High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B),...

44
BARNSTEAD THERMOLYNE CORPORATION High Temperature Tube Furnaces OPERATION MANUAL AND PARTS LIST Series 705 & 706 1500 ° C 1700 ° C F54530CM F59330CM Automatic F54538CM F59338CM Automatic F54540CM F59340CM Programmable F54548CM F59348CM Programmable F59348CM-75 Multi-Programmable F59340CM-75 Multi-Programmable LT705X1 10/26/98

Transcript of High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B),...

Page 1: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

1

BARNSTEAD THERMOLYNE CORPORATION

High TemperatureTube Furnaces

OPERATION MANUALAND PARTS LISTSeries 705 & 706

1500°C 1700°CF54530CM F59330CM AutomaticF54538CM F59338CM AutomaticF54540CM F59340CM ProgrammableF54548CM F59348CM ProgrammableF59348CM-75 Multi-ProgrammableF59340CM-75 Multi-Programmable

LT705X1 10/26/98

Page 2: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

2

Safety Information .............................................................................................................................................. 3Alert Signals ................................................................................................................................................ 3Warnings ...................................................................................................................................................... 3

Introduction ........................................................................................................................................................ 5Intended Use ............................................................................................................................................... 5Principles of Operation ................................................................................................................................ 5Two Types of Controllers ............................................................................................................................. 6

General Specifications ....................................................................................................................................... 8F5400 Tube Furnace ................................................................................................................................... 8F59300 Tube Furnace ................................................................................................................................. 9

Unpacking ........................................................................................................................................................ 10Installation ........................................................................................................................................................ 11

Site Selection ............................................................................................................................................. 11Furnace Connection .................................................................................................................................. 11

General Operation of Furnace ......................................................................................................................... 12Circuit Breaker ........................................................................................................................................... 12Fans ........................................................................................................................................................... 12Chamber Opening ..................................................................................................................................... 12Chamber Repositioning ............................................................................................................................. 12Installing Tubes .......................................................................................................................................... 13

Tube bracket ....................................................................................................................................... 13Automatic Control Models ......................................................................................................................... 14Control Parameters ................................................................................................................................... 14Operation ................................................................................................................................................... 18Single Set Point ......................................................................................................................................... 18Program Ramp Rate .................................................................................................................................. 19Program Ramp Reset ................................................................................................................................ 19SAT (Self Adaptive Tuning) ........................................................................................................................ 19Programmable Models .............................................................................................................................. 21Control Parameters ................................................................................................................................... 21

Operation ............................................................................................................................................ 26Single Set Point ................................................................................................................................... 26SAT (Self Adaptive Tuning) ................................................................................................................. 27Programming Controller ...................................................................................................................... 27Multi-Programmable Controller Program Entry ................................................................................... 27Program Entry (all models) ................................................................................................................. 29Holdback ............................................................................................................................................. 30Parameter Change While Running ..................................................................................................... 30Loop Count .......................................................................................................................................... 31Program Hold ...................................................................................................................................... 31Program Reset .................................................................................................................................... 31

Furnace Loading .............................................................................................................................................. 32Furnace Atmospheres ...................................................................................................................................... 33Preventive Maintenance................................................................................................................................... 34Troubleshooting Guide ..................................................................................................................................... 36Maintenance and Servicing .............................................................................................................................. 37

To Replace a Heating Element (Refer to Figure 1) .................................................................................... 38To Replace Thermocouple ......................................................................................................................... 39

Replacement Parts ........................................................................................................................................... 40Figure 1 ............................................................................................................................................................ 41Element Replacement ...................................................................................................................................... 41Wiring Diagram ................................................................................................................................................ 42Ordering Procedures ........................................................................................................................................ 43One Year Limited Warranty .............................................................................................................................. 44

Table of Contents

Page 3: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

3

Your Thermolyne High Temperature Tube Furnace hasbeen designed with function, reliability, and safety inmind. It is the user’s responsibility to install it in conform-ance with local electrical codes. For safe operation,please pay attention to the alert signals throughout themanual.

This manual contains important operating and safetyinformation. The user must carefully read and understandthe contents of this manual prior to the use of this equip-ment.

WarningsTo avoid electrical shock:

1. This furnace must be installed by a competent,qualified electrician who ensures compatibilityamong furnace specification, power source andground code requirements.

2. Disconnect from the power supply prior tomaintenance and servicing.

To avoid personal injury:1. To avoid burns, do not touch or stand directly in

front of the chamber ends without wearing aheat resistant face shield, gloves and apron.

2. To avoid eye damage, do not operate or cleanfurnace without wearing proper eye protection.

3. To avoid fire, do not place combustible materi-als where exposed to heat from open chamberends.

4. To avoid burns, do not open heating chamber orreplace tube unless unit is cooled to ambienttemperature.

5. Do not use in the presence of flammable orcombustible materials; fire or explosion mayresult. This device contains components whichmay ignite such materials.

6. Refer servicing to qualified personnel.

Safety Information

WarningWarnings alert you to a possibility ofpersonal injury.

CautionCautions alert you to a possibility ofdamage to the equipment.

NoteNotes alert you to pertinent facts andconditions.

Hot SurfaceHot surfaces alert you to a possibility ofpersonal injury if you come in contact witha surface during use or for a period oftime after use.

Alert Signals

Page 4: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

4

WarningThis warning is presented for compliance with CaliforniaProposition 65 and other regulatory agencies and onlyapplies to the insulation in this product. This productcontains refractory ceramic, refractory ceramic fiber orfiberglass insulation, which can produce respirable dust orfibers during disassembly. Dust or fibers can cause irritationand can aggravate preexisting respiratory diseases.Refractory ceramic and refractory ceramic fibers (afterreaching 1000°C) contain crystalline silica, which can causelung damage (silicosis). The International Agency forResearch on Cancer (IARC) has classified refractoryceramic fiber and fiberglass as possibly carcinogenic(Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1).

The insulating materials can be located in the door, thehearth collar, in the chamber of the product or under the hotplate top. Tests performed by the manufacturer indicate thatthere is no risk of exposure to dust or respirable fibersresulting from operation of this product under normalconditions. However, there may be a risk of exposure torespirable dust or fibers when repairing or maintaining theinsulating materials, or when otherwise disturbing them in amanner which causes release of dust or fibers. By usingproper handling procedures and protective equipment youcan work safely with these insulating materials and mini-mize any exposure. Refer to the appropriate Material SafetyData Sheets (MSDS) for information regarding properhandling and recommended protective equipment. Foradditional MSDS copies, or additional information concern-ing the handling of refractory ceramic products, pleasecontact the Customer Service Department atBarnstead|Thermolyne Corporation at 1-800-553-0039.I

SAFETY INFORMATION

Page 5: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

5

Intended UseThe type F54500 (1500°C) & type F59300 (1700°C) aregeneral purpose laboratory tube furnaces intended forapplications requiring temperatures up to 1500°C or1700°C.

Principles of OperationThe chamber section is heated by eight Super Kanthal 33type heating elements suspended in a chamber made ofa special very high temperature refractory fiber.

This high temperature refractory fiber is in the form ofblocks which line the inside of the chamber. Because ofthe stresses caused by the extremely high temperatureoperation, these blocks will show some surface cracking.This cracking is not detrimental to the operation of thefurnace.

A precious metal type B thermocouple senses thetemperature in the chamber and transmits this informa-tion to the temperature control as a very small voltage.

The control section consists of a temperature controller, acurrent controller, a transformer, a contactor (relay), acircuit breaker, and a pilot light.

The temperature controller senses the furnace tempera-ture via the thermocouple and adjusts power to theheating elements by means of the current controller.

The current controller controls power to the heatingelements by limiting the magnitude of the current (ratherthan turning the power completely on or off). This is thepreferred method of controlling power to molybdenumdisilicide heating elements.

