

    123B

    PHYSICS FTFACULTY OFFICE 6

    123C

    PHYSICSTUTORING

    CENTER/OFFICESUITE

    123

    PHYS. SCALE UP 1

    122

    PHYS. SCALE UP 2

    117

    PHYS. TEACH PREP

    116

    PHYS. SCALE UP 3

    112

    PHYS.ELECTRONICS/

    HARDWARE LAB

    113

    PHYS. MACHINESHOP

    109

    PHYS COMP.RESEARCH

    111

    PHYSICS FTFACULTY OFFICE 7

    121C

    PHYSICS FTFACULTY OFFICE

    10

    114D

    PHYSICS FTFACULTY OFFICE 8

    121B

    PHYSICS FTFACULTY OFFICE

    11

    114C

    SHARED CONF.

    108

    PHYSICS OFFICESUITE

    114

    PHYSICS FTFACULTY OFFICE 9

    121A

    PHYSICS FTFACULTY OFFICE

    13

    114A

    SHARED ADJUCTOFFICES

    110

    MEN'S TLT

    105

    SHARED MEETINGROOM

    107

    JAN.

    103

    UNISEX ADA TLT

    106

    UNISEX ADA TLT

    118

    WOMEN'S TLT

    119

    DATA

    115

    STAIR 1A

    ST1A

    STAIR 1B

    ST1B

    NORTH ENTRY

    100

    SOUTH ENTRY

    102C

    CORR.

    101C.A

    PHYS. ADV LAB /MAT. RESEARCH

    125

    PHYSICS OFFICESUITE

    121

    PHYSICS FTFACULTY OFFICE

    12

    114B

    VENDING

    127

    ELEC.

    101

    MENS TLTVESTIBULE

    105.A

    PHYSICSMAIL/COPY/FILE

    STORAGE

    128

    ELEVATOR

    100E

    36"x18"

    24"x14" 24"x14"

    12"x

    12"

    16"x

    12"

    18"x

    12"

    1

    1

    1

    1

    1

    1

    1 12"x8"

    18"x10"

    22"x12"

    16"x10"12"x8"

    1

    20"x14"

    20"x10" 10"x10"

    1

    1

    16"x10"

    118"x10"16"x10"

    1

    1

    16"x8" 10"x8"

    3

    175

    PD208

    75

    PD206

    165

    PD208

    175

    PD208

    145

    PD208

    85

    PD206

    145

    PD208

    125

    PD208

    380

    PD210

    140

    PD208

    90

    PD206

    85

    PD206

    405

    PD212

    405

    PD212

    425

    PD212

    425

    PD212

    425

    PD212

    425

    PD212

    425

    PD212

    425

    PD212

    400

    PD212

    400

    PD212

    400

    PD212

    400

    PD212

    75

    PD206

    75

    PD206

    325

    PD210

    180

    PD208

    160

    PD208

    160

    PD208

    140

    PD208

    120

    PD208

    105

    PD206

    130

    PD208

    35

    PD106

    465

    PD212

    465

    PD212

    430

    PD212

    445

    PD212

    440

    PD212

    75

    PD206

    325

    PD210

    325

    PD210

    135

    SWS2

    135

    SWS2

    4

    290

    SWS1

    125

    PD208ELEV. MACHINE

    ROOM

    101.A

    B-2

    B-1

    HWP-1

    HWP-2

    CWP-1

    CWP-2

    250

    LF222

    75

    LF222

    50

    LF222

    200

    LF222

    50

    LF111

    FCU-1

    FCU-2

    FCU-3

    VAV-124

    VAV-123C

    VAV-123B

    VAV-123A

    VAV-121

    VAV-120

    VAV-126

    VAV-100

    VAV-105

    VA

    V-1

    07

    VAV-108

    VAV-109

    VAV-110

    VAV-111VAV-104

    VAV-102VAV-125

    VAV-122 VAV-117

    VAV-112

    VAV-113

    VAV-114B

    VAV-114A

    VAV-119VAV-102C

    100

    PD206

    WATER HEATER MANUFACTURER'SCONCENTRIC VENT KIT. INSTALL AT 13'-4" AFG.

    WH-1

    4" WH FLUE ANDAIR INTAKE

    85

    LF222

    145

    LF222

    125

    LF222

    380

    LF222

    85

    LF222

    90

    LF222

    140

    LF222

    810

    LF222

    650

    LF222

    75

    LF222

    440

    LF222

    875

    LF222

    820

    LF222

    75

    LF222

    820

    LF222820

    LF222

    100

    LF222

    775

    LF222

    775

    LF222

    180

    LF222

    160

    LF222

    160

    LF222

    140

    LF222

    225

    LF222

    175

    LF222

    75

    LF222

    165

    LF222

    175

    LF222

    145

    LF222

    5

    400

    LF222

    485

    LF222

    FUME HOODS

    10"ø

    6"ø

    12"ø

    14"ø

    8"ø

    12"ø

    24"x

    12"

