HV testing of insulator

12
High Voltage Insulator Testing. THE UNIVERITY OF LAHORE. BY : JAWAD ALI. SYED IMRAN ALI. SIDRA REHMAN. TO : SIR USMAN ZAHID

description

HV testing of insulator

Transcript of HV testing of insulator

Page 1: HV testing of insulator

High Voltage Insulator Testing.

THE UNIVERITY OF LAHORE.

BY : JAWAD ALI. SYED IMRAN ALI. SIDRA REHMAN.

TO : SIR USMAN ZAHID

Page 2: HV testing of insulator

Tests on Insulators

The tests on insulators can be divided into three groups.

1) Type Test.

2) Sample Test.

3) Routine Test.

Page 3: HV testing of insulator

1. Type Tests

These tests are done to determine whether the particular design is suitable for the purpose.

(a) Withstand Test:• Specified voltage is applied.• Flashover or puncture should not occur. [otherwise permanently damaged].• The test is repeated five times for each polarity.

(b) Dry One-minute Test• The insulator (dry) at prescribed voltage should be gradually brought up and maintained for one min.• There shall not be puncture or flash-over during the test.

(c) Dry flash-over test:• The voltage shall then be increased gradually until flash-over occurs. • This is repeated ten times. There shall be no damage to the insulator.

suspension-insulator-dry-flashover-test-.mp4

Page 4: HV testing of insulator

(d) One-minute Rain test: • The insulator is made wet at temp 10’c. • The prescribed voltage is maintained for one min.

Wet flash-over test: • The voltage shall then be increased gradually until flash-over occurs.• This is repeated ten times. There shall be no damage to the insulator.

dry n wet test ok.mp4

Page 5: HV testing of insulator

Impulse Frequency Flashover Voltage Test of Insulator

The overhead outdoor insulator must be capable of sustaining high voltage surges caused by lightning etc. So this must be tested against the high voltage surges.

1. The insulator is kept as it would be used practically.

2. Then several hundred thousands Hz very high impulse voltage generator is connected to the insulator.

3. Such a voltage is applied to the insulator and the spark over voltage is noted.

Impulse-lightning-withstand-voltage-test.mp4

Page 6: HV testing of insulator

2. Sample Tests

The sample is tested fully, up to and including the point of breakdown. This is done only on a few samples of the insulator.

a) Mechanical loading test: • Insulator , mechanically loaded up to the point of failure. • When failure occurs, the load should not be less than 2000 lbf.

(b) Electro-mechanical test: • The insulator is simultaneously subjected to electrical and mechanical stress.• There should be no damage caused.

High Voltage Disc Insulator Test ok.mp4

Page 7: HV testing of insulator

(d) Puncture Voltage Test of Insulator• The insulator is first suspended in an insulating oil.• Then voltage of 1.3 times of flash over voltage, is applied to the insulator.

A good insulator should not puncture under this condition.

(e) Porosity test: • The insulator is first broken into pieces.• Then These broken pieces of insulator are immersed in a 0.5 % alcohol solution of fuchsine

dye under pressure of about 2000 PSI for 24 hours.• After that the sample are removed and examine.• The presence of a slight porosity in the material is indicated by a deep penetration of the dye

into it.

Page 8: HV testing of insulator

3. Routine Tests

Mechanical Routine Test:• Mechanical load of 20% more than working load, applied after suspending the insulator for

one minute.• There should be no mechanical failure of the insulator.

Corrosion Test of InsulatorIn corrosion test of insulator,

1. Insulator is suspended into a copper sulfate solution for 1 min.2. Then the insulator is removed from the solution and wiped, cleaned.3. Again it is suspended into the copper sulfate solution for one minute.4.The process is repeated for four times.Then it should be examined and there should not be any corrosion on it.

Page 9: HV testing of insulator

Tensile test for composite insulator.

Uniflex-ITM-300---Tensile-test-bench-for-composite-insulator-testing.mp4

Page 10: HV testing of insulator

Insulator Tester

Positrons-Insulator-Testers-are-safe-and-reliable.mp4

Page 11: HV testing of insulator

The Best Insulator.

Safety considerations favour hollow composite insulators on high voltage apparatus - PlayIt.pk.mp4

Page 12: HV testing of insulator

THANK YOU