HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of...

15
Mounting and operating instructions HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER

Transcript of HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of...

Page 1: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

Mounting and operating instructions

HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER

Page 2: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 2 - 15

Table of contents

SAFETY AND PRECAUTIONS 3

PRODUCT DESCRIPTION 4

ARTICLE CODES 4

INTENDED AREA OF USE 4

TECHNICAL DATA 4

STANDARDS 5

OPERATIONAL DIAGRAM 5

WIRING AND CONNECTIONS 5

MOUNTING INSTRUCTIONS IN STEPS 6

VERIFICATION OF THE INSTALLATION INSTRUCTIONS 7

OPERATING INSTRUCTIONS 8

MODBUS REGISTER MAPS 10

TRANSPORT AND STOCK KEEPING INFORMATION 15

WARRANTY INFORMATION AND RESTRICTIONS 15

MAINTENANCE 15

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 3: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 3 - 15

back to the table of contents

SAFETY AND PRECAUTIONS

Read all information, the datasheet, mounting instructions and wiring scheme before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product.

For safety and licensing (CE) reasons, unauthorised conversion and / or modifications to the product are not permitted.

The product must not be exposed to abnormal conditions, such as: extreme temperatures, direct sunlight or vibrations. Chemical vapours with high concentration in combination with long exposure times can affect the product performance. Make sure the work environment is as dry as possible; check for condensation spots.

All installations shall comply with the local health and safety regulations and local electrical codes. This product can only be installed by an engineer or a technician who has an expert knowledge of the product and safety precautions.

Avoid contacts with energised electrical parts; always treat the product as if it is life. Always disconnect the power source before connecting the power cables, servicing or repairing the product.

Always verify that you apply appropriate power supply to the product and use wires with appropriate size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well.

Recycling of equipment and packaging should be taken into consideration and disposed in accordance with local and national legislation / regulations.

In case there are any questions that are not answered, please contact your technical support or consult a professional.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 4: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 4 - 15

back to the table of contents

PRODUCT DESCRIPTION

The HPS-X -2 series are high resolution differential pressure transmitters with Modbus RTU communication, which are equipped with a fully digital pressure transducer designed for a wide range of applications. Air flow velocity readout is available by connecting an external Pitot tube connection set. All parameters are accessible via Modbus RTU (3S Modbus software or Sensistant).

ARTICLE CODES

Article code Power supply Connection Range, [Pa]

HPS-F-1K0-2

18—34 VDC 4-wire (separate grounds)

0—1.000 Pa0—2.000 Pa0—4.000 Pa0—10.000 Pa

HPS-F-2K0-2

HPS-F-4K0-2

HPS-F-10K -2

HPS-G-1K0-2

18—34 VDC / 15—24 VAC ± 10 %

3-wire* (common ground)

0—1.000 Pa0—2.000 Pa0—4.000 Pa0—10.000 Pa

HPS-G-2K0-2

HPS-G-4K0-2

HPS-G-10K -2

INTENDED AREA OF USE

■ Differential pressure measurement in HVAC applications ■ Air flow volume measurement ** in HVAC applications ■ Air flow velocity measurement (by using an external PSET-PTX-200 Pitot tube

connection set) in HVAC applications ■ Differential pressure / airflow monitoring in clean rooms ■ Clean air and non-aggressive, non-combustible gases

TECHNICAL DATA

■ Built-in digital high resolution differential pressure sensor ■ Air flow velocity can be measured via Modbus RTU (by using an external PSET-PTX-200 Pitot tube connection set)

■ Selectable analogue / digital output: 0—10 VDC / 0—20 mA / PWM (open collector type):

► 0—10 VDC mode: min. load 50 kΩ (RL ≥ 50 kΩ) ► 0—20 mA mode: max. load 500 Ω (RL ≤ 500 Ω) ► PWM mode: PWM Frequency: 1 kHz, min. load 50 kΩ (RL ≥ 50 kΩ)

