Hydroplus Eng 50hz

28
1 HYDROPLUS Flow rates up to: 195 m 3 /h Head up to: 240 m CE Max. operating pressure: 16 & 25 bar Max. water temperature: H/V 70°C VS 50°C Max. ambient temperature: 40°C ND of threaded manfolds: G2, G3 ND of flanged manifolds: ND 80 to 150 OPERATING LIMITS N.T. N o 143-1/ENG. - Ed4. /05-05 H 240 195 0 m 1300 400 HYDROMODULES HYDROPLUS /h Qm 3 BOOSTERS Range of boosters fitted with MULTi-V or MULTi-H pumps: Commercial and industrial use 2 pole - 50 Hz Pressurizing and maintaining pressure of water distribution networks with insufficient or non existent pressure, in: - housing, office projects, - private residences, - hotels, hospitals, clinics, - shopping centres, shops, - schools, high-schools, universities, barracks, - industrial and farm buildings, - irrigation, spraying… N-ALTi-VS405-3-CE-16-T4 • N-ALTi-VS... Wet rotor technology Silent-operation booster from 38 to 58 dB(A) APPLICATIONS N-ALTi-H803-2-T4 N-ALTi-V806-3-CA-16-T4

Transcript of Hydroplus Eng 50hz

Page 1: Hydroplus Eng 50hz

1

HYDROPLUSFlow rates up to: 195 m3/h

Head up to: 240 m CE

Max. operating pressure: 16 & 25 bar

Max. water temperature: H / V 70°C

VS 50°C

Max. ambient temperature: 40°C

ND of threaded manfolds: G2, G3

ND of flanged manifolds: ND 80 to 150

OPERATING LIMITS

N.T. No 143-1/ENG. - Ed4. /05-05

H

240

1950

m

1300

400

HYDROMODULES

HYDROPLUS

/hQm3

BOOSTERSRange of boosters fitted

with MULTi-V or MULTi-H pumps:Commercial and industrial use

2 pole - 50 Hz

Pressurizing and maintaining pressure ofwater distribution networks with insufficientor non existent pressure, in:- housing, office projects,- private residences,

- hotels, hospitals, clinics,- shopping centres, shops,- schools, high-schools, universities, barracks,- industrial and farm buildings,- irrigation, spraying…

• N-ALTi-VS405-3-CE-16-T4

• N-ALTi-VS...

• Wet rotor technology

• Silent-operation booster from 38 to 58 dB(A)

APPLICATIONS

• N-ALTi-H803-2-T4

• N-ALTi-V806-3-CA-16-T4

Page 2: Hydroplus Eng 50hz

2

HYDROPLUS

ADVANTAGES DESIGN

ALTi-H. ALTi-V. ALTi-VS range

Compact boosters, specifically designed fordirect or standard booster systems equippedwith:

– Two or three MULTi-V or MULTi-H pumps,having predetermined hydraulic characteristics.

– Two suction-discharge pipes made of stainless: connections may be to the rightor left side as desired.

– Discharge and suction valves for eachpump.

– Silent-operation non-return discharge valvefor each pump fitted with interchangeablecartridges on the N-ALTi 2/4/8/16 range.

– An automatic pump control pressureswitch (CA-CV).

– A pressure transmitter (CV).– A dry-running pressure switch (town water

network version).– A dry-running float switch (version for

storage tank).– A pressure gauge.– A support and attachment frame

(dampers for ALTi-H version).– Lifting rings or holes for lifting bars.– A regulation box available in three

configurations:

CA: electromechanical with API (Automate Programmable)

CE: electronic

CV: variable speed control.

OPTION

- ELiNOX-V/H Version: 316 stainless steelversion .

- Boosters with 4 or more pumps, jockeypumps,…

• Compact modules, factory preset andready to install.

• Small ground space.

• Easy to install: 2 hydraulicconnections and one electricalconnection.

• Control and protection functions grouped in the cabinet assuringintegral automatic operation.

• N-ALTi 2/4/8/16 range non-returnvalve fitted with interchangeable cartridge. Easy to maintain.

• Stainless steel hydraulic system: reliable corrosion resistance andlonger life.

• Base protected by an electrolytictreatment ensuring excellent resistance to saline mist.

BOOSTER IDENTIFICATION - HYDROPLUS

N-ALTI-H D (regulator)N-ALTI-V 02 BP (by-pass)N-ALTI-VS 11 CA M (sleeves)N-ELINOX-H 03 CE V T2 V (Isolating valves)

N-ELINOX-V 1804 21 CV B T4 3 CB (counter flanges)

Codes for optional accessories (indicate in the order).

Tank code 3: state capacity and pressure.

Three-phase supply voltage - T2: TRI 230 V - T4: TRI 400 V.

Water supply - V: on town network - B: on tank (not supplied).

Control:

CA : electromechanical box with API

CE : electronic box

CV : speed controller box

N° of pumps 2 : 2 pumps in series in cascade

11 : 1 pump + 1 standby pump

3 : 3 pumps in cascade

21 : 2 pumps + 1 standby pump

Nominal flow-rate and number of stages

N-ALTi-H. V. VS : standard booster fitted with stainless steel 304 pump

N-ELiNOX-H. V : special all 316 stainless steel booster.

}

Page 3: Hydroplus Eng 50hz

3

HYDROPLUS

BOOSTER DESCRIPTION

1 7 2

9 3 5

4 86

• N-ALTi-H

1 27

4 5 3

6

8

• N-ALTi-V / N-ALTi-VS

1 - Controller box

2 - Pumps (Type MULTi-H. MULTi-V or MULTi-VS)

3 - Suction manifold

4 - Discharge manifold

5 - Non return valve

6 - Isolating valves

7 - Pressure gauge

8 - Sensor

9 - Damping pads (for N-ALTi-H)

SUPPLIES

N-ALTi-H N-ALTi-V N-ALTi-VS

Components 2 pumps 3 pumps 2 pumps 3 pumps 2 pumps 3 pumps

Pumps MULTi-H 2 3 — — — —

Pumps MULTi-V — — 2 3 — —

Pumps MULTi-VS — — — — 2 3

Valves 4 6 4 6 4 6

Non return valves 2 3 2 3 2 3

Stainless steel manifolds 2 2 2 2 2 2

Pressure switch (CA.CE) - Transmitter (CV) 1 1 1 1 1 1

Pressure switch

Dry running (for V version)

protection Float1 1 1 1 1 1

(for B version )

Pressure gauge 1 1 1 1 1 1

Controller box 1 1 1 1 1 1

Damping pads 4 4 — — — —

Base plate 1 1 1 1 1 1

Standards and specifications:

• Machines Directive 98/37/CE. • Electromagnetic compatibility Directive

89/336/CEEmod.• Low Voltage Directive: 73/23/CEEmod.

• CEI 60364 (NFC 15-100) (Electrical).• EN 61800-3 (Adjustable speed electrical

power drive systems).• EN 809 – Pumps and motor-pump units

for liquids.

• EN 61000-6 – 1 & 3 or EN 61000-6 2& 4 (Immunity / Emission).

• EN 60204-1 (Machines safety). EN 60034-1 (Rotating electrical machines).EN 60439-1 (Electric and electronic box).

Page 4: Hydroplus Eng 50hz

4

HYDROPLUS

SUPPLIES

Example with a 3-pump Hydroplus.

Same representation with a 2-pump

Hydroplus.

