    Schneider buswayfrom 630A to 6000 A

    I-LINE II

    Catalogue 2010

  • 8/11/2019 I-LINE II Catalogue 2010

    3/113

    1Schneider Electric

    Contents

    Introduction 3

    Presentation and description 19

    Catalogue numbers and dimensions 35

    Design guide 81

    Installation guide 95

    In decentralised distribution, Schneider busway hits the high note!With Schneider busway, you play all the right notes!Schneider busway, in total harmony with the environment!Schneider busway, fortissimo throughout the range!Schneider busway, a display of advantages!Schneider busway, every one to their music!Schneider busway, hits the right notes!With the Schneider busway tools and services, let us compose your project!

    Panorama of Schneider busway rangeGeneralStraight lengthsFittingsSupports and fixings

    Special fittingsPlug-in units

    Catalogue number coding

    I-LINE II Copper Busway (CFC)Straight lengthsStraight length componentsElbowsFlanged endsCable Tap BoxFeed units for transformerSupports and fixings

    I-LINE II Copper Contact Busway (BFC)Straight lengthsStraight length componentsElbowsFlanged endsCable Tap Boxfeed units for transformerSupports and fixings

    Plug-in units

    CharacteristicsDesigning with I-LINE II busbar trunking systemHarmonic currentsFire resistanceMeasurements and metering

    Direct current

    Layout adviceRising mainsReception, handling and storageTesting and CommissioningMaintenanceSuggested specification

    346810121617

    2026282931

    3233

    36

    38394151545557

    60616368717274

    76

    8284889092

    94

    9699101103107110

  • 8/11/2019 I-LINE II Catalogue 2010

    4/113

    2 Schneider Electric

  • 8/11/2019 I-LINE II Catalogue 2010

    5/113

    3Schneider Electric

    Introduction

    In decentralised distribution,Schneider busway hits the high note!

    Schneider busway on its second world tour More than 50 years of experience, with hundreds of thousands of installations inoperation throughout the world. Full KEMA-KEUR type test certification (IEC60439) for each and every ampererating of busway.

    A total coordination with theSchneider Electric systemBusway is a part of a comprehensive offering of Schneider Electric productsdesigned to operate together. This concept covers all low and mediumvoltage electrical distribution components. The result is an optimised electricalinstallation with even higher performance through full electrical, mechanical andcommunication compatibility.With the new range, you get a complete, tested distribution solution thatcomplies with standards. It is perfectly suited to traditional applications (factories,

    warehouses, etc.) and to the distribution of electrical power from the incomingtransformer on through to all types of loads in offices, commercial premises,

    laboratories, etc.

    Schneider Busway Guangzhou was initially set up by Square D, USA in 1997, andnow is a professional busbar trunking manufacturer, product including I-LINE II andCanalis series, mainly supplying to the Asia Pacific and Middle East market.

    More than 50,000 km of Schneider busbar trunking has been

    sold around the world.

    Square D facility in Oxford, Ohio U.S.A. is an ISO 9001 and

    ISO 14001 registered busbar trunking manufacturing facility.

    Schneider Buway (Guangzhou) Ltd. is certified having ISO

    9001 quality management system, ISO 14001 environment

    management system and OHSAS 18001 occupational health

    and safety management system.

    I-LINE busbar trunking system was first introduced by Square D in 1961 in itsproduction facility in Oxford, Ohio U.S.A. As one of the major brands of theSchneider Electric, Square D has acquired worldwide recognition in a variety ofbusway applications.

    Dijon Factory was set up in 1972, manufacturing Canalis Busbar trunking system,ISO 9001 and ISO 14001 certified.

    Canlis Factory, Dijon, France

    Schneider Busway Factories

  • 8/11/2019 I-LINE II Catalogue 2010

    6/113

    4 Schneider Electric

    Introduction

    With Schneider busway, you playall the right notes!

    Distribution systems Schneider Electric offers different distribution systems to fit your operating needs.

    Centralised distribution

    For all continuous processes:cement plants,oil and gas,petrochemicals,steel,paper, etc.Centralised distribution offers:continuity of service,combined distribution of power, control and monitoring circuits,

    supervision, etc.

    Our solutions:Prisma Plus and Okken switchboards.

    Decentralised distribution

    For manufacturing industries:mechanical,textiles,lumberinjection moulding,electronics,pharmaceuticals,livestock, etc.Decentralised distribution lets you:

    design installations without layout details,upgrade without shutting down production,get systems up and running sooner thanks to faster installation,generate savings depending on the number of loads.

    Our solutions: Prisma Plus switchboards,Schneider busbar trunking.

    Combined distribution

    Where the advantages of both centralised and decentralised distribution arerequired.Commercial and service buildings:offices,stores,hospitals,

    exhibition halls, etc.Infrastructures:airports,telecommunications,internet data centres,tunnels, etc.Industrial facilities:pharmaceuticals,food processing, etc.

    Our solutions:Prisma Plus and Okken switchboards,Schneider busbar trunking.

  • 8/11/2019 I-LINE II Catalogue 2010

    7/113

    5Schneider Electric

    Introduction

    With Schneider busway, you playall the right notes!

    The Schneider buswaydecentralised distributionconcept

    Electrical power available at all points, throughout the

    installation.

    Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of lifeand property, continuity of service, upgradeability and ease of installation.

    Product characteristics are checked by calculations and tests carried out in ourlaboratories and certified in independent international recognized laboratories.

    A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.

    Savings start with installationWith plug-in points, Schneider busbar trunking reduces installation costs.Given the low cost of adding new circuits, savings increase as the number of loadsincreases, a natural consequence of the growth of your business.

    Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs areintegrated right from the start.The addition, relocation or replacement of load equipment can be carried outquickly, without de-energising the supply trunking or shutting down operation,The cost of making such changes is greatly reduced:loads are located close to supply points,plug-in points are always available,plug-in units can be reused or new ones added quickly for load relocation orreplacement needs.

    Reusable in the event of major changesWhen making major modifications to your installation, the existing trunking can beeasily dismantled and reused.

    Schneider busbar trunking

  • 8/11/2019 I-LINE II Catalogue 2010

    8/113

    6 Schneider Electric

    Introduction

    Schneider busway, in totalharmony with the environment!

    Safety of life and property With Schneider Busway, no toxic emission in case of fireThe busbar trunking has a low combustible load. Its construction uses very littleconsumable material and is halogen free.In the event of a fire, the busbar trunking does not emit any gas or toxic smoke.

    The busbar trunking helps prevent the propagation of a fire through partition wallsand floors.

    Halogen-sensitive applicationsPublic buildings (infrastructures, hospitals, schools, etc.),Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activitybuildings,Sensitive processes (production of electronic components, etc.).

    Schneider Busway contains no PVCs

    When PVCs burn, they produce large amounts of smoke that can be a serioussafety hazard.Reduced visibility:risk of panic,complicates rescue work,Smoke toxicity:hydrogen chloride gas (highly toxic),carbon monoxide (danger of asphyxiation).

    Schneider Busway reduces the risk of exposure to

    electromagnetic fieldsAccording to the WHO (World Health Organisation), exposure to electromagneticfields can be a health hazard starting at levels as low as 0.2 micro-Teslas and

    could represent a long-term risk of cancer. Some countries have created standardsthat stipulate limits

    All electrical conductors generate magnetic fields proportional to the distancebetween them. The design of Schneider busbar trunking with tightly spacedconductors in a metal enclosure helps to considerably reduce radiatedelectromagnetic fields.The electromagnetic field characteristics of Schneider busbar trunking are well-defined and measurements show that they are far below potentially dangerouslevels.

    Example:Consequences of a fire in a 100 m2 office withelectrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces:4400 m3 of smoke,7.5 m3 of hydrochloric acid,3.7 kg of corroded steel.

    Health

  • 8/11/2019 I-LINE II Catalogue 2010

    9/113

    7Schneider Electric

    Introduction

    Schneider busway, in totalharmony with the environment!

    Environment Schneider Busway is fully recyclableSchneider Busway busbar trunking can be reused.Schneider Busway busbar trunking is designed for a long service life and caneasily be dismantled, cleaned and reused.All packaging materials can be recycled (cardboard or recyclable polyethylenefilm).All Schneider Busway products are designed for safe end-of-life recycling. PVC,on the other hand, requires neutralisation of the hydrochloric acid produced usinglime and generates dioxins that are extremely toxic.

    Schneider Busway helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoingconcerns.For this reason, we have optimised the used of all materials used to make ourbusbar trunking:

    Reduction of dangerous or polluting materials.Reduction in the weight of insulating materials,Reduction in the use of plastics for improved fire performance: less energyreleased during combustion, thereby limiting propagation and facilitating extinction(lower calorific value).

    Example:1 kg of PVC generates 1 kg of waste.

    Conservation of naturalresources

    Schneider Busway reduces your line losses by 20 %

    Schneider Busway divides your consumption of plastic by a

    factor of fourThe cost of an electrical installation includes the initial investment for theequipment and its installation, the cost of maintenance and the cost of energylosses during operation.The concept of decentralised distribution is a way to merge all the circuits in oneand thus to reduce to the maximum the low cross-section lengths and the weight of

    insulating materials.

    Example:34m of 250A Schneider busbar trunking eqipped with 7 sets of 25A load.

  • 8/11/2019 I-LINE II Catalogue 2010

    10/113

    Application1. Transformer/ Switchboard connection

    2. Horizontal distribution, from the substation to the loads in workshop

    3. Vertical distribution, from the substation to the loads of each high rise floor

    4. Lighting application, in Park place, supermarket, exhibition center, metro ect.

    1

    2

    3

    4

    8 Schneider Electric

    Introduction

    Schneider busway, fortissimothroughout the range!

  • 8/11/2019 I-LINE II Catalogue 2010

    11/113

    1 2

    3 4

    Lighting application

    Horizontal distribution

    Vertical distribution

    Transformer/ Switchboard connection

    9Schneider Electric

    Introduction

    Schneider busway, fortissimothroughout the range!

  • 8/11/2019 I-LINE II Catalogue 2010

    12/113

    10 Schneider Electric

    Introduction

    Schneider busway, a display ofadvantages!

    The compact size of Schneider busway means it takes up very little space in thebuilding:used as a rising main, it takes up only a minimum of space,used for horizontal distribution, it fits easily into the buildings structure (falsefloors, false ceilings, service shafts, etc).

    Changes in direction have been designed to optimise the space taken up,contrary to an equivalent installation using cables which requires large bendingradii.

    Tap-off units, complete with protective devices, are fitted along the entire lengthof the busbar trunking thus reducing the floor area taken up by the electricaldistribution switchboards.

    A compact solution

    A simple and economicalsystem

    The design study is easy to perform as it does not require a detailed layout ofeach load. Equipment choice is pre-determined and optimised.

    Installing the busbar trunking requires 2 or 3 people only, for a time equivalentto that for installing cableways. The time normally needed for laying cables istherefore saved.

    Connection to the MV/LV substation is made using a quick fitting joint block. Theplug-in units can be prepared in the workshop thus reducing on-site time. Theirconnection to the busbar trunking is done in a single plugging-in operation.Forthose ratings more than 500A, it is done by bolt-on operation.

    Installing busbar trunking lengths can be done as and when building workprogresses, thus optimising on-site work and allowing possible unexpected eventsto be anticipated in advance.

    It is also important to note that busbar trunking is a factory tested solution,meaning the time needed for inspecting connections is reduced (visual inspectionof tightening torque).

  • 8/11/2019 I-LINE II Catalogue 2010

    13/113

    11Schneider Electric

    Introduction

    Complete safety Busbar trunking temperature rise and short-circuit withstand are known andindependent of the installation. Coordination of the Schneider Electric systemresults in complete control of the electrical network.

