    Our ref. EIPL/HT-CAP/NS-245/NRDear Sir, Date 31.05.13

    SUB: Your requirement of 12.65 kV, 18000 kVAr APFC Capacitor Bank

    We acknowledge with thanks the receipt of your enquiry referred above. We have pleasure in

    putting forth our most competitive proposal as per enclosed annexure.

    We are market leaders in India as well as globally for LT & MV power factor correction capacitors

    and are a leading manufacturer of all power factor correction system accessories such as power

    factor controllers, de-tuning & current limiting reactors, thyristor switching modules, capacitor

    switching contactors, power analyzers etc.

    We seek your careful consideration and patronage and are pleased to keep the contract proposal

    valid for your acceptance till 60days and would be glad to extend any further information/

    clarifications regarding the same. We trust you will find our proposal in line with your expectation

    and look forward to the pleasure of receiving your favorable response.

    Thanking you and assuring you of our best services at all times,

    Yours faithfully,

    For EPCOS India Private Limited

    Narender Sharma

    Executive-Sales and MarketingPower Quality Solution

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    2/14

    2 / 14

    TECHNICAL OFFER

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    3/14

    3 / 14

    ANNEXURE-I

    !"

    #$ %& ' ( )*

    ( ( (

    !+)(,$ -.

    /0!+)

    12$3

    2$

    /$

    4$5"

    ,$ $ 4$

    "(4

    6$$"

    +78$

    & 9$$ ' :

    *

    9$2$2#

    !+"$

    8$!$ 4"4

    9$2" &$2

    9$2" $

    "42

    ,$12$

    ;7&

    %

    9$$

    &

    /"

    1&$

    %$"50=$

    $$+7!$7$@

    $2 $7)$$7!2 2$0 $

    >6

    /1&$

    &'(')

    /7!$"

    A4$2$

    >$2$)2!2 12!$

    40&&$$;$"$BA $

    2$$"-A! $27

    27&$

    27&$

    27&$

    /;

    9$2"$&$

    A ! & A !

    2A!

    /7!$"

    '&'

    C(

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    4/14

    4 / 14

    Annexure-II

    !2

    /0!2

    @

    !"

    1"22"

    #22?>

    1"&

    *+,-

    2

    . 8:$2

    / /$

    +#%(1)

    /$

    #2$

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    5/14

    5 / 14

    Annexure III:

    GENERAL TECHNICAL PARTICULARS FOR RESIDUAL VOLTAGE TRANSFORMER:

    Sr. No. Particulars Specifications

    !24 #43

    /0 #$

    %$72$

    $0&

    6D20 >@

    !20;$$ /;

    $ ((-

    7 "< 22202

    *8$C$$'4*

    7*12$C$$'9* 1

    8"!22$ 4(4G9

    - # $ &

    *$;!D20

    '84*

    62

    $4$

    7"$

    8)$2!7"$ '8$$*

    For EPCOS India Private Limited

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    6/14

    6 / 14

    Technical C

    Annexure-IV

    TECHNICAL PARTICULARS OF Vacuum Contactor $27 #43--3;$"$H

    /0

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    7/14

    7 / 14

    Annexure V

    TECHNICAL PARTICULARS OF APFC Controller

    SI. No. Particulars Pro osed Offered

    1. Feed-back Voltage: 3ph, 3wire, 110Volt (+10%/- OK

    2. Current input: Selectable IA or SA for both OK

    load & capacitor.

    3. Auxiliary Supply: 1Ph 415V (+10% to -20%). OK

    4. Output banks control for 8 banks. (Isolated 'NO' contacts of rating OK

    5 Am ac / 250 Vac .

    5. RS-232 baud rate selectable upto 38.4 kBPS. OK6. Dedicated RS232 ort on front fascia. OK

    7. Facility for separate temperature

    robe PT100 rovided. OK

    8. Operating temperature: 0 to 50 o C OK

    9. Stora e tem erature: -10 to +75 o C OK

    10. Humidity: 0 to 98%. OK

    11. Supply frequency: 45 Hz to 55 Hz. OK

    12. Automatic synchronization capable of

    ivin correct results even for OKwron connections at CT terminals(& also wrong polarity of CTs).

    13. Load V,I and Ca . current THD

    coeff. u to 15th

    harmonic.

