1/43
11
MCC PRESENTATION - GMPMCC PRESENTATION - GMP
MANUFACTURINGMANUFACTURING
ENVIRONMENTSENVIRONMENTS
Presented by :Presented by :
Deryck Smith Consulting EngineersDeryck Smith Consulting Engineers
Module 4
-
8/8/2019 HVAC4_0506
2/43
22
GMPGMP Manufacturing EnvironmentsManufacturing Environments
Air Handling SystemsAir Handling Systems
HVAC SystemsHVAC Systems
HHeatingeating
VVentilationentilation
AAirir CConditioningonditioning
ModuleModule 44:: Pressure Cascades &Pressure Cascades &
Building LayoutsBuilding Layouts
-
8/8/2019 HVAC4_0506
3/43
33
GMPGMP
Manufacturing EnvironmentsManufacturing Environments
Topics for this Module:
1. The integration of air conditioning systems andbuilding layouts.
2. The requirements for pressure cascades and howto achieve them.
3. How building finishes and plant componentsaffect facility cleanliness.
4. Pharmaceutical Equipment
-
8/8/2019 HVAC4_0506
4/43
44
Inter-dependenceInter-dependence of Airof Air
Handling SystemHandling System
s & Buildingss & Buildings
Building layouts, Pressure cascades,
Air handling systems andPharmaceutical equipment are all
inter-related.
No one can exist without the other.
-
8/8/2019 HVAC4_0506
5/43
55
What is a PressureWhat is a Pressure
Cascade?Cascade?Pressure Cascade
A process whereby air flows from the cleanest area,
which is maintained at the highest pressure to a less
clean area at a lower pressure.
-
8/8/2019 HVAC4_0506
6/43
66
What Is the Purpose of aWhat Is the Purpose of a
Pressure Cascade?Pressure Cascade?
Helps prevent cross-contamination between adjacent
areas.
Helps prevent ingress of contaminants from outside.
Is used to enhance separation between areas of different
cleanliness.
The unit of measurement for pressure is the PASCAL (Pa)
-
8/8/2019 HVAC4_0506
7/43
77
Air Pressure CascadeAir Pressure Cascade
D i r t y E n v i r o n
A m b i e n t P r e s
1 5 P a P r e s s
D i f f e r e n t i a
L e s s C l e a n E n v i r o
L o w e r P r e s s u r
1 5 P a P r e s s u
D i f f e r e n t i a l
C l e a n e s t E n v i r o n
H i g h e s t R o o m P r
-
8/8/2019 HVAC4_0506
8/43
88
Measuring the Air PressureMeasuring the Air Pressure
CascadeCascadeThe pressure differential over the doorway isThe pressure differential over the doorway ismeasured with a portable magnahelic gauge or micromeasured with a portable magnahelic gauge or micro
manometer.manometer.
Permanently installedgauges are preferred.
-
8/8/2019 HVAC4_0506
9/43
99
Room Pressure & AirRoom Pressure & Air
MovementMovement A room pressure cascade system forces air toA room pressure cascade system forces air to
flow from clean areas to less-clean areas.flow from clean areas to less-clean areas.
Directional air movement helps carry
contaminants away from a critical process.
Air movement, such as laminar flow (UDAF) over
the product, protects the product. (aseptic packing / filling)
-
8/8/2019 HVAC4_0506
10/43
1010
Typical OSD Plant :Typical OSD Plant :
Cross-contamination ProtectionCross-contamination Protection
What should the room pressures be ?
T A B L E T S
C O M P R .
T A B L E T S
C O M P R .
E N C A P S U L A
P R O D U C T I O N C O R R I D O
A I R
L O C K
1 5 P a 1 5 P a 1 5 P a
1 5 P a
3 0 P
-
8/8/2019 HVAC4_0506
11/43
1111
Dispensary LayoutDispensary Layout
M A T E R E A L SF R O M W A R E H O U S
W E I G H E D M A TT O P R O D U C T I
S T A G I N G A R E A
W E I G HB O O T H 2
W E I G HB O O T H 1
Is this a good layout ? PIC/S PH 1/97 (Rev.3) #3.3 & 3.12
-
8/8/2019 HVAC4_0506
12/43
1212
Improved DispensaryImproved Dispensary
LayoutLayout
What should the room pressures be ?
