HouseScan Professional Snagging After care and advice included at no extra cost for anytime before, during or after your inspection. Whether it’s advice contacting your developer or a question about your home. HouseScan Introduction & Sample Report Thermal imaging on the day of your inspection ensures your windows and doors have been installed properly, heating system is working properly and no wall and ceiling bridging has occurred. We use our own in-house software to create the most comprehensive reports available from any snagging company. We take a picture of all defects and clearly annotate and describe. We also offer a de-snag service. Where we ensure all remedial works have been completed to the correct standard. If you book this at the time of your snagging inspection booking you save 20%. Our prices are competitive. Despite us offering the most comprehensive reports and hiring industry experts we look to always ensure out pricing stays fair. We do inspections on houses and apartments across most of England. We check all parts of your property from your garden to your loft and your plumbing to your bricklaying.

Transcript of HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone...

Page 1: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScanProfessional Snagging

Aftercareandadviceincludedatnoextracostforanytime

before,duringorafteryourinspection.Whetherit’sadvice

contactingyourdeveloperoraquestionaboutyourhome.

HouseScanIntroduction&SampleReport

Thermalimagingonthedayofyourinspectionensuresyour

windowsanddoorshavebeeninstalledproperly,heatingsystem

isworkingproperlyandnowallandceilingbridginghasoccurred.

Weuseourownin-housesoftwaretocreatethemost

comprehensivereportsavailablefromanysnaggingcompany.

Wetakeapictureofalldefectsandclearlyannotateanddescribe.

Wealsoofferade-snagservice.Whereweensure

allremedialworkshavebeencompletedtothe

correctstandard.Ifyoubookthisatthetimeof

yoursnagginginspectionbookingyousave20%.

Ourpricesarecompetitive.Despiteusofferingthemost

comprehensivereportsandhiringindustryexpertswelook

toalwaysensureoutpricingstaysfair.

Wedoinspectionsonhousesandapartmentsacrossmostof

England.Wecheckallpartsofyourpropertyfromyour

gardentoyourloftandyourplumbingtoyourbricklaying.

Page 2: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

Customer:

HouseScan Sample Report

Developer:

Sample Builder

Site Name:

Sample Site

Inspector:

Harry Yates

Date:

06/01/20

20 Rooms:

Front Elevation (20)

Left Elevation (2)

Rear Elevation (8)

Garage (4)

Hallway (24)

DWC (15)

Cupboard Understairs (3)

Kitchen (19)

Dining Room (5)

Living Room (15)

Stairs 1 (14)

Landing (7)

Bed 4 (10)

Bed 2 (8)

Bed 3 (8)

Bathroom 1 (18)

Stairs 2 (8)

Bed 1 (16)

Ensuite 1 (16)

Loft (5)

Number of Snags:

226

This report is version: 1

Site teams can assign (sub)contractors, view, edit and manage this report for free

by signing up to https://buildscan.net/register and entering the report code:a850370b

1

Page 3: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

Thermographic Survey

Camera Settings

Camera Flir e6

Internal Temperature °C 25

External Temperature °C 10

Emissivity 95.00

Reflective Temperature °C 20

Wind Direction Front elevation

Front door

The FD is showing cold air ingress to the foot of the door. The issue is worsened to the bottom

corners to which there is a small gap between the skirting and fd cill.

22

Page 4: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

Trickle vents

The trickle vents to the DWC and bathroom are showing an inconsistent amount of cold air ingress

when closed. This is likely due to incorrect installation and them not being able to close full flush to

the frame.

Plinth

Cold air ingress is noted to around the kitchen plinth, this is usually in relation to the wall below the

external wall (behind the kitchen units) not being finished and thus a draught being present.

3

Page 5: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

Bed 2

The window within bed 2 is showing condensation build up, this is likely in relation to cold air

ingress and an inadequate window seal.

