How to read a P&ID for Risk Analysis
-
Upload
riskinspired -
Category
Business
-
view
27 -
download
5
description
Transcript of How to read a P&ID for Risk Analysis
![Page 1: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/1.jpg)
How to Read a P&ID ForRiskAnalysis
![Page 2: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/2.jpg)
P&ID is a Piping and Instrumentation Diagram
![Page 3: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/3.jpg)
To identify risk from a set of P&ID you must have clear understanding of three things…
![Page 4: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/4.jpg)
#1
Understand the process
![Page 5: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/5.jpg)
#2 Understand the failures
![Page 6: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/6.jpg)
#3
Understand the consequence
![Page 7: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/7.jpg)
Lines are used for showing piping, equipment and instrumentation connections…
![Page 8: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/8.jpg)
…so people can communicate the process sequence and the relationship of different equipment
![Page 9: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/9.jpg)
Equipment and instrumentation are connected by lines
Here are some common connections
![Page 10: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/10.jpg)
Pipe
Common Failure Modes:- Collapse- Burst/Rupture- Erosion- Corrosion
![Page 11: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/11.jpg)
Electrical Signal
Common Failure Modes:- Open connection- Electrical shorting- Electromagnetic interference
![Page 12: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/12.jpg)
Pneumatic Signal
Common Failure Modes:- Leakage of internal fluid- High components friction level- Loss of pressure
![Page 13: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/13.jpg)
Data Signal
Common Failure Modes:- Radio interference - Signal filtering- Packets Loss- Loss of signal
![Page 14: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/14.jpg)
Flexible Pipe
Common Failure Modes:- Compressive failure- Tensile failure- Over bending - Rupture
![Page 15: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/15.jpg)
Symbols are used to simplify drawings
From this To this
>>>>>>
>>>
![Page 16: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/16.jpg)
Some equipment are used to add or reduce energy in the material
![Page 17: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/17.jpg)
Blower
Common Failure Modes:- Fail to operate on demand- Loss of pressure
![Page 18: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/18.jpg)
Furnace
Common Failure Modes:- Flame out
![Page 19: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/19.jpg)
Pump
Common Failure Modes:- Fail to operate on demand- Loss of pressure- Over pressure
![Page 20: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/20.jpg)
Compressor
Common Failure Modes:- Fail to start- Damage due to liquid- Over pressure- Excessive vibration
![Page 21: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/21.jpg)
Heat exchanger
Common Failure Modes:- Leakage- Corrosion- Plugged
![Page 22: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/22.jpg)
Plate Heat Exchanger
Common Failure Modes:- Leakage- Corrosion- Plugged
![Page 23: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/23.jpg)
Aerial Fan
Common Failure Modes:- Loss of air circulation
![Page 24: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/24.jpg)
Some equipment are used for material storage
![Page 25: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/25.jpg)
Floating Storage Tank
Common Failure Modes:- Overflow- Leakage
![Page 26: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/26.jpg)
Sphere Tank
Common Failure Modes:- Overpressure
![Page 27: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/27.jpg)
Pressurized Vessel
Common Failure Modes:- Overpressure
![Page 28: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/28.jpg)
Some equipment are used to separate material
![Page 29: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/29.jpg)
Horizontal Separator
Common Failure Modes:- Overpressure
![Page 30: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/30.jpg)
Vertical Separator
Common Failure Modes:- Overpressure
![Page 31: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/31.jpg)
Fluid Contacting Column
Common Failure Modes:- Overpressure- Corrosion- Plugged
![Page 32: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/32.jpg)
Tray Column
Common Failure Modes:- Overpressure- Contamination
![Page 33: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/33.jpg)
Valves are used to control the flow of material
![Page 34: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/34.jpg)
Manual Valve
Common Failure Modes:- External leakage- Internal leakage- Inadvertent position
![Page 35: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/35.jpg)
Control Valve
Common Failure Modes:- Fail to close on demand- Fail to open on demand- Spurious operation- Leakage
![Page 36: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/36.jpg)
Solenoid Valve
S
Common Failure Modes:- Structural failure- Seat Leakage- Seal Leakage- Loss of actuator
![Page 37: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/37.jpg)
Motor-operated Valve
M
Common Failure Modes:- Motor failure- Fail to stroke
