Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

32
Setting the standard for comfort and efficiency for your heating and hot water system. Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717

Transcript of Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

Page 1: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

Setting the standard for comfort and efficiency for your heating and hot water system.

Heat Transfer Products, Inc.120 Braley Road

East Freetown, MA 02717

Page 2: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

USING THIS MANUAL

2

TABLE OF CONTENTS SECTION 1

General Information Pg. 3

SECTION 2Installation of your Vision I System Pg. 4

SECTION 3Wire Functions Pg. 9

SECTION 4Programming the Controller Pg. 10

SECTION 5Programming The Central Heat Curve Pg.13

SECTION 6Status Menu Pg. 15

SECTION 7Test Mode Pg. 15

SECTION 8Piping and Wiring the Vision System Pg. 17

SECTION 9Appendix Pg. 29

DANGER DANGER indicates an imminently hazardoussituation which, if not avoided, will result indeath or serious injury.

B. SPECIAL ATTENTION BOXES Throughout this manual you will see thesespecial attention boxes similar to this onewhich are intended to supplement theinstructions and make special notice ofpotential hazards. These categories are asdefined by the ANSI Z535.A Standard.

A. INSTALLATION SEQUENCE Follow the installation instructions provided inthis manual in the order shown. The order ofthese instructions has been set in order toprovide the installer with a logical sequence ofsteps that will minimize potential interferencesand maximize safety during heater installation. WARNING

WARNING indicates a potentially hazardoussituation which, if not avoided, could result indeath or serious injury.

CAUTION CAUTION Indicates a potentially hazardoussitutation which, if not avoided, may result inminor or moderate injury.

CAUTIONCAUTION used without the safety alert symbolindicates a potentially hazardous situation which,if not avoided, may result in property damage.

USING THIS MANUAL

Page 3: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

GENERAL INFORMATION

3

SECTION 1. GENERAL INFORMATIONTHE VISION I SYSTEM

You have purchased the Vision I System, which is the first truly advanced control system thateliminates the need for those expensive auxiliary controls. The Vision I System will allow the installingcontractor to take the highly efficient modulating 92% AFUE Munchkin Heater and make it even moreefficient by controlling the temperature delivered to the central heating circuits based on the outsidetemperature. The Vision I system is also a two temperature system, one temperature for CentralHeating and the other temperature to the Super Stor Ultra Indirect water heater. This allows the userto increase the temperature supplied to the Super Stor Ultra indirect water heater to get a fast recoveryby prioritizing the flow at a higher temperature than may be needed for the Central Heating Circuits(this will require two separate circulators). Once the Super Stor Ultra Indirect is satisfied, the Vision Isystem will switch back to the Central Heating Circuit to continue to heat the living space at atemperature based on outside temperature. This gives you a higher comfort level and further increasesthe efficiency of the Munchkin Heater. Details within this manual will show you the proper piping andwiring of the Vision I System. Only factory authorized trained contractors are qualified to install theVision I system to assure quality of the installation for each system. If you have any questions, pleasecall your factory representative or call technical service line at 1-800-323-9651.

SYSTEM OPERATION

Modulation during the central heating operation is based on the supply temperature. The set pointused for the control depends upon the programmed central heating curve. The slope of the heatingcurve can be changed by the installer of the Munchkin in the sense that both turning points of thecurve can be moved. If the outside temperature sensor is not connected, the set point is the user setpoint for the central heating. When the heater calls for heat, a minimum “burner on” time is defined.If, during this time the temperature exceeds the set point temperature, the burner will remain fireduntil the timer has ended. This is done to give the heater a chance to start modulating after ignition.This can be very useful in cases where there is a low heat request.

As soon as the supply temperature exceeds the set point of the central heating curve or user setpoint, the burner will switch off. The circulator will continue to run (Note: This will occur only if ther-mostats are calling). The anti-cycling time begins at the completion of a heating cycle (either the indi-rect fired water heater or central heat.) There is a one minute anti-cycling time that prevents theburner from coming on unless there is a call from either the indirect fired water heater or centralheat. The purpose of the anti-cycling feature is to prevent the burner from erratic cycling. Regulationis based upon set point central heating. The maximum capacity of the Munchkin can be limited bystep modulation. The Munchkin has a 6-step function programmed into the controller. (Note: This 6-step function cannot be changed.) When the Munchkin burner is activated, the burner output is reg-ulated in one minute intervals. As shown in the chart, Section 9, Fig. 9.2, Appendix. Note: These per-centages are based on the rated maximum output. This feature helps the Munchkin from over-shooting the heat set point and minimizes short cycling. As soon as the central heating is active(including pre-purge), step modulation begins. When in operation, the step will be increased. Oncethe heating demand is satisfied the step modulation will start from the beginning of its cycle.