P R E - W E I G H
S T A G I N GP O S T - W E I G H
S T A G I N G
W E I G H
B O O T H 1
W E I G H
B O O T H 2
U N I - D I R E C T I O N A L
A I R F L O W
U N I - D I R E C T I O N A L
A I R F L O WM A T E R E A L S
F R O M
W A R E H O U S E
W E I G H E D
M A T E R I A L
P R O D U C T
1 0 P a 2 0 P a 3 0 P a
2 0 P
Airflow direction
-
8/8/2019 HVAC4_0506
13/43
1313
Sampling Booth Layout (1)Sampling Booth Layout (1)
SAMPLING
BOOTH
EXTRACT
HOOD
WAREHOUSE
-
8/8/2019 HVAC4_0506
14/43
-
8/8/2019 HVAC4_0506
15/43
1515
Sampling Booth Layout (2)Sampling Booth Layout (2)
SAMPLINGBOOTH
UDAF
HOOD
AIR
LOCK
AIRLOCK
Step-over-bench
CHANGE
-
8/8/2019 HVAC4_0506
16/43
1616
Typical Section ThroughTypical Section Through
Sampling BooothSampling BooothR e t u r n a i r S u p p l y a i r
L a m i n a r f l o w
d i s t r i b u t o r
-
8/8/2019 HVAC4_0506
17/43
-
8/8/2019 HVAC4_0506
18/43
1818
Ablution Layout 1Ablution Layout 1
Production
Plant
ChangeRoom
ToiletsStaff
Staff
-
8/8/2019 HVAC4_0506
19/43
1919
Ablution Layout 2Ablution Layout 2
Production
Plant
ChangeRoom ToiletsStaff
Staff
-
8/8/2019 HVAC4_0506
20/43
-
8/8/2019 HVAC4_0506
21/43
2121
Protective GarmentsProtective Garments
Outside ??Outside ??
It is pointless having
a change room if it
is not used properly
-
8/8/2019 HVAC4_0506
22/43
Sterile Suite Pressure Cascade
= Room Pressure
= ISO Cleanroom Class
T = TurbulentU = Uni-directional
8
FILLING
MAC
HINE
15Pa
AUTO-CLAVES
AUTO-CLAVES
STERILEFILLING RM
FINISHED PRODUCT STAGING
MAT.
A/L
MAT.
A/L
A/L
FORMULATIONROOM
PERSONELA/L
CHANGE
A/L
STERILECHANGE
STERILESTAGING
COMPONENTPREP
6 0 P
5 0 P a
4 0 P a
4 0 P a
2 5 P a
3 0 P a
2 0 P a
2 0 P a
1 5 P a
1 5 P a
1 5 P a
1 0 P a
7
5T
67
5T
5T
6
6
7
8
8
9
5U
6/7
-
8/8/2019 HVAC4_0506
23/43
2323
Product Flow DiagramProduct Flow Diagram
DISPATCH
SECONDARYPACKING
PRIMARYPACKING
DISPENSARY
RAW MAT.RECEIPT PACK. MAT.
RECEIPT
PACK. MATSTORE
MANUFACTURING
GMP ZONE
PRIMARY PACK
MAT. CLEAN DOWN
Wood free zone
-
8/8/2019 HVAC4_0506
24/43
2424
StaffStaffflow Diagramflow Diagram
DISPATCH
SECONDARYPACKING
PRIMARYPACKING
DISPENSARY
RAW MAT.RECEIPT PACK. MAT.
RECEIPT
PACK. MATSTORE
PRODUCTION
STAFF ENTRY CANTEEN
CHANGE
GMPCHANGE
GMP ZONE
PRIMARY PACK
MAT. CLEAN DOWN
-
8/8/2019 HVAC4_0506
25/43
2525
Negative Pressure FacilitiesNegative Pressure Facilities
Required for facilities handling potentRequired for facilities handling potentcompounds such as penicillin & hormones.compounds such as penicillin & hormones.
Special precautions required to prevent productSpecial precautions required to prevent productcontamination from the atmosphere.contamination from the atmosphere.
Exhaust air must be efficiently filtered and safeExhaust air must be efficiently filtered and safefilter handling must be used.filter handling must be used.
-
8/8/2019 HVAC4_0506
26/43
2626
Safe Change FiltersSafe Change Filters
Used for filtering hazardousmaterials:
Dirty filters are removed into a
plastic bag
The bag is automatically sealedat the filter unit housingA new filter is inserted via a
plastic bag and the cover closed
At no time is the operator or
the atmosphere exposed to the
hazardous powder.
