HYDROPLUSFlow rates up to: 195 m3/h
Head up to: 240 m CE
Max. operating pressure: 16 & 25 bar
Max. water temperature: H / V 70°C
VS 50°C
Max. ambient temperature: 40°C
ND of threaded manfolds: G2, G3
ND of flanged manifolds: ND 80 to 150
OPERATING LIMITS
N.T. No 143-1/ENG. - Ed4. /05-05
H
240
1950
m
1300
400
HYDROMODULES
HYDROPLUS
/hQm3
BOOSTERSRange of boosters fitted
with MULTi-V or MULTi-H pumps:Commercial and industrial use
2 pole - 50 Hz
Pressurizing and maintaining pressure ofwater distribution networks with insufficientor non existent pressure, in:- housing, office projects,- private residences,
- hotels, hospitals, clinics,- shopping centres, shops,- schools, high-schools, universities, barracks,- industrial and farm buildings,- irrigation, spraying…
• N-ALTi-VS405-3-CE-16-T4
• N-ALTi-VS...
• Wet rotor technology
• Silent-operation booster from 38 to 58 dB(A)
APPLICATIONS
• N-ALTi-H803-2-T4
• N-ALTi-V806-3-CA-16-T4
2
HYDROPLUS
ADVANTAGES DESIGN
ALTi-H. ALTi-V. ALTi-VS range
Compact boosters, specifically designed fordirect or standard booster systems equippedwith:
– Two or three MULTi-V or MULTi-H pumps,having predetermined hydraulic characteristics.
– Two suction-discharge pipes made of stainless: connections may be to the rightor left side as desired.
– Discharge and suction valves for eachpump.
– Silent-operation non-return discharge valvefor each pump fitted with interchangeablecartridges on the N-ALTi 2/4/8/16 range.
– An automatic pump control pressureswitch (CA-CV).
– A pressure transmitter (CV).– A dry-running pressure switch (town water
network version).– A dry-running float switch (version for
storage tank).– A pressure gauge.– A support and attachment frame
(dampers for ALTi-H version).– Lifting rings or holes for lifting bars.– A regulation box available in three
configurations:
CA: electromechanical with API (Automate Programmable)
CE: electronic
CV: variable speed control.
OPTION
- ELiNOX-V/H Version: 316 stainless steelversion .
- Boosters with 4 or more pumps, jockeypumps,…
• Compact modules, factory preset andready to install.
• Small ground space.
• Easy to install: 2 hydraulicconnections and one electricalconnection.
• Control and protection functions grouped in the cabinet assuringintegral automatic operation.
• N-ALTi 2/4/8/16 range non-returnvalve fitted with interchangeable cartridge. Easy to maintain.
• Stainless steel hydraulic system: reliable corrosion resistance andlonger life.
• Base protected by an electrolytictreatment ensuring excellent resistance to saline mist.
BOOSTER IDENTIFICATION - HYDROPLUS
N-ALTI-H D (regulator)N-ALTI-V 02 BP (by-pass)N-ALTI-VS 11 CA M (sleeves)N-ELINOX-H 03 CE V T2 V (Isolating valves)
N-ELINOX-V 1804 21 CV B T4 3 CB (counter flanges)
Codes for optional accessories (indicate in the order).
Tank code 3: state capacity and pressure.
Three-phase supply voltage - T2: TRI 230 V - T4: TRI 400 V.
Water supply - V: on town network - B: on tank (not supplied).
Control:
CA : electromechanical box with API
CE : electronic box
CV : speed controller box
N° of pumps 2 : 2 pumps in series in cascade
11 : 1 pump + 1 standby pump
3 : 3 pumps in cascade
21 : 2 pumps + 1 standby pump
Nominal flow-rate and number of stages
N-ALTi-H. V. VS : standard booster fitted with stainless steel 304 pump
N-ELiNOX-H. V : special all 316 stainless steel booster.
}
3
HYDROPLUS
BOOSTER DESCRIPTION
1 7 2
9 3 5
4 86
• N-ALTi-H
1 27
4 5 3
6
8
• N-ALTi-V / N-ALTi-VS
1 - Controller box
2 - Pumps (Type MULTi-H. MULTi-V or MULTi-VS)
3 - Suction manifold
4 - Discharge manifold
5 - Non return valve
6 - Isolating valves
7 - Pressure gauge
8 - Sensor
9 - Damping pads (for N-ALTi-H)
SUPPLIES
N-ALTi-H N-ALTi-V N-ALTi-VS
Components 2 pumps 3 pumps 2 pumps 3 pumps 2 pumps 3 pumps
Pumps MULTi-H 2 3 — — — —
Pumps MULTi-V — — 2 3 — —
Pumps MULTi-VS — — — — 2 3
Valves 4 6 4 6 4 6
Non return valves 2 3 2 3 2 3
Stainless steel manifolds 2 2 2 2 2 2
Pressure switch (CA.CE) - Transmitter (CV) 1 1 1 1 1 1
Pressure switch
Dry running (for V version)
protection Float1 1 1 1 1 1
(for B version )
Pressure gauge 1 1 1 1 1 1
Controller box 1 1 1 1 1 1
Damping pads 4 4 — — — —
Base plate 1 1 1 1 1 1
Standards and specifications:
• Machines Directive 98/37/CE. • Electromagnetic compatibility Directive
89/336/CEEmod.• Low Voltage Directive: 73/23/CEEmod.
• CEI 60364 (NFC 15-100) (Electrical).• EN 61800-3 (Adjustable speed electrical
power drive systems).• EN 809 – Pumps and motor-pump units
for liquids.
• EN 61000-6 – 1 & 3 or EN 61000-6 2& 4 (Immunity / Emission).
• EN 60204-1 (Machines safety). EN 60034-1 (Rotating electrical machines).EN 60439-1 (Electric and electronic box).
4
HYDROPLUS
SUPPLIES
Example with a 3-pump Hydroplus.
Same representation with a 2-pump
Hydroplus.
“V” VERSION
FROM THE PUBLIC WATER SYSTEM
“B” VERSION
FROM A STORAGE TANK(in charge)
2
8
10
Code 3
BP CB V M D
4 3
5
3
1
6
5
7
10
9
11
Code 3
STANDARD SUPPLIES (1 to 9) :
1 - Two or three multistage pumps.
2 - Support frame.
3 - Cutoff valves at pump suction anddischarge.
4 - Check valve at pump discharge.
5 - Suction-discharge manifolds.
6 - Pressure transmitter.
7 - Control and protection panel.
COMPULSORY SUPPLIES:(according to the booster’s water supply).
08 - Dry running protection pressureswitch,supplied fitted, booster suppliedwith city water (included in the price),or
09 - Float switch, supplied not fitted,booster supplied on charged tank(included in the price).
10 - CODE 3 bladder vessel, 100 to2000 liter, specify operating pressureand capacity (option priced separately).