The Vision I also has a Fault Code Alarm Output. This is activated if the Munchkin Boiler goes into alockout. The Fault Code Alarm wire is rated at 3 amp max. and is connected to the main controlboard of the Munchkin Boiler. This alarm can be connected to an external relay or an audible alarm.

Page 4: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

4

GENERAL INFORMATION / INSTALLATION

PARTS INCLUDED IN THE VISION I SYSTEM

1. Outside sensor 1 Pc 7250P-319

2. Indirect Tank Sensor 1 Pc. 7250P-325

3. Light green wires 2 Pcs. (Outdoor Sensing)

4. Light blue wires 2 Pcs. (Indirect sensor or standard 4080b-1395 control)

5. Purple wire 1 Pc. (Hot Lead for the 120 Volt connection to the Indirect circulator,)

6. Pink wire 1 pc. (Neutral lead for the 120 volt connection to the Indirect circulator)

7. Green wire 1 Pc. (Ground lead for the 120 volt connection to the Indirect circulator)

8. Red Wire 1 Pc. (Hot Lead for the 120-volt connection to the fault code alarm)

9. Installation Manual 1 Pc.

10. Warranty Registration Card

Note: Only Products Manufactured by Heat Transfer Products will be covered under this warranty.

SECTION 2. INSTALLATION OF YOUR VISION I SYSTEMYou must use the wires supplied by Heat Transfer Products to connect your Vision I system to yourexisting Munchkin control. You may choose to leave out some connections that you may not need inyour installation. Follow the diagram to connect the individual wire leads into the correct Molex toactivate the designated functions on the main control board. Listed below is an explanation for theindividual wire functions. (When making the connection, be sure that the black marking on the wireconnector is facing upward as shown in the illustration shown in Fig. 2-1 this section.) You will notethat there are two different types of connections.

1. 24 volt connections – 2 Pcs. light green wire leads (outdoor sensor) / 2 Pcs. light blue leads(Indirect Fired Water Heater sensor).

2. 120 volt connection – Purple (Neutral lead to DHW Circulator) and Pink (Hot lead to DHWCirculator) Green (Ground Lead to DHW Circulator) and Red (Hot lead to Fault Code Alarm).

It is also important to note that the standard Munchkin comes with a 120 volt connection for the CentralHeating Circulator and 2 gray wires for the Central Heating thermostat connection to the MunchkinBoiler. Install the wires based on the color diagrams, Figs. 2-1, 2-2 and Figs. 2-3 and 2-4 in this sectionshowing the open port connection on the Molex Plug which will show where the wire will be connectedto the appropriate Molex Port Connections.

(See Resistance table in theAppendix Section 9)

Page 5: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

INSTALLATION

5

Fig. 2-2

Fig. 2-1

VISION CONNECTIONS AS VIEWED FROM THE FRONT ON A 140/199M MUNCHKIN

VISION CONNECTIONS AS VIEWED FROM THE FRONT ON A T50/T80M/80M MUNCHKIN

Page 6: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

INSTALLATION

6

Fig. 2-3: Vision I Molex and Color Wire Connections

VISION I – MUNCHKIN WITH SPARK IGNITION

NOTE: Vision One connections are outlined in black.

Page 7: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

INSTALLATION

7

Fig. 2-4: Vision I Molex and Color Wire Connections for “HA” models

VISION I – MUNCHKIN WITH HOT SURFACE IGNITION

NOTE: Vision One connections are outlined in black.

Page 8: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

INSTALLATION

8

Fig. 2-5: Vision I Routing Connection

Page 9: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

9

WIRE FUNCTIONS

SECTION 3. WIRE FUNCTIONS1. Outdoor Sensor (2-Light Green Wires) are connected to the main controller on the Munchkin.

Route wires from the Munchkin control to the external junction box, to your outdoor sensor, which willallow the user to change the temperature going to the Central Heating loop automatically. Place theoutdoor sensor preferably to the north or northwest or to the side which will be affected by changingweather conditions outside. NOTE: Do not locate the sensor in the direct sunlight.

