Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation...

32
BUILD YOUR REPUTATION ON OURS Horizontal Series FAN COIL TECHNICAL CATALOG

Transcript of Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation...

Page 1: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

BUILD YOUR REPUTATION ON OURS

Horizontal SeriesFAN COIL TECHNICAL CATALOG

Page 2: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com2

Horizontal Series

International Environmental Corporation (IEC) works continually

to improve its products. As a result, the design and specifications

of each product may be changed without notice and may not be

as described herein. Please contact IEC for information regarding

current design and product specif ications. Statements and

other information contained herein are not express warranties

and do not form the basis of any bargain between the parties

but are merely IEC’s opinion or commendation of its products.

Manufacturer’s standard limited warranty applies.

2 Table of Contents

3-4 Portfolio

5 Features & Benefits

6 Unit Model Key

7 Ratings & Listings

8 Air Delivery

9 Sound Data

10-13 Fan Performance Curves

14 Electric Heating

15 Motor Data

16-25 Physical Data

26-30 Standard Features & Options

31 Piping Packages (Typical)

TABLE OF CONTENTS

Page 3: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

3

PORTFOLIO

CBY - Horizontal Telescoping Hideaway 200 CFM to 1200 CFMThe Horizontal Telescoping Hideaway (CBY) fan coil unit is

mounted fully-recessed for ceiling-recessed applications. The

CBY’s telescoping frame with hinged panel adapts to any

ceiling type and ensures exact alignment of the panel with

the ceiling. The hinged-bottom panel provides easy access

to all internal components. Standard CBY units are provided

with a galvanized finish on the cabinet and powder-coat

paint finish on the bottom-access panel.

CHY - Horizontal Hideaway 200 CFM to 1200 CFMThe Horizontal Hideaway (CHY) fan coil unit is designed

specifically to meet the many varied requirements for a

ceiling hideaway installation. The low-silhouette styling of

the CHY makes this unit ideally suited for drop-ceiling and

over-closet applications. Standard CHY units are provided

with a galvanized finish.

Page 4: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com4

Horizontal SeriesPORTFOLIO, Cont’d.

CXB - Horizontal Cabinet 200 CFM to 1200 CFMThe Horizontal Cabinet (CXB) fan coil unit is designed

specifically for exposed mounting in hotels, motels,

hospitals, nursing homes, offices or other commercial

establishments. With the CXB, valuable floor space is not

required, and its slim, attractively-styled cabinet blends

with all types of decor. Since there is no requirement for

duct work or structure modifications, the CXB is ideal for

retrofit applications. Standard CXB units are provided with a

powder-coat paint finish.

CPY - Horizontal Hideaway with Plenum 200 CFM to 1200 CFMThe Horizontal Hideaway with Plenum (CPY) fan coil unit

provides the same basic features of the CHY plus a return

air plenum for above-ceiling mounting in closets, hallways

or bathroom areas. The CPY design enables the unit to be

adapted to installations requiring return air ducts or to be

used as a return-air plenum with a unit-mounted filter and

filter-rack assembly. CPY units are shipped from the factory

ready for installation with the plenum section in place. No

field fabrication is required. CPY units are designed with

interchangeable panels so that the unit may be modified on

site to accommodate a rear or bottom return. Standard CPY

units are provided with a galvanized finish.

Page 5: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

5

FEATURES & BENEFITS

Application Fit• Multiple cabinet choices are available in 7 nominal

CFM sizes for application in a variety of room layouts.

o Horizontal Cabinet units (CXB) with aesthetically

pleasing cabinetry offer capacities that are ideal for

air conditioning in dormitories, small apartments,

schools and many other applications. Front supply,

bottom or rear return are available.

o Horizontal Telescoping Hideaway units with

painted access panel (CBY) allows smooth fit up

to plaster or sheet rock ceilings. Standard units

include bottom louvered return air with the filter

located in the access panel.

o Horizontal Hideaway models (CHY) units are

installed above the ceiling with or without ducted

supply air and open “soffit” return with an optional

ceiling-mounted filter-grille.

o Horizontal Hideaway models with plenum (CPY)

units are installed above the ceiling with or

without ducted supply air and ducted return air.

The return air filter is either mounted on the unit

plenum or installed in an optional ceiling filter-

grille.

Design Flexibility• Easy to use ratings program to speed up project

design.

• Standard and high capacity hydronic coils and DX coils

are available to match the heating and cooling loads of

the space.

• Optional powder-paint finish colors and grille

selections will complement most décors (exposed

units).

• CXB and CBY units ordered with optional rear return

are constructed with a solid bottom panel.

• Customizable cabinetry makes these units ideal for

renovation jobs or where special sizes are required to

fit oversized valves and control packages.

• Optional airflow configuration (front supply, bottom

supply, rear return or bottom return) to meet certain

design limitations.

• Outside air connections are available to meet

ventilation requirements and reduce field labor (CXB/

CBY/CPY).

• Wide variety of factory assembled valve packages to

meet desired controls specifications.

• Optional condensate overflow switch to address latest

building codes where required.

• Wide variety of optional insulation materials are

available to address IAQ concerns.

Ease of Installation• Factory assembled valve packages minimize piping

work at the job site (shipped loose for field mounting).

• Optional unit mounted controls, service switches and

fusing minimize the electrical work required on site.

• Units are tagged at the factory for clear identification

on job site.

• Opposite end connection units may minimize the

piping work on renovation jobs.

Ease of Service• All components are accessible by simply removing the

access panel.

• Filters can be replaced without tools or by opening the

bottom panels on exposed units.

• Blower assembly easily removed from the rear of coil

for service and cleaning.

Quality and Safety• Every unit is tested and inspected at the factory for

trouble free start-up.

• ETL and CETL listed.

• AHRI certified.

Page 6: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com6

Horizontal SeriesUNIT MODEL KEY

Y • NoneYY • None

• R • 3 Row, AAVS • 4 Row, AAV

CoilConstruction

Y • StdS • SS Wrapper

Code ItemsCode

* Consult factory for 50Hz applications.

** Note that kWs depend on voltage and unit size.

*** Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections.

Arrangement

56

CHY • Horizontal HideawayCPY • Horizontal Hideaway with PlenumCBY • Horizontal Telescoping HideawayCXB • Horizontal Cabinet

02 • 200 CFM03 • 300 CFM04 • 400 CFM06 • 600 CFM08 • 800 CFM10 • 1000 CFM12 • 1200 CFM

Two-pipe Cooling and Heating or Four-pipe Cooling

A 3 RowB • 4 RowD • 2 Row

Voltage

C • 120 VD • 208 VE • 240 VF • 277 VV • 220 V (50)*U • 240 V (50)*

Four-pipe Heating

Y • None6 • 1 Row7 • 2 Row

Voltage

C • 115-1-60

D • 208-1-60

E • 230-1-60

F • 277-1-60

V • 220-1-50*

U • 240-1-50*

Hand***

R • RightL • Left

Voltage

C • 120 VB • 24 V

D • 208 VE • 240 VF • 277 VV • 220 V (50)*

System

Manual Fan Operation

A • Standard Wall Mount (Switch Only)