“V” VERSION

FROM THE PUBLIC WATER SYSTEM

“B” VERSION

FROM A STORAGE TANK(in charge)

2

8

10

Code 3

BP CB V M D

4 3

5

3

1

6

5

7

10

9

11

Code 3

STANDARD SUPPLIES (1 to 9) :

1 - Two or three multistage pumps.

2 - Support frame.

3 - Cutoff valves at pump suction anddischarge.

4 - Check valve at pump discharge.

5 - Suction-discharge manifolds.

6 - Pressure transmitter.

7 - Control and protection panel.

COMPULSORY SUPPLIES:(according to the booster’s water supply).

08 - Dry running protection pressureswitch,supplied fitted, booster suppliedwith city water (included in the price),or

09 - Float switch, supplied not fitted,booster supplied on charged tank(included in the price).

10 - CODE 3 bladder vessel, 100 to2000 liter, specify operating pressureand capacity (option priced separately).

11 - Balance piping for suction tank.

OPTIONAL SUPPLIES:(options priced separately).

BP - Direct water supply bypass when thepublic water system pressure isinsufficient. (comes fitted if ordered).

M - Anti-vibration sleeves (supplied by 2).

CB - Counterflanges to be screwed or weldedonto the manifolds (supplied by 2).

D - Pressure regulator-stabilizer for suctionand/or discharge.

V - Isolating valves.

NB: when a bypass and an suction pressure regulator are fitted onto the booster, we recommend fitting the pressure regulator between the bypass and the booster.

OPERATING LIMITS

Flow rates up to: 3 pumps version 80 m3/h

4 pumps version *105 m3/h

Max. head: 70m (NP10)

Max. operating pressure: 10 bar

Max. inlet pressure: 4 bar

Max. water temperature: ALTi-H 70°C

Max. ambient temperature: 40°C

ND of threaded manfolds: G2, G21/2

Flow rates up to: 3 pumps version 195 m3/h

4 pumps version *260 m3/h

Max. head: 150m (NP16) - **230m (NP25)

Max. operating pressure: 25 bar

Max. inlet pressure: 10 bar

Max. water temperature: ALTi-V 70°C

Max. ambient temperature: 40°C

ND of threaded manfolds: G2, G21/2

ND of flanged manifolds: DN 80 to 150

Flow rates up to: 3 pumps version 42 m3/h

4 pumps version *56 m3/h

Max. head: 110m (NP16)

Max. operating pressure: 16 bar

Max. inlet pressure: 6 bar

Max. water temperature: ALTi-VS 50°C

Max. ambient temperature: 40°C

ND of threaded manfolds: G2, G21/2

NB: An ALTi-VS should be installed on a public water supplyor flooded on a storage tank with a water height > 0.5 mabove the pump.

• N-ALTi-H 2,4,8,16 • N-ALTi-V 2,4,8,16,18,36,60 • N-ALTi-VS 2,4,8

H

70

800

m

*105

HYDROPLUS-H

/hQm3

H

150

1950

m

*260

**230

HYDROPLUS-V

/hQm3

H

110

420

m

*56

HYDROPLUS-S

/hQm3

Page 5: Hydroplus Eng 50hz

5

HYDROPLUS

CONTROL AND REGULATION: A STANDARDISED PANEL

CONTROL PANEL COMMON TO THE THREE

UNITS WITH:

➊ – Switch per pump: automatic

start/stop/forced start (transient).

➋ – Indicator: on per pump.

➌ – Indicator: pump fault per pump.

➍ – Indicator: dry running

➎ – Indicator: module powered up.

➏ – Booster type.

SPEED VARIATION CHARACTERISTICS

17 – Embossed key: varied pump rearming.

18 – Indicator: varied pump fault.

19 – Embossed key: rearm, variable speed

controller.

10 – Indicator: variable speed controller fault.

11 – Switch: variable speed controller.

ELECTROMECHANICAL BOX WITH PLC (CA) : DESCRIPTION AND OPERATION

Complies with NF C15-100 and CE

standards in force

– Leaktightness: protection index IP 54.

Power supply:

Three-phase: 230/400V (50 Hz)

220 /380 V (60 Hz option)

Single-phase: (optional)

230 V (50 Hz)

220/240 V (60 Hz)

DESCRIPTION: (2 or 3 pumps).

Front panel:

– Control and display panel.

– Safety and mains power rotary switch.

Inside:

– Magneto-thermal circuit breakers with

motor intensity adjustment switch (and

reset button) for pump(s).

– Pump contactors with motor connection

terminals.

– Safety switch controlled from the outside

via lockable handle.

– 24-230 V safety transformer.

– Control power supply protection fuses.

– External control unit connection terminal

strip (pressure switch, float switch, remote

control, etc).

– Programmable controller.

OPERATION

The pumps are operated by a neutral range

pressure switch (low pressure and high

pressure).

On detection of a low pressure, a first timer

“T1M” is activated. If after ”T1M” the pressu-

re remains low, the pump “P1” is activated

and a timer “T2M”. After “T2M”, the pump

“P2” is activated and a timer “T3M” in a 3

pump version. After “T3M”, the pump “P3” is

activated.

If the flow rate is adequate (between low

pressure and high pressure levels) none of

the pumps are started up.

If the high pressure level is reached, the

timers “T1A”, “T2A” and “T3A” are activated

to stop the pumps in the same way in which

they are started.

If the flow rate is adequate, the pumps in

operation are not stopped.

When the last pump has stopped, a cyclical

change-over takes place when the pumps

start up again.

After dry running has been detected, a

“TME-ON” timer is activated and the pumps

are stopped when the time elapses.

Restarting is only permitted once the water

has returned to an adequate level and a

second “TME-OFF” timer has run out.

If there is a fault in one of the pumps, the

machine automatically switches to one of

the remaining valid pumps.

NB

On all booster models (2 and 3 pumps)

the pump starting order after stopping is

permuted.

7 8 9 10 11

➊ ➋ ➌ ➍ ➎ ➏

Page 6: Hydroplus Eng 50hz

6

HYDROPLUS

VARIABLE SPEED BOX : DESCRIPTION AND OPERATION

Complies with NF C15-100 and CE

standards in force

– Leaktightness: guard index IP 559.

Power supply

Three-phase: 230/400V (50 Hz)

220 /380 V (60 Hz-option)

Single phase: (optional)

230 V (50 Hz)

220/240 V (60 Hz)

DESCRIPTION: (one varied pump and one

or two fixed pumps).

Front panel:

– Control and display panel.

– Regulator panel.

– Key-operated lock.

– Safety and mains power rotary switch.

Inside:

– Magneto-thermal circuit breaker with

motor intensity adjusting switch (and reset

button) for fixed pump(s).

– Contactor (one per pump).

– 24 V safety transformer.

– Electrical connection terminal strip.

– Main disconnect switch controlled from the

outside via lockable handle.

– Pump start and stop timer (adjustable).

– Last pump hold-in timer (adjustable).

– Change-over clock.

– Set of HPC three-pole circuit breakers.

– External control unit connection terminal

strip (pressure switch, float switch, remote

control, etc).

– Relay module.

– Speed variator.

ELECTRONIC BOX: DESCRIPTION AND OPERATION

Complies with NF C15-100 and CE

standards in force

– Leaktightness: guard index IP 54.

Power supply

Three-phase: 230/400V (50 Hz)

220 /380 V (60 Hz-option)

Single-phase: (optional)

230 V (50 Hz)

220/240 V (60 Hz)

DESCRIPTIF : (2 or 3 pumps).