Outdoor Sensor Function: The user can program the desired supply temperature based onthe heat transmitter (Baseboard, Radiant Floor, Air Handler) that will be used in the installation.Once the outdoor sensor (Light Green Wires) is connected to the heater, the water temperatureof the heater will adjust to run the heater more efficiently and provide greater comfort to the liv-ing space. See section 4: “Programming the Controller”.

Connection Specification – Wire 22 AWG maximum to 100 feet or 18 AWG up to 150feet. Length of wire run cannot exceed 150 feet.

22.. Indirect Sensor (2-Light Blue Wires) are connected to the main control on the Munchkin.Route wires from the Munchkin control to the external junction box to the sensor (Included inThe Vision I Package) or the mechanical control Honeywell Part # L4080b-1395 (Not included inVision I Package) into the control well located in the front of the Super Stor Ultra Indirect FiredWater Heater. This will allow the installer to control the temperature of the indirect from theMunchkin and give the Super Stor Indirect Fired Water Heater priority over the Central HeatingCircuit. Once the Water Heater is satisfied, the Munchkin will then switch back to the CentralHeating Circuit only if there is a call for heat, otherwise the Munchkin will then shut down.

Indirect Sensor Function: The Maximum run time on priority function for the Super Stor UltraIndirect Fired Water Heater is from 1-60 minutes. The Super Stor Ultra tank temperature can only beadjusted when using a sensor (not a mechanical control). Temperature adjustments are from 95 to185 degrees, plus a differential 1-18 degrees (Note: It is recommend that you do not exceed 5 min-utes on the DHW pump post purge cycle to avoid cooling down your DHW tank). See section 4,“Programming the Controller”.

Connection Specification – Wire 22 AWG maximum to 100 feet or 18 AWG up to 150feet. Length of wire run cannot exceed 150 feet.

3. Indirect Circulator Lead (1-Pink Wires/1-Purple Wires/1-Green Wires) areconnected to the main controller on the Munchkin. Route wires from the Munchkin control tothe external junction box. Run the wire and connect it directly to the Super Stor Ultra Indirectcirculating pump. The purple wire will be your neutral lead and the pink wire will be your hot.This will supply 120 volts to the Super Stor Ultra Indirect Water Heater Circulator directly (TheCirculator is not supplied in the Vision-1 the Package).

Indirect Circulator Program function: The Super Stor Ultra Indirect circulator program functionwill automatically start when the Super Stor Ultra sensor reads a call for heat, the installer can alsoprogram the post purge function on the circulator. The Post purge circulator function ranges from 1-30 minutes. Connection Specification – Wire 18 AWG maximum. Length of wire run cannot exceed100 feet.

CAUTION The wire to outdoor sensor must not be laid closer than 6' to line voltage wiring

(120/240 V) and must never be in the same conduit.

Page 10: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

4. Fault Code Alarm Output (1-Red Wire) is connected to the main controller on theMunchkin. Route wire from the Munchkin controller to an external relay or an audible alarm.The red wire will be your hot lead supplying 120 volts. The neutral connection will be connectedto the neutral on the incoming power to the Munchkin.

Connection Specification – Wire 18 AWG maximum. Length of wire run cannot exceed100 feet.

SECTION 4. PROGRAMMING THE CONTROLLER

WIRE FUNCTIONS / PROGRAMMING THE CONTROLLER

10

Fig. 3-1

CAUTIONDo not tie neutrals or hot wire leads to any other wires, go directly from theMunchkin controller to the circulator. It is also important to note that the Munchkincontroller is fused up to 6.3 Amps. The Munchkin requires 2.0 amps or 3.0 amps (HAmodels only). If electrical requirements of either the Indirect circulator or the CentralHeating Pump exceeds the 4.0 amps limit or 3.0 amps on (HA Models Only), pleasefollow the wiring diagram Fig. 3-1, this page, to wire a relay if your circulators exceedload requirements.

CAUTION Only Vision I contractors are authorized to program the individual settings on theVision I. A pass code must be entered in order to get to the Programming Menu. ThisPass code may change. Only Vision dealers will know where to locate the pass code.The Standard Munchkin Heater can only be upgraded to a Vision I by a Vision dealer.

Page 11: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

The Vision I Dealer is the only one qualified to set the system limits and the heat curve for the MunchkinHeater. These system limits cannot be changed by anyone except an authorized Vision dealer oncethey are programmed. The Munchkin owner can make adjustments only to the hot water set point, thecentral heating differential and central heating temperature.

Programming the Vision I system is quite simple, it is recommend that you write down the settings onthe Control Program Reference Chart provided in section 5 Fig. 4-3 for future reference. All thefunctions featured can be programmed right from the display located inside the Munchkin Heater.