Type

CHY, BHY

CPY, BPY

CBY

CXB

kW**

AY • 0.50 HY • 5.00BY • 1.00 JY • 6.00CY • 1.50 KY • 7.00DY • 2.00 LY • 8.00FY • 3.00 NY • 10.00GY • 4.00

Stages

Y • Single Stage Only

Coil Connection

Y • NoneS • Same EndO • Opposite End

•U • 240 V (50)*

6

6

6

6

5

5

5

MOTOR

05C 2

SIZE

030 4

CONTROLS

07C BP

ELECTRIC HEAT

04aY YC B

VINTAGEUNIT

02Y

01C B

COILS

04Y YA Y

HAND/ARRANGEMENT

06R 5

Thermostat

Function ControlG • 2 Pipe Heat OnlyH • 2 Pipe Cool OnlyK • 2 Pipe Heat and CoolM • 2 Pipe Heat and Cool w/Aux. Elec. HeatP • 2 Pipe Cool Only w/Total Elec. HeatR • 4 Pipe Heat and Cool

A • TB155 Wall Series, ACO, Vertical Mnt.B • TB155 Wall Series, ACO, Horizontal Mtd.P • Basic 24V Digital Programmable, ACO N • Basic 24V Non-Programmable, ACOF • Premium 24V Digital 7-Day Programmable, with Proportional Fan/Valves Option, ACOG • Premium 24 Digital BACnet with Proportional Fan/Valves Option, ACO

2 • Permanent Split CapacitorA • ECM, 3-Spd Relay Brd (L/M/H)B • ECM, Proportional (0-10VDC)C • ECM, 4-Spd EVO Board, Solid State w/PWM

Page 7: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

7

RATINGS & LISTINGS

C-ETL US ListingIEC’s Horizontal Series units are

listed by ETL. The C-ETL-US listing

signifies that IEC’s fan coil units

have been examined by ETL and

are in compliance with both the

U.S. and Canadian applicable

standards.

AHRI CertificationIEC’s Horizontal Series units are

certified in compliance with

Air-Conditioning, Heating, and

Refrigeration Institute (AHRI) industry standard AHRI-440 for

room fan coil units. Approved standard ratings are tabulated

below.3061627

HEATING AND COOLING EQUIPMENT

Standard Ratings

Unit Type

Unit Cell Size

Nominal CFM

Cooling Capacity Power Input

Watts PSCTotal MBH

Sensible MBH

CHYCPYCXBCBY

02-A 200 6.0 4.4 87

03-A 300 9.0 6.3 85

04-A 400 12.1 8.8 165

06-A 600 17.3 13.0 225

08-A 800 22.6 16.2 235

10-A 1000 27.5 21.0 305

12-A 1200 32.8 25.0 450

CHYCPYCXBCBY

02-B 200 6.9 4.3 87

03-B 300 9.8 6.5 85

04-B 400 13.8 9.8 145

06-B 600 19.6 14.3 220

08-B 800 25.5 18.8 235

10-B 1000 31.0 22.0 300

12-B 1200 37.2 27.7 425

NOTES: 1. Ratings are based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F water temperature rise, high fan speed, motor voltage 115/1/60, and air flow under dry coil conditions.

2. For all application ratings, use IEC’s computer selection program, the quick-selection ratings provided in this catalog, or contact your local IEC representative.

3. For additional information, please consult AHRI’s website at www.ahrinet.org.

Page 8: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com8

Horizontal SeriesAIR DELIVERY

Air Delivery (60 Hz)Model Coil Unit

SizeCFM@ 0.0 ESP - For Fan Speed High Speed CFM @ ESP IndicatedLow Med High 0.05 0.10 0.15 0.20 0.25 0.30 0.35

CHY

3 Row

2 221 271 357 338 318 298 277 256 234 2123 238 291 384 359 333 308 282 258 233 2094 296 410 656 610 565 522 479 438 398 3606 275 402 733 698 663 626 587 547 506 4648 367 700 928 893 856 818 779 738 696 652

10 622 845 1291 1215 1140 1068 997 929 862 79812 726 1300 1560 1478 1394 1305 1213 1117 1017 913

4 Row

2 218 260 327 312 296 279 262 244 224 2053 218 264 337 313 291 271 252 234 219 2044 279 382 567 526 488 452 418 387 358 3316 266 388 683 652 619 585 550 514 476 4378 350 670 902 857 815 775 737 700 666 633

10 612 824 1208 1146 1084 1022 959 897 834 77112 696 1245 1480 1407 1330 1249 1164 1075 982 885

CPY

3 Row

2 198 232 285 270 254 237 221 204 186 1683 221 270 346 325 304 283 260 237 212 1874 265 358 523 491 459 428 397 368 338 3096 267 384 650 619 586 549 509 466 420 3718 356 642 789 752 713 672 630 586 540 492

10 552 738 1063 1008 953 899 846 794 742 69112 668 1122 1307 1241 1173 1103 1031 958 884 807

4 Row

2 194 230 276 261 245 228 211 193 175 1553 213 258 325 305 284 262 239 216 192 1664 259 346 490 462 434 406 377 349 320 2916 275 390 628 597 563 525 483 438 390 3378 349 622 755 726 692 655 612 566 515 459

10 541 723 1023 971 918 865 813 761 709 65712 635 1079 1271 1204 1136 1066 995 922 847 771

CBY

3 Row

2 211 259 333 310 287 265 244 224 204 1843 216 270 353 335 317 297 277 256 234 2114 303 398 572 544 515 486 456 427 396 3656 294 422 712 676 637 597 554 509 462 4138 375 678 821 786 748 707 664 617 568 516

10 536 719 1098 1038 978 916 853 790 726 66012 634 1115 1313 1248 1180 1111 1041 969 896 821

4 Row

2 196 240 302 277 253 232 212 194 178 1643 210 262 340 322 303 284 264 243 221 1994 286 375 523 495 466 437 407 377 347 3166 277 400 666 628 588 547 505 461 417 3718 364 652 776 737 696 653 608 560 511 459

10 508 680 1019 964 907 850 791 732 672 61112 598 1032 1188 1131 1072 1012 949 885 818 750

CXB

3 Row

2 203 241 306 290 271 249 225 199 170 1393 220 273 335 325 310 289 263 232 195 1534 279 371 519 493 466 439 410 380 350 3186 308 418 640 602 564 526 487 447 408 3688 314 625 776 746 710 669 622 570 513 450

10 474 648 1027 965 900 833 764 693 620 54412 684 1179 1226 1154 1082 1009 935 861 785 710

4 Row

2 191 233 291 271 250 229 207 184 161 1373 195 256 320 296 272 247 220 192 163 1334 263 348 481 458 434 407 378 347 315 2806 293 402 606 565 525 486 446 408 369 3328 296 595 728 701 665 621 568 507 439 361

10 447 607 981 920 855 786 713 635 553 46612 578 972 1108 1040 971 901 830 759 686 613

NOTES: 1. Tabled values are standard CFM at sea level, 70°F with dry coil. 2. Ratings include factory-installed filter and/or grille, where applicable. 3. Consult factory for 50 Hz applications.