The transformer supplies the proper voltage to theheating elements.

The contactor removes power from the heating elementsif the furnace temperature equals or exceeds the highlimit set point of the controller. The circuit breaker is usedto turn the furnace on and off and also protects the powerline in the event that the furnace draws too much current.

Introduction

Page 6: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

6

The pilot light indicates that the circuit breaker is ON andthat the controller is being supplied with power.

Two fans in the furnace provide forced air cooling.

Two Types of ControllersThe automatic (single set point) digital models enables theuser to bring the furnace up to a preset point and hold thetemperature.

The programmable digital models enable the operator toprogram up to 8 ramp segments (heat up rate) and 8 dwellsegments (soak) for applications that require time andtemperature relationship.

INTRODUCTION

NoteThe fans operate continuously, evenwhen the circuit breaker is OFF, toassure that the control section and theterminals of the heating elements arekept cool at all times, otherwise re-sidual heat from the furnace chambercan cause overheating after thefurnace is turned off.

CautionDo not completely remove power fromthe furnace until furnace temperaturefalls below 500°C.

Typical profile for programmable models. Other profiles may be formed.

Page 7: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

7

INTRODUCTION

Programmable Control and Automatic Control

Current Control

Page 8: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

8

F5400 Tube Furnace

Dimensions

OverallF54540CM F54530CM F54548CM F54538CM

Width: 22.74 (57.8) 22.75 (57.8) 22.75 (57.8) 22.75 (57.8)Height: 28.5 (72.4) 28.5 (72.4) 28.5 (72.4) 28.5 (72.4)Depth: 22 (55.9) 22 (55.9) 22 (55.9) 22 (55.9)

ChamberWidth: 3” dia. max. 3” dia. max. 3” dia. max. 3” dia. max.Depth: 20” 20” 20” 20”

Weight (in Lbs. (kg)160 (72.6) 160 (72.6) 160 (72.6) 160 (72.6)

ElectricalVolts 240 240 208 208Amps 40 40 40 40Watts 3500 3500 3500 3500Freq. 50/60 50/60 50/60 50/60Phase 1 1 1 1

Operating Temp Range800°C -1500°C 800°C -1500°C 800°C -1500°C 800°C -1500°C

General Specifications

Page 9: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

9

F59300 Tube Furnace

Dimensions

OverallF59340CM & F59340CM-75 F59330CM F59348CM &F59348CM-75 F59338CM

Width: 20.5 (52.1) 20.5 (52.1) 20.5 (52.1) 22.75 (57.8)Height: 28.5 (72.4) 28.5 (72.4) 28.5 (72.4) 28.5 (72.4)Depth: 22 (55.9) 22 (55.9) 22 (55.9) 22 (55.9)ChamberWidth: 3” dia. max. 3” dia. max. 3” dia. max. 3” dia. max.Depth: 20” 20” 20” 20”

Weight (in Lbs. (kg)160 (72.6) 160 (72.6) 160 (72.6) 160 (72.6)

ElectricalVolts 240 240 208 208Amps 40 40 40 40Watts 3500 3500 3500 3500Freq. 50/60 50/60 50/60 50/60Phase 1 1 1 1

Operating Temp Range800°C -1700°C 800°C -1700°C 800°C -1700°C 800°C -1700°C

GENERAL SPECIFICATIONS

Page 10: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

10

Visually check for any physical damage to the shippingcontainer. Inspect the equipment surfaces that are adjacentto any damaged area. Open the furnace chamber andremove packing material from inside the furnace chamber.Vacuum the chamber prior to use to remove the insulationdust due to shipment.

Packaged with the furnace are four ceramic sleeves: 2 - 2"(dia.) and 2 - 1" (dia.) collars.

Retain the original packaging material if reshipment isforeseen or required.

The tube furnaces do not come with a power cord becausecurrent requirements are too great to be handled by ordi-nary power cords and standard wall supply.

Unpacking

Page 11: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

11

Site SelectionInstall furnace on a sturdy surface and allow space forventilation.

The electrical specifications are located on the specifica-tion plate on the back of the furnace. Consult Barnstead/Thermolyne if your electrical service is different thanthose listed on the specification plate. Prior to connectingyour tube furnace to your electrical supply, be sure thefront circuit breaker is in the OFF position.

Furnace ConnectionRemove cover plate for access to the electrical connec-tions. Connect power to the three terminals found behindthis plate; one side of the 208 or 240 volt service to thetop terminal, L1; the other side of the 208 or 240 voltservice to the bottom terminal, L2, and the ground(usually green wire) to the center terminal marked GND.For 220 volt service, connect the neutral to the topterminal (marked L1); the 220 volt line to the bottomterminal, L2, and the ground to the center terminalmarked GND. Power is brought to the furnace through anappropriate conduit system, through the hole in the backpanel at the bottom left rear of the furnace, and con-nected as described. Be sure to observe local wiringcodes in connecting.

Installation

CautionBe sure ambient temperature does notexceed 104°F (40°C). Ambients abovethis level may result in damage to thecontroller. Allow at least six inches ofspace between the furnace and anyvertical surface. This permits the heatfrom furnace case to escape so as not tocreate a possible fire hazard.

NoteIt is recommended to use a dedicatedpower source to furnace in order tominimize possibility of line interference.

WarningTo avoid electrical shock, this furnacemust be installed by a competent, quali-fied electrician who ensures compatibilityamong furnace specification, powersource and ground code requirements.

CautionFor supply connections, use 8 AWG orlarger wires suitable for at least 90°C.Failure to observe this caution couldresult in damage to furnace.

Page 12: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

12

OBSERVE THESE WARNINGS BEFORE OPERATINGYOUR FURNACE:

Circuit BreakerA double pole circuit breaker is located at the right side ofthe control section. It serves to turn power ON and OFFand to protect the electrical circuit.

FansThe fans, located in the rear of the heating section, will runcontinuously as long as power is supplied to the furnace,even when the furnace panel circuit breaker is OFF. Thisserves to remove residual heat after the furnace is turnedOFF so the heat does not cause damage to sensitiveelectronic components.

Chamber OpeningThe heating chamber is of split tube design to allow accessto inside of chamber. While supporting front half of cham-ber, unhook latches and move front half towards controlsection. To close chamber, move front chamber half to-wards rear half and relatch.

Chamber Repositioning (OnlyOn F54530CM, F54538CM,F54540CM, F54548CM):Due to the unique design, the chamber can be used in thehorizontal, angular or vertical position. To reposition cham-ber, simply unlock lever and move chamber to the desiredposition, then relock lever to hold furnace chamber intoposition.

General Operation of Furnace

WarningDo not use in the presence of flam-mable or combustible materials; fire orexplosion may result. This devicecontains components which may ignitesuch materials. To avoid burns, do nottouch or stand directly in front of thechamber ends without wearing a heatresistant face shield, gloves and apron.To avoid eye damage, do not operateor clean furnace without wearing propereye protection. To avoid fire, do notplace combustible materials whereexposed to heat from open chamberends. To avoid burns, do not openheating chamber or replace tube unlessunit is cooled to ambient temperature.

CautionIf the power supply must be discon-nected from the furnace at any time, besure the chamber temperature is 500°Cor less before doing so.

NoteTo prevent chamber damage, remem-ber to support chamber with one handwhen removing the chamber fromvertical or angular position, to thehorizontal position.

Page 13: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

13

Installing TubesThe furnace is supplied with (2) 3” dia. collars, (2) 2" dia.collars and (2) 1" dia. collars. The 3" dia. collars areinstalled in the furnace from the factory.

To install 1" dia. or 2” dia. tubes, simply open furnacechamber and slide appropriate sized ceramic collars overtube. Insert tube and ceramic collars in front half ofchamber. Slowly, move front chamber half towards rearhalf and relatch.