■ Variety of operating ranges and measurement windows ■ Minimum differential pressure range span: 50 Pa ■ Minimum volume flow range span: 10 m3/h ■ Minimum air velocity range span:1 m/s ■ Selectable response time: 0,1—10 s ■ Implemented K-factor ■ Selectable internal voltage source for PWM output – 3,3 or 12 VDC ■ Differential pressure, air volume** or air velocity readout via Modbus RTU ■ Selectable minimum and maximum operating ranges ■ Modbus registers reset function (to factory pre-set values) ■ Four LEDs with light guides for transmitter status indication

* In case of 3-wire connection, the analogue output GND signal is internally connected with the GND of the power supply. Therefore, G and F-type devices cannot be used together in the same network. G and F-type devices must be supplied with separate power supplies. Do not connect the GND terminals of G and F-type devices together!** Only when K-factor of fan / drive is known. If K-factor is unknown, air volume flow can be calculated via multiplying the duct cross-sectional area (A) by the air flow velocity (V) using the formula: Q = A * V

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 5: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 5 - 15

back to the table of contents

■ Modbus RTU communication ■ Sensor calibration procedure via tact switch ■ Aluminium pressure connection nozzles ■ Accuracy: ± 2 % of the operating range ■ Four LEDs with light guides for transmitter status indication ■ Operating ambient conditions:

► Temperature: -5—65 °C ► Rel. humidity: < 95 % rH (non-condensing)

■ Storage temperature: -20—70 °C

STANDARDS

■ Low Voltage Directive 2014/34/EC ■ EMC Directive 2014/30/EC: EN 61000-6-2: 2005/AC:2005, EN 61000-6-3:2007/A1:2011/AC:2012, EN 61326-2-3:2013

■ WEEE Directive 2012/19/EC ■ RoHs Directive 2011/65/EC

OPERATIONAL DIAGRAM

10

20

30

40

50

60

70

80

90

100

Min. pressure limit

Ou

tpu

t [%

]

Measured value (pressure, volume flow or air velocity) vs. Output

Control range min.

Control range max.

Max. pressure limit

Differential pressureAir volume flow Air velocity

Out of rangeLED4 ON

LED2 ON

AlertLED3 ON

AlertLED3 ON

Out of rangeLED4 ON

WIRING AND CONNECTIONS

VinG-version: 18—34 VDC / 15—24 VAC ± 10 %F-version: 18—34 VDC

GND Ground / AC ~A Modbus RTU (RS485), signal A/B Modbus RTU (RS485), signal /BAO1 Analogue / digital output (0—10 VDC / 0—20 mA / PWM)GND Ground

ConnectionsCable cross section 1,5 mm2

Cable gland clamping range 3,5 mmConnecting tube diameter 6—7 mm

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 6: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 6 - 15

back to the table of contents

ATTENTION G and F-types devices cannot be used together in the same network. G and F-type devices must be supplied by separate power supplies. Do not connect the GND terminals of G and F-type devices together.

MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the HPS-X-2 differential pressure transmitter, read carefully “Safety and Precautions”. Choose a smooth surface for an installation location (a wall, panel, etc.) and follow these steps:

1. Unscrew the front cover of the enclosure to remove it.2. Fix the enclosure onto the surface by means of suitable fasteners while adhering

to the mounting dimensions shown in Fig. 1 Mounting dimensions and the correct mounting position shown in Fig. 2 Mounting position.

Fig. 1 Mounting dimensions Fig. 2 Mounting position

2x Ø 3,449

52

Acceptable Not acceptable

HPS

+ _

HPS

+_

HPS

+_

3. Insert the cable though the grommet. 4. Connect as shown in Fig. 3 Connections adhering to the information in section

“Wiring and connections”.

Fig. 3 Connections

Power supplyG: 15—24 VAC ± 10% /

18—34 VDC F: 18—34 VDC

Modbus RTUA /B

Analogue / digital (PWM) output0—10 VDC / 0—20 mA

5. Connect the nozzles with the tubing. 6. Put back the front cover and fix it.7. Switch on the power supply.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 7: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 7 - 15

back to the table of contents

NOTE For sensor calibration and Modbus register reset procedures, refer to section “Operating instructions”.