Page 9: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

9

SOUND DATA

Sound DataUNIT SIZE RATING FAN

SPEED CFMSOUND POWER LEVEL, Lw (dB one reference pico watt)

125 Hz 250 Hz 500 Hz 1K Hz 2K Hz 4K Hz 8K Hz A-wgt (dBA)

2

CASING RADIATED

H 270 60 54 51 48 43 38 37 53M 170 55 51 44 39 35 31 34 47L 135 53 49 39 34 29 29 34 44

DUCTED DISCHARGE

H 270 52 52 53 47 46 40 37 54M 170 47 45 45 39 37 31 34 46L 135 46 43 40 33 31 29 34 42

3

CASING RADIATED

H 290 63 54 52 49 44 40 38 54M 205 59 47 44 40 35 31 34 47L 155 55 42 39 34 29 29 34 43

DUCTED DISCHARGE

H 290 59 54 54 51 47 41 38 56M 205 55 46 47 41 37 31 34 48L 155 51 42 42 35 31 29 34 43

4

CASING RADIATED

H 540 70 58 55 52 48 43 39 58M 360 62 49 46 42 37 32 34 50L 250 54 42 38 32 30 30 34 42

DUCTED DISCHARGE

H 540 64 57 59 55 50 44 39 60M 360 55 49 51 52 46 36 36 50L 250 48 42 43 35 30 28 33 43

6

CASING RADIATED

H 680 65 59 57 52 48 45 42 59

M 445 57 50 47 41 37 33 34 49L 330 52 43 40 34 29 29 34 43

DUCTED DISCHARGE

H 680 63 58 59 56 50 46 42 60M 445 57 49 50 45 39 33 34 50L 330 53 43 42 37 30 29 34 44

8

CASING RADIATED

H 765 65 61 58 54 51 48 45 60M 670 63 58 55 51 47 44 41 57L 410 55 47 44 38 34 31 34 46

DUCTED DISCHARGE

H 765 63 61 61 58 53 50 46 63M 670 60 58 58 54 50 46 42 59L 410 52 47 47 41 36 32 35 48

10

CASING RADIATED

H 1105 68 64 59 55 52 48 45 62M 730 64 55 51 45 41 37 35 54L 490 59 48 43 36 31 30 34 47

DUCTED DISCHARGE

H 1105 65 62 64 60 55 50 46 65M 730 63 54 56 50 44 38 36 56L 490 58 46 47 40 33 30 34 48

12

CASING RADIATED

H 1225 68 65 61 57 53 50 45 63M 1140 67 63 59 54 51 47 42 61L 745 59 54 50 44 40 35 34 52

DUCTED DISCHARGE

H 1225 65 63 65 60 57 52 47 66M 1140 63 61 63 58 54 50 44 64L 745 56 54 55 48 43 37 35 54

Page 10: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com10

Horizontal SeriesFAN PERFORMANCE CURVES

SCFM

ECM Operating Range:PSC Motor Fan Curve: 3-Row- 5-Row4-Row

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0 50 100 150 200 250 300 350

ESP

(in.W

.C.)

Low

Med

High

Unit Size 02 - CPY

ECM Operating Range:

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

0 50 100 150 200 250 300 350 400 450

ESP

(in.W

.C.)

SCFM

Unit Size 03 - CPY

Low

Med

High

PSC Motor Fan Curve: 3-Row 5-Row4-Row

Page 11: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

11

FAN PERFORMANCE CURVES, Cont’d.

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

100 150 200 250 300 350 400 450 500 550 600 650

ESP

(in.W

.C.)

SCFM

Unit Size 04 - CPY

ECM Operating Range:

Low

Med

High

PSC Motor Fan Curve: 3-Row- 5-Row4-Row

SCFMPSC Motor Fan Curve: 3-Row 5-Row

4-Row

Unit Size 06 - CPY

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

100 150 200 250 300 350 400 450 500 550 600 650 700 750

ESP

(in.W

.C.)

ECM Operating Range:

Low

Med

High

Page 12: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com12

Horizontal SeriesFAN PERFORMANCE CURVES, Cont’d.

SCFM

ECM Operating Range:PSC Motor Fan Curve: 3-Row- 5-Row4-Row

Unit Size 08 - CPY

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

200 250 300 350 400 450 500 550 600 650 700 750 800 850

ESP

(in.W

.C.)

Low

Med

High

-

SCFM

ECM Operating Range:PSC Motor Fan Curve: 3-Row- 5-Row4-Row

Unit Size 10 - CPY

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250

ESP

(in.W

.C.)

Low

Med

High

Page 13: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

13

FAN PERFORMANCE CURVES, CONT’D.

SCFM

ECM Operating Range:

Unit Size 12 - CPY

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5

350 450 550 650 750 850 950 1050 1150 1250 1350 1450 1550

ESP

(in.W

.C.)

Low

Med

High

PSC Motor Fan Curve: 3-Row- 5-Row4-Row

Page 14: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com14

Horizontal SeriesELECTRIC HEATING

Electric Heater Selection

Voltage kWUnit Size

02 03 04 06 08 10 12

120 V

0.5 • • - - - - -

1.0 • • • • • - -

1.5 • • • • • - -

2.0 • • • • • • •3.0 - • • • • • •

208 V

0.5 • • - - - - -

1.0 • • • • • - -

1.5 • • • • • - -

2.0 • • • • • • •3.0 - • • • • • •4.0 - - - • • • •5.0 - - - •

Note 6 • • •6.0 - - - •

Note 6•

Note 6 • •8.0 - - - - - •

Note 6•

Note 6

240 V277 V

0.5 • • - - - - -

1.0 • • • • • - -

1.5 • • • • • - -

2.0 • • • • • • •3.0 - • • • • • •4.0 - - - • • • •5.0 - - - •

Note 6 • • •6.0 - - - •

Note 6•

Note 6 • •8.0 - - - - - •

Note 6•

Note 6

10.0 - - - - - - • Note 6

NOTES: 1. All heaters are single stage and single phase. 2. Heaters over 48 Amps are subdivided and fused. 3. Electric Heating Capacities (BTUH) = Heater kW x 3413. 4. Electric Heater Amperage = (Heater kW x 1000)/Applied

Voltage) 5. Consult factory for 50 Hz applications. 6. High and medium speed only.

Electric Resistance HeatingElectric heaters are available on IEC Horizontal Series fan coil

units for the following applications.

Total Electric HeatTotal electric heat eliminates the requirement for a boiler.

Heating and/or cooling may be available on an individual

basis throughout the year. Two-pipe chilled water is used

for cooling; and the electric heater is used for heating.

Individual room controls can be supplied for either manual

or automatic changeover.

Auxiliary Electric HeatAuxiliary electric heat is ideal for tempering room air

between seasons and during the cooling season when

chilled water is being circulated. Individual room controls

are supplied to provide electric heat only when chilled water

is being circulated. During regular heating season, heating is

provided by hot water being circulated in the system.

ConstructionThe heater coils of high-grade resistance wire are supported

by ceramic insulators on plated steel brackets. These heat

elements are suspended directly in front of the fan outlet

between the blower and the coil. High limit thermal cutouts

protect the heater in the event of air failure. There are many

special applications and control sequences for electric heat.

For special applications, please consult the factory.

Page 15: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

15

MOTOR DATA

Thermal Overload Protection and ETL ListingAll permanently lubricated split-capacitor motors furnished by IEC contain internal thermal-

overload protection. The overload automatically resets when the temperature returns to a

safe limit. Electronics Testing Laboratories, Inc. approves the motor and thermal overload

combination at locked rotor conditions only.

