Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted...

40
Submittal Data Sheet Package Basic System Heating and Air Conditioning ® Form: 036-22243-001 Rev A (602) Supersedes: Nothing

Transcript of Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted...

Page 1: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Submittal Data

Sheet Package

Basic System

Heating and Air Conditioning

®

Form: 036-22243-001 Rev A (602)Supersedes: Nothing

Page 2: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22284-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The Meridian Basic control system converts a singlezone HVAC unit into a variable air volume/variableair temperature multiple zone system. The micro-processor based Zone Manager calculates theheating and cooling requirements for each zonebased on real time information received from eachZone Controller. The Zone Manager then directs theHVAC unit to provide the appropriate amount ofheating, cooling, and ventilation to satisfy eachzone's requirements. A static pressure sensor, whichmodulates a bypass damper, maintains a constantsystem duct pressure.

Substantial savings can be realized using the Me-ridian Basic system instead of installing multipleHVAC units to accommodate multiple zones. TheMeridian Basic system is versatile and can be usedwith any 3-40 ton HVAC unit. It controls a variety ofterminal units including single duct pressure de-pendent or pressure independent zone damper.

User friendly, menu driven, fill in the blank pro-gramming, makes the Meridian Basic easy to set upand operate without the need for specialized training.

MeridianView, a Windows based color graphic soft-ware package is available at no additional charge.The optional CommLink II must be ordered andconnected to a PC in order to use the software foron-site control and monitoring. If remote monitoringand control is required, an optional Remote Link(Modem) must be ordered ..

Wiring Requirements• All control devices are 24 VAC and can be pow-

ered from common or individual transformers.• CommLink - 24 VAC (Plug-in transformer in-

cluded)• Communications - RS-485/9600 Baud - Daisy

Chain Configuration - Twisted Pair/Shielded

Page 3: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22285-001 Rev. A (0602) Supersedes: Nothing Page 1 of 3

Part No Description Quantity

2ZMB0047020242ZMB004702124OE710 – ºFOE710 – ºF

Basic System PackageIncludes: Zone Manager Mounted in an Enclosure with Integral Keypad and Display, Supply,Return and Outside Air Temperature Sensors, Bypass Pressure Sensor, Installation Manual,Wiring Diagram.

2ZDM0047 Series Zone Air Damper AssembliesSee Page 2 for Round Dampers Pages 3 for Rectangular Dampers.

2ZPK004700224OE742 – ºF2ZPK004700324OE742 – ºC

Zone Package - Pressure Dependent (Air Damper Not Included)Includes: Zone Controller, Damper Actuator, Modular Cable.

2ZPK0047001024OE744 – ºF2ZPK0047001124OE744 – ºC

Zone Package - Pressure Independent (Air Damper Not Included)Includes: Zone Controller, Damper Actuator, Cable for Actuator to Controller Connection,Airflow Sensor. Note: The Air Damper used in Conjunction with this Package Must Have anAirflow Probe Installed for Connection to the Airflow Sensor.

2ZSK0047000024OE282-03

Slaved-Zone Package (Air Damper Not Included)Use for Zones Requiring Slave Damper(s) Only. Not Required w/ Bypass Applications.Includes: Damper Actuator, Wiring Interface, Cable, Slave Actuator Terminal Card. Max. of(2) Slaves Allowed per Master Zone Air Damper.

2ZBI004709124OE282-02

Bypass Package (Air Damper Not Included)Includes: Damper Actuator, Wiring Interface, and Cable.Up to (3) Bypass Dampers May be Connected in Parallel for Applications Requiring MoreThan One Bypass Damper.

2ZRE0047001024OE321

Relay Expansion Board for Zone ControllersFor Control of Auxiliary Heat, Box Heat, Series and Parallel Flow Fan Terminal Units.