Tube bracketSince the chamber can be moved to the vertical position,a stop is needed to keep the tube secured in the cham-ber. Whenever a 2” dia. or a 1" dia. tube is used, be sureto adjust the stop. The stop is located at the left end ofchamber and is secured with two screws. One adjustablebracket is supplied with the furnace.

GENERAL OPERATION OF FURNACE

Page 14: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

14

(Models F54530CM, F54538CM,F59330CM, F59338CM)This furnace controller consists of a microprocessor basedthree-mode (Proportional, Integral, Derivative), program-mable control with overtemperature protection and appro-priate output switching devices to control the furnace. Thedigital readout continuously displays chamber (upperdisplay) and setpoint (lower display) temperatures unlessthe scroll button is depressed.

If the scroll button is depressed and released, the lowerdisplay will indicate output power (OP) or setpoint (SP).This is referred to as the “short scroll”. Continued singlestep action of scroll button will cause lower display toalternate between setpoint (SP) and output power (OP).

To enter the main scroll list (list of all controller parametersthat are accessed through front keyboard), the scroll buttonshould be held depressed. “PR” (program ramp rate willappear). To progress through the parameter list, the scrollbutton must first be released, subsequent single stepdepression will advance you through the list. Rapid pro-gression through the parameter list is achieved by holdingthe scroll button depressed.

Control ParametersTo be sure the temperature control parameter values havenot been altered during shipment, follow the subsequentprocedures:

1. Switch the power source to the unit “ON”.

2. Switch the “ON/OFF” front circuit breaker switchto “ON”. The digital display should be displayingchamber (upper display) and setpoint “sp” (lowerdisplay) temperatures

3. Depress and hold the “DOWN” push button untilthe setpoint (lower) display reads twenty.

4. Verify that the proper parameter values are stillloaded into the controller’s memory by performingthe following procedure:

Automatic Control Models

NoteWhen performing the operationalcheck, it is important that the setpointbe set at twenty so that the furnace isnot heating during the check outprocedures.

NoteIf you depress and release either the“scroll”, “up”, or “down” push buttonsand more than 8 seconds elapsebefore the buttons are used again, thedisplay screen will automatically switchback to displaying setpoint tempera-ture. If this happens, you will have tostep through each parameter until youreach the point at which the interrup-tion occurred. The parameter valuesyou checked earlier, however, will notbe lost or altered.

Page 15: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

15

• Depress and hold scroll button until “PR” appearson lower display. “PR” = program ramp rate whichis the rate of heat increase or decrease in °C/minute. Pushing the up or down button will givecurrent setting of this ramp. Setting will indicate“1.” If it does not, depress down button until “1” isdisplayed.

• Depress and release scroll button, “SP1” will bedisplayed. SP1 = set point one which indicatescurrent set point. Push up or down button. Settingwill be “20.” If it is not, depress down button until“20” is displayed.

• Depress and release scroll button, “SP2” will bedisplayed. Setpoint two = is not configured intocontrol and is nonfunctional. Push up or downbutton. Setting will be “20.” If it is not, depressdown button until “20” is displayed.

• Depress and release scroll button, “ST” will bedisplayed. ST = Self Tune automatically loads PIDvalues on initial start up. This function does nothave a value, it is either ON or OFF. (See FurnaceOperation for function of Self Tune).

• Depress and release scroll button, “AT” will bedisplayed. AT = Adaptive Tune analyzes andinputs optimum PID values when temperature hasreached set point, or “OFF.” (See Furnace Opera-tion for function of Adaptive Tune).

• Depress and release scroll button, “SAT” will bedisplayed. SAT = Self Adaptive Tune whenengaged starts controller off in self-tune modethen automatically switches to Adaptive Tune(AT). This function does not have a value, it iseither “ON” or “OFF” (See Furnace Operation forfunction of Adaptive Tune).

• Depress and release scroll button, “ATR” will bedisplayed. ATR = Adaptive Tune Band settingdetermines the operational band width of theadaptive tuning function. Self-tuning automaticallydetermines this setting.

NoteOnce the desired parameter has beenselected, depressing either the raise orlower button will cause the parameter tobe replaced with the new value. At thispoint, the “top dot” of the least significantdigit of the secondary display will flash onand off. Any further use of up or downbuttons will change parameter value. Inall cases, the value shown on the displayis the current working value of thatparameter.

NoteThermolyne recommends that you set thevalue either at maximum operatingtemperature of the furnace (1500°C) TypeF54500 & (1700°C) Type F59300 or avalue of 20 degrees above your workingtemperature if you desire to provideprotection for your workload. Push up ordown button, (1500°C) Type F54500 or(1700°C) Type F59300 should be dis-played, if it is not, depress up button until1500°C or 1700°C is displayed.

AUTOMATIC CONTROL MODELS

Page 16: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

16

• Depress and release scroll button, “AL1” will bedisplayed. AL1 = Alarm 1 is a full scale alarmwhich protects load and furnace when tempera-ture exceeds preset value. Furnace will controltemperature at the preset temperature value, it willnot shut off furnace.

• Depress and release scroll button, (Pb) will bedisplayed. Push up or down button; proportionalband setting will be 60.

• Depress and release scroll button, (+i) will bedisplayed. Push up or down button. Integralsetting will be 300.

• Depress and release scroll button, (+d) will bedisplayed. Push up or down button. Derivativesetting should be 60.

• The next two parameters, cutback low (cbl) andcutback high (cbh), are to aid the control inpreventing temperature overshoots and tempera-ture undershoots. The point from setpoint wherethe power starts “cutting back” is defined as thecutback value. Push up or down button, both cbhand cbl will be “OFF”. These values are alsoautomatically adjusted by the Self and Adaptivetuning features. These values cannot be changedby the user; the controller automatically installsoptimum cutback values when in Self and Adap-tive Tuning.

• Depress and release scroll button, HL will bedisplayed. HL = Output Power limits the averagemaximum power that is applied to the heatingelements.

• Depress and release up or down button, 100 willbe displayed. If “100” is not displayed, depress the“UP” or “DOWN” push button until the propervalue is displayed.

• Depress and release scroll button, Sbr will bedisplayed. Sbr is the power that is required toindicate if an open thermocouple condition exists.Push up or down button. 0.0 will be displayed.This parameter cannot be changed. If 0.0 is notdisplayed, contact Barnstead/Thermolyne.

AUTOMATIC CONTROL MODELS

NoteThe parameters proportional (PB),integral (+i) and derivative (+d) are forhigh accuracy control. Thermolyne hasinstalled values that will generally givegood results for most applications.These parameters cannot be changedby user. (See Self-Adaptive Tuning inFurnace Operation).

Note“OR” will be displayed if an openthermocouple condition exists.

Page 17: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

17

Mnemonic Parameter Specified UserValue Access

SP Setpoint 20 YesOP Output 0.0Pr Program ramp rate 1 YesSP 1 Main setpoint 20 YesSP 2 Second setpoint 20 YesSt Selftune - YesAt Adaptive tune - YesSAt Self-adaptive tune - YesATR Adaptive tune band - YesAL 1 Alarm 1 1500°C (1700°C)* YesPb Proportional band 60 Noti Integral time 300 Notd Derivative time 60 Nocb1 Cutback low OFF Nocbh Cutback high OFF NoHl Output 1 limit 100 NoSbr Sensor break power 0.0 No

* (1700°C) Type F59300

NoteTo change from °C to °F indication,contact Barnstead/Thermolyne .

AUTOMATIC CONTROL MODELS

Page 18: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

18

Operation

Single Set PointThe automatic control is used as a single setpoint controlwhich includes one ramp to setpoint capability. To use as asingle set point control, push up or down buttons to choosea specific temperature.

To operate the control:Turn power switch to the “ON” position.