    14. Mode of switching user defined. OK

    15. Standard 144 X 144 cabinet for panel OK

    16. Serial communication through OK

    17. Selectable communication port OKMODBUS RS48S or RS232, on rear side.

    18. Logging of data in the form of Hourly

    Records, Fault Records & Dail OKRecording all electrical values.

    19. Protections provided20. Over/under Volta e

    21. Ca . Over/under current / THD.

    22. OverlUnder frequency

    23. Over / Under load.

    24. Load unbalance.

    2S. Over tem erature.

    26. Out of stens (only for indication).

    27. NY-RAM battery down.

    All these are user sellable. OK

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    8/14

    8 / 14

    I. Product Control Panel

    2. Application Automatic Switching of 11 kV Capacitor banks

    3. Installation Indoor

    4. Ambient Temperature 55 Deg C

    5. No. of steps Three / Four

    6. Power Frequency Voltage 3 kV

    7. Control Mode Intelligent

    8. Control Parameter Power Factor

    9. Protection MCBs shall be provided

    10. Ingress Protection IP-54

    II. Inputs Signals from CT& PT of substation

    12. Output Signals to Capswitch for ON/OFF of Capacitor steps

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    9/14

    9 / 14

    Annexure VI:

    GENERAL TECHNICAL PARTICULARS FOR 9 KV METAL OXIDE (GAPLESS)

    LIGHTNING ARRESTERS

    Sr.

    No.

    Particulars Specifications

    1. Name of the manufacturer Oblum/Equivalent

    2. Type Metal Oxide, Gapless type, FRP type

    indoor Station class , as per IEC

    60099 without surge monitor &

    insulating base, operation counters

    and leakage current indicators.

    3. Applicable standard IEC:99-4, 1991/IS:3070 Part 3/1993

    4. Rated voltage (KV rsm) 9 KV

    5. Rated frequency (HZ) 50 Hz

    6. No. of unit per arrester One

    7. Nominal discharge current (8x20 micro second wave) (KA) 5 KA

    8. Maximum continuous operating voltage KV (rms) 7.65 KV

    Insulation withstand voltage

    a) Dry power frequency 28 KV

    9.

    c) Impulse (1.2x50 micro second) 75 KV

    Lightning impulse residual voltage (8/20 micro second

    wave)

    a) 5000 A 27.0 KV (Max.)

    b) 10000 A 28.0 KV (Max.)

    10.

    c) 20000 A 32.0 KV (Max.)

    Minimum clearance

    a) Between arresters 340 mm

    11.

    b) Arrester & adjoining earthed object 230 mm

    12. Quantity 06 Nos.

    #&'8+1+

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    10/14

    10 / 14

    !%

    Sr. No. Material Make Unit Qty/bank

    17.3kV, 200 kVAR 1ph E/F, CRCA,2 BCap Unit EPCOS no. 95

    2

    0.2% Dry Al wound Reactor for 1800kVAR Step (1.2kvar, 82.15A, 0.178 ohm,14.6V) EPCOS no. 24

    3

    0.2% Dry Al wound Reactor for 3600kVAR Step (2.4kvar, 164.3A, 0.088 ohm,14.6V) EPCOS no. 3

    4Vacuum Contactor 12 kV, 100 ACapacitive current, 3 ph, Coil 230 VAC EPCOS no. 8

    5HRC Fuse for 1800 kvar step 2 x 100Amp set/ph Cooper Bussman no. 48

    6

    HRC Fuse for 3600 kvar Fix step 70Amp

    per unit

    Cooper

    Bussman/Eswari no. 18

    711kV/110/190V, 100VA, 3P10 indoorresin cast RVT class-1 Gyro no. 1

    8 11kV 0.1mfd RC surge suppressor 3ph EPCOS no. 8

    9IP54 enclosure with 2mm SheetThickness CRCA steel. EPCOS set 3

    10 Neuprene Gasket for IP54 enclosure Neuprene Set 3

    11 Al Bus Bar 75x12 EPCOS kG 90

    12 FRP Canopy EPCOS set 3

    13

    11kV, 1250 Amp 25 kA OFF Load Isolator

    outdoor Panniker/Megawin no. 1

    149kV, 5kA, static class indoor FRP TypeSurge Arrester Oblum no. 3

    1511kV, 100/1 5P10 class 1 indoor resinclass CT Fateh Power no. 6

    16

    Indoor Auto control Unit indoor withBR5008 relay, 1No.NDR, 1 No.3OC+1EFRelay ON/OFF indication , Ammeter withselector switch for complete bank current. EPCOS no. 1

    Technical Comments

    ! "# $ %$ & '(!"#)$$

    *#&$)$$

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    11/14

    11 / 14

    COMMERCIAL OFFER

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    12/14

    12 / 14

    1. Price:

    +#+

    "# 7 2/

    )9 ":!"