Motor Performance Data - CHY, CPY, CXB, CBY

Voltage Fan SpeedUnit Size 02 03 04 06 08 10 12

Nominal HP 1/30 1/30 1/12 1/12 1/6 (2) 1/12 (2) 1/6

115 V

60 Hz

1 Phase

HighAmps 0.53 0.83 1.40 1.40 2.50 2.80 5.00

Watts 78 89 144 151 223 286 399

MediumAmps 0.31 0.50 0.70 0.72 1.50 1.40 2.80

Watts 58 62 91 86 166 184 307

LowAmps 0.27 0.34 0.45 0.45 1.20 0.90 1.20

Watts 44 47 68 60 83 134 166

208 V

60 Hz

1 Phase

HighAmps 0.48 0.48 0.69 0.69 1.30 1.38 2.60

Watts 98 99 120 132 189 245 325

MediumAmps 0.29 0.29 0.43 0.47 0.69 0.94 1.33

Watts 75 75 88 92 109 182 208

LowAmps 0.15 0.15 0.22 0.24 0.47 0.46 0.94

Watts 49 49 54 55 60 109 120

230 V

60 Hz

1 Phase

HighAmps 0.48 0.48 0.69 0.69 1.30 1.38 2.60

Watts 114 112 137 150 206 281 356

MediumAmps 0.31 0.32 0.45 0.52 0.70 1.00 1.34

Watts 87 86 104 111 128 210 241

LowAmps 0.15 0.15 0.24 0.28 0.50 0.50 1.00

Watts 57 57 62 65 72 130 143

277 V

60 Hz

1 Phase

HighAmps 0.35 0.35 0.69 0.69 0.91 1.38 1.82

Watts 104 112 143 155 245 288 426

MediumAmps 0.26 0.26 0.43 0.43 0.62 0.80 1.20

Watts 86 91 107 112 152 219 293

LowAmps 0.16 0.16 0.25 0.35 0.35 0.25 0.66

Watts 55 57 65 67 120 132 234

NOTES: 1. Total unit motor Amps and Watts are shown. 2. Consult factory for 50 Hz applications.

Page 16: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com16

Horizontal SeriesPHYSICAL DATA

CHY - Horizontal Hideaway

AIR VENT

1"(25) SUPPLY

DUCT COLLAR

SUPPLYAIR

MTG. HOLES

CHILLED/HOT WATERSUPPLY & RETURNCONNECTIONS(SEE SUPPLEMENTALDRAWING FOR COILSTUBOUT LOCATIONS)

A'OPTIONAL EXTENDEDDRAIN PAN

OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 4)

OPTIONAL 5/8 (16) O.D. TELL-TALE

DRAIN CONNECTION, AVAILABLE ON

STANDARD AND EXTENDED DRAIN PANS

7/8 (22) O.D. CONDENSATE DRAIN

FLEXIBLE METALCONDUIT - SEE

JUNCTION BOX

(REMOTE MOUNT)

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

6(152)

1-1/2(38)

B

A

3(76)

2-1/4(57)

1-1/8(29)

1(25)

H

E

3/4(19)TYP

16(406)

G F

17-1/2(445)

8-3/8(213)

D'

7/8(22)

4(102)

4(102)

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)DIMENSION "J"

RESILIENT MOUNTINGGROMMET W/ 3/8 (10)DIA. HOLES (TYP. OF 4)

7-1/3(187)

2(51)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ E F G H J Blower Motor

CHY02 21-1/4 (540) 31-1/4 (794) 16 (406) 13 (330) 18-1/4 (464) 6-1/4 (159) 8-3/4 (222) 19-3/4 (502) 38 (965) 1 1 36CHY03 25-1/4 (641) 36-1/4 (921) 20 (508) 14 (356) 22-1/4 (565) 6-1/4 (159) 8-3/4 (222) 23-3/4 (603) 38 (965) 1 1 39CHY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 38 (965) 2 1 49CHY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 38 (965) 2 1 59CHY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 38 (965) 2 1 64CHY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 60 (1524) 4 2 95CHY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 13 (330) 62-1/4 (1581) 7-1/2 (191) 10 (254) 63-3/4 (1619) 65 (1651) 4 2 107

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Drip lip recommended. 5. Product specifications are subject to change without notice. 6. Control box size and position may vary (consult factory). 7. Dimension “G” represents maximum on lowest end of sloped drain pan. 8. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 17: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

17

PHYSICAL DATA, Cont’d.

CHY - Horizontal Hideaway with Electric Heat

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

CONTROL BOX

(REMOTE MOUNT)

HEATER ELEMENTELECTRIC STRIPHIGH LIMITSTRIP HEATER

CONDUIT - SEEFLEXIBLE METAL

7/8 (22) O.D. CONDENSATE DRAIN

OPTIONAL 5/8 (16) O.D. TELL-TALE

DRAIN CONNECTION, AVAILABLE ON

STANDARD AND EXTENDED

DRAIN PANS

SHIPPED LOOSEOPTIONAL DRIP LIP

A'

CONNECTIONSSUPPLY & RETURNCHILLED/HOT WATER

MTG. HOLES

AIRSUPPLY

DUCT COLLAR1"(25) SUPPLY

VENTAIR

6(152)

1-1/2(38)

1-1/8(29)

2-1/4(64)

A

B

E

1(25)

D'

21-1/2(546)

12-3/8(314)

G F

7/8(22)

16(406)

H3/4(19)TYP

3(76)

(NOTE 4)

6(152)STD.

5-3/8(137)STD.

DIMENSION "J"

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)

RESILIENT MOUNTING GROMMETW/ 3/8 (10)

DIA. HOLES(TYP. OF 4)

OPTIONAL EXTENDEDDRAIN PAN

7-1/3(187)

2(51)

(SEE SUPPLEMENTALDRAWING FOR COILSTUBOUT LOCATIONS)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ E F G H J Blower Motor

CHY02 21-1/4 (540) 31-1/4 (794) 16 (406) 13 (330) 18-1/4 (464) 6-1/4 (159) 8-3/4 (222) 19-3/4 (502) 38 (965) 1 1 38CHY03 25-1/4 (641) 36-1/4 (921) 20 (508) 14 (356) 22-1/4 (565) 6-1/4 (159) 8-3/4 (222) 23-3/4 (603) 38 (965) 1 1 41CHY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 38 (965) 2 1 51CHY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 38 (965) 2 1 61CHY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 38 (965) 2 1 66CHY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 60 (1524) 4 2 97CHY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 13 (330) 62-1/4 (1581) 7-1/2 (191) 10 (254) 63-3/4 (1619) 65 (1651) 4 2 109

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Drip lip recommended. 5. Product specifications are subject to change without notice. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 18: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com18

Horizontal SeriesPHYSICAL DATA, Cont’d.

CPY - Horizontal Hideaway with Plenum

15-1/4(387)

11-3/8(289)

FILTER REMOVAL

FILTER REMOVAL

10-1/2(267)

20(508)

19(483)

7/8(22)

FG

1"(25) SUPPLYDUCT COLLAR

SUPPLYAIR

E

A 16(406)

1-1/2(38)

1-1/8(29) C

2-1/4(57) B 3(76)

MTG. HOLES

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS(SEE SUPPLEMENTALDRAWING FOR COILSTUBOUT LOCATIONS)

D'

A'

OPTIONALEXTENDED DRAIN PAN

OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 4)

AIR VENT

REAR ACCESSPANEL

1"(25) FILTER

1"(25) RETURNDUCTCOLLAR

1"(25) FILTER

FILTERRETAINER CLIP

BOTTOM ACCESS

PANEL

7/8 (22) O.D.CONDENSATEDRAIN

RETURNAIR

AIRRETURN

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

OPTIONAL5/8 (16) O.D.