Front panel:

– Control and display panel.

– Safety and mains power rotary switch.

Inside:

– Pump protection thermal relay with motor

connection terminals.

– Pump contactors.

– Safety switch with power supply network

connection terminals.

– 230 or 400 V protection and voltage

selection fuse.

– Control unit low voltage power supply 12 V

transformer.

– Motor thermal protection potentiometers

(max I: 32 A/pump).

– Connectors receiving the indicator light

and timer power supply contact pin.

– External control unit connection terminal

strip (pressure switch, float switch, remote

control, etc).

OPERATION

Booster operation is assured by two simple

pressure switches, in the 2-pump version

and by a neutral range pressure switch in

the 3 or more pump version.

Otherwise, the operating principle is the

same as for the electromechanical unit.

The automatic system and connection block

can accept a remote control unit.

OPERATION

The pressure transmitter records the pressure

in the discharge line and sends signals to the

regulator. If the pressure becomes lower than

the set-point value, the regulator signals the

variable speed controller to increase the

speed of the controlled or “varied” pump.

• If the varied pump reaches its maximum

speed of rotation whilst the pressure is still

too low, the regulator starts pump “P2” at a

fixed speed; the speed of “P1” is adjusted to

keep the chosen set-point value. If the

accumulated flow-rate of “P1” and “P2” is not

enough, “P3” (3-pump HYDROPLUS) is

started in the same way.

• If the pressure gets too high, the regulator

adjusts “P1” to the minimum chosen speed

and if the pressure is still too high, it stops the

last fixed-speed pump that was turned on.

• Then “P1” is put back at its maximum

speed before being reduced to the minimum

speed, then the last but one fixed-speed

pump is stopped (if necessary) and so on

until the set-point value is reached.

NB:

On all booster models (2 and 3 pumps) the

pump starting order after stopping is

permuted.

Page 7: Hydroplus Eng 50hz

7

HYDROPLUS

ELECTRICAL DATA

TYPE P2 Total installed Max. service Voltage Total

motor power in kW pressure current

2 PUMPS - Box CA. CE or CV - City or Tank

N-ALTi-H203-2...T4 2x 0.55 10 bar 400V-3~50 Hz 3.4A

N-ALTi-H204-2...T4 2x 0.55 10 bar 400V-3~50 Hz 3.4A

N-ALTi-H205-2...T4 2x 0.75 10 bar 400V-3~50 Hz 4.2A

N-ALTi-H206-2...T4 2x 1.1 10 bar 400V-3~50 Hz 6.2A

N-ALTi-H403-2...T4 2x 0.55 10 bar 400V-3~50 Hz 3.4A

N-ALTi-H404-2...T4 2x 0.75 10 bar 400V-3~50 Hz 4.2A

N-ALTi-H405-2...T4 2x 1.1 10 bar 400V-3~50 Hz 6.2A

N-ALTi-H406-2...T4 2x 1.5 10 bar 400V-3~50 Hz 7.6A

N-ALTi-H803-2...T4 2x 1.1 10 bar 400V-3~50 Hz 6.2A

N-ALTi-H804-2...T4 2x 1.5 10 bar 400V-3~50 Hz 7.6A

N-ALTi-H805-2...T4 2x 1.85 10 bar 400V-3~50 Hz 9.9A

N-ALTi-H1602-2...T4 2x 1.5 10 bar 400V-3~50 Hz 7.6A

N-ALTi-H1603-2...T4 2x 1.85 10 bar 400V-3~50 Hz 9.9A

N-ALTi-H1604-2...T4 2x 2.5 10 bar 400V-3~50 Hz 11.7A

3 PUMPS - Box CA. CE or CV - City or Tank

N-ALTi-H203-3...T4 3x 0.55 10 bar 400V-3~50 Hz 5.1A

N-ALTi-H204-3...T4 3x 0.55 10 bar 400V-3~50 Hz 5.1A

N-ALTi-H205-3...T4 3x 0.75 10 bar 400V-3~50 Hz 6.3A

N-ALTi-H206-3...T4 3x 1.1 10 bar 400V-3~50 Hz 9.3A

N-ALTi-H403-3...T4 3x 0.55 10 bar 400V-3~50 Hz 5.1A

N-ALTi-H404-3...T4 3x 0.75 10 bar 400V-3~50 Hz 6.3A

N-ALTi-H405-3...T4 3x 1.1 10 bar 400V-3~50 Hz 9.3A

N-ALTi-H406-3...T4 3x 1.5 10 bar 400V-3~50 Hz 11.4A

N-ALTi-H803-3...T4 3x 1.1 10 bar 400V-3~50 Hz 9.3A

N-ALTi-H804-3...T4 3x 1.5 10 bar 400V-3~50 Hz 11.4A

N-ALTi-H805-3...T4 2x 1.85 10 bar 400V-3~50 Hz 14.9A

N-ALTi-H1602-3...T4 3x 1.5 10 bar 400V-3~50 Hz 11.4A

N-ALTi-H1603-3...T4 3x 1.85 10 bar 400V-3~50 Hz 14.9A

N-ALTi-H1604-3...T4 3x 2.5 10 bar 400V-3~50 Hz 17.6A

TYPE P2 Total installed Max. service Voltage Total current Total current

motor power in kW pressure 2 pumps 3 pumps

2 or 3 PUMPS - Box CA. CE or CV - City or TankN-ALTi-V203-2 or 3 pumps...T4 2 or 3x 0.55 16 bar 400V-3~50 Hz 2.7A 3.9AN-ALTi-V204-2 or 3 pumps...T4 2 or 3x 0.75 16 bar 400V-3~50 Hz 3.4A 5.0AN-ALTi-V205-2 or 3 pumps...T4 2 or 3x 0.75 16 bar 400V-3~50 Hz 3.4A 5.0AN-ALTi-V206-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V207-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V208-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V210-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V212-2 or 3 pumps...T4 2 or 3x 1.85 16 bar 400V-3~50 Hz 8.0A 11.7AN-ALTi-V403-2 or 3 pumps...T4 2 or 3x 0.75 16 bar 400V-3~50 Hz 3.4A 5.0AN-ALTi-V404-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V405-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V406-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V407-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V408-2 or 3 pumps...T4 2 or 3x 1.85 16 bar 400V-3~50 Hz 8.0A 11.7AN-ALTi-V410-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V412-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V803-2 or 3 pumps...T4 2 or 3x 1.1 16 bar 400V-3~50 Hz 4.8A 7.2AN-ALTi-V804-2 or 3 pumps...T4 2 or 3x 1.5 16 bar 400V-3~50 Hz 6.4A 9.6AN-ALTi-V805-2 or 3 pumps...T4 2 or 3x 1.85 16 bar 400V-3~50 Hz 7.8A 11.7AN-ALTi-V806-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V807-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V808-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V810-2 or 3 pumps...T4 2 or 3x 3.7 16 bar 400V-3~50 Hz 15.6A 23.4AN-ALTi-V811-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V812-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21.6A 31.5AN-ALTi-V1603-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V1604-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V1605-2 or 3 pumps...T4 2 or 3x 3.7 16 bar 400V-3~50 Hz 15.6A 23.4AN-ALTi-V1606-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V1607-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21.6A 32.4AN-ALTi-V1608-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21.6A 32.4AN-ALTi-V1609-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V1610-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V1802-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 8.8A 13.2AN-ALTi-V1803-2 or 3 pumps...T4 2 or 3x 3 16 bar 400V-3~50 Hz 12.6A 18.9AN-ALTi-V1804-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V1805-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V1806-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V1807-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V1808-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V3602-2 or 3 pumps...T4 2 or 3x 4 16 bar 400V-3~50 Hz 16.8A 25.2AN-ALTi-V3603-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V3604-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V3605-2 or 3 pumps...T4 2 or 3x 9 16 bar 400V-3~50 Hz 34A 51AN-ALTi-V3606-2 or 3 pumps...T4 2 or 3x 11 16 bar 400V-3~50 Hz 40A 60AN-ALTi-V3607-2 or 3 pumps...T4 2 or 3x 15 16 bar 400V-3~50 Hz 53A 79.5AN-ALTi-V6002-2 or 3 pumps...T4 2 or 3x 5.5 16 bar 400V-3~50 Hz 21A 31.5AN-ALTi-V6003-2 or 3 pumps...T4 2 or 3x 7.5 16 bar 400V-3~50 Hz 28.6A 42.9AN-ALTi-V6004-2 or 3 pumps...T4 2 or 3x 11 16 bar 400V-3~50 Hz 40A 60AN-ALTi-V6005-2 or 3 pumps...T4 2 or 3x 15 16 bar 400V-3~50 Hz 53A 79.5AN-ALTi-V6006-2 or 3 pumps...T4 2 or 3x 15 16 bar 400V-3~50 Hz 53A 79.5AN-ALTi-V6007-2 or 3 pumps...T4 2 or 3x 18.5 16 bar 400V-3~50 Hz 66A 99A