PWM voltage selection: ■ When the internal pull-up resistor (JP1) is connected , the voltage source is set via Modbus holding register 39, i.e. 3,3 VDC or 12 VDC. See Fig. 4 Pull -up resistor jumper 1

Fig. 4 Pull-up resistor jumper 1

■ When JP1 is disconnected, the output type is Open collector. See Fig. 5 PWM (Open collector) connection.

■ Only when JP1 is not connected and the analogue output (AO1) is assigned as PWM output (via holding resister 31 - see Modbus Maps below), an external pull-up resistor is used.

Fig. 5 PWM (Open collector) connection

External voltagesource (5—50 VDC)

Analogue / digital (PWM) output0—10 VDC / 0—20 mA

External voltagesource (5—50 VDC)

VERIFICATION OF THE INSTALLATION INSTRUCTIONS

Continuous green LED1 indication as shown in Fig. 6 Power / Modbus communication indication means the unit is supplied. If LED1 is not on, check the connections again.

Blinking green LED1 indication as shown in Fig. 6 Power / Modbus communication indication means the unit has detected a Modbus network. If LED1 does not blink, check the connections again.

NOTE For more information, click here to refer to the product datasheet - Settings.

Fig. 6 Power / Modbus communication indication

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 8: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 8 - 15

back to the table of contents

ATTENTION The status of the LEDs can be checked only when the unit is energised. Take the relevant safety measures!

The Network Bus Terminator (NBT) is controlled via Modbus RTU. By default the NBT is disconnected. For more information, see the Modbus Registers Maps below.

If your unit starts or terminates the network, activate the NBT via Modbus RTU, see the examples below.

Example 1 Example 2

Slave 1

RX

ТX

NBT

NBT

NBT

Slave 2Master

Slave n

Slave 2Slave 1

RX

ТX

NBT

NBT

Master

Slave n

NOTE Connect the terminator only in the two most distant units on the network line!

OPERATING INSTRUCTIONS

Calibration procedure:1. Disconnect the nozzles.2. There are two options for starting the calibration process:

Either write “1” in holding register 40 or press button SW1 for 4 seconds until the green LED2 and yellow LED3 on the printed circuit board blink twice and release it (see Fig. 7 Sensor calibration and Modbus register reset tact switch and indication).

3. After 2 seconds the green LED2 and yellow LED3 will blink twice once again to indicate that the calibration procedure has finished.

Fig. 7 Sensor calibration and Modbus register reset tact switch (SW1) and calibration indication

NOTE Press and hold the button until both LEDs on the PCB blink twice and hold it until both LEDs blink again three times. If the button is released before both LEDs blink again three times, the sensor will have carried out a calibration procedure instead of Modbus registers reset procedure.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 9: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 9 - 15

back to the table of contents

Communication holding registers reset procedure:1. Put the jumper onto pins 1 and 2 of the P4 connector for more than 20 s while the

device is powered. (See Fig. 8 Modbus holding register reset jumper ).

Fig. 8 Modbus holding register reset jumper

12345

2. Modbus communication holding registers from 1 to 3 will be reset to the default values.

3. Remove the jumper.

ATTENTION Make sure that the nozzles are free and not connected.

LED indications (See Fig. 9):1. When the green LED1 is on, the power supply is adequate and Modbus RTU

communication is active.2. When the green LED2 is on, the measured value (pressure, volume or air velocity)

is between the minimum and maximum alert range.3. When the yellow LED3 is on, the measured value (pressure, volume or air velocity)

is below the minimum alert range or above the maximum alert range.4. When the red LED4 is on, the measured value (pressure, volume or air velocity) is

below the minimum measurement range or above the maximum.

Fig. 9 LED indications

5. Sensor element failure indication:In case of failure of sensor element or loss of communication with it, the red LED4 blinks. See Fig. 10.