2ZTS004704024OE2102ZTO004704024OE2112ZTA004704124OE2122ZTB004704124OE213

Room Sensor – Plain

Room Sensor with Override

Room Sensor with Setpoint Adjust

Room Sensor with Override and Setpoint Adjust

2ZCP004703124OE361-04-CLSG

CommLink II Communications InterfaceFor Use with Auto Zone Basic Systems Only. Includes Cables and 115/24VACPower Supply. Required if Direct Computer or Remote Computer Connectionis Required. ZoneView Software must be Installed on Direct or RemoteComputer to Communicate With Auto-Zone System.Note: Remote Computer Connection Also Requires An External York SuppliedModem (2ZEM004703424) Be Connected To The CommLink.

Project: ___________________________________________________________________

Page 4: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22285-001 Rev. A (0602) Supersedes: Nothing Page 2 of 3

Part No Description

Pressure Dependent Zone Air DampersIncludes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure.2ZMD0047006242ZMD0047010624

Zone Air Damper Assembly - 6″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047008242ZMD0047010824

Zone Air Damper Assembly - 8″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047010242ZMD00470101024

Zone Air Damper Assembly - 10″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047012242ZMD00470101224

Zone Air Damper Assembly - 12″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047014242ZMD00470101424

Zone Air Damper Assembly - 14″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047016242ZMD00470101624

Zone Air Damper Assembly - 16″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

Pressure Independent Zone Air DampersIncludes: Damper Actuator, Zone Controller, Air Flow Sensor, Mounted on Round Air Damper with Control Enclosure.2ZMD0047106242ZMD0047110624

Zone Air Damper Assembly - 6″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047108242ZMD0047110824

Zone Air Damper Assembly - 8″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047110242ZMD0047111024

Zone Air Damper Assembly - 10″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047112242ZMD0047111224

Zone Air Damper Assembly - 12″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047114242ZMD0047111424

Zone Air Damper Assembly - 14″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

2ZMD0047116242ZMD0047111624

Zone Air Damper Assembly - 16″ Diameter (Fahrenheit) “ “ “ “ “ “ (Celsius)

Bypass Air DampersIncludes: Damper Actuator, Wiring Interface, Mounted on Air Damper with Control Enclosure. Up to (3) Bypass Dampers May beConnected in Parallel for Applications Requiring More Than One Bypass Damper.2ZBD004701024 Bypass Air Damper Assembly - 10″ Diameter2ZBD004701224 Bypass Air Damper Assembly - 12″ Diameter2ZBD004701424 Bypass Air Damper Assembly - 14″ Diameter2ZBD004701624 Bypass Air Damper Assembly - 16″ DiameterSlaved-Zone Air Dampers (Use for Zones Requiring Slave Damper(s) Only. Not Required for Bypass Applications)Includes: Damper Actuator, Wiring Interface, Mounted on Air Damper with Control Enclosure. Also Includes Slave Actuator Terminal CaFor Connecting to Zone Damper. Max. of (2) Slaves Allowed per Master Zone Air Damper.2ZSD004700624 Slaved-Zone Air Damper Assembly – 6″ Diameter2ZSD004700824 Slaved-Zone Air Damper Assembly – 8″ Diameter2ZSD004701024 Slaved-Zone Air Damper Assembly – 10″ Diameter2ZSD004701224 Slaved-Zone Air Damper Assembly – 12″ Diameter2ZSD004701424 Slaved-Zone Air Damper Assembly – 14″ Diameter2ZSD004701624 Slaved-Zone Air Damper Assembly – 16″ Diameter

Project: ___________________________________________________________________

Page 5: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22285-001 Rev. A (0602) Supersedes: Nothing Page 3 of 3

Part No Width (A) Height (B) Description Quantity1ZRD00470 Rectangular Damper

Includes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

1ZRD00470 Rectangular DamperIncludes: Rectangular Damper Designed for Flanged to Duct Mounting.Size Damper for Nominal Duct Size. Dampers are Supplied with 1” flangeAll Around for Mounting to Ductwork.

