Finley Home Services 8417 Washington Blvd #180 Roseville CA 95678 916-741-2847 [email protected] www.finleyhomeservices.com Inspection reference: 031419JH5 Page 1 © Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited. Home Inspection Report 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville CA 95678 This report is the exclusive property of the inspection company and the client whose name appears herewith and its use by any unauthorized persons is prohibited.

Transcript of Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St...

Page 1: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Finley Home Services 8417 Washington Blvd #180

Roseville CA 95678 916-741-2847

[email protected] www.finleyhomeservices.com

Inspection reference: 031419JH5

Page 1

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Home Inspection Report5678 Goodlife St

Roseville CA 95678

March 14, 2019

Prepared for:

James Sample5678 Goodlife St

Roseville CA 95678

This report is the exclusive property of the inspection company and the client whose name appears herewith and

its use by any unauthorized persons is prohibited.

Page 2: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 2

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Inspection Contents

Summary 3

GENERAL INFORMATION 7

GROUNDS 9

EXTERIOR - FOUNDATION 11

ROOF SYSTEM 14

CRAWLSPACE - BASEMENT 18

ELECTRICAL SYSTEM 21

HEATING - AIR CONDITIONING 24

PLUMBING SYSTEM 28

KITCHEN - APPLIANCES 32

BATHROOMS 33

INTERIOR ROOMS 35

LAUNDRY AREA 37

GARAGE - CARPORT 38

POOL/SPA & EQUIPMENT 40

Page 3: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 3

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Monday, April 08, 2019

Mr. James Sample5678 Goodlife St Roseville CA 95678

5678 Goodlife St Roseville CA 95678

Dear Mr. James Sample:

At your request, a visual inspection of the above referenced property was conducted on Thursday, March 14, 2019. Anearnest effort was made on your behalf to discover all visible defects, however, in the event of an oversight, maximumliability must be limited to the fee paid. The following is an opinion report, reflecting the visual conditions of the property atthe time of the inspection only. Hidden or concealed defects cannot be included in this report. No warranty is eitherexpressed or implied. This report is not an insurance policy, nor a warranty service.

SUMMARY OF AREAS REQUIRING FURTHER EVALUATION

IMPORTANT: The Summary is not the entire report. The complete report may include additional information of concern tothe client as well as maintenance recommendations. It is advised that the client read the complete report. The entireInspection Report, including the Standards of Practice, limitations and scope of Inspection, and Pre-Inspection Agreementmust be carefully read to fully assess the findings of the inspection. This list is not intended to determine which items mayneed to be addressed per the contractual requirements of the sale of the property. Any areas of uncertainty regarding thecontract should be clarified by consulting an attorney or real estate agent.

It is strongly recommended that you have appropriate licensed contractors evaluate each concern further and the entiresystem for additional concerns that may be outside our area of expertise or the scope of our inspection BEFORE the closeof escrow. Please call our office for any clarifications or further questions.

The following is a list of major defects (RR) that need further evaluation or repair by reputable and appropriately LicensedContractors. Major items are also noted in the complete inspection report.

EXTERIOR - FOUNDATIONExterior Walls:3.1 Materials & Condition: Walls constructed with wood / vinyl siding and stucco along with some stone facades. General condition appearsserviceable. Stucco cracks are typical. As a normal maintenance precaution, we recommend caulking/sealing allcracks 1/16" or larger to avoid the possibility of water intrusion. Wood siding has signs of normal aging and wear.Regular maintenance suggested. Some of the stone facades at the front of the house have come loose.Recommend repairs as needed. Some deterioration / rot observed to siding on various sides of the house.Recommend repairs to damaged areas as needed by a qualified siding contractor. Also refer to pestinspection report for repair recommendations.

Page 4: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 4

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

ROOF SYSTEMRoof:4.3 Roof Covering: Type: Composition shingles. General condition appears serviceable with normal signs of aging. The average lifeexpectancy in the local area for a composite shingle roof is 25-30 years. Regular maintenance recommended:This usually consists of repair/replacement of damaged/missing shingles. This maintenance should help insurethe weather tightness of the building and should be performed on a regular basis. Note: Fibers starting to showat the edge of the shingles is a sign of aging shingles and should be monitored and repaired as needed. Mildew / moss growth observed. Moderate mildew growth can be lightened by the gentle application ofbleach or a more eco friendly option with a brush or broom then rinsed off. It is common for roofs to havesome mildew growth, especially on the north-facing portions of the roof due to less direct sunlight. Ridgeand hip cap shingles show signs of advanced wear. This is a normal indication of age or exposure to theelements. A few nail heads have risen through shingles, with small holes now exposed in the roofingmaterial. Recommend sealing as needed to prevent potential leakage. All exposed nails will requireperiodic resealing. You may wish to have a roofing contractor make further evaluation and repairs asneeded.

Eaves - Soffits - Fascias:4.17 Roof: General condition of the overhangs appear serviceable. As part of regular maintenance, we recommendoverhangs be kept painted to avoid the possibility of premature deterioration. Deterioration noted to some ofthe overhangs / eaves and rafter tails . Recommend repair as needed by a qualified contractor. Also referto pest inspection report for repair recommendation.

Page 5: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 5

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

ELECTRICAL SYSTEMWiring:6.16 Crawlspace: Some cables in the crawlspace are contacting the ground. Recommend properly securing these cablesabove the ground.

PLUMBING SYSTEMWater Heater:8.16 Condition: Pressure relief valve noted, not tested. Flue vent intact. A water shutoff valve is installed but was not tested. Waterheater appears to be seismically secured. An expansion tank appears to be properly installed. General conditionappears serviceable. Recommend draining the water heater at least once per year or as recommended permanufacturer's specifications. This maintenance will help to remove sediment and extend the life of the waterheater. Consider installing an overflow pan under the water heater to help route any leaks to the exterior. Pressure relief valve drain line ends in the garage. Recommend extending drain line to terminate at anexterior location within 6" of the surface.

GARAGE - CARPORTGarage Interior:13.4 Garage Fire Wall: The wall covering appears to meet the minimum fire separation safety standards. However, it is not possible toconfirm after the drywall is finished. General condition appears serviceable. There is a pull down attic ladder

Page 6: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 6

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

installed in the ceiling. The ladder face cover is made of combustible material(s) and a fire rated materialshould be installed. Correction recommended with approved fire rated materials such as 24 gauge sheetmetal or thicker, or 5/8 Type X drywall covering any flammable material to restore its fire rating. There are openings in the wall in the garage attic and the firewall is diminished. Repair any openings with anapproved fire rated material to bring it into compliance with current safety regulations. All drywallpatches separating the garage from living space require taping and sealing according to current firesafety recommendations.

POOL/SPA & EQUIPMENTPool Decking:14.9 Pool Area Enclosure Fencing: General condition appears serviceable. Gate(s) opened outward. Self-closing mechanism(s) installed andoperated properly. See Fence section of this report for more details regarding maintenancerecommendations. Latch on gate missing and needs repair. Since this allows for access to the pool areathis presents a potential liability and is considered a safety concern. Recommend repairing the latch andverifying it operates properly prior to the close of escrow.

Minor items (MM) are also noted in the complete inspection report and should receive eventual attention, but do not affectthe immediate habitability of the house. The majority of these items are the result of aging and normal wear and tear.

Thank you for selecting Finley Home Services to perform your home inspection. If you have any questions regarding theinspection report or the home, please feel free to call us.

Sincerely,

Jeremy Hearn

Finley Home ServicesTermite, Pest Control & Home Inspections(916) 741-BUGS(2847)

Page 7: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 7

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

GENERAL INFORMATIONClient & Site Information:

1.1 Inspection Date:3/14/2019.

1.2 Inspection Time:12:00 PM.

1.3 Client:James Sample916-555-5785

1.4 Inspection Site:5678 Goodlife St Roseville, CA 95678.

1.5 People Present:Buyer, Buyer's spouse,Buyer's child/children andBuyer's agent.

Building Characteristics:

1.6 Main Entry Faces:West.

1.7 Estimated Age:Approximately 47 years.

1.8 Building Style & Type:Single Family Dwelling.Contemporary.

1.9 Stories:1

1.10 Space Below Grade:Part slab on grade / partcrawlspace.

1.11 Water Source:Public.

1.12 Sewage Disposal:Public.

1.13 Utilities Status:All utilities on.

Climatic Conditions:

1.14 Weather:Clear.

1.15 Outside Temperature(F):50-60.

1.16 Soil Conditions:Damp. Precipitation in theprevious 24 hours.

About Rated Items:1.17 Items not found in this report are beyond the scope of this visual inspection and should

not be considered as inspected at this time. Please read the entire report for importantdetails and recommendations. Inspected items are generally rated as follows:

OK = "Serviceable" = Item is functional and we did not observe conditions that wouldlead us to believe problems exist within this system or its components. Some serviceableitems may show general wear and tear due to age and usage. Other conditions andobservations may be noted in the body of the report.

MM = "Marginal/Maintenance" = Item is in need attention or monitoring, or has alimited useful life expectancy remaining, which may require replacement in thenear future. Further evaluation or servicing may be needed by a qualified licensedcontractor, technician or specialty tradesman dealing with that item or system.Depending on the defect/deficiency noted, an experienced handyman may bequalified to make the repair at a lower price point.

RR = "Repair or Replace" = Item, component, or unit specified is not functioningas designed and needs immediate repair or replacement. These are usually healthand safety items, or high cost repairs that should prompt attention and servicesooner than later. Further evaluation is highly recommended by a qualifiedlicensed contractor, technician, or specialty tradesman who specializes in the areaindicated.

REPORT LIMITATIONS

This report is intended only as a general guide to help the client make their own evaluation of the overall condition of thehome, and is not intended to reflect the value of the premises, nor make any representation as to the advisability of

Page 8: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 8

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

purchase. The report expresses the personal opinions of the inspector, based upon his visual impressions of theconditions that existed at the time of the inspection only. The inspection and report are not intended to be technicallyexhaustive, or to imply that every component was inspected, or that every possible defect was discovered. Nodisassembly of equipment, opening of walls, moving of furniture, appliances or stored items, or excavation wasperformed. All components and conditions which by the nature of their location are concealed, camouflaged or difficult toinspect are excluded from the report. The inspection is performed in compliance with generally accepted standard ofpractice, a copy of which is at the end of this report. Generally, all locations noted in the report are noted as if standing atthe front entrance of the home (i.e. Left side of the home, back of the home etc)

Systems and conditions which are not within the scope of the inspection include, but are not limited to: formaldehyde, leadpaint, asbestos, toxic or flammable materials, and other environmental hazards; pest infestation, playground equipment,efficiency measurement of insulation or heating and cooling equipment, shutoff valves anywhere on the property, internalor underground drainage or plumbing, any systems which are shut down or otherwise secured; water wells (water qualityand quantity) zoning ordinances; intercoms; security systems; heat sensors; cosmetics or building code conformity. Anygeneral comments about these systems and conditions are informational only and do not represent an inspection.

