HMWPE Cathodic Protection Cable - Groundbed · HMWPE Cathodic Protection Cable Application HMWPE...

2
HMWPE Cathodic Protection Cable Application HMWPE insulated cable is composed of copper wire, which is covered by High Molecular Weight Polyethylene (HMWPE) high thickness insulation. The copper wire is stranded and annealed to permit extra flexibility. The polyethylene on the cable is approximately twice as thick as on conventional HMWPE wire; it serving as both electrical insulator and mechanical cover for the conductor. This provides cable with outstanding dielectric strength and moisture resistance. During installation, the cable can withstand considerable mechanical abuse without risk of damage to the copper electrical conductor. The polyethylene cover is also chemically resistant and protects against most organic and inorganic substances. Availability HMWPE cable is offered in a variety of sizes. It can be used as a header cable on cathodic protection systems or to make anode-lead or negative-return connections. The thick polyethylene cover permits direct burial of the cable in native soils or submersion in freshwater. The cable exhibits superior flexibility and can be bent without risk of notch propagation. It is not recommended for use in environments containing chlorine, hydrochloric acid, or petroleum hydrocarbons. Construction Ref: CTS-MDS-05-01-Rev0 Cable Azerbaijan l Bahrain l Georgia l India l Kingdom of Saudi Arabia l Qatar l United Arab Emirates l United Kingdom [email protected] www.ctsonline.com Conductors Insulation Thickness Colour Temperature Rating Min. Bending Radius Testing Stranded soft bare annealed copper class B-8 High molecular weight polyethylene conforming to ASTM D-1248 Type 1, Grades E1-E5, J1 to J3 The minimum thickness of the insulation at any point shall not be less than 90% of the specified average thickness Black. Other colours available on request Overall 75 o C, 600V 10xOD of cable The cable shall be tested in accordance with ASTM B-3, B-8, D-1248. Spark testing at 7500VAC

Transcript of HMWPE Cathodic Protection Cable - Groundbed · HMWPE Cathodic Protection Cable Application HMWPE...

Page 1: HMWPE Cathodic Protection Cable - Groundbed · HMWPE Cathodic Protection Cable Application HMWPE insulated cable is composed of copper wire, which is covered by High Molecular Weight

HMWPE Cathodic Protection Cable

Application

HMWPE insulated cable is composed of copper wire, which is covered by High Molecular Weight Polyethylene (HMWPE) high thickness insulation. The copper wire is stranded and annealed to permit extra flexibility. The polyethylene on the cable is approximately twice as thick as on conventional HMWPE wire; it serving as both electrical insulator and mechanical cover for the conductor. This provides cable with outstanding dielectric strength and moisture resistance. During installation, the cable can withstand considerable mechanical abuse without risk of damage to the copper electrical conductor.

The polyethylene cover is also chemically resistant and protects against most organic and inorganic substances.

Availability

HMWPE cable is offered in a variety of sizes. It can be used as a header cable on cathodic protection systems or to make anode-lead or negative-return connections. The thick polyethylene cover permits direct burial of the cable in native soils or submersion in freshwater. The cable exhibits superior flexibility and can be bent without risk of notch propagation. It is not recommended for use in environments containing chlorine, hydrochloric acid, or petroleum hydrocarbons.

Construction

Ref: CTS-MDS-05-01-Rev0

Cab

le

Azerbaijan l Bahrain l Georgia l India l Kingdom of Saudi Arabia l Qatar l United Arab Emirates l United Kingdom

[email protected] www.ctsonline.com

Conductors

Insulation

Thickness

Colour

Temperature Rating

Min. Bending Radius

Testing

Stranded soft bare annealed copper class B-8

High molecular weight polyethylene conforming to ASTM D-1248 Type 1, Grades E1-E5, J1 to J3

The minimum thickness of the insulation at any point shall not be less than 90% of the specified average thickness

Black. Other colours available on request

Overall 75oC, 600V

10xOD of cable

The cable shall be tested in accordance with ASTM B-3, B-8, D-1248. Spark testing at 7500VAC

Page 2: HMWPE Cathodic Protection Cable - Groundbed · HMWPE Cathodic Protection Cable Application HMWPE insulated cable is composed of copper wire, which is covered by High Molecular Weight

* Typical current ratings are given as a guide only. Check manufacturer’s rating for the particular site operating conditions including all relevant de-rating factors.

Ref: CTS-MDS-05-01-Rev0

Cab

le

DisclaimerThe information provided in this document was accurate at the time it was published, however, we reserve the right to revise this document without prior warning.

Performance Data

Size Strands InsulationThickness

NominalOverall

Diameter

DC at20oC

Approx.shippingWeight

MaximumCurrentRating

mm2

2.5

4

6

10

16

25

35

50

70

95

120

No

7

7

7

7

7

7

7

19

19

19

19

mm

2.8

2.8

2.8

2.8

2.8

2.8

2.8

3.18

3.18

3.18

3.18

mm

7.65

8.20

8.75

9.70

10.70

12.10

13.20

15.30

17.10

19.00

20.65

Ohm/km

7.41

4.63

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

kg/km

70

90

120

146

171

249

374

464

782

1048

1295

Amp*

18

24

30

42

56

73

90

145

185

230

260