TELL-TALE DRAINCONNECTION,

AVAILABLE ON STANDARD

AND EXTENDED DRAIN PANS3-1/4

(83)

HREAR MTG. HOLES

JUNCTION

INSULATED PLENUM

1-1/2(38)

1(25)

3/4(19)TYP

OPTIONAL REAR RETURN

4(102)

3(76) BOX

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)

RESILIENT MOUNTING GROMMET

W/ 3/8 (10) DIA. HOLES

(TYP. OF 4)

2(51)

7-1/3(187)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ E F G H Blower Motor

CPY02 21-1/4 (540) 31-1/4 (794) 16 (406) 18-1/4 (464) 13 (330) 19-3/4 (502) 6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 1 1 55CPY03 25-1/4 (641) 36-1/4 (921) 20 (508) 22-1/4 (565) 14 (356) 23-3/4 (603) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 1 1 60CPY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 2 1 70CPY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 33-1/4 (845) 10 (254) 34-3/4 (883) 7-1/2 (190) 10 (254) 30-3/8 (772) 2 1 82CPY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 37-3/8 (949) 2 1 95CPY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 51-3/8 (1305) 4 2 135CPY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 62-1/4 (1581) 13 (330) 63-3/4 (1619) 7-1/2 (190) 10 (254) 59-3/8 (1508) 4 2 154

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Drip lip recommended. 5. Product specifications are subject to change without notice. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 19: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

19

PHYSICAL DATA, Cont’d.

CPY - Horizontal Hideaway with Plenum with Electric Heat

FRONT VIEW RIGHT SIDE VIEWCONTROL BOXIN TOP & BOTTOM OFELECTRICAL KNOCKOUTS

CONTROL BOX

STRIP HEATER HIGH LIMIT

ELECTRIC STRIP HEATER ELEMENT

3-1/4(83)

3/4(19)

AIRRETURN

INSULATED PLENUM

REAR MTG. HOLESH 1-1/2

(38)

7/8 (22) O.D. CONDENSATION DRAIN

1"(25) FILTER

REARACCESSPANEL

VENT

OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)

W/ 3/8 (10) DIA. HOLES (TYP. OF 4)RESILIENT MOUNTING GROMMET

1(25)

16(406)

3/4(19)TYP

AIRSUPPLY

1"(25)SUPPLY

DUCTCOLLAR

7/8(22)

23(584)

24(610)

10-1/2(267)

FILTERREMOVAL

11-3/8(289)

19-1/4(489)

FILTER REMOVAL

D'

A'

OPTIONAL EXTENDED DRAIN PAN

1"(25) RETURNDUCT COLLAR

1"(25) FILTER

FILTER RETAINER CLIP

BOTTOM ACCESS

PANEL

AIRRETURN

OPTIONAL 5/8 (16) O.D.

TELL-TALE DRAIN CONNECTION,

AVAILABLE ON STANDARD

AND EXTENDED DRAIN PANS

1-1/2(38)

1-1/8(29) C

2-1/4(57) B 3

(76)A

FRONT MTG. HOLES

TOP VIEW OPTIONAL REAR RETURN

FG

6(152)STD.

5-3/8(137)STD.

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 7)

AIR

7-1/3(187)

2(51)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ E F G H Blower Motor

CPY02 21-1/4 (540) 31-1/4 (794) 16 (406) 18-1/4 (464) 13 (330) 19-3/4 (502) 6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 1 1 57CPY03 25-1/4 (641) 36-1/4 (921) 20 (508) 22-1/4 (565) 14 (356) 23-3/4 (603) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 1 1 62CPY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 2 1 72CPY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 33-1/4 (845) 13 (330) 34-3/4 (883) 7-1/2 (190) 10 (254) 30-3/8 (772) 2 1 84CPY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 37-3/8 (949) 2 1 97CPY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 51-3/8 (1305) 4 2 137CPY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 62-1/4 (1581) 13 (330) 63-3/4 (1619) 7-1/2 (190) 10 (254) 59-3/8 (1508) 4 2 156

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested. 7. Control box size and position may vary (consult factory).

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 20: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com20

Horizontal SeriesPHYSICAL DATA, Cont’d.

CBY - Horizontal Telescoping Hideaway

TOP VIEW

FRONT VIEW RIGHT SIDE VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2 (38) KNOCKOUT (TYPICAL)

7/8 (22) KNOCKOUT

DRAIN CONNECTION7/8 (22) O.D. CONDENSATE

AIRRETURN STAMPED

RETURN AIR GRILLE & 1"(25) FILTER

DUCT COLLAR1"(25) SUPPLY

F

1-1/4(32)

24(610)

1-1/2(38)

20-3/4(527)

1-1/2(38)

D

12 (305) MIN.

14 (356)MAX.

11-1/4(286)

A6-1/8(156) B C

1-1/2(38)TYP

CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPED DRIP

JUNCTIONBOX

26(660)

1(25)

1(25)

1-1/2(38)

20-3/4(527)

1-1/2(38) 1

(25)1

(25)

E

6-1/8(156)

AIR

SUPPLY

HINGED BOTTOM RETURN AIR PANEL

OPTIONAL DUCTED REAR RETURN

AIRVENT

UNIT LABEL AND WIRING DIAGRAM (SEE NOTE 6)

1(25)

6(152)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A B C D E F Blower Motor

CBY02 35 (889) 16 (406) 12-3/4 (324) 37 (940) 32 (813) 6 (152) 1 1 115CBY03 35 (889) 20 (508) 8-3/4 (222) 37 (940) 32 (813) 6 (152) 1 1 120CBY04 41 (1041) 26 (660) 8-3/4 (222) 43 (1092) 38 (965) 6 (152) 2 1 135CBY06 53 (1346) 31 (787) 15-3/4 (400) 55 (1397) 50 (1270) 7 (178) 2 1 150CBY08 53 (1346) 38 (965) 8-3/4 (222) 55 (1397) 50 (1270) 7 (178) 2 1 155CBY10 75 (1905) 52 (1321) 16-3/4 (425) 77 (1956) 72 (1829) 7 (178) 4 2 227CBY12 75 (1905) 60 (1524) 8-3/4 (222) 77 (1956) 72 (1829) 7 (178) 4 2 241

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 21: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

21

PHYSICAL DATA, Cont’d.

CBY - Horizontal Telescoping Hideaway with Electric Heat

TOP VIEW

FRONT VIEW

ELECTRIC STRIPHEATER ELEMENT

STRIPA HEATER

HIGH LIMIT

F

D

12(305)MIN.

14(356)MAX.

11-1/4(286)

A6-1/8(156) B C1-1/2

(38)TYP

OPTIONAL "L" SHAPED DRIPLIP, SHIPPED LOOSE (NOTE 5)

CONTROL

26(660)

1(25) 1-1/2

(38)

20-3/4(527)

1-1/2(38)

1(25)

1(25)

E

6-1/8(156)

1(25)

BOX

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)

1(25)

RIGHT SIDE VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2 (38)KNOCKOUT

(TYPICAL)

7/8 (22) KNOCKOUT

DRAIN CONNECTION7/8 (22) O.D. CONDENSATE

AIRRETURN STAMPED

RETURN AIR GRILLE & 1"(25) FILTER

DUCT COLLAR1"(25) SUPPLY

1-1/4(32)

24(610)

1-1/2(38)

20-3/4(527)

1-1/2(38)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)

RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)

AIR

SUPPLY

HINGED BOTTOM RETURN AIR PANEL

OPTIONAL DUCTED REAR RETURN

AIRVENT

6(152)

Unit Model

Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A B C D E F Blower Motor

CBY02 35 (889) 16 (406) 12-3/4 (324) 37 (940) 32 (813) 6 (152) 1 1 117CBY03 35 (889) 20 (508) 8-3/4 (222) 37 (940) 32 (813) 6 (152) 1 1 122CBY04 41 (1041) 26 (660) 8-3/4 (222) 43 (1092) 38 (965) 6 (152) 2 1 137CBY06 53 (1346) 31 (787) 15-3/4 (400) 55 (1397) 50 (1270) 7 (178) 2 1 152CBY08 53 (1346) 38 (965) 8-3/4 (222) 55 (1397) 50 (1270) 7 (178) 2 1 157CBY10 75 (1905) 52 (1321) 16-3/4 (425) 77 (1956) 72 (1829) 7 (178) 4 2 229CBY12 75 (1905) 60 (1524) 8-3/4 (222) 77 (1956) 72 (1829) 7 (178) 4 2 243

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 22: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com22

Horizontal SeriesPHYSICAL DATA, Cont’d.