Fig. 10 Sensor element error

HPS

HPS

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 10: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 10 - 15

back to the table of contents

MODBUS REGISTER MAPS

INPUT REGISTERSData type Description Data Values

1 Output unsigned int. Output value in percentage 0—1.000 100 = 10,0%

2 Differential pressure unsigned int. Measured differential pressure

HPS-X-1K0 -2HPS-X-2K0 -2HPS-X-4K0 -2HPS-X-10K -2

0— 10.0000— 20.000 0— 40.0000—10.000

1.000 =1.000 = 1.000 = 1.000 =

100,0 Pa 100,0 Pa 100,0 Pa1.000 Pa

3 Volume flow rate high unsigned int.

Air Volume flow rate

HPS-X-1K0 -2HPS-X-2K0 -2HPS-X-4K0 -2HPS-X-10K -2

0—25.0000—40.000

0—100.0000—180.000

1.000 = 1.000 m3/h4 Volume flow rate low unsigned int.

5 Air velocity unsigned int. Measured air velocity 0—300 100 = 10 m/s

6 unsigned int. Reserved, returns 0

7Air pressure/volume/velocity alert flag

unsigned int.The flag indicates that measured data is outside the set alert values.

0—1

0 = Pressure/Volume/Velocity measurement is OK

1 =Pressure/Volume/Velocity measurement is too

low/high

8Air pressure/volume/velocity range limit flag

unsigned int.The flag indicates that measured data is outside the set range limit values.

0—10 = Pressure/Volume/Velocity range is OK

1 = Pressure/Volume/Velocity range is too low/high

9 Sensor fault unsigned int. Indicates sensor failure 0—10 = Sensor OK

1 = Sensor fault (Red LED4 blinks)

10 unsigned int. Reserved, returns 0

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 11: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 11 - 15

back to the table of contents

HOLDING REGISTERSData type Description Data Default Values

1 Device slave address unsigned int. Modbus device address 1—247 1

2 Modbus baud rate unsigned int. Modbus communication baud rate 0—6 2

0 =1 =2 = 3 =4 =5 = 6 =

4.8009.600

19.200 38.40057.600

115.200230.400

3 Modbus parity mode unsigned int. Parity check mode0 = 1 = 2 =

8N18E18O1

10 = 1 =2 =

NoneEvenOdd

4 Device type unsigned int. Device type (Read-only)

HPS-X-1K0 -2 = HPS-X-2K0 -2 = HPS-X-4K0 -2 = HPS-X-10K -2 =

1079108010811082

5 HW version unsigned int. Hardware version of the device (Read-only) XXX 0 x 0100 = HW version 1.00

6 FW version unsigned int. Firmware version of the device (Read-only) XXX 0 x 0100 = FW version 1.00

7-10 Reserved, return 0

11 Minimum pressure range unsigned int. Minimum of the pressure range 0 - Max. pressure range minus 50 Pa 0100 = 10,0 Pa

100 = 100,0 Pa (HPS-X-10K -2)

12 Maximum pressure range unsigned int. Maximum of the pressure rangeMin. control

range plus 50 Pa

HPS-X-1K0 -2HPS-X-2K0 -2HPS-X-4K0 -2HPS-X-10K -2

50—10.000 Pa50—20.000 Pa50—40.000 Pa50—10.000 Pa

10.00020.00040.00010.000

1.000 = 1.000 = 1.000 = 1.000 =

100,0 Pa100,0 Pa100,0 Pa1.000 Pa

13 Minimum pressure alert unsigned int. Minimum differential pressure alarm value Min pressure range—max. pressure alarm 0

100 = 10,0 Pa

100 = 100,0 Pa (HPS-X-10K -2)

14 Maximum pressure alert unsigned int. Maximum differential pressure alarm value

Max. pressure limit

HPS-X-1K0 -2HPS-X-2K0 -2HPS-X-4K0 -2HPS-X-10K -2

10.00020.00040.00010.000

10.00020.00040.00010.000

1.000 = 1.000 = 1.000 = 1.000 =

100,0 Pa100,0 Pa100,0 Pa1.000 Pa

15 Minimum volume flow range high unsigned int.Minimum volume flow range value Maximum volume flow range minus 10 m³/h 0 10 = 10 m³/h