4

Page 6: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportFront Elevation

Damage to gas meter box - split visible and

various scratched

Damage to Kitchen stone cill - chipped and

showing various areas of abrasion

Kitchen waste not cleaned

Pointing inconsistent to kitchen lintel

FD cill damaged and unfinished - as well as

side sections left exposed to weathering

FD not cleaned and once cleaned recheck for

damage

5

Page 7: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportFront Elevation

Cap missing to FD canopy

FD frame surround split at joint to top rhs and

left exposed to weathering

FD handle loose in various places

FD cill aco damaged and clogged across

entire section of fd cill

Recommendation to fire fill voids within

electrical meter box with fire rated insulation

Area unfinished rhs of FD - no conduit fitted

6

Page 8: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportFront Elevation

Damage to dwc stone cill across entire section

FD canopy not watertight - GRP section not

flush to brickwork and no seal present

Lintel to dwc window twisted over 15 mm

from rhs to lhs

1st floor stone cills damaged - showing

various chips and abrasive marks

Bathroom lintel twisted - deviation greater

than 15mm

Sealant inconsistent around dormer window

perimeter to 2nd floor

7

Page 9: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportFront Elevation

Turf joints not flush and damaged due to not

being fitted continuously to top soil below

5mm+ deviation to slabs infront of door

8

Page 10: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportLeft Elevation

Cap can't be fitted to boiler flue as it's inset to

wall too far

Pointing inconsistent along dpc

9

Page 11: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportRear Elevation

Pen marks and scuffs to reveals

Foam visible around FD perimeter

Patio doors and cill not cleaned once cleaned

recheck for damage

Marks to patio doors to various positions -

worsened to the corners

Pointing inconsistent above patio door

Pointing inconsistent to kitchen window lintel

10

Page 12: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportRear Elevation

Damage to guttering at the joint - connection

has split and is no longer water tight

Seal incomplete to waste ingress to brickwork

above bed 4

11

Page 13: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportGarage

Man hole cover fixings not fully inserted and

not cleaned

Fence posts to neighbouring property not

fixed properly

See to lhs

Cut slab loose to inspection chamber

12

Page 14: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportHallway

FD difficult to lock due to door not being fitted

flush to the frame

Fixing missing to head of FD frame within

profile

Finish around FD perimeter incomplete and

paint running onto frame

Plaster seperated around FD perimeter and

increases when door opened and closed

Margin around FD perimeter inconsistent and

draught seal hairs coming through to rhs

Seal inconsistent to foot of FD cill

13

Page 15: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportHallway

Scratches to FD spy glass

Scuffs with plaster to wall around FD

Various scratches to FD letter plate and door

frame

Finish around alarm controller incomplete and

plaster jointing tape visible

Paint finish to skirting and wall above

incomplete either side of door

Finish to and around socket in inconsistent

14

Page 16: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportHallway

Paint finish to kitchen door frame and

surround incomplete

Flashings to walls around hallway

Paint finish to wall and skirting around rad

incomplete

Paint finish to living room door frame, skirting

and wall surround incomplete

Plaster finish around alarm sensor untidy

Damage to floor tile lhs of kitchen door - top

finish to tile has chipped away

15

Page 17: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportHallway

Paint finish to understair storage door frame

and surround incomplete

Paint finish to protruding newel post

incomplete

Stat loose to wall and finish around

incomplete

Finish around components inconsistent lhs of

dwc

Paint finish to dwc door frame and surround

incomplete

Paint finish to ceiling incomplete

16

Page 18: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportDWC

Adjustment required to door as not catching

to lock properly

Paint finish to skirting and wall above

incomplete

Damage to splashback tile trim joints

Damage to wall behind basin and pedestal

Marks to floor around pedestal

Tile trim seperated around splashback

17

Page 19: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportDWC

Plaster uneven to wall above basin

Paint finish to wall and skirting around rad

incomplete

Area not cleaned behind rad

Large gap in plaster behind consumer unit

Cap missing to boxing lhs of toilet

Paint finish to wall and skirting around toilet

incomplete

18

Page 20: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportDWC

Paint finish to window board and reveals

incomplete

Finish around window board incomplete

Finish to wall behind rad incomplete

19

Page 21: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportGeneral

Various window frame not cleaned around

property

20

Page 22: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportCupboard Understairs