    Installation standards IEC 60 364 chapter 5.523.6 stipulate that above 4 parallelcables, it is preferable to use busbar trunking. Paralleling many cables leads touneven distribution of currents and the risk of abnormal temperature rise.

    The busbar trunking and plug-in units are designed to guarantee the safety ofpersonnel and equipment:Fully silver-plated cooper contact solution.bolted connections with tightening torque guaranteed by torque nuts.foolproof system to avoid the risk of assembly errors.

    Its metal enclosure and high protection degree protect the busbar trunking from allexternal aggressions (corrosion, rodents, etc).

    Operating continuity

    Seismic Compliance

    When working on the electrical installation, the busbar trunking provides immediatereadability of the electrical circuit thus allowing the appropriate zone to be quicklyidentified.Plug-in units(

  • 8/11/2019 I-LINE II Catalogue 2010

    14/113

    Key projects

    Pentronas Towers (Malaysia)

    Hong Kong International Financial Center (HongKong)

    Shanghai Jin Mao Building (China)

    Emirates Palace (UAE)

    Grand Indonesia Building (Indonesia)

    Dubai International Finance Center (UAE)

    Al Shira'a Tower (Kuwait)

    Beverly Hill Tower (Qatar)

    Al Safwa Tower (Saudi Arabia)

    Robinson Cybergate Center Tower (Philippines)

    Mita Koyamacho High-rise Apartment (Japan)

    International Commerce Centre (Hongkong)

    Congresss Conference Building (Egypt)

    ......

    Key projects

    Carrefour supermarket(World wide)

    Guangzhou International ExhibitionCentre(China)

    Convention & Exhibition Centre(Hong Kong)

    Asia World Expo(Hong Kong)

    Central World Mall(Thailand)

    Siam paragon (Thailand)

    Abu Dhabi National Exhibition Center( UAE)

    Mall of Arabia (Saudi Arabia)

    Melbourne Convention Centre (Australia)

    Mall of the Emirates (UAE)National Convention Centre (Vietnam)

    Queensgate shopping Mall (New Zealand)

    National Olympic Stadium (Guangzhou, China)

    Panda Distribution Facility (Saudi Arbia)

    Las Vegas Sands (Macau)

    ......

    12 Schneider Electric

    Introduction

    Schneider busway, everyone totheir music!

    Key points

    Fire barrier.

    Halogen free.

    Small size.

    Operating continuity.

    Office and Hotel buildings

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    Shopping centres andExhibition centres

  • 8/11/2019 I-LINE II Catalogue 2010

    15/113

    Key projects

    General Motors (World wide)

    Hitachi Semiconductor manufacturing(China)

    Chartered Semiconductor manufacturing(Singapore)

    Maruti Suzuki (India)

    Jabil Plant (India)

    Nikon Factory (Thailand)

    Intel Plant (Malaysia)

    Infineon Plant (Malaysia)

    Bosch (Korea)

    Seagate Factory (Singapore)

    ST Microelectronics (Singapore)

    Ansell Lanka (PVT) Limited (Sri Lanka)......

    Key projects

    Bank of China Tower (Hongkong)

    China Construction Bank (China)

    Citibank Hongkong (Hong Kong)

    Maybank (Malaysia)

    Commercial Bank (Qatar)

    Saudi Telecom Company (SaudiArabia)

    Bharti data Centre (India)

    HSBC Bank HQ (Babrain)......

    13Schneider Electric

    Introduction

    Schneider busway, everyone totheir music!

    Key points

    Operating continuity.

    Able to be evolved.

    Low voltage drops.

    Network readability.

    Industry buildings

    Key points

    Operating continuity.

    High tap-off density.

    Able to be evolved.

    Network compactnessand readability.

    Data centers and Banks

  • 8/11/2019 I-LINE II Catalogue 2010

    16/113

    Key projects

    Three Gorges PowerStation(China)

    Wind Farm(China)

    ExxonMobil Chemicalplant(Malaysia)

    Hysco Steel(India)

    Shell Chemical plant (Malaysia)

    Petro Rabigh(Saudi Arabia)......

    Key projects

    Beijing Capital New InternationalAirport(China)

    Suvarnabhumi Airport (Thailand)

    Tan Son Nhat Airport(Vietnam)

    India Ahmedabad Airport(Inida)

    Cairo Airport(Egypt)

    Dubai Airport(UAE)

    Jebel Ail Airport(UAE)......

    Schneider Busway, everyone totheir music!

    Key points

    Operating continuity.

    Able to be evolved.

    Low voltage drops.

    Network readability.

    Energy

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    Airport

    14 Schneider Electric

    Introduction

  • 8/11/2019 I-LINE II Catalogue 2010

    17/113

    Key projects

    The first affiliated Hospital,Guangzhou(China)

    Angkor InternationalHospital(Thailand)

    Al-Maidan Hospital(Kuwait)

    Beijing 301 Hospital(China)

    Mina Hosptital (Saudi Arabia)

    Dammam Hospital (Saudi Arabia)

    ......

    Key projects

    Guangzhou Metro(China)

    Singapore Metro

    Madrid Metro (Spain)

    London Metro (UK)

    ......

    Schneider Busway, everyone totheir music!

    Key points

    Fire barrier.

    Halogen free.

    Small size.

    Operating continuity.

    Hospital

    Key points

    Halogen free.

    Distribution and metering.

    Able to be evolved.

    Sprinklers.

    Metro

    15Schneider Electric

    Introduction

  • 8/11/2019 I-LINE II Catalogue 2010

    18/113

    16 Schneider Electric

    Introduction

    Schneider busway, hits the rightnotes!

    IEC Certification ASTA / ASEFA /KEMA / IECEE / CNALUL CertificationCCC approvedISO 9001, ISO14001OHS18001Six Sigma Program

    Quality - Accreditations

  • 8/11/2019 I-LINE II Catalogue 2010

    19/113

    17Schneider Electric

    Introduction

    With the Schneider busway toolsand services, let us compose yourproject!

    Work-out yoursolution together

    Our teams are available to provide customers with technical assistance throughoutthe installation of their projects.

    Design of electrical distribution architectures:design of decentralised transport and distribution systems,technical and financial optimisation of busbar trunking design projects,transformer / switchboard l ink,installation coordination and discrimination.

    Full installation drawings:3D drawings with corresponding parts lists,2D drawing with dimensions,detailed connection drawings.

    Site supervision and commissioning assistance.

    Training for designers and contractors.

    Project

    launch

    Technical

    support

    Autocad

    drawing

    BRASS

    drawing

    Production

    Project

    management

    On-site

    instruction

    and

    installation

    After-salesservice

  • 8/11/2019 I-LINE II Catalogue 2010

    20/113

    Horizontal distribution

    Vertical distribution

    18 Schneider Electric

    Introduction

    With the Schneider busway toolsand services, let us compose yourproject!

    Schneider Electric offers a comprehensive design software.The BRASSsoftware, edited by Schneider Electric, was developed to help youdesign I-LINE II busbar trunking runs.

    BRASS, a comprehensive toolThe BRASS software allows you to quickly design the best layout for your project.It allows:the material needed to be easily chosena list of catalogue numbers and their exact quantities to be defined

    BRASS gives you all thehelp you need

    State-of-the-art softwareThe advanced BRASS design software enables you design from the routing to

    component detail in a more accurate, convenient and quicker way.

  • 8/11/2019 I-LINE II Catalogue 2010

    21/113

    19Schneider Electric

    Presentation 20Panorama of Schneider Busway range 20Lighting distribution 20Power distribution 22

    I-LINE II from 630 to 6000 A 24

    Description 26

    General 26

    Straight lengths 28

    Fittings 29

    Supports and fixings 31

    Special fittings 32

    Plug-in units 33

    Presentation and description

    Presentation

    Description

  • 8/11/2019 I-LINE II Catalogue 2010

    22/113

    20 Schneider Electric

    Presentation

    Presentation

    Canalis

    Panorama of Schneider Busway rangeLighting distribution

    Range Canalis KDP

    Run components

    Degree of protection IP55

    Number of circuits 1

    Rating 20 A

    Tap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm

    Standard lengths 24 and 192 meters

    Finish -

    Maximum distance between fixing points 0,70 meter

    KDP-KBA-KBB tap-off units

    Rating 10 and 16 A

  • 8/11/2019 I-LINE II Catalogue 2010

    23/113

    21Schneider Electric

    Presentation

    Canalis KBA Canalis KBB

    IP55 IP55

    1 1 or 2

    25 and 40 A 25 and 40 A

    500 - 1000 and 1500 mm 500 and 1000 mm

    2 and 3 meters 2 and 3 meters

    Galvanised steel Galvanised steel

    3 meters 5 meters

    10 and 16 A 10 and 16 A

    Presentation

    Canalis

    Panorama of Schneider Busway rangeLighting distribution

  • 8/11/2019 I-LINE II Catalogue 2010

    24/113

    22 Schneider Electric

    Presentation

    Presentation Panorama of Schneider Busway rangePower distribution

    Canalis

    Range Canalis KS Canalis KS rising mains

    Run components

    Degree of protection IP52/54 IP52/54

    Polarity 3L + N + PE 3L + N + PE

    Rating 100, 160, 250, 400, 500, 630, 800 100, 160, 250, 400, 500, 630, 800

    Tap-off intervals 1000 mm on each face 500 mm

    Standard lengths 3 and 5 meters Defined by the floor pitch

    Finish White RAL 9001 White RAL 9001

    Maximum distance between fixing points 3 meters Defined by the floor pitch

    Tap-off units

    Rating Plug-in 25 to 400 A 25 to 400 A

    Bolt-on

  • 8/11/2019 I-LINE II Catalogue 2010

    25/113

    23Schneider Electric

    Presentation

    Presentation Panorama of Schneider Busway rangePower distribution

    I-LINE II

    I-LINE II Copper busway I-LINE II Copper contact busway

    IP40 / 41 / 54 / 55 / 65 / 66/ 67 IP40 / 41 / 54 / 65 / 66/ 67

    3L + N+PE / 3L+ PE ; 3L + N+PE / 3L+ PE ;

    630 - 6000A 800 - 5000A

    610mm/1220mm 610mm/1220mm

    10 Feet 10 Feet

    ANSI 49 ANSI 49

    10Ft 10Ft

    15 to 500 A 15 to 500 A

    630A to 1600 A 630A to 1600 A

  • 8/11/2019 I-LINE II Catalogue 2010

    26/113

    24 Schneider Electric

    Presentation

    Run sections Plug-in units Elbow Fittings

    Rating: 13 ratings are available, from630A to 6000AStandard length: 10 feet, 6 feet, 4 feetNone-standard length: minimum length406mm

    All I-LINE plug-in units are compatible withI-LINE II busbar trunking systemCategory: plug-in unit with MCCB,Plug-in unit with Schneider MCCB, am-pere rating from 15A to 1000A

    Standard elbow:Flatwise elbowEdgewise elbowNon-standard elbow:Double elbowOffset elbowElbow plus flanged endElbow in special angleElbow in special length

    I-LINE II from 630 to 6000 AHigh Power transport anddistribution

    Presentation

    I-LINE II

  • 8/11/2019 I-LINE II Catalogue 2010

    27/113

    25Schneider Electric

    Presentation

    Connection fittings Fixing supports

    Supply connections allow thebusbar trunking to be connected to theswitchboards busbar or to the transformer.Flanged endQwik Flanged endcable connection, transport currentbetween cable and busbar trunking.End cable tap boxCenter cable tap box

    Vertical supportFix hangerSpring hangerHorizontal supportFlatwise hangerEdgewise hanger

    I-LINE II

    I-LINE II from 630 to 6000 AHigh Power transport anddistribution

    Presentation

  • 8/11/2019 I-LINE II Catalogue 2010

    28/113

    26 Schneider Electric

    Description

    Description

    The I-LINE II busbar trunking is intended for high power distribution and transportin industrial, commercial and tertiary buildings.Assembly of prefabricated sections that adapt to all run configurations.

