VCM-CLAD
3.6/7.2/12kVHigh-voltage Metal-enclosed Switchgear and Controlgear
07A1-E-0009
1 2
1. Applicabilityn VCM-CLAD has a high applicability as a switchgear for various
industrial facilities and power plants with its wide range ratings (up to 12kV, up to 4000A, up to 50kA). The suitable system can be made a plan by the wide selection.
n VCM-V3, V6 A maximum of up to three units can be stacked so allowing a drastic reduction in the number of units and panels required.
Scope of VCB basic type
Rated voltage [kV] 3.6/7.2
Rated breaking current [kA]
8 12.5 20 25 31.5 40 50
Rated current [A]
400
600
1200
2000
3000
4000
Rated voltage [kV] 12
Rated breaking current [kA]
12.5 16 20 25 31.5 40 50
Rated current [A]
600
1200
2000
3000
4000
: MULTI.VCB, Auto.V
: HS Series (Motor-spring stored-energy)
Features
2. Safety designn VCM-CLAD is designed for horizontal isolation, and the unit
housing is of firm fabricated-steel construction.
n The metal-clad design of VCM-CLAD ensures safety with perfect interlocks. The withdrawable circuit breaker has complete mechanical interlocks to prevent a mal-operation.
n Busbar and circuit spout orifices are fitted with automatically operated safety shutters. The shutters are of resin, and close orifices by withdrawal of the breaker.
Degree of protection Enclosure IP 2X 1)
Partition IP 2X 2)
Busbar system Single Bare 3)
Note. 1) Enclosures are available for the degrees of protection of IP3X, if required. 2) Partitions are available for the degree of protection of IP3X, if required. 3) Busbars can be insulated, when required.
Safety shutters
DK8745
3. Safety interlocksThe following mechanical interlocks are provided to achieve safety.(1) The circuit breaker cannot be drawn-out or inserted to/from the service position while it is closed.(2) The circuit breaker cannnot be closed while it is being drawn-out or inserted.(3) When IEC298 standard (Metal clad type) is applied, aux. circuit plug interlock is provided as shown below.Aux. circuit plug can not be removed while the circuit breaker isin [SERVICE] position.
Aux. circuit plug interlock for IEC298 (Metal Clad Type)
Front cover of VCB
Floor of cradle
Knob
Fixture
Interlockpin
Aux. circuit plugof VCB side
Interlock rail
Moving rod
Insertioninhibitionstopper
Aux.circuitplug ofpanel side
Isolated position (test position when aux. circuit plug is inserted.)
4. Maintenance and inspectionThe long mechanical and electrical life of the vacuum circuit breaker has minimized maintenance and inspection work with its simple and unique design.
Multiple function protector and controller (option)
DK10734
5. Variety of optional itemsn Earthing switchn Multiple function protector and controllern Surge absorber
Earthing switch (option)
N89-4322-13
DK3252
3 4
Ratings
g 3.6/7.2kVSwitchgear Type VCM-V3/VCM-V6
Rated voltage [kV] 3.6/7.2
Applicable standard JEM1425-CW IEC298 JEM1425-MW IEC298 JEM1425-MWG IEC298
Construction Partition Not provided Provided Provided
VCB shutter Not provided Provided (Resin) Provided (Resin)
Busbar Bare Bare Insulated
Rated frequency [Hz] 50/60
Rated busbar current [A] 630 630ñ1250ñ2000ñ3150 (3000) 630ñ1250ñ2000ñ3150 (3000)ñ4000
Rated short-time current [kA] 12.5 20 25 31.5 40 50
Rated insulation level 16kV AC/1min, 45kV peak (class 3A) 10kV AC/1min, 40kV peak (IEC298)22kV AC/1min, 60kV peak (class 6A) 20kV AC/1min, 60kV peak (IEC298)
Rated operating voltage [V] AC 100/200, DC 100/200
Cricuit breaker Type HB1206 HS2006 HS2506 HS3106 HS4006 HS5006