The inspection report should not be construed as a compliance inspection of any governmental or non governmentalcodes or regulations. The report is not intended to be a warranty or guarantee of the present or future adequacy orperformance of the structure, its systems, or their component parts. This report does not constitute any express orimplied warranty of merchantability or fitness for use regarding the condition of the property and it should not be reliedupon as such. Any opinions expressed regarding adequacy, capacity, or expected life of components are generalestimates based on information about similar components and occasional wide variations are to be expected betweensuch estimates and actual experience.

We certify that our inspectors have no interest, present or contemplated, in this property or its improvement and noinvolvement with tradespeople or benefits derived from any sales or improvements. To the best of our knowledge andbelief, all statements and information in this report are true and correct.

Should any disagreement or dispute arise as a result of this inspection or report, it shall be decided by arbitration andshall be submitted for binding, non-appealable arbitration to the American Arbitration Association. Construction DisputeResolution Services, LLC. or Resolute Systems Inc., in accordance with their Construction Industry Arbitration Rules thenobtaining, unless the parties mutually agree otherwise. In the event of a claim, the Client will allow the Finely HomeServices to inspect the claim prior to any repairs or waive the right to make the claim. Client agrees not to disturb orrepair or have repaired anything which may constitute evidence relating to the complaint, except in the case of anemergency.

Page 9: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 9

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

GROUNDSThis inspection is not intended to address or include any geological conditions or site stability information. Finley HomeServices does not perform any engineering analysis. We do not comment on coatings or cosmetic deficiencies and thewear and tear associated with the passage of time, which would be apparent to the average person. However, cracks inhard surfaces can imply the presence of expansive soils that can result in continuous movement, but this can only beconfirmed by a geological evaluation of the soil by a licensed engineering firm. Any reference to grade is limited to onlyareas around the exterior of the exposed areas of foundation or exterior walls. We cannot determine drainageperformance of the site or the condition of any underground piping, including subterranean drainage systems andmunicipal water and sewer service piping or septic systems. Decks and porches are often built close to the ground,where no viewing or access is possible. Any areas too low to enter or not accessible are excluded from the inspection. We do not evaluate any detached structures such as storage sheds and stables, nor mechanical or remotely controlledcomponents such as driveway gates. We do not evaluate or move landscape components such as trees, shrubs,fountains, ponds, statuary, pottery, fire pits, patio fans, heat lamps, and decorative or low-voltage lighting. Any suchmention of these items is informational only and not to be construed as inspected.

Paving Conditions:OK MM RR

2.1 Driveway: þ ¨ ¨ The driveway was paved with concrete. The driveway appeared to be inserviceable condition at the time of the inspection. Normal crackspresent.

2.2 Walks: þ ¨ ¨ Home walkways were constructed of poured / finished concrete, pavers,shredded bark, decomposed granite, and soil. Home walkwaysgenerally appeared to be in serviceable condition at the time of theinspection. Normal cracks present.

Front Patio / Porch:2.3 Slab / Surface: þ ¨ ¨ Patio type: Concrete and Pavers. General condition appears

serviceable. Normal settling cracks observed.

2.4 Structure: þ ¨ ¨ Pergola structure. Material Type: Wood. Detached / Self standing. General condition appears serviceable. The installed visible posts aresolid wood with a metal bracket and concrete base.

2.5 Cover / Roof: þ ¨ ¨ Pergola. Material Type: Wood slats. General condition appearsserviceable.

Back Patio / Porch:2.6 Slab / Surface: ¨ þ ¨ Patio type: Concrete. General condition appears serviceable. Normal

settling cracks observed. Portions of wood spacers missing /sunken. Recommend replace as needed. There is some piping thatprotrudes from the surface of the patio and presents a potentialtripping hazard. You may wish to have a qualified contractor makefurther evaluation and repairs as needed.

Page 10: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 10

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Fences & Gates:OK MM RR

2.7 Condition: þ ¨ ¨ Type: Wood and stucco. General condition of fencing and gate(s)appear serviceable. Normal maintenance recommended: Thisincludes making repairs and adjustments to gates, repair orreplacement of loose/rusted posts and repair or repainting of rustedcomponents on a regular basis.

Grading:2.8 Site: þ ¨ ¨ Flat site. Grade at foundation appears properly sloped away. Monitor

for proper site drainage during the rainy season.

Landscaping:2.9 Condition: þ ¨ ¨ General condition of the landscaping appeared serviceable. As a

preventative maintenance measure we recommend keeping at least a 1foot clearance between the house and any vegetation and a 5-6 footclearance between the house and any trees to prevent contact with thehouse, lower the likelihood of pest infestation, allow moisture toevaporate or drain appropriately and allow room for routinemaintenance.

2.10 Irrigation System ¨ þ ¨ General condition of the irrigation system appears serviceable. Theauto-controller was not tested. Sprinklers operated manually using thebleed valves at each location. Every zone is tested for proper operationof valves and heads during the inspection. Minor leaks, damaged headsand sufficiency of coverage may not be noted in this report. Buriedground irrigation pipe leaks will be reported, but only if noticeable at thetime of the inspection. Typical Maintenance Recommended: Thisincludes making repairs/adjustments to sprinklers and drips lines asneeded on a regular basis. Irrigation shutoff valve is located on thefront of the house.

Outdoor Cooking Area:2.11 Grill / Cooktop: ¨ ¨ ¨ None noted. Gas supply provided for future grill. Service is capped.

NOTE: Low voltage lighting systems, underground drains, fountains and ponds are beyond the scope of this inspection forFinley Home Services and are not included or noted as part of this inspection.

Page 11: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 11

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

EXTERIOR - FOUNDATIONAll structures are dependent on the soil beneath them for support, but soils are not uniform. Some that appear to be firmand solid can become unstable during seismic activity or may expand with the influx of water, moving structures withrelative easy and fracturing slabs and other hard surfaces. In accordance with our standards of practice, we here atFinley Home Services identify foundation types and look for any evidence of structural deficiencies. However, minorcracks or deteriorated surfaces are common in many foundations and most do not represent a structural problem. Ifmajor cracks are present along with bowing, we routinely recommend further evaluation be made by a qualified structuralengineer. All exterior grades should allow for surface and roof water to flow away from the foundation. All concrete floorslabs experience some degree of cracking due to shrinkage in the curing process. In most instances floor coveringsprevent recognition of cracks or settlement in all but the most severe cases. Where carpeting and other floor coveringsare installed, the materials and condition of the flooring underneath cannot be determined. Areas hidden from view byfinished walls or stored items cannot be judged and are not a part of this inspection. We will certainly alert you to anysuspicious cracks if they are clearly visible. However, we are not specialists, and in the absence of any major defects, wemay not recommend that you consult with a foundation contractor, a structural engineer, or a geologist, but this should notdeter you from seeking the opinion of any such expert. We also routinely recommend that inquiry be made with the sellerabout knowledge of any prior foundation or structural repairs.

Exterior Walls:OK MM RR

3.1 Materials & Condition: ¨ ¨ þ Walls constructed with wood / vinyl siding and stucco along with somestone facades. General condition appears serviceable. Stucco cracksare typical. As a normal maintenance precaution, we recommendcaulking/sealing all cracks 1/16" or larger to avoid the possibility ofwater intrusion. Wood siding has signs of normal aging and wear.Regular maintenance suggested. Some of the stone facades at thefront of the house have come loose. Recommend repairs asneeded. Some deterioration / rot observed to siding on varioussides of the house. Recommend repairs to damaged areas asneeded by a qualified siding contractor. Also refer to pestinspection report for repair recommendations.

¨ ¨ þ

¨ ¨ þ

3.2 Flashing & Trim: þ ¨ ¨ The condition of flashing and trim appears to be in generally good

Page 12: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 12

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

condition. As part of regular maintenance, we recommendcaulking/sealing small openings and any voids around windows, doorsand penetrations on stucco walls and caulking/sealing any voids atsiding joints, trim, and around windows, doors and penetrations to avoidpotential water intrusion. All wood materials should be kept painted toavoid the possibility of premature moisture related deterioration.

Exterior Doors:OK MM RR

3.3 Main Entry Door: þ ¨ ¨ Appears serviceable. Hardware operational. Aluminum screen door(s)present. The screen is torn and needs repair or replacement.

3.4 Rear Door: þ ¨ ¨ Door(s) in the family room. Appears serviceable. Hardware operational.Loosely hung screen with magnets is present.

3.5 Side Door: þ ¨ ¨ Door(s) in the office. Appears serviceable. Hardware operational.Aluminum screen door(s) present.

3.6 Other Door: þ ¨ ¨ Door(s) in the master bedroom. Sliding door. Appears serviceable. Hardware operational.

Exterior Windows:3.7 Predominant Type: Vinyl Clad Aluminum. Double paned.

3.8 Overall Condition: þ ¨ ¨ Satisfactory overall, considering age.

Foundation:3.9 Materials & Condition: þ ¨ ¨ Partial Slab / Partial Raised foundation appears satisfactory: The

exposed exterior portions of the perimeter foundation walls appear to beadequate. Also see crawlspace/basement section of the report. Slab isnot visible from inside the house due to floor covering. Typical cracks

Page 13: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 13

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

noted. Slab is not visible from inside the house due to the floorcovering(s) throughout. Normal minor cracking observed. Crack notedin foundation wall at the front of the house. Crack appears to beold due to the smooth nature of the crack sides. No structuraldisplacement noted. Recommend sealing with an epoxy seal toprevent water intrusion and monitor.

Page 14: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 14

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

ROOF SYSTEMAlthough not required, we here at Finley Home Services generally attempt to evaluate various roof types by walking ontheir surfaces. If we are unable or unwilling to do this for any reason, we will indicate the method used to evaluate them.We normally are unable to access roofs that are over 10 feet high from the ground to the eaves, or on the second storylevel or higher. Every roof will wear differently relative to its age, number of layers, quality of material, method ofapplication, exposure to weather conditions, and the regularity of its maintenance. We can only offer an opinion of thegeneral quality and condition of the roofing material.

The inspector cannot and does not offer an opinion or warranty as to whether the roof leaks or may be subject to futureleakage. The waterproof membrane beneath roofing materials is generally concealed and cannot be examined withoutremoving the roof material. Although roof condition can be evaluated, it is virtually impossible for anyone to detect a leakexcept as it is occurring or by specific water tests, which are beyond the scope of our service. Even water stains onceilings or on framing within attics will not necessarily confirm an active leak without some corroborative evidence, andsuch evidence can be deliberately concealed. We evaluate every roof conscientiously, and even attempt to approximateits age, but we will not predict its remaining life expectancy, or guarantee that it will not leak. Naturally, the sellers or theoccupants of a residence will generally have the most intimate knowledge of the roof and of its history. Therefore, werecommend that you ask the sellers about it, and that you either include comprehensive roof coverage in your homeinsurance policy, or that you obtain a roof certification from an established local roofing company. We do not inspectattached accessories including but not limited to solar systems, antennae, and lightning arrestors.

Roof:4.1 Style: Hip: Roofing surfaces that slopes upward from all sides of a structure, having no vertical

ends. The hip is the external angle at which adjacent sloping sides of a roof meet.