11 - Balance piping for suction tank.
OPTIONAL SUPPLIES:(options priced separately).
BP - Direct water supply bypass when thepublic water system pressure isinsufficient. (comes fitted if ordered).
M - Anti-vibration sleeves (supplied by 2).
CB - Counterflanges to be screwed or weldedonto the manifolds (supplied by 2).
D - Pressure regulator-stabilizer for suctionand/or discharge.
V - Isolating valves.
NB: when a bypass and an suction pressure regulator are fitted onto the booster, we recommend fitting the pressure regulator between the bypass and the booster.
OPERATING LIMITS
Flow rates up to: 3 pumps version 80 m3/h
4 pumps version *105 m3/h
Max. head: 70m (NP10)
Max. operating pressure: 10 bar
Max. inlet pressure: 4 bar
Max. water temperature: ALTi-H 70°C
Max. ambient temperature: 40°C
ND of threaded manfolds: G2, G21/2
Flow rates up to: 3 pumps version 195 m3/h
4 pumps version *260 m3/h
Max. head: 150m (NP16) - **230m (NP25)
Max. operating pressure: 25 bar
Max. inlet pressure: 10 bar
Max. water temperature: ALTi-V 70°C
Max. ambient temperature: 40°C
ND of threaded manfolds: G2, G21/2
ND of flanged manifolds: DN 80 to 150
Flow rates up to: 3 pumps version 42 m3/h
4 pumps version *56 m3/h
Max. head: 110m (NP16)
Max. operating pressure: 16 bar
Max. inlet pressure: 6 bar
Max. water temperature: ALTi-VS 50°C
Max. ambient temperature: 40°C
ND of threaded manfolds: G2, G21/2
NB: An ALTi-VS should be installed on a public water supplyor flooded on a storage tank with a water height > 0.5 mabove the pump.
• N-ALTi-H 2,4,8,16 • N-ALTi-V 2,4,8,16,18,36,60 • N-ALTi-VS 2,4,8
H
70
800
m
*105
HYDROPLUS-H
/hQm3
H
150
1950
m
*260
**230
HYDROPLUS-V
/hQm3
H
110
420
m
*56
HYDROPLUS-S
/hQm3
5
HYDROPLUS
CONTROL AND REGULATION: A STANDARDISED PANEL
CONTROL PANEL COMMON TO THE THREE
UNITS WITH:
➊ – Switch per pump: automatic
start/stop/forced start (transient).
➋ – Indicator: on per pump.
➌ – Indicator: pump fault per pump.
➍ – Indicator: dry running
➎ – Indicator: module powered up.
➏ – Booster type.
SPEED VARIATION CHARACTERISTICS
17 – Embossed key: varied pump rearming.
18 – Indicator: varied pump fault.
19 – Embossed key: rearm, variable speed
controller.
10 – Indicator: variable speed controller fault.
11 – Switch: variable speed controller.
ELECTROMECHANICAL BOX WITH PLC (CA) : DESCRIPTION AND OPERATION
Complies with NF C15-100 and CE
standards in force
– Leaktightness: protection index IP 54.
Power supply:
Three-phase: 230/400V (50 Hz)
220 /380 V (60 Hz option)
Single-phase: (optional)
230 V (50 Hz)
220/240 V (60 Hz)
DESCRIPTION: (2 or 3 pumps).
Front panel:
– Control and display panel.
– Safety and mains power rotary switch.
Inside:
– Magneto-thermal circuit breakers with
motor intensity adjustment switch (and
reset button) for pump(s).
– Pump contactors with motor connection
terminals.
– Safety switch controlled from the outside
via lockable handle.
– 24-230 V safety transformer.
– Control power supply protection fuses.
– External control unit connection terminal
strip (pressure switch, float switch, remote
control, etc).
– Programmable controller.
OPERATION
The pumps are operated by a neutral range
pressure switch (low pressure and high
pressure).
On detection of a low pressure, a first timer
“T1M” is activated. If after ”T1M” the pressu-
re remains low, the pump “P1” is activated
and a timer “T2M”. After “T2M”, the pump
“P2” is activated and a timer “T3M” in a 3
pump version. After “T3M”, the pump “P3” is
activated.
If the flow rate is adequate (between low
pressure and high pressure levels) none of
the pumps are started up.
If the high pressure level is reached, the
timers “T1A”, “T2A” and “T3A” are activated
to stop the pumps in the same way in which
they are started.
If the flow rate is adequate, the pumps in
operation are not stopped.
When the last pump has stopped, a cyclical
change-over takes place when the pumps
start up again.
After dry running has been detected, a
“TME-ON” timer is activated and the pumps
are stopped when the time elapses.
Restarting is only permitted once the water
has returned to an adequate level and a
second “TME-OFF” timer has run out.
If there is a fault in one of the pumps, the
machine automatically switches to one of
the remaining valid pumps.
NB
On all booster models (2 and 3 pumps)
the pump starting order after stopping is
permuted.
7 8 9 10 11
➊ ➋ ➌ ➍ ➎ ➏
6
HYDROPLUS
VARIABLE SPEED BOX : DESCRIPTION AND OPERATION
Complies with NF C15-100 and CE
standards in force
– Leaktightness: guard index IP 559.
Power supply
Three-phase: 230/400V (50 Hz)
220 /380 V (60 Hz-option)
Single phase: (optional)
230 V (50 Hz)
220/240 V (60 Hz)
DESCRIPTION: (one varied pump and one
or two fixed pumps).
Front panel:
– Control and display panel.
– Regulator panel.
– Key-operated lock.
– Safety and mains power rotary switch.
Inside:
– Magneto-thermal circuit breaker with
motor intensity adjusting switch (and reset
button) for fixed pump(s).
– Contactor (one per pump).
– 24 V safety transformer.
– Electrical connection terminal strip.
– Main disconnect switch controlled from the
outside via lockable handle.
– Pump start and stop timer (adjustable).
– Last pump hold-in timer (adjustable).
– Change-over clock.
– Set of HPC three-pole circuit breakers.
– External control unit connection terminal
strip (pressure switch, float switch, remote
control, etc).
– Relay module.
– Speed variator.
ELECTRONIC BOX: DESCRIPTION AND OPERATION
Complies with NF C15-100 and CE
standards in force
– Leaktightness: guard index IP 54.
Power supply
Three-phase: 230/400V (50 Hz)
220 /380 V (60 Hz-option)
Single-phase: (optional)
230 V (50 Hz)
220/240 V (60 Hz)
DESCRIPTIF : (2 or 3 pumps).
Front panel:
– Control and display panel.
– Safety and mains power rotary switch.
Inside:
– Pump protection thermal relay with motor
connection terminals.
– Pump contactors.
– Safety switch with power supply network
connection terminals.
– 230 or 400 V protection and voltage
selection fuse.