Part No Description Quantity

2ZDK0047000740OE740

Zone Damper Kit (Damper Not included)Includes: Damper Actuator and Zone Controller, Factory Mounted In an Enclosure

2ZDK0047000741OE741

Bypass Damper Kit (Damper Not included)Includes: Damper Actuator, Wiring Interface, Mounted in Control Enclosure. Up to (3)Bypass Damper Kits May be Connected in Parallel for Applications Requiring More ThanOne Bypass Damper.

2ZDK0047000739OE739

Slaved-Zone Damper Kit (Damper Not included)Use for Zones Requiring Slave Damper(s) Only. Not Required for Bypass Applications.Includes: Damper Actuator, Wiring Interface, Mounted in Control Enclosure. AlsoIncludes 2ZWA004700124 Slave Wiring Adapter For Connecting to Zone Damper Kit.Max. of (2) Slaves Allowed per Master Zone Air Damper Kit.

Part Number: 1ZRD00470XX XXDamper Width Damper Height

Project: ___________________________________________________________________

Page 6: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22286-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The Meridian 2ZMO004700224 and the2ZMO004700324 Basic Zone Managers aremicroprocessor based HVAC unit controllers.The 2ZMO004700224 is the Fahrenheit ver-sion and the 2ZMO004700324 is the Celsiusversionn. The Zone Manager calculates theheating and cooling requirements for eachzone based on real time information receivedfrom the Zone Controllers. It then controls theHVAC unit to provide the appropriate amountof heating, cooling, and ventilation to satisfyeach zones requirements. The Zone Manageralso controls a bypass damper which modu-lates the bypass airflow at the HVAC unit, inorder to maintain proper duct static pressure.One Zone Manager is required for each multi-ple zoned HVAC unit that is to be part of thebuilding HVAC system. Each Zone Managercan accommodate up to 16 zones.

The Zone Manager keypad & display provide acentral operators interface to all controllers onthe network. All system variables, setpoints,and values can be viewed and modified fromone convenient location. Menu driven pro-gramming makes the Meridian Basic systemeasy to set up and operate. The Zone Man-ager is password protected to prevent unau-thorized access to the system.

The Zone Manager is designed to be mountedindoors on a flat surface. Typically, the Zone Manager is mounted on a wall in the building managers office, orlocated on the wall of an equipment room or other location that prevents access by unauthorized personnel.

Technical Data 2ZMO004700224 Zone Manager for Basic SystemsPower 24 VAC Display 4 Line x 20 Char. Backlighted LCDPower Consumption 25 VA Maximum Network Connection RS-485Operating Temp 10°F(12ºC) to

149°F(65ºC)Protocol HSI Open Protocol Token Passing

OperatingHumidity

90% RHNon-Condensing

Color Beige Enclosure, Black Keypad w/White Keys & Black Numerals

Keypad 16 Key Membrane Communications RS-485 - 9600 BaudInputs: Thermistor (Type III) Weight Approx. 4 lbs.Outside Air Sensor -30º F(-34ºC) to

80ºF(82ºC)Outputs: Digital (2 Amp @ 24VAC)

Supply Air Sensor Fan - Continuous or Cycling N.O. RelayReturn Air Temp

30º F(-1ºC) to180º F(82ºC) Heating (2 Stages) N.O. Relay

Inputs: Analog Cooling (2 Stages) N.O. RelayPressure Sensor 0” to 5” WC Exhaust Fan or Relief Dmpr. N.O. RelayBypass Actuator Feedback 500 to 7300 Ω Bypass Damper Actuator Tri-StateInputs: DigitalChange Filter Alarm Dry ContactForced Occupied Mode Dry Contact Analog Output: 1K Ω Min. LoadEconomizer Disable Dry Contact Economizer Actuator 0-10 VDCYork reserves the right to change specifications without notice