CBY - Horizontal Telescoping Hideaway with Bottom Supply

FRONT VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2 (38) KNOCKOUT

(TYPICAL)

7/8 (22) KNOCKOUT

D

12"(305)MIN.

14"(356)MAX.

11-1/4(286)

A1-1/2(38)

1-1/2(38)

30-3/4(781)

34(864)

RIGHT SIDE VIEW

AIR PANELBOTTOM RETURNHINGED

1-1/2(38)

AIR GRILLE &

AIR

1"(25) FILTER

STAMPED RETURN

7/8 (22) O.D.CONDENSATE

DRAIN CONNECTION

RETURN

1-1/2(38)

SUPPLYAIR

STAMPED SUPPLY

AIR GRILLE

E

36(914) 30-3/4

(781)

1(25)

1-1/2(38)

1(25) TOP VIEW

1(25) 1-1/2

(38)JUNCTION BOX

1(25)

1-1/2 (38)

RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPED DRIP LIP, SHIPPED LOOSE (NOTE 5)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)

6(152)

OPTIONALDUCTEDREAR RETURN

1(25)

6(152)

AIR VENT

1-1/2 (38)

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit

Unit Weight*A D E F Blower Motor

CBY02 35 (889) 37 (940) 32 (813) 6 (152) 1 1 115CBY03 35 (889) 37 (940) 32 (813) 6 (152) 1 1 120CBY04 41 (1041) 43 (1092) 38 (965) 6 (152) 2 1 135CBY06 53 (1346) 55 (1397) 50 (1270) 7 (178) 2 1 150CBY08 53 (1346) 55 (1397) 50 (1270) 7 (178) 2 1 155CBY10 75 (1905) 77 (1956) 72 (1829) 7 (178) 4 2 227CBY12 75 (1905) 77 (1956) 72 (1829) 7 (178) 4 2 241

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 23: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

23

PHYSICAL DATA, Cont’d.

CBY - Horizontal Telescoping Hideaway with Bottom Supply with Electric Heat

FRONT VIEW

(TYPICAL BOTH SIDES)PARTIAL REAR VIEW

1-1/2 (38) KNOCKOUT

(TYPICAL)

7/8 (22)KNOCKOUT

D

12"(305)MIN.

14"(356)MAX.

11-1/4(286)

A1-1/2

(38) TYP

30-3/4(781)

34(864)

RIGHT SIDE VIEW

1-1/2(38)

AIRRETURN

1-1/2(38)

SUPPLYAIR

E

36(914)

30-3/4(781)

1(25)

1-1/2(38)

1(25)

1-1/2(38)

TOP VIEW

1(25)

1-1/2(38)

1(25)

1-1/2(38)

RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)

OPTIONAL "L" SHAPED DRIP LIP, SHIPPED LOOSE (NOTE 5)

CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)

6(152)

STRIP HEATERHIGH LIMIT

ELECTRIC STRIPHEATER ELEMENT

CONTROLBOX

UNIT LABEL AND WIRING DIAGRAM (SEE NOTE 6)

AIR PANELBOTTOM RETURNHINGED

STAMPED RETURN AIR GRILLE & 1"(25) FILTER

STAMPED SUPPLY

AIR GRILLE

7/8 (22) O.D.CONDENSATE

DRAIN CONNECTION

AIRVENT OPTIONAL

DUCTED REAR RETURN

1(25)

6(152)

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit

Unit Weight*A D E Blower Motor

CBY02 35 (889) 37 (940) 32 (813) 1 1 117CBY03 35 (889) 37 (940) 32 (813) 1 1 122CBY04 41 (1041) 43 (1092) 38 (965) 2 1 137CBY06 53 (1346) 55 (1397) 50 (1270) 2 1 152CBY08 53 (1346) 55 (1397) 50 (1270) 2 1 157CBY10 75 (1905) 77 (1956) 72 (1829) 4 2 229CBY12 75 (1905) 77 (1956) 72 (1829) 4 2 243

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 24: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com24

Horizontal SeriesPHYSICAL DATA, CONT’D.

CXB - Horizontal Cabinet

SUPPLYAIR

APPROX.REF.

1-1/2(38)

RETURNAIR

7/8" (22) O.D.

DRAIN CONNECTIONAIR VENT

RESILIENT MOUNTINGGROMMETS WITH 3/8" (10)DIA. HOLE (TYP. OF 4)

2(51)

2(51)

2(51)

SUPPLY AIR GRILLESTANDARD STAMPED

OPTIONAL "L" SHAPEDDRIP LIP, SHIPPEDLOOSE (NOTE 5)

CHILLED/HOT WATERSUPPLY & RETURN

CONNECTIONS

STAMPED RETURNAIR GRILLE &1" (25) FILTER

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

REMOVABLE HINGEDR.A./ACCESS

PANEL

7/8 (22) KNOCKOUT

(TYP. OF 2)1-1/2 (38) KNOCKOUT(TYP. OF 5)

PARTIAL REAR VIEW(TYPICAL BOTH SIDES)

2(51)

5-3/4(146)AIR

RETURN

1" (25) FILTERAIR GRILLE &STAMPED RETURNOPTIONAL

OPTIONAL

LOCATION

STANDARD

C B C

E

A

FG

3 1/2(89)

23-1/2(597)

CONDENSATE

JUNCTION BOX

18(457)

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)

(SEE SUPPLEMENTALDRAWING FOR COIL

STUBOUT LOCATIONS)

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit Unit

Weight*A B C E F G Blower MotorCXB02 38 (965) 17-1/8 (435) 10-7/16 (265) 34 (864) 5-3/4 (146) 11 (279) 1 1 98CXB03 42 (1067) 21-1/2 (546) 10-1/4 (260) 38 (965) 5-3/4 (146) 11 (279) 1 1 118CXB04 48 (1219) 25-7/8 (657) 11-1/16 (281) 44 (1118) 5-3/4 (146) 11 (279) 2 1 126CXB06 53 (1346) 34-5/8 (879) 9-3/16 (233) 49 (1245) 6-3/4 (171) 12 (305) 2 1 168CXB08 60 (1524) 39 (991) 10-1/2 (267) 56 (1422) 6-3/4 (171) 12 (305) 2 1 176CXB10 74 (1880) 52-1/8 (1324) 10-15/16 (262) 70 (1778) 6-3/4 (171) 12 (305) 4 2 215CXB12 82 (2083) 60-7/8 (1546) 10-9/16 (268) 78 (1981) 6-3/4 (171) 12 (305) 4 2 245

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 25: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

25

PHYSICAL DATA, Cont’d.

CXB - Horizontal Cabinet with optional Electric Heat

SUPPLYAIR

APPROX.REF.

1-1/2(38)

RETURNAIR

7/8 (22) O.D.