    General

    Straight Length

    Joint Pak

    I-LINE II

    13 ratings are available, from 630A to 6000ASilver plated copper contactConductors full-length insulated using Mylar film, class B, 130CAvailable polarities: 3L +PE, 3L +N+PEMaximum rated voltage: 1000 VoltsInsulation voltage: 1000 Volts

    Compact Size, Sandwich Structure, totally enclosed housing

    Universal Installation, no need to consider de-rating factor, regardless of themounting position.The accumulation of dirt on exposed bus bars and possibility of accidentalcontact with bus bar are greatly reduced.No Chimney effectContinuous air spaces inside I-line busway housing are closed off with specialbarriers to help prevent the spread of smoke and gases in the event of a fire inthe area of the busway installation. This standard internal barrier allows busway toextend through wall or floors without creating open space for a chimney effect firepath.Improve systems ventilation, satisfy higher ampere ratingLess space required for installation, investment saving

    The I-LINE II busbar trunking is suitable for applications containing harmonics bytaking into account the appropriate derating factor. See Harmonic currents in theDesign guide.

    Joint-Pak is standard on I-LINE II system. It allows for quick removal of lengthsfrom the busbar trunking runs for load shifting or maintenance. It also can beremoved and relocated on the opposite end of the length for the last minutes jobchanges

    Single bolt connection makes installation fasterBelleville washer provides equal pressure across the complete joint contact areato assure proper electrical contact

    Double, Silver plated surface contact ensure a good current continuity.Adjustable range: +/- 3mm

    VIST-TITE BoltThe double head design, introduced by Square D in 1967, allows the customer totighten the joint to the proper torque using a standard spanner. The outer head willbreak off when the correct torque is achieved. A second bolt head remains to allowfor joint maintenance or busbar relocation. No need to purchase a replacementbolt. For maintenance of the joint or when busway is relocated, the VISIT-TITE boltshould be tightened to 70 lb-ft (95Nm) with a torque wrench

    Electro-galvanized steel, better anti-corrosion.Paint: Epoxy electrostatic powder finishColor: ANSI 49 gray, special color are optional upon customers request.

    Housing

  • 8/11/2019 I-LINE II Catalogue 2010

    29/113

    27Schneider Electric

    Description

    GeneralDescription

    I-LINE II

    Earthing Bus

    I-line II is furnished with the integral earthing bus as standard. The earthing busis the bus housing itself and completely encloses the bus sandwich. It is rated at50% capacity. The earthing bus is Continuous bonding between top and bottombus.

    Internal Aluminum/copper earthing bus is optional.

    Schneider believes an earthing conductor is extremely important, to provide the

    maximum amount of protection for a distribution system in todays ever expandingelectrical systems. With our design, we have given the maximum amount ofprotection in an economical package.

    Conductor

    Copper (Copper busway)99.97% purity of copperSilver plated copper in full lengthminimize surface oxygenation, assure low surface contact resistance and lowvoltage drop

    Insulation

    Two layers surrounding each bus barClass B, 130C, Vendor certified polyester film (DuPont Mylar)Excellent dielectric performanceOver 40 years of application record without failureClass F is optional upon requestHalogen free, safe in fire

    Degree of Protection

    Schneider offers the I-LINE II bus bar trunking system in a variety of housingconstructions to meet your application and needs.

    Feeder type IP40-IP67Riser type IP40-IP54Plug-in type IP40-IP54

    Aluminum with copper contact (Copper Contact busway)Use silver-plated Bi-metal cladding on Aluminum conductor through high

    current and high pressure.Special process enabling molecular fusion of Copper and Aluminum throughthe use of very high pressure and temperature.

    All of connection zone are silver to silver.

    Integral Earth Bus Internal Earth Bus

  • 8/11/2019 I-LINE II Catalogue 2010

    30/113

    28 Schneider Electric

    Description

    Feeder

    Transport the current without plug-in opening.All straight lengths and fittings of feeder trunking are fully compatible, rating forrating, with straight lengths of plug-in trunking.13 ratings are available, from 630A to 6000AMinimum length 406 mmPolarity: 3L+N+PE, 3L+PE system100% neutral capacity, 50% earth bus capacity

    Straight lengthsDescription

    Straight section

    Riser

    Plug-in opening (PIO) on one side, only 4, 6, 10ft available

    Maximum 2 PIO for 6 feet riser element

    Maximum 4 PIO for 6 feet plug-in element

    Maximum 1 PIO for 4 feet riser element

    Maximum 2 PIO for 4 feet plug-in element

    Maximum 3 PIO for 10 feet riser element

    Maximum 6 PIO for 10 feet plug-in element

    Plug-in

    Plug-in opening on both sides, only 4, 6, 10ft available

    I-LINE II

    Note: tap-off outlet also can be in the circle position.

    Note: tap-off outlet also can be in the circle position.

    Note: tap-off outlet also can be in the circle position.

    Note: tap-off outlet also can be in the circle position.

  • 8/11/2019 I-LINE II Catalogue 2010

    31/113

    29Schneider Electric

    Description

    FittingsDescription

    I-LINE II

    Simple changes of direction

    Changes of direction

    Elbows - Types LF, LE and T

    Double elbows - Types OF, OE DR and DL

    type OE, edgewise offset

    type DR, double right elbow

    type DL, double left elbow

    type OF, flatwise offset

    to go up or down, to turn right or leftStandard angle: 90Special angles : 91- 179

    flat or edgewise, to move the run ais upwards, downwards, to the right or to theleft without having to bend the busbar trunking:

    type LE, edgewise elobw

    type T, flatwise tee

    type LF, flatwise elobw

  • 8/11/2019 I-LINE II Catalogue 2010

    32/113

    30 Schneider Electric

    Description

    FittingsDescription

    I-LINE II

    Connetions to swithboards and transformers

    Connetions to cable

    Type FE, standard flanged end

    Type QF, qwik flanged end

    type LEFE, edgewise elbow plus f langed end

    type LFFE, flatwise elbow plus flanged end

    type ETB, end cable tap box

    type CTB, center cable tap box

    Cable Tap Boxcable connection , transport current between cable and busbar trunking

    Flanged ends - Type FEThey allow the busbar trunking to be connected to a switchboards busbar, or to theterminals of an transformer, generator set, etc.

    They come complete with a mounting plate fitted:

    either directly to the roof of the switchboard,or via the intermediary of a protective cover.

    Vertical or horizontal incoming busbar trunking.

  • 8/11/2019 I-LINE II Catalogue 2010

    33/113

    31Schneider Electric

    Description

    I-LINE II

    Supports and fixingsDescription

    Horizontal Supports

    Vertical Supports

    The horizontal type hanger allow the busbar trunking to be fixed and ajusted alongits length, as well as absorbing its movements.

    The spring hanger has the following advantages:.

    Fix hanger

    Spring hanger

    spring adjustment to ensure distribution of the load at each flooravoids the transmission of buiding forces to the busbar trunking (expansion andvibration)

    type HFF, flatwise hanger

    type HFE, edgewise hanger

    type HFVS1, spring hanger

    type HFV, fix hanger, for all ratings.

    type HFVS2, spring hanger

    type HFVS8, spring hanger

  • 8/11/2019 I-LINE II Catalogue 2010

    34/113

    32 Schneider Electric

    Description

    I-LINE II

    Special fittingsDescription

    Reducer

    Expansion Joint

    An Expansion Fitting should be used under the following conditions:whenever a busway run crosses a building expansion; when a long straight runof busway does not contain any elbows or both ends of the run are fixed and thebusway length is more than 30 meters.No need for riser38mm expansion allowablemore detail in page 99

    Connect the high power and low power runBest way to save investmentStandard reducer is non-fusible, reducer with fuse/MCCB is optional

    The end closure protects and insulates the conductor ends and is fitted to the lastsection.

    End closure

    Connection accessory

    type EJ, absorb horizontal expansion

    type R

    Flexible linkfor the connection between the conducting plates, to reduce the vibration from the

    transformer.

    Connection platesthe conductors of flanged ends are connected via connection plates to the

    switchboard busbars.

  • 8/11/2019 I-LINE II Catalogue 2010

    35/113

    33Schneider Electric

    Description

    Plug-in UnitsDescription

    I-LINE II

    CompatibilityAll plug-in units are compatible with I-LINE II busbar trunking system, regardlesswhether they bear MCCB or fusible switch.

    Plug-in device mountingPlug-in units are positioned along the busbar trunking length by notches in thebusbar trunking housing top which accept the mounting hooks of the plug-in unit.This aligns the plug-in unit jaws with the plug-in opening. After the unit is positionedon the busway, it is allowed to swing down into the plug-in opening where the plug-in jaws make contact with the bus bars. This is accomplished in hook-swing.

    Plug-in JawsThe plug-in jaws contact to the bus bars directly with the silver plated coopercontact. The contact surface is fully silver plated to ensure a proper contact forceand low contact resistance.

    EarthingEarthing established at first and switched off at last as to protect worker againstelectrical contact shock.All plug-in devices incorporate an earthing spring which cuts through the paint andforms an equipment earth between the housing and the body of the device beforethe phase jaws make contact with the busbars.

    Interlock30 A to 250 A plug-in devices are interlocked with the busway housing to preventinstallation or removal of the unit when the disconnect is turned ON.All devices incorporates an interlock to prevent the door over the disconnectfrom being opened when the unit is ON. This door interlock can be defeated fromoutside the unit.

    Operating handleThe side operating handle in the PIU makes the heavy duty switch moreconvenient and safer. When the PIU is installed in the high position, you can easilyoperate the PIU on the group by the side handle.

    Protection functionSchneider Plug-in unit equipped with Schneider original protection unit, whichcan provide complete overload protection, short circuit protection and earthingmalfunction protection. The maximum interrupting is 150KA.

    Transparent shield over Line side parts - that means safety & visible

    Product features of I-LINE II Plug-in Unit

  • 8/11/2019 I-LINE II Catalogue 2010

    36/113

    34 Schneider Electric

    Description

    Plug-in Units

    I-LINE II

    Description

    Plug-in Unit with Merlin Gerins MCCB

    Plug-in typePNS (15-250A), PBNS (350-500A)Bolt-on typePTNS (630-1000A) (different for horizontal/vertical mounting)Fitted with Compact NSEN/ NSES/ NSEH/ NSD / NSN / NSH / NSL(on request)available for 3-pole and 4 pole configurationsavailable for earth leakage current protection (Vigi)IP rating up to IP54Operation type: Side handle type or rotary type

    Category of I-LINE Plug-in Unit

    Plug-in Unit with Merlin Gerins MCCB

  • 8/11/2019 I-LINE II Catalogue 2010

    37/113

    Schneider Electric 35

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Catalogue number coding 36

    I-LINE II Copper Busway (CFC)

    Straight lengths 38

    Straight length components 39

    Elbows 41

    Double elbows 43

    Offset elbows 44

    Elbow plus flanged end 45

    Internal Grounding Elbows 46

    Flanged ends 51

    Cable Tap Box 54

    Feed units for transformer 55

    Supports and fixings 57

    I-LINE II Copper Contact Busway (BFC)

    Straight lengths 60

    Straight length components 61

    Elbows 63

    Double elbows 65

    offset 66

    Elbow plus flanged end 67

    Flanged ends 68

    Cable Tap Box 71

    Feed units for transformer 72

    Supports and fixings 74

    Plug-in units 76

  • 8/11/2019 I-LINE II Catalogue 2010

    38/113

    Schneider Electric36

    Cataloguenumbers

    Dimensions

    Catalogue-number coding

    Catalogue Numbering System Generic v Discrete

    Catalogue-number composition (I-LINE II Copper Busway)