Three Year Warranty

FAN

CO

OL

1

CO

OL

2

HE

AT

1

HE

AT

2

BY

PAS

SO

PE

N

BY

PAS

SC

LO

SE

CO

MM

UN

ICATIO

N

ALA

RM

A=

ALL

ZO

NE

S

B=

EA

CH

ZO

NE

C=

HVA

CU

NIT

/CLE

AR

D=

ALA

RM

S

#=

STE

P/E

NTE

R

* =D

EC

IMA

L

+

+

+

+

Meridian

Cool

Mode

08-08-01

03:48PMFRI

OCCUPIED

NOALARMS

2

8

5

0

A

C

B

D

1

7

4

*

3

9

6

#

3.00

11.50

Keypad

Display

9.25

Heating and Air Conditio

ning

®

Page 7: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22287-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

The 2ZBD00470xxxx Bypass Damper as-sembly, consists of a round air valve, actua-tor and bypass wiring interface card mountedin the enclosure.

The Bypass Damper controls duct staticpressure to insure proper system airflow.The Bypass Damper is controlled by the Me-ridian System Zone Manager. The ZoneManager modulates the Bypass Damper inresponse to the duct static pressure basedon a signal received from a static pressuresensor located in the main system ductwork.

All Bypass Dampers are tested and certifiedin accordance with ARI standard 880. An ARIlabel is affixed to all units.

The Bypass Damper Assembly should bemounted according to standard duct installa-tion practices with airflow direction as shownin the illustration above. After installation ofthe Bypass Damper in the ductwork, insula-tion should be applied around any remaininguninsulated surface on the air valve inlet and outlet. The Bypass Damper should be mounted so the control enclo-sure is positioned to the left or right side of the ductwork with the control enclosure in a vertical plane. Do notmount the Bypass Damper Assembly with the control enclosure on the top or bottom of the ductwork. Adequateclearance should be maintained between the control panel and any obstruction to allow for removal of the controlpanel cover and access to the controls.

Technical Data 2ZBD00470XXX Bypass DamperActuator Air Damper Construction:Supply Power 24 Volt AC Damper Body 24 Ga. Galv. SteelPower Consumption 3.4 VA Maximum Damper Blade Round -18 Ga. Galv. SteelOperating Temperature 35°F(2°C) to 125°F(52°C) Damper Bearings Oil Impregnated BronzeOperating Humidity 90% RH Non-Condensing Damper Seal Volara Type A Gasket

Leakage Less Than 1% @ 3” SPInsulation ½” Foil Faced Fiberglass

Inputs: Dimensions:Actuator Position Feedback Air Damper Model “A” “B” “C”

OE512-10 (10”) 19.00 9.88 13.38OE512-12 (12”) 21.00 11.88 15.38OE512-14 (14”) 21.00 13.88 17.38OE512-16 (16”) 21.00 15.88 19.38

WattMaster reserves the right to change specifications without notice

Three Year Warranty On Electronic Components One Year Warranty On Air Damper

1/2" Foil FacedInsulation

Actuator

Round DamperBlade Assembly

Control Enclosure(Cover Removed)

AIRFLO

W AIRFLOW

Bypass & Slave Interface

Page 8: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22287-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Because the zones in a Meridian Systemare controlled using variable air volume, it isunlikely that all zones will be at design loadat the same time. This zoning allows forload diversity to be taken into account whensizing the central HVAC unit. This typicallywill provide better comfort with a smallerHVAC unit than with the use of a constantvolume system. Use a load program to de-termine the individual zone loads. Becauseof zone diversity the HVAC unit should besized for the correct instantaneous peakload, not the sum of the peak loads aswould be the case when sizing a normalconstant volume unit system. The BypassDamper should be sized to provide for themaximum amount of air to be bypassed inthe system. This is typically 60 to 70% ofthe HVAC units rated capacity. These cal-culations will be used in selecting the ap-propriate Bypass Damper Size(s).