Cycle Indicator: The amber cycle light will illuminate when-ever the power is being applied to the elements.

The setpoint temperature presently set in the control will beread out on the lower display.

To change this set point, depress the “UP” or “DOWN” pushbutton until the desired setpoint value is displayed, thenrelease the button.

At this point the furnace will begin to heat, if the new setpoint temperature you have chosen is higher than thepresent chamber temperature.

The upper display indicates actual furnace temperature.

AUTOMATIC CONTROL MODELS

CautionDo not operate furnace under 800°C.The element life is reduced whenoperating below this temperaturebecause the protective layer of silicaglass is not formed.

NoteTemperature setpoint or out power isindicated on lower display, singledepression of scroll button will alter-nate between these two parameters.This is referred to as the “short scroll”.The control will cause the furnacechamber to heat to the chosen tem-perature and hold it at this temperatureuntil you turn off the power switch orselect another temperature.

NoteInitial heat-up procedure:The elements may bend slightlysideways due to electromagneticforces generated between the elementshanks. To prevent this bending, heatthe furnace up to 1500°C and hold atthis temperature for 10 - 20 minutes.Then let furnace cool to ambienttemperature. (For 1700°C model heatfurnace to 1600°C & hold for 10-20minutes, then let furnace cool toambient temperature).

CautionRemember that whenever the powerswitch is turned “ON,” the furnace willbegin to heat to the setpoint tempera-ture that was previously set in. Thisvalue will remain unchanged for up to ayear without power being applied to thecontrol.

NoteThe two center push buttons areinactive and not used.

Page 19: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

19

Program Ramp RateIf you desire to ramp to the set temperature at a specifiedrate, depress scroll button until “PR” appears. (“PR” =program ramp rate, which is the rate of heat increase ordecrease in °C/minute). Depress up or down button togive current setting of ramp rate.Depress up or downbutton again until you achieve desired setting.

To start the temperature ramp, push the run button. Withthe run initiated, the program will commence and thelegend on the display will indicate “RAMP.” While a rampis running, the short scroll will contain three parameters.SP = setpoint. OP = output power. Time = time remainingin program ramp to reach setpoint temperature. Singledepression of the scroll button will allow you to view eachof these parameters.

When the program ramp has ended, an “E” will appearon the display.

Program Ramp ResetA running or finished program can be reset by depressingthe up and down buttons together.

When the reset has been enabled, the parts of thedisplay associated with programming will be extinguishedand the controller will operate as a single setpoint controlas described before.

SAT (Self Adaptive Tuning)The following procedure is instruction on how to initiatethe SAT (Self and Adaptive Tuning) feature. This featurestarts the controller in the Self Tune mode then automati-cally switches over to the Adaptive Tuning Feature. SelfTuning is a onetime function which permits the user toretune the instrument control parameters to suit newprocess conditions.

Adaptive tuning takes over when the self tune is com-pleted and continuously reevaluates tuning parameters.Adaptive tuning will then automatically install new valuesif a better response could have been attained.

AUTOMATIC CONTROL MODELS

NoteThe program ramp rate is designed toreduce the heat up rate or cooling ratethat the furnace normally exhibits. Whennot using this feature, the furnace willoperate at its maximum heating andcooling capability.

NoteWhen the program ramp has ended orhas been reset, the furnace will continueto maintain setpoint temperature. It willnot cool to ambient temperature unlesssetpoint is set to ambient temperature.

NoteThe automatic control has automatictuning features which install optimumtuning parameters to attain the besttemperature accuracy. No manual loadingof tuning parameters is needed.Thermolyne highly recommends usingthese features to provide the best tem-perature accuracy the controller canattain.

Page 20: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

20

Depress scroll button until SAT is displayed. Depress the upand down buttons simultaneously to start self tuning. The A-T indicator is then illuminated (upper right hand corner) andthe lower display indicates the setpoint at which the self-tune sequence will occur. The “SP” indicator will flash for 1minute, during which time the setpoint may be changed(use temperature setpoint that your application requires), ifit is required to retune at a new setpoint either above orbelow the process value indicated on the upper display. Atthe end of the minute, the “SP” indicator will stop flashing,indicating that the setpoint can no longer be changed. TheA-T indicator will start flashing and continue to flash untilthe self tune has completed. Once the self tune is com-pleted, adaptive tune takes over and the A-T indicator willremain illuminated.

To stop tuning function scroll until SAT is displayed andsimultaneously push up and down buttons.

AUTOMATIC CONTROL MODELS

NoteThe self tune and adaptive tunefeatures are inactive when a programramp (PR) is initiated.

Page 21: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

21

(F54540CM, F54548CM,F59340CM, F59348CM,F59340-75, F59348CM-75)This furnace controller consists of a microprocessorbased three-mode (Proportional, Integral, Derivative),programmable control with overtemperature protectionand appropriate output switching devices to control thefurnace. The digital readout continuously displays cham-ber (upper display) and setpoint (lower display) tempera-tures unless the scroll button is depressed.

If the scroll button is depressed and released, the lowerdisplay will indicate output power (OP) or setpoint (SP).This is referred to as the “short scroll.” Continued singlestep action of scroll button will cause lower display toalternate between setpoint (SP) and output power (OP).

To enter the main scroll list (list of all controller param-eters that are accessed through front keyboard), thescroll button should be held depressed. PR1 (programramp rate 1) will appear. To progress through the param-eter list, the scroll button must first be released, subse-quent single step depression will advance you throughthe list. Rapid progression through the parameter list isachieved by holding the scroll button depressed.

Control ParametersTo be sure the temperature control parameter valueshave not been altered during shipment, follow the subse-quent procedures:

1. Switch the power source to the unit “ON.”

2. Switch the “ON/OFF” front power switch to“ON.” The digital display should be displayingchamber (upper display) and setpoint “sp”(lower display) temperatures.

3. Depress and hold the “Down” push button untilthe setpoint (lower) display reads twenty.

Programmable Models

NoteWhen performing “operational check,” it isimportant that the setpoint be set attwenty so that the furnace is not heatingduring the check out procedures.

NoteIf you depress and release either the“scroll,” “up,” or “down” push buttons andmore than 8 seconds elapse before thebuttons are used again, the displayscreen will automatically switch back todisplaying setpoint temperature. If thishappens, you will have to step througheach parameter until you reach the pointat which the interruption occurred. Theparameter values you checked earlier,however, will not be lost or altered.

Page 22: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

22

4. Verify that the proper parameter values are stillloaded into the controller’s memory by perform-ing the following procedure:

• Depress and hold scroll button until “PR”appears on lower display. “PR1” = programramp rate which is the rate of heat increase ordecrease in °C/minute. Pushing the up or downbutton will give current setting of this ramp.Setting will indicate “END,” if it does not,depress down button until “END” is displayed.

• Depress and release scroll button, PL1 will bedisplayed. PL1 = program level is the tempera-ture to which the furnace needs to attain. Pushup or down button. Setting will indicate “20.” If itdoes not, depress up or down until “20” isdisplayed.

• Depress and release scroll button, PD1 will bedisplayed. PD1 = program dwell “1” is amountof time in minutes to hold PL1 program tem-perature level entered. Push up or down button.Setting will indicate “END”, if it is not, depressthe down button until “END” is displayed.

• Repeat the previous procedures used for PR1,PL1, PD1 for the remaining Program RampRates PR2 - PR8, Program Levels PL2 - PL8,and Program Dwells PD2 - PD8.

• After PD8 depress and release scroll button.“HB” will be displayed. HB = “Holdback” auto-matically places the programmer into “Hold” ifthe measured value deviates more than aspecified amount from programmer setpoint.When measured value reenters the holdbackband, the timing for the segment resumes.(Parameter is expressed in °C and only func-tions when running a program). Push up ordown button. Setting will be “OFF”, if it is not,depress down button until “OFF” is displayed.