4.2 Roof Access: Walked on roof.

OK MM RR4.3 Roof Covering: ¨ ¨ þ Type: Composition shingles. General condition appears serviceable with

normal signs of aging. The average life expectancy in the local area fora composite shingle roof is 25-30 years. Regular maintenancerecommended: This usually consists of repair/replacement ofdamaged/missing shingles. This maintenance should help insure theweather tightness of the building and should be performed on a regularbasis. Note: Fibers starting to show at the edge of the shingles is asign of aging shingles and should be monitored and repaired asneeded. Mildew / moss growth observed. Moderate mildewgrowth can be lightened by the gentle application of bleach or amore eco friendly option with a brush or broom then rinsed off. It iscommon for roofs to have some mildew growth, especially on thenorth-facing portions of the roof due to less direct sunlight. Ridgeand hip cap shingles show signs of advanced wear. This is anormal indication of age or exposure to the elements. A few nailheads have risen through shingles, with small holes now exposedin the roofing material. Recommend sealing as needed to preventpotential leakage. All exposed nails will require periodic resealing. You may wish to have a roofing contractor make further evaluationand repairs as needed.

¨ ¨ þ

Page 15: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 15

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR4.4 Flashings: þ ¨ ¨ Type: Metal. General condition appears serviceable. As part of regular

maintenance, we recommend sealing all roof penetrations on anongoing basis to avoid the potential of water intrusion. Periodic removalof debris will extend the useful life of the roof flashing.

4.5 Valleys: ¨ ¨ ¨ The roof valleys are closed and covered by the roofing material. Flashing under closed valley not visible and not inspected. As part ofregular maintenance, we recommend keeping valleys clean of debris.

4.6 Gutters & Downspouts: ¨ þ ¨ Gutters and downspout materials are metal. Building is fully guttered. General condition of the gutters and downspouts appear serviceable.Neither the slope of the gutter or drainage flow was observable atthe time of inspection. Periodic cleaning and maintenance isrecommended. Rusting observed at some of the seams indicatingsigns of aging. Recommend monitoring in the future and budgetingfor eventual replacement as needed. Damage / denting noted tosome of the gutters along the main runs on various sides of thehouse. Leaks noted to some of the gutters at corners and seams atthe back of house needs sealing and repair.

¨ þ ¨

In accordance with our home inspection certification standards, we here at Finley Home Services do not attempt to enterattics that have less than thirty-six inches of headroom, are restricted by ducts, or in which the insulation obscures thejoists and thereby makes mobility hazardous, in which case we would inspect them as best we can from the access point.In regard to evaluating the type and amount of insulation on the attic floor, we use only generic terms and approximate

measurements, and do not sample or test the material for specific identification. Also, we do not disturb or move anyportion of insulation, and it may obscure water pipes, electrical conduits, junction boxes, exhaust fans, and othercomponents.

Attic:4.7 Access: ¨ þ ¨ Viewing limited. Access restricted by tight fitting hatch. Cracked

drywall noted on access hatch. The hatch was slightly too large forthe opening rendering the attic inaccessible. Recommend repair orreplace with an appropriate sized hatch as needed to gain accessand re-inspecting prior to close of escrow.

Page 16: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 16

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR4.8 Structure: ¨ þ ¨ There is a rafter system installed in the attic enclosure to support the

roof decking. The majority of the rafter system was not observabledue to inaccessible at the time. Re-inspection is recommendedprior to the close of escrow.

4.9 Insulation: þ ¨ ¨ Insulation type: Blown in fiberglass.

4.10 Depth & R-Value: þ ¨ ¨ There appears to be sufficient insulation installed. Approximately: 8-10inches. R-26+/-.

4.11 Ventilation Provisions: þ ¨ ¨ There appears to be sufficient ventilation.

Chimney:4.12 Chimney Exterior: þ ¨ ¨ Chimney is constructed of There is an ash pit access door on the

exterior side of the chimney indicating there is an ash pit below thefireplace. An ash pit is used for easier clean up of the fireplace.. Generalcondition appears serviceable.

4.13 Flue: ¨ ¨ ¨ The inspector was unable to determine the condition of the flue liner dueto limited visibility. Periodic inspection and cleaning recommended by aqualified chimney sweep.

4.14 Flashing: þ ¨ ¨ Satisfactory. The installed flashing around the chimney stack appearsto be installed properly and functional.

4.15 Chimney Cap: þ ¨ ¨ There is a chimney cap. The chimney cap is made of mortar. Its functionis to keep water from entering the stack and causing deterioration. Themetal rain hat appears to be properly installed. It will help keep rainfrom entering the flue. The metal spark arrestor appears to be properlyinstalled. In addition to preventing fires, it will also keep unwantedanimals and birds out of the flue.

Page 17: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 17

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR4.16 Height & Clearance: þ ¨ ¨ The chimney installation appears to meet clearance requirements.

Eaves - Soffits - Fascias:4.17 Roof: ¨ ¨ þ General condition of the overhangs appear serviceable. As part of

regular maintenance, we recommend overhangs be kept painted toavoid the possibility of premature deterioration. Deterioration noted tosome of the overhangs / eaves and rafter tails . Recommend repairas needed by a qualified contractor. Also refer to pest inspectionreport for repair recommendation.

¨ ¨ þ

Page 18: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 18

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

CRAWLSPACE - BASEMENTWhile the inspector makes every effort to find all areas of concern, here at Finley Home Services, some areas can gounnoticed. During the course of the inspection, the inspector does not enter any area or perform any procedure that maydamage the property or its components or be dangerous to or adversely affect the health of the inspector or otherpersons.

Crawlspace:OK MM RR

5.1 Access: ¨ þ ¨ This inspection does not cover the presence or lack of wood destroyinginsects or rodents. Crawlspace is fully accessible. Inspected byentering and crawling through. Unable to inspect some areas due toductwork, low head clearance and limited access. Gaps notedaround the access hatch / door. This provides a potential point ofentry for pests / animals. Recommend repair as needed.

5.2 Walls: ¨ þ ¨ Wall materials are poured concrete. Exposed portions of the interiorfoundation perimeter walls appear to be satisfactory. Crack noted infoundation wall. Crack appears to be old due to the smooth natureof the crack sides. No structural displacement noted. Recommendsealing with an epoxy seal to prevent water intrusion and monitor.An excellent way to verify that no further settlement is occurring isby installing a crack monitor. These devices are inexpensive andconsist of a couple pieces of plastic with cross-hairs that can bealigned before being affixed with quick hardening epoxy.

5.3 Moisture: ¨ þ ¨ There were no elevated moisture levels noted on most of the exposedareas of the walls. Presence of efflorescence noted to a few areasof the foundation walls. Efflorescence is a white mineral depositleft behind when moisture passes through a surface. Efflorescence seen on walls indicates the presence of periodicmoisture. High moisture content in the exterior walls can lead tomildew and even wood rot in high concentrations. Water seepagemay recur in the future. The best defense against water seepage isgood drainage of soils near the foundation wall.

Page 19: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 19

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR5.4 Beams/Underfloor: þ ¨ ¨ The sub-structure of the home appeared to be in generally serviceable

condition at the time of the inspection. The visible subfloor appears tobe in serviceable condition. Underfloor support beams are wood.Insulation is not installed to the underside of the floor. You maywish to consider having a contractor install insulation under thefloor for energy efficiency purposes inside the house.

5.5 Posts / Piers / Columns: ¨ þ ¨ Satisfactory. The piers as installed appear to be sufficient. Noengineering analysis is inferred or implied. Installed posts / piers: Solidwood with a concrete base. They appeared to be properly installed withevidence of some normal staining at various locations. At least two ofthe wood pads located on the top of the concrete piers are crackedand damaged. Recommend monitoring in the future and makingrepairs as needed.

5.6 Foundation Bolts: þ ¨ ¨ Foundation bolts were present and correctly used to secure the framingto the foundation.

5.7 Floor: ¨ þ ¨ Type: Soil. Appears serviceable. There is a full vapor barrier installedcovering the floor. Evidence of rodent / pest activity noted. You maywish to have treatment carried out by Finley Home Services oranother licensed exterminator.

5.8 Crawlspace Ventilation: þ ¨ ¨ The cross-ventilation in the crawlspace appears to be adequate.

Insulation & Vapor Retarders:5.9 In Unfinished Areas: þ ¨ ¨ There is a full vapor barrier installed covering the floor. Insulation is

not installed to the underside of the floor. You may wish toconsider having a contractor install insulation under the floor for

Page 20: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 20

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

efficiency purposes inside the house.

Page 21: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 21

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

ELECTRICAL SYSTEMWe are not electricians and in accordance with the standards of practice we only test a representative number of switchesand outlets and do not perform load-calculations to determine if the supply meets the demand. However, every electricaldeficiency or recommended upgrade should be regarded as a latent hazard that should be serviced as soon as possible,along with evaluation and certification of the entire system as safe by a licensed contractor. Therefore, it is essential thatany recommendations that we may make for service or upgrades should be completed before the close of escrow,because an electrician could reveal additional deficiencies or recommend additional upgrades for which we disclaim anyresponsibility. Any electrical repairs or upgrades should be made by a licensed electrician. Aluminum wiring requiresperiodic inspection and maintenance by a licensed electrician. Smoke Alarms should be installed within 15 feet of allbedroom doors, and tested regularly.

Operation of time clock motors is not verified. Inoperative light fixtures often lack bulbs or have dead bulbs installed. Theinspector is not required to insert any tool, probe, or testing device inside the panels, test or operate any over-currentdevice except for ground fault interrupters, nor dismantle any electrical device or control other than to remove the coversof the main and auxiliary distribution panels. Any ancillary wiring or system that is not part of the primary electricaldistribution system is not part of this inspection but may be mentioned for informational purposes only, including but notlimited to low voltage systems, security system devices, heat detectors, carbon monoxide detectors, telephone, security,cable TV, intercoms, and built in vacuum equipment.

Service:OK MM RR

6.1 Type & Condition: þ ¨ ¨ 110/220 Volt. Circuit breakers. Appears serviceable. Underground.

6.2 Grounding Equipment: þ ¨ ¨ Appears to be grounded via rod in ground. General condition appearsserviceable.

Electrical Distribution Panels:6.3 Main Panel Location: The main electrical service panel is on the back of the house exterior.

6.4 Main Circuit Rating: 100 amps.

6.5 Service Disconnect Switch: þ ¨ ¨ Located inside the main panel on the right side. General conditionappears serviceable. Main service disconnect was not tested during theinspection.

6.6 Main Panel Observations: ¨ þ ¨ This electrical panel appeared to be in serviceable condition at the timeof the inspection. Panel is labeled, but the some of the print is fading/ illegible. Recommend verifying breakers and properly labelingpanel. Circuit and wire sizing correct so far as visible. Groundingsystem is present. This electrical service panel contained circuitbreakers manufactured by Zinsco / GTE / Sylvania. Zinsco breakersare known to have a high rate of trip failure when exposed tooverheating. Failure to trip during overheating is a potential firehazard. Information about Zinsco circuit breaker problems iswidely available on the internet. Recommend monitor in the futureand upgrade as needed.

