4
Up to 36 kV800 A & 1250 A
Separableconnector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)
min. max.
750LR775LR
3636
8001250
3535
630630
750LR & 775LRINTERFACE E - 5/8"
TEE CONNECTOR
ApplicationSeparable tee connector (bolted5/8" type) designed to connectpolymeric insulated cable toequipment (transformers, switchgear, motors...).Also connects cable to cable,using the appropriate matingpart.
Technical characteristics• A thick conductive EPDM
jacket provides a total safe totouch screen.
• Each separable connector istested for AC withstand andpartial discharge prior toleaving the factory.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Specifications andstandardsThe separable connectors750LR and 775LR meet therequirements of CENELEC HD629.1.
DesignSeparable connectorcomprising:
1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer
moulded between the insertand the jacket.
4. Type E interface asdescribed in ANSI/IEEE std.386.
5. Threaded stud 5/8".6. Conductor connector.7. Cable reducer.8. Dead end plug (with VD
point).9. Conductive rubber cap.
10. Cable adaptor.
295 mm260 mm
355 mm
9
3
1
4
6
10
8
5
7
2
5
Kit contentsThe complete 750LR or 775LRtee connector kit comprises thefollowing components:
The kit also comprises lubricant, wipers,installation instructions and crimp chart.
For use withother cable types.
Please contact ourrepresentative.
For outdoorapplications.
Order: +MWS.
Components can beordered individually.
For use withcopper tape
screened cables.Order: Kit MT.
For use with fabric tape(graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
+ + + + = 750LR-W-X1+11TLor
775LR-W-X2+11TLconnector kit
Ordering instructionsSelect the part number whichgives the best centring to thecable core insulation diameter.
Example:The copper wire screened cableis 36 kV, 300 mm2 strandedaluminium with a diameter overcore insulation of 38.8 mm.Order a 750LR-M-300KM-10-2+11TL tee connector kit for+11TL tee connector kit fortee connector kit for800 A application.
Table W
Table X
Ordering partnumber - 800 A
Ordering partnumber - 1250 A
Dia. over core insulation (mm)min. max.
750LR-G-X1+11TL750LR-H-X1+11TL750LR-J-X1+11TL750LR-K-X1+11TL750LR-L-X1+11TL750LR-M-X1+11TL750LR-N-X1+11TL750LR-P-X1+11TL750LR-Q-X1+11TL
775LR-G-X2+11TL775LR-H-X2+11TL775LR-J-X2+11TL775LR-K-X2+11TL775LR-L-X2+11TL775LR-M-X2+11TL775LR-N-X2+11TL775LR-P-X2+11TL775LR-Q-X2+11TL
19.321.624.927.730.034.838.543.848.3
24.126.730.033.337.241.145.249.153.9
Conductorsizes
(mm²)
Table X1: 800 A Table X2: 1250 A
Aluminium conductor Copper conductor Aluminium conductor Copper conductor
DINhexagonal
Deepindent
DINhexagonal
DINhexagonal
Deepindent
DINhexagonal
35507095120150185240300400500630
35(K)M-10-250(K)M-10-270(K)M-10-295(K)M-10-2120(K)M-10-2150(K)M-10-2185(K)M-10-2240(K)M-10-2300(K)M-10-2400(K)M-10-2500(K)M-10-2630(K)M-10-2
35KM-10-150(K)M-10-170(K)M-10-195(K)M-10-1120(K)M-10-1150(K)M-10-1185(K)M-10-1240(K)M-10-1300(K)M-10-1400(K)M-10-1500(K)M-10-1630(K)M-10-1
35(K)M-1450(K)M-1470(K)M-1495(K)M-14120(K)M-14150(K)M-14185(K)M-14240(K)M-14300(K)M-14400(K)M-14500(K)M-14630(K)M-14
35(K)M-12-250(K)M-12-270(K)M-12-295(K)M-12-2120(K)M-12-2150(K)M-12-2185(K)M-12-2240(K)M-12-2300(K)M-12-2400(K)M-12-2500(K)M-12-2630(K)M-12-2
35KM-12-150(K)M-12-170(K)M-12-195(K)M-12-1120(K)M-12-1150(K)M-12-1185(K)M-12-1240(K)M-12-1300(K)M-12-1400(K)M-12-1500(K)M-12-1630(K)M-12-1
35(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2
120(K)M-11-2150(K)M-11-2185(K)M-11-2240(K)M-11-2300(K)M-11-2400(K)M-11-2500(K)M-11-2630(K)M-11-2
Connector housing750BLR
Cableadaptor
11TL
ConductorcontactTBC-X1
or TBC-X2
Dead end plug+ rubber cap
750DPor 775DP
Cable reducer755CA-W
For use with copper wirescreened cables.
No earthing device isnecessary.