PROGRAMMABLE MODELS

NoteMODELS F59340CM-75 &F59348CM-75: The procedure in Step4 varies slightly for these two models.To verify that the proper parametervalues are still loaded into thecontroller’s memory, depress and holdthe scroll button until “Pnr 1” is dis-played. Pnr is the program numberselected. By pushing the up or downbutton, you can select a program from1 to 15. Depress and release the scrollbutton; “Cnt n” will be displayed. Cnt isused to allow linking of programs. Cnt(continued) may be selected as “y”(yes) or “n” (no) by pushing the up ordown button. This parameter should beset to “Cnt n” (continued no). Theremaining parameters will follow thesequence listed in Step 4.

NoteOnce the desired parameter has beenselected, depressing either the raise orlower button will cause the parameterto be replaced with the new value. Atthis point, the “top dot” of the leastsignificant digit of the secondarydisplay will flash on and off. Any furtheruse of up or down buttons will changeparameter value. In all cases, the valueshown on the display is the currentworking value of that parameter.

Page 23: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

23

• Depress and release scroll button, “PLC” will bedisplayed. PLC = Program Loop Count is thenumber of times a program will be repeated.Push up or down button. Setting will be “1.” If itis not, depress down button until “1” is dis-played.

• Depress and release scroll button, “SP1” will bedisplayed. SP1 = setpoint one which indicatescurrent setpoint. Push up or down button.Setting will be “20.” If it is not, depress downbutton until “20” is displayed.

• Depress and release scroll button, “SP2” will bedisplayed. Setpoint two = is not configured intocontrol and is nonfunctional. Push up or downbutton. Setting will be “20.” If it is not, depressdown button until “20” is displayed.

• Depress and release scroll button, “ST” will bedisplayed. ST = Self Tune automatically loadsPID values on initial start up. This function doesnot have a value, it is either ON or OFF. (SeeFurnace Operation for function of Self Tune.

• Depress and release scroll button, “AT” will bedisplayed. AT = Adaptive Tune analyzes andinputs optimum PID values when temperaturehas reached setpoint. This function does nothave a value, it is either “ON” or “OFF.” (SeeFurnace Operation for function of AdaptiveTune.)

• Depress and release scroll button. SAT will bedisplayed. SAT = Self Adaptive Tune whenengaged starts controller off in self-tune modethen automatically switches to Adaptive Tune(AT). This function does not have a value, it iseither “ON” or “OFF”. (See Furnace Operationfor function of Adaptive Tune).

• Depress and release scroll button, “ATR” will bedisplayed. ATR = Adaptive Tune Band settingdetermines the operational band width of theadaptive tuning function. Self-tuning automati-cally determines this setting.

PROGRAMMABLE MODELS

Page 24: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

24

• Depress and release scroll button, AL1 will bedisplayed. AL1 = Alarm 1 is a full scale alarmwhich protects load and furnace when tempera-ture exceeds preset value. Furnace will controltemperature at the preset temperature value, itwill not shut off furnace.

• Depress and release scroll button, Pb will bedisplayed. Push up or down button proportionalband setting will be 60.

• Depress and release scroll button, (+i) will bedisplayed. Push up or down button. Integralsetting will be 300.

• Depress and release scroll button, (+d) will bedisplayed. Push up or down button. Derivativesetting should be 60.

• The next two parameters cutback low (cbl) andcutback high (cbh) are to aid the control in pre-venting temperature overshoots and temperatureundershoots. The point from setpoint where thepower starts “cutting back” is defined as thecutback value. Push up or down button; both cbhand cbl will be “OFF.” These values are alsoautomatically adjusted by the Self and Adaptivetuning features. These values cannot be changedby the user; the controller automatically installsoptimum cutback values when in Self and Adap-tive Tuning.

• Depress and release scroll button, HL will bedisplayed. HL = Output Power limits the averagemaximum power that is applied to the heatingelements.

• Depress and release up or down button, 100 willbe displayed. If “100” is not displayed, depressthe “UP” or “DOWN” push button until the propervalue is displayed.

• Depress and release scroll button, Sbr will bedisplayed. Sbr = is the percent of power that issupplied to the control output terminals if an openthermocouple condition exists. Push up or downbutton, 0.0 will be displayed. This parametercannot be changed. If 0.0 is not displayed, contactBarnstead|Thermolyne.

PROGRAMMABLE MODELS

NoteThermolyne recommends that you setthe value either at maximum operatingtemperature of the furnace (1500°C -Type F54500 or 1700°C -Type F59300)or a value of 20 degrees above yourworking temperature if you desire toprovide protection for your workload.Push up or down button, 1500°C or1700°C should be displayed, if it is not,depress up button until 1500°C or1700°C is displayed.

NoteThe next three parameters proportional(PB), integral (+i) and derivative (+d)are for high accuracy control.Thermolyne has installed values thatwill generally give good results for mostapplications. These parameters cannotbe changed by user. (See self-adaptivetuning in furnace operation).

NoteThe upper display will flash “OR” if anopen thermocouple condition exists.

NoteTo change from °C indication to °Findication, contactBarnstead|Thermolyne.

Page 25: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

25

Mnemonic Parameter Specified UserValue Access

SP Setpoint 20 YesOP Output 0.0**Prr 1-15 Program number Pnr 1 Yes**Cnt Continue Cnt n YesPr 1-8 Ramp 1 thru 8 End YesPL 1-8 Level 1 thru 8 20 YesPd 1-8 Dwell 1 thru 8 End YesHb Holdback OFF YesPLC Loop counts 1 YesSP 1 Main setpoint 20 YesSP 2 Second setpoint 20 YesSt Selftune - YesAt Adaptive tune - YesSAt Self-adaptive tune - YesATR Adaptive tune band - YesAL 1 Alarm 1 1500°C (1700°C)* YesPb Proportional band 60 Noti Integral time 300 Notd Derivative time 60 Nocb1 Cutback low OFF Nocbh Cutback high OFF NoHl Output 1 limit 100 NoSbr Sensor break power 0.0 No

* (1700°C) Type F59300** For Models F59340CM-75 and F59348CM-75

PROGRAMMABLE MODELS

NoteTo change from °C indication to °Findication, contact Barnstead|Thermolyne.

Page 26: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

26

Operation

Single Set PointThe programmable control can be used as a single setpointcontrol or as a programmable control. To use as a singleset point control simply push up or down buttons to choosea specific temperature.

1 . To operate the control:

Turn power switch to the “ON” position.

Cycle Indicator: The amber cycle light will illumi-nate whenever the power is being applied to theelements.

The setpoint temperature presently set in thecontrol will be read out on the lower display.

To change this set point, depress the “UP” or“DOWN” push button until the desired setpointvalue is displayed then release the button.

At this point the furnace will begin to heat if thenew set point temperature you have chosen ishigher than the present chamber temperature.

The upper display indicates actual furnacetemperature.

CautionDo not operate furnace under 800°C.The element life is reduced whenoperating below this temperaturebecause the protective layer of silicaglass is not formed.

NoteInitial start-up procedureThe elements may bend slightly side-ways due to electromagnetic forcegenerated between the elementshanks. To prevent this bending, heatthe furnace up to 1500°C and hold atthis temperature for 10-20 minutes,then let furnace cool to ambient tem-perature. (For 1700°C model heatfurnace to 1600°C & hold for 10-20minutes, then let furnace cool toambient temperature.)

NoteTemperature setpoint or output poweris indicated on lower display, singledepression of scroll button will alternatebetween these two parameters. Thecontrol will cause the furnace chamberto heat to the chosen temperature andhold it at this temperature until you turnoff the power switch or select anothertemperature.