Page 22: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 22

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR6.7 Pool Electrical Equipment: þ ¨ ¨ This electrical panel appeared to be in serviceable condition at the time

of the inspection. Panel was properly labeled. GFCI breakers presentand tested properly.

Conductors:6.8 Entrance Cables: þ ¨ ¨ Copper. Appears serviceable as far as visible.

6.9 Branch Wiring: þ ¨ ¨ Copper. Aluminum for 220 volt; this is a normal and acceptableconfiguration. Appears serviceable as far as visible.

Electrical Outlets:6.10 Exterior Walls: þ ¨ ¨ Exterior electrical outlets were Ground Fault Circuit Interrupter

(GFCI)-protected, enclosed in weather-resistant covers, responded totesting and appeared to be in serviceable condition at the time of theinspection.

6.11 Interior: þ ¨ ¨ Outlets were tested throughout the house. Generally, the outlets andswitches are in serviceable condition. Ground Fault Circuit Interrupter(GFCI) protected electrical outlets in the kitchen, bathroom(s) andgarage appeared to be operational at the time of the inspection. Themain GFCI reset controls are in the kitchen, the bathrooms and theexterior. Each GFCI outlet operates independently and has beenupdated from the original outlets. If loss of power is experienced in anarea with a GFCI, try resetting the outlet as the first step introubleshooting.

6.12 Laundry: ¨ ¨ ¨ 220V service blocked by stored items, cabinetry and/or laundryequipment.

Switches and Fixtures:6.13 Interior: þ ¨ ¨ General condition of the fixtures and switches throughout the house are

in serviceable condition. A few of the lights did not respond when testedwith the switches, likely due to bad bulbs. Replace burned out bulbs andtest fixtures for proper operation prior to the close of escrow.

6.14 Exterior Fixtures: þ ¨ ¨ General condition of the exterior fixtures throughout the house are inserviceable condition. Lights are not operational in some areas, possiblydue to bad bulbs. Replace burned out bulbs and test fixtures for properoperation.

Page 23: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 23

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Ceiling Fans:OK MM RR

6.15 Interior: þ ¨ ¨ Ceiling fans operated in family room, office, and all bedrooms. Theyappear to be serviceable and balanced throughout. There is a remotecontrol for the ceiling fan(s). Be sure to verify its presence at the closingwalk-through inspection. The fan responded to controls from theremote.

Wiring:6.16 Crawlspace: ¨ ¨ þ Some cables in the crawlspace are contacting the ground.

Recommend properly securing these cables above the ground.

Page 24: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 24

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

HEATING - AIR CONDITIONINGThe inspector with Finley Home Services can only readily open access panels provided by the manufacturer or installerfor routine homeowner maintenance, and will not operate components when weather conditions or other circumstancesapply that may cause equipment damage. The inspector does not light pilot lights or ignite or extinguish solid fuel fires,nor are safety devices tested by the inspector. The inspector is not equipped to inspect furnace heat exchangers forevidence of cracks or holes, or inspect concealed portions of evaporator and condensing coils, heat exchanger or firebox,electronic air filters, humidifiers and de-humidifiers, ducts and in-line duct motors or dampers, as this can only be done bydismantling the unit. This is beyond the scope of this inspection. Thermostats are not checked for calibration or timedfunctions. Adequacy, efficiency or the even distribution of air throughout a building cannot be addressed by a visualinspection. Have these systems evaluated by a qualified individual. The inspector does not perform pressure tests oncoolant systems, therefore no representation is made regarding coolant charge or line integrity. We perform aconscientious evaluation of the system, but we are not specialists.

Please note that even modern heating systems can produce carbon monoxide, which in a poorly ventilated room canresult in sickness and even death. Therefore, it is essential that any recommendations we make for service or furtherevaluation be scheduled prior to the close of escrow, because a specialist could reveal additional defects or recommendfurther upgrades that could affect your evaluation of the property, and our service does not include any form or warrantyor guarantee. Normal service and maintenance is recommended on a yearly basis. Determining the presence ofasbestos materials commonly used in heating systems can ONLY be preformed by laboratory testing and is beyond thescope of this Finley Home Services inspection. Determining the condition of oil tanks, whether exposed or buried, isbeyond the scope of this inspection. Leaking oil tanks represent an environmental hazard which is sometimes costly toremedy.

Heating Equipment:7.1 Type & Location: Forced Air. Location: Exterior of the house.

7.2 Brand: Bryant.

OK MM RR7.3 Capacity / Approx. Age: þ ¨ ¨ 80K-100K BTU. Installed furnace is about 3 years old according to the

data plate information. Based on the local average, normal service lifefor a forced air natural gas furnace is 18 - 25 years. The nationalaverage is 15 - 18 years.

7.4 Fuel Source: þ ¨ ¨ Natural Gas. Electrical disconnect present.

7.5 General Operation & Cabinet: þ ¨ ¨ General condition appears serviceable. Unit operated properly duringlimited use at the time of inspection. Suggest periodicallycleaning/servicing blower motor, pilot light, vent system and burners.Sufficient temperature rise observed. Annual tune-up recommendedby a licensed HVAC contractor. Sealed access panels limited theinspection of the furnace.

7.6 Return Air Temp: 70 F.

Page 25: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 25

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

7.7 Supply Air Temp: 122 F.

OK MM RR7.8 Burners / Heat Exchangers: ¨ ¨ ¨ Closed System; unable to inspect.

7.9 Pump / Blower Fan: þ ¨ ¨ Blower fan operated properly at the time of the inspection.

7.10 Combustion Air: þ ¨ ¨ Sufficient.

7.11 Flues, Vents, Plenum: þ ¨ ¨ General condition appears serviceable as far as visible. During a visualinspection it is impractical to determine the condition of most if not all ofthe interior of the flue. The interior of the flue may be damaged ordeteriorated, but was not visible.

7.12 Air Filters: ¨ þ ¨ Intake located in the hallway. The filter size is 20"x30"x1". The filter isin need of cleaning or replacement. Recommend replacing orcleaning filters every 45 to 90 days as needed.

7.13 Normal Controls: þ ¨ ¨ Thermostat located in the hallway. Appropriate response noted usingnormal controls. Electronic thermostat controls are installed for centralheating and air conditioning. Programmable / automatic controls werenot tested or overridden. The HVAC system thermostat is part of atechnologically advanced system that allows for control using anapp on your cell phone. Be sure to inquire and get the details fromthe seller.

Air Conditioning:7.14 Primary Type: Central System - Package Unit. Condenser fan is enclosed at the same location with the

furnace and evaporator unit. Location of the condenser fan: Exterior of the house on theleft side.

7.15 Brand: Bryant.

Page 26: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 26

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR7.16 Approx. Age / Capacity: þ ¨ ¨ Current air conditioner is approximately 3 years old according to the

data plate information. The typical service life for an air conditioningunit in the local area is 15 - 18 years. 12-15 based on the nationalaverage. Cooling Capacity: 3.0 Tons.

7.17 Return Air Temp: 64 F.

7.18 Supply Air Temp: 44 F.

7.19 Air Temp Drop: þ ¨ ¨ 20 F Good cooling. The unit produced an adequate temperature dropduring limited test run.

7.20 Power Source: þ ¨ ¨ 220 Volt. Electrical disconnect present. The condenser fan maximumamp / fuse capacity: 40 Amps. The installed breaker / fuses is properlysized.

7.21 System Condition: þ ¨ ¨ General condition appears serviceable. Annual tune-uprecommended by a licensed HVAC contractor.

7.22 Condensate Line: þ ¨ ¨ Condensate line installed. Appears serviceable as far as visible. Condensate line(s) discharge to the exterior.

7.23 Normal Controls: þ ¨ ¨ Electronic thermostat controls functioned properly during the inspection.See Heating Equipment thermostat controls for detailed information.

Ductwork / Distribution:7.24 Ducts / Air Supply: ¨ þ ¨ Type: Flexible round and insulated sheet metal. Visibility of the ductwork

is limited. Generally, the condition appears serviceable as far as visible.Air supply appears to be sufficient. Note: The inspector does not moveor interrupt ductwork. In general, air volume varies from room to room. Old ductwork is disconnected and is no longer in use under thehouse. Recommend removal of old ducting by a qualified HVAC

Page 27: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 27

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

technician.

Auxiliary Equipment:OK MM RR

7.25 Whole House Attic Fan: þ ¨ ¨ The whole house fan operated properly during the inspection. Makesure to open windows or doors before operating the whole house fan. While the structure was not visible from the attic (access blocked), fromthe view below it appears the framing is intact below the whole housefan. The whole house fan switch is located near/in the hallway. There isa switch that controls the fan speed.. Fan has a timed switch toautomatically shutoff after a preset operating time. The timed switchmust be set before the house fan will operate.

7.26 Fireplaces / Solid FuelHeating:

þ ¨ ¨ Fireplace located in the family room. Gas/Wood - The fireplace isdesigned to use gas fuel and/or burn wood. General condition appearsserviceable. Damper is operational. Fire was not lit at the time ofinspection. Gas service is capped and will require some additionalcomponents and service to convert the fireplace using the gasoption. Recommend installing a fireplace enclosure. A fireplaceenclosure will prevent sparks from entering the living space. The glassdoors will increase the efficiency of the house by keeping the heatinside the house while the fireplace is not in use.

þ ¨ ¨

Page 28: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 28

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

PLUMBING SYSTEMWater quality or hazardous materials (lead) testing is available from local testing labs, however it is not included in thisFinley Home Services inspection. All underground piping related to water supply, waste, or sprinkler use are excludedfrom this inspection. Leakage or corrosion in underground piping cannot be detected by a visual inspection, nor can thepresence of mineral build-up that may gradually restrict their inner diameter and reduce water volume. Plumbingcomponents such as gas pipes, potable water pipes, drain and vent pipes, and shut-off valves are not generally tested ifnot in daily use. The inspector cannot state the effectiveness or operation of any anti-siphon devices, automatic safetycontrols, water conditioning equipment, fire and lawn sprinkler systems, on-site water quality and quantity, on-site wastedisposal systems, foundation irrigation systems, spa and swimming pool equipment, solar water heating equipment, orobserve the system for proper sizing, design, or use of materials.

The water pressure within pipes is commonly confused with water volume, but whereas high water volume is good highwater pressure is not. Therefore a regulator is recommended whenever street pressure exceeds 80 psi. However,regardless of pressure, leaks will occur in any system, and particularly in one with older galvanized pipes, or one in whichthe regulator fails and high pressure begins to stress washers and diaphragms within various components.

Waste and drainpipes pipe condition is usually directly related to their age. Older ones are subject to damage throughdecay and root movement, whereas the more modern ABS ones are virtually impervious to damage, although some rarebatches have been alleged to be defective. Older homes with galvanized or cast iron supply or waste lines can beobstructed and barely working during an inspection but later fail under heavy use. If the water is turned off or not used forperiods of time (such as a vacant house waiting for closing), rust or deposits within the piping can further clog the pipingsystem. However, inasmuch as significant portions of drainpipes are concealed, we can only infer their condition byobserving the draw at drains at the time of inspection. Nonetheless, blockages will still occur in the life of any system.