TYPE P1 Total installed Max. service Voltage Total current Total current

motor power in kW pressure at TRI 230V at TRI 400V2 PUMPS - Box CA. CE or CV - City or Tank

N-ALTi-VS202-2 or 3 pumps...T4 2 or 3x 0.51 16 bar 400V-3~50 Hz 2 or 3x 2.1A 2 or 3x 1.2AN-ALTi-VS203-2 or 3 pumps...T4 2 or 3x 0.72 16 bar 400V-3~50 Hz 2 or 3x 2.6A 2 or 3x 1.5AN-ALTi-VS204-2 or 3 pumps...T4 2 or 3x 0.88 16 bar 400V-3~50 Hz 2 or 3x 3A 2 or 3x 1.7AN-ALTi-VS205-2 or 3 pumps...T4 2 or 3x 1.2 16 bar 400V-3~50 Hz 2 or 3x 4.51A 2 or 3x 2.6AN-ALTi-VS206-2 or 3 pumps...T4 2 or 3x 1.38 16 bar 400V-3~50 Hz 2 or 3x 4.9A 2 or 3x 2.8AN-ALTi-VS207-2 or 3 pumps...T4 2 or 3x 1.53 16 bar 400V-3~50 Hz 2 or 3x 5.2A 2 or 3x 3AN-ALTi-VS208-2 or 3 pumps...T4 2 or 3x 1.69 16 bar 400V-3~50 Hz 2 or 3x 5.6A 2 or 3x 3.2AN-ALTi-VS209-2 or 3 pumps...T4 2 or 3x 2.14 16 bar 400V-3~50 Hz 2 or 3x 8A 2 or 3x 4.6AN-ALTi-VS210-2 or 3 pumps...T4 2 or 3x 2.33 16 bar 400V-3~50 Hz 2 or 3x 8.5A 2 or 3x 4.9AN-ALTi-VS402-2 or 3 pumps...T4 2 or 3x 0.69 16 bar 400V-3~50 Hz 2 or 3x 2.6A 2 or 3x 1.5AN-ALTi-VS403-2 or 3 pumps...T4 2 or 3x 1.02 16 bar 400V-3~50 Hz 2 or 3x 4.2A 2 or 3x 2.4AN-ALTi-VS404-2 or 3 pumps...T4 2 or 3x 1.26 16 bar 400V-3~50 Hz 2 or 3x 4.5A 2 or 3x 2.6AN-ALTi-VS405-2 or 3 pumps...T4 2 or 3x 1.48 16 bar 400V-3~50 Hz 2 or 3x 5.2A 2 or 3x 3AN-ALTi-VS406-2 or 3 pumps...T4 2 or 3x 1.7 16 bar 400V-3~50 Hz 2 or 3x 5.6A 2 or 3x 3.2AN-ALTi-VS407-2 or 3 pumps...T4 2 or 3x 2.2 16 bar 400V-3~50 Hz 2 or 3x 8A 2 or 3x 4.6AN-ALTi-VS408-2 or 3 pumps...T4 2 or 3x 2.4 16 bar 400V-3~50 Hz 2 or 3x 8.5A 2 or 3x 4.9AN-ALTi-VS409-2 or 3 pumps...T4 2 or 3x 2.69 16 bar 400V-3~50 Hz 2 or 3x 9.2A 2 or 3x 5.3AN-ALTi-VS410-2 or 3 pumps...T4 2 or 3x 2.94 16 bar 400V-3~50 Hz 2 or 3x 9.7A 2 or 3x 5.6AN-ALTi-VS802-2 or 3 pumps...T4 2 or 3x 1.25 16 bar 400V-3~50 Hz 2 or 3x 4.5A 2 or 3x 2.6AN-ALTi-VS803-2 or 3 pumps...T4 2 or 3x 1.6 16 bar 400V-3~50 Hz 2 or 3x 5.4A 2 or 3x 3.1AN-ALTi-VS804-2 or 3 pumps...T4 2 or 3x 1.95 16 bar 400V-3~50 Hz 2 or 3x 6.3A 2 or 3x 3.6AN-ALTi-VS805-2 or 3 pumps...T4 2 or 3x 2.67 16 bar 400V-3~50 Hz 2 or 3x 9.2A 2 or 3x 5.3AN-ALTi-VS806-2 or 3 pumps...T4 2 or 3x 2.98 16 bar 400V-3~50 Hz 2 or 3x 9.7A 2 or 3x 5.6A

To 2900 RPM

Page 8: Hydroplus Eng 50hz

8

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-H - 2900 RPM - 200 AND 400 SERIES

Imp.gpmHftHm

70

60

50

40

30

20

10

0

60

40

20

0

206

205

204

203

η %

5 10 15

200

150

100

50

0

N-ALTi-H 200

2 POLE - 50Hz

Qm /h3 1 2 3 4

Qm /h3 1 2 3 4

Qm /h3 1 2 3 4

1

2 3 4 5 6 7 8 92

3 6 9 123

6

4

2

0

mNPSH

Number of pumps

Qm /h3

Qm /h3

70

60

50

40

30

20

10

0

60

40

20

0

406

405

404

403

200

150

100

50

0

10 15 20 25

6

4

2

01 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

2 4 6 128 10 14 16

3 6 9 2115 18 2412

N-ALTi-H 400

2 POLE - 50Hz

Imp.gpmHftHm

η %

Qm /h3

Qm /h3

Qm /h3

1

2

3

m

NPSH

Number of pumps

Qm /h3

Qm /h3

Page 9: Hydroplus Eng 50hz

9

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-H - 2900 RPM - 800 AND 1600 SERIES

50

40

30

20

10

20

0

80

60

40

0

4

3

1

2

0

20 30 40 50

25

50

60

100

125

150

175

0

803

804

805

2 1210 144 6 8

2 1210 144 6 8

2 1210 144 6 8

84 12 16 20 24 28

126 2418 30 4236

N-ALTi-H 800

2 POLE - 50Hz

Imp.gpmHftHm

η %

Qm /h3

Qm /h3

Qm /h3

mNPSH

Number of pumps

Qm /h3

Qm /h3

1

2

3

55

50

45

40

35

15

5

60

40

20

0

2,0

2,5

1,5

0

6

4

2

0

m

NPSH 1604

η % (1603)