16 Minimum volume flow range low unsigned int.

17 Maximum volume flow range high unsigned int.Maximum volume flow range value Minimum volume flow

range plus 10 m³/h

HPS-X-1K0 -2HPS-X-2K0 -2HPS-X-4K0 -2HPS-X-10K -2

25.00040.000

100.000180.000

20.000 = 20.000 m³/h18 Maximum volume flow range low unsigned int.

19 Minimum volume flow alert high unsigned int.Minimum volume flow alarm value Min. volume flow range—max. volume flow

alarm 0 1.000 = 1.000 m³/h 20 Minimum volume flow alert low unsigned int.

21 Maximum volume flow alert high unsigned int.Maximum volume flow alarm value

Min. volume flow range—max. volume

flow range

HPS-X-1K0 -2HPS-X-2K0 -2HPS-X-4K0 -2HPS-X-10K -2

25.00040.000

100.000180.000

10.000 = 10.000 m³/h22 Maximum volume flow alert low unsigned int.

23 Minimum air velocity range unsigned int. Minimum air velocity range value 0—(Maximum air velocity range minus 1 m/s) 0 100 = 10,0 m/s

24 Maximum air velocity range unsigned int. Maximum air velocity range value (Minimum air velocity range plus 1 m/s)—300 300 300 = 30,0 m/s

25 Minimum air velocity alert unsigned int. Minimum air velocity alarm value Min. air velocity range—Max. air velocity alarm 0 100 = 10,0 m/s

26 Maximum air velocity alert unsigned int. Maximum mum air velocity alarm value Min. velocity alarm—Max. air velocity range 300 300 = 30,0 m/s

27 Reserved, returns 0

28 Response time unsigned int. Response time selection 1—100 10 10 = 1,0 s

29 Power-up timer unsigned int. Power-up timer before setting alert and range limit flags. 0—1.000 60 s 100 = 100 s

30 K-factor. unsigned int. K-factor according to motor / fan specifications 0—1.000 0

31 Reserved, returns 0

32 Modbus network resistance terminator (NBT) unsigned int. Sets device as an end device on

the line 0—1 0 0 = 1 =

NBT disconnected NBT connected

33 Altitude unsigned int. Current altitude 0—5.000 0 1.000 = 1.000 m

34 Pitot air velocity unsigned int. Enables Air Velocity Readout. 0—1 0 0 = 1 =

Disabled Enabled

35 Duct cross sectional area [ cm2] unsigned int. Calculation of the Volume Flow Rate when K-factor is not known 0—32.000 0 0 =

100 Not used100 cm2

36 Reserved, returns 0

37 Measurement readout unsigned int. 4-digit measurement indication ON / OFF 0—1 1 0 =

1 = LED display offLED display on

38 Operating mode unsigned int. Operating mode selection 1—3 11 = 2 = 3 =

Differential pressure(1)

Volume flow rate(2) Air velocity(3)

39 Reserved, returns 0

40 Recalibrate sensor unsigned int. Sensor recalibration 0—1 0 0 = 1 =

Inactive Active

For more information about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf

(1) To measure differential pressure, use use PSET-QF or PSET-PVC set;(2) To measure air flow volume while using PSET-PTx, enter the duct cross sectional area [cm²] in Modbus register 35. To measure air flow volume while using PSET-QF or PSET-PVC, enter the K-factor of the fan in Modbus register 30;(3) To measure air velocity, use PSET-PTx set.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 12: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 12 - 15

back to the table of contents

INPUT REGISTERS (see Table Input registers above)

The input registers are read-only. All data can be read using the ‘Read Input Registers’ command. Table Input registers shows the returned data type and the way it should be interpreted.

■ Input register 1 contains the value of the output as a percentage of the selected control range.

■ Input register 2 contains the value of the currently measured differential pressure.