Main Water Line:OK MM RR

8.1 Water Shut Off: þ ¨ ¨ Water meter is located at the front of the property. Main shutoff valve islocated on the front of the building. Valve was not tested foroperation.

8.2 Water Line Material: þ ¨ ¨ Copper.

8.3 Water Pressure: þ ¨ ¨ Water pressure checked at an exterior hose bib. There is a waterpressure regulator valve that appears to be correctly installed. Thisallows adjustment of the incoming water pressure. Pressure regulatorwas not adjusted at the time of inspection. The static water pressuremeasured 95 pounds per square inch (psi) at the hosebib locatedin front of the pressure regulator. The static water pressure measured60 pounds per square inch (psi) at a hosebib down line from thepressure regulator. Water pressure from 40 to 80 psi is consideredwithin an acceptable range. Water pressure from 40 to 80 psi isconsidered within an acceptable range.

Page 29: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 29

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Supply Lines:OK MM RR

8.4 Material: þ ¨ ¨ Combination of materials: Copper. Sharkbite PEX.

8.5 Condition: þ ¨ ¨ Lines are not fully visible. Visible lines appear to be in serviceablecondition. No leakage noted, but monitoring in the future isrecommended. Shut-off valves are provided at water lines servingfixtures. Shut-off valves are not tested for operation during theinspection. Be forewarned that most shut-off valves are not operatedregularly and as such they are prone to leak when operated. Theyshould only be used to shut off the water in the event of a leak thatcould damage surrounding materials.

Waste Lines:8.6 Material: Combination of materials: Cast iron and ABS.

8.7 Condition: þ ¨ ¨ Lines not fully visible. Visible lines, traps and vents appear to be inserviceable condition. No problems noted at the time of the inspection,but monitoring in the future is recommended. We highly recommend acamera inspection of the main sewer lateral plumbing line onhomes older than 40 years.

8.8 Sewer Clean Outs: ¨ ¨ ¨ Secondary / point of use waste clean out(s) are on various sides of thehouse. We highly recommend a camera inspection of the mainsewer lateral on homes older than 40 years. A main sewerclean-out was not located. Recommend inquire with seller as tothe location of the main clean-out.

Hose Bibs / Hookups:8.9 Exterior Walls: þ ¨ ¨ Exterior hose bibs appeared to be in serviceable condition at the time of

the inspection. Anti-backflow valves are recommended to preventbackflow into the water supply line.

8.10 Laundry: þ ¨ ¨ There is a connection installed with both hot and cold water and drainpiping. The drain pipe was not flood tested and the supply valvepositions were not adjusted during the inspection. Plumbing appearsserviceable.

The temperature pressure relief valve at the upper portion of the water heater is a required safety feature which should beconnected to a drain line of proper size terminating just above floor elevation. If no drain is located in the floor a catchpan should be installed with a drain extending to a safe location. The steam caused by a blow-off can cause scalding. It

Page 30: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 30

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

should be noted that not all piping materials are rated for this level of heat, which is why Finley Home Services makesspecific recommendations regarding piping . Improper installations should be corrected prior to the close of escrow.

Water Heater:

8.11 Location:Garage.

8.12 Brand:Bradford White.

8.13 Capacity:50 Gallons.

8.14 Power Source:Natural Gas.

OK MM RR8.15 Age of Tank: þ ¨ ¨ Approximately 12 years. The average service life for a natural gas

water heater in the local area is about 15-18 years. The nationalaverage is 12-15 years.

8.16 Condition: ¨ ¨ þ Pressure relief valve noted, not tested. Flue vent intact. A water shutoffvalve is installed but was not tested. Water heater appears to beseismically secured. An expansion tank appears to be properly installed.General condition appears serviceable. Recommend draining the waterheater at least once per year or as recommended per manufacturer'sspecifications. This maintenance will help to remove sediment andextend the life of the water heater. Consider installing an overflowpan under the water heater to help route any leaks to the exterior. Pressure relief valve drain line ends in the garage. Recommendextending drain line to terminate at an exterior location within 6" ofthe surface.

¨ ¨ þ

8.17 Recorded Water Temp: 120 F.

Page 31: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 31

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Fuel System:OK MM RR

8.18 Fuel Meter / Tank: þ ¨ ¨ Public. Meter and main shutoff valve are on the left side of the house. Natural Gas. System appears serviceable. Lines are not fully visible.

Sinks:8.19 Kitchen Interior: þ ¨ ¨ The sink, fixtures and drainage appeared to be in generally serviceable

condition. Both cold and hot water sides were observed for functionalityand flow. Shutoff valves under the sink(s) are not tested for operationduring the home inspection. Diverter to the spray handle anddetachable faucet head appears to be serviceable. Stored itemsprevent access and full viewing under the sink.

8.20 Master Bath: ¨ þ ¨ The sink, fixtures and drainage appeared to be in generally serviceablecondition. Both cold and hot water sides were observed for functionalityand flow. Shutoff valves under the sink(s) are not tested for operationduring the home inspection. Stored items prevent access and fullviewing under the sink. The sink is loose. Recommend securing tothe countertop as needed to prevent damage from movement.

8.21 Hall Bath: ¨ þ ¨ The sink, fixtures and drainage appeared to be in generally serviceablecondition. Both cold and hot water sides were observed for functionalityand flow. Shutoff valves under the sink(s) are not tested for operationduring the home inspection. Drain stopper missing at the sink andneeds replacement. Faucet handle is loose. Recommendtightening as needed.

See the Bathrooms and/or Crawlspace section of this report for additional information about plumbing and fixtures inthese areas.

Page 32: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 32

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

KITCHEN - APPLIANCESFinley Home Services may test kitchen appliances for basic functionality, but cannot evaluate them for their performancenor for the variety of their settings or cycles. Appliances older than ten years may exhibit decreased efficiency. Theseitems are not inspected: free-standing appliances, refrigerators, freezers, ice makers, trash-compactors, built-in toasters,coffee-makers, can-openers, blenders, instant hot-water dispensers, water-purifiers, barbecues, grills, or rotisseries,timers, clocks, thermostats, the self-cleaning and cooking capability of ovens, and concealed or countertop lighting, whichis convenient but often installed after the initial construction and not wired to national electrical standards. Even if generalcomments are made, these items should be considered outside the scope of the inspection with Finley Home Services.Appliances are not moved during the inspection. Portable dishwashers are not inspected or operated, as they requireconnection to facilitate testing.

Kitchen Interior:OK MM RR

9.1 Dishwasher: þ ¨ ¨ The dishwasher operated through a full cycle and appeared to be inserviceable condition at the time of the inspection. The dishwasher drainline had an air gap device installed at the time of the inspection. Anoperable air gap prevents drain water from contaminating thedishwasher in the event of a clog or siphoning. The air gap appeared tobe operating properly at the time of the inspection.

9.2 Oven: þ ¨ ¨ Gas. Appears serviceable. Appropriate temperature rise observedusing regular controls at time of inspection. Light operated normally.

9.3 Cooktop: þ ¨ ¨ Gas. Cooktop combined with oven. General condition appearsserviceable. Operated all burners/elements at time of inspection.

9.4 Microwave: þ ¨ ¨ The microwave operated properly at the time of the inspection.

9.5 Ventilation: þ ¨ ¨ Vent fan was operational at the time of the inspection. ExternallyVented. Light was operable.

9.6 Refrigerator: ¨ ¨ ¨ Not inspected. Water line is present for an ice maker/water dispenserconnection to a refrigerator. Valve was not tested for operation. Generalcondition appears serviceable. Refrigerator opening size is 70.5 x 35.5inches. Be sure to install a refrigerator this size or smaller for it to fitproperly.

9.7 Garbage Disposal: þ ¨ ¨ The garbage disposal operated properly at the time of the inspection. Wiring appears serviceable.

9.8 Cabinets & Counters: þ ¨ ¨ The cabinets and counters appeared to be in generally serviceablecondition.

Page 33: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 33

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

BATHROOMSIn accordance with industry standards of practice, we here at Finley Home Services do not comment on commoncosmetic deficiencies, and do not evaluate window treatments, steam showers, and saunas. More importantly, we doleak-test shower pans at our discretion, which is usually the responsibility of a termite inspector. However, because of thepossibility of water damage, most termite inspectors will not leak-test second floor shower pans without the writtenconsent of the owners or occupants.

Our inspection of interior areas includes the visually accessible areas of walls, floors, cabinets and closets, and arepresentative number of windows and doors, switches and outlets. We do not evaluate window treatments, nor movefurniture, lift carpets or rugs, empty closets or cabinets, and we do not comment on common cosmetic deficiencies.

Cabinets & Counters:OK MM RR

10.1 Master Bath: þ ¨ ¨ The cabinets and counters appeared to be in generally serviceablecondition.

10.2 Hall Bath: þ ¨ ¨ The cabinets and counters appeared to be in generally serviceablecondition.

Tub/Shower Fixtures:10.3 Master Bath: þ ¨ ¨ The fixtures appeared to be in generally serviceable condition at the

time of the inspection.

10.4 Hall Bath: ¨ þ ¨ The fixtures appeared to be in generally serviceable condition at thetime of the inspection. Dripping observed at the showerhead hoseconnections. Recommend repair and/or replace as needed.

Tub/Shower And Walls:10.5 Master Bath: þ ¨ ¨ Tub/shower walls appear serviceable. Enclosure appears serviceable.

Caulk and seal all tub and shower areas as part of regular maintenance.

10.6 Hall Bath: ¨ þ ¨ Tub/shower walls appear serviceable. The current configuration is setup for a shower curtain only. There is no shower enclosure. Caulk andseal all tub and shower areas as a precaution. Voids noted to thegrout on the right side of the tub. Recommend repair as needed.

Page 34: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 34

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Toilet:OK MM RR

10.7 Master Bath: ¨ þ ¨ General condition appears serviceable. Shutoff valves are not tested foroperation during the home inspection. The toilet was loose at the floorand needs securing or to be reset with a new wax ring. No leakagenoted. Note: As toilets age, it is normal to see corrosion / rust atthe tank and at the floor bolts/nuts/washers. This should bemonitored periodically in the future and repaired as needed.

10.8 Hall Bath: ¨ þ ¨ General condition appears serviceable. Shutoff valves are not tested foroperation during the home inspection. The toilet was loose at the floorand needs securing or to be reset with a new wax ring. No leakagenoted. Note: As toilets age, it is normal to see corrosion / rust atthe tank and at the floor bolts/nuts/washers. This should bemonitored periodically in the future and repaired as needed.

Ventilation:10.9 Master Bath: þ ¨ ¨ Sufficient. There is an exhaust fan installed. The fan operated properly

at the time of the inspection. Recommend allowing the fan to run for about half an hour after a bath or shower to assist in removing humid airfrom the bathroom. Note: The inspector was unable to verify that thevent fan was properly ducted to the exterior due to low headclearance / inaccessibility in that portion of the attic.

10.10 Hall Bath: þ ¨ ¨ Sufficient. There is an exhaust fan installed. The fan operated properlyat the time of the inspection. Recommend allowing the fan to run for about half an hour after a bath or shower to assist in removing humid airfrom the bathroom. Note: The inspector was unable to verify that thevent fan was properly ducted to the exterior due to low headclearance / inaccessibility in that portion of the attic.