30

25

20

10

0

180

160

140

120

100

20

40

60

80

4 8 12 16 20 24 28 32

4 8 12 16 20 24 28 32

4 8 12 16 20 24 28 32

80

0,5

1,0

8 16 24 32 40 48 56 64

12 24 36 48 60 72 84 96

1604

1603

1602

1602

1603

1604

0

10080604020

N-ALTi-H 1600

2 POLE - 50Hz

Imp.gpmHftHm

Qm /h3

Qm /h3

Qm /h3

NPSH

Number of pumps

Qm /h3

Qm /h3

1

2

3

%

kW

Page 10: Hydroplus Eng 50hz

10

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 200 AND 400 SERIES

220

200

4

180

160

140

120

100

80

60

40

20

0

80

60

40

20

4

3

1

2

0

0

217*

214*

212

210

208

207

206

205

204

203

220*

700

600

500

400

300

200

100

0

6 8 10 12 14

1 1,5 2,5 3,5 4,52 3 4

1 1,5 2,5 3,5 4,52 3 4

1 1,5 2,5 3,5 4,52 3 4

2 3 4 5 6 7 8 9

3 4,5 7,56 10,5 13,59 12

N-ALTi-V 200

2 POLE - 50Hz

Imp.gpmHftHm

η %

Qm /h3

Qm /h3

Qm /h3

1

2

3

m

NPSH

Number of pumps

Qm /h3

Qm /h3

220

200

10 15 20 25

180

160

140

120

100

80

60

40

20

0

80

60

40

20

2

3

4

1

0

0

419*

417*

414*

412

410

408

407

406

405

404

403100

200

300

400

500

600

700

0

1 76 82 3 4 5

1 76 82 3 4 5

1 76 82 3 4 5

42 6 8 10 12 14 16

64 129 18 2415 21

N-ALTi-V 400

2 POLE - 50Hz

Imp.gpmHftHm

η %

Qm /h3

Qm /h3

Qm /h3

1

2

3

m

NPSH

Number of pumps

Qm /h3

Qm /h3

Page 11: Hydroplus Eng 50hz

11

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 800 AND 1600 SERIES

220

200

180

160

140

120

100

80

60

40

20

20

0

80

60

40

0

4

3

1

2

0

819*

817*

814*

812

811

810

808

806805

804

803

807

20 30 40 50

100

200

300

400

500

600

700

0

2 1210 144 6 8

2 1210 144 6 8

2 1210 144 6 8

84 12 16 20 24 28

126 2418 30 4236

N-ALTi-V 800

2 POLE - 50Hz

Imp.gpmHftHm

η %

Qm /h3

Qm /h3

Qm /h3

1

2

3

m

NPSH

Number of pumps

Qm /h3

Qm /h3

24

6

5

7

4

3

2

1

0

10

0

20

30

40

50

60

70

80

90

100

110

120

50

0

100

150

200

250

300

350

400

36 48 60 72 84 96 108

1602

16021603160416051606160716081609

16111610

1603

1604

1605

1606

1609

1610

1611

40

200

60

80

20

4

61611

5 10 15 20 25 30

5 10 15 20 25 30

5 10 15 20 25 30

6010 20 30 40 50

9015 30 45 60 75

1608

1607

N-ALTi-V 1600

2 POLE - 50Hz

Imp.gpmHftHm

Qm /h3

Qm /h3

Qm /h3

NPSH

Number of pumps

Qm /h3

Qm /h3

1

2

3

%

kW

m

η %

Page 12: Hydroplus Eng 50hz

12

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 1800 AND 3600 SERIES

Imp.gpmHftHm

Qm /h31

2

3

m ft

kW

Number of pumps

Qm /h3

Qm /h3

N-ALTi-V 1800

2 POLE - 50Hz

%

η %

NPSH

140

120

100

80

60

40

20

20

40

60

80

0

0

2

4

6

8

0

1808

1807

1806

1805

1804

1803

1802100

200

300

400

0

0,8

25

15

8

4 6 8 10 12 14 16 18 20 22 24 26

Qm /h3 4 6 8 10 12 14 16 18 20 22 24 26

Qm /h3 4 6 8 10 12 14 16 18 20 22 24 26

8 12 16 20 24 28 32 36 40 44 48 52

12 18 24 30 36 42 48 54 60 66 72 78

0

0,6

0,4

0,2

0

25 37,5 50 62,5 75 87,5

kW

Imp.gpmHftHm

N-ALTi-V 3600

2 POLE - 50Hz

140

120

100

80

60

40

20

0

100

200

300

400

0

50 75 100 125 150 175

Qm /h31

2

3

m ft

kW

Number of pumps

Qm /h3

Qm /h3

%

η %

NPSH

20

40

60

80

0

0

2

4

6

8

1,6

25

15

8

8 12 16 20 24 28 32 36 40 44 48 52

Qm /h3 8 12 16 20 24 28 32 36 40 44 48 52

Qm /h3 8 12 16 20 24 28 32 36 40 44 48 52

16 24 32 40 48 56 64 72 80 88 96 104

24 36 48 60 72 84 96 108 120 132 144 156

0

1,2

0,8

0,4

0

kW

3602

3603

3604

3605

3606

3607

Page 13: Hydroplus Eng 50hz

13

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-V - 2900 RPM - 6000 SERIES

Imp.gpmHftHm

Qm /h3

NPSH

Number of pumps

Qm /h3

Qm /h3

1

2

3

%

kW

m

η %

N-ALTi-V 6000

2 POLE - 50Hz180

0

20

60

40

20

20

15

10

5

0

0

40

60

80

100

120

140

160

600

500

400

300

200

100

0

6

4

20

50 100 150 200

6009

6008

6007

6006

6005

6004

6003

6002

600960086007

60066005600460036002

10 20 30 40 50 60 70

Qm /h3 10 20 30 40 50 60 70

Qm /h3 10 20 30 40 50 60 70

20 40 60 80 100 120 140

30 60 90 120 150 180 210

Page 14: Hydroplus Eng 50hz

14

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-VS - 2900 RPM - 200 AND 400 SERIES