Rated breaking current [kA] 12.5 20 25 31.5 40 50
Rated current [A] 600 (630) 600 (630)ñ1200 (1250)ñ2000 1200 (1250)ñ2000ñ3000ñ4000*1
Closing system Motor-spring stored-energy
Note *1: Available only for HS4006
g 12kVSwitchgear Type VCM-V10
Rated voltage [kV] 12
Applicable standard JEM1425-CW IEC298 JEM1425-MW IEC298 JEM1425-MWG IEC298
Construction Partition Not provided Provided Provided
VCB shutter Not provided Provided (Resin) Provided (Resin)
Busbar Bare Bare Insulated
Rated frequency [Hz] 50/60
Rated busbar current [A] 630ñ1250ñ2000ñ3150 (3000)ñ4000
Rated short-time current [kA] 12.5 20 25 31.5 40 50
Rated insulation level 28kV AC/1min, 75kV peak (class 10B) Same as IEC298
Rated operating voltage [V] AC 100/200, DC 100/200
Cricuit breaker Type HS1210 HS2010 HS2510 HS3110 HS4010 HS5010
Rated breaking current [kA] 12.5 20 25 31.5 40 50
Rated current [A] 600 (630)ñ1200 (1250)ñ2000 1200 (1250)ñ2000ñ3000ñ4000*2
Closing system Motor-spring stored-energy
Note *2: Available only for HS4010
Construction
1. Example of switchgear and controlgear
Metal-clad type (MW) Cubicle type (CW)
Protective platePartitionCT
Shutter
CT
ZCT
Earth bar
Busbarcompartment
Cablecompartment
Circuit breakercompartment
VCB
VCB
Service position
Test/lsolatedposition
Control cableentry room
Protective plateCT
CT
ZCT
Earth bar
Busbar
Test/lsolated position
Service position
VCB
VCB
Control cableentry room
2. BusbarsThe busbars are of hard-drawn high-conductivity copper, and can be insulated with epoxy-coating except connections. The connections are covered with easily removable insulated cover.The insulations can withstand a rated voltage for 1 minute as well as a temperature rise caused by short-circuit currents.
Busbar compartment DK8746
3. Voltage Transformers (VTs)The VTs are epoxy resin molded type. The VTs and its associated primary fuses are withdrawable type, and are installed in the independent compartment. The VTs have the "service" and "disconnected" positions with a indicator visible from the outside of the unit.
Drawable truck DK8747
5 6
g Lead-in of main circuit
Item Specifications
Parts of lead-in Rear and bottom in cabinet by cable
Kind of cable XLPE cable without armour
Cable termination facilities
Cable lugs, glands, terminating facilities, etc.will not be supplied by Fuji.
g Lead-in auxiliary and control circuit
Item Specifications
Parts of lead-in Front and bottom in cabinet by cable
Allowable cable size Maximum 5.5mm2
Cable termination facilities
Cable lugs, glands, etc. will not be supplied by Fuji.
g Specifications of auxiliary and control circuit wiring
Item Specifications
Wiring method Duct and/or bundle wiring
Kind of wires 600V PVC insulation wires
As per JIS C 3307
Size of wires For general circuit Minimum 1.25mm2
Secondary circuit of instrument transformer
Minimum 1.25mm2
Sheath color of wires
Yellow (Green: Earthing circuit)
g Color identification of phases and polarities
Item Specifications
Kind of source
Alternating current (AC) Direct current (DC)
Phases and polarities
1st phase (R)
2nd phase (S)
3rd phase (T)
Zero or neutral (O or N)
Positive pole (P)
Negative pole (N)
Color identification
Red White Blue Black Red Blue
g Specifications of finish color
Parts to be colored Color(Munsell notation)
External and internal surfaces of metal enclosure 5Y7/1
Frames of apparatus, i.e., meter and relays appearing on the surface of the panel
N1.5
Switch handles, operating handles, etc.