CautionRemember that whenever the powerswitch is turned “ON,” the furnace willbegin to heat to the setpoint tempera-ture that was previously set in. Thisvalue will remain unchanged for up to ayear without power being applied to thecontrol.

NoteThe two center push buttons areinactive and not used.

PROGRAMMABLE MODELS

Page 27: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

27

SAT (Self Adaptive Tuning)The following procedure is instruction on how to initiatethe SAT (Self and Adaptive Tuning) feature. This featurestarts the controller in the Self Tune mode then automati-cally switches over to the Adaptive Tuning Feature. SelfTuning is a one-shot function which permits the user toretune the instrument control parameters to suit newprocess conditions.

Adaptive tuning takes over when the self tune is com-pleted and continuously reevaluates the tuned param-eters. Adaptive tuning will then automatically install newvalues if a better response could have been attained.

a. Depress scroll button until SAT is displayed.Depress the up and down buttons simulta-neously to start self tuning. The A-T indicator isthen illuminated (upper right hand corner) andthe lower display indicates the setpoint at whichthe self-tune sequence will occur. The “SP”indicator will flash for 1 minute, during whichtime the setpoint may be changed (use tem-perature setpoint that your application requires),if it is required to retune at a new setpoint eitherabove or below the process value indicated onthe upper display. At the end of the minute, the“SP” indicator will stop flashing, indicating thatthe setpoint can no longer be changed. The A-Tindicator will start flashing and continue to flashuntil the self tune has completed. Once the selftune is completed, adaptive tune takes over andthe A-T indicator will remain illuminated.

To stop tuning function scroll until SAT isdisplayed and simultaneously push up anddown buttons.

Programming ControllerTo run a program, first determine your ramp rate, dwelltimes, program levels. It is helpful to graph your programout for ease of loading program into controller. Observemaximum ramp rates (heat up time) on specificationsheet before programming in ramp rates.

NoteThe programmable control has automatictuning features which install optimumtuning parameters to give the besttemperature accuracy. No manual loadingof tuning parameters is needed.Thermolyne highly recommends usingthese features to provide the best tem-perature accuracy the controller canattain.

PROGRAMMABLE MODELS

NoteThe self-tune feature is inactive whilerunning a program. The adaptive tunefeature is active only in the dwell seg-ments of a program.

Page 28: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

28

A maximum of 8 ramp and 8 dwell segment combinationsare available, thus enabling eight different setpoint levels tobe achieved. Each ramp is programmed by specifying theprogram level (PL) and the required ramp rate (PR). Theprogrammer then automatically calculates the time that isrequired to attain the program level (PL) based on desiredramp rate (PR). Dwell segments (soak) then can be at-tached to each program level (PL) to hold that temperaturefor a specified amount of time.

Multi-Programmable Controller Program Entry(Models F59340CM-75 and F59348CM-75)The multi-programmable controller in these units providesup to 15 separate programs of 8 ramps and 8 dwells each.This controller also allows you to link programs together.These functions are governed by the controller’s first twoprogramming parameters, “Pnr” and Cnt.”

To Select Program NumberPush scroll button until “Pnr 1” is displayed. Push the up ordown button to select a program number from 1 to 15.

To Link Programs TogetherPush scroll button until “Cnt n” is displayed. Press andrelease the up and down buttons to switch between “Cnt y”(continue yes) and “Cnt n” (continue no). The effect ofselecting “Cnt y” is to continue the program to the nextprogram number. For example, if in program #3 you select“Cnt y,” when program #3 is complete, program #4 will runautomatically. Setting “Cnt y” in program #15 will initiatethe start of program #1 upon the completion of program#15. Each program will complete the selected number ofloops before continuing (see Loop Count).

These two parameters (“Pnr” and “Cnt”) are the only onesthat differ from the single program 8 ramp and 8 dwellcontrol. Program entry for the multi-programmable modelscontinues with the following instructions, which are appli-cable to both the multi-programmable and single program-mable models

PROGRAMMABLE MODELS

Page 29: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

29

Program Entry (all models)With the programmer not operating, indicated by thebottom right hand side of the display extinguished,depress scroll button until “PR1” is displayed. Push theup or down button to scroll to the desired value, which isdegrees per minute.

Scrolling down below zero will give three other options forthe ramp:

NONE — which will force the program to skip to the nextsegment;

END — which will cause the program to stop or restart ifloops remaining is not zero;

STEP — which will cause the program to jump to the nextlevel.

All other ramps in the program are set in a similar fashionby selecting “PR” followed by the relevant ramp number.

The level to which the first ramp is aiming is entered byscrolling through the main scroll list until “PL1” is dis-played. By pressing either the up or down button thepresent value of this level is indicated in display units.Using the up or down button will scroll the present valueto the new value required. All other levels in the programare set in a similar fashion by selecting “PL” followed bythe relevant number.

To set the dwell time for the first level scroll through themain scroll list until “Pd1” is displayed. Pressing the up ordown button will reveal the current value of time inminutes. Using the up or down button will scroll thepresent value to the new value required. Scrolling thisvalue downscale will allow a setting of “END.” A setting of“END” will terminate the program, or force it to restart ifloops remaining are not zero at the beginning of thatdwell.

All other dwells in the program can be set in a similarfashion by selecting “PD” followed by the relevant dwellnumber.

PROGRAMMABLE MODELS

NoteThe temperature control in these modelsis a programmable and automatic singleset point device. When a program hasended, the controller will maintain thechamber temperature at a value equal tothe last programmed level until theprogram is cancelled. When a program iscancelled, the controller will maintain thechamber temperature at a value equal tothe main set point (SP1 or SP). To cancela program, depress and release the “UP”and “DOWN” push buttons simulta-neously.

Page 30: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

30

Scrolling through the main scroll until the parameter “PLC”is displayed and then depressing the up or down button willreveal the present setting of the loop count. This is thenumber of times that the entered program will be repeatedbefore a continuous setpoint at the last level of the programis achieved. By pushing the up or down button the numberof loops can be set at any value from 1 to 999.

HoldbackScroll through the main scroll list until “HB” is displayed.Push the up or down button to reveal the current value ofholdback. The up or down button can now be depressed toscroll to the required value. Holdback is set in display unitsand represents the allowable excursion of measured valueaway from the current setpoint, either above or below,before the program is forced into hold. The program willremain in hold until the measured value comes withinholdback limits. This feature is active the whole time thatthe program is running. When hold is forced onto theprogram by holdback, the “HOLD” legend is not illuminatedbut either the “RAMP” or “DWELL” legend will flash.

Once the program has been entered it can be set runningby depressing the “RUN/HOLD” push button on the front.

With the run initiated, the program will commence and thelegend on the display will indicate if a ramp or dwell is beingperformed. While a program is running the short scroll willcontain a third parameter “TIME.” Push scroll button once,time remaining for the current segment, either ramp ordwell will be indicated. If the loop counter has been set toany value other than one, then the above procedure will berepeated for each loop.

At the end of the complete program, an “E” will appear onthe display.

Parameter Change While RunningThe previous parameters can be inspected but not changedwhile a program is running. If it is necessary to alter aparameter while a program is running, the program must beplaced into the hold condition. To put program into hold,push run/hold button once. After modification of the param-

PROGRAMMABLE MODELS

Page 31: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

31

eter, returning the program to the run state will cause theprogram to continue with the changed value(s) installed.Push run/hold button again to restart program.

Loop CountIf the loop count is set to values other than one, then thenumber of loops remaining in a running program can bedisplayed. To determine which loop is being performeddepress scroll button until “LR” is displayed and bypushing either the up or down button the remainingnumber of loops, excluding the one being executed, isdisplayed.

Program HoldA running program can be forced into hold at any stageby depressing the “RUN/HOLD” push button on the front.When a running program is forced into hold, “HOLD”legend will appear on the display together with thesegment type and will be flashing. Pushing “RUN/HOLD”button again will return the program to a run situation andextinguish the “HOLD” legend.