VISION 1 PROGRAM ACCESS

To start, press down and hold the S/3 and S/4 simultaneously for three seconds. You will notice thatthe display will change to 000 . Then, with your S1/- key on the display press down until you see925 . This is the pass code. To confirm that the pass code is correct, you will need to press and holdthe S3/Program for 1 second to confirm. If the pass code is entered incorrectly, the controller programfunction will be cancelled and the control returns to normal operation. If the code is entered correctly,the control will switch off the gas valve and purge fan while showing a solid – – – in the display. Thedisplay will than show a 1 alternating to de . This first function verifies that the control will addressthe requirements of the Superstor Indirect Fired Water Heater.

VISION 1 PROGRAM NAVIGATION

Next you will have to press the S/3 key to move through each function. To increase or decrease avalue, you will need to press either the S/1- key or S/2+ key to change the default values. If there isno key action for 1 minute, the display returns to normal operation. Changes are effective immediatelybut not directly stored until the S/4 key is pressed down for 3 seconds then the new values are stored.

Listed below are the variety of functions the installer can program into the Vision I System.

Function Default Value Function Description

1 de Not Applicable

2 149ºF Not Applicable

3 185ºF Maximum Domestic Delivery Water Temperature Setpoint theInstaller will program for SuperStor Indirect Fired Water Heater(Note: Does not apply if used with Mechanical Control) Range:95ºF to 185ºF

4 36ºF Not Applicable

5 7ºF Allows the installer to change the differential in the Indirect FiredWater Heater (Does not apply if used with a Mechanical Control)Range: 1ºF to 18ºF

6 0 Minutes Allows the installer to change the Indirect Circulator Post PurgeTime once the sensor is satisfied (NOTE: it is recommend thatCirculator Post Purge Time be set no greater than 5 minutes).Range: 0 to 60 minutes

7 68ºF Outdoor temperature that you wish the central heating should bedisabled—(warm weather shut-off) Range: 41ºF to 122ºF

11

PROGRAMMING THE CONTROLLER

CAUTION The Heater cannot be programmed while there is a call for heat.

Page 12: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

Function Default Value Function Description

*8 5ºF Allows the installer to change the Minimum Outside DesignTemperature. Range: –49ºF to 32ºF (See the chart on page 14,Fig. 5-1 to set outdoor reset curve)

*9 201ºF Allows the installer to change the Design Supply Water Temperaturefrom the Munchkin based on the Minimum Outside DesignTemperature (See the chart on page 14, Fig. 5-1 to set outdoor resetcurve) Range: 203ºF to 77ºF

*10 68ºF Allows the installer to change the Maximum Outside DesignTemperature for Central Heating. (See the chart on page 14, Fig.5-1 to set outdoor reset curve) Range: 95ºF to 32ºF

*11 95ºF Allows the installer to change the Design Supply WaterTemperature from the Munchkin based on the Maximum OutsideDesign Temperature. (See Fig. 5-1 on page 14) Range: 32ºF to185ºF

12 68º F Allows the installer to set the lowest temperature on theMunchkin for Central Heating. Range: 32ºF to 194ºF

13 0 Minutes Allows the installer to change the Central Heating Circulator PostPurge Time once the thermostat is satisfied. Range 0 to 10minutes.

14 30 Minutes Allows the installer to set the Maximum run time for the IndirectFired Water Heater and the Minimum run time for CentralHeating. Range 0 to 60 Minutes

15 0 Bus address (0=zone master 1–8 — cascade slave) (Not currentlyused.)

16 0 Interface Board Activation0 = not active1 = activeWARNING: Never change the default setting without theMunchkin Interface Board installed.**

17 0 Interface Board Function0 = Building Management 1 = Enables Tekmar Modulating control.(Consult with Tekmar to assure the Tekmar Control is compatible)

18 1 Step Modulation1 = on0 = off

19 180° Indirect boiler set point (flow)Temperature default = 119° to 203°

20 1 Not applicable

* Central Heating Curve Function see Fig. 5-1 Section 5.

** The Munchkin Interface board allow the Munchkin Boiler to connect to either a building man-agement system (0-10 volt) a Tekmar or allows the user to provide a boost function along with theVision 1 to drop the outside sensor to the highest central heating set point.

Once the parameters are stored and the S/4 key is pressed for 3 seconds, the unit will return tonormal operation. All the new parameters will now be reflected in the operation of the Munchkin.

