OVERVIEW Healthcare Associated Infections (HAIs), or Nosocomial infections, are one of the leading causes of death in the United States of America more than Breast Cancer, AIDS, and Auto Accidents combined. According to the American CDC (Centers for Disease Control and Prevention),one of every 25 patients contracts an infection in the hospital causing more than 75,000 deaths each year in the US. 205 Americans die from Hospital-Acquired Infections each day. HAI cost almost $10 billion annually in the US. Airborne transmission is one of the environmental routes of Nosocomial infections in hospitals such as Inuenza, SARS, Measles, Tuberculosis. Hospital occupants (patients, Hospital staff, visitors) and their activities are responsible for most of the contaminants in the conditioned space and some microorganisms are transmitted directly from person to person in the form of droplets in the air. When droplets are produced during a cough or sneeze, a cloud of infectious particles is released into the air, resulting in potential exposure of susceptible persons within three feet of the source person. The coarsest particles (larger than 2.5 micrometers) fall fast enough, their residence time in the air is of the order of 1 day, while the nest can stay up to 1 week in suspension and travel thousands of kilometers. Once deposited, the particles can then be re suspended by the wind or by indoor air ow. OBJECTIVE Monitor 24/7 Indoor air quality (particles, VOCs, CO2, RH, Temperature) from any computer or smartphone or from central building control system to detect risk of contagious airborne diseases and environment pollution risk (viruses, bacteria, spores, VOCs). For particles : Principle of detection The P4000 uses laser diffraction technology (Light Scattering) m a e b r e s a l a n e h w : g n i w o l l o f e h t s i e l p i c n i r p e h T passes through pure air, the beam is invisible. When the beam is visible, this is because the beam is diffracted onto particles along its path. If you look at beam from the side, the more the beam is visible, the more the particle density. This particle probe uses a sensor with a near-infrared source (laser diode). The sensor is an avalanche photodiode with amplier. Infrared is used to avoid TECHNOLOGY OPERATION The device must be placed in the area of occupancy of the premise served by outlet vents AMD mounted on a wall at eyes level (breathing human level, between 1.5 and 1.8m). INDOOR AIR QUALITY CONTROL BENEFITS AREAS Hospitals Clinics & Medical centers Dental clinics and dental surgery Laboratories Pharmaceutical Industry Food & Beverage Industry, storage facilities Commercial buildings Industrial Airports Continuous air quality monitoring : PM1, PM2.5, PM10 particles VOCs, CO2, Humidity, Temperature Detect ventilation and ltration malfunctions Computer, smartphone, central control building compatible Easy installation and low maintenance Calibration performed in factory (ready to install) Compatible with various standardized automation systems (KNX, LON, Modbus, RS485, IP (POE), EnOcean,…) INDOOR AIR QUALITY CONTROL interference with the day light entering the chamber. The detection principle looks like this: For CO2, VOCs, Temperature, Humidity : Solid state sensors or NDIR sensors calibrated in factory PM1 PM2.5 PM10 VOC CO2 T RH (REAL TIME)

Transcript of I N D O O R A I R Q U A L I T Y C O N T R O L ( R E A L T ... · Densities of PM1, PM2.5 and PM10...

Page 1: I N D O O R A I R Q U A L I T Y C O N T R O L ( R E A L T ... · Densities of PM1, PM2.5 and PM10 expressed in μg/m3 Density of PM1, PM2.5 and PM10 also expressed in number/m3 Measuring

OVERVIEWHealthcare Associated Infections (HAIs), or Nosocomial infections, are one of the leading causes of death in the United States of America more than Breast Cancer, AIDS, and Auto Accidents combined.According to the American CDC (Centers for Disease Control and Prevention),one of every 25 patients contracts an infection in the hospital causing more than 75,000 deaths each year in the US.205 Americans die from Hospital-Acquired Infections each day.HAI cost almost $10 billion annually in the US.Airborne transmission is one of the environmental routes of Nosocomial infections in hospitals such as Infl uenza, SARS, Measles, Tuberculosis.Hospital occupants (patients, Hospital staff, visitors)

and their activities are responsible for most of the contaminants in the conditioned space and some microorganisms are transmitted directly from person to person in the form of droplets in the air. When droplets are produced during a cough or sneeze, a cloud of infectious particles is released into the air, resulting in potential exposure of susceptible persons within three feet of the source person.The coarsest particles (larger than 2.5 micrometers) fall fast enough, their residence time in the air is of the order of 1 day, while the fi nest can stay up to 1 week in suspension and travel thousands of kilometers. Once deposited, the particles can then be re suspended by the wind or by indoor air fl ow.

OBJECTIVEMonitor 24/7 Indoor air quality (particles, VOCs, CO2, RH, Temperature) from any computer or smartphone or from central building control system to detect risk of contagious airborne diseases and environment pollution risk (viruses, bacteria, spores, VOCs).

For particles :Principle of detection The P4000 uses laser diffraction technology (Light Scattering)

maeb resal a nehw :gniwollof eht si elpicnirp ehTpasses through pure air, the beam is invisible. When the beam is visible, this is because the beam is diffracted onto particles along its path. If you look at beam from the side, the more the beam is visible, the more the particle density. This particle probe uses a sensor with a near-infrared source (laser diode). The sensor is an avalanche photodiode with amplifi er. Infrared is used to avoid

TECHNOLOGY

OPERATIONThe device must be placed in the area of occupancy of the premise served by outlet vents AMD mounted on a wall at eyes level (breathing human level, between 1.5 and 1.8m).