Program ResetA running, held or finished program can be reset bydepressing the up and down push buttons together.

When the reset has been enabled the parts of the displayassociated with programming will be extinguished andthe controller will operate as a single setpoint control.

PROGRAMMABLE MODELS

NoteWhen the program has ended, thecontroller will maintain the chambertemperature at a value equal to the lastprogrammed level (PL) until the programis cancelled. It will not automatically coolto ambient unless last programmed level(PL) is set at ambient. When a program iscancelled, the controller will maintain thechamber temperature at a value equal tothe main set point (SP1 or SP). To cancela program, depress and release the “UP”and “DOWN” push buttons simulta-neously. Be sure single set point mode isset to 20° value as described earlier inthis manual.

Page 32: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

32

Be sure not to block the flow of radiant heat from theheating elements to the thermocouple; the thermocouplemust be able to respond directly to the heating elements.Failure to observe this will permit the heating elements tooverheat and possible burn out. Poor temperature controlcan also result from improper loading.

For best results, use the center 12" of the heating zone.The optimum temperature uniformity and stability is in thegeometric center of heating zone (10").

In general, space should be left on all sides of a load or onall sides of individual components of a load so that heat canpenetrate through the surfaces. The load should not occupymore than half to two-thirds of the inside dimensions of thechamber.

The extent to which a furnace may be loaded dependsupon such factors as operating temperature, desiredaccuracy, and type of material. A furnace may be loadedmore heavily at lower temperatures, if highest accuracy isnot needed, and if the material of the load absorbs heateasily.

Furnace Loading

CautionBe sure to use great care in loadingand unloading the furnace chamber.Molybdenum disilicide heating ele-ments are extremely fragile and cancrack or break with just a slight bump.

Page 33: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

33

These furnaces are designed to be used to 1500°C(F54500) or 1700°C (F59300) in pure air only. It may beused with nitrogen, argon, or helium atmospheres to1500°C (F54500) or 1700°C (F59300). Reducing atmo-spheres are not recommended.

The heating elements in these furnaces are attacked byfluorine, chlorine, sodium and potassium compounds andalso by molten metals.

Furnace Atmospheres

Page 34: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

34

WarningThis warning is presented for compliance with CaliforniaProposition 65 and other regulatory agencies and onlyapplies to the insulation in this product. This productcontains refractory ceramic, refractory ceramic fiber orfiberglass insulation, which can produce respirable dust orfibers during disassembly. Dust or fibers can cause irritationand can aggravate preexisting respiratory diseases.Refractory ceramic and refractory ceramic fibers (afterreaching 1000°C) contain crystalline silica, which can causelung damage (silicosis). The International Agency forResearch on Cancer (IARC) has classified refractoryceramic fiber and fiberglass as possibly carcinogenic(Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials can be located inthe door, the hearth collar, in the chamber of the product orunder the hot plate top. Tests performed by the manufac-turer indicate that there is no risk of exposure to dust orrespirable fibers resulting from operation of this productunder normal conditions. However, there may be a risk ofexposure to respirable dust or fibers when repairing ormaintaining the insulating materials, or when otherwisedisturbing them in a manner which causes release of dustor fibers. By using proper handling procedures and protec-tive equipment you can work safely with these insulatingmaterials and minimize any exposure. Refer to the appro-priate Material Safety Data Sheets (MSDS) for informationregarding proper handling and recommended protectiveequipment. For additional MSDS copies, or additionalinformation concerning the handling of refractory ceramicproducts, please contact the Customer Service Departmentat Barnstead|Thermolyne Corporation at 1-800-553-0039.

A few simple procedures will help ensure that your furnacewill give you long service.

1 . Keep the chamber clean; this furnace is capableof achieving temperatures which will causevaporization of many materials. In turn, thesevapors can react with the heating elements, theinsulation, or other materials you have placed inthe chamber. In many instances this is detrimentalto the operation.

Preventive Maintenance

WarningRefer servicing to qualified personnel.

WarningDisconnect from the power supply priorto maintenance and servicing. Referservicing to qualified personnel.

Page 35: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

35

2. Occasionally check the power connections inthe control section. Repeated heating andcooling can cause terminals to loosen.

3. The type B thermocouple used in this furnace ismatched to the temperature controller. It ispossible that its calibration can drift, particularlywhen operated near the upper temperaturelimit, and especially in the presence of contami-nants. It is a good idea to inspect it at regularintervals or when its accuracy is suspect.

4. Check the cooling fans at regular intervals to besure they are functioning properly and are notobstructed by foreign matter.

PREVENTIVE MAINTENANCE

Page 36: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

36

The following pages are intended to help you resolve functional problems with your furnace.

Thermolyne is always available to assist you with problems. If this guide does not direct you to your specificproblem, call Barnstead|Thermolyne at (1-800-553-0039) or write to the address on the back cover of thismanual.

Problem Possible Causes Corrective Action

Inaccurate temperatures. Contaminated thermocouple. Replace thermocouple.

Repeated element burn-out. Loose element connections. Check element connections.

Heating element contamination. Contact Barnstead|Thermolyne.

“OR” Displayed. Open thermocouple. Replace thermocouple.

Slow heat-up. Operating 240V furnace on Contact Barnstead|Thermolyne.208V line.

Furnace overloaded. Lighten load.

Main fuses blow or circuit breakers Fuses or breakers not properly Install service line of sufficient sizetrip. rated to furnace power to match furnace power requirement.

requirements. Contact qualified electrician forassistance.

CH.. C, DH.. H, Err-r Displayed. Contact Barnstead|Thermolyne .

No heat. Broken element. Replace element.

Troubleshooting Guide

Page 37: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

37

WarningTHIS PRODUCT CONTAINS REFRACTORY CERAMIC,REFRACTORY CERAMIC FIBER OR FIBERGLASS(GLASS WOOL) INSULATION WHICH CAN PRODUCERESPIRABLE FIBERS AND DUST WHEN HANDLED.THESE FIBERS OR DUSTS CAN CAUSE IRRITATIONAND CAN AGGRAVATE PRE—EXISTING RESPIRA-TORY DISEASE. REFRACTORY CERAMIC INSULA-TIONS MAY CONTAIN OR MAY FORM CRYSTALLINESILICA (CRYSTOBALITE) WHICH MAY CAUSE LUNGDAMAGE (SILICOSIS). THE INTERNATIONAL AGENCYFOR RESEARCH ON CANCER (IARC) HAS CLASSI-FIED REFRACTORY CERAMIC FIBER AND FIBER-GLASS AS (2B) POSSIBLY CARCINOGENIC. IARCHAS CLASSIFIED CRYSTALLINE SILICA AS (2A)PROBABLY CARCINOGENIC. The insulating materialsare located in the door, the hearth collar, in the chamberof the product or the top plate assembly. Tests performedby the manufacturer indicate that there is no significantrisk of exposure to dust or respirable fibers resulting fromoperation of this equipment under normal conditions.However, there may be a risk of exposure to respirabledusts or fibers when repairing or maintaining the insulat-ing materials, or when otherwise disturbing the materialsin a manner which causes release of dust or fiberstherefrom. Through the use of proper handling proce-dures you can work safely with these insulating materialsand minimize any exposure. Accordingly, before yourepair or replace any insulating materials, or perform anyother servicing on this product which could disturb orcause exposure to dust from insulating materials, youshould consult the appropriate Material Safety DataSheets (MSDS’s) for such products with respect to properhandling and appropriate protective equipment. Foradditional MSDS’s, or additional information concerningthe handling of refractory ceramic products, pleasecontact the Customer Service Department ofBarnstead|Thermolyne Corporation at 1-800-553-0039.