C St d P i illiCase Study Penicillin
-
8/8/2019 HVAC4_0506
27/43
2727
Case Study PenicillinCase Study Penicillin
PlantPlant
P R O D U C T I O N P A S S A G E
W E I G H
R O O M
F
IN
IS
H
E
D
G
O
O
D
S
A I R
L O C K
M
A
L
E
A
B
L
U
T
IO
N
S
G R A N U L A T I N G
S Y R U P S
F I L L I N G
S U P E R -
V I S O R
F E M A L E
C H A N G E
M A L E
C H A N G E
F E M A L E
A B L U T I O N S
P A C K I N G
P R O D U C T
S T O R EA / L
M A T
A / L
P A C K I N G
G O O D S
D R Y
P O W D E R
F I L L I N G
T A B L E T
C O M P R E S -
S I O N
S Y R U P S
P R E P A R A T I O N
W A S H
U P
M I X I N G
C A P S U L E
F I L L I N G
S T A G I N G
Add room pressures,
Cleanroom class and
comment on layout
MALE
ABLUT.
LAUNDRY
FINISH.
GOODS
C St d P i illiC St d P i illi
-
8/8/2019 HVAC4_0506
28/43
2828
Case Study PenicillinCase Study Penicillin
PlantPlant
PRODUCTION PASSAGE
-25Pa
-15Pa ROOM PRESSURE RELATIVETO AMBIENTAIR LEAKAGE DIRECTION
LEGEND
WEIGHROOM
-40Pa
F I N I S H E D
G O O D S
AIRLOCK
M A L E
A B L U T I O N S
GRANULATING SYRUPSFILLING
SUPER-
VISOR
FEMALECHANGE
MALECHANGE
FEMALEABLUTIONS
PACKING
PRODUCTSTORE
A/L
MATA/L
PACKINGGOODS
DRYPOWDERFILLING
TABLET
COMPRES-SIONSYRUPSPREPARATION
WASHUP
MIXING
CAPSULEFILLING
STAGING
-40Pa
-35Pa
-30Pa
-30Pa
-35Pa
-25Pa
-15Pa
-30Pa
-20Pa-30Pa
-10Pa -35Pa
-25Pa
-45Pa
-35Pa
-35Pa
-35Pa
-35Pa
-35Pa
-15Pa-25Pa
- 2 5 P
a
- 4 5 P
a
- 2 5 P
a
-
8/8/2019 HVAC4_0506
29/43
2929
Building Finishes:Building Finishes:
In module 1 we discussed the need for all
facility components to complement each other.
Therefore a good air handling system must
be complemented by a building of good
design and good finishes.
On the next slide we will be looking at someof the Acceptable and Un-acceptable building
finishes.
-
8/8/2019 HVAC4_0506
30/43
3030
Building FinishesBuilding FinishesNot Acceptable Acceptable
PVA Paint Epoxy or Enamel paint
Window sills Flush glazed windows
Exposed pipes Smooth surfaces
Horizontal pipes &services
Concealed services
Open floor drains Hygienic drains
Floor cracks, flakingfloor surfaces
Homogonous sealedfloors epoxy finish orwelded vinyl
Ceiling cracks &joints
Smooth sealedceilings
Exposed, open lightfittings
Flush light fittings
Wooden furniture S/Steel or Melaminefurniture
-
8/8/2019 HVAC4_0506
31/43
3131
Floors / drainsFloors / drains
Tiled Floor
Epoxy Floor
-
8/8/2019 HVAC4_0506
32/43
3232
Poor & Good WindowsPoor & Good Windows
BacteriaC
ity!!!
-
8/8/2019 HVAC4_0506
33/43
3333
Paint FinishPaint Finish
Not only buildingNot only buildingpaintwork must bepaintwork must beconsidered but alsoconsidered but alsoequipmentequipment
Is there anything wrong
with this Tablet Press?
-
8/8/2019 HVAC4_0506
34/43
3434
Building & EquipmentBuilding & Equipment
FinishesFinishes
-
8/8/2019 HVAC4_0506
35/43
3535
Services DistributionServices Distribution
Impossible to clean! Easy to clean!
KKeep a
-
8/8/2019 HVAC4_0506
36/43
3636
Keep aKeep a
BalanceBalance
Dont ignoreDont ignore
buildingbuilding
finishesfinishes
and then gooverboard onstaff dress code.