12

PROGRAMMING THE CONTROLLER

Page 13: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

ADJUSTING TEMPERATUREThe installer can program

1. Central Heating Temperature Range: 50ºF to 203ºF (Factory setting 180º)2. Central Heating Differential Range: 5ºF to 30ºF (Factory setting 30º)3. Super Stor Ultra Indirect Temperature Range: 95ºF to 185ºF (Factory setting 119º)

4. Temperature measurement with either F(Fahrenheit) or C(Celsius) (Factory default [F])

NOTICEIt is important to note that the homeowner can adjust the heat curve down by adjustingthe central heating temperature to a lower setting.

Before you can change the temperature from the factory default setting. You must make sure thatnone of the thermostats are calling for heat. The Munchkin controller will not memorize a programsetting while in a heating cycle. To adjust the Munchkin Supply Water Temperature, press in theS3/Program key for three seconds until you see a flashing C alternating to 180 . This number is thefactory default set point of 180 degrees for the central heating. To change the temperature, pusheither the S1/- or S2/+ on the display. The S1/- button will decrease the temperature setting whilethe S2/+ will increase the maximum supply water temperature of the Munchkin. To change the nextvalue (Central Heating differential) press in the S3/Program and the display will read ch alternat-ing to a value of 30 . This number is the factory default set point of 30 degrees for the CentralHeating differential. To change the temperature, push either the S1/- or S2/+ on the display. Thisrepresents the starting point as to when the Munchkin will activate the burner. So, if the factory set-ting is 180 degrees the Munchkin will not start the burner unless the thermostat is calling for heatand the return sensor is measuring a temperature below 150 degrees (180 – 30 = 150 degree startpoint for burner activation). This will help minimize short cycling of the Munchkin. To change thenext value (Indirect Fired Water Heater) press in the S3/Program and the display will read de alter-nating value of 119F degree. This number is the factory default set point of 119 F degrees for themaximum Indirect Fired Water Heater (potable water). To change the temperature, push either theS1/- or S2/+ on the display. To change the next value (Fahrenheit F to Celsius C measurement)press in the S3/Program and the display will read t alternating value of F measurement inFahrenheit. To change temperature measurement, push either S1/- or S2/+ on the display.

SECTION 5: PROGRAMMING THE CENTRAL HEAT CURVEThe central heating demand is detected when the room thermostat closes. When an outside sensoris also connected, the water temperature will depend on this as indicated in the Fig. 5-1.

To set your heat curve you will have to set the following parameters1. Minimum outside design temperature: Function 82. Design Supply water temperature at the minimum design outside temperature: Function 9 3. Maximum outside design temperature: Function 10 4. Design Supply water temperature at the maximum outside temperature: Function 11

13

PROGRAMMING THE CONTROLLER / PROGRAMMING CENTRAL HEAT CURVE

DANGER Water temperature over 125 degrees F. can cause severe burnsinstantly, or death from scalds. Children, disabled, and elderlyare at highest risk of being scalded. See instruction manualbefore setting temperature at water heater. Feel water beforebathing or showering! Temperature limiting valves are available.

Page 14: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

Function Default Setting Programmed Setting

1 de No Change allowed

2 149 F No Change allowed

3 185 F

4 36 F No Change allowed

5 7 F

6 0 minutes

7 68 F

8 5 F

9 201 F

10 68 F

11 95 F

12 68 F

13 0 minutes

14 30 minutes

15 0

16 0

17 0

18 1

19 194°F

CONTROL PROGRAM REFERENCE CHART

14

PROGRAMMING CENTRAL HEAT CURVE

50

32

41

167

158

149

131

122

113

104

77

59

68

86

95

212

203

194

185

176

201˚

SU

PP

LY

OU

TLE

T T

EM

PE

RA

TU

RE

(F)

-24-59 -41

OUTSIDE TEMPERATURE (F)

-9 9 27 6345 81 99

FUNCTION 9

FUNCTION 11

FUN

CTI

ON

8

FUN

CTI

ON

10

0

68˚5˚

DEFAULT RESET CURVE

CENTRAL HEATING CURVEFactory Default

50

OUTSIDE TEMPERATURE (F)

-59

32

41

-41 -24 279-90

8145 63 99

Plot your CurveCENTRAL HEATING CURVE

SU

PP

LY

OU

TLE

T T

EM

PE

RA

TU

RE

(F)

167

104

77

59

68

86

95

131

113

122

149

158

194

176

185

203

212

Fig. 5-1 Fig. 5-2

Fig. 5-3

Page 15: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

STATUS MENU / TEST MODE

15

SECTION 6: STATUS MENU Installers are also able to check the current status of the Munchkin parameters by pressing S4/RESETkey for 3 seconds. Once activated, the display will show d1 alternating value of the actual outlet tem-perature. Actual values are displayed for each function. To view the next value simply press the S/4key to go to the next displayed value. Listed below are the values which can be displayed. These val-ues cannot be changed. To exit this menu, simply press S3/Program key to resume normal operation.