![Page 38: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/38.jpg)
Butterfly Valve
Common Failure Modes:- Fail to close on demand- Fail to open on demand- Spurious operation
![Page 39: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/39.jpg)
Globe Valve
Common Failure Modes:- Fail to close on demand- Fail to open on demand- Spurious operation- Leakage
![Page 40: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/40.jpg)
Needle Valve
Common Failure Modes:- Fail to close on demand- Fail to open on demand- Spurious operation- Leakage
![Page 41: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/41.jpg)
Ball Valve
Common Failure Modes:- Fail to close on demand- Fail to open on demand- Spurious operation- Leakage
![Page 42: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/42.jpg)
Check valve
Common Failure Modes:- Leakage- Stuck at open position
![Page 43: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/43.jpg)
Some equipment are used to relief pressure in the process
![Page 44: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/44.jpg)
Relief Valve
Common Failure Modes:- Fail to open
![Page 45: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/45.jpg)
Curved Gas Vent
Common Failure Modes:- Plugged
![Page 46: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/46.jpg)
Rupture Disk
Common Failure Modes:- Corrosion
![Page 47: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/47.jpg)
Control system are used to manage the behaviour of the process
![Page 48: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/48.jpg)
Programmable Logic Control
Common Failure Modes:- Software error- Execution error
![Page 49: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/49.jpg)
Shared display, shared Control
Common Failure Modes:- Software error- Execution error
![Page 50: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/50.jpg)
Sensors are used to measure the physical properties of the process and convert it into a signal
![Page 51: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/51.jpg)
Flow Transmitter
FT
Common Failure Modes:- Spurious measurement- Loss of measurement
![Page 52: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/52.jpg)
Pressure Transmitter
PT
Common Failure Modes:- Spurious measurement- Loss of measurement
![Page 53: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/53.jpg)
Level Transmitter
LT
Common Failure Modes:- Spurious measurement- Loss of measurement
![Page 54: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/54.jpg)
Now lets identify the risk of this process…
![Page 55: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/55.jpg)
LT253
HLL=2550 mmNLL=1650 mm
LLL=250 mm LC
LY LV
Steam
Condensate
To atmosphere at safe location
PSV
D-101
D-101 Re-boiler Condensate Pot
253253
253
111
Drawing Ref.
Drawing Ref.
LG253
2”
2”
3”
3”
3/4”
3/4”
6” 6”
6”
6”
Size ½SET @ 700kPag
6”
![Page 56: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/56.jpg)
Step 1: Understand the process
• There is low pressure steam flowing into the vessel
• The steam cools and forms condensate in the condensate pot
• The level of the condensate liquid is controlled by a level control loop
• Condensate is drained out the bottom of the vessel
![Page 57: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/57.jpg)
LT253
HLL=2550 mmNLL=1650 mm
LLL=250 mm LC
LY LV
Steam
Condensate
To atmosphere at safe location
PSV
D-101
D-101 Re-boiler Condensate Pot
253253
253
111
Drawing Ref.
Drawing Ref.
LG253
2”
2”
3”
3”
3/4”
3/4”
6” 6”
6”
6”
Size ½SET @ 700kPag
6”
Star
t
![Page 58: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/58.jpg)
Step 2: Identify possible failures
The control loop can malfunction causing the valve LV253 to fail in the closed position
![Page 59: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/59.jpg)
LT253
HLL=2550 mmNLL=1650 mm
LLL=250 mm LC
LY LV
Steam
Condensate
To atmosphere at safe location
PSV
D-101
D-101 Re-boiler Condensate Pot
253253
253
111
Drawing Ref.
Drawing Ref.
PG253
2”
2”
3”
3”
3/4”
3/4”
6” 6”
6”
6”
Size ½SET @ 700kPag
6”
![Page 60: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/60.jpg)
Step 3: Assess the consequence
• The level control valve fails in the closed position blocking the drain line
• Hazard is high level and high pressure in the tank
• Potential consequence of loss of containment and equipment damage with $$$$ losses
![Page 61: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/61.jpg)
Now you have identified the cause of the overpressure hazard, can you identify the safeguard?
![Page 62: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/62.jpg)
The pressure relief with a set point of 700 kPa will open and reduce but not eliminate the risk of rupture
![Page 63: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/63.jpg)
LT253
HLL=2550 mmNLL=1650 mm
LLL=250 mm LC
LY LV
Steam
Condensate
To atmosphere at safe location
PSV
D-101
D-101 Re-boiler Condensate Pot
253253
253
111
Drawing Ref.
Drawing Ref.
LG253
2”
2”
3”
3”
3/4”
3/4”
6” 6”
6”
6”
Size ½SET @ 700kPag
6”
![Page 64: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/64.jpg)
By understanding the P&ID you can clearly assess risk in your operation and make good decisions
![Page 65: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/65.jpg)
Any Questions?
![Page 66: How to read a P&ID for Risk Analysis](https://reader034.fdocuments.in/reader034/viewer/2022050801/5453d83faf7959a4058b7a81/html5/thumbnails/66.jpg)
Risk. Inspired.