    One letter designating the application.Busbar material Code

    Copper C

    Type Code

    Feeder F

    Riser plug-in R

    Plug-in P

    Standard Code

    IEC C

    I-LINE II 2

    Polarity Code

    3L + PE 3

    3L + N + IGB (integral earth) 5

    3L + N + ING (internal earth) 6

    Rating Code

    630 06

    800 08

    1000 10

    1250 12

    1350 13

    1600 16

    2000 20

    2500 25

    3000 30

    3200 32

    4000 40

    5000 50

    6000 60

    Type of PE Code

    AL G

    CU GGDimension of component

    Two letters identifying the type of component.Type Code

    Generic Code

    Elbow EL

    Flange End FE

    Qwik Flange End QF

    Expension Joint EJ

    End Tap Box ETB

    Center Tap Box CTB

    Flat Tee T

    Unfused Reducer R

    Discrete Code

    Edgewise Elbow LE

    Flatwise Elbow LF

    Edgewise Offset Elbow OE

    Flatwise Offset Elbow OF

    Double Left Elbow DL

    Double Right Elbow DR

    Flange End Edgewise Elbow LEFE

    Flange End Flatwise Elbow LFFE

    Flange End - Double left FEDL

    Flange End - Double right FEDR

    Straight Length - Feeder/Plug-in/Riser ST

    Phase Transition PT

    Degree of Pretection Code

    IP40 --

    IP54 M54

    IP55*** M55

    IP65*** M65

    IP66*** M66IP67*** M67*** Available for feeder system only

    Catalogue numbers anddimensions

    CC2GM

    Generic catalogue # describes all the features of busway (e.g. copper, ampere rating,

    IP rating, 3/4 poles etc except length. Hence it is not for describing individual pieces

    of busway but rather for quotation/contract/invoicing purposes. The unit is 1 piece (for

    fittings) or 1 feet (straights)

    Discrete catalogue # describes all the features of busway including length of the

    individual pieces. With the discrete catalogue number itself, it tells the detailed length

    of busway and is sufficient enough for production purposes. We also call this as BOM

    (Bill of Materials)

    I-LINE II Copper Busway

  • 8/11/2019 I-LINE II Catalogue 2010

    39/113

    Schneider Electric 37

    Cataloguenumbers

    Dimensions

    Catalogue-number coding

    Catalogue Numbering System Generic v Discrete

    Catalogue-number composition (I-LINE II Copper Contact Busway)

    Catalogue numbers anddimensions

    BC2GM

    I-LINE II Copper Contact Busway

    One letter designating the application.Busbar material Code

    Bimetal B

    Type Code

    Feeder F

    Riser plug-in R

    Plug-in P

    Standard Code

    IEC C

    I-LINE II 2

    One digit indicating the trunking polarityPolarity Code

    3L + PE 3

    3L + N + IGB (integral earth) 5

    Rating Code800 08

    1000 10

    1250 12

    1350 13

    1600 16

    2000 20

    2500 25

    3200 32

    4000 40

    5000 50

    Type of PE Code

    AL G

    Dimension of component

    Two letters identifying the type of component.Type Code

    Generic CodeElbow EL

    Flange End FE

    Qwik Flange End QF

    Expension Joint EJ

    End Tap Box ETB

    Center Tap Box CTB

    Flat Tee T

    Unfused Reducer R

    Discrete Code

    Edgewise Elbow LE

    Flatwise Elbow LF

    Edgewise Offset Elbow OE

    Flatwise Offset Elbow OF

    Double Left Elbow DL

    Double Right Elbow DRFlange End Edgewise Elbow LEFE

    Flange End Flatwise Elbow LFFE

    Flange End - Double left FEDL

    Flange End - Double right FEDR

    Straight Length - Feeder/Plug-in/Riser ST

    Phase Transition PT

    Degree of Pretection Code

    IP40 --

    IP54 M54

    IP55*** M55

    IP65*** M65

    IP66*** M66

    IP67*** M67

    *** Available for feeder system only

  • 8/11/2019 I-LINE II Catalogue 2010

    40/113

  • 8/11/2019 I-LINE II Catalogue 2010

    41/113

    C

    N

    N

    C

    39Schneider Electric

    Cataloguenumbers

    Dimensions

    OrderingComplete the catalogue number by replacing by the rating and protection

    degree.

    Example:Generic catalogue number of 1000A expansion joint, 3L+N+PE :

    CFC2510GEJM54

    Discrete catalogue number of a standard 1000A expansion joint,3L+N+PE:

    CFC2510GEJM54

    Rating

    Rating

    Protection degree

    Protection degree

    Catalogue numbers anddimensions

    Straight length components

    Type Length(mm)

    Height(mm)

    Width (mm)

    630 800 1000 1250 1350 1600 2000 2500 3000 3200 4000 5000 6000

    Fixed 1016 508 343 343 343 343 343 442 442 492 492 594 594 819 819

    I-LINE II Copper Busway

    Type Length(mm)

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Fixed 966 CFC23G38PTM CFC25G38PTM CFC26GG38PTM

    Type Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Fixed CFC23GEJM CFC25GEJM CFC26GGEJM

    Unfused Reducer

    Phase transition

    Type Length(mm)

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Fixed 610 CFC23GRM CFC25GRM CFC26GGRM

    Note: Replace R with below code. For example, CFC2520GR10M54.

    Bolt side

    AmpereRating

    400 600 800 1000 1250 1350 1600 2000 2500 3000 3200 4000

    800 - R4 - R6 - - - - - - - - - -

    1000 - R4 - R6 - R8 - - - - - - - - -

    1250 - R4 - R6 - R8 -R10 - - - - - - - -

    1350 - - R6 - R8 -R10 -R12 - - - - - - -

    1600 - - R6 - R8 -R10 -R12 - R13 - - - - - -

    2000 - - - R8 -R10 -R12 - R13 - R16 - - - - -

    2500 - - - -R10 -R12 - R13 - R16 - R20 - - - -

    3000 - - - -R10 -R12 - R13 - R16 - R20 - R25 - - -

    3200 - - - - -R12 - R13 - R16 - R20 - R25 - R30 - -

    4000 - - - - - - R13 - R16 - R20 - R25 - R30 - -

    5000 - - - - - - - R16 - R20 - R25 - R30 - R32 -

    6000 - - - - - - - - - R25 - R30 - R32 - R40

    Note: MCCB reducers are available. Contact us for details.

    Expansion Joint

  • 8/11/2019 I-LINE II Catalogue 2010

    42/113

    40 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Straight length components

    I-LINE II Copper Busway

    Wall and floor flange (WF)

    End closure

    Type Rating(A)

    Dimension (mm) Cat. no.

    A

    End closure 630 110 ACF38EC

    800 110 ACF38EC

    1000 110 ACF38EC

    1250 123 ACF43EC

    1350 148 ACF53EC

    1600 161 ACF58EC

    2000 184 ACF67EC

    2500 250 ACF93EC

    3000 336 ACF13EC

    3200 399 ACF15EC

    4000 425 ACF17EC

    5000 612 ACF24EC

    6000 650 ACF25EC

    Rating(A)

    Straight Length Flanged End Cat. no

    A(mm) Y W Y W

    630 211 152 203 254 341 ACF38WF

    800 211 152 203 254 381 ACF38WF

    1000 211 152 203 254 381 ACF38WF

    1250 224 152 203 254 381 ACF43WF

    1350 249 178 203 279 381 ACF53WF

    1600 262 203 203 305 381 ACF58WF

    2000 285 229 203 356 381 ACF67WF

    2500 351 279 203 483 533 ACF93WF

    3000 437 381 203 483 533 ACF13WF

    3200 500 432 203 584 533 ACF15WF

    4000 526 457 203 584 533 ACF17WF

    5000 713 660 203 813 533 ACF24WF

    Flatwise Elbow Wall thickness (mm)

    Rating(A)

    100 200 300 400 500 600

    W(mm) Y(mm)

    630 203 229 279 330 381 432 483

    800 203 229 279 330 381 432 483

    1000 203 229 279 330 381 432 483

    1250 203 254 305 356 407 457 508

    1350 203 305 356 406 457 508 559

    1600 203 305 356 406 457 508 559

    2000 203 356 406 457 508 559 610

    2500 203 432 483 533 584 635 686

    3000 203 559 610 660 711 762 813

    3200 203 660 711 762 813 864 914

    4000 203 686 737 787 838 889 940

    5000 203 940 991 1041 1092 1143 1194

    Edgewise Elbow Wall thickness (mm)

    Rating(A)

    100 200 300 400 500 600

    Y(mm) W(mm)

    630 150 305 356 406 457 509 559

    800 150 305 356 406 457 509 559

    1000 150 305 356 406 457 509 559

    1250 150 305 356 406 457 509 559

    1350 176 305 356 406 457 509 559

    1600 203 305 356 406 457 509 559

    2000 229 305 356 406 457 509 559

    2500 279 305 356 406 457 509 559

    3000 381 305 356 406 457 509 559

    3200 432 305 356 406 457 509 559

    4000 457 305 356 406 457 509 559

    5000 660 305 356 406 457 509 559

  • 8/11/2019 I-LINE II Catalogue 2010

    43/113

    41Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Elbows

    Type Rating(A)

    Cat. no3L+PE 3L+N+IGB

    Standard 630 CFC2306GLFM11M CFC2506GLFM11M800 CFC2308GLFM11M CFC2508GLFM11M1000 CFC2310GLFM11M CFC2510GLFM11M1250 CFC2312GLFM11M CFC2512GLFM11M1350 CFC2313GLFM12M CFC2513GLFM12M1600 CFC2316GLFM12M CFC2516GLFM12M2000 CFC2320GLFM12M CFC2520GLFM12M2500 CFC2325GLFM14M CFC2525GLFM14M3000 CFC2330GLFM15M CFC2530GLFM15M3200 CFC2332GLFM16M CFC2532GLFM16M4000 CFC2340GLFM17M CFC2540GLFM17M5000 CFC2350GLFM21M CFC2550GLFM21M6000 CFC2360GLFM21M CFC2560GLFM21M

    Made tomeasure

    All CFC23GLFSBM CFC25GLFSBM

    Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)

    630 279 279800 279 2791000 279 2791250 279 2791350 305 3051600 305 3052000 305 3052500 356 3563000 381 3813200 406 4064000 432 4325000 533 5336000 533 533

    Made to measure All min ~ 1219 min ~ 1219

    I-LINE II Copper Busway

    Flatwise elbows with made to measure angles

    Flatwise elbow

    Type Rating Angle(W)

    Cat. no

    3L+PE 3L+N+IGB

    Made tomeasure

    All 91 ~ 179 CFC23GLFOASBAM CFC25GLFOASBAM

    =+, A=A+angle

    OA - special angle

    OrderingComplete the catalogue number by replacing by the rating and protectiondegree.

