2
Digital Heavy Duty, Medium Voltage Soft Starter 2.3-13.8kV up to 48MW HRVS - DN Features > Configurable starting & stopping characteristics Enhanced motor protection package > User friendly setup and operation > Multi-soft start and multi-soft stop > Unique synchronous motor starting module > Pump and load control > > > Partial Discharge test according to EN50178/625.1 Direct Power Factor Capacitor connection > > > EMC compliant design and tested Communication options: Modbus, Profibus, DeviceNet, Anybus Tested and certified against shock , vibration and Seismic Compact 2-phase control configuration (optional) > Bypass open > Under Voltage > Under current > Current unbalance > Phase sequence Maximum start time > Electronic overload Time over current > > Ground fault > Over Voltage Integral Protections more than a smart Start Solcon Industries Ltd. is a dynamic power-electronics company that has been at the forefront of design, development and manufacturing of industrial electronic motor starting and control systems for over 40 years. We utilize advanced technol- range of Soft Starters, including both Low Voltage and Medium Voltage units, for a range of applications. The HRVS-DN’s sophisticated motor control technology ensures smooth acceleration and deceleration as it minimizes the effect of high in-rush current and mechanical torque shock.The flexible design, enhanced motor protection and a superior global reputation make the HRVS-DN the starting solution of choice for Medium Voltage applications - even under the most demanding conditions. The HRVS-DN’s flexible configuration is designed to meet the requirements of new applications, retrofits and OEM customization.

Transcript of HRVS - DN - Solcon - brochure.pdf · 2019. 9. 16. · Digital Heavy Duty, Medium Voltage Soft...

  • Digital Heavy Duty, Medium Voltage Soft Starter2.3-13.8kV up to 48MW

    HRVS - DN

    Features> Configurable starting & stopping characteristics Enhanced motor protection package

    > User friendly setup and operation

    > Multi-soft start and multi-soft stop

    > Unique synchronous motor starting module

    > Pump and load control

    >

    >

    >

    Partial Discharge test according to EN50178/625.1

    Direct Power Factor Capacitor connection

    >

    >

    >

    EMC compliant design and tested

    Communication options: Modbus, Profibus, DeviceNet, Anybus

    Tested and certified against shock , vibration and Seismic

    Compact 2-phase control configuration (optional)

    > Bypass open

    > Under Voltage > Under current > Current unbalance

    > Phase sequence Maximum start time

    > Electronic overload

    Time over current>

    > Ground fault

    > Over Voltage

    Integral Protections

    more than a smart Start

    Solcon Industries Ltd. is a dynamic power-electronics company that has been at the forefront of design, development and

    manufacturing of industrial electronic motor starting and control systems for over 40 years. We utilize advanced technol-

    range of Soft Starters, including both Low Voltage and Medium Voltage units, for a range of applications.

    The HRVS-DN’s sophisticated motor control technology ensures smooth acceleration and deceleration as it minimizes the effect of high in-rush current and mechanical torque shock.The flexible design, enhanced motor protection and a superior global reputation make the HRVS-DN the starting solution of choice for Medium Voltage applications - even under the most demanding conditions.The HRVS-DN’s flexible configuration is designed to meet the requirements of new applications, retrofits and OEM customization.

  • Meeting your needs across industries

    WATER OIL & GAS INDUSTRY MINING MARINE HVAC

    www.solcon.com [email protected]

    Motor Insulation Protection Relay

    MIP-6

    Models | 2.3-13.8kV, 60-1,800AMains

    Voltage (kV)

    Rated Current

    (A)

    Motor kW (kW)

    2.3

    60 200110 360200 660320 1,060400 1,330500 1,660600 2,000700 2,300800 2,660

    1,000 3,330

    3.3

    60 280110 520200 950320 1,530400 1,910500 2,390600 2,850700 3,325800 3,820

    1,000 4,780

    Mains Voltage

    (kV)

    Starter Current

    (A)

    Motor kW

    (kW)

    10

    70 1,020140 2,040250 3,650300 4,300400 5,800500 7,250600 8,700700 10,150800 11,600

    1,000 14,5001,200 17,4001,400 22,0001,600 25,0001,800 28,000

    Mains Voltage

    (kV)

    Rated Current

    (A)

    Motor kW (kW)

    4.16

    60 360110 660200 1,200320 1,930400 2,410500 3,010600 3,610700 4,210800 4,820

    1,000 6,030

    6.6

    70 670140 1,340250 2,390300 2,870400 3,820500 4,780600 5,736700 6,740800 7,650

    1,000 9,5701,200 11,5001,400 14,0001,600 16,0001,800 18,000

    Mains Voltage

    (kV)

    Starter Current

    (A)

    Motor kW

    (kW)

    11

    70 1,100140 2,200250 4,000300 4,800400 6,400500 8,000600 9,600700 11,200800 12,800

    1,000 16,0001,200 19,2001,400 22,4001,600 25,6001,800 28,800

    13.8

    70 1,400140 2,800250 5,000300 6,000400 8,000500 10,000600 12,000700 14,000800 16,000

    1,000 20,0001,200 24,000

    Solcon’s HRVS-DN can also be paired with the MIP-6 so as to monitor the level of deterioration in the insulation of the Motor. The MIP-6 measures the motor’s insulation resistance and displays

    the actual and average highs and lows over a predefined period of time. The unit is available with an additional resistor box(Up to 15kV Medium Voltage motors)