I N D O O R A I R Q U A L I T Y C O N T R O L

BENEFITS AREASHospitals ▪Clinics & Medical centers ▪Dental clinics and dental surgery ▪Laboratories ▪Pharmaceutical Industry ▪Food & Beverage Industry, storage ▪facilities ▪Commercial buildings ▪Industrial ▪Airports ▪

Continuous air quality monitoring : ▪ PM1, PM2.5, PM10 particles VOCs, CO2, Humidity, Temperature

Detect ventilation and fi ltration malfunctions ▪Computer, smartphone, central control building ▪compatibleEasy installation and low maintenance ▪Calibration performed in factory (ready to install) ▪Compatible with various standardized automation ▪systems (KNX, LON, Modbus, RS485, IP (POE), EnOcean,…)

INDOOR AIR QUALITY CONTROL

interference with the day light entering the chamber. The detection principle looks like this:

For CO2, VOCs, Temperature, Humidity :Solid state sensors or NDIR sensors calibrated ▪in factory

PM1PM2.5PM10

VOCCO2

TRH

( R E A L T I M E )

Page 2: I N D O O R A I R Q U A L I T Y C O N T R O L ( R E A L T ... · Densities of PM1, PM2.5 and PM10 expressed in μg/m3 Density of PM1, PM2.5 and PM10 also expressed in number/m3 Measuring

SPECSHEETFOR PARTICLES MONITOR

FOR VOCs, CO2, RH, TEMPERATURE MONITOR

PROJECT:

APP

RO

VALS

INFO © 2014 ı STERIL INNOVATIONS www.sterilinnovations.com Email: [email protected]

RS485 Modbus digital output (Contact us for Modbus protocol ▪details)ASCII or RTU Modbus mode (to be chosen when ordering) ▪Densities of PM1, PM2.5 and PM10 expressed in μg/m3Density of PM1, PM2.5 and PM10 also expressed in number/m3 ▪Measuring range 0-950 μg/m3 and 0-65 535 000 particles /m3 ▪Resolution 0.1μg/m3 and 1000 particles per m3 Running average ▪on 30 seconds The sensor cannot see particles below 0.5μm Power supply 12 to 24V DC or ACPower: 1W Operating Temperature: 0 to 45 °C. Storage temperature: ▪-30 to 60 °C Compatible with VOCs,CO2,RH,Temperature monitor for interfacing with EnOcean, LON or KNX 20 selectable BUS addresses (1 to 10 then 11 to 20 with a jumper).

Calibration Performed at factory. Do not touch the potentiometer. ▪No recalibration required if preventive maintenance is performed according to the rulesDimensions: ▪ 135 x 90 x 28 mm

73 / 23 / EEC89 / 336 / EEC (EMC Directive)

INDOOR AIR QUALITY CONTROL

Dimensions are nominal, and illustrations and specifi cations are based on the latest product information available at the time of publication.STERIL INNOVATIONS reserves the right to make changes at any time without notice.

Power supply: KNX bus (45mA) or separate from 12V to 24V ▪AC or 15 to 31V DC (+ / -10%) / 45mA for RS485 or LON.Sensors: ▪

CO2: solid state or NDIR as an option for severe environment -with chlorine.VOC: solid state -Humidity: solid state capacitive -Temperature: NTC -

Recalibration of Zero: Automatic every 24 hours for CO2, every ▪20 days for VOC.Outputs: ▪

Two dry contacts with following activation threshold of CO2 1. or VOC or RH parameterized by four DIP switches:

Threshold 1: CO2: 500 or 900 ppm (selectable) / 0.5 ppm -formaldehyde equivalent (VOC) / 75% RH over 20 minutesThreshold 2: CO2: 1250 or 1800ppm (selectable) / 3 ppm -formaldehyde equivalent (VOC) / 85% RH over 5 minutesType of contacts: normally open (NO) or closed (NC) -

selectable for each alarm.Dry contacts: Isolation 3750 V rms / 1 min, 30VDC / 0.6A -max. Hysteretic of contact: CO2: 100 ppm, VOC: 10% threshold -equivalent formaldehyde, RH: 10% threshold.

1-10 V output representing a mix of CO2, VOC and RH if > 2. 75%.Output Bus Communication: Modbus RS485, KNX, LON and 3. or EnOcean according to module installed.

Information available on the Bus: ▪ - CO2 expressed in ppm - VOC expressed as equivalent ppm formaldehyde - Ambient Temperature in °C - Relative Humidity in % and Absolute in gr/l, Dew Point in °C in KNX and LON

Response time < 30 seconds ▪Start Time for 90% of performance ratings: 24 hours (C02 and ▪VOCs measured after 20 minutes)

LifetimeGas sensors: 10 years under normal use. ▪Humidity: drift max +/-0.5% RH/Y ▪Temperature: Unlimited. ▪

AccuracyCO2: + / - 100 ppm & 15% (50ppm & 2% in NDIR) at 25°C and ▪1013mbar, measuring range: 390 to 3500 ppm (2000ppm in NDIR), 10 ppm resolution.VOC: + / - 0.1 ppm & 15% (Formaldehyde equivalent, see table). ▪Max 300ppm, 0.01 ppm resolution

Above accuracies require the probe to be associated with active air renewal.

Relative Humidity: + / - 3%, measuring range: 10% to 90%, ▪resolution 1%.Temperature: + / - 0.3 ° C, resolution 0.1 ° C, range from 0 ° to + ▪50 ° C.

Dimensions: 135 x 90 x 28 mm

REAL TIME INDOOR AIR QUALITY