    14"ø

    12"ø

    10"ø

    10"ø10"ø

    10"ø

    24"x

    12"

    14"ø

    8"ø

    16"x

    12"

    14"ø

    12"x

    12"

    14"ø

    14"ø 14"ø

    14"ø

    20"x14" 20"x20"16"x12"

    14"ø

    14"ø

    14"ø

    16"ø

    12"ø

    325

    LF222

    8"ø

    135

    SWS2

    135

    SWS2

    100

    SDS50

    100

    SDS50

    100

    SDS50

    100

    SDS50

    100

    SDS50

    100

    SDS50

    100

    SDS50

    100

    SDS50

    BP-1

    BP-2

    6

    50"x14"

    1

    50"x14"

    1

    10"ø

    12"ø

    8"ø

    10"ø

    10"ø

    10"ø

    12"ø

    10"ø

    50"x20"

    8"ø

    10"ø

    110

    SDS50

    165

    SDS75

    160

    SDS75

    165

    SDR75

    160

    SDR75

    7

    8"ø

    10"ø10"ø

    12"ø

    8"ø

    T

    T

    T

    T

    T

    T

    T

    T T T

    T

    T

    T

    T

    T

    T

    T

    TTTT

    T T

    T

    T

    T

    395

    PD212

    T

    VAV-101C

    425

    PD212 12"ø

    FD

    DDC

    ET-1

    ET-2

    50"x14"

    50"x14"

    1

    1

    20"x12"

    1

    20"x12"

    6"ø(TYP)

    6"ø(TYP)

    2

    COMM.

    115A

    FD

    FD

    FD

    20"x50"

    12"x12"

    100

    LF222

    18"x

    12"

    12"ø

    8

    1. CONTRACTOR SHALL COORDINATE WITH THE OWNER TO PROVIDE A METHODOF MARKING THE CEILING GRID TO INDICATE THE LOCATION OF THE VAV BOX.AN EXAMPLE WOULD BE A SMALL BLUE DOT ON THE CEILING GRID.

    2. ALL COMPONENTS INSTALLED ABOVE THE CEILING SHALL BE PLENUM RATED.3. ALL RETURN GRILLES AND TRANSFER BOOTS SHALL BE PROVIDED WITH

    MANUAL DAMPERS FOR BALANCING.

    AM

    ILI

    LW

    BAD E N

    I

    A

    II

    R

    L L

    DG

    No.

    TU

    D

    SIS

    RE

    TE

    AA

    30241RE

    GE

    ER

    INEN

    L

    RCAHOR

    P

    SEF

    OLN

    S IOIN

    OCERTI FICAT

    EO F A U

    T H

    ORI ZATION

    S

    OUTH

    CAROLINA

    CONSULTING

    ENGINEERS

    DWG, INC.

    No.C03649

    0

    N

    CHECKED BY:

    DRAWN BY:

    DATE:

    PROJECT:

    REVISIONS:

    MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

    1

    A

    2 3 4 5 6

    B

    C

    D

    E

    COPYRIGHT 2015 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

    WWW.LS3P.COM

    TEL. 843.577.4444 FAX 843.722.4789

    205 1/2 KING ST. CHARLESTON SC 29401

    H17-9548-PD

    8 16 24 32

    SCALE: 1/8" = 1'-0"5/31/2

    016 1

    1:1

    5:4

    7 A

    M

    C:\

    Users

    \mg

    allag

    her\

    Do

    cu

    men

    ts\M

    EP

    _C

    CU

    Sm

    ith

    Scie

    nce B

    uild

    ing

    _2015_M

    GA

    LL

    AG

    HE

    R@

    DW

    GIN

    C.C

    OM

    .rvt

    11257

    05/31/16

    KTD

    WDB

    FIRST FLOORHVACDUCTWORKPLAN

    M-101

    SCIENCE BUILDINGRENOVATION

    BID CONSTRUCTION DOCUMENTS

    SCALE: 1/8" = 1'-0"M-101

    1 FIRST FLOOR HVAC DUCTWORK PLAN

    KEYED NOTES

    1 PROVIDE TRANSFER OPENING IN WALL ABOVE CEILING ACCORDING TO SIZESHOWN ON DRAWINGS. PROVIDE A SHORT DUCT INTO SPACE WITH 90° FITTING TOLIMIT NOISE.

    CONDENSATE ROUTED THROUGH NEUTRALIZER KIT TO FLOOR DRAIN.

    AIR FLOW MONITORS ON LAB HOOD EXHAUST SHALL BE PROVIDED ANDINSTALLED BY CMI. FIRE CAULK SHALL BE PROVIDED WHERE LAB EXHAUST DUCTPENETRATES UP INTO CHASE.