    Example:Generic catalogue number of 1000A flatwise elbow, 3L+N+PE

    CFC2510GELM54

    Discrete catalogue number of a 24 inch, 1000A flatwise elbow, 3L+N+PE:

    CFC2510G24LFS13B11M54

    S - the elbow side without joint pakB - the elbow side with joint pak

    Rating

    Rating

    Protection degree

    Protection degree

    - the length of the elbow side with joint pak - the length of the elbow side without joint pak - the total length of elbow

  • 8/11/2019 I-LINE II Catalogue 2010

    44/113

    42 Schneider Electric

    Cataloguenumbers

    Dimensions

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Standard 630 CFC2306GLEM11M CFC2506GLEM11M800 CFC2308GLEM11M CFC2508GLEM11M10 00 CFC 231 0GL EM11M CFC2510GLEM11M12 50 CFC 231 2GL EM11M CFC2512GLEM11M13 50 CFC 231 3GL EM11M CFC2513GLEM11M16 00 CFC 231 6GL EM11M CFC2516GLEM11M20 00 CFC 232 0GL EM11M CFC2520GLEM11M25 00 CFC 232 5GL EM11M CFC2525GLEM11M30 00 CFC 233 0GL EM11M CFC2530GLEM11M32 00 CFC 233 2GL EM11M CFC2532GLEM11M40 00 CFC 234 0GL EM11M CFC2540GLEM11M50 00 CFC 235 0GL EM11M CFC2550GLEM11M60 00 CFC 236 0GL EM11M CFC2560GLEM11M

    Made tomeasure

    All CFC23GLESBM CFC25GLESBM

    =+

    Catalogue numbers anddimensions

    Elbows

    Edgewise elbows

    Edgewise elbows with made to measure angles

    Dimension

    Type Rating (A) Dimensions (mm)

    A BStandard(min) All 279 279Made to measure All min ~ 1219 min ~ 1219

    I-LINE II Copper Busway

    Type Rating Angle(W)

    Cat. no

    3L+PE 3L+N+IGB

    Made tomeasure

    All 91~179CFC23GLESBAM CFC25GLESBAM

    =+, A=A+angle

    A

    B

    Flatwise Tee

    Type Rating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Standard 630 CFC2306G33T FS 11B11S11M CFC2506G33TFS11B11S11M

    800 CFC2308G33T FS 11B11S11M CFC2508G33TFS11B11S11M

    1000 CFC2310G33TFS11B11S11M CFC2510G33TFS11B11S11M

    1250 CFC2312G33TFS11B11S11M CFC2512G33TFS11B11S11M

    1350 CFC2313G36TFS12B12S12M CFC2513G36TFS12B12S12M

    1600 CFC2316G36TFS12B12S12M CFC2516G36TFS12B12S12M

    2000 CFC2320G36TFS12B12S12M CFC2520G36TFS12B12S12M

    2500 CFC2325G42TFS14B14S14M CFC2525G42TFS14B14S14M

    3000 CFC2330G45TFS15B15S15M CFC2530G45TFS15B15S15M

    3200 CFC2332G48TFS16B16S16M CFC2532G48TFS16B16S16M

    4000 CFC2340G51TFS17B17S17M CFC2540G51TFS17B17S17M

    5000 CFC2350G63TFS21B21S21M CFC2550G63TFS21B21S21M

    6000 CFC2360G63TFS21B21S21M CFC2560G63TFS21B21S21M

    Made tomeasure All CFC23GTFSBSM CFC25GTFSBSM

    =++

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 279

    800 279 279 279

    1000 279 279 279

    1250 279 279 279

    1350 305 305 305

    1600 305 305 305

    2000 305 305 305

    2500 356 356 356

    3000 381 381 381

    3200 406 406 406

    4000 432 432 432

    5000 533 533 5336000 533 533 533

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1219

  • 8/11/2019 I-LINE II Catalogue 2010

    45/113

    A

    B

    C

    43Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Double elbows

    Double left elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Made tomeasure

    630 CFC2306GDLBCSM CFC2506GDLBCSM800 CFC2308GDLBCSM CFC2508GDLBCSM1000 CFC2310GDLBCSM CFC2510GDLBCSM1250 CFC2312GDLBCSM CFC2512GDLBCSM1350 CFC2313GDLBCSM CFC2513GDLBCSM1600 CFC2316GDLBCSM CFC2516GDLBCSM2000 CFC2320GDLBCSM CFC2520GDLBCSM2500 CFC2325GDLBCSM CFC2525GDLBCSM3000 CFC2330GDLBCSM CFC2530GDLBCSM3200 CFC2332GDLBCSM CFC2532GDLBCSM4000 CFC2340GDLBCSM CFC2540GDLBCSM5000 CFC2350GDLBCSM CFC2550GDLBCSM6000 CFC2360GDLBCSM CFC2560GDLBCSM

    =++Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 178800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 203

    2500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    B

    C

    A

    Double right elbow

    Type Rating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Made tomeasure

    630 CFC2306GDRBCSM CFC2506GDRBCSM800 CFC2308GDRBCSM CFC2508GDRBCSM1000 CFC2310GDRBCSM CFC2510GDRBCSM1250 CFC2312GDRBCSM CFC2512GDRBCSM1350 CFC2313GDRBCSM CFC2513GDRBCSM1600 CFC2316GDRBCSM CFC2516GDRBCSM2000 CFC2320GDRBCSM CFC2520GDRBCSM2500 CFC2325GDRBCSM CFC2525GDRBCSM3000 CFC2330GDRBCSM CFC2530GDRBCSM3200 CFC2332GDRBCSM CFC2532GDRBCSM4000 CFC2340GDRBCSM CFC2540GDRBCSM5000 CFC2350GDRBCSM CFC2550GDRBCSM6000 CFC2360GDRBCSM CFC2560GDRBCSM

    =++

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 178800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 330

    5000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example:Generic catalogue number of 1000A double left elbow, 3L+N+PE:CFC2510GELM54

    Rating

    Rating

    Protection degree

    Protection degreeS - the elbow side without joint pak

    B - the elbow side with joint pakC or O - the straight feeder of the elbow

    - the total length of elbow- the length of the elbow side with joint pak- the length of straight feeder- the length of the elbow side without joint pak

    Discrete catalogue number of a 29 inch, 1000A double left elbow, 3L+N+PE:CFC2510G29DLB11C07S11M54

  • 8/11/2019 I-LINE II Catalogue 2010

    46/113

    A

    B

    C

    A

    B

    44 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Offset elbows

    Flatwise offset elbow

    Edgewise offset elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Made tomeasure

    630 CFC2306GOFSOBM CFC2506GOFSOBM800 CFC2308GOFSOBM CFC2508GOFSOBM1000 CFC2310GOFSOBM CFC2510GOFSOBM1250 CFC2312GOFSOBM CFC2512GOFSOBM1350 CFC2313GOFSOBM CFC2513GOFSOBM1600 CFC2316GOFSOBM CFC2516GOFSOBM2000 CFC2320GOFSOBM CFC2520GOFSOBM2500 CFC2325GOFSOBM CFC2525GOFSOBM3000 CFC2330GOFSOBM CFC2530GOFSOBM3200 CFC2332GOFSOBM CFC2532GOFSOBM4000 CFC2340GOFSOBM CFC2540GOFSOBM5000 CFC2350GOFSOBM CFC2550GOFSOBM6000 CFC2360GOFSOBM CFC2560GOFSOBM

    =++

    Type Rating (A)

    Cat. no3L+PE 3L+N+IGB

    Made tomeasure

    630 CFC2306GOESOBM CFC2506GOESOBM800 CFC2308GOESOBM CFC2508GOESOBM1000 CFC2310GOESOBM CFC2510GOESOBM1250 CFC2312GOESOBM CFC2512GOESOBM1350 CFC2313GOESOBM CFC2513GOESOBM1600 CFC2316GOESOBM CFC2516GOESOBM2000 CFC2320GOESOBM CFC2520GOESOBM2500 CFC2325GOESOBM CFC2525GOESOBM3000 CFC2330GOESOBM CFC2530GOESOBM3200 CFC2332GOESOBM CFC2532GOESOBM4000 CFC2340GOESOBM CFC2540GOESOBM5000 CFC2350GOESOBM CFC2550GOESOBM6000 CFC2360GOESOBM CFC2560GOESOBM

    =++

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 102800 279 279 1021000 279 279 1021250 279 279 1021350 305 305 1021600 305 305 1022000 305 305 1522500 356 356 2793000 381 381 3563200 406 406 4064000 432 432 4065000 533 533 5846000 533 533 635

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)All 279 279 152

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

  • 8/11/2019 I-LINE II Catalogue 2010

    47/113

    45Schneider Electric

    Cataloguenumbers

    Dimensions

    B

    A

    Catalogue numbers anddimensions

    Elbow plus Flanged end

    Flatwise elbow flanged end

    Edgewise elbow flanged end

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Made tomeasure

    630 CFC2306GLFFE*FM CFC2506GLFFE*FM800 CFC2308GLFFE*FM CFC2508GLFFE*FM1000 CFC2310GLFFE*FM CFC2510GLFFE*FM1250 CFC2312GLFFE*FM CFC2512GLFFE*FM1350 CFC2313GLFFE*FM CFC2513GLFFE*FM1600 CFC2316GLFFE*FM CFC2516GLFFE*FM2000 CFC2320GLFFE*FM CFC2520GLFFE*FM2500 CFC2325GLFFE*FM CFC2525GLFFE*FM3000 CFC2330GLFFE*FM CFC2530GLFFE*FM3200 CFC2332GLFFE*FM CFC2532GLFFE*FM4000 CFC2340GLFFE*FM CFC2540GLFFE*FM

    5000 CFC2350GLFFE*FM CFC2550GLFFE*FM6000 CFC2360GLFFE*FM CFC2560GLFFE*FM=+

    Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)

    630 204 279800 204 2791000 204 2791250 204 2791350 204 3051600 229 3052000 229 3052500 254 3563000 305 3813200 330 4064000 356 4325000 457 533

    6000 457 533Made to measure All min ~ 1219 min ~ 1219

    Type Rating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Made tomeasure

    630 CFC2306GLEFE*FM CFC2506GLEFE*FM800 CFC2308GLEFE*FM CFC2508GLEFE*FM1000 CFC2310GLEFE*FM CFC2510GLEFE*FM1250 CFC2312GLEFE*FM CFC2512GLEFE*FM1350 CFC2313GLEFE*FM CFC2513GLEFE*FM1600 CFC2316GLEFE*FM CFC2516GLEFE*FM2000 CFC2320GLEFE*FM CFC2520GLEFE*FM2500 CFC2325GLEFE*FM CFC2525GLEFE*FM3000 CFC2330GLEFE*FM CFC2530GLEFE*FM3200 CFC2332GLEFE*FM CFC2532GLEFE*FM4000 CFC2340GLEFE*FM CFC2540GLEFE*FM5000 CFC2350GLEFE*FM CFC2550GLEFE*FM6000 CFC2360GLEFE*FM CFC2560GLEFE*FM

    =+Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)

    630 152 279800 150 2791000 152 2791250 152 2791350 152 2791600 152 2792000 152 2792500 152 2793000 152 2793200 152 2794000 152 279

    5000 152 2796000 152 279

    Made to measure All min ~ 1219 min ~ 1219

  • 8/11/2019 I-LINE II Catalogue 2010

    48/113

    46 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Internal Grounding Elbows

    Flatwise Elbow

    Edgewise Elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    1a 1b

    Standard 630 CFC2606GG22LFIS11B11M CFC2506GG22LFOS11B11M800 CFC2608GG22LFIS11B11M CFC2508GG22LFOS11B11M1000 CFC2610GG22LFIS11B11M CFC2510GG22LFOS11B11M1250 CFC2612GG22LFIS11B11M CFC2512GG22LFOS11B11M1350 CFC2613GG24LFIS12B12M CFC2513GG24LFOS12B12M1600 CFC2616GG24LFIS12B12M CFC2516GG24LFOS12B12M2000 CFC2620GG24LFIS12B12M CFC2520GG24LFOS12B12M2500 CFC2625GG28LFIS14B14M CFC2525GG28LFOS14B14M3000 CFC2630GG30LFIS15B15M CFC2530GG30LFOS15B15M3200 CFC2632GG32LFIS16B16M CFC2532GG32LFOS16B16M4000 CFC2640GG34LFIS17B17M CFC2540GG34LFOS17B17M5000 CFC2650GG42LFIS21B21M CFC2550GG42LFOS21B21M6000 CFC2660GG42LFIS21B21M CFC2560GG42LFOS21B21M