10.11 Laundry: þ ¨ ¨ Sufficient. Screened vents on the walls provide adequate air flow forventilation.

Page 35: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 35

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

INTERIOR ROOMSFinley Home Services inspection of living space includes the visually accessible areas of walls, floors, cabinets andclosets, and the testing of a representative number of windows and doors, switches and outlets. We do not evaluatewindow treatments or coverings, move furnishings or possessions, lift carpets or rugs, empty closets or cabinets, norcomment on cosmetic deficiencies. We may not comment on cracks that appear around windows and doors, along linesof framing members or along seams of drywall and plasterboard. These are typically caused by minor movement, suchas wood shrinkage, common settling, and seismic activity, and will often reappear if they are not correctly repaired. Suchcracks can become the subject of disputes, and are therefore best evaluated by a specialist. Floor covering damage orstains may be hidden by furniture, and the condition of floors underlying floor coverings is not inspected. Determining thecondition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. Checkwith owners for further information. All fireplaces should be cleaned and inspected on a regular basis to make sure thatno cracks have developed. Large fires in the firebox can overheat the firebox and flue liners, sometimes resulting ininternal damage. Testing, identifying, or identifying the source of environmental pollutants or odors (including but notlimited to lead, mold, allergens, odors from household pets and cigarette smoke) is beyond the scope of our service, butcan become equally contentious or difficult to eradicate. We recommend you carefully determine and schedule whateverremedial services may be deemed advisable or necessary before the close of escrow.

Smoke alarm and Carbon Monoxide detectors note: Current standards recommend that smoke alarms be installed in allcommon hallways on each floor level and in all bedrooms/home office rooms. Carbon Monoxide detectors arerecommended in common areas such as hallways on each floor level.

Interior:OK MM RR

11.1 Doors: þ ¨ ¨ The doors and hardware throughout the home appeared to be inserviceable condition at the time of the inspection.

11.2 Windows: þ ¨ ¨ Vinyl coated, Dual-Pane. The windows appeared to be in serviceablecondition throughout the home at the time of the inspection. Windowsare inspected for proper operation, condition of sill, sash, hardware andthe condition of weather-resistant components. Note: Condensation /discoloration can be difficult to visually observe in some instances andmay not be visible at the time of inspection. With Dual Paned windows,each location described as a single location, despite two panes of glass.Single hung. No leaks observed. Hardwater staining / scale noted

to the exterior side of some of the windows, likely due to oversprayof sprinklers or deferred maintenance over time. Make repairs asneeded.

11.3 Ceilings: ¨ þ ¨ Ceilings are made of drywall. The ceilings throughout the house appearto be serviceable at the time of the inspection. Note: The houseinterior has been newly painted making it difficult to detectevidence of leaks or staining. There is some minor cracking noted.Be sure to take note of any future movement. Most cracking is dueto shrinkage of the construction materials and minor settling. Thisis generally considered a cosmetic deficiency. Recommend repairas needed.

11.4 Walls: þ ¨ ¨ Walls are made of drywall. Walls appeared to be in generallyserviceable condition throughout the home at the time of the inspection.

Page 36: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 36

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Stored items or furnishings prevent full inspection. Note: The houseinterior has been newly painted making it difficult to detectevidence of leaks or staining.

OK MM RR11.5 Closets: þ ¨ ¨ General condition of the closets throughout the house are in serviceable

condition. Due to stored items in the closet, it is not possible todetermine the condition of the walls and the ceiling that are not visible.

11.6 Floors: þ ¨ ¨ The home floor surfaces appeared to be in generally serviceablecondition at the time of the inspection. Stored items or furnishingsprevented full inspection.

11.7 Smoke / Fire and CarbonMonoxide Detectors:

þ ¨ ¨ Smoke detectors and carbon monoxide alarms responded properly totest button operation. Sufficient smoke detectors and carbon monoxidealarms observed at the time of the inspection.

Page 37: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 37

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

LAUNDRY AREALaundry appliances are not tested or moved during the inspection and the condition of any walls or flooring hidden by theinstalled appliances cannot be judged by Finley Home Services. Drain lines and water supply valves serving washingmachines are not operated. Water supply valves may be subject to leaking if turned. See Plumbing and Electrical pagesfor more details about those types of system components.

Laundry:12.1 Location: Service area main floor. Garage.

OK MM RR12.2 Fuel System: ¨ ¨ ¨ There is a 220-volt outlet provided for an electric dryer. A gas valve

may or may not be present, but was not visible during theinspection due to installed appliances.

12.3 Dryer Vent: ¨ ¨ ¨ Dryer vent was connected to the dryer or blocked by installedappliances. Interior of dryer vent not visible and not inspected. Afterdisconnecting the dryer from the vent, recommend checking for debris /clogging of dryer vent and cleaning regularly as needed.

12.4 Clothes Washer: ¨ ¨ ¨ Washer was not operated at the time of inspection. Often, the inspectoris unaware of whether or not the appliance is included with the purchaseof the house.

12.5 Clothes Dryer: ¨ ¨ ¨ Dryer was not operated at the time of inspection. Often, the inspector isunaware of whether or not the appliance is included with the purchaseof the house.

Page 38: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 38

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

GARAGE - CARPORTDetermining the heat resistance rating of firewalls is beyond the scope of this inspection. Flammable materials should notbe stored within closed garage areas. Garage door openings are not standard, so you may wish to measure the openingto ensure that there is sufficient clearance to accommodate your vehicles. It is not uncommon for moisture to penetrategarages, particularly with slabs on-grade construction, and this may be apparent in the form of efflorescence or saltcrystal formations on the concrete. You may want to have any living space above the garage evaluated further by astructural engineer, as it may be seismically vulnerable.

Garage Interior:13.1 Type Two car. Attached.

OK MM RR13.2 Garage Ceilings Condition: þ ¨ ¨ Ceilings are made of drywall. The ceilings in the garage appear to be

serviceable at the time of the inspection.

13.3 Garage Walls Type &Condition:

þ ¨ ¨ Walls are made of drywall. The garage walls appeared to beserviceable at the time of the inspection. Pet door opening noted to thegarage wall.

13.4 Garage Fire Wall: ¨ ¨ þ The wall covering appears to meet the minimum fire separation safetystandards. However, it is not possible to confirm after the drywall isfinished. General condition appears serviceable. There is a pull downattic ladder installed in the ceiling. The ladder face cover is madeof combustible material(s) and a fire rated material should beinstalled. Correction recommended with approved fire ratedmaterials such as 24 gauge sheet metal or thicker, or 5/8 Type Xdrywall covering any flammable material to restore its fire rating. There are openings in the wall in the garage attic and the firewallis diminished. Repair any openings with an approved fire ratedmaterial to bring it into compliance with current safety regulations. All drywall patches separating the garage from living space requiretaping and sealing according to current fire safetyrecommendations.

¨ ¨ þ

13.5 Garage Floors: þ ¨ ¨ The floor is concrete. The garage floor appeared to be in generallyserviceable condition at the time of the inspection. Minor crackingnoted. No expansion joints noted. The expansion joints provideroom for shrinkage and expansion. The lack of expansion joints in

Page 39: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 39

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

a large concrete slab can cause cracks that typically do not affectthe structural integrity. Recommend monitoring cracks for furtherdeterioration. Some uneven areas observed.

OK MM RR13.6 Service Doors: þ ¨ ¨ The door had operable, self-closing hinges installed, which appeared to

be in serviceable condition at the time of the inspection. There is a solidcore door separating the garage from the living areas of the house.

13.7 Cabinets & Counters: þ ¨ ¨ The cabinets and counters appeared to be in generally serviceablecondition.

Garage Overhead Door:13.8 Material - Condition: þ ¨ ¨ Metal. The overhead vehicle door(s) appeared to be in serviceable

condition at the time of the inspection.

13.9 Door Operator: þ ¨ ¨ The automatic garage door opener(s) responded to the controls at thetime of the inspection. The photo-reverse and tension reverse featuresappeared to operate properly at the time of the inspection.

Page 40: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 40

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

POOL/SPA & EQUIPMENTInspection was limited to those areas which are above ground or water level. The only way to detect an underground leakin a supply line, buried pipe fitting, or pool surface crack is by observation of the persistent and continuous loss of waterfrom the pool over an extended period of time. Purchasers are encouraged to ask sellers about the existence of any pastor present leaks in the pool, spa or associated equipment. Pool filtering devices are not disassembled to determine thecondition of any installed filter elements. Operation of time clock motors and thermostatic temperature controls cannot beverified during a visual inspection. Testing of backflush mechanisms is beyond the scope of this inspection. Pilot lightson LP gas pool heaters are not lit during the inspection.

General Comments:14.1 Recommend all pool owners learn how to operate and maintain their pools safely.

Water chemistry is very important. There are pool companies which can service the poolon a regular basis and maintain this swimming pool. Recommend a competent poolcontractor be consulted before draining the pool. High ground water levels may causethe pool to lift if drained improperly. The following are recommended maintenancetimelines for a pool: check the water level once a day, check the pH twice a week, checkhardness, TDS, and total alkalinity once a month, test for metals once every six months,check the skimmer basket twice a week, check the pump strainer pot once a week, lookfor leaks every day, vacuum the pool once or twice a week, brush the pool walls andbottom once a week, clean the waterline once a week, clean the solar panels once amonth, empty and clean the filter every three months.

Pool Surface:14.2 Type: Concrete/Marcite.

OK MM RR14.3 Condition: þ ¨ ¨ General condition appears serviceable. Auto-fill valve installed. These

systems work in a similar manner to a toilet float switch. The manual fillvalve must be open for the auto-fill valve to operate. General conditionappears serviceable. Anti-entrapment type drains are noted, not tested.Pool vacuum installed. General condition appeared serviceable.Vacuum responded to normal controls.

þ ¨ ¨

14.4 Pool Coping: þ ¨ ¨ General condition appears serviceable. Tile.

14.5 Skimmer and Basket: þ ¨ ¨ General condition appears serviceable. The skimmer basket(s) needto be cleaned. Skimmers will require routine cleaning in the future.

Page 41: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 41

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Pool Decking:OK MM RR

14.6 Type & Condition: þ ¨ ¨ Type: Stamped concrete. General condition appears serviceable. Typical cracks noted. Water supply lines and electrical conduit havebeen installed for future use.

14.7 Hand Railings: þ ¨ ¨ General condition appears serviceable.

14.8 Child Protection Fencing: ¨ þ ¨ General condition appears serviceable. Gate does not latch properlyand needs minor adjustment for it to function appropriately.

14.9 Pool Area Enclosure Fencing: ¨ ¨ þ General condition appears serviceable. Gate(s) opened outward. Self-closing mechanism(s) installed and operated properly. See Fencesection of this report for more details regarding maintenancerecommendations. Latch on gate missing and needs repair. Sincethis allows for access to the pool area this presents a potentialliability and is considered a safety concern. Recommend repairingthe latch and verifying it operates properly prior to the close ofescrow.