The Meridian Systems utilize a typical lowpressure duct design. To reduce noiseproblems, duct pressures should not ex-ceed 1” W.C..

Using the maximum acceptable velocity fora bypass duct (typically 1750-2250 FPM forminimal noise), find the smallest damperthat will deliver the required CFM as deter-mined by the load program.

Bypass Air Damper Selection Data 2ZBD00470XXX Bypass DamperBypass Air Damper Round Duct Size

(Area Ft2)10”

(0.532)12”

(0.769)14”

(1.050)16”

(1.375)

Velocity Through Bypass Air DamperFPM

Airflow Through Bypass Air Damper - CFM(∆PS inches W.C. w/ Air Damper Full Open)

750 399(0.01)

577(0.02)

788(0.01)

1031(0.01)

1000 532(0.02)

769(0.03)

1050(0.02)

1375(0.01)

1250 665(0.03)

961(0.04)

1313(0.03)

1718(0.02)

1500 798(0.04)

1154(0.05)

15750.04)

2062(0.03)

1750 931(0.06)

1346(0.06)

1838(0.05)

2405(0.04)

2000 1064(0.07)

1538(0.07)

2100(0.07)

2749(0.05)

2250 1197(0.08)

1730(0.08)

2363(0.08)

3093(0.06)

York reserves the right to change specifications without notice

When determining the bypass duct size, be sure to take into ac-count any transition fittings and their associated pressure drops.Locate the bypass duct velocity used in the duct design program inthe left hand column of the Bypass Damper Selection Data table.Move across the table and find the Bypass Damper size which willprovide the acceptable CFM to meet the bypass airflow require-ments.

Compare the Bypass Air Damper size selectedagainst the bypass duct size to determine if the nextsize up or down will provide acceptable performancewithout requiring a transition fitting.

Up to a maximum of two additional Bypass Dampers may beslaved together with the main Bypass Damper for large bypassairflow requirements. This design should be reserved only forsituations when it is not practical to use a single large BypassDamper. The slaved valves should all be of the same size forproper control. Divide the total CFM by two or three depending onhow many bypass and slave dampers you will be using and sizeaccordingly.

Page 9: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Meridian Control Systems

Form: 036-22288-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

DescriptionThe 2ZMD00470xxxx series Pressure De-pendent Zone Damper for Fahrenheit op-eration consists of a round air damper,zone controller, and actuator. An optionalauxiliary relay board (2ZRE0047000024) isavailable for control of auxiliary heat and/orcontrol of series or parallel flow fan terminalunits.

The Zone Controller (2ZC0047000024) ismicroprocessor based and communicateswith the Zone Manager on the Meridiannetwork communications loop. The ZoneController monitors the space temperatureand allocates the proper airflow into its as-signed space to achieve the desired com-fort and ventilation levels.

Pressure Dependent Zone Dampers areused in air conditioning systems that do notrequire pressure independent airflow con-trol. If your system requires pressure inde-pendent control of the airflow, see the“2ZMD00471xxxx series - Pressure Inde-pendent Zone Damper - Fahrenheit” datasheet for the correct specifications.

All Zone Dampers are tested and certifiedin accordance with ARI standard 880. An ARI label is affixed to all units.

MountingThe Zone Damper assembly should be mounted according to standard duct installation practices with airflow di-rection as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation shouldbe applied around any remaining uninsulated surface on the air valve inlet and outlet. The Zone Damper shouldbe mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclo-sure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or bottomof the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allowfor removal of the control panel cover and access to the controls.