– Control unit low voltage power supply 12 V
transformer.
– Motor thermal protection potentiometers
(max I: 32 A/pump).
– Connectors receiving the indicator light
and timer power supply contact pin.
– External control unit connection terminal
strip (pressure switch, float switch, remote
control, etc).
OPERATION
Booster operation is assured by two simple
pressure switches, in the 2-pump version
and by a neutral range pressure switch in
the 3 or more pump version.
Otherwise, the operating principle is the
same as for the electromechanical unit.
The automatic system and connection block
can accept a remote control unit.
OPERATION
The pressure transmitter records the pressure
in the discharge line and sends signals to the
regulator. If the pressure becomes lower than
the set-point value, the regulator signals the
variable speed controller to increase the
speed of the controlled or “varied” pump.
• If the varied pump reaches its maximum
speed of rotation whilst the pressure is still
too low, the regulator starts pump “P2” at a
fixed speed; the speed of “P1” is adjusted to
keep the chosen set-point value. If the
accumulated flow-rate of “P1” and “P2” is not
enough, “P3” (3-pump HYDROPLUS) is
started in the same way.
• If the pressure gets too high, the regulator
adjusts “P1” to the minimum chosen speed
and if the pressure is still too high, it stops the
last fixed-speed pump that was turned on.
• Then “P1” is put back at its maximum
speed before being reduced to the minimum
speed, then the last but one fixed-speed
pump is stopped (if necessary) and so on
until the set-point value is reached.
NB:
On all booster models (2 and 3 pumps) the
pump starting order after stopping is
permuted.
7
HYDROPLUS
ELECTRICAL DATA
TYPE P2 Total installed Max. service Voltage Total
motor power in kW pressure current
2 PUMPS - Box CA. CE or CV - City or Tank
N-ALTi-H203-2...T4 2x 0.55 10 bar 400V-3~50 Hz 3.4A
N-ALTi-H204-2...T4 2x 0.55 10 bar 400V-3~50 Hz 3.4A
N-ALTi-H205-2...T4 2x 0.75 10 bar 400V-3~50 Hz 4.2A
N-ALTi-H206-2...T4 2x 1.1 10 bar 400V-3~50 Hz 6.2A
N-ALTi-H403-2...T4 2x 0.55 10 bar 400V-3~50 Hz 3.4A
N-ALTi-H404-2...T4 2x 0.75 10 bar 400V-3~50 Hz 4.2A
N-ALTi-H405-2...T4 2x 1.1 10 bar 400V-3~50 Hz 6.2A
N-ALTi-H406-2...T4 2x 1.5 10 bar 400V-3~50 Hz 7.6A
N-ALTi-H803-2...T4 2x 1.1 10 bar 400V-3~50 Hz 6.2A
N-ALTi-H804-2...T4 2x 1.5 10 bar 400V-3~50 Hz 7.6A
N-ALTi-H805-2...T4 2x 1.85 10 bar 400V-3~50 Hz 9.9A
N-ALTi-H1602-2...T4 2x 1.5 10 bar 400V-3~50 Hz 7.6A
N-ALTi-H1603-2...T4 2x 1.85 10 bar 400V-3~50 Hz 9.9A
N-ALTi-H1604-2...T4 2x 2.5 10 bar 400V-3~50 Hz 11.7A
3 PUMPS - Box CA. CE or CV - City or Tank
N-ALTi-H203-3...T4 3x 0.55 10 bar 400V-3~50 Hz 5.1A
N-ALTi-H204-3...T4 3x 0.55 10 bar 400V-3~50 Hz 5.1A
N-ALTi-H205-3...T4 3x 0.75 10 bar 400V-3~50 Hz 6.3A
N-ALTi-H206-3...T4 3x 1.1 10 bar 400V-3~50 Hz 9.3A
N-ALTi-H403-3...T4 3x 0.55 10 bar 400V-3~50 Hz 5.1A
N-ALTi-H404-3...T4 3x 0.75 10 bar 400V-3~50 Hz 6.3A
N-ALTi-H405-3...T4 3x 1.1 10 bar 400V-3~50 Hz 9.3A
N-ALTi-H406-3...T4 3x 1.5 10 bar 400V-3~50 Hz 11.4A
N-ALTi-H803-3...T4 3x 1.1 10 bar 400V-3~50 Hz 9.3A
N-ALTi-H804-3...T4 3x 1.5 10 bar 400V-3~50 Hz 11.4A
N-ALTi-H805-3...T4 2x 1.85 10 bar 400V-3~50 Hz 14.9A
N-ALTi-H1602-3...T4 3x 1.5 10 bar 400V-3~50 Hz 11.4A
N-ALTi-H1603-3...T4 3x 1.85 10 bar 400V-3~50 Hz 14.9A
N-ALTi-H1604-3...T4 3x 2.5 10 bar 400V-3~50 Hz 17.6A
TYPE P2 Total installed Max. service Voltage Total current Total current
motor power in kW pressure 2 pumps 3 pumps
2 or 3 PUMPS - Box CA. CE or CV - City or TankN-ALTi-V203-2 or 3 pumps...T4 2 or 3x 0.55 16 bar 400V-3~50 Hz 2.7A 3.9AN-ALTi-V204-2 or 3 pumps...T4 2 or 3x 0.75 16 bar 400V-3~50 Hz 3.4A 5.0AN-ALTi-V205-2 or 3 pumps...T4 2 or 3x 0.75 16 bar 400V-3~50 Hz 3.4A 5.0AN-ALTi-V206-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V207-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V208-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V210-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V212-2 or 3 pumps...T4 2 or 3x 1.85 16 bar 400V-3~50 Hz 8.0A 11.7AN-ALTi-V403-2 or 3 pumps...T4 2 or 3x 0.75 16 bar 400V-3~50 Hz 3.4A 5.0AN-ALTi-V404-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V405-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V406-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V407-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V408-2 or 3 pumps...T4 2 or 3x 1.85 16 bar 400V-3~50 Hz 8.0A 11.7AN-ALTi-V410-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V412-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V803-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V804-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V805-2 or 3 pumps...T4 2 or 3x 1.85 16 bar 400V-3~50 Hz 7.8A 11.7AN-ALTi-V806-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V807-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V808-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V810-2 or 3 pumps...T4 2 or 3x 3.7 16 bar 400V-3~50 Hz 15.6A 23.4AN-ALTi-V811-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V812-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21.6A 31.5AN-ALTi-V1603-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V1604-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V1605-2 or 3 pumps...T4 2 or 3x 3.7 16 bar 400V-3~50 Hz 15.6A 23.4AN-ALTi-V1606-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V1607-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21.6A 32.4AN-ALTi-V1608-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21.6A 