Page 42: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 42

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

OK MM RR14.10 Door Alarms: ¨ þ ¨ Door alarms were not located. Recommend installation of door

alarms to any doors that allow access to the backyard as needed.

14.11 Slide(s): þ ¨ ¨ General condition appears serviceable. Slide appeared to beadequately secured. Water sprayers operated normally. Note:Improper use of slides has been identified as a cause for asignificant amount of injuries in pools. Recommend use withcaution, ensure water depth is sufficient for the height and speedof the slide, always actively observe children in the vicinity of theslide and consider removal for safety purposes.

Pool Electrical Equipment:14.12 Timers: þ ¨ ¨ General condition appears serviceable. Analog Timer.

14.13 Pool Light: þ ¨ ¨ Operable. GFCI protection present and tested properly.

Page 43: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 43

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Pumping Equipment:OK MM RR

14.14 Pump & Motor: þ ¨ ¨ Brand(s): Jandy. Horsepower rating(s): 2 HP motor(s). Variable speedpumps installed. Running the pumps at the lower power setting fornormal operation can have a significant impact on the electrical cost ofoperating a pool. Flow meter installed not tested. Inquire with the selleras to an operation instructions and manuals for more information.

þ ¨ ¨

14.15 Evidence of Water Leakage: þ ¨ ¨ None noted.

14.16 Visible Plumbing Lines: þ ¨ ¨ General condition appears serviceable. Note: Consider applyinglabels showing pipe use to eliminate confusion in operation of thisequipment.

14.17 Hair/Lint Filter: þ ¨ ¨ Cartridge. General condition appears serviceable. No significant airbubbles noted. Recommend cleaning filter at regular intervals permanufacturer's specifications.

14.18 Pressure: þ ¨ ¨ Pool filter system appeared to be operating within operation limits. Filterpressure measured 5 pounds per square inch (psi). Labeled pressureindicating the filter needs cleaning is 40 psi. Labeled maximum pressurefor this filtration system is 50. Cleaning and/or replacement of filtermedia is normally recommended before reaching this pressure.

14.19 Chlorinator: þ ¨ ¨ Floating chlorine dispenser observed in addition to a Chlorine feeder.The chlorine feeder is installed within the pool piping system. Thisusually has a removable cap where you install chlorine tablets asneeded. Note: Water chemistry was not tested.

Page 44: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Inspection: 031419JH5 Address: 5678 Goodlife St

Page 44

© Finley Home Services Confidential - for client use only. Use by any unauthorized persons is prohibited.

Heaters:OK MM RR

14.20 Type & Condition: þ ¨ ¨ Natural gas. Visual condition appears serviceable. System operatedproperly at the time of inspection. System operated properly at the timeof inspection with digital controls on the face of the heater.

Page 45: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

InterNACHI STANDARDS OF PRACTICE

Finley Home Services is proud to conduct your inspection in accordance with the Standards of Practice of the InternationalAssociation of Certified Home Inspectors (InterNACHI)

Table of Contents

1. Definitions and Scope

2. Limitations, Exceptions & Exclusions

3. Standards of Practice3.1. Roof 3.2. Exterior 3.3. Basement, Foundation, Crawlspace & Structure3.4. Heating 3.5. Cooling 3.6. Plumbing 3.7. Electrical 3.8. Fireplace 3.9. Attic, Insulation & Ventilation3.10. Doors, Windows & Interior

4. Glossary of Terms

1. Definitions and Scope

1.1. A general home inspection is a non-invasive, visual examination of the accessible areas of a residential property(as delineated below), performed for a fee, which is designed to identify defects within specific systems and componentsdefined by these Standards that are both observed and deemed material by the inspector. The scope of work may bemodified by the Client and Inspector prior to the inspection process.

I. The general home inspection is based on the observations made on the date of the inspection, andnot a prediction of future conditions.

II. The general home inspection will not reveal every issue that exists or ever could exist, but only thosematerial defects observed on the date of the inspection.

1.2. A material defect is a specific issue with a system or component of a residential property that may have a significant,adverse impact on the value of the property, or that poses an unreasonable risk to people. The fact that a system orcomponent is near, at, or beyond the end of its normal, useful life is not, in itself, a material defect.

1.3. A general home inspection report shall identify, in written format, defects within specific systems and componentsdefined by these Standards that are both observed and deemed material by the inspector. Inspection reports may includeadditional comments and recommendations.

2. Limitations, Exceptions & Exclusions

2.1. Limitations:

I. An inspection is not technically exhaustive.

Page 46: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

II. An inspection will not identify concealed or latent defects.

III. An inspection will not deal with aesthetic concerns or what could be deemed matters of taste,cosmetic defects, etc.

IV. An inspection will not determine the suitability of the property for any use.

V. An inspection does not determine the market value of the property or its marketability.

VI. An inspection does not determine the insurability of the property.

VII. An inspection does not determine the advisability or inadvisability of the purchase of the inspectedproperty.

VIII.An inspection does not determine the life expectancy of the property or any components or systemstherein.

IX. An inspection does not include items not permanently installed.

X. This Standards of Practice applies to properties with four or fewer residential units and their attachedgarages and carports.

2.2. Exclusions:

I. The inspector is not required to determine:

A. property boundary lines or encroachments.

B. the condition of any component or system that is not readily accessible.

C. the service life expectancy of any component or system.

D. the size, capacity, BTU, performance or efficiency of any component or system.

E. the cause or reason of any condition.

F. the cause for the need of correction, repair or replacement of any system or component.

G. future conditions.

H. compliance with codes or regulations.

I. the presence of evidence of rodents, birds, bats, animals, insects, or other pests.

J. the presence of mold, mildew or fungus.

K. the presence of airborne hazards, including radon.

L. the air quality.

M. the existence of environmental hazards, including lead paint, asbestos or toxic drywall.

N. the existence of electromagnetic fields.

O. any hazardous waste conditions.

P. any manufacturers' recalls or conformance with manufacturer installation, or any informationincluded for consumer protection purposes.

Page 47: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

Q. acoustical properties.

R. correction, replacement or repair cost estimates.

S. estimates of the cost to operate any given system.

II. The inspector is not required to operate:

A. any system that is shut down.

B. any system that does not function properly.

C. or evaluate low-voltage electrical systems, such as, but not limited to:

1. phone lines; 2. cable lines; 3. satellite dishes;4. antennae; 5. lights; or 6. remote controls.

D. any system that does not turn on with the use of normal operating controls.

E. any shut-off valves or manual stop valves.

F. any electrical disconnect or over-current protection devices.

G. any alarm systems.

H. moisture meters, gas detectors or similar equipment.

III. The inspector is not required to:

A. move any personal items or other obstructions, such as, but not limited to: throw rugs,carpeting, wall coverings, furniture, ceiling tiles, window coverings, equipment, plants, ice,debris, snow, water, dirt, pets, or anything else that might restrict the visual inspection.

B. dismantle, open or uncover any system or component.

C. enter or access any area that may, in the inspector's opinion, be unsafe.

D. enter crawlspaces or other areas that may be unsafe or not readily accessible.

E. inspect underground items, such as, but not limited to: lawn-irrigation systems, orunderground storage tanks (or indications of their presence), whether abandoned or activelyused.

F. do anything that may, in the inspector's opinion, be unsafe or dangerous to him/herself orothers, or damage property, such as, but not limited to: walking on roof surfaces, climbingladders, entering attic spaces, or negotiating with pets.

G. inspect decorative items.

H. inspect common elements or areas in multi-unit housing.

I. inspect intercoms, speaker systems or security systems.

J. offer guarantees or warranties.

Page 48: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

K. offer or perform any engineering services.

L. offer or perform any trade or professional service other than general home inspection.

M. research the history of the property, or report on its potential for alteration, modification,extendibility or suitability for a specific or proposed use for occupancy.

N. determine the age of construction or installation of any system, structure or component of abuilding, or differentiate between original construction and subsequent additions,improvements, renovations or replacements.

O. determine the insurability of a property.

P. perform or offer Phase 1 or environmental audits.

Q. inspect any system or component that is not included in these Standards.

3. Standards of Practice

3.1. Roof

I. The inspector shall inspect from ground level or the eaves:

A. the roof-covering materials;

B. the gutters;

C. the downspouts;

D. the vents, flashing, skylights, chimney, and other roof penetrations; and

E. the general structure of the roof from the readily accessible panels, doors or stairs.

II. The inspector shall describe:

A. the type of roof-covering materials.

III. The inspector shall report as in need of correction:

A. observed indications of active roof leaks.

IV. The inspector is not required to:

A. walk on any roof surface.

B. predict the service life expectancy.

C. inspect underground downspout diverter drainage pipes.

D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces.

E. move insulation.

F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similarattachments.

Page 49: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

G. walk on any roof areas that appear, in the inspector's opinion, to be unsafe.

H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage.

I. perform a water test.

J. warrant or certify the roof.

K. confirm proper fastening or installation of any roof-covering material.

3.2. Exterior

I. The inspector shall inspect:

A. the exterior wall-covering materials;

B. the eaves, soffits and fascia;

C. a representative number of windows;

D. all exterior doors;

E. flashing and trim;

F. adjacent walkways and driveways;

G. stairs, steps, stoops, stairways and ramps;

H. porches, patios, decks, balconies and carports;

I. railings, guards and handrails; and

J. vegetation, surface drainage, retaining walls and grading of the property, where they mayadversely affect the structure due to moisture intrusion.

II. The inspector shall describe:

A. the type of exterior wall-covering materials.

III. The inspector shall report as in need of correction:

A. any improper spacing between intermediate balusters, spindles and rails.

IV. The inspector is not required to:

A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, orexterior accent lighting.

B. inspect items that are not visible or readily accessible from the ground, including window anddoor flashing.

C. inspect or identify geological, geotechnical, hydrological or soil conditions.

D. inspect recreational facilities or playground equipment.

E. inspect seawalls, breakwalls or docks.

Page 50: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

F. inspect erosion-control or earth-stabilization measures.

G. inspect for safety-type glass.

H. inspect underground utilities.

I. inspect underground items.

J. inspect wells or springs.

K. inspect solar, wind or geothermal systems.

L. inspect swimming pools or spas.

M. inspect wastewater treatment systems, septic systems or cesspools.

N. inspect irrigation or sprinkler systems.

O. inspect drainfields or dry wells.

P. determine the integrity of multiple-pane window glazing or thermal window seals.

3.3. Basement, Foundation, Crawlspace & Structure

I. The inspector shall inspect:

A. the foundation;

B. the basement;

C. the crawlspace; and

D. structural components.

II. The inspector shall describe:

A. the type of foundation; and

B. the location of the access to the under-floor space.

III. The inspector shall report as in need of correction:

A. observed indications of wood in contact with or near soil;

B. observed indications of active water penetration;

C. observed indications of possible foundation movement, such as sheetrock cracks, brickcracks, out-of-square door frames, and unlevel floors; and

D. any observed cutting, notching and boring of framing members that may, in the inspector'sopinion, present a structural or safety concern.

IV. The inspector is not required to:

A.A. enter any crawlspace that is not readily accessible, or where entry could cause damage orpose a hazard to him/herself.