general use N1.5
for emergency stop 7.5R4.5/14
g Specifications of nameplates (labels)
Item Specifications
Materials Color of background
Color of letter
Calligraphis style
For title and purpose Plastics White Black Round gothic type
For operation of the control and selection switches
Metal Silver aventurine
Black Round gothic type
g VCM-V3 and VCM-V6
Rated breaking current [kA]
12.5/20/25
Rated busbar current [A]
630 to 2000 3150 (3000) 4000
Rated unit current [A]
600 1200
600 1200 2000
600 1200
3000 600 1200
4000
Drawing number
①②③④⑥⑦⑧
⑥⑦ ⑦⑧ ⑤⑥ ⑦⑧ ⑤⑥
W [mm] 700 700 900 800 1150
D [mm] 1960 2160 2260
H [mm] 2300 (Base channel + 50)
Mass [kg] 800 900 1000 1300 1500
Rated breaking current [kA]
31.5/40
Rated busbar current [A]
630 to 2000 3150 (3000) 4000
Rated unit current [A]
600 1200
600 1200 2000
600 1200
2000 3000 600 1200
2000 4000
Drawing number
⑦⑧ ⑥⑦ ⑦⑧ ⑥ ⑤⑥ ⑦⑧ ⑥ ⑤⑥
W [mm] 800 800 900 800 1150
D [mm] 2160 2260
H [mm] 2300 (Base channel + 50)
Mass [kg] 1100 1300 1400 1500 1400 1500 1700
g VCM-V10
Rated breaking current [kA]
12.5/20/25
Rated busbar current [A]
630 to 2000 3150 (3000) 4000
Rated unitcurrent [A]
600 1200
600 1200 2000
600 1200
3000 600 1200
4000
Drawing number
⑩⑫⑬ ⑩⑪⑫ ⑩⑫⑬ ⑨⑪ ⑩⑫⑬ ⑨⑪
W [mm] 800 1100 800 1200
D [mm] 2360 2460 2560
H [mm] 2600 (Base channel + 50)
Mass [kg] 1300 1500 1600
Rated breaking current [kA]
31.5/40
Rated busbar current [A]
630 to 2000 3150 (3000) 4000
Rated unit current [A]
600 1200
600 1200 2000
600 1200
3000 600 1200
4000
Drawing number
⑩⑫⑬ ⑩⑪⑫ ⑩⑫⑬ ⑨⑪ ⑩⑫⑬ ⑨⑪
W [mm] 900 900 1200 900 1200
D [mm] 2360 2460 2560
H [mm] 2600 (Base channel + 50)
Mass [kg] 1400 1600 1700
3.6/7.2kV Typical Arrangement
g 2 units typeSkeleton
DS
VCB
2×CT
VCB
2×CT
2×VT
3×LA
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
1
2 2
Unit arrangement
DS
VCB
VCB
VCB
2×CT
2×CT
2×CT
2×VT
3×LA
ZCT ZCT
VCB
VCB
2×CT
2×CT
ZCT ZCT
1 2 2
Section viewJEM1425-CWIEC298-Cubicle Type
Dwg.No. ① ②
Specifications Dimensions
g 3 units typeSkeleton
3
4 4
DS
VCB
2×CT
VCB
2×CT
2×VT
3×LA
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