32.4AN-ALTi-V1609-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V1610-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V1802-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V1803-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V1804-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V1805-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V1806-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V1807-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V1808-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V3602-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V3603-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V3604-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V3605-2 or 3 pumps...T4 2 or 3x 9 16 bar 400V-3~50 Hz 34A 51AN-ALTi-V3606-2 or 3 pumps...T4 2 or 3x 11 16 bar 400V-3~50 Hz 40A 60AN-ALTi-V3607-2 or 3 pumps...T4 2 or 3x 15 16 bar 400V-3~50 Hz 53A 79.5AN-ALTi-V6002-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V6003-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V6004-2 or 3 pumps...T4 2 or 3x 11 16 bar 400V-3~50 Hz 40A 60AN-ALTi-V6005-2 or 3 pumps...T4 2 or 3x 15 16 bar 400V-3~50 Hz 53A 79.5AN-ALTi-V6006-2 or 3 pumps...T4 2 or 3x 15 16 bar 400V-3~50 Hz 53A 79.5AN-ALTi-V6007-2 or 3 pumps...T4 2 or 3x 18.5 16 bar 400V-3~50 Hz 66A 99A
TYPE P1 Total installed Max. service Voltage Total current Total current
motor power in kW pressure at TRI 230V at TRI 400V2 PUMPS - Box CA. CE or CV - City or Tank
N-ALTi-VS202-2 or 3 pumps...T4 2 or 3x 0.51 16 bar 400V-3~50 Hz 2 or 3x 2.1A 2 or 3x 1.2AN-ALTi-VS203-2 or 3 pumps...T4 2 or 3x 0.72 16 bar 400V-3~50 Hz 2 or 3x 2.6A 2 or 3x 1.5AN-ALTi-VS204-2 or 3 pumps...T4 2 or 3x 0.88 16 bar 400V-3~50 Hz 2 or 3x 3A 2 or 3x 1.7AN-ALTi-VS205-2 or 3 pumps...T4 2 or 3x 1.2 16 bar 400V-3~50 Hz 2 or 3x 4.51A 2 or 3x 2.6AN-ALTi-VS206-2 or 3 pumps...T4 2 or 3x 1.38 16 bar 400V-3~50 Hz 2 or 3x 4.9A 2 or 3x 2.8AN-ALTi-VS207-2 or 3 pumps...T4 2 or 3x 1.53 16 bar 400V-3~50 Hz 2 or 3x 5.2A 2 or 3x 3AN-ALTi-VS208-2 or 3 pumps...T4 2 or 3x 1.69 16 bar 400V-3~50 Hz 2 or 3x 5.6A 2 or 3x 3.2AN-ALTi-VS209-2 or 3 pumps...T4 2 or 3x 2.14 16 bar 400V-3~50 Hz 2 or 3x 8A 2 or 3x 4.6AN-ALTi-VS210-2 or 3 pumps...T4 2 or 3x 2.33 16 bar 400V-3~50 Hz 2 or 3x 8.5A 2 or 3x 4.9AN-ALTi-VS402-2 or 3 pumps...T4 2 or 3x 0.69 16 bar 400V-3~50 Hz 2 or 3x 2.6A 2 or 3x 1.5AN-ALTi-VS403-2 or 3 pumps...T4 2 or 3x 1.02 16 bar 400V-3~50 Hz 2 or 3x 4.2A 2 or 3x 2.4AN-ALTi-VS404-2 or 3 pumps...T4 2 or 3x 1.26 16 bar 400V-3~50 Hz 2 or 3x 4.5A 2 or 3x 2.6AN-ALTi-VS405-2 or 3 pumps...T4 2 or 3x 1.48 16 bar 400V-3~50 Hz 2 or 3x 5.2A 2 or 3x 3AN-ALTi-VS406-2 or 3 pumps...T4 2 or 3x 1.7 16 bar 400V-3~50 Hz 2 or 3x 5.6A 2 or 3x 3.2AN-ALTi-VS407-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 2 or 3x 8A 2 or 3x 4.6AN-ALTi-VS408-2 or 3 pumps...T4 2 or 3x 2.4 16 bar 400V-3~50 Hz 2 or 3x 8.5A 2 or 3x 4.9AN-ALTi-VS409-2 or 3 pumps...T4 2 or 3x 2.69 16 bar 400V-3~50 Hz 2 or 3x 9.2A 2 or 3x 5.3AN-ALTi-VS410-2 or 3 pumps...T4 2 or 3x 2.94 16 bar 400V-3~50 Hz 2 or 3x 9.7A 2 or 3x 5.6AN-ALTi-VS802-2 or 3 pumps...T4 2 or 3x 1.25 16 bar 400V-3~50 Hz 2 or 3x 4.5A 2 or 3x 2.6AN-ALTi-VS803-2 or 3 pumps...T4 2 or 3x 1.6 16 bar 400V-3~50 Hz 2 or 3x 5.4A 2 or 3x 3.1AN-ALTi-VS804-2 or 3 pumps...T4 2 or 3x 1.95 16 bar 400V-3~50 Hz 2 or 3x 6.3A 2 or 3x 3.6AN-ALTi-VS805-2 or 3 pumps...T4 2 or 3x 2.67 16 bar 400V-3~50 Hz 2 or 3x 9.2A 2 or 3x 5.3AN-ALTi-VS806-2 or 3 pumps...T4 2 or 3x 2.98 16 bar 400V-3~50 Hz 2 or 3x 9.7A 2 or 3x 5.6A
To 2900 RPM
8
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-H - 2900 RPM - 200 AND 400 SERIES
Imp.gpmHftHm
70
60
50
40
30
20
10
0
60
40
20
0
206
205
204
203
η %
5 10 15
200
150
100
50
0
N-ALTi-H 200
2 POLE - 50Hz
Qm /h3 1 2 3 4
Qm /h3 1 2 3 4
Qm /h3 1 2 3 4
1
2 3 4 5 6 7 8 92
3 6 9 123
6
4
2
0
mNPSH
Number of pumps
Qm /h3
Qm /h3
70
60
50
40
30
20
10
0
60
40
20
0
406
405
404
403
200
150
100
50
0
10 15 20 25
6
4
2
01 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2 4 6 128 10 14 16
3 6 9 2115 18 2412
N-ALTi-H 400
2 POLE - 50Hz
Imp.gpmHftHm
η %
Qm /h3
Qm /h3
Qm /h3
1
2
3
m
NPSH
Number of pumps
Qm /h3
Qm /h3
9
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-H - 2900 RPM - 800 AND 1600 SERIES
50
40
30
20
10
20
0
80
60
40
0
4
3
1
2
0
20 30 40 50
25
50
60
100
125
150
175
0
803
804
805
2 1210 144 6 8
2 1210 144 6 8
2 1210 144 6 8
84 12 16 20 24 28
126 2418 30 4236
N-ALTi-H 800
2 POLE - 50Hz
Imp.gpmHftHm
η %
Qm /h3
Qm /h3
Qm /h3
mNPSH
Number of pumps
Qm /h3
Qm /h3
1
2
3
55
50
45
40
35
15
5
60
40
20
0
2,0
2,5
1,5
0
6
4
2
0
m
NPSH 1604
η % (1603)
30
25
20
10
0
180
160
140
120
100
20
40
60
80
4 8 12 16 20 24 28 32
4 8 12 16 20 24 28 32
4 8 12 16 20 24 28 32
80
0,5
1,0
8 16 24 32 40 48 56 64
12 24 36 48 60 72 84 96
1604
1603
1602
1602
1603
1604
0
10080604020
N-ALTi-H 1600
2 POLE - 50Hz
Imp.gpmHftHm
Qm /h3
Qm /h3
Qm /h3
NPSH
Number of pumps
Qm /h3
Qm /h3
1
2
3
%
kW
10
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 200 AND 400 SERIES
220
200
4
180
160
140
120
100
80
60
40
20
0
80
60
40
20
4
3
1
2
0
0
217*
214*
212
210
208
207
206
205
204
203
220*
700
600
500
400
300
200
100
0
6 8 10 12 14
1 1,5 2,5 3,5 4,52 3 4
1 1,5 2,5 3,5 4,52 3 4
1 1,5 2,5 3,5 4,52 3 4
2 3 4 5 6 7 8 9
3 4,5 7,56 10,5 13,59 12
N-ALTi-V 200
2 POLE - 50Hz
Imp.gpmHftHm
η %
Qm /h3
Qm /h3
Qm /h3
1
2
3
m
NPSH
Number of pumps
Qm /h3
Qm /h3
220
200
10 15 20 25
180
160
140
120
100
80
60
40
20
0
80
60
40
20
2
3
4
1
0
0
419*
417*
414*
412
410
408
407
406
405
404
403100
200
300
400
500
600
700
0
1 76 82 3 4 5
1 76 82 3 4 5
1 76 82 3 4 5
42 6 8 10 12 14 16
64 129 18 2415 21
