High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R

Transcript of High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s...

Page 1: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

High Voltage Surge ArrestersBuyer´s Guide — Section PEXLIM R

Page 2: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

ABB Surge Arresters — Buyer´s Guide | Technical information 29

Zinc Oxide Surge Arrester PEXLIM R

Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. For use when requirements of lightning intensity, energy capability and pollution are moderate.

Superior where low weight, reduced clearances, flexible mounting, non-fragility and additional personnel safety is required.Major component in PEXLINKTM concept for transmission line protection.

Other data can be ordered on request. Please contact your local sales representative.

Brief performance data

System voltages (Um) 24 - 170 kV

Rated voltages (Ur) 18 - 144 kV

Nominal discharge current (IEC) 10 kApeak

Discharge current withstand strength:

High current 4/10 µs

Low current 2 000 µs

100 kApeak

600 Apeak

Energy capability:

Line discharge class (IEC)

[2 impulses, (IEC Cl. 8.5.5)

Fulfils/exceeds requirements of ANSI transmission-

line discharge test for 170 kV systems.

Class 2

5.1 kJ/kV (Ur)]

Short-circuit/Pressure relief capability 50 kAsym

External insulation Fulfils/exceeds

standards

Mechanical strength:

Specified long-term load (SLL)

Specified short-term load (SSL)

1 000 Nm

1 600 Nm

Service conditions:

Ambient temperature

Design altitude

Frequency

-50 °C to +45 °C

max. 1 000 m

15 - 62 Hz

Page 3: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

30 Technical information | ABB Surge Arresters — Buyer´s Guide

PEXLIM RGuaranteed protective data 24 - 100 kV

Max. system voltage

Rated voltage

Max. continuous operating voltage 1)

TOV capability 2) Max. residual voltage with current wave

as per IEC

as per ANSI/IEEE

30/60 µs 8/20 µs

Um

kVrms

Ur

kVrms

Uc

kVrms

MCOV

kVrms

1 s

kVrms

10 s

kVrms

0.5 kA

kVpeak

1 kA

kVpeak

2 kA

kVpeak

5 kA

kVpeak

10 kA

kVpeak

20 kA

kVpeak

40 kA

kVpeak

243) 18 14.4 15.3 20.7 19.8 37.1 38.5 40.3 44.0 46.7 52.3 59.7

21 16.8 17.0 24.1 23.1 43.2 44.9 47.0 51.3 54.4 61.0 69.7

24 19.2 19.5 27.6 26.4 49.4 51.3 53.8 58.7 62.2 69.7 79.6

27 21.6 22.0 31.0 29.7 55.6 57.7 60.5 66.0 70.0 78.4 89.6

363) 30 24.0 24.4 34.5 33.0 61.7 64.2 67.2 73.3 77.7 87.1 100

33 26.4 26.7 37.9 36.3 67.9 70.6 73.9 80.6 85.5 95.8 110

36 28.8 29.0 41.4 39.6 74.1 77.0 80.6 88.0 93.3 105 120

39 31.2 31.5 44.8 42.9 80.3 83.4 87.3 95.3 102 114 130

42 34 34.0 48.3 46.2 86.4 89.8 94.0 103 109 122 140

48 38 39.0 55.2 52.8 98.8 103 108 118 125 140 160

52 42 34 34.0 48.3 46.2 86.4 89.8 94.0 103 109 122 140

48 38 39.0 55.2 52.8 98.8 103 108 118 125 140 160

51 41 41.3 58.6 56.1 105 109 115 125 133 148 170

54 43 42.0 62.1 59.4 112 116 121 132 140 157 180

60 48 48.0 69.0 66.0 124 129 135 147 156 175 199

66 53 53.4 75.9 72.6 136 142 148 162 171 192 219

72 54 43 42.0 62.1 59.4 112 116 121 132 140 157 180

60 48 48.0 69.0 66.0 124 129 135 147 156 175 199

66 53 53.4 75.9 72.6 136 142 148 162 171 192 219

72 58 58.0 82.8 79.2 149 154 162 176 187 209 239

75 60 60.7 86.2 82.5 155 161 168 184 195 218 249

84 67 68.0 96.6 92.4 173 180 188 206 218 244 279

90 72 72.0 103 99.0 186 193 202 220 234 262 299

96 77 77.0 110 105 198 206 215 235 249 279 319

100 75 60 60.7 86.2 82.5 155 161 168 184 195 218 249

84 67 68.0 96.6 92.4 173 180 188 206 218 244 279

90 72 72.0 103 99.0 186 193 202 220 234 262 299

96 77 77.0 110 105 198 206 215 235 249 279 319

More detailed information on the TOV capability and the protective characteristics are given in Publ. 1HSM 9543 13-01en.