Maintenance and Servicing

WarningRefer servicing to qualified personnel.

WarningDisconnect from the power supply prior tomaintenance and servicing. Refer servic-ing to qualified personnel.

Page 38: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

38

To Replace a Heating Element(Refer to Figure 1)

a. Remove top cover from heating chamber side offurnace.

b. Remove the clips holding the connector cable tothe defective heating element. Unwrap theconnector cable from the element.

c. Slide the heating element with element ceramicholder attached upward out of the slot in theinsulation. Save the blanket insulation for reuse.Discard element insulation tail.

d. Remove the element ceramic holder, noting itsexact position on the heating element. Also besure that the heating element projects sufficientlyinto the chamber as shown in Figure 1.

e. Fasten the element ceramic holder on the newelement in exactly the same position it was on theold element. Maintain 1 13/16" space fromceramic holder to top of element tail.

f. Begin inserting the new element with elementceramic holder attached into the slot in theinsulation; stop when there is just enough roomleft to insert the new element insulation tail.

g. Continue sliding the element with the elementinsulation tail into the slot. DO NOT FORCE -even slight pressure can fracture the heatingelement.

h. When the element ceramic holder is nearly seatedagainst the main insulation, check the top ofelement insulation tail. In its final position, the topshould be about 1/8 inch below the surface of themain insulation.

i. Position the blanket insulation piece from step c inthe cavity over the insulation piece.

j. Complete insertion of the heating element untilthe element ceramic holder rests on top of themain insulation.

MAINTENANCE AND SERVICING

CautionTo avoid breakage of a replacementheating element, be sure that the slotinto which the replacement heatingelement slides is free of all debris sothat the element goes in very easily.Forcing an element into a slot, howeverslightly, can result in its breakage. Alsobe sure that the heating elementprojects sufficiently into the chamber.Element should extend into chamberuntil welded section (the larger diam-eter portion of element) protrudesapprox. 1/4” inside of chamber. Toavoid premature burnout of a replace-ment heating element, be sure that theinsulation piece supplied with thereplacement element is insertedbetween the two legs of the elementsas shown in Figure 1.

Page 39: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

39

k. Check the heating element on the inside of thechamber. The large diameter section of theelement must be flush with or slightly projectingfrom the surface of the insulation (if not, reposi-tion element ceramic holder).

l. Carefully wrap the connector cable around theelement ends; fasten with clips.

m. Replace top cover.

To Replace Thermocouple:a. Remove top cover from the thermocouple side

of furnace.

b. Loosen diagonal screw holding ceramic con-nection block.

c. Lift connection block.

d. Loosen connection block screws holdingthermocouple; noting which side of block theside of the thermocouple with the colored beadis connected to.

e. Remove thermocouple.

f. Install new thermocouple with colored bead insame position.

g. With thermocouple through the hole in theinsulation, replace block in its holder andretighten diagonal screw.

h. Turn furnace ON for a few minutes; check to besure the temperature reads upscale.

i. Replace cover.

NoteInitial heat-up procedureThe elements may bend slightly sidewaysdue to electromagnetic forces generatedbetween the element shanks. To preventthis bending, heat the furnace up to*1500°C (F54500) and hold at thistemperature for 10-20 minutes. Then letfurnace cool to ambient temperature.(*1600°C for model F59300).

MAINTENANCE AND SERVICING

Page 40: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

40

Series 705 & 706Description Part No. (All Models Unless Specified)

Elements EL461X1 (8 req’d)

Element ceramic holder HRX2 (8 req’d)

Element connector clips CEX135 (16 req’d)

Element connector cable 4" long CE461X1 (6 req’d)

Circuit breaker switch SWX54

Fans FAX7 (3 req’d)

Relay RYX31

Transformer TNX80

Thermocouple TCX5

Thermocouple terminal block TRX137

Element Insulation tail JN545X18 (8 req’d)

Connector cable 48" long CE545X1 (3 req’d)

Sleeving for 48" cable SL545X1 (3 req’d)

Temperature Control Automatic (Single Set Point) CN71X36 (F54530CM & F54538CM)

Temperature Control Programmable CN71X60

(8 ramp and 8 dwell 1 program) (F54540CM & F59548CM)

Temperature Control Automatic (Single Set Point) CN71X32 (F59330CM & F59338CM)

Temperature Control Programmable CN71X59

(8 ramp and 8 dwell, 1 program) (F59340CM & F59348CM)

Multi-Programmable Temperature Control CN71X46

(8 ramp and 8 dwell, 15 programs) (F59340CM-75 & F59348CM-75)

Current controller CN71X50

1" diameter insulation sleeve JN545X12 (2 req’d)

2" diameter insulation sleeve JN545X13 (2 req’d)

3" diameter insulation collar JN545X14 (4 req’d)

Controller fuse, 50 Amp FZX42

Replacement Parts

NoteFor service on control units - contact Barnstead|Thermolyne Corp. (1-800-553-0039)

Page 41: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

41

Figure 1: Element Replacement

Page 42: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

42

Ordering Procedures

Please refer to the Specification Plate for the completemodel number, serial number, and series number whenrequesting service, replacement parts or in anycorrespondence concerning this unit.

All parts listed herein may be ordered from theBarnstead|Thermolyne dealer from whom you purchasedthis unit or can be obtained promptly from the factory.When service or replacement parts are needed we ask thatyou check first with your dealer. If the dealer cannot handleyour request, then contact our Customer ServiceDepartment at 319-556-2241 or 800-553-0039.

Prior to returning any materials to Barnstead|ThermolyneCorp., please contact our Customer Service Department fora “Return Goods Authorization” number (RGA). MaterialReturned without an RGA number will be returned.

Page 43: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

43

Barnstead|Thermolyne Corporation warrants that if a product manufactured by Barnstead|Thermolyne andsold by it within the continental United States or Canada proves to be defective in material or construction, itwill provide you, without charge, for a period of ninety (90) days, the labor, and a period of one (1) year, theparts, necessary to remedy any such defect. Outside the continental United States and Canada, the warrantyprovides, for one (1) year, the parts necessary to remedy any such defect. The warranty period shallcommence either six (6) months following the date the product is sold by Barnstead|Thermolyne or on thedate it is purchased by the original retail consumer, whichever date occurs first.

All warranty inspections and repairs must be performed by and parts obtained from an authorizedBarnstead|Thermolyne dealer or Barnstead|Thermolyne (at its own discretion). Heating elements, however,because of their susceptibility to overheating and contamination, must be returned to our factory, and if, uponinspection, it is concluded that failure is not due to excessive high temperature or contamination, warrantyreplacement will be provided by Barnstead|Thermolyne . The name of the authorized Barnstead|Thermolynedealer nearest you may be obtained by calling 1-800-446-6060 (319-556-2241) or writing to:

Barnstead|ThermolyneP.O. Box 797

2555 Kerper BoulevardDubuque, IA 52004-0797

USAFAX: (319) 589-0516

E-MAIL ADDRESS: [email protected]

Barnstead|Thermolyne’s sole obligation with respect to its product shall be to repair or (at its own discretion)replace the product. Under no circumstances shall it be liable for incidental or consequential damage.

THE WARRANTY STATED HEREIN IS THE SOLE WARRANTY APPLICABLE TO Barnstead|ThermolynePRODUCTS. Barnstead|Thermolyne EXPRESSLY DISCLAIMS ANY AND ALL OTHER WARRANTIES,EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE.

One Year Limited Warranty

Page 44: High Temperature Tube Furnaces...ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to hu-mans (Group 1). The insulating materials

44

9001ISOREGISTERED

Barnstead|Thermolyne2555 Kerper Blvd.P.O. Box 797Dubuque, IA 52004-2241Phone: 319-556-2241 800-553-0039Fax: 319-589-0516E-Mail Address: [email protected]