N-ALTi-V 400
2 POLE - 50Hz
Imp.gpmHftHm
η %
Qm /h3
Qm /h3
Qm /h3
1
2
3
m
NPSH
Number of pumps
Qm /h3
Qm /h3
11
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 800 AND 1600 SERIES
220
200
180
160
140
120
100
80
60
40
20
20
0
80
60
40
0
4
3
1
2
0
819*
817*
814*
812
811
810
808
806805
804
803
807
20 30 40 50
100
200
300
400
500
600
700
0
2 1210 144 6 8
2 1210 144 6 8
2 1210 144 6 8
84 12 16 20 24 28
126 2418 30 4236
N-ALTi-V 800
2 POLE - 50Hz
Imp.gpmHftHm
η %
Qm /h3
Qm /h3
Qm /h3
1
2
3
m
NPSH
Number of pumps
Qm /h3
Qm /h3
24
6
5
7
4
3
2
1
0
10
0
20
30
40
50
60
70
80
90
100
110
120
50
0
100
150
200
250
300
350
400
36 48 60 72 84 96 108
1602
16021603160416051606160716081609
16111610
1603
1604
1605
1606
1609
1610
1611
40
200
60
80
20
4
61611
5 10 15 20 25 30
5 10 15 20 25 30
5 10 15 20 25 30
6010 20 30 40 50
9015 30 45 60 75
1608
1607
N-ALTi-V 1600
2 POLE - 50Hz
Imp.gpmHftHm
Qm /h3
Qm /h3
Qm /h3
NPSH
Number of pumps
Qm /h3
Qm /h3
1
2
3
%
kW
m
η %
12
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 1800 AND 3600 SERIES
Imp.gpmHftHm
Qm /h31
2
3
m ft
kW
Number of pumps
Qm /h3
Qm /h3
N-ALTi-V 1800
2 POLE - 50Hz
%
η %
NPSH
140
120
100
80
60
40
20
20
40
60
80
0
0
2
4
6
8
0
1808
1807
1806
1805
1804
1803
1802100
200
300
400
0
0,8
25
15
8
4 6 8 10 12 14 16 18 20 22 24 26
Qm /h3 4 6 8 10 12 14 16 18 20 22 24 26
Qm /h3 4 6 8 10 12 14 16 18 20 22 24 26
8 12 16 20 24 28 32 36 40 44 48 52
12 18 24 30 36 42 48 54 60 66 72 78
0
0,6
0,4
0,2
0
25 37,5 50 62,5 75 87,5
kW
Imp.gpmHftHm
N-ALTi-V 3600
2 POLE - 50Hz
140
120
100
80
60
40
20
0
100
200
300
400
0
50 75 100 125 150 175
Qm /h31
2
3
m ft
kW
Number of pumps
Qm /h3
Qm /h3
%
η %
NPSH
20
40
60
80
0
0
2
4
6
8
1,6
25
15
8
8 12 16 20 24 28 32 36 40 44 48 52
Qm /h3 8 12 16 20 24 28 32 36 40 44 48 52
Qm /h3 8 12 16 20 24 28 32 36 40 44 48 52
16 24 32 40 48 56 64 72 80 88 96 104
24 36 48 60 72 84 96 108 120 132 144 156
0
1,2
0,8
0,4
0
kW
3602
3603
3604
3605
3606
3607
13
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 6000 SERIES
Imp.gpmHftHm
Qm /h3
NPSH
Number of pumps
Qm /h3
Qm /h3
1
2
3
%
kW
m
η %
N-ALTi-V 6000
2 POLE - 50Hz180
0
20
60
40
20
20
15
10
5
0
0
40
60
80
100
120
140
160
600
500
400
300
200
100
0
6
4
20
50 100 150 200
6009
6008
6007
6006
6005
6004
6003
6002
600960086007
60066005600460036002
10 20 30 40 50 60 70
Qm /h3 10 20 30 40 50 60 70
Qm /h3 10 20 30 40 50 60 70
20 40 60 80 100 120 140
30 60 90 120 150 180 210
14
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-VS - 2900 RPM - 200 AND 400 SERIES
Imp.gpmHftHm
Qm /h31
2
3
WP1 210
209
208207206205
Number of pumps
Qm /h3
Qm /h3
4
350
300
250
200
150
100
50
0
100
80
60
40
20
0
1500
2000
1000
500
01 1,5 2,5 3,5 4,52 3 4
Qm /h3 1 1,5 2,5 3,5 4,52 3 4
2 3 4 5 6 7 8 9
3 4,5 7,56 10,5 13,59 12
6 8 10 12 14 16
N-ALTi-VS 200
2 POLE - 50Hz
203
202
204
202
203
204
205
206
207
208
209
210
402
403
404
405
Imp.gpmHftHm
Qm /h31
2
3
WP1
209
Number of pumps
Qm /h3
Qm /h3
4
350
300
250
200
150
100
50
0
100
80
60
40
20
0
1500
2000
2500
1000
500
01 3 4
2 6 8
3
2
4
6 9 12
5
10
15
6
12
18
7
14
21
8
Qm /h3 1 3 42 5 6 7 8
16
24
6 8 10 12 14 16
N-ALTi-VS 400
2 POLE - 50Hz
410
409
408
407
406
405
404
403
402
406
407
408
409410
15
HYDROPLUS
HYDRAULIC PERFORMANCES - N-ALTi-VS - 2900 RPM - 800 SERIE
Imp.gpmHftHm
Qm /h31
2
3
WP1
209
Number of pumps
Qm /h3
Qm /h3
10
200
150
100
50
0
60
40
50
30
20
10
0
1500
2000
2500
3000
1000
500
02 4
4 8
6 12
6
12
18
8
16
24
10
20
30
12
24
36
14
Qm /h3 2 4 6 8 10 12 14
28
42
20 30 40 50
N-ALTi-VS 800
2 POLE - 50Hz
802
803
804
805
806
802
804
803
805
806
16
HYDROPLUS
DIMENSIONS - N-ALTi-H SERIE - CE VERSION
*
P1
300PL
H
H1
H2
P2
TYPE Ø H L P H1 H2 P1 P2
Manifolds mm mm mm mm mm mm mm
2 PUMPS
N-ALTi-H203-2-CE-V or B-10-T4 2” 773 600 656 188 344 296 55
N-ALTi-H204-2-CE-V or B-10-T4 2” 773 600 704 188 344 344 55
N-ALTi-H205-2-CE-V or B-10-T4 2” 773 600 704 188 344 344 55
N-ALTi-H206-2-CE-V or B-10-T4 2” 773 600 728 188 344 368 55
N-ALTi-H403-2-CE-V or B-10-T4 2” 773 600 670 188 344 310 55
N-ALTi-H404-2-CE-V or B-10-T4 2” 773 600 718 188 344 358 55
N-ALTi-H405-2-CE-V or B-10-T4 2” 773 600 718 188 344 358 55
N-ALTi-H406-2-CE-V or B-10-T4 2” 773 600 742 188 344 382 55
N-ALTi-H803-2-CE-V or B-10-T4 2”1/2 773 600 713 188 352 345 63
N-ALTi-H804-2-CE-V or B-10-T4 2”1/2 773 600 773 188 352 405 63
N-ALTi-H805-2-CE-V or B-10-T4 2”1/2 773 600 773 188 352 405 63
N-ALTi-H1602-2-CE-V or B-10-T4 3” 773 600 760 188 392 383 72
N-ALTi-H1603-2-CE-V or B-10-T4 3” 773 600 760 188 392 383 72
N-ALTi-H1604-2-CE-V or B-10-T4 3” 773 600 833 198 392 428 72
3 PUMPS
N-ALTi-H203-3-CE-V or B-10-T4 2” 773 900 656 188 344 296 55
N-ALTi-H204-3-CE-V or B-10-T4 2” 773 900 704 188 344 344 55
N-ALTi-H205-3-CE-V or B-10-T4 2” 773 900 704 188 344 344 55
N-ALTi-H206-3-CE-V or B-10-T4 2” 773 900 728 188 344 368 55
N-ALTi-H403-3-CE-V or B-10-T4 2” 773 900 670 188 344 310 55
N-ALTi-H404-3-CE-V or B-10-T4 2” 773 900 718 188 344 358 55
N-ALTi-H405-3-CE-V or B-10-T4 2” 773 900 718 188 344 358 55
N-ALTi-H406-3-CE-V or B-10-T4 2” 773 900 742 188 344 382 55
N-ALTi-H803-3-CE-V or B-10-T4 2”1/2 773 900 712 188 352 345 63
N-ALTi-H804-3-CE-V or B-10-T4 2”1/2 773 900 773 188 352 405 63
N-ALTi-H805-3-CE-V or B-10-T4 2”1/2 773 900 773 188 352 405 63
N-ALTi-H1602-3-CE-V or B-10-T4 ND100* 773 900 813 188 407 398 110
N-ALTi-H1603-3-CE-V or B-10-T4 ND100* 773 900 813 188 407 398 110
N-ALTi-H1604-3-CE-V or B-10-T4 ND100* 773 900 886 198 407 443 110
17
HYDROPLUS
DIMENSIONS - N-ALTi-H SERIE - CA VERSION
*
P1
300PL
H
H1
H2
P2
TYPE Ø H L P H1 H2 P1 P2
Manifolds mm mm mm mm mm mm mm
2 PUMPS