Function Valued1/ Actual Temperature from outlet sensor d2/ Actual Temperature from inlet sensor d3/ If using a standard mechanical control, the control will display 1 for closed 0 for open

If the sensor is connected to the SuperStor Indirect Fired Water Heater it will measurethe actual temperature.

d4/ Not usedd5/ Actual Temperature from the outdoor sensor d6/ Actual Fan speed multiplied by 10 (Example: If fan speed displayed is

410 RPM x 10 = 4100 actual fan speed)d7/ Actual Ionization current read from Flame Rectification probed8/ Actual Status of the Central Heating Circulator Off = 0 , On = 1d9/ Actual Status of the Indirect Fired Circulator Off = 0 , On = 1d10/ Actual Status bus communication co = connected, no = not connected d11/ Central Heating Set Pointd12/ Power on time. (Example: Hours ÷ 1000 [Ex. 0.1 = 100 hrs. or 1.0 = 1000 hrs.])d13/ Central Heating Hours (CH – Hrs. ÷ 1000)d14/ Indirect Heating Hours (IND – Hrs. ÷ 1000)d15/ Passed ignition (Passed Ignition ÷ 1000)

SECTION 7: TEST MODEThis function is intended to simplify the gas valve adjustment if needed. Listed below are therecommended limits on each Munchkin Heater and the Combustion Settings (Fig. 7-2, pg. 16).Automatic modulation does not take place when the controller is in Test mode, only temperaturelimitation based on the Munchkin Central Heating set point. The user will be allowed to increase ordecrease the fan speed by pressing in either the S1/- or S2/+ keys.

To activate the Test mode simply press the S2/+ and S3/Program key together for 1 second. Onceactivated, you will see in the display Ser and the actual fan speed. The measurement of thecombustion levels should always be taken at the highest and lowest fan speed. After 10 minutes, theTest mode stops automatically. To exit Test Mode press S1/- and S2/+ key together for 1 second.

Page 16: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

16

TEST MODE / PIPING AND WIRING

OUTMIN

V1V2

THROTTLE ADJUSTMENT SCREW.

INLET PRESSURE TAP

OUTLET PRESSURE TAP

DO NOT REMOVE THIS SCREWOR ATTEMPT TO MAKE

ANY ADJUSTMENT TO THIS SCREW.

24 VOLT DC ELECTRICAL CONNECTION

1/2" NPTGAS INLET

OF DEBRISAIR INLET, KEEP FREE

NOTE: IF FOR ANY REASON THE SCREW IS ADJUSTED, A "COMBUSTION ANALYZER" MUST BE USED TO ENSURE SAFE AND PROPER OPERATION. TURNING THE SCREW CLOCKWISE DECREASES YOUR GAS FLOW WHICH WILL LOWER THE CO/CO2 % LEVELS. TURNING THE SCREW COUNTER-CLOCKWISE INCREASES YOUR GAS FLOW WHICH WILL RAISE THE CO/CO2 % LEVELS.

Fig. 7-1A

WARNING Failure to follow all precautions could result in fire, explosion or death!

HONEYWELL GAS VALVE

Fig. 7-1

DUNGS GAS VALVE

COMBUSTION SETTINGS FOR DUNGS GAS VALVEHIGH FIRING RATES and LOW FIRING RATES

Natural Gas Propane LPlow high low high

Carbon CO ppmMonoxide

0 –10 ppm 70 ppm –135 ppm 0 – 20 ppm 70 – 95 ppm

Carbon CO2%Dioxide

8.5% – 9.5% 8.5% – 9.5% 9.5% –10.5% 9.5% –10.5%

Page 17: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

17

PIPING AND WIRING

CAUTION The drawings included in this manual are for reference purpose only. Heat TransferProducts, Inc. will not be held responsible for any installation that is not piped orwired correctly.

CAUTION Installation of additional controls or valves to the system design is not theresponsibility of Heat Transfer Products, Inc. Certain components which are notsupplied with the Vision I system may be recommended and should not be consideredan endorsement from Heat Transfer Products, Inc.