Unit arrangement
2×CT
2×CT
VCB
VCB
VCB
ZCT ZCT ZCT ZCT
3 4 4
DS
VCB
2×CT
2×CT
2×VT
3×LA
2×CT
2×CT
VCB
VCB
VCB
ZCT ZCT
2×CT
Section viewJEM1425-CWIEC298-Cubicle Type
Dwg.No. ③ ④
VCB Rated Current≦600A
Up
to
25k
A
Up
to
20k
A
7 8
Substations
g 3.6/7.2kV
VCB
VCB
2×VT
3×LA
2×CT
2×CT
2×CT
3×CT
3øTr
VCB
2×VT
3×LA
2×CT3×CT
3øTr
VCB
VCB
VCB
ZCT
2×CT3×EVT
VCB
ZCT
2×CT
VCB
ZCT
2×CT
2×CT
VCB
ZCT
3×EVT
5
8 86
5
7
G
Skeleton
Unit arrangement 8 5 6 7 5 8
3×LA
2×CT2×VT 3×EVT
VCB
VCB
2×CT
VCB
2×CT
VCB
2×CT3×CT
ZCT
VCB
2×CT
ZCTZCT
2×CT
VCB
VCB
2×CT
ZCT
3×LA
2×VT
VCB
2×CT3×CT
3×EVT
g 12kVG
3×LA
VCB
VCB
2×VT
2×CT
2×CT
2×CT
3×CT
3øTr 3øTr
VCB
2×VT
2×CT3×CT
VCB
VCB
VCB
ZCT
2×CT3×EVT
VCB
ZCT
2×CT
3×LAVCB
ZCT
2×CT
VCB
ZCT
2×CT
VCB
ZCT
2×CT
2×CT
VCB
ZCT
3×EVT
9
13 1310 1011 12
9
Skeleton
Unit arrangement
3×LA
3×LA
VCB
2×CT3×CT
13 1310 1011 129 9
2×CT2×VT
2×CT
VCB
ZCT
3×EVT
3×EVT2×CT
VCB
VCB
2×CT
ZCT ZCT
2×CT
VCB
VCB
2×CT
ZCT
VCB
2×CT
ZCT
VCB
2×CT
ZCT
VCB
VCB
2×CT3×CT
2×VT
Section View : JEM1425-MW, IEC 298-Metal Clad Type.
g 3.6/7.2kVDwg.No.
Up to 25kA 31.5/40kA
5
6
7
8
g 12kVDwg.No.
Up to 25kA 31.5/40kA
9
10
11
12
13
9 10
F-MPC60 (Fuji Multiple Protector and Controller; option)
1. Product
Name Function
Protection Measurement (Monitor) Control
Bus unit OV, UV, OVG 3V, Vo, Hz –
Feeder unit HOC, OC, DG(67), SP(46), RV(47) 3A, kW, kvar, kWh, cos, Ao C. B ON/OFF
Receiving unit HOC, OC, OCG, OV, UV, SP(46), RV(47) 3A, 3V, Hz, cos, kW, kvar, kWh, Vo, Ao, kvarh C. B ON/OFF
Other Monitor Functions : Fault current /voltage. Running hours/times etc.Option : T-link communication system.
2. Indication and operation function
①Monitor LEDs
②Fault code table
③ Indicator (7seg LEDs)
④LEDs
⑤Sheet sw
Remote-local
C. B On-Off
N99-2332-1
Front panel (Shows feeder unit)
NO. Name Bus Unit / Feeder receiving unit
① Monitor LED POWER Indicates that power supply is ready
RUN Indicates that the unit is normal running
ALARM Indicates that error occurs (by self-diagnosis)
FAULT Indicates fault (ex. Overcurrent, Earthfault, Over/Undervoltage etc.)