    * *,+;3/%#

    #"7"1#!##7!

    9$!2 0 !) 8=:4 "&$ !' & I . ) !$:* 2 2 2 2 $ 7 )

    27$2;$"#12/"7)""& ) )& " $ - ;$" H 4 ,$/" , $ " 7 # /0/"+E"7:G##2$ +) " "& 2"$2$2:#4 $ 2 " "& 2" $2 $2:?##

    4

    634*---25

    634*---25

    =9J4/J=:

    Quoted prices are on Ex- works basic price.

    Scope:

    The scope includes supply of equipment detailed above only.

    Following are not included in our scope of supply:-

    1. Hardware / clamps / Foundation bolts3. XLPE conductors4. Anything that is not explicitly included in the scope of supply5. The scope also does not include erection and commissioning, electrical inspectorateapproval etc.

    2. Taxes and Duties:

    The price quoted does not include excise duty, sales tax and any other tax applicable. These

    shall be charged extra at the time of dispatch at applicable rates at the time of dispatch. Present

    rate of excise duty is @ 10.3% and CST Extra as applicable. In case of ED Exemption the

    necessary documents shall be submitted by you and based on benefit the ED waiver shall

    be applicable.

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    13/14

    13 / 14

    3. Terms of payment:

    a) 30 % advance along with purchase order and

    b) Balance along with duties, taxes etc. against Proforma invoice after inspection and

    acceptance at our works but before dispatch from our works.

    4. Inspection: Normally equipment will be inspected by our engineer before dispatch. In case

    inspection is to be done by your inspecting authority, the same may be intimated to us in

    advance.

    5. Delivery:

    Delivery will be within 16 weeks from the date of receipt of technically and commercially clear

    order/ Advance/ Approval of Drawings, whichever is later. Delivery shall be subject to Force

    Majeure conditions.

    6. Workmanship guarantee:

    Equipments offered by us are guaranteed against any manufacturing defects for a period of 18

    months from date of supply or 12 months from the date of commissioning, whichever is earlier.We undertake to replace or repair at our option any parts found defective on account of defective

    workmanship or defective materials brought to our notice within 12 months from the date of

    erection & commissioning or 18 months from the date of delivery whichever is earlier. Any

    replacement / repair required to be carried out under the provision of the above guarantee will be

    carried out at our option either at our works or at site. The above guarantee will become invalid if

    a) The equipment is not operated as per our instructions given in the operation & maintenance

    manual

    b) The ultimate customer resells the equipment to another party

    c) Attempts have been made to service and / or modify the equipment during the warranty

    period.

    The defect liability under this guarantee period shall be taken by us only for the job done by us. In

    case of bought out items, the defect liability will be limited to the guarantee provided by our

    principals.

    7. Penalty/LD:

    All deliveries are given in good faith and we shall not be liable for penalty/LD for late delivery.

    Every effort will be sincerely made to stick to the delivery quoted. Delivery commitment is also

    subject to Force Majeure conditions.

    8. Force Majeure Conditions:

    Standard force Majeure clause shall apply.

  • 7/30/2019 HTNS 245 (Skipper G 15) 11 Kv 18 Mvar

    14/14

    9. Note on Prices

    The prices given are based on the technical specification and bill of materials therein. If during

    the course of detailed engineering, it becomes necessary to delete or add a few electrical

    components, our prices will be subject to revision after mutual discussions.

    Please note that unless other wise agreed upon mutually in writing the Terms & Conditions as

    above would only apply and we will not accept any other terms & conditions contrary to the above

    printed or otherwise.

    10. Insurance:

    Transit insurance is not included in our offer. The same can be arranged by us at an extra cost

    as applicable (Insurance against damage in transit, pilferage, non delivery or theft, damage,

    storage for a period not exceeding 30 days). We are not responsible for transit damage, if

    insurance is not covered by us.

    11. Validity:

    Unless previously withdrawn, this offer is valid for your consideration upto 30 days from the date