■ Input registers 3 and 4 provide information about the current air volume / flow rate. Input register 3 holds the high significant word, while input register 4 holds the low significant word. The value in these registers is equal to the K-factor of the fan (holding register 30) multiplied by square root of the current differential pressure. If K-factor is not known, volume flow rate is calculated via multiplying the duct cross sectional area (holding register 35) by air flow velocity ( i.e. Pitot air velocity enabled by holding register 34).

■ Input register 5 is “Air velocity”. It is active only when holding register 34 is set to “1”.

■ Input register 6 is not used. When addressed, it returns ‘0’.

■ Input register 7 indicates that measured air pressure, volume or velocity is outside the set alert values. It is set to ‘1’ when the measured value is outside the pressure, volume or velocity alert values defined by holding registers 13, 14, 19, 20, 21, 22, 25 and 26. It is not active during the power-up period defined by holding register 29.

■ Input register 8 indicates that measured air pressure, volume or velocity is outside the set range limit values. It is set to ‘1’ when the measured pressure is outside the pressure, volume or velocity limit range values defined by holding registers 11, 12, 15, 16, 17, 18, 23 and 24. It is not active during the power-up period defined by holding register 29.

■ Input register 9 indicates a problem with the sensor.

■ Input register 10 is not used. When addressed, it returns ‘0’.

HOLDING REGISTERS (see Table Holding registers above)

These registers are read / write registers and they can be managed via “Read Holding Registers”, “Write Single Register” and “Write Multiple Registers” commands. The registers that are not used are read-only and, therefore, writing in these registers neither returns a Modbus error exception, nor makes any changes.

■ Holding register 1 contains the sensor address at which the sensor replies in a Modbus network. The default address is ‘1’. It can be changed in two ways:1. Send command “Write Single Register” with address ‘1’ and write the new

address value. 2. Connect only your unit to a master controller or a PC application, send the

command “Write Single Register” to address ‘0’ (Modbus broadcast address) and write a new address value.

■ The next two holding registers (2 and 3) also contain Modbus settings. Changing these registers changes the communication settings. The default Modbus settings are as stated in the Modbus Protocol Specification.

■ The next three holding registers (4, 5 and 6) are read-only. They return information about the sensor hardware and firmware versions.

■ The next four holding registers (7, 8, 9 and 10) are not used. They are read-only.

NOTE Writing in these registers neither returns a Modbus error exception, nor makes any changes!

■ Holding registers 11 determines the minimum pressure range. It cannot be set higher than the maximum pressure range minus the minimum pressure range span (i.e. 50 Pa).

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 13: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 13 - 15

back to the table of contents

NOTE The minimum pressure range cannot be higher than the maximum control range minus 50 Pa.

■ Holding register 12 defines the maximum pressure range. It cannot be set lower than the minimum pressure range plus the minimum pressure range span (i.e. 50 Pa). This register accepts values as specified in the Modbus map. (See Table Holding registers above). Writing values other the those specified in the Modbus map does not change anything in this register.

NOTE The maximum pressure range cannot be less than the minimum range plus 50 Pa.

■ Holding registers 13 and 14 contain the minimum and maximum differential pressure alarm value respectively.

■ Holding registers 15 and 16 hold the minimum volume flow range, which cannot be set higher than the maximum volume flow range minus the minimum volume flow range span (10 m³/h). The air volume flow rate is measured in m3/h. Holding register 15 contains the high significant word, while holding register 16 contains the low significant word of the minimum volume flow rate range.

■ Holding registers 17 and 18 hold the maximum volume flow, which cannot be set lower than the minimum volume flow range plus the minimum volume flow range span (10 m³/h). The air volume flow rate is measured in m3/h. Holding register 17 contains the high significant word, while holding register 18 contains the low significant word of the maximum volume flow rate range.

■ Holding registers 19 and 20 hold the minimum volume flow alarm value. The air volume flow rate is measured in m3/h. Holding register 19 contains the high significant word, while holding register 20 contains the low significant word of the minimum volume flow rate alert.