Imp.gpmHftHm

Qm /h31

2

3

WP1 210

209

208207206205

Number of pumps

Qm /h3

Qm /h3

4

350

300

250

200

150

100

50

0

100

80

60

40

20

0

1500

2000

1000

500

01 1,5 2,5 3,5 4,52 3 4

Qm /h3 1 1,5 2,5 3,5 4,52 3 4

2 3 4 5 6 7 8 9

3 4,5 7,56 10,5 13,59 12

6 8 10 12 14 16

N-ALTi-VS 200

2 POLE - 50Hz

203

202

204

202

203

204

205

206

207

208

209

210

402

403

404

405

Imp.gpmHftHm

Qm /h31

2

3

WP1

209

Number of pumps

Qm /h3

Qm /h3

4

350

300

250

200

150

100

50

0

100

80

60

40

20

0

1500

2000

2500

1000

500

01 3 4

2 6 8

3

2

4

6 9 12

5

10

15

6

12

18

7

14

21

8

Qm /h3 1 3 42 5 6 7 8

16

24

6 8 10 12 14 16

N-ALTi-VS 400

2 POLE - 50Hz

410

409

408

407

406

405

404

403

402

406

407

408

409410

Page 15: Hydroplus Eng 50hz

15

HYDROPLUS

HYDRAULIC PERFORMANCES - N-ALTi-VS - 2900 RPM - 800 SERIE

Imp.gpmHftHm

Qm /h31

2

3

WP1

209

Number of pumps

Qm /h3

Qm /h3

10

200

150

100

50

0

60

40

50

30

20

10

0

1500

2000

2500

3000

1000

500

02 4

4 8

6 12

6

12

18

8

16

24

10

20

30

12

24

36

14

Qm /h3 2 4 6 8 10 12 14

28

42

20 30 40 50

N-ALTi-VS 800

2 POLE - 50Hz

802

803

804

805

806

802

804

803

805

806

Page 16: Hydroplus Eng 50hz

16

HYDROPLUS

DIMENSIONS - N-ALTi-H SERIE - CE VERSION

*

P1

300PL

H

H1

H2

P2

TYPE Ø H L P H1 H2 P1 P2

Manifolds mm mm mm mm mm mm mm

2 PUMPS

N-ALTi-H203-2-CE-V or B-10-T4 2” 773 600 656 188 344 296 55

N-ALTi-H204-2-CE-V or B-10-T4 2” 773 600 704 188 344 344 55

N-ALTi-H205-2-CE-V or B-10-T4 2” 773 600 704 188 344 344 55

N-ALTi-H206-2-CE-V or B-10-T4 2” 773 600 728 188 344 368 55

N-ALTi-H403-2-CE-V or B-10-T4 2” 773 600 670 188 344 310 55

N-ALTi-H404-2-CE-V or B-10-T4 2” 773 600 718 188 344 358 55

N-ALTi-H405-2-CE-V or B-10-T4 2” 773 600 718 188 344 358 55

N-ALTi-H406-2-CE-V or B-10-T4 2” 773 600 742 188 344 382 55

N-ALTi-H803-2-CE-V or B-10-T4 2”1/2 773 600 713 188 352 345 63

N-ALTi-H804-2-CE-V or B-10-T4 2”1/2 773 600 773 188 352 405 63

N-ALTi-H805-2-CE-V or B-10-T4 2”1/2 773 600 773 188 352 405 63

N-ALTi-H1602-2-CE-V or B-10-T4 3” 773 600 760 188 392 383 72

N-ALTi-H1603-2-CE-V or B-10-T4 3” 773 600 760 188 392 383 72

N-ALTi-H1604-2-CE-V or B-10-T4 3” 773 600 833 198 392 428 72

3 PUMPS

N-ALTi-H203-3-CE-V or B-10-T4 2” 773 900 656 188 344 296 55

N-ALTi-H204-3-CE-V or B-10-T4 2” 773 900 704 188 344 344 55

N-ALTi-H205-3-CE-V or B-10-T4 2” 773 900 704 188 344 344 55

N-ALTi-H206-3-CE-V or B-10-T4 2” 773 900 728 188 344 368 55

N-ALTi-H403-3-CE-V or B-10-T4 2” 773 900 670 188 344 310 55

N-ALTi-H404-3-CE-V or B-10-T4 2” 773 900 718 188 344 358 55

N-ALTi-H405-3-CE-V or B-10-T4 2” 773 900 718 188 344 358 55

N-ALTi-H406-3-CE-V or B-10-T4 2” 773 900 742 188 344 382 55

N-ALTi-H803-3-CE-V or B-10-T4 2”1/2 773 900 712 188 352 345 63

N-ALTi-H804-3-CE-V or B-10-T4 2”1/2 773 900 773 188 352 405 63

N-ALTi-H805-3-CE-V or B-10-T4 2”1/2 773 900 773 188 352 405 63

N-ALTi-H1602-3-CE-V or B-10-T4 ND100* 773 900 813 188 407 398 110

N-ALTi-H1603-3-CE-V or B-10-T4 ND100* 773 900 813 188 407 398 110

N-ALTi-H1604-3-CE-V or B-10-T4 ND100* 773 900 886 198 407 443 110

Page 17: Hydroplus Eng 50hz

17

HYDROPLUS

DIMENSIONS - N-ALTi-H SERIE - CA VERSION

*

P1

300PL

H

H1

H2

P2

TYPE Ø H L P H1 H2 P1 P2

Manifolds mm mm mm mm mm mm mm

2 PUMPS

N-ALTi-H203-2-CA-V or B-10-T4 2” 773 600 759 188 344 310 55

N-ALTi-H204-2-CA-V or B-10-T4 2” 773 600 807 188 344 358 55

N-ALTi-H205-2-CA-V or B-10-T4 2” 773 600 807 188 344 358 55

N-ALTi-H206-2-CA-V or B-10-T4 2” 773 600 831 188 344 382 55

N-ALTi-H403-2-CA-V or B-10-T4 2” 773 600 773 188 344 310 55

N-ALTi-H404-2-CA-V or B-10-T4 2” 773 600 821 188 344 358 55

N-ALTi-H405-2-CA-V or B-10-T4 2” 773 600 821 188 344 358 55

N-ALTi-H406-2-CA-V or B-10-T4 2” 773 600 845 188 344 382 55

N-ALTi-H803-2-CA-V or B-10-T4 2”1/2 773 600 813 188 352 345 63

N-ALTi-H804-2-CA-V or B-10-T4 2”1/2 773 600 876 188 352 405 63

N-ALTi-H805-2-CA-V or B-10-T4 2”1/2 773 600 876 188 352 405 63

N-ALTi-H1602-2-CA-V or B-10-T4 3” 773 600 863 188 392 372 72

N-ALTi-H1603-2-CA-V or B-10-T4 3” 773 600 863 188 392 372 72

N-ALTi-H1604-2-CA-V or B-10-T4 3” 773 600 908 198 392 372 72

3 PUMPS

N-ALTi-H203-3-CA-V or B-10-T4 2” 773 900 759 188 344 310 55

N-ALTi-H204-3-CA-V or B-10-T4 2” 773 900 807 188 344 358 55

N-ALTi-H205-3-CA-V or B-10-T4 2” 773 900 807 188 344 358 55

N-ALTi-H206-3-CA-V or B-10-T4 2” 773 900 831 188 344 382 55

N-ALTi-H403-3-CA-V or B-10-T4 2” 773 900 773 188 344 310 55

N-ALTi-H404-3-CA-V or B-10-T4 2” 773 900 821 188 344 358 55

N-ALTi-H405-3-CA-V or B-10-T4 2” 773 900 821 188 344 358 55

N-ALTi-H406-3-CA-V or B-10-T4 2” 773 900 845 188 344 382 55

N-ALTi-H803-3-CA-V or B-10-T4 2”1/2 773 900 813 188 352 345 63

N-ALTi-H804-3-CA-V or B-10-T4 2”1/2 773 900 876 188 352 405 63

N-ALTi-H805-3-CA-V or B-10-T4 2”1/2 773 900 876 188 352 405 63

N-ALTi-H1602-3-CA-V or B-10-T4 ND100* 773 900 916 188 392 372 100

N-ALTi-H1603-3-CA-V or B-10-T4 ND100* 773 900 916 188 392 372 100

N-ALTi-H1604-3-CA-V or B-10-T4 ND100* 773 900 961 198 392 472 100

Page 18: Hydroplus Eng 50hz

18

HYDROPLUS

DIMENSIONS - N-ALTi-V OR VS SERIE - CE VERSION

P1

300

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V or VS 203-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 204-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 205-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 206-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 207-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 208-2-CE-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-VS 209-2-CE-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V 210-2-CE-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V 212-2-CE-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V or VS 403-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 404-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 405-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 406-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 407-2-CE-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 408-2-CE-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V or VS 410-2-CE-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V 412-2-CE-V or B-16-T4 2” 1320 600 610 100 550