SECTION 8: PIPING AND WIRING THE VISION SYSTEM

Various drawings have been included in this section to show the Vision contractor the correct instal-lation guidelines. If the Vision has a installation which requires different piping or wiring, it is rec-ommend that you contact the factory at 1-800-323-9651. These drawings are for reference purposeonly. It is important to note that the Vision I system is normally used as a Two Temperature/TwoCirculator System (One Circulator for the SuperStor Indirect Fired Water Heater and One Circulatorfor Central Heating). The Vision I can also be used without the Indirect Fired Water Heater.

CAUTION Piping and wiring must be done correctly or overheating of the flooring

will cause damage!

Fig. 7-2

COMBUSTION SETTINGS FOR HONEYWELL GAS VALVEHIGH FIRING RATES and LOW FIRING RATES

Natural Gas Propane LPlow high low high

Carbon CO ppmMonoxide

0 – 20 ppm 70 ppm –135 ppm 0 – 20 ppm 80 –150 ppm

Carbon CO2%Dioxide

8.5% – 9.5% 8.5% – 9.5% 9.5% –10.5% 9.5% –10.5%

Page 18: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

PIPING

18

Piping SymbolLegend

circulator (w/ isolation flanges)

gate valve

globe valve

circuit setter

manual 3-way valve

pressure gauge

float -typeair vent

heat exchanger

diaphragm-type expansion tank

swing-check valve

flow-check valve

spring-loaded check valve

hose bib / boiler drain

TRV (straight)

TRV angle

zone valve

pressure reducing valve

diff. pressure bypass

3-way thermostatic

4-way motorized mixing valve

3-way motorized mixing valve

backflow preventer

union

ball valve

air separator

radiant manifold

T/P

temperature / pressuregauge

circulator w/ integral flow check

pressure relief valveP&T relief valve

Munchkin heater

Super Storindirect DHW tank

Fig. 8-1

Page 19: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

PIPING

19

Munchkin VISION 1 system(zoning with valves)Space heating mode

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure

drop operates by itself.

Drawing 3A

Munchkin boiler

DHW temperature sensor

purge

high limit safetyzonevalves

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

differentialpressurebypassvalve

T/P

OFF

P1

P2

purge

make-up water

coldwater

purg

e

Fig. 8-2

Page 20: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

20

PIPING

Munchkin VISION 1 system(zoning with valves)Domestic water heating mode

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure

drop operates by itself.

Drawing 3B

Munchkin boiler

DHW temperature sensor

purge

high limit safetyzonevalves

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

differentialpressurebypassvalve

T/P

OFF

OFF

P1

P2

purge

make-up water

coldwater

purg

e

Fig. 8-3

Page 21: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

21

PIPING

Munchkin VISION 1 system(zoning with valves)Space heating mode (w/ submixing)

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure

drop operates by itself.11. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.

Drawing 3C

Munchkin boiler

DHW temperature sensor

purge

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

purge

high limit safety

air handler

vent

3-way(manually-set)mixing valve

low temperaturemanifold station

P1

P2T/P

differentialpressurebypassvalvebalancing

valve

OFF

make-up water

coldwater

purg

e

Fig. 8-4

Page 22: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

22

PIPING

Munchkin VISION 1 system(zoning with circulators)Space heating mode

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.

Drawing 4A

Munchkin boiler

DHW temperature sensor

closely spaced tees

purge

make-up water

high limit safety

zonecirculators

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

T/P

P1

P2

OFF

purge

make-up water

coldwater

purg

e

Fig. 8-5

Page 23: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

23

PIPING

Munchkin VISION 1 system(zoning with circulators)Domestic water heating mode

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.

Drawing 4B

Munchkin boiler

DHW temperature sensor

closely spaced tees

purge

high limit safety

zonecirculators

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

T/P

P1

P2

purge

make-up water

coldwater

purg

e

OFF

OF

F

OF

F

OF

F

Fig. 8-6

Page 24: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

24

PIPING

Munchkin VISION 1 system(zoning with circulators)Space heating mode (w/ submixing)

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.

Drawing 4C

Munchkin boiler

DHW temperature sensor

purge

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

high limit safety

air handler

vent

3-way(manually-set)mixing valve

low temperaturemanifold station

P1

P2

balancingvalve

T/P

OFF

purge

make-up water

coldwater

purg

e

Fig. 8-7

Page 25: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

25

PIPING

Munchkin VISION 1 system(zoning with circulators)Space heating mode (3 fully reset supply temperatures)

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Do not use valve actuators on manifolds supplied by manually-set 3-way mixing vaalves.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.