1) The continuous operating voltages Uc (as per IEC) and MCOV (as per ANSI) differ only due to deviations in type test procedures. Uc has to be considered only when the actual system voltage is higher than the tabulated. Any arrester with Uc higher than or equal to the actual system voltage divided by √3 can be selected.

2) With prior duty equal to the maximum single-impulse energy stress (2.5 kJ/kV (Ur)).

3) Arresters for system voltages 36 kV or below can be supplied, on request, when the order also includes arresters for higher system voltages.

Arresters with lower or higher rated voltages may be available on request for special applications.

Page 4: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

ABB Surge Arresters — Buyer´s Guide | Technical information 31

Max. system voltage

Rated voltage

Max. continuous operating voltage 1)

TOV capability 2) Max. residual voltage with current wave

as per IEC

as per ANSI/IEEE

30/60 µs 8/20 µs

Um

kVrms

Ur

kVrms

Uc

kVrms

MCOV

kVrms

1 s

kVrms

10 s

kVrms

0.5 kA

kVpeak

1 kA

kVpeak

2 kA

kVpeak

5 kA

kVpeak

10 kA

kVpeak

20 kA

kVpeak

40 kA

kVpeak

123 90 72 72.0 103 99.0 186 193 202 220 234 262 299

96 77 77.0 110 105 198 206 215 235 249 279 319

102 78 82.6 117 112 210 218 229 250 265 296 339

108 78 84.0 124 118 223 231 242 264 280 314 359

120 78 98.0 138 132 247 257 269 294 311 349 398

132 78 106 151 145 272 283 296 323 342 383 438

138 78 111 158 151 284 295 309 338 358 401 458

144 78 115 165 158 297 308 323 352 373 418 478

145 108 86 86.0 124 118 223 231 242 264 280 314 359

120 92 98.0 138 132 247 257 269 294 311 349 398

132 92 106 151 145 272 283 296 323 342 383 438

138 92 111 158 151 284 295 309 338 358 401 458

144 92 115 165 158 297 308 323 352 373 418 478

170 132 106 106 151 145 272 283 296 323 342 383 438

138 108 111 158 151 284 295 309 338 358 401 458

144 108 115 165 158 297 308 323 352 373 418 478

More detailed information on the TOV capability and the protective characteristics are given in Publ. 1HSM 9543 13-01en.

1) The continuous operating voltages Uc (as per IEC) and MCOV (as per ANSI) differ only due to deviations in type test procedures. Uc has to be considered only when the actual system voltage is higher than the tabulated. Any arrester with Uc higher than or equal to the actual system voltage divided by √3 can be selected.

2) With prior duty equal to the maximum single-impulse energy stress (2.5 kJ/kV (Ur)).

Arresters with lower or higher rated voltages may be available on request for special applications.

PEXLIM RGuaranteed protective data 123 - 170 kV

Page 5: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

32 Technical information | ABB Surge Arresters — Buyer´s Guide

PEXLIM RTechnical data for housings

Max. system voltage

Rated voltage

Housing Creepage distance

mm

External insulation *) Dimensions

Um

kVrms

Ur

kVrms

1.2/50 µs dry

kVpeak

50 Hz wet (60s)

kVrms

60 Hz wet (10s)

kVrms

250/2500 µs wet

kVpeak

Mass

kg

Amax

mm

B

mm

C

mm

Fig.

