HIGH VOLTAGE LINK BOX - TE Connectivity: Connectors & · PDF file · 2017-01-14HIGH...

2
HIGH VOLTAGE LINK BOX FOR HIGH VOLTAGE CABLE SYSTEMS UP TO 245 kV • Stainless steel box • Easy installation of non- compression connection • Install on wall or underground • 1-phase and 3-phase boxes available • With or without ZnO surge arresters (SVL) • With or without removable links KEY FEATURES TE Connectivity’s (TE) high voltage link boxes are used for earthing and bonding cable sheaths of single core cables to eliminate or reduce induced voltages and circulating currents. Single core cables in operation carry alternating currents and induced voltage in the metallic sheath of the cable. These currents may cause, depending on different sheath bonding, circulating currents flowing in the cable sheath which reduce the transmission capacity of the cable and cause an additional heating. ENERGY /// HIGH VOLTAGE LINK BOX Customers can count on consistent, high quality products, driven by TE’s proven innovation and backed by our extraordinary customer support.

Transcript of HIGH VOLTAGE LINK BOX - TE Connectivity: Connectors & · PDF file · 2017-01-14HIGH...

Page 1: HIGH VOLTAGE LINK BOX - TE Connectivity: Connectors & · PDF file · 2017-01-14HIGH VOLTAGE LINK BOX FOR HIGH VOLTAGE CABLE SYSTEMS UP TO 245 kV • Stainless steel box • Easy installation

HIGH VOLTAGE LINK BOXFOR HIGH VOLTAGE CABLE SYSTEMS UP TO 245 kV

• Stainless steel box

• Easy installation of non-compression connection

• Install on wall or underground

• 1-phase and 3-phase boxes available

• With or without ZnO surge arresters (SVL)

• With or without removable links

KEY FEATURES TE Connectivity’s (TE) high voltage link boxes are used for earthing and bonding cable sheaths of single core cables to eliminate or reduce induced voltages and circulating currents.

Single core cables in operation carry alternating currents and induced voltage in the metallic sheath of the cable. These currents may cause, depending on different sheath bonding, circulating currents flowing in the cable sheath which reduce the transmission capacity of the cable and cause an additional heating.

ENERGY /// HIGH VOLTAGE LINK BOX

Customers can count on consistent, high quality products, driven by TE’s proven innovation and backed by our extraordinary customer support.

Page 2: HIGH VOLTAGE LINK BOX - TE Connectivity: Connectors & · PDF file · 2017-01-14HIGH VOLTAGE LINK BOX FOR HIGH VOLTAGE CABLE SYSTEMS UP TO 245 kV • Stainless steel box • Easy installation

High Voltage Link Box

te.com/energy©2014 TE Connectivity Ltd. family of companies. All Rights Reserved. EPP-1655-10/14

Raychem, TE Connectivity and TE connectivity (logo) are trademarks. Other logos, product and/or company names might be trademarks of their respective owners. While TE has made every reasonable effort to ensure the accuracy of the information in this brochure, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications are subject to change without notice. Consult TE for the latest dimensions and design specifications.

ENERGY /// HIGH VOLTAGE LINK BOX

PRODUCT SELECTION INFORMATIONDescription 1/3 Phase SVL Earthing

OptionConfiguration Cable Size Application Voltage

HVLB-E-S-0-1-1 single phase direct earthing 1 in, 1 out 300 mm2 66 kV, 110 kV, 220 kV

HVLB-E-S-2-1-1 single phase SVL protection 1 in, 1 out 300 mm2 110 kV

HVLB-E-S-0-3-1 three phase direct earthing 3 in, 1 out 300 mm2 66 kV, 110 kV, 220 kV

HVLB-E-S-2-3-1 three phase SVL protection 3 in, 1 out 300 mm2 110 kV

HVLB-C-C-2-3-1 three phase SVL protection 3 in, 1 out 300 mm2 110 kV

HVLB-E-S-3-3-1 three phase SVL protection 3 in, 1 out 400 mm2 220 kV

HVLB-C-C-3-3-1 three phase SVL protection 3 in, 1 out 400 mm2 220 kV

ORDERING INFORMATIONDescription Part Number

HVLB-E-S-0-1-1 2197360-1

HVLB-E-S-2-1-1 2197363-1

HVLB-E-S-0-3-1 2197295-1

HVLB-E-S-2-3-1 2197296-1

HVLB-C-C-2-3-1 2197297-1

HVLB-E-S-3-3-1 2197296-2

HVLB-C-C-3-3-1 2197297-2

FOR MORE INFORMATION: TE Technical Support Centers

USA: + 1 800 327 6996France: + 33 380 583 200UK: + 44 0870 870 7500Germany: + 49 896 089 903Spain: + 34 916 630 400Benelux: + 32 16 351 731Canada: + 1 (905) 475-6222Mexico: + 52 (0) 55-1106-0800Latin/S. America: + 54 (0) 11-4733-2200China: + 86 (0) 400-820-6015