Drawing 4E

Munchkin boiler

DHW temp. sensor

purge

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

high limit safety

air handler(higher temp.)

vent

low temperaturemanifold station

P1

P2T/P

OFF

ventmedium temperaturemanifold station

balancingvalves

3-way (manually-set) mixing valve

purge

make-up water

coldwater

purg

e

Fig. 8-8

Page 26: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

26

PIPING

Munchkin VISION 1 system(zoning with circulators)Space heating mode (3 different supply temperatures)

NOTES:1. This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Follow all instructions for installation of injection mixing system.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.

Drawing 4F

Munchkin boiler

DHW temp. sensor

purge

Super Storindirect DHW tank

anti-scald mixing valve

outdoortemperature

sensor

thermal trap(w/ drain plug)

high limit safety

air handler(higher temp.)

vent

low temperaturemanifold station

P1

P2T/P

OFF

vent

medium temperaturemanifold station

balancingvalves

variablespeedinjectionmixing

3-way manually-setmixing valve

purge

make-up water

purge

make-up water

coldwater

purg

e

Fig. 8-9

Page 27: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

PIPING

27

anti-scald mixing valve

Munchkin heater

closely spaced tees

purge

purge

make-up water

high limit safety

zonecirculators

outdoortemperature

sensor

thermal trap(w/ drain plug)

T/P

P1

P2

Super Storindirect DHW tank

air handler

air handler

multi-zonerelay center

differential pressurebypass valve

Munchkin VISION 1 system

Multiple high temperature priority loads controlled with zone valves

NOTES:

1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes.

2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. High temperature loads cannot operate simultaneously with low temperature loads.11. Supply water temperature to high temperature loads is not reset based on outdoor temperature.12. Domestic water heating is highest priority load, and controlled through priority zone of multi-zone relay center

Drawing 4G

high temperature loads low temperature loads

purg

e

OFFO

FF

OF

F

OF

F

Fig. 8-10

Page 28: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

PIPING

28

Munchkin VISION 1 systemMultiple high temperature priority loads controlled with zone circulatorsMultiple low temperature load controls with zone circulators

NOTES:

1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes.

2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream

of all closely spaced tees.4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches.6. All pumps are shown with isolation flanges and integral flow check valves.

The alternative is standard flanges with full port ball valves and a separate flow check valve. 7. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.9. A purging valve may be used in lieu of the ball valve / hose bib combination shown.10. High temperature loads cannot operate simultaneously with low temperature loads.11. Supply water temperature to high temperature loads is not reset based on outdoor temperature.12. Domestic water heating is highest priority load, and controlled through priority zone of multi-zone relay center

Drawing 4H

anti-scald mixing valve

Munchkin heater

closely spaced tees

purge

purge

make-up water

high limit safety

zonecirculators

outdoortemperature

sensor

thermal trap(w/ drain plug)

T/P

P1

P2

Super Storindirect DHW tank

air handler

air handler

multi-zonerelay center

high temperature loads low temperature loads

OF

F

OF

F

OF

F

purg

e

OFF

Fig. 8-11

Page 29: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

APPENDIX

29

SECTION 9: APPENDIX

Boiler Sensor (7250P-059) Indirect Sensor (7250P-320)Outside Temperature ( F) Resistance (ohms) Boiler & Indirect Temperature ( F) Resistance (ohms)

-22 171800 32 32550-13 129800 41 25340-4 98930 50 198705 76020 59 15700

14 58880 68 1249023 45950 77 1000032 36130 86 805941 28600 95 653550 22800 104 533059 18300 113 437268 14770 122 360577 12000 131 298986 9804 140 249095 8054 149 2084

104 6652 158 1753113 5522 167 1481

176 1256185 1070194 915203 786212 667

RESISTANCE TABLES

Outdoor Sensor (7250P-319)

Fig. 9-2

Fig. 9-1

Page 30: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

NOTES

30

Page 31: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

NOTES

31

Page 32: Hvac Munchkin Vision 1 Manual 0712-7 Lp-102

SuperStor Ultra, SuperStor, Voyager, Voyager Sanitizer, and Everlast are registered trademarks of Heat Transfer Products, Inc.

© 2006, 2005, 2004 Heat Transfer Products, Inc. LP-102 REV. 1/1/06