    Made tomeasure

    All CFC26GGLFISBM CFC25GGLFOSBM

    =+

    Type Rating (A)

    Cat. no

    2a 2b

    Standard 630 CFC2606GG22LEIS11B11M CFC2506GG22LEOS11B11M800 CFC2608GG22LEIS11B11M CFC2508GG22LEOS11B11M1000 CFC2610GG22LEIS11B11M CFC2510GG22LEOS11B11M1250 CFC2612GG22LEIS11B11M CFC2512GG22LEOS11B11M1350 CFC2613GG22LEIS11B11M CFC2513GG22LEOS11B11M1600 CFC2616GG22LEIS11B11M CFC2516GG22LEOS11B11M2000 CFC2620GG22LEIS11B11M CFC2520GG22LEOS11B11M

    2500 CFC2625GG22LEIS11B11M CFC2525GG22LEOS11B11M

    3000 CFC2630GG22LEIS11B11M CFC2530GG22LEOS11B11M3200 CFC2632GG22LEIS11B11M CFC2532GG22LEOS11B11M4000 CFC2640GG22LEIS11B11M CFC2540GG22LEOS11B11M5000 CFC2650GG22LEIS11B11M CFC2550GG22LEOS11B11M6000 CFC2660GG22LEIS11B11M CFC2560GG22LEOS11B11M

    Made tomeasure

    All CFC26GGLEISBM CFC25**GGLEOSBM

    =+

    Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)

    630 279 279800 279 2791000 279 2791250 279 2791350 305 3051600 305 3052000 305 3052500 356 3563000 381 3813200 406 4064000 432 4325000 533 5336000 533 533

    Made to measure All min ~ 1219 min ~ 1219

    Flatwise elbows with made to measure angles

    Type Rating (A)

    Angle(W)

    3L+N+ING

    Ground bar inside Ground bar outside

    Standard(min)

    All 91 ~ 179 CFC26GGLFIOASBAM CFC26**GGLFOOASBAM

    =+,A=A+angle

    Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)All 279 279

    Made to measure All min ~ 1219 min ~ 1219

    EL1N

    L2L3

    EL1L2L3

    N

    B

    S

    B

    A

    1a

    EL1N

    L2L3

    EL1L2L3N

    B

    S

    A

    B

    1b

    EL1

    NL2

    L3

    EL1

    L2

    L3

    N

    CFC2608GG22LEIS11B11

    B

    S

    A

    B

    2a

    EL1

    N

    L2L3

    EL1L2L3

    N

    CFC2608GG22LEOS11B11

    B

    S

    A

    B

    2b

  • 8/11/2019 I-LINE II Catalogue 2010

    49/113

    47Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Internal Grounding Elbows

    Tee - Feeder

    Double left elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    3a 3b

    Made tomeasure

    630 CFC2606GGDLIBCSM CFC2606GGDLOBCSM800 CFC2608GGDLIBCSM CFC2608GGDLOBCSM1000 CFC2610GGDLIBCSM CFC2610GGDLOBCSM1250 CFC2612GGDLIBCSM CFC2612GGDLOBCSM1350 CFC2613GGDLIBCSM CFC2613GGDLOBCSM1600 CFC2616GGDLIBCSM CFC2616GGDLOBCSM2000 CFC2620GGDLIBCSM CFC2620GGDLOBCSM

    2500 CFC2625GGDLIBCSM CFC2625GGDLOBCSM

    3000 CFC2630GGDLIBCSM CFC2630GGDLOBCSM3200 CFC2632GGDLIBCSM CFC2632GGDLOBCSM4000 CFC2640GGDLIBCSM CFC2640GGDLOBCSM5000 CFC2650GGDLIBCSM CFC2650GGDLOBCSM6000 CFC2660GGDLIBCSM CFC2660GGDLOBCSM

    =++

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 279800 279 279 2791000 279 279 2791250 279 279 2791350 305 305 3051600 305 305 3052000 305 305 3052500 356 356 3563000 381 381 3813200 406 406 4064000 432 432 4325000 533 533 5336000 533 533 533

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1219

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 178800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    Type Rating Cata. no

    3L+N+ING

    Standard

    630 CFC2606GG33TFS11B11S11M800 CFC2608GG33TFS11B11S11M1000 CFC2610GG33TFS11B11S11M1250 CFC2612GG33TFS11B11S11M1350 CFC2613GG36TFS12B12S12M1600 CFC2616GG36TFS12B12S12M2000 CFC2620GG36TFS12B12S12M2500 CFC2625GG42TFS14B14S14M3000 CFC2630GG45TFS15B15S15M3200 CFC2632GG48TFS16B16S16M4000 CFC2640GG51TFS17B17S17M5000 CFC2650GG63TFS21B21S21M6000 CFC2660GG63TFS21B21S21M

    Made to measure All CFC26**GGTFSBSM=++

    EL1

    N L2L3

    EL1

    L2L3N

    CFC2608GG29DLIS11C07B11

    S

    B

    A

    C

    B

    3a

    CFC2608GG29DLIB11C07S11

    EL1

    NL2L3

    EL1

    L2

    L3

    N

    B

    S

    A

    C

    B

    3a

    CFC2608GG29DLOS11C07B11

    EL1

    N

    L2L3

    EL1

    L2

    L3

    N

    S

    B

    A

    C

    B

    3b

    CFC2608GG29DLOB11C07S11

    EL1N

    L2L3

    EL1

    L2

    L3

    N

    B

    S

    A

    C

    B

    3b

  • 8/11/2019 I-LINE II Catalogue 2010

    50/113

    48 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Internal Grounding Elbows

    Double Right elbow

    Flatwise offset elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    4a 4b

    Made tomeasure

    630 CFC2606GGDRIBCSM CFC2606GGDROBCSM800 CFC2608GGDRIBCSM CFC2608GGDROBCSM1000 CFC2610GGDRIBCSM CFC2610GGDROBCSM1250 CFC2612GGDRIBCSM CFC2612GGDROBCSM1350 CFC2613GGDRIBCSM CFC2613GGDROBCSM1600 CFC2616GGDRIBCSM CFC2616GGDROBCSM2000 CFC2620GGDRIBCSM CFC2620GGDROBCSM2500 CFC2625GGDRIBCSM CFC2625GGDROBCSM3000 CFC2630GGDRIBCSM CFC2630GGDROBCSM3200 CFC2632GGDRIBCSM CFC2632GGDROBCSM4000 CFC2640GGDRIBCSM CFC2640GGDROBCSM5000 CFC2650GGDRIBCSM CFC2650GGDROBCSM6000 CFC2660GGDRIBCSM CFC2660GGDROBCSM

    =++

    Type Rating (A)

    Cat. no

    6a 6b

    Made tomeasure

    630 CFC2606GGOFISOBM CFC2606GGOFOSOBM800 CFC2608GGOFISOBM CFC2608GGOFOSOBM1000 CFC2610GGOFISOBM CFC2610GGOFOSOBM1250 CFC2612GGOFISOBM CFC2612GGOFOSOBM1350 CFC2613GGOFISOBM CFC2613GGOFOSOBM1600 CFC2616GGOFISOBM CFC2616GGOFOSOBM2000 CFC2620GGOFISOBM CFC2620GGOFOSOBM

    2500 CFC2625GGOFISOBM CFC2625GGOFOSOBM

    3000 CFC2630GGOFISOBM CFC2630GGOFOSOBM3200 CFC2632GGOFISOBM CFC2632GGOFOSOBM4000 CFC2640GGOFISOBM CFC2640GGOFOSOBM5000 CFC2650GGOFISOBM CFC2650GGOFOSOBM6000 CFC2660GGOFISOBM CFC2660GGOFOSOBM

    =++

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 178800 279 279 1781000 279 279 1781250 279 279 1781350 305 279 2031600 305 279 2032000 305 279 2032500 356 279 2793000 381 279 2793200 406 279 3304000 432 279 3305000 533 279 4576000 533 279 457

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)

    630 279 279 102800 279 279 1021000 279 279 1021250 279 279 1021350 305 305 1021600 305 305 1022000 305 305 1522500 356 356 2793000 381 381 3563200 406 406 4064000 432 432 4065000 533 533 5846000 533 533 635

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    EL1L2L3N

    EL1

    NL2

    L3

    B

    S

    CFC2608GG29DRIB11C07S11

    C

    B

    A

    4a

    EL1

    N

    L2L3

    S

    EL1

    L2

    L3

    N

    B

    CFC2608GG29DRIS11C07B11

    AC

    B

    4a

    EL1N

    L2L3

    S

    CFC2608GG29DROS11C07B11

    C A

    4b

    EL1

    L2

    L3

    N

    B

    B

    B

    EL1N

    L2L3

    EL1

    L2

    L3

    N

    S

    CFC2608GG29DROB11C07S11

    AC

    B

    4b

    EL1

    N

    L2

    L3

    EL1

    N

    L2

    L3

    B

    S

    CFC2608GG26OFIS11O04B11

    A

    B

    C

    6a

    EL1

    N

    L2L3

    B

    S

    EL1

    N

    L2L3

    CFC2608GG26OFOS11O04B11

    A

    B

    C

    6b

  • 8/11/2019 I-LINE II Catalogue 2010

    51/113

    49Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Internal Grounding Elbows

    Edgewise offset elbow

    Flange end flatwise elbow

    I-LINE II Copper Busway

    Type Rating (A)

    Cat. no

    5a 5b

    Made tomeasure

    630 CFC2606GGOEISOBM CFC2606GGOEOSOBM800 CFC2608GGOEISOBM CFC2608GGOEOSOBM1000 CFC2610GGOEISOBM CFC2610GGOEOSOBM1250 CFC2612GGOEISOBM CFC2612GGOEOSOBM1350 CFC2613GGOEISOBM CFC2613GGOEOSOBM1600 CFC2616GGOEISOBM CFC2616GGOEOSOBM2000 CFC2620GGOEISOBM CFC2620GGOEOSOBM2500 CFC2625GGOEISOBM CFC2625GGOEOSOBM3000 CFC2630GGOEISOBM CFC2630GGOEOSOBM3200 CFC2632GGOEISOBM CFC2632GGOEOSOBM4000 CFC2640GGOEISOBM CFC2640GGOEOSOBM5000 CFC2650GGOEISOBM CFC2650GGOEOSOBM6000 CFC2660GGOEISOBM CFC2660GGOEOSOBM

    =++

    Type Rating (A)

    Cat. no

    7a 7b

    Made tomeasure

    630 CFC2606GGLFIFE*FM CFC2606GGLFOFE*FM

    800 CFC2608GGLFIFE*FM CFC2608GGLFOFE*FM

    1000 CFC2610GGLFIFE*FM CFC2610GGLFOFE*FM

    1250 CFC2612GGLFIFE*FM CFC2612GGLFOFE*FM1350 CFC2613GGLFIFE*FM CFC2613GGLFOFE*FM

    1600 CFC2616GGLFIFE*FM CFC2616GGLFOFE*FM

    2000 CFC2620GGLFIFE*FM CFC2620GGLFOFE*FM

    2500 CFC2625GGLFIFE*FM CFC2625GGLFOFE*FM

    3000 CFC2630GGLFIFE*FM CFC2630GGLFOFE*FM

    3200 CFC2632GGLFIFE*FM CFC2632GGLFOFE*FM

    4000 CFC2640GGLFIFE*FM CFC2640GGLFOFE*FM

    5000 CFC2650GGLFIFE*FM CFC2650GGLFOFE*FM

    6000 CFC2660GGLFIFE*FM CFC2660GGLFOFE*FM

    =+

    * = B or S. B - elbow side with joint pak, S - elbow side without joint pak

    Dimension

    Type Rating (A) Dimension (mm)

    A B C

    Standard (min)All 279 279 152

    Made to measure All min ~ 1219 min ~ 1219 min ~ 1016

    Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)