Finish around components incomplete

Paint finish to door frame and surround

incomplete

Tile cut not straight to door

21

Page 23: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportKitchen

Paint finish to door frame and surround

incomplete

Door hinges binding

Scratches to light switch face plate

Hole in plinth rhs of door

Paint finish to wall above upstand incomplete

Paint finish to and around components

incomplete

22

Page 24: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportKitchen

Inconsistencies to seal around window

perimeter

Paint finish to window board and reveals as

well as wall surround incomplete

Holes to plinth below window units

Damage at pipe ingres to backboard below

sink - no rosettes used

Finish to wall around boiler fuse spur

inconsistent

Cabling cut off stuck within boiler controller

screen

Paint and plaster finish to wall below boiler

incomplete

23

Page 25: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportKitchen

Paint finish to wall and ceiling around

extractor hood incomplete

Sealed incomplete to splashback and upstand

Gas seal incomplete to hob - check spec

Finish to wall around component incomplete

Cut to plinth inconsistent - margin varying

around room perimeter (no trim has been

installed) ☐

Plaster board joint visible to ceiling infront of

window

24

Page 26: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportDining Room

Various marks to wall around dining room

Finish to wall and skirting around rad

incomplete

Damage to the rad

Cover loose and finish around perimeter

incomplete to components

Finish to and around alarm sensor incomplete

25

Page 27: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportLiving Room

Door handle loose

Gap in door frame to floor tiles to bottom rhs -

can see straight to unfinished flooring

Paint finish to door frame and surround

incomplete

Finish to and around light switch incomplete

Marks to wall rhs of door

26

Page 28: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportLiving Room

Finish to and around component inconsistent

lhs of TV position

Paint finish to reveals and wall return

incomplete

Paint finish to window board incomplete

Handle sticking to patio doors and adjustment

required to locking mechanism

Patio door threshold not cleaned out

Paint finish to skirting and reveals incomplete

27

Page 29: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportLiving Room

Marks to patio door and glass

Residue and gap to door frame foot

Marks to ceiling inconsistent

Finish around alarm sensor incomplete

28

Page 30: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportStairs 1

Damage to floor tiling at foot of stair string

Step creaking at bottom of stairs

Paint finish to stair string and wall above

incomplete around

Paint finish inconsistencies to stair furniture

Paint finish to between stairs and first floor

incomplete

Damage to handrail

29

Page 31: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportStairs 1

Finish around protruding newel post

incomplete

Paint finish to the ceiling above stairs

incomplete

Finish to and around stair nosing incomplete

from landing / 1st floor

Nail coming through handrail into newel post

at top of of stairs

Damage to newel post at top of stairs

Damage to stair string at top of stairs

30

Page 32: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportStairs 1

Damage to handrail

Damage to stair spindles

31

Page 33: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportLanding

Paint finish to bathroom door frame and

surround incomplete

Finish around components incomplete lhs of

bathroom

Paint finish to bed 2,3 and 4 door frames and

surround incomplete

Light switches not central and finish around

perimeter incomplete between bed 2 and 3

Finish around room sensor incomplete

Nail coming through door frame to top rhs

(bed 4)