DRAIN CONNECTION

AIR VENT

RESILIENT MOUNTINGGROMMETS WITH 3/8 (10)DIA. HOLE (TYP. OF 4)

2(51)

2(51)

2(51)

SUPPLY AIR GRILLESTANDARD STAMPED

OPTIONAL "L" SHAPEDDRIP LIP, SHIPPEDLOOSE (NOTE 5)

CHILLED/HOT WATERSUPPLY & RETURN

CONNECTIONS

STAMPED RETURNAIR GRILLE &1"(25) FILTER

ELECTRIC STRIPHEATER ELEMENT

RIGHT SIDE VIEWFRONT VIEW

TOP VIEW

REMOVABLE HINGEDR.A./ACCESS

PANEL

7/8 (22)KNOCKOUT(TYP. OF 2)

1-1/2 (38) KNOCKOUT

(TYP. OF 5)

PARTIAL REAR VIEW(TYPICAL BOTH SIDES)

2(51)

CONTROL BOX

5-3/4(146)AIR

RETURN

OPTIONAL

OPTIONAL

LOCATION

STANDARD

C B C

E

A

FG

3-1/2(89)

23-1/2(597)

CONDENSATE

UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)

18(457)

1" (25) FILTERAIR GRILLE &STAMPED RETURNOPTIONAL

(SEE SUPPLEMENTALDRAWING FOR COIL

STUBOUT LOCATIONS)

Unit ModelDimensions - Inches (Millimeters) Quantity/Unit Unit

Weight*A B C E F G Blower MotorCXB02 38 (965) 17-1/8 (435) 10-7/16 (265) 34 (864) 5-3/4 (146) 11 (279) 1 1 100CXB03 42 (1067) 21-1/2 (546) 10-1/4 (260) 38 (965) 5-3/4 (146) 11 (279) 1 1 120CXB04 48 (1219) 25-7/8 (657) 11-1/16 (281) 44 (1118) 5-3/4 (146) 11 (279) 2 1 128CXB06 53 (1346) 34-5/8 (879) 9-3/16 (233) 49 (1245) 6-3/4 (171) 12 (305) 2 1 170CXB08 60 (1524) 39 (991) 10-1/2 (267) 56 (1422) 6-3/4 (171) 12 (305) 2 1 178CXB10 74 (1880) 52-1/8 (1324) 10-15/16 (262) 70 (1778) 6-3/4 (171) 12 (305) 4 2 217CXB12 82 (2083) 60-7/8 (1546) 10-9/16 (268) 78 (1981) 6-3/4 (171) 12 (305) 4 2 247

NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4" (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.

Drawing is not to scale and is provided for reference only. Dimensions may vary with options ordered. Consult IEC web site for

up to date drawings.

Page 26: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com26

Horizontal SeriesSTANDARD FEATURES & OPTIONS

Features And Options StandardFactory

Installed Option

Field Installed Option

Factory Special Quote

Air Flow ArrangementFront Supply/Rear Return (CHY) X – – –Front Supply/Rear or Bottom Return (CPY, CBY, CXB) X (Bottom) X (Rear) – –Coils2 Rows 2-Pipe (CHY, CPY, CBY, CXB) – X – –3 Rows 2-Pipe (CHY, CPY, CBY, CXB) X – – –4 Rows 2-Pipe (CHY, CPY, CBY, CXB) – X – –3/1, 3/2, 4/1 Rows 4-Pipe (CHY, CPY, CBY, CXB) – X – –Manual Air Vent X – – –Automatic Air Vent – X – –DX Coils – X – –Steam Coils – X – XConnectionRight or Left (Same End) X – – –Right or Left (Opposite End) – X – –Drain PanGalvanized Internally Coated with 2-part closed Cell Foam X – – –Stainless Steel Externally Coated – X – –Drip Lip (recommended with motorized valves) – – X –Extended Drain Pans (CHY, CPY) – X – –Secondary Drain Connection – X – vFin MaterialAluminum with Galvanized End Sheets X – – –Copper with Stainless End Sheets & Bottom Coil Baffle – X – XNichrome Wire Strip Electric Heater (Total and Auxiliary) – X – –Filters1" Throwaway non-woven synthetic filter X – – –1" Permanent – X – –1" Pleated MERV 8 – X – –Insulation1/2" Standard Fiberglass X – – –1/2" Premium IAQ Fiberglass – X – X1/2" Foil Face – X – –1/4" Closed Cell – X – –Motor TypePSC Motors with Quick Connect Plug X – – –Motor Voltage120/1/60 3-Speed X – – –208/230/277/1/60 3-Speed (Optional Voltage) – X – –Supply/Return Air GrillesLouvered Stamped Supply Grille (CXB) X – – –

Double Deflection, Aluminum Finish Supply Grille – X (CXB X (CHY, CPY, CBY)

X (CHY, CPY, CBY)

Double Deflection, Integral Supply Grille - painted – X (CXB) – –Stamped Return Grille (CBY, CXB) X – – –

Hinged Bar-Type, Aluminum-finish Return Grille with Throwaway Filter - F.O. – – X (CHY, CPY, CBY)

X (CHY, CPY, CBY)

ControlsService Switch with Lockout Tabs – X – –Single Point Power Connection – X – –Incoming Power Fusing – X – –24 V Controls – X – –Condensate Overflow Switch – X – –3-Speed Switch X – X –Thermostats – – X –Custom Control (DDC) – X – X

Page 27: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

27

STANDARD FEATURES & OPTIONS, Cont’d.

As detailed in the table on page 27, we offer a control

for most of the customer needs. Additional controls and

devices are available to meet even the most demanding

operating logic.

Three-speed Fan ControlAll of our basic control schemes utilize a 2- or 3-speed

switch to modulate the cooling output, to maximize the

percentage of latent heat removal, and to further minimize

the sound level when maximum cooling or heating

performance is not required.

Low Voltage Control (24 V)A low voltage control is available with all of our control

schemes.

Condensate High Level SwitchThis switch shuts down the unit when the water level in the

drain pan reaches an unsafe level. Building code changes in

much of the country now require this type of device.

Service SwitchesWe offer concealed service switches for use by maintenance

and service personnel to shut off the power while working

on the unit.

FusingWe offer incoming power fusing for all units as well as

blower motor and control sub-fusing for units that use

electric heat. The blower motor and control sub-fusing

(single power source wiring) is required when single source

power with electric heat is specified.

Control Packages

Vertical Wall Series 155

24 V Programmable and Non-Programmable

Digital Series

Page 28: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com28

Horizontal SeriesSTANDARD FEATURES & OPTIONS, Cont’d.

Control Package Applications

Unit Type Control Option System Type Changeover Type Vertical and Horizontal

Wall Series 155

24 V Programmable and Non-Programmable

Digital Series– Manual Fan Manual1 None – –

2-PipeValve Cycle*

Heat Only None

Cool Only None

Heat/CoolManual –

Automatic

Heat/Cool with Auxiliary Electric Heat

Manual –Automatic

Cool with Total Electric Heat

Manual –Automatic

4-Pipe Heat/CoolManual –

Automatic

NOTE: 1. Fan switch only; no thermostat.

Thermostat Features

All listed controls include fan switching.Control Type1

Vertical and Horizontal Wall Series 155 24 V Digital Series

24 V, 115 V, 208 V, 240 V, 277 V 24 V onlyRemote Wall Mounted

Manual Fan Switch Operation

Auto Fan Speed Control N/A

Continuous 3-Speed Fan

Cycling Fan N/A

O.A. Damper Signal

Remote Temperature Sensor Opt OptAdjustable Operating Range Kit

Touch Pad/Digital Display N/A

Local Temperature Set-Back N/A

Water Temperature Purge Cycle N/A

Pipe Sensor N/A

NOTES: 1. Control packages with valve cycle control are continuous fan operation only. 2. All wall-mount control packages are shipped loose for field installation. (Boxes, tile rings, plaster rings, etc. are not provided.) 3. Aquastats are included in control packages, as required.

