HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

29
HumidiClean

Transcript of HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Page 1: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean

Page 2: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean

Page 3: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

New

After 400 Hours

After 800 Hours

Ionic Bed

Page 4: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean Series 3000 Service Life Cycle

Factory set service life cycle is related to:

Steam output capacity per tank

Water hardness

Page 5: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean Series 3000 Service Life Cycle

Service life cycle Determines when ionic beds need replacement Relates to monitoring of “Element on Time”

history

Communicates ionic bed capacity for solids Current factory standards are 500, 1000, 2000,

3000 hours.

Is field adjustable

Page 6: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Ionic bed

Page 7: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

PerformanceService: 100% demand on 16 gr/gal

hardness water100% 100% 95.6%

0

20

40

60

80

100

1 hour 731 hours 986 hours

% Maximum output

Page 8: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean Capacity vs. Operation

Hours of Service

Percent of Original Output

0

20

40

60

80

100

0 200 400 600 800 1000

Page 9: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.
Page 10: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Energy Savings

Does not require frequent drainage to purge solids

Does not drain to reduce output

Standard drainage once per 24 hours

Page 11: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Energy Consumption Due to Drainage

Assumptions

45 PPH Output

100% Output $ 0.045/KW Electrical Costs

Operation 212 days/yr

Incoming water 50°F

Drainage Cost Comparison

HumidiClean $22.60/yr

EHU-601 $261.00/yr

Page 12: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

IAQ Features

• Generates high quality steam for distribution.

• Design incorporates an operating cycle forcartridge replacement, both simplifying anddemanding periodic attention.

• After 72 hours without demand, the unitdrains itself and initiates a drying cycle forthe ionic beds.

Page 13: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Maintenance Cost Comparison

$0 50 100 150 200 250 300 400350 450

Parts Labor

HumidiClean$185 Per Season

Cleanable$350 Per Season

Non-Cleanable$450 Per Season

Dollars

Page 14: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiCleanFeatures Advantages Benefits

Immersed resistanceheating element

Current not passedthrough water.Conductivity not aconsideration

Greater flexibility for us onlow conductivity water orhard water.

Proven safety

Annealed tankoptions

May be used on DIwater

Opens new markets notgenerally available toelectric units

Tank operatinghistory monitored

Unit demandsattention asoperating cycleexpires

Assists in assuringcartridges are replaced ona timely basis. Thismaximizes performanceand component life andminimizes maintenancecosts.

Page 15: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiCleanFeatures Advantages Benefits

Ionic Bed Cartridges Attract solidsfrom water asits temperatureis increased

Reduces cleaning frequencyof tank

Lengthens life of drain valve

Humidifier retains capacitylonger

Reduces downtime andresulting labor costs

Does not require an electricianto perform basic maintenance

Substantially reduces depositsof solids

Page 16: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean

Features Advantages Benefits

"Oven door" cabinet design Easy access to tank Simplifies maintenance andincreases likelihood ionic bedcartridges will be replaced

"Oven door" safety switchKey locked access doorOK To Open lightHigh & Low water level detectionConnections for Class 2 Alarm deviceTemperature sensing switchOvercurrent protection

Inherent HumidiCleanSafety features

Maximizes safety for servicepersonnel or owner.

Lengthens component life

Page 17: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean

Features Advantages Benefits

Drain valve operatesonce per 24 hrs. ofcontactor "on time"

Less frequentdrainage thanrequired of otherhumidifiers

Saves waterSaves energyLengthens drain valve lifeand improvesresponsiveness, resultingin better control

Drain water temperedby fill valve

Insures hot water isnot drained from theunit

Helps meet local codes.Assists for any electricalpumping requirements

Accepts various inputsignals

Unit is easilyadaptable to variouscontrol systems

Simplifies installation

Page 18: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

HumidiClean

Features Advantages Benefits

Baking cycle initiatesafter 72 hours of nodemand

Tank is drained &heating elements drythe cartridges

IAQ benefit ensuring nostagnant water or wet(and cold) media isexposed to the air

Steam dispersionoptions includedispersion tube, fanpackage &HumidiPack

Allows for use in airhandling systems aswell as direct roomdischarge

Can handle broad range ofapplications, simplifyingdesign and installation

Page 19: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Frame Assembly (MickStack)

Features Advantages Benefits

Pre-piped assembly Simplifiesinstallation andminimizes installedcost

Minimizes field problemsReduces total humidifiercost

Customized Q.S.header performance

Ensures properquantity and spacingof manifolds

Optimizes vapor trail

Factory header sizing Controls steamvelocity

Minimizes moisturecarry-over

Page 20: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Frame Assembly (MickStack)

Features Advantages Benefits

Stainless steelheader

Provides corrosionresistance

Long service life

Header inlet matchedto humidifier model

Minimizesfittings/joints

Simplifies installation

Drain connectionsupplied

Dictates headertrapped properly

Minimizes field problems

Shippedpre-assembled

Simplifies handlingfor OEM

Differentiates productReduces installed cost

Page 21: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Quick Stack Header

Page 22: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Quick Stack Header

Page 23: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Armstrong Frame Assembly

Page 24: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Unfired Steam GeneratorBenefits of Total Armstrong International Package

Single Source Ownership

Armstrong International Inc. name assigned to entire package

Improved equipment Coordination

Page 25: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Unfired Steam GeneratorBenefits of Total Armstrong International Package

Improved humidifier performance with Series 1000/9000 Optimum Control More capacity per unit Decreased Maintenance Greater Reliability Reduced Cost/lb of Output

Page 26: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Unfired Steam GeneratorsInformation Needed to Quote

Inlet Steam Pressure

Secondary Steam Pressure

Humidification Load Required

Type of Control Desired

Materials of Construction (Is water DI?)

Supply Water Temperature

Page 27: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Unfired Steam GeneratorDisadvantages

Initial Cost

Blowdown Necessary

Need Central Boiler

Page 28: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Unfired Steam GeneratorComponents

Vessel

Coil

Controls

Jacket

Insulation

Base

Page 29: HumidiClean. New After 400 Hours After 800 Hours Ionic Bed.

Unfired Steam GeneratorsOptions

Materials Alarm Bell Remote Control Feed Water Solenoid Feed Water Pump & Receiver Feed Water Pump Auto Blowdown -- Timer Auto Blowdown -- TDS Sampling High Water Cut-Off