    DUCT IN MACHINE ROOM SHALL BE EXPOSED DOUBLE WALL. COORDINATE WITHARCHITECTURAL DRAWINGS FOR DUCT PAINTING COLOR.

    INSTALL CONDENSING BOILER FLUE AND AIR INTAKE PER MANUFACTURER'SINSTALLATION INSTRUCTION AND RECOMMENDATIONS.

    PROVIDE 20"x36" TRANSFER DUCT THROUGH SECOND FLOOR FOR TRANSFER OFRETURN AIR WITH FIRE DAMPERS.

    DUCT IN SOUTH ENTRY AREA WILL BE PARTIALLY EXPOSED ABOVE FLOATINGCEILING. CONTRACTOR SHALL PAINT DUCT IN THIS AREA TO MATCHCEILING/STRUCTURE COLOR ABOVE.

    PROVIDE BACKDRAFT DAMPER THAT ONLY ALLOWS AIR INTO THE LAB.

    2

    3

    4

    5

    6

    7

    GENERAL NOTES

    No. Description Date

    1 OSE COMMENTREVISIONS

    02/18/2016

    3 OSE COMMENTS 04/15/2016

    GENERAL NOTES

    8

  • UP

    DN

    MATH CLASSROOM

    206

    WOMEN'S TLT

    214

    MATH RESEARCHLAB

    208

    MATH STUDENT

    207

    LECTURE OFFICE 1

    207B

    PSYCH. FTFACULTY OFFICE

    10

    217A

    MEN'S TLT

    204

    TENURE OFFICE 7

    205BLECTURE OFFICE 5

    218N

    PSYCH. OFFICESUITE

    210

    PSYCH. CHAIRSOFFICE

    210B

    PSYCH. FTFACULTY OFFICE 3

    217K

    UNISEX ADA TLT

    213

    STAIR 2A

    ST2A

    STAIR 2B

    ST2B

    ADMIN OFFICE

    218Q

    ELEC.

    203JAN.

    201

    MATH CHAIR

    218P

    LAB MONITOR

    216H

    WAITING

    211

    VIDEO GAMING

    216G

    INTERVIEW ROOM

    211A

    OBSERVATIONROOM

    211B

    OBSERV. VIEWING

    216I

    VIDEO PRESENT/CONF.

    216F

    OBSERVATIONROOM

    216E

    PHYSIOLOGICALROOM

    216C

    TESTING

    216B

    TESTING

    216A

    PSYCH. FTFACULTY OFFICE 9

    217B

    STOR.

    216D

    DATA

    212

    PSYCHOLOGYSUITE

    216

    GENERALCLASSROOM 3

    219

    TENURE OFFICE 5

    207F

    TENURE OFFICE 4

    207E

    LECTURE OFFICE 2

    207G

    TENURE OFFICE 2

    207C

    TENURE OFFICE 1

    207A

    TENURE OFFICE 6

    207H

    LECTURE OFFICE 4

    205A

    TENURE OFFICE 8

    218O

    LECTURE OFFICE 3

    205C

    PSYCH. FTFACULTY OFFICE

    12

    210D

    PSYCH. FTFACULTY OFFICE

    13

    210C

    PSYCH. FTFACULTY OFFICE

    14

    217F

    PSYCH. FTFACULTY OFFICE

    11

    210E

    PSYCH. FTFACULTY OFFICE

    15

    217H

    TENURE OFFICE 9

    218J

    TENURE OFFICE 12

    218E

    TENURE OFFICE 13

    218C

    PSYCH. FTFACULTY OFFICE 1

    217I

    MATH STUDENTSUITE

    218

    PSYCH. FTFACULTY OFFICE 8

    217D

    PSYCH. FTFACULTY OFFICE 6

    217E

    PSYCH. FTFACULTY OFFICE 7

    217C

    TENURE OFFICE 3

    207D

    PSYCH. MAIL/COPY/STOR. ROOM

    215

    LECTURE OFFICE 6

    218M

    LECTURE OFFICE 7

    218L

    PSYCH. FTFACULTY OFFICE 2

    217J

    PSYCH. FTFACULTY OFFICE 4

    217L

    PSYCH. FTFACULTY OFFICE 5

    217M

    TENURE OFFICE 11

    218F

    LECTURE OFFICE 8

    218I

    LECTURE OFFICE 9

    218G

    LECTURE OFFICE10

    218D

    TENURE OFFICE 14

    218B

    TENURE OFFICE 15

    218A

    TENURE OFFICE 10

    218H

    MATH OFFICESUITE

    218C

    ADMIN OFF

    210A

    MATH MAIL/COPYROOM

    202

    CORR.

    201C.A

    SECURE STOR.

    218K

    PSYCH. OFFICESUITE

    217C

    OFFICES

    205

    STORAGE

    211B.1 STORAGE

    211A.1

    PSYCH. FTFACULTY OFFICE

    16

    217G

    PSYCH. STUDENTRECORDS

    215A

    12"x

    1