-
8/8/2019 HVAC4_0506
37/43
3737
Services DistributionServices Distribution
Where ever possible services should be located
behind wall panels
Exposed services & pipes are very difficult to
clean & sometimes impossible to clean
Equipment such as Film Coaters should be
enclosed so that only the front face is in the GMP
area. This makes cleaning much easier.
Make use of service corridors behind equipment(but must be under negative pressure)
-
8/8/2019 HVAC4_0506
38/43
3838
Split UnitSplit Unit
RETURN AIR
SUPPLY AIR
Fan liberates dust
into the air
Condensate drip tray
Cooling Coil
Poor quality
Air filter
-
8/8/2019 HVAC4_0506
39/43
3939
Fluid Bed DrierFluid Bed Drier
Is the quality of the
supply air to the FBD
correct?
What filtration is used?
Is the exhaust air filtered?
-
8/8/2019 HVAC4_0506
40/43
4040
S e r v i c e R o o m
W a r e h o u s e
A
/L
o
c
k
1
A
ir
L
o
c
k
2
A i r S h o w e r
S a m p l i n gR o o o m S e r v i c e C o r r i d o r
( c o n t a i n s V a c u u m & R O w a t e r s u p p l y )
W e i g h i n g T a b l e t 1T a b l e t 2L i q u i d s M i xS o f t g e l C a p
P a c k i n g
E m e r g e n c y
E x i t
C l e a n C o r r i d o r
E q u i p m e n t W a s h
A i r L o c k 3
S t e r i l e e y e d r o p s
d i s p e n s i n g
& a c e p t i c f i l l i n g
2 S t a g ep e r s o n n e l
e n t r y f o r
e y e d r o p s
M a l e
C h a n g e 2
M a l e
C h a n g e 1
F e m a l e
C h a n g e 1
F e m a l e
C h a n g e 2
P a c k e d
G o o d sQ u a r a n t i n e
A i r L o c k 4
P r i m a r y & S e c
P a c k i n g
Group sessionGroup session
Airlock
difi d i hM difi d L t ith
-
8/8/2019 HVAC4_0506
41/43
4141
Modified Layout withModified Layout with
CascadeCascade
S e c o n d a r y
P a c k i n g
3 0 P a
0 P a
2 0 P a 3 0 P a
0 P a0 P a
1 0 P a
1 0 P a 1 0 P a
2 0 P a2 0 P a
4 0 P a
5 0 P a
6 0 P a
5 0 P a
4 0 P a
1 5 P a
1 5 P a
P r i m a r yP a c k i n g
C h a n g e
M A L 3
A i r L o c k
3 0 P a
P o s t
S t a g i n g
3 0 P a
3 0 P a
0 P a
1 5 P a1 5 P a
2 0 P a
2 0 P a
3 0 P a
2 0 P a
0 P a
1 0 P a
S e r v i c e R o o mA i r L o c k 4
P a c k e d
G o o d sQ u a r a n t i n e
F e m a l eC h a n g e 2
F e m a l e
C h a n g e 1
M a l e
C h a n g e 1
M a l eC h a n g e 2
P A L
S t e r i l e e y e d r o p s
d i s p e n s i n g
& a s c e p t i c f i l l i n g
M A L 4
E q u i p m e n t W a s h
C l e a n C o r r i d o r E m e r g e n c
E x i t
S o f t g e l C a p
P a c k i n gL i q u i d s M i xT a b l e t 2T a b l e t 1
W e i g h
B o o t h
( c o n t a i n s V a c u u m & R O w a t e r s u p p l y )
S e r v i c e C o r r i d o r
S a m p l i n g
R o o o m
A i r S h o w e r
M
A
L
2
M
A
L
1
W a r e h o u s e
MAL = Material Air Lock
PAL = Personnel Air Lock
-
8/8/2019 HVAC4_0506
42/43
Work session: Connect the arrows
-
8/8/2019 HVAC4_0506
43/43
Product Flow DiagramProduct Flow Diagram
F/GDispatch
SecondaryPacking
PrimaryPacking
Sampling A/L
Raw Mat.Store Released
Materials
Pack Mat.Store
PharmaceuticalManufacturing
Primary Pack
Mat. Clean Down
Work session: Connect the arrows
between processes for Product
Flow and Staff Flow
Quarantine
Sampling A/L
SamplingBooth
PrimaryChange room
GMP ChangeRoom
DispensaryPre-Staging
DispensaryPost-Staging
DispensaryWeiigh Booth