    630 204 279800 204 2791000 204 2791250 204 2791350 204 3051600 229 3052000 229 3052500 254 3563000 305 3813200 330 4064000 356 4325000 457 5336000 457 533

    Made to measure All min ~ 1219 min ~ 1219

    EL1

    N

    L2L3

    EL1

    N

    L2L3

    S

    B

    CFC2608GG28OEIS11O06B11

    A

    B

    C

    5a

    EL1

    N

    L2L3

    S

    B EL1

    N

    L2L3

    CFC2608GG28OEOS11O06B11

    A

    B

    C

    5b

    L1L2

    L3N

    E

    S

    EL1NL2L3

    CFC2608GG19LFIFES11F08

    B

    A

    7a

    L1L2

    L3N

    E

    B

    EL1N

    L2L3

    CFC2608GG19LFIFEB11F08

    B

    A

    7a

    S

    EL1

    NL2L3

    NL3

    L2L1

    E

    CFC2608GG19LFOFES11F08

    B

    A

    7b B

    EL1N

    L2L3

    NL3

    L2L1

    E

    CFC2608GG19LFOFEB11F08

    B

    A

    7b

  • 8/11/2019 I-LINE II Catalogue 2010

    52/113

  • 8/11/2019 I-LINE II Catalogue 2010

    53/113

  • 8/11/2019 I-LINE II Catalogue 2010

    54/113

    52 Schneider Electric

    Cataloguenumbers

    Dimensions

    Rating (A) Dimension (mm)

    S T U

    630 76 92 97

    800 76 92 97

    1000 76 92 97

    1250 76 92 97

    1350 76 92 97

    1600 76 92 97

    2000 76 92 97

    2500 127 169 173

    3000 127 169 173

    3200 127 169 173

    4000 127 169 173

    5000 127 169 173

    6000 127 169 173

    Rating (A) Figure Dimension (mm)

    A B C D

    630 1 64 - - -

    800 1 64 - - -

    1000 1 64 - - -

    1250 1 76 - - -1350 1 102 - - -

    1600 1 114 - - -

    2000 1 137 - - -

    2500 4 203 - - 127

    3000 2 114 289 60 -

    3200 2 127 353 99 -

    4000 2 152 378 73 -

    5000 3 114 565 111 -

    6000 3 152 604 73 -

    Rating (A) Catalogue No. No. of Pieces required per phase&neutral

    630 FLEX506 2

    800 FLEX508 2

    1000 FLEX510 3

    1250 FLEX512 3

    1350 FLEX513 4

    1600 FLEX516 4

    2000 FLEX520 5

    2500 FLEX525 7

    3000 FLEX530 8

    3200 FLEX532 8

    4000 FLEX540 105000 FLEX550 13

    6000 FLEX560 15

    Catalogue numbers anddimensions

    Flanged ends

    Figure 1

    4-pole with Earth Bus

    (Bottom View)

    4-pole with Earth Bus 3-pole with Earth Bus

    Flanged end termination details

    Physical Data

    Figure 2

    Figure 3 Figure 4

    I-LINE II Copper Busway

    Flexible link

    Flanged Collar

    G C B A G

    T T

    3-Pole(Bottom View)

    CL

    Flanged Collar

  • 8/11/2019 I-LINE II Catalogue 2010

    55/113

    53Schneider Electric

    Cataloguenumbers

    Dimensions

    Rating (A) Figure Dimension (mm)

    A B C D

    630 1 64 - - -

    800 1 64 - - -

    1000 1 64 - - -

    1250 1 76 - - -

    1350 1 102 - - -

    1600 1 114 - - -

    2000 1 137 - - -

    2500 4 165 - - 127

    3000 2 114 289 60 -

    3200 2 127 353 86 -5000 3 114 565 111 -

    6000 3 152 604 73 -

    Rating (A) Dimension (mm)

    A B X Y Z

    630 650 432 267 458 190

    800 650 432 267 458 190

    1000 650 432 267 458 190

    1250 650 432 267 458 190

    1350 650 432 267 458 190

    1600 650 432 267 458 190

    2000 650 432 267 458 190

    2500 650 445 279 458 190

    3000 650 533 364 458 190

    3200 650 584 428 458 190

    4000 650 610 453 458 1905000 650 813 641 458 190

    6000 650 838 679 458 190

    Catalogue numbers anddimensions

    Flanged ends

    Figure 1

    Figure 3

    Figure 2

    Figure 4

    I-LINE II Copper Busway

    Qwik Fange (Indoor Only)

    CL

    A

    D3271

    TypeRating (A)

    Cat. no

    3L+PE 3L+N+IGB

    Satandard

    630 CFC2306GQF CFC2506GQF

    800 CFC2308GQF CFC2508GQF

    1000 CFC2310GQF CFC2510GQF

    1250 CFC2312GQF CFC2512GQF

    1350 CFC2313GQF CFC2513GQF

    1600 CFC2316GQF CFC2516GQF

    2000 CFC2320GQF CFC2520GQF

    2500 CFC2325GQF CFC2525GQF

    3000 CFC2330GQF CFC2530GQF

    3200 CFC2332GQF CFC2532GQF

    4000 CFC2340GQF CFC2540GQF

    5000 CFC2350GQF CFC2550GQF

    6000 CFC2360GQF CFC2560GQF

    Note: please add the suffix Mfor higher protection degree. For example, CFC2508GQFM54

    CL

    A

    3271

    B

    CA A

    B

    A A AC C

  • 8/11/2019 I-LINE II Catalogue 2010

    56/113

    D

    54 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Cable Tap Box

    Type Rating(A)

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+IGB

    Standard all CFC23GETB*M CFC25GETB*M CFC26GGETB*M

    Made to

    measure

    630 CFC2306GETB*M CFC2506GETB*M CFC2606GGETB*M

    800 CFC2308GETB*M CFC2508GETB*M CFC2608GGETB*M

    1000 CFC2310GETB*M CFC2510GETB*M CFC2610GGETB*M

    1250 CFC2312GETB*M CFC2512GETB*M CFC2612GGETB*M

    1350 CFC2313GETB*M CFC2513GETB*M CFC2613GGETB*M

    1600 CFC2316GETB*M CFC2516GETB*M CFC2616GGETB*M

    2000 CFC2320GETB*M CFC2520GETB*M CFC2620GGETB*M

    2500 CFC2325GETB*M CFC2525GETB*M CFC2625GGETB*M

    3000 CFC2330GETB*M CFC2530GETB*M CFC2630GGETB*M

    3200 CFC2332GETB*M CFC2532GETB*M CFC2632GGETB*M

    4000 CFC2340GETB*M CFC2540GETB*M CFC2640GGETB*M

    5000 CFC2350GETB*M CFC2550GETB*M CFC2650GGETB*M

    6000 CFC2360GETB*M CFC2560GETB*M CFC2660GGETB*M

    Type Ampererating

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Standard all CFC23GETB*M CFC25GETB*M CFC26GGETB*M

    Cable Tap Box - End

    I-LINE II Copper Busway

    Cable Tap Box - Center

    Dimension

    Type Rating(A)

    Lugs perPH&N

    Earth lugs Dimension (mm)

    300 mm2 150 mm2 300 mm2 A B C D

    Standard(Min)

    630 3 3 - 740 279 406 254

    800 3 3 - 740 279 406 254

    1000 3 3 - 740 279 406 254

    1250 4 4 - 740 279 406 254

    1350 4 4 - 740 279 406 254

    1600 5 5 - 740 378 406 254

    2000 6 - 3 740 378 406 254

    2500 8 - 4 1000 530 660 254

    3000 9 - 5 1000 530 660 254

    3200 10 - 5 1000 530 660 254

    4000 12 - 6 1000 530 660 254

    5000 15 - 8 1000 756 660 254

    6000 17 - 9 1000 756 660 254

    Made tomeasure

    All min min min min ~ 1219

    Dimension

    Type Rating (A) Lugs perPH&N

    Earth lugs Dimension (mm)

    300 mm2 150 mm2 300 mm2 A B C D

    Standard(Min)

    630 3 3 - 889 356 406 185

    800 3 3 - 889 356 406 185

    1000 3 3 - 889 356 406 185

    1250 4 4 - 889 356 406 185

    1350 4 4 - 889 356 406 185

    1600 5 5 - 889 356 406 185

    2000 6 - 3 889 356 406 1852500 8 - 4 1059 508 447 261

    OrderingComplete the catalogue number by replacing by the rating and protection degree.

    Example:Generic catalogue number of 1000 A end cable tap box, 3L+N+PE:CFC2510GETBM54

    Discrete catalogue number example of a 10 inch, 1000A end cable tap box, 3L+N+PE:CFC2510G10ETBBM54

    Rating

    Rating *

    Protection degree

    Protection degree

    - the length of the straight feeder of end cable tap box

    *= B or S. B - with joint pak, S - without joint pak

    Note: please contact us for the ratings not shown above

  • 8/11/2019 I-LINE II Catalogue 2010

    57/113

    55Schneider Electric

    Cataloguenumbers

    Dimensions

    TL Type Feed units for dry-type transformers

    Feed units for dry-typetransformers

    OrderingComplete the catalogue number by replaceing by the rating and protectiondegree

    Example:Example: the catalogue number of a 3200A end feed unit , 3L+N+PECFC2532GFETM54

    Rating Protection degree

    Cat.no.

    3L+N+PE 3L+N+ING

    CFC25GFETM CFC26GFETM

    Notes: 1. Flexible links and Adapter box are not included. Please contactSchneider local office to order.

    Overall dimension

    Flange detail

    Rating Figure Dimensions(mm)

    (A) E N L Xe

    800 to 1250 1 290 to 473 94 to 197 1400 to 1900 63.5~127

    1350 to 2000 2 335 to 566 132 to 260 1570 to 2500 101~203

    2500 to 6000 3 436 to 728 233 to 350 1960 to 2800 101~203

    Dimension C is based on the position where the transformer located

    Rating Figure Dimensions(mm)

    (A)

    Rating Fig. Xp W1 W2800 1 63.5 98 71

    1000 1 63.5 98 71

    1200 1 76.2 110 83

    1350 2 101.6 136 109

    1600 2 114.3 148 121

    2000 2 137.2 171 144

    2500 3 203.2 237 210

    3000 3 203.2 323 296

    3200 3 203.2 387 360

    4000 3 203.2 412 385

    5000 3 254.0 599 572

    6000 3 305.0 638 611

    TT Type feed units for dry-type transformers

    Cat.no.

    3L+N+PE 3L+N+ING

    CFC25GFETM CFC26GFETM

    Earth

  • 8/11/2019 I-LINE II Catalogue 2010

    58/113

    56 Schneider Electric

    Cataloguenumbers

    Dimensions

    Angle brackets for TL & TT feed units flat

    Protective covers for feet units

    Feed units for dry-typetransformers

    Overall dimension

    Flange detail

    Rating Figure Dimensions(mm)

    (A) E N L Xe800 to 1250 figure 1 290 to 473 94 to 197 1146 to 1646 63.5~127

    1350 to 2500 figure 2 335 to 566 132 to 260 1316 to 2500 101~203

    3000 to 6000 figure 3 436 to 728 233 to 350 1706 to 2800 101~203

    Rating Figure Dimensions(mm)

    (A)

    Rating Fig. Xp W1 W2

    800 1 63.5 98 70

    1000 1 63.5 98 70

    1200 1 76.2 110 83

    1350 2 101.6 136 108

    1600 2 114.3 148 121

    2000 2 137.2 171 144

    2500 3 203.2 237 210

    3000 3 203.2 323 267

    3200 3 203.2 387 2924000 3 203.2 412 343

    5000 3 254.0 599 381

    6000 3 305.0 638 496

    Cat.no.