B. move stored items or debris.

Page 51: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

C. operate sump pumps with inaccessible floats.

D. identify the size, spacing, span or location or determine the adequacy of foundation bolting,bracing, joists, joist spans or support systems.

E. provide any engineering or architectural service.

F. report on the adequacy of any structural system or component.

3.4. Heating

I. The inspector shall inspect:

A. the heating system, using normal operating controls.

II. The inspector shall describe:

A. the location of the thermostat for the heating system;

B. the energy source; and

C. the heating method.

III. The inspector shall report as in need of correction:

A. any heating system that did not operate; and

B. if the heating system was deemed inaccessible.

IV. The inspector is not required to:

A. inspect, measure, or evaluate the interior of flues or chimneys, fire chambers, heatexchangers, combustion air systems, fresh-air intakes, makeup air, humidifiers,dehumidifiers, electronic air filters, geothermal systems, or solar heating systems.

B. inspect fuel tanks or underground or concealed fuel supply systems.

C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, orsupply adequacy of the heating system.

D. light or ignite pilot flames.

E. activate heating, heat pump systems, or other heating systems when ambient temperaturesor other circumstances are not conducive to safe operation or may damage the equipment.

F. override electronic thermostats.

G. evaluate fuel quality.

H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs orclocks.

I. measure or calculate the air for combustion, ventilation, or dilution of flue gases forappliances.

3.5. Cooling

Page 52: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

I. The inspector shall inspect:

A. the cooling system, using normal operating controls.

II. The inspector shall describe:

A. the location of the thermostat for the cooling system; and

B. the cooling method.

III. The inspector shall report as in need of correction:

A. any cooling system that did not operate; and

B. if the cooling system was deemed inaccessible.

IV. The inspector is not required to:

A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, orsupply adequacy of the cooling system.

B. inspect portable window units, through-wall units, or electronic air filters.

C. operate equipment or systems if the exterior temperature is below 65° Fahrenheit, or whenother circumstances are not conducive to safe operation or may damage the equipment.

D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks orclocks.

E. examine electrical current, coolant fluids or gases, or coolant leakage.

3.6. Plumbing

I. The inspector shall inspect:

A. the main water supply shut-off valve;

B. the main fuel supply shut-off valve;

C. the water heating equipment, including the energy source, venting connections,temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing;

D. interior water supply, including all fixtures and faucets, by running the water;

E. all toilets for proper operation by flushing;

F. all sinks, tubs and showers for functional drainage;

G. the drain, waste and vent system; and

H. drainage sump pumps with accessible floats.

II. The inspector shall describe:

A. whether the water supply is public or private based upon observed evidence;

B. the location of the main water supply shut-off valve;

Page 53: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

C. the location of the main fuel supply shut-off valve;

D. the location of any observed fuel-storage system; and

E. the capacity of the water heating equipment, if labeled.

III. The inspector shall report as in need of correction:

A. deficiencies in the water supply by viewing the functional flow in two fixtures operatedsimultaneously;

B. deficiencies in the installation of hot and cold water faucets;

C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories andtubs; and

D. toilets that were damaged, had loose connections to the floor, were leaking, or had tankcomponents that did not operate.

IV. The inspector is not required to:

A. light or ignite pilot flames.

B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater.

C. inspect the interior of flues or chimneys, combustion air systems, water softener or filteringsystems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinklersystems, or fire sprinkler systems.

D. determine the exact flow rate, volume, pressure, temperature or adequacy of the watersupply.

E. determine the water quality, potability or reliability of the water supply or source.

F. open sealed plumbing access panels.

G. inspect clothes washing machines or their connections.

H. operate any valve.

I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflowprotection.

J. evaluate the compliance with conservation, energy or building standards, or the proper designor sizing of any water, waste or venting components, fixtures or piping.

K. determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices.

L. determine whether there are sufficient cleanouts for effective cleaning of drains.

M. evaluate fuel storage tanks or supply systems.

N. inspect wastewater treatment systems.

O. inspect water treatment systems or water filters.

P. inspect water storage tanks, pressure pumps, or bladder tanks.

Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heaterelements.

Page 54: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

R. evaluate or determine the adequacy of combustion air.

S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-reliefvalves, control valves, or check valves.

T. examine ancillary or auxiliary systems or components, such as, but not limited to, thoserelated to solar water heating and hot water circulation.

U. determine the existence or condition of polybutylene plumbing.

V. inspect or test for gas or fuel leaks, or indications thereof.

3.7. Electrical

I. The inspector shall inspect:

A. the service drop;

B. the overhead service conductors and attachment point;

C. the service head, gooseneck and drip loops;

D. the service mast, service conduit and raceway;

E. the electric meter and base;

F. service-entrance conductors;

G. the main service disconnect;

H. panelboards and over-current protection devices (circuit breakers and fuses);

I. service grounding and bonding;

J. a representative number of switches, lighting fixtures and receptacles, including receptaclesobserved and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI testbutton, where possible;

K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to beGFCIs using a GFCI tester, where possible; and

L. smoke and carbon-monoxide detectors.

II. The inspector shall describe:

A. the main service disconnect's amperage rating, if labeled; and

B. the type of wiring observed.

III. The inspector shall report as in need of correction:

A. deficiencies in the integrity of the service-entrance conductors’ insulation, drip loop, andvertical clearances from grade and roofs;

B. any unused circuit-breaker panel opening that was not filled;

Page 55: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible;

D. any tested receptacle in which power was not present, polarity was incorrect, the cover wasnot in place, the GFCI devices were not properly installed or did not operate properly,evidence of arcing or excessive heat, and where the receptacle was not grounded or was notsecured to the wall; and

E. the absence of smoke detectors.

IV. The inspector is not required to:

A. insert any tool, probe or device into the main panelboard, sub-panels, distributionpanelboards, or electrical fixtures.

B. operate electrical systems that are shut down.

C. remove panelboard cabinet covers or dead fronts.

D. operate or re-set over-current protection devices or overload devices.

E. operate or test smoke or carbon-monoxide detectors or alarms.

F. inspect, operate or test any security, fire or alarm systems or components, or other warning orsignaling systems.

G. measure or determine the amperage or voltage of the main service equipment, if not visiblylabeled.

H. inspect ancillary wiring or remote-control devices.

I. activate any electrical systems or branch circuits that are not energized.

J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or anytime-controlled devices.

K. verify the service ground.

L. inspect private or emergency electrical supply sources, including, but not limitedto: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility.

M. inspect spark or lightning arrestors.

N. inspect or test de-icing equipment.

O. conduct voltage-drop calculations.

P. determine the accuracy of labeling.

Q. inspect exterior lighting.

3.8. Fireplace

I. The inspector shall inspect:

A. readily accessible and visible portions of the fireplaces and chimneys;

B. lintels above the fireplace openings;

Page 56: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

C. damper doors by opening and closing them, if readily accessible and manually operable; and

D. cleanout doors and frames.

II. The inspector shall describe:

A. the type of fireplace.

III. The inspector shall report as in need of correction:

A. evidence of joint separation, damage or deterioration of the hearth, hearth extension orchambers;

B. manually operated dampers that did not open and close;

C. the lack of a smoke detector in the same room as the fireplace;

D. the lack of a carbon-monoxide detector in the same room as the fireplace; and

E. cleanouts not made of metal, pre-cast cement, or other non-combustible material.

IV. The inspector is not required to:

A. inspect the flue or vent system.

B. inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels.

C. determine the need for a chimney sweep.

D. operate gas fireplace inserts.

E. light pilot flames.

F. determine the appropriateness of any installation.

G. inspect automatic fuel-fed devices.

H. inspect combustion and/or make-up air devices.

I. inspect heat-distribution assists, whether gravity-controlled or fan-assisted.

J. ignite or extinguish fires.

K. determine the adequacy of drafts or draft characteristics.

L. move fireplace inserts, stoves or firebox contents.

M. perform a smoke test.

N. dismantle or remove any component.

O. perform a National Fire Protection Association (NFPA)-style inspection.

P. perform a Phase I fireplace and chimney inspection.

3.9. Attic, Insulation & Ventilation

Page 57: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

I. The inspector shall inspect:

A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas;

B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and

C. mechanical exhaust systems in the kitchen, bathrooms and laundry area.

II. The inspector shall describe:

A. the type of insulation observed; and

B. the approximate average depth of insulation observed at the unfinished attic floor area or roofstructure.

III. The inspector shall report as in need of correction:

A. the general absence of insulation or ventilation in unfinished spaces.

IV. The inspector is not required to:

A. enter the attic or any unfinished spaces that are not readily accessible, or where entry couldcause damage or, in the inspector's opinion, pose a safety hazard.

B. move, touch or disturb insulation.

C. move, touch or disturb vapor retarders.

D. break or otherwise damage the surface finish or weather seal on or around access panels orcovers.

E. identify the composition or R-value of insulation material.

F. activate thermostatically operated fans.

G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets,boilers or wiring.

H. determine the adequacy of ventilation.

3.10. Doors, Windows & Interior

I. The inspector shall inspect:

A. a representative number of doors and windows by opening and closing them;

B. floors, walls and ceilings;

C. stairs, steps, landings, stairways and ramps;

D. railings, guards and handrails; and

E. garage vehicle doors and the operation of garage vehicle door openers, using normaloperating controls.

II. The inspector shall describe:

A. a garage vehicle door as manually-operated or installed with a garage door opener.

Page 58: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

III. The inspector shall report as in need of correction:

A. improper spacing between intermediate balusters, spindles and rails for steps, stairways,guards and railings;

B. photo-electric safety sensors that did not operate properly; and

C. any window that was obviously fogged or displayed other evidence of broken seals.

IV. The inspector is not required to:

A. inspect paint, wallpaper, window treatments or finish treatments.

B. inspect floor coverings or carpeting.

C. inspect central vacuum systems.

D. inspect for safety glazing.

E. inspect security systems or components.

F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures.

G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect theconcealed floor structure.

H. move suspended-ceiling tiles.

I. inspect or move any household appliances.

J. inspect or operate equipment housed in the garage, except as otherwise noted.

K. verify or certify the proper operation of any pressure-activated auto-reverse or related safetyfeature of a garage door.

L. operate or evaluate any security bar release and opening mechanisms, whether interior orexterior, including their compliance with local, state or federal standards.

M. operate any system, appliance or component that requires the use of special keys, codes,combinations or devices.

N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights.

O. inspect microwave ovens or test leakage from microwave ovens.

P. operate or examine any sauna, steam-generating equipment, kiln, toaster, ice maker, coffeemaker, can opener, bread warmer, blender, instant hot-water dispenser, or other small,ancillary appliances or devices.

Q. inspect elevators.

R. inspect remote controls.

S. inspect appliances.

T. inspect items not permanently installed.

U. discover firewall compromises.

Page 59: Home Inspection Reportfinleyhomeservices.com/.../uploads/...Goodlife-St.pdf · 5678 Goodlife St Roseville CA 95678 March 14, 2019 Prepared for: James Sample 5678 Goodlife St Roseville

V. inspect pools, spas or fountains.

W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects.

X. determine the structural integrity or leakage of pools or spas.