N-ALTi-H203-2-CA-V or B-10-T4 2” 773 600 759 188 344 310 55
N-ALTi-H204-2-CA-V or B-10-T4 2” 773 600 807 188 344 358 55
N-ALTi-H205-2-CA-V or B-10-T4 2” 773 600 807 188 344 358 55
N-ALTi-H206-2-CA-V or B-10-T4 2” 773 600 831 188 344 382 55
N-ALTi-H403-2-CA-V or B-10-T4 2” 773 600 773 188 344 310 55
N-ALTi-H404-2-CA-V or B-10-T4 2” 773 600 821 188 344 358 55
N-ALTi-H405-2-CA-V or B-10-T4 2” 773 600 821 188 344 358 55
N-ALTi-H406-2-CA-V or B-10-T4 2” 773 600 845 188 344 382 55
N-ALTi-H803-2-CA-V or B-10-T4 2”1/2 773 600 813 188 352 345 63
N-ALTi-H804-2-CA-V or B-10-T4 2”1/2 773 600 876 188 352 405 63
N-ALTi-H805-2-CA-V or B-10-T4 2”1/2 773 600 876 188 352 405 63
N-ALTi-H1602-2-CA-V or B-10-T4 3” 773 600 863 188 392 372 72
N-ALTi-H1603-2-CA-V or B-10-T4 3” 773 600 863 188 392 372 72
N-ALTi-H1604-2-CA-V or B-10-T4 3” 773 600 908 198 392 372 72
3 PUMPS
N-ALTi-H203-3-CA-V or B-10-T4 2” 773 900 759 188 344 310 55
N-ALTi-H204-3-CA-V or B-10-T4 2” 773 900 807 188 344 358 55
N-ALTi-H205-3-CA-V or B-10-T4 2” 773 900 807 188 344 358 55
N-ALTi-H206-3-CA-V or B-10-T4 2” 773 900 831 188 344 382 55
N-ALTi-H403-3-CA-V or B-10-T4 2” 773 900 773 188 344 310 55
N-ALTi-H404-3-CA-V or B-10-T4 2” 773 900 821 188 344 358 55
N-ALTi-H405-3-CA-V or B-10-T4 2” 773 900 821 188 344 358 55
N-ALTi-H406-3-CA-V or B-10-T4 2” 773 900 845 188 344 382 55
N-ALTi-H803-3-CA-V or B-10-T4 2”1/2 773 900 813 188 352 345 63
N-ALTi-H804-3-CA-V or B-10-T4 2”1/2 773 900 876 188 352 405 63
N-ALTi-H805-3-CA-V or B-10-T4 2”1/2 773 900 876 188 352 405 63
N-ALTi-H1602-3-CA-V or B-10-T4 ND100* 773 900 916 188 392 372 100
N-ALTi-H1603-3-CA-V or B-10-T4 ND100* 773 900 916 188 392 372 100
N-ALTi-H1604-3-CA-V or B-10-T4 ND100* 773 900 961 198 392 472 100
18
HYDROPLUS
DIMENSIONS - N-ALTi-V OR VS SERIE - CE VERSION
P1
300
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V or VS 203-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 204-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 205-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 206-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 207-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 208-2-CE-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-VS 209-2-CE-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V 210-2-CE-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V 212-2-CE-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V or VS 403-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 404-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 405-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 406-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 407-2-CE-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 408-2-CE-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V or VS 410-2-CE-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V 412-2-CE-V or B-16-T4 2” 1320 600 610 100 550
3 PUMPS
N-ALTi-V or VS 203-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 204-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 205-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 206-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 207-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 208-3-CE-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-VS 209-3-CE-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V 210-3-CE-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V 212-3-CE-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V or VS 403-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 404-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 405-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 406-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 407-3-CE-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 408-3-CE-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V or VS 410-3-CE-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V or VS 412-3-CE-V or B-16-T4 2” 1320 900 610 100 550
19
HYDROPLUS
DIMENSIONS - N-ALTi-V OR VS SERIE - CA VERSION
P1
300
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V or VS 203-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 204-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 205-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 206-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 207-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 208-2-CA-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-VS 209-2-CA-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V 210-2-CA-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V 212-2-CA-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V or VS 403-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 404-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 405-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 406-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 407-2-CA-V or B-16-T4 2” 1150 600 610 100 550
N-ALTi-V or VS 408-2-CA-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V or VS 410-2-CA-V or B-16-T4 2” 1320 600 610 100 550
N-ALTi-V 412-2-CA-V or B-16-T4 2” 1320 600 610 100 550
3 PUMPS
N-ALTi-V or VS 203-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 204-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 205-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 206-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 207-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 208-3-CA-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-VS 209-3-CA-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V 210-3-CA-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V 212-3-CA-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V or VS 403-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 404-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 405-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 406-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 407-3-CA-V or B-16-T4 2” 1150 900 610 100 550