3 PUMPS

N-ALTi-V or VS 203-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 204-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 205-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 206-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 207-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 208-3-CE-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-VS 209-3-CE-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V 210-3-CE-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V 212-3-CE-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V or VS 403-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 404-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 405-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 406-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 407-3-CE-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 408-3-CE-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V or VS 410-3-CE-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V or VS 412-3-CE-V or B-16-T4 2” 1320 900 610 100 550

Page 19: Hydroplus Eng 50hz

19

HYDROPLUS

DIMENSIONS - N-ALTi-V OR VS SERIE - CA VERSION

P1

300

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V or VS 203-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 204-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 205-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 206-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 207-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 208-2-CA-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-VS 209-2-CA-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V 210-2-CA-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V 212-2-CA-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V or VS 403-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 404-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 405-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 406-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 407-2-CA-V or B-16-T4 2” 1150 600 610 100 550

N-ALTi-V or VS 408-2-CA-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V or VS 410-2-CA-V or B-16-T4 2” 1320 600 610 100 550

N-ALTi-V 412-2-CA-V or B-16-T4 2” 1320 600 610 100 550

3 PUMPS

N-ALTi-V or VS 203-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 204-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 205-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 206-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 207-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 208-3-CA-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-VS 209-3-CA-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V 210-3-CA-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V 212-3-CA-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V or VS 403-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 404-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 405-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 406-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 407-3-CA-V or B-16-T4 2” 1150 900 610 100 550

N-ALTi-V or VS 408-3-CA-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V or VS 410-3-CA-V or B-16-T4 2” 1320 900 610 100 550

N-ALTi-V or VS 412-3-CA-V or B-16-T4 2” 1320 900 610 100 550

Page 20: Hydroplus Eng 50hz

20

HYDROPLUS

DIMENSIONS - N-ALTi-V OR VS SERIE - CE VERSION

*

**

P1

450

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-VS 802-2-CE-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 803-2-CE-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 804-2-CE-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 805-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V or VS 806-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 807-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 808-2-CE-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 810-2-CE-V or B-16-T4 2”1/2 1450 600 717 130 640N-ALTi-V 811-2-CE-V or B-16-T4 2”1/2 1450 600 717 130 640N-ALTi-V 812-2-CE-V or B-16-T4 2”1/2 1450 600 717 130 640N-ALTi-V 1603-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1604-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1605-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1606-2-CE-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1607-2-CE-V or B-16-T4 3” 1450 600 745 140 656N-ALTi-V 1608-2-CE-V or B-16-T4 3” 1450 600 745 140 656N-ALTi-V 1609-2-CE-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1610-2-CE-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1611-2-CE-V or B-16-T4 3” 1223** 600 745 140 656

3 PUMPS

N-ALTi-VS 802-3-CE-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 803-3-CE-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 804-3-CE-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 805-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V or VS 806-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 807-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 808-3-CE-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 810-3-CE-V or B-16-T4 2”1/2 1450 900 717 130 640N-ALTi-V 811-3-CE-V or B-16-T4 2”1/2 1450 900 717 130 640N-ALTi-V 812-3-CE-V or B-16-T4 2”1/2 1450 900 717 130 640N-ALTi-V 1603-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1604-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1605-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1606-3-CE-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1607-3-CE-V or B-16-T4 ND100* 1450 900 906 140 686N-ALTi-V 1608-3-CE-V or B-16-T4 ND100* 1450 900 906 140 686N-ALTi-V 1609-3-CE-V or B-16-T4 ND100* 1150** 900 906 140 686N-ALTi-V 1610-3-CE-V or B-16-T4 ND100* 1150** 900 906 140 686N-ALTi-V 1611-3-CE-V or B-16-T4 ND100* 1223** 900 906 140 686

** For these boosters, the unit is

positioned on the discharge side

(rotating of bracket by 180°).

Page 21: Hydroplus Eng 50hz

21

HYDROPLUS

DIMENSIONS - N-ALTi-V OR VS SERIE - CA VERSION

P1

450

PL

H

H1

*

**

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-VS 802-2-CA-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 803-2-CA-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 804-2-CA-V or B-16-T4 2”1/2 1150 600 717 130 640N-ALTi-V or VS 805-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V or VS 806-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 807-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 808-2-CA-V or B-16-T4 2”1/2 1320 600 717 130 640N-ALTi-V 810-2-CA-V or B-16-T4 2”1/2 1470 600 717 130 640N-ALTi-V 811-2-CA-V or B-16-T4 2”1/2 1470 600 717 130 640N-ALTi-V 812-2-CA-V or B-16-T4 2”1/2 1470 600 717 130 640N-ALTi-V 1603-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1604-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1605-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1606-2-CA-V or B-16-T4 3” 1320 600 745 140 656N-ALTi-V 1607-2-CA-V or B-16-T4 3” 1470 600 745 140 656N-ALTi-V 1608-2-CA-V or B-16-T4 3” 1470 600 745 140 656N-ALTi-V 1609-2-CA-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1610-2-CA-V or B-16-T4 3” 1150** 600 745 140 656N-ALTi-V 1611-2-CA-V or B-16-T4 3” 1223** 600 745 140 656

3 PUMPS

N-ALTi-VS 802-3-CA-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 803-3-CA-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 804-3-CA-V or B-16-T4 2”1/2 1150 900 717 130 640N-ALTi-V or VS 805-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V or VS 806-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 807-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 808-3-CA-V or B-16-T4 2”1/2 1320 900 717 130 640N-ALTi-V 810-3-CA-V or B-16-T4 2”1/2 1470 900 717 130 640N-ALTi-V 811-3-CA-V or B-16-T4 2”1/2 1470 900 717 130 640N-ALTi-V 812-3-CA-V or B-16-T4 2”1/2 1470 900 717 130 640N-ALTi-V 1603-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1604-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1605-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1606-3-CA-V or B-16-T4 ND100* 1320 900 906 140 686N-ALTi-V 1607-3-CA-V or B-16-T4 ND100* 1470 900 906 140 686N-ALTi-V 1608-3-CA-V or B-16-T4 ND100* 1470 900 906 140 686N-ALTi-V 1609-3-CA-V or B-16-T4 ND100* 1470 900 906 140 686N-ALTi-V 1610-3-CA-V or B-16-T4 ND100* 1150** 900 906 140 686N-ALTi-V 1611-3-CA-V or B-16-T4 ND100* 1223** 900 906 140 686

** For these boosters, the unit is

positioned on the discharge side

(rotating of bracket by 180°).