PLURAL F. Indicates that plural fault occurs
② Fault code table Shows fault code
③ Indicator (7seg LEDs) CODE Indicates Fault-code, Setting-code, Historical-code and Test-code
DATA Indicates measurement, Fault, Setting-data and historical-data
④ LEDs Shows unit of measurement
⑤ Sheet switches ᐯ ᐱ Pushbutton for display (No.③ etc.) selectionSET NET RESET Pushbutton for set. reset
3. Protection function
Function Setting ranges
Overcurrent instantaneous
Current : 2 to 16 Multiplied, LockTime : 0 and 0.2~2s
Overcurrent Characteristic curves : SI/EI/l2t OverloadCurrent : 20~240%, Lock Time : 0.5 to 20 Multiplied
Ground direction(DG)(EVT or ZPC)
Current : 0.1~1.0A(ZCT) , LockVoltage : 2.5~40%Maximum sensitivity angle : 30˚,45˚,60˚ (leading)Time : 0.1~3.0s
Over voltage Voltage : 110~140V, Lock, Time : 0~5s
Under voltage Voltage : 50~90V, Lock, Time : 0~5s
Ground fault (OVG) Voltage : 2.5~40%, Lock, Time : 0~30s
Ground fault (OCG) Current : 0.1~1.0A (ZCT), Lock, Time : 0.1~3.0s
Single phase (46) Unbalanced current ratio 50~80%, Lock
Reverse voltage (47) Reversevoltage, Lock
4. Connection(Shows example of feeder unit)
P
N
T.Tm
T.Tm
PT
T.Tm
2×CT
ZCT
RUVWMN
ST
CB
From BUS UNIT Vo
INST
3A
DG SP RV
F-MPC60
OC (I2t, Sl, El)
kW
TCSON
OC
cos A0kvar kWh
OF
FTr
ip
DC
arar
m
DC100V/110V
TE
ST
CC TC X2CB X2 T
Rem
ote-
ON
Rem
ote-
OF
F
Trip
1
Trip
2A
ux, i
nputCB
Overcurrent curves
L=10
L=10
L=10
Input current (100%=Setting current)
100
0.1
1
10
100
1000
200 500 1000 2000 [%]
Ope
ratin
g tim
e [s
]
Sl
El
l2t
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, JapanPhone : (03)5435-7111
⑫ーi
Internet address : http://www.fujielectric.co.jpInformation in this catalog is subject to change without notice.
Printed on recycled paper
2013-3(C2013/G1998)KO-H/CTP3FOLS Printed in Japan
Application Guide of Surge AbsorberThe high surge voltage by the VCB that injures the insulation of the machines and apparatus is generated under certain specific conditions. The necessity of surge protection depends on the dielectric strength of the device used as a load.The application guide given below is based on the results of switching surge tests. When the dielectric strength of the device is low, use of a surge absorber is recommended.
g Surge absorber application guide
VoltegeLoad 3.3kV 6.6kV 11kV
Rotating machine
C-R suppressor
C-R suppressor
C-R suppressor
Molded transformer*1
– *2,*3
(BIL≧45kV)– *2,*3
(BIL≧60kV) *3C-R suppressor or gapless arrester (BIL≧55kV)
Oil-immersed transformer*1
– *2,*3
(BIL≧45kV)– *2,*3
(BIL≧60kV)– *2,*3
(BIL≧90kV)
Dry-type transformer*1
*3C-R suppressor (BIL≧25kV)
*3C-R suppressor (BIL≧35kV)
*3C-R suppressor or gapless arrester (BIL≧55kV)
Notes : Protection device required – : Protection device not required *1 : The withstand voltages (impulse) of transformer must
exceed the values listed above. *2 : When interrupting a magnetizing inrush current, it is
recommended that a protection device be used. A standard lightning arrester is sufficient.
*3 : Semiconductor device must be provided with suitable protection devices when a semiconductor is installed on the load side of transformer, since a surge on the low voltage side will also cause a voltage appear on the load side, depending on the turns ratio.
Ordering SpecificationsWhen placing your valued order, please specify the following1) Single line diagram of electrical equipments (plants) for
planning2) Rated operational voltage, frequency, normal current, short-
time withstand current, (i.e., 6.6kV 50Hz, 1250A, 31.5kA at 1 sec.) and kind of loads, their ratings their circuit numbers (i.e. 5-motors 6.6kV, 500kW, 2-transformer 6.6kV/420V, 1500kVA)
3) Kind, size, core and quantity per phase of cable at each circuit4) Rated control circuit (or supply) voltage and AC or DC5) Normal or special service conditions and their detail6) Requirement of transportation and installation7) Protection and control system8) Requirement from standard optional extras