N-ALTi-V or VS 408-3-CA-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V or VS 410-3-CA-V or B-16-T4 2” 1320 900 610 100 550
N-ALTi-V or VS 412-3-CA-V or B-16-T4 2” 1320 900 610 100 550
20
HYDROPLUS
DIMENSIONS - N-ALTi-V OR VS SERIE - CE VERSION
*
**
P1
450
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-VS 802-2-CE-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 803-2-CE-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 804-2-CE-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 805-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V or VS 806-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 807-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 808-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 810-2-CE-V or B-16-T4 2”1/2 1450 600 717 130 640N-ALTi-V 811-2-CE-V or B-16-T4 2”1/2 1450 600 717 130 640N-ALTi-V 812-2-CE-V or B-16-T4 2”1/2 1450 600 717 130 640N-ALTi-V 1603-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1604-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1605-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1606-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1607-2-CE-V or B-16-T4 3” 1450 600 745 140 656N-ALTi-V 1608-2-CE-V or B-16-T4 3” 1450 600 745 140 656N-ALTi-V 1609-2-CE-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1610-2-CE-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1611-2-CE-V or B-16-T4 3” 1223** 600 745 140 656
3 PUMPS
N-ALTi-VS 802-3-CE-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 803-3-CE-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 804-3-CE-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 805-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V or VS 806-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 807-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 808-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 810-3-CE-V or B-16-T4 2”1/2 1450 900 717 130 640N-ALTi-V 811-3-CE-V or B-16-T4 2”1/2 1450 900 717 130 640N-ALTi-V 812-3-CE-V or B-16-T4 2”1/2 1450 900 717 130 640N-ALTi-V 1603-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1604-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1605-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1606-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1607-3-CE-V or B-16-T4 ND100* 1450 900 906 140 686N-ALTi-V 1608-3-CE-V or B-16-T4 ND100* 1450 900 906 140 686N-ALTi-V 1609-3-CE-V or B-16-T4 ND100* 1150** 900 906 140 686N-ALTi-V 1610-3-CE-V or B-16-T4 ND100* 1150** 900 906 140 686N-ALTi-V 1611-3-CE-V or B-16-T4 ND100* 1223** 900 906 140 686
** For these boosters, the unit is
positioned on the discharge side
(rotating of bracket by 180°).
21
HYDROPLUS
DIMENSIONS - N-ALTi-V OR VS SERIE - CA VERSION
P1
450
PL
H
H1
*
**
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-VS 802-2-CA-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 803-2-CA-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 804-2-CA-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 805-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V or VS 806-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 807-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 808-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 810-2-CA-V or B-16-T4 2”1/2 1470 600 717 130 640N-ALTi-V 811-2-CA-V or B-16-T4 2”1/2 1470 600 717 130 640N-ALTi-V 812-2-CA-V or B-16-T4 2”1/2 1470 600 717 130 640N-ALTi-V 1603-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1604-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1605-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1606-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1607-2-CA-V or B-16-T4 3” 1470 600 745 140 656N-ALTi-V 1608-2-CA-V or B-16-T4 3” 1470 600 745 140 656N-ALTi-V 1609-2-CA-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1610-2-CA-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1611-2-CA-V or B-16-T4 3” 1223** 600 745 140 656
3 PUMPS
N-ALTi-VS 802-3-CA-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 803-3-CA-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 804-3-CA-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 805-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V or VS 806-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 807-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 808-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 810-3-CA-V or B-16-T4 2”1/2 1470 900 717 130 640N-ALTi-V 811-3-CA-V or B-16-T4 2”1/2 1470 900 717 130 640N-ALTi-V 812-3-CA-V or B-16-T4 2”1/2 1470 900 717 130 640N-ALTi-V 1603-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1604-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1605-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1606-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1607-3-CA-V or B-16-T4 ND100* 1470 900 906 140 686N-ALTi-V 1608-3-CA-V or B-16-T4 ND100* 1470 900 906 140 686N-ALTi-V 1609-3-CA-V or B-16-T4 ND100* 1470 900 906 140 686N-ALTi-V 1610-3-CA-V or B-16-T4 ND100* 1150** 900 906 140 686N-ALTi-V 1611-3-CA-V or B-16-T4 ND100* 1223** 900 906 140 686
** For these boosters, the unit is
positioned on the discharge side
(rotating of bracket by 180°).