24 18-27 YV024 1863 310 150 150 250 13 641 - - 1

36 30-48 YV036 1863 310 150 150 250 14 641 - - 1

52 42-60 YV052 1863 310 150 150 250 14 641 - - 1

66 YV052 2270 370 180 180 300 16 727 - - 1

72 54-60 YH072 1863 310 150 150 250 14 641 - - 1

54-72 YV072 2270 370 180 180 300 16 727 - - 1

75-96 YV072 3726 620 300 300 500 24 1216 - - 2

100 75-96 YV100 3726 620 300 300 500 24 1216 - - 2

123 90 YH123 3726 620 300 300 500 26 1236 400 160 3

96-120 YH123 3726 620 300 300 500 25 1216 - - 2

90-96 YV123 4133 680 330 330 550 28 1322 400 160 3

102-132 YV123 4133 680 330 330 550 27 1302 - - 2

138-144 YV123 4540 740 360 360 600 29 1388 - - 2

145 108 YH145 3726 620 300 300 500 27 1236 400 160 3

120 YH145 3726 620 300 300 500 25 1216 - - 2

108 YV145 4540 740 360 360 600 30 1408 400 160 3

120-144 YV145 4540 740 360 360 600 29 1388 - - 2

170 132-144 YH170 4540 740 360 360 600 31 1408 400 160 3

Neutral-ground arresters52 30-36 YN052 1863 310 150 150 250 14 641 - - 1

72 42-54 YN072 1863 310 150 150 250 14 641 - - 1

100 60 YN100 1863 310 150 150 250 14 641 - - 1

123 72 YN123 2270 370 180 180 300 16 727 - - 1

84-120 YN123 3726 620 300 300 500 25 1216 - - 2

145 75-120 YN145 3726 620 300 300 500 25 1216 - - 2

170 75-120 YN170 3726 620 300 300 500 25 1216 - - 2

*) Sum of withstand voltages for empty units of arrester.

Page 6: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

ABB Surge Arresters — Buyer´s Guide | Technical information 33

PEXLIM RTechnical data for housings

Figure 1 Figure 2 Figure 3

Page 7: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

34 Technical information | ABB Surge Arresters — Buyer´s Guide

Line terminals

1HSA410 000-LAluminium

1HSA410 000-MAluminium flag with other

items in stainless steel

1HSA410 000-NAluminium

1HSA410 000-PStainless steel

Earth terminals

1HSA420 000-AStainless steel

1HSA420 000-BStainless steel

Drilling plans

Without insulating baseAluminium

Insulating base1HSA430 000-H

Epoxy resin

M12 bolts for connection to structure are not supplied by ABB. Required threaded grip length is 15-20 mm.

PEXLIM RAccessories

Page 8: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

ABB Surge Arresters — Buyer´s Guide | Technical information 35

Rated voltage Housing Number of arresters per crate

One Three Six

Ur

kVrms

Volume

m3

Gross

kg

Volume

m3

Gross

kg

Volume

m3

Gross

kg

18-27 YV024 0.5 35 0.5 65 0.9 110

30-48 YV036 0.5 36 0.5 68 0.9 116

42-60 YV052 0.5 36 0.5 68 0.9 116

66 YV052 0.5 38 0.5 74 0.9 128

54-60 YH072 0.5 36 0.5 68 0.9 116

54-72 YV072 0.5 38 0.5 74 0.9 128

75-96 YV072 0.7 51 0.7 103 1.2 181

75-96 YV100 0.7 51 0.7 103 1.2 181

90 YH123 0.7 53 0.7 109 1.2 193

96-120 YH123 0.7 52 0.7 106 1.2 187

90-96 YV123 0.7 55 0.7 115 1.2 205

102-132 YV123 0.7 54 0.7 112 1.2 199

138-144 YV123 0.9 61 0.9 123 1.5 216

108-120 YH145 0.7 54 0.7 112 1.2 199

108 YV145 0.9 62 0.9 126 1.5 222

120-144 YV145 0.9 61 0.9 123 1.5 216

132-144 YH170 0.9 63 0.9 129 1.5 228

Neutral-ground arresters30-36 YN052 0.5 36 0.5 68 0.9 116

42-54 YN072 0.5 36 0.5 68 0.9 116

60 YN100 0.5 36 0.5 68 0.9 116

72 YN123 0.5 38 0.5 74 0.9 128

84-120 YN123 0.7 52 0.7 106 1.2 187

75-120 YN145 0.7 52 0.7 106 1.2 187

75-120 YN170 0.7 52 0.7 106 1.2 187

PEXLIM RShipping data

Each crate contains a certain number of arrester units and accessories for assembly and erection. A packing list is at-tached externally on each crate.

Each separate crate is numbered and the numbers of all crates and their contents are listed in the shipping specifica-

tion. ABB reserves the right to pack arresters in the most effective/economic combination. Alternate or non-standard crates may involve additional charges.

The table above is to be seen as an approximation and specific data for deliveries may differ from the values given.

Page 9: High Voltage Surge Arresters Buyer´s Guide — Section PEXLIM R...ABB Surge Arresters — Buyer´s Guide | Technical information 35 Rated voltage Housing Number of arresters per crate

Sec

tion

of 1

HS

M 9

543

12-0

0en

Sur

ge A

rres

ters

Buy

er´s

Gui

de,

Ed

ition

7.1

, 20

09-1

0For more information please contact: ABB AB High Voltage Products Surge Arresters SE-771 80 Ludvika, Sweden Phone: +46 (0)240 78 20 00 Fax: +46 (0)240 179 83 E-Mail: [email protected] www.abb.com/arrestersonline

©Copyright 2009 ABB

All rights reserved