■ Holding registers 21 and 22 hold the maximum volume flow alarm value. The air volume flow rate is measured in m3/h. Holding register 21 contains the high significant word, while holding register 22 contains the low significant word of the maximum volume flow rate alert.

■ Holding registers 23 and 24 hold the minimum and maximum air velocity range respectively. The minimum air velocity range cannot be set higher than the maximum air velocity range minus minimum air velocity range span (1 m/s). The maximum air velocity range, cannot be set lower than the minimum air velocity range plus the minimum air velocity range span (1 m/s).

NOTE The minimum value cannot be higher than the maximum value. When a value higher than the defined maximum is written inside a register, it automatically becomes equal to the predefined maximum value.

■ Holding register 25 and 26 hold the minimum and maximum air velocity alarm values respectively.

NOTE If a value written in a holding register is lower than the predefined minimum value, the unit automatically adjusts the minimum limit to the new maximum limit value. (For example: when min. = 200 and max. = 1.000, if the max. value is changed to 150, i.e. is lower than the min. value, the unit automatically sets the min. value to 150 because the min. cannot be higher than the max.)

■ Holding register 27 is not used. When addressed, it returns “0”.

■ Holding register 28 contains the response time, which can be given values from 1 to 100, where 10 = 1,0 second.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 14: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 14 - 15

back to the table of contents

■ Holding register 29 contains the value of the ‘Power-up timer’ before setting the alert and range limit flags. The default value is 60 s. During this interval the alerts and range limits are not compared with the current differential pressure / volume / velocity and alert and range limit flags registers remain ‘0’. You can change the value in this register only within the first 60 s after you have switched on your unit.

■ Holding register 30 holds the K-factor. Enter the K-factor of the used fan / drive, if it is known (check the datasheets of the selected fan / drive). The default value is ‘0’, and you are allowed to write values in the range of 0—1.000. Writing values out of this range does not change anything in this register.

■ Holding register 31 is not used. When addressed, it returns “0”.

■ Holding register 32 specifies if the device is an end device on the line or not via connecting the NBT.

■ Holding register 33 holds information about the current altitude varying from “0” to “5.000”. The default value is ‘0‘, i.e. 0 m.

■ Holding register 34 enables air velocity readout. If the value is ‘0’, air velocity readout is disabled and if the value is ‘1’, air velocity readout is enabled and it is accessible in input register 5. PSET-PTX-200 Pitot tube is necessary.

■ Holding register 35 is used for calculation of the volume flow rate when K-factor is not known. This register accepts values from 0 to 32.000. When the value is 0, it is not used, if in use it takes values from 1 to 32.000 corresponding to the duct cross sectional area in cm2.

■ Holding register 36 is not used. When addressed, it returns “0”.

■ Holding register 37 is used to define if the LED display will be on or off.

■ Holding registers 38 defines the operating modes, i.e. differential pressure, volume flow rate or air velocity.

■ Holding register 39 is not used. When addressed, it returns “0”.

■ Holding register 40 is used for sensor recalibration.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2

Page 15: HPS-X -2 DIFFERENTIAL PRESSURE TRANSMITTER miw-hps-x-2-en-000 - 14 / 03 / 2017 2 - 15 table of contents safety and precautions 3 product description 4 article codes 4 intended area

www.sentera.euMIW-HPS-X-2-EN-000 - 14 / 03 / 2017 15 - 15

back to the table of contents

TRANSPORT AND STOCK KEEPING INFORMATION

Avoid shocks and extreme conditions; stock in original packing.

WARRANTY INFORMATION AND RESTRICTIONS

Two years from the delivery date against defects in manufacturing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. The manufacturer bears no responsibility for any misprints or mistakes in this data.

MAINTENANCE

In normal conditions this product is maintenance-free. If soiled, clean with a dry or dampish cloth. In case of heavy pollution, clean with a non-aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry.

DIFFERENTIAL PRESSURE TRANSMITTER HPS-X -2