    3L+N+PE 3L+N+ING

    CFC25GFETM CFC26GFETM

    For dimensions,refer to TL or TT type.

    Protective covers will be designed in accordance with the way that end feet unit mounted on. Please contactSchneider for detail information.

    Earth

  • 8/11/2019 I-LINE II Catalogue 2010

    59/113

    57Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Supports and fixings

    Flatwisehorizontal hanger

    Edgewisehorizontal hanger

    Type Rating(A)

    Dimension (mm) Cat. no.

    A (mm) B (mm)

    Flatwise horizontal hanger 630 186 148 HF38F

    800 186 148 HF38F

    1000 186 148 HF38F

    1250 199 161 HF43F

    1350 225 186 HF53F

    1600 237 199 HF58F

    2000 260 222 HF67F

    2500 326 288 HF93F

    3000 412 374 HF13F

    3200 475 437 HF15F

    4000 501 463 HF16F

    5000 688 650 HF24F

    6000 726 688 HF25F

    Type Rating(A)

    Dimension (mm) Cat. no.

    A (mm)

    Edgewise horizontal hanger 630 212 HF43E

    800 212 HF43E

    1000 212 HF43E

    1250 212 HF43E1350 250 HF58E

    1600 250 HF58E

    2000 276 HF67E

    2500 339 HF93E

    3000 438 HF13E

    3200 501 HF15E

    4000 527 HF16E

    5000 714 HF24E

    6000 752 HF26E

    I-LINE II Copper Busway

  • 8/11/2019 I-LINE II Catalogue 2010

    60/113

    58 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Supports and fixings

    Vertical fixed hanger

    Vertical spring hanger

    Type Rating(A) Cat. no.

    Vertical Spring hanger 630 HFVS1

    800 HFVS1

    1000 HFVS1

    1250 HFVS1

    1350 HFVS1

    1600 HFVS2

    2000 HFVS2

    2500 HFVS2

    3000 HFVS8

    3200 HFVS8

    4000 HFVS8

    5000 HFVS8

    6000 HFVS8

    Type Rating(A) Cat. no.

    Vertical fixed hanger all HFV

    I-LINE II Copper Busway

  • 8/11/2019 I-LINE II Catalogue 2010

    61/113

    59Schneider Electric

    Cataloguenumbers

    Dimensions

  • 8/11/2019 I-LINE II Catalogue 2010

    62/113

    60 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Straight lengths

    Type Length L Cat. no.

    3L + PE 3L + N + IGB 3L + N + ING

    Fixed 10 Feet BFC23G10STM BFC25G10STM BFC26G10STM

    Made to measure16 inches ~119 inches BFC23G**STM BFC25G**STM BFC26G**STM

    Type Length Number of

    opening

    (Nos sides)

    Cta.no

    3L+PE 3L+N+IGB 3L+N+ING

    Plug-in 4 feet 12 BPC23G4S2M BPC25G4S2M BPC26G4S2M

    6 feet 12 BPC23G6S2M BPC25G6S2M BPC26G6S2M

    22 BPC23G6S4M BPC25G6S4M BPC26G6S4M

    10 feet 12 BPC23G10S2M BPC25G10S2M BPC26G10S2M

    22 BPC23G10S4M BPC25G10S4M BPC26G10S4M

    32 BPC23G10S6M BPC25G10S6M BPC26G10S6M

    Riser 4 feet 11 BRC23G4S1M BRC25G4S1M BRC26G4S1M

    6 feet 11 BRC23G6S1M BRC25G6S1M BRC26G6S1M

    21 BRC23G6S2M BRC25G6S2M BRC26G6S2M

    10 feet 11 BRC23G10S1M BRC25G10S1M BRC26G10S1M

    21 BRC23G10S2M BRC25G10S2M BRC26G10S2M

    31 BRC23G10S3M BRC25G10S3M BRC26G10S3M

    I-LINE II Copper Contact Busway

    Straight feeder lengths

    Straight lengths with plug-in openings

    OrderingComplete the catalogue number by replacing by the rating and protection

    degree.

    Example:Generic catalogue number of 1000A straight feeder, 3L+N+PE :

    BFC2510GM54

    Discrete catalogue number of a 10feet 1000A straight feeder, 3L+N+PE.

    BFC2510G10STM54

    Rating

    Rating**

    Protection degree

    Protection degree

    **= the length of the straight feeder. If the number is larger than 10, the unit is inch. otherwise,the unit is feet.

    Trunking cross-section

    Rating (A) Type 800 1000 1250 1350 1600 2000 2500 3200 4000 5000

    Weight

    (kg/m)

    3L + PE Feeder 13.0 14.2 15.9 16.5 18.0 20.5 28.4 33.2 44.8 50.4

    Plug-in 15.8 17.3 18.8 19.6 21.2 23.6 31.5 36.3 47.0 53.6

    3L + N + IGB Feeder 14.0 15.6 17.8 18.6 20.5 23.5 33.5 39.7 51.8 60.1

    Plug-in 17.2 18.8 21.0 21.7 23.7 26.6 36.6 42.8 55.0 63.2

    W(mm) 98 120 148 161 186 225 323 412 566 650

    Figure A A A A A A B B C C

  • 8/11/2019 I-LINE II Catalogue 2010

    63/113

    61Schneider Electric

    Cataloguenumbers

    Dimensions

    I-LINE II Copper Contact Busway

    Catalogue numbers anddimensions

    Straight length components

    Type Length(mm)

    Height(mm)

    Width (mm)

    800 1000 1250 1350 1600 2000 2500 3200 4000 5000

    Fixed 1016 508 343 343 343 343 442 442 492 594 819 819

    Phase transition

    Type Length(mm)

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Fixed 966 BFC23G38PTM BFC25G38PTM BFC26GG38PTM

    Type Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Fixed BFC23GEJM BFC25GEJM BFC26GEJM

    Bolt side

    Ampere Rating 400 630 800 1000 1250 1350 1600 2000 2500 3200 4000

    800 R04 R06 - - - - - - - -

    1000 R04 R06 R08 - - - - - - - -

    1250 R04 R06 R08 R10 - - - - - - -

    1350 - R06 R08 R10 R12 - - - - - -

    1600 - R06 R08 R10 R12 R13 - - - - -

    2000 - - R08 R10 R12 R13 R16 - - - -

    2500 - - - R10 R12 R13 R16 R20 - - -

    3200 - - - - R12 R13 R16 R20 R25 - -

    4000 - - - - - R13 R16 R20 R25 R32 -

    5000 - - - - - - R16 R20 R25 R32 R40

    Note: MCCB reducers are available. Contact us for details.

    Type Length(mm)

    Cat. no.

    3L+PE 3L+N+IGB 3L+N+ING

    Fixed 610 BFC23GRM BFC25GRM BFC26GRM

    Note: Replace R with below code. For example, BFC2520GR10M54.

    Unfused Reducer

    OrderingComplete the catalogue number by replacing by the rating and protection

    degree.

    Example:Generic catalogue number of 1000A expansion joint, 3L+N+PE :

    BFC2510GEJM54

    Discrete catalogue number of a standard 1000A expansion joint,3L+N+PE:

    BFC2510GEJM54

    Rating

    Rating

    Protection degree

    Protection degree

    Expansion Joint

    C

    N

    N

    C

  • 8/11/2019 I-LINE II Catalogue 2010

    64/113

    62 Schneider Electric

    Cataloguenumbers

    Dimensions

    Catalogue numbers anddimensions

    Straight length components

    I-LINE II Copper Contact Busway

    Wall and floor flange (WF)

    End closure

    Type Rating(A)

    Dimension (mm) Cat. no.

    A

    End closure 800 110 ACF38EC

    1000 132 ACF47EC

    1250 161 ACF58EC

    1350 174 ACF63EC

    1600 199 ACF73EC

    2000 237 ACF88EC

    2500 336 ACF13EC

    3200 425 ACF17EC

    4000 578 ACF22EC

    5000 663 ACF26EC

    Note: please add the suffix Mfor higher protection degree. For example, ACF38ECM54

    Rating(A)

    Straight Length Flanged End Cat. no

    A(mm) Y W Y W

    800 211 152 229 254 381 ACF38WF

    1000 233 174 229 276 381 ACF47WF

    1250 262 203 229 305 381 ACF58WF

    1350 275 203 229 330 381 ACF63WF

    1600 300 229 229 356 381 ACF73WF

    2000 338 279 229 432 533 ACF88WF

    2500 437 381 229 483 533 ACF13WF

    3200 526 457 229 584 533 ACF17WF

    4000 679 620 229 722 533 ACF22WF

    5000 764 711 229 813 533 ACF26WF

    Flatwise Elbow Wall thickness (mm)

    Rating(A)

    100 200 300 400 500 600

    W(mm) Y(mm)

    800 203 229 279 330 381 432 483

    1000 203 305 356 406 457 508 559

    1250 203 305 356 406 457 508 559

    1350 203 330 381 432 483 533 584

    1600 203 356 406 457 508 559 610

    2000 203 432 483 533 584 635 686

    2500 203 559 610 660 711 762 813

    3200 203 686 737 787 838 889 940

    4000 203 1016 1067 1118 1168 1219 1270

    5000 203 1016 1067 1118 1168 1219 1270

    Edgewise Elbow Wall thickness (mm)

    Rating(A)

    100 200 300 400 500 600

    Y(mm) W(mm)

    800 152 305 356 406 457 509 559

    1000 178 305 356 406 457 509 559

    1250 203 305 356 406 457 509 559

    1350 203 305 356 406 457 509 559

    1600 229 305 356 406 457 509 559

    2000 279 305 356 406 457 509 559

    2500 381 305 356 406 457 509 559

    3200 457 305 356 406 457 509 559

    4000 711 305 356 406 457 509 559

    5000 711 305 356 406 457 509 559

  • 8/11/2019 I-LINE II Catalogue 2010

    65/113

    63Schneider Electric

    Cataloguenumbers

    Dimensions

    OrderingComplete the catalogue number by replacing by the rating and protectiondegree.

    Example:Generic catalogue number of 1000A flatwise elbow, 3L+N+PE

    BFC2510GELM54

    Discrete catalogue number of a 24 inch, 1000A flatwise elbow, 3L+N+PE:

    BFC2510G24LFS13B11M54

    S - the elbow side without joint pakB - the elbow side with joint pak

    I-LINE II Copper Contact Busway

    Catalogue numbers anddimensions

    Elbows

    Type Rating(A)

    Cat. no

    3L+PE 3L+N+IGB 3L+N+ING

    Standard 800 BFC2308GLFM11M BFC2508GLFM11M BFC2608GLFM11M

    1000 BFC2310GLFM11M BFC2510GLFM11M BFC2610GLFM11M

    1250 BFC2312GLFM12M BFC2512GLFM12M BFC2612GLFM12M

    1350 BFC2313GLFM12M BFC2513GLFM12M BFC2613GLFM12M

    1600 BFC2316GLFM13M BFC2516GLFM13M BFC2616GLFM13M

    2000 BFC2320GLFM13M BFC2520GLFM13M BFC2620GLFM13M

    2500 BFC2325GLFM15M BFC2525GLFM15M BFC2625GLFM15M

    3200 BFC2332GLFM17M BFC2532GLFM17M BFC2632GLFM17M

    4000 BFC2340GLFM21M BFC2540GLFM21M BFC2640GLFM21M

    5000 BFC2350GLFM22M BFC2550GLFM22M BFC2650GLFM22M

    Made tomeasure

    All BFC23GLFSBM BFC25GLFSBM BFC26GLFSBM

    =+

    Dimension

    Type Rating (A) Dimension (mm)

    A B

    Standard (min)

    800 279 279

    1000 279 279

    1250 305 305

    1350 305 305

    1600 330 330

    2000 330 330

    2500 381 381

    3200