Control Options• 24 V control packages• Unit-mounted fan switches (Special Quote)• Single power source wiring (motor/control fusing)• Incoming power fusing• Service switches

• Minimum room temperature thermostats (Special Quote)• Low voltage remote shutdown relays (Special Quote)• Fan and valve cycle applications (Special Quote)• Thermostats available with large letter print for handicap

applications (Special Quote)• DX coil applications

Page 29: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

29

STANDARD FEATURES & OPTIONS, Cont’d.

Supply Air Grilles

Unit Size Nominal CFMRecommended

Grille Size - Inches (Millimeters)

02 200 16" x 6" (406 x 152)

03 300 20" x 6" (508 x 152)

04 400 26" x 6" (660 x 152)

06 600 30" x 6" (762 x 152)

08 800 38" x 6" (965 x 152)

10 1000 52" x 6" (1320 x 152)

12 1200 60" x 6" (1524 x 152)

NOTES: 1. Refer to Physical Data, pages 13 through 26 for actual unit supply air opening dimensions.

2. Field-furnished duct transitions may be required.

Return Air Filter Grilles

Unit Size Nominal CFMRecommended

Grille Size - Inches (Millimeters)

02 200 24" x 10" (610 x 254)

03 300 28" x 10" (711 x 254)

04 400 32" x 10" (813 x 254)

06 600 42" x 10" (1067 x 254)

08 800 42" x 10" (1067 x 254)

10 1000 54" x 10" (1372 x 254)

12 1200 64" x 10" (1626 x 254)

NOTES: 1. Refer to Physical Data, pages 13 through 26 for actual unit return air opening dimensions.

2. Field-furnished duct transitions may be required.

Optional Double-deflection, Integral Supply Grille Painted to Match Color of Unit

Optional Double Deflection, Aluminum-finish Supply Grille (Optional special ship separate for models CHY, CPY, and CBY.

Consult factory for details.)Optional Hinged, Bar-type, Aluminum-finish Return Grille

with Throwaway Filter (Optional special ship separate for models CHY, CPY, and CBY.

Consult factory for details.)

Page 30: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com30

Horizontal SeriesSTANDARD FEATURES & OPTIONS, Cont’d.

Nominal Filter SizesAll cabinet model units (except CH) have non-woven synthetic throwaway filters furnished as standard equipment. Cleanable

and pleated filters are optional.

Unit Size

Nominal One-Inch Filter Size - Inches (Millimeters)

CHY (Note 1) CPY

CBY Bottom Return

Stamped

CBY Rear Return

Stamped

CXB Bottom Return

Stamped

CXB Rear Return

Stamped

CXB Rear Return

Ducted

02 10" x 24"(254 x 610)

10" x 18" (254 x 457)

10" x 28"(254 x 711)

7" x 21"(178 x 533)

10" x 23-1/2"(254 x 597)

8" x 23-1/2"(203 x 597)

8" x 23-1/2"(203 x 597)

03 10" x 28"(254 x 711)

10" x 22" (254 x 559)

10" x 28"(254 x 711)

7" x 21"(178 x 533)

10" x 28"(254 x 711)

8" x 28"(203 x 711)

8" x 28"(203 x 711)

04 10" x 32"(254 x 813)

10" x 28" (254 x 711)

10" x 33"(254 x 838)

7" x 27"(178 x 533)

10" x 32-1/2"(254 x 826)

8" x 32-1/2"(203 x 826)

8" x 32-1/2" (203 x 826)

06 10" x 42"(254 x 1067)

10" x 33" (254 x 838)

10" x 45"(254 x 1143)

7" x 38"(178 x 965)

10" x 37"(254 x 940)

8" x 37"(203 x 940)

8" x 37"(203 x 940)

08 10" x 42"(254 x 1067)

10" x 40" (254 x 1016)

10" x 45"(254 x 1626)

7" x 38"(178 x 965)

10" x 41"(254 x 1041)

8" x 41"(203 x 1041)

8" x 41"(203 x 1041)

10 10" x 54"(254 x 1372)

10" x 54" (254 x 1372)

10" x 62"(254 x 1575)

7" x 52"(178 x 1321)

10" x 54-1/2"(254 x 1384)

8" x 54-1/2"(203 x 1384)

8" x 54-1/2"(203 x 1384)

12 10" x 64" (254 x 1626)

10" x 62" (254 x 1575)

10" x 62"(254 x 1575)

7" x 52"(178 x 1321)

10" x 63"(254 x 1600)

8" x 63" (203 x 1600)

8" x 63"(203 x 1600)

NOTES: 1. Filter sizes for the CH models are recommended filter sizes only. No filter is factory provided with these models. 2. Sizes shown are nominal ordering sizes.

Page 31: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

International Environmental Corporation • Horizontal Series Fan Coil Technical Catalogwww.iec-okc.com

Horizontal Series

31

PIPING PACKAGES (TYPICAL)

Two-way Motorized Control ValveIn a two-way motorized control valve package, the motor

drives the valve open, and a spring returns the valve to a

normally closed position. No water flows with the unit off.

The standard supply connection from the coil will accept

a swaged copper fitting for field brazing. As an option, this

connection may be factory furnished with a union. When a

swage is necessary, it becomes part of the valve package.

The isolation, or ball, valve in the return piping is shipped

loose for field installation.

(Ships Separate)

2-way ValveCoil

Air Vent

SwageS

R

S

R BallValve

BallValve

Two-way Motorized Control Valve with ChangeoverIn a two-way motorized changeover control valve package,

the motor drives the valve open, and a spring returns the

valve to a normally closed position. No water flows through

the coil with the unit off. The aquastat bypass line allows

a small amount of water to flow from the supply to the

return piping when the control valve is closed. The strap-

on aquastat senses whether the flowing water is cold or

hot and switches a contact closed to provide automatic

summer/winter changeover (ACO) for the system.

S

R

S

Swage

2-way ValveAquastat BleedBypass Line

A

Aquastat

R

Coil

Air Vent

Swage

BallValve

BallValve

Three-way Motorized Control ValveIn a three-way motorized control valve package, a diverting

valve controls water flow to the coil. When the unit is off,

water bypasses the coil and flows directly to the system

return. A balancing valve may be specified in the bypass line

to permit equal flow balancing.

OptionalBalance Valve

S

Swage

3-way Valve

R

Coil

Air Vent

SwageA

Aquastat

S

R BallValve

BallValve

NOTES: 1. Please note that project specifications for system pressure, pressure drop limitations and flow rate should be checked prior to selecting specific components or the valve package size.

2. The supply and return piping connections of the factory-provided valve package are either swaged for field brazing (standard) or union fitted (optional) for connection to the coil.

3. Consult IEC’s Valve Packages and Piping Components manual or your local representative for detailed piping and valve application information. Factory-provided valve packages are assembled, brazed, wired electrically and dry-fit to the coil connections before shipping. Field brazing to the coil completes the installation. Some applications dictate shipping isolation valves loose.

Page 32: Horizontal Series - IEC Environmental · PDF fileInternational Environmental Corporation • Horizontal Series Fan Coil Technical Catalog Horizontal Series 3 PORTFOLIO CBY - Horizontal

P.O. Box 2598Oklahoma City, OK 73101-2598

p: 405.605.5000f: 405.605.5001

www.iec-okc.com

IEC Catalog Part #: I100-90002102

CA-020 Revision 8 (8/2016)

©2000-2016 International Environmental Corporation (IEC)