Paint not cleaned from ceiling components

32

Page 34: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 4

Door dropped from hinges and margin

showing to be inconsistent and increasing to

lhs ☐

Floor creaking infront of door

Finish to skirting and wall above incomplete

and nails visible

Various marks to wall rhs of door

Finish to wall and skirting around rad

incomplete

Paint finish to window board and reveals

incomplete

33

Page 35: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 4

Inconsistencies to seal around window

perimeter

Beading seperated to LH window head and

sticker residue not removed

Marks visible to ceiling around pendant and

rhs

Finish around light switch inconsistent

34

Page 36: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 2

Door rattling within keep

Paint finish to door frame and surround

incomplete

Door dropped from hinge

Paint finish to window board incomplete

Sticker residue visible around window

perimeter to beading

Paint finish to reveals incomplete

35

Page 37: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 2

Flooring creaking lhs of door

Finish around pendant incomplete

36

Page 38: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 3

Paint finish to door frame and surround

incomplete

Door rattling within keep

Paint finish to skirting and wall above

incomplete around room

Paint finish to window board and reveals

incomplete

Seal incomplete around window perimeter

Paint finish to wall and skirting around rad

incomplete

Nicks to skirting

37

Page 39: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 3

Various flashings to ceiling

38

Page 40: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBathroom 1

Paint finish to door frame and surround

incomplete

Nail coming through door frame to rhs and

head

Inconsistencies to sealant around window

perimeter

Bath panel bowed to lhs where likely ill

supported

Bath creaking when stepped on - likely ill

supported below to feet - this can cause

sealant to seperate and water ingress below ☐

39

Page 41: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBathroom 1

Sealant incomplete around shower mixer,

outset from wall so will allow water to ingress

Shower screen not water tight

Grouting inconsistencies rhs of bath

Basin leaking

Finish to behind rad incomplete

40

Page 42: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBathroom 1

Grouting incomplete to window cill including

to front

Tile trim not cleaned around room

Tile trim corner joints not fitted flush

Wall tiling short to floor behind toilet and

sealant seperated

Paint finish to wall and skirting around rad

incomplete

41

Page 43: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBathroom 1

Finish to behind rad incomplete and no

rosettes to angle valves

Finish to skirting and wall above incomplete

Door stop loose

42

Page 44: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportStairs 2

Finish to skirting and wall above incomplete

Paint finish to stair furniture and apron

incomplete

Plaster board joint visible to wall

Paint finish incomplete between stairs and

2nd floor

Finish to top newel post incomplete

43

Page 45: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportStairs 2

Finish to skirting and wall above inconsistent

at top of stairs

Finish to and around light switch at top of

stairs incomplete

Paint finish to door frame and surround

incomplete and nail visible lhs

44

Page 46: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 1

Paint finish to both door frames and surround

incomplete including around components

Paint finish to skirting and wall above

incomplete around room

Door handle loose and rattling

Plaster finish to ceiling arch uneven

Paint finish to window board and reveals

incomplete

Scuffs to window frame

45

Page 47: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 1

Plaster and paint finish to wall around rad

incomplete

Plaster finish uneven to lhs of window

Plaster board joint visible to ceiling and

plaster uneven

Paint finish to walls around window

incomplete

Finish to wall and skirting around rad

incomplete

46

Page 48: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportBed 1

Paint and plaster finish to reveals uneven

Inconsistencies to sealant around skylight

window perimeter

Paint finish to wall lhs of ensuite incomplete

Finish to ceiling around loft hatch incomplete

Pendant casing not cleaned

47

Page 49: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportEnsuite 1

Paint finish to door frame and surround

incomplete

Plaster inconsistencies to wall above door

Door hinges creaking

Finish to skirting and wall above incomplete

around toilet

Finish to behind toilet untidy

Finish to behind basin incomplete

Finish to tile trim around splashback

inconsistent

48

Page 50: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportEnsuite 1

Inconsistencies to sealant around skylight

window perimeter

Plaster and paint finish to skylight window

reveals incomplete

Tile trim joint jagged

Finish to wall and skirting either side of shower

Shower screen not cleaned out to frame

Paint finish incomplete around shower

49

Page 51: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportEnsuite 1

Finish to behind towel rad incomplete and

around angle valves

Paint finish behind rad incomplete

Finish around ceiling components incomplete

50

Page 52: HouseScan Pr ofessional Snagging · HouseScan Sample Report Front Elevation Damage to dwc stone cill across entire section & FD canopy not watertight - GRP section not flush to brickwork

HouseScan Sample ReportLoft

Ducting not connected to ensuite fan from tile

vent through insulated warm roof chipboard

section ☐

No durgoe or capping fitted to SVP

Nails visible coming through chipboard

Flies within loft would suggest

ingress/infestation point - this could not be

located during inspection ☐

Nails sticking up coming through timbers

51