Page 22: Hydroplus Eng 50hz

22

HYDROPLUS

DIMENSIONS - N-ALTi-V OR VS SERIE - CV VERSION

P1

300

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V or VS 203-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 204-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 205-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 206-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 207-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 208-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-VS 209-2-CV-V or B-16-T4 2” 1830 600 610 100 550

N-ALTi-V 210-2-CV-V or B-16-T4 2” 1830 600 610 100 550

N-ALTi-V 212-2-CV-V or B-16-T4 2” 1830 600 610 100 550

N-ALTi-V or VS 403-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 404-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 405-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 406-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 407-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 408-2-CV-V or B-16-T4 2” 1630 600 610 100 550

N-ALTi-V or VS 410-2-CV-V or B-16-T4 2” 1830 600 610 100 550

N-ALTi-V 412-2-CV-V or B-16-T4 2” 1830 600 610 100 550

3 PUMPS

N-ALTi-V or VS 203-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 204-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 205-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 206-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 207-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 208-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-VS 209-3-CV-V or B-16-T4 2” 1830 900 610 100 550

N-ALTi-V 210-3-CV-V or B-16-T4 2” 1830 900 610 100 550

N-ALTi-V 212-3-CV-V or B-16-T4 2” 1830 900 610 100 550

N-ALTi-V or VS 403-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 404-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 405-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 406-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 407-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 408-3-CV-V or B-16-T4 2” 1630 900 610 100 550

N-ALTi-V or VS 410-3-CV-V or B-16-T4 2” 1830 900 610 100 550

N-ALTi-V 412-3-CV-V or B-16-T4 2” 1830 900 610 100 550

Page 23: Hydroplus Eng 50hz

23

HYDROPLUS

DIMENSIONS - N-ALTi-V OR VS SERIE - CV VERSION

P1

450

PL

H

H1

*

**

** For these boosters, the unit is

positioned on the discharge side

(rotating of bracket by 180°).

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V or VS 803-2-CV-V or B-16-T4 2”1/2 1630 600 717 130 640N-ALTi-V or VS 804-2-CV-V or B-16-T4 2”1/2 1630 600 717 130 640N-ALTi-V or VS 805-2-CV-V or B-16-T4 2”1/2 1630 600 717 130 640N-ALTi-V or VS 806-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 807-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 808-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 810-2-CV-V or B-16-T4 2”1/2 1830 600 717 130 640N-ALTi-V 811-2-CV-V or B-16-T4 2”1/2 1630** 600 717 130 640N-ALTi-V 812-2-CV-V or B-16-T4 2”1/2 1630** 600 717 130 640N-ALTi-V 1603-2-CV-V or B-16-T4 3” 1630 600 745 140 656N-ALTi-V 1604-2-CV-V or B-16-T4 3” 1830 600 745 140 656N-ALTi-V 1605-2-CV-V or B-16-T4 3” 1830 600 745 140 656N-ALTi-V 1606-2-CV-V or B-16-T4 3” 1830 600 745 140 656N-ALTi-V 1607-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1608-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1609-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1610-2-CV-V or B-16-T4 3” 1630** 600 745 140 656N-ALTi-V 1611-2-CV-V or B-16-T4 3” 1630** 600 745 140 656

3 PUMPS

N-ALTi-V or VS 803-3-CV-V or B-16-T4 2”1/2 1630 900 717 130 640N-ALTi-V or VS 804-3-CV-V or B-16-T4 2”1/2 1630 900 717 130 640N-ALTi-V or VS 805-3-CV-V or B-16-T4 2”1/2 1630 900 717 130 640N-ALTi-V or VS 806-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 807-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 808-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 810-3-CV-V or B-16-T4 2”1/2 1830 900 717 130 640N-ALTi-V 811-3-CV-V or B-16-T4 2”1/2 1630** 900 717 130 640N-ALTi-V 812-3-CV-V or B-16-T4 2”1/2 1630** 900 717 130 640N-ALTi-V 1603-3-CV-V or B-16-T4 ND100* 1630 900 906 140 686N-ALTi-V 1604-3-CV-V or B-16-T4 ND100* 1830 900 906 140 686N-ALTi-V 1605-3-CV-V or B-16-T4 ND100* 1830 900 906 140 686N-ALTi-V 1606-3-CV-V or B-16-T4 ND100* 1830 900 906 140 686N-ALTi-V 1607-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1608-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1609-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1610-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686N-ALTi-V 1611-3-CV-V or B-16-T4 ND100* 1630** 900 906 140 686

Page 24: Hydroplus Eng 50hz

24

HYDROPLUS

DIMENSIONS - N-ALTi-V SERIE - CE VERSION

P1

450

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V 1802-2-CE-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1803-2-CE-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1804-2-CE-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1805-2-CE-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1806-2-CE-V or B-16-T4 3” 1320 600 880 140 790

3 PUMPS

N-ALTi-V 1802-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1803-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1804-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1805-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1806-3-CE-V or B-16-T4 ND100 1320 900 1020 140 800

Page 25: Hydroplus Eng 50hz

25

HYDROPLUS

DIMENSIONS - N-ALTi-V SERIE - CA VERSION

P1

450

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V 1802-2-CA-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1803-2-CA-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1804-2-CA-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1805-2-CA-V or B-16-T4 3” 1320 600 880 140 790

N-ALTi-V 1806-2-CA-V or B-16-T4 3” 1320 600 880 140 790

3 PUMPS

N-ALTi-V 1802-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1803-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1804-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1805-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800

N-ALTi-V 1806-3-CA-V or B-16-T4 ND100 1320 900 1020 140 800

Page 26: Hydroplus Eng 50hz

26

HYDROPLUS

DIMENSIONS - N-ALTi-V SERIE - CE VERSION

P1

500

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V 3602-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3603-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3604-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3605-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3606-2-CE-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 6002-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6003-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6004-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6005-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6006-2-CE-V or B-16-T4 ND125 1175 1700 1160 170 900

3 PUMPS

N-ALTi-V 3602-3-CE-B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3603-3-CE-B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3604-3-CE-B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3605-3-CE-B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3606-3-CE-B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 6002-3-CE-B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6003-3-CE-B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6004-3-CE-B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6005-3-CE-B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6006-3-CE-B-16-T4 ND150 1175 2200 1220 170 930

Page 27: Hydroplus Eng 50hz

27

HYDROPLUS

DIMENSIONS - N-ALTi-V SERIE - CA VERSION

P1

500

PL

H

H1

TYPE Ø H L P H1 P1

Manifolds mm mm mm mm mm

2 PUMPS

N-ALTi-V 3602-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3603-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3604-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3605-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 3606-2-CA-V or B-16-T4 ND100 1175 1700 1160 170 940

N-ALTi-V 6002-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6003-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6004-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6005-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900

N-ALTi-V 6006-2-CA-V or B-16-T4 ND125 1175 1700 1160 170 900

3 PUMPS

N-ALTi-V 3602-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3603-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3604-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3605-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 3606-3-CA-V or B-16-T4 ND125 1175 2200 1210 170 970

N-ALTi-V 6002-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6003-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6004-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6005-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930

N-ALTi-V 6006-3-CA-V or B-16-T4 ND150 1175 2200 1220 170 930

Page 28: Hydroplus Eng 50hz

28

HYDROPLUS

RECOMMENDED ACCESSORIES

• Direct water supply bypass when the public water system

pressure is insufficient.

(Accessory reference: BP)

• Anti-vibration sleeves.

(Accessory reference: M)

• Counter flanges, supplied by 2.

(Accessory reference: CB)

• Isolating valves.

(Accessory reference: V)

FEATURES

a) Installation

- On smooth floor or a concrete block with attachment by anchor

bolts.

- Connection of suction and discharge manifolds, either on right or

left as desired.

b) Packaging

On pallet.

53 bd de la République - Espace Lumière - Bât. 6 - 78403 Chatou Cedex FRANCE

Tel: +33 (0)1 30 09 82 39 - Fax: +33 (0)1 30 09 82 34 - www.salmson.com