22
HYDROPLUS
DIMENSIONS - N-ALTi-V OR VS SERIE - CV VERSION
P1
300
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V or VS 203-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 204-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 205-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 206-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 207-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 208-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-VS 209-2-CV-V or B-16-T4 2” 1830 600 610 100 550
N-ALTi-V 210-2-CV-V or B-16-T4 2” 1830 600 610 100 550
N-ALTi-V 212-2-CV-V or B-16-T4 2” 1830 600 610 100 550
N-ALTi-V or VS 403-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 404-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 405-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 406-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 407-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 408-2-CV-V or B-16-T4 2” 1630 600 610 100 550
N-ALTi-V or VS 410-2-CV-V or B-16-T4 2” 1830 600 610 100 550
N-ALTi-V 412-2-CV-V or B-16-T4 2” 1830 600 610 100 550
3 PUMPS
N-ALTi-V or VS 203-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 204-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 205-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 206-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 207-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 208-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-VS 209-3-CV-V or B-16-T4 2” 1830 900 610 100 550
N-ALTi-V 210-3-CV-V or B-16-T4 2” 1830 900 610 100 550
N-ALTi-V 212-3-CV-V or B-16-T4 2” 1830 900 610 100 550
N-ALTi-V or VS 403-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 404-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 405-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 406-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 407-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 408-3-CV-V or B-16-T4 2” 1630 900 610 100 550
N-ALTi-V or VS 410-3-CV-V or B-16-T4 2” 1830 900 610 100 550
N-ALTi-V 412-3-CV-V or B-16-T4 2” 1830 900 610 100 550
23
HYDROPLUS
DIMENSIONS - N-ALTi-V OR VS SERIE - CV VERSION
P1
450
PL
H
H1
*
**
** For these boosters, the unit is
positioned on the discharge side
(rotating of bracket by 180°).
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V or VS 803-2-CV-V or B-16-T4 2”1/2 1630 600 717 130 640N-ALTi-V or VS 804-2-CV-V or B-16-T4 2”1/2 1630 600 717 130 640N-ALTi-V or VS 805-2-CV-V or B-16-T4 2”1/2 1630 600 717 130 640N-ALTi-V or VS 806-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 807-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 808-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 810-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 811-2-CV-V or B-16-T4 2”1/2 1630** 600 717 130 640N-ALTi-V 812-2-CV-V or B-16-T4 2”1/2 1630** 600 717 130 640N-ALTi-V 1603-2-CV-V or B-16-T4 3” 1630 600 745 140 656N-ALTi-V 1604-2-CV-V or B-16-T4 3” 1830 600 745 140 656N-ALTi-V 1605-2-CV-V or B-16-T4 3” 1830 600 745 140 656N-ALTi-V 1606-2-CV-V or B-16-T4 3” 1830 600 745 140 656N-ALTi-V 1607-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1608-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1609-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1610-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1611-2-CV-V or B-16-T4 3” 1630** 600 745 140 656
3 PUMPS
N-ALTi-V or VS 803-3-CV-V or B-16-T4 2”1/2 1630 900 717 130 640N-ALTi-V or VS 804-3-CV-V or B-16-T4 2”1/2 1630 900 717 130 640N-ALTi-V or VS 805-3-CV-V or B-16-T4 2”1/2 1630 900 717 130 640N-ALTi-V or VS 806-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 807-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 808-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 810-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 811-3-CV-V or B-16-T4 2”1/2 1630** 900 717 130 640N-ALTi-V 812-3-CV-V or B-16-T4 2”1/2 1630** 900 717 130 640N-ALTi-V 1603-3-CV-V or B-16-T4 ND100* 1630 900 906 140 686N-ALTi-V 1604-3-CV-V or B-16-T4 ND100* 1830 900 906 140 686N-ALTi-V 1605-3-CV-V or B-16-T4 ND100* 1830 900 906 140 686N-ALTi-V 1606-3-CV-V or B-16-T4 ND100* 1830 900 906 140 686N-ALTi-V 1607-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1608-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1609-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1610-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1611-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686
24
HYDROPLUS
DIMENSIONS - N-ALTi-V SERIE - CE VERSION
P1
450
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V 1802-2-CE-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1803-2-CE-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1804-2-CE-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1805-2-CE-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1806-2-CE-V or B-16-T4 3” 1320 600 880 140 790
3 PUMPS
N-ALTi-V 1802-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1803-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1804-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1805-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1806-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800
25
HYDROPLUS
DIMENSIONS - N-ALTi-V SERIE - CA VERSION
P1
450
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V 1802-2-CA-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1803-2-CA-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1804-2-CA-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1805-2-CA-V or B-16-T4 3” 1320 600 880 140 790
N-ALTi-V 1806-2-CA-V or B-16-T4 3” 1320 600 880 140 790
3 PUMPS
N-ALTi-V 1802-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1803-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1804-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1805-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800
N-ALTi-V 1806-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800
26
HYDROPLUS
DIMENSIONS - N-ALTi-V SERIE - CE VERSION
P1
500
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V 3602-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3603-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3604-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3605-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3606-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 6002-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6003-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6004-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6005-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6006-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900
3 PUMPS
N-ALTi-V 3602-3-CE-B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3603-3-CE-B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3604-3-CE-B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3605-3-CE-B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3606-3-CE-B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 6002-3-CE-B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6003-3-CE-B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6004-3-CE-B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6005-3-CE-B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6006-3-CE-B-16-T4 ND150 1175 2200 1220 170 930
27
HYDROPLUS
DIMENSIONS - N-ALTi-V SERIE - CA VERSION
P1
500
PL
H
H1
TYPE Ø H L P H1 P1
Manifolds mm mm mm mm mm
2 PUMPS
N-ALTi-V 3602-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3603-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3604-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3605-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 3606-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940
N-ALTi-V 6002-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6003-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6004-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6005-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900
N-ALTi-V 6006-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900
3 PUMPS
N-ALTi-V 3602-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3603-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3604-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3605-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 3606-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970
N-ALTi-V 6002-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6003-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6004-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6005-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930
N-ALTi-V 6006-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930
28
HYDROPLUS
RECOMMENDED ACCESSORIES
• Direct water supply bypass when the public water system
pressure is insufficient.
(Accessory reference: BP)
• Anti-vibration sleeves.
(Accessory reference: M)
• Counter flanges, supplied by 2.
(Accessory reference: CB)
• Isolating valves.
(Accessory reference: V)
FEATURES
a) Installation
- On smooth floor or a concrete block with attachment by anchor
bolts.
- Connection of suction and discharge manifolds, either on right or
left as desired.
b) Packaging
On pallet.
53 bd de la République - Espace Lumière - Bât. 6 - 78403 Chatou Cedex FRANCE