2ZMD00470xxxx

Pressure Dependent

Zone Damper - Fahrenheit

Technical Data 2ZMD00470xxxx Pressure Dependent Zone Damper - FahrenheitZone Controller: Air Damper Construction:Supply Power 24 Volt AC Damper Body 24 Ga. Galv. SteelPower Consumption 12 VA Maximum Damper Blade Round -18 Ga. Galv. SteelOperating Temperature 35°F to 125°F Damper Bearings Oil Impregnated BronzeOperating Humidity 90% RH Non-Condensing Damper Seal Volara Type A GasketCommunications RS-485 - 9600 Baud Leakage Less Than 1% @ 3” SP

Insulation ½” Foil Faced FiberglassInputs: Dimensions:Room Temperature Sensor Air Damper Model “A” “B” “C”Setpoint Adjustment 2ZMD004700624 (6”) 19.00 5.88 9.38Actuator Position Feedback 2ZMD004700824 (8”) 19.00 7.88 11.38

2ZMD004701024 (10”) 19.00 9.88 13.38Outputs: 2ZMD004701224 (12”) 21.00 11.88 15.38Expansion Port for Auxiliary Relay Board 2ZMD004701424 (14”) 21.00 13.88 17.38Actuator Port for Connection to Damper Actuator 2ZMD004701624 (16”) 21.00 15.88 19.38York reserves the right to change specifications without notice

Three Year Warranty On Electronic Components One Year Warranty On Air Damper

1/2" Foil FacedInsulation

Actuator

Zone Controller

Round DamperBlade Assembly

Control Enclosure(Cover Removed)

AIRFLO

W AIRFLOW

Page 10: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Meridian Control Systems

Form: 036-22288-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Zone Damper SizingUse a load program to determine the peakload for each zone. These calculations will beused to select Zone Damper sizes.

The Meridian Systems utilize a typical lowpressure duct design. To reduce noise prob-lems, duct pressures should not exceed 1”W.C.

Primary trunk ducts used with Meridian sys-tems should not be “undersized”. This is es-pecially true of “pressure dependent” sys-tems. With larger trunk ducts, it is easier toassure relatively constant pressure to eachZone Damper. Runs should be as short aspossible, and the trunk duct system kept assymmetrical as possible to facilitate systembalancing. Wherever possible, run the trunkducts above corridors and locate the ZoneDampers above corridors to reduce the noisein the space and facilitate service of thevalves. Trunk ducts should be sized for nomore than 0.1” W.C. drop per 100 ft. of duct,and a maximum duct velocity of 2000 FPM.

Using the maximum acceptable velocity for abranch duct (typically 1000-1500 FPM forminimal noise), find the smallest ZoneDamper that will deliver the required CFM asdetermined by the load program.

Zone Damper Selection Data 2ZMD00470xxxx Pressure Dependent Zone Damper - FahrenheitZone Damper Round Duct Size

(Area Ft2)6”

(0.188)8”

(0.338)10”

(0.532)12”

(0.769)14”

(1.050)16”

(1.375)

Velocity Through Zone DamperFPM

Airflow Through Zone Damper - CFM(∆PS inches W.C. w/ Damper Full Open)

500 94(0.01)

169(0.01)

266(0.01)

385(0.01)

525(0.01)

687(0.01)

750 141(0.03)

254(0.02)

399(0.01)

577(0.02)

788(0.01)

1031(0.01)

1000 188(0.05)

338(0.03)

532(0.02)

769(0.03)

1050(0.02)

1375(0.01)

1250 235(0.07)

423(0.04)

665(0.03)

961(0.04)

1313(0.03)

1718(0.02)

1500 282(0.09)

507(0.06)

798(0.04)

1154(0.05)

15750.04)

2062(0.03)

1750 329(0.12)

592(0.08)

931(0.06)

1346(0.06)

1838(0.05)

2405(0.04)

2000 376(0.15)

676(0.10)

1064(0.07)

1538(0.07)

2100(0.07)

2749(0.05)

York reserves the right to change specifications without notice

Locate the branch velocity used in the duct design program inthe left hand column of the Zone Damper Selection Data table.Move across the table and find the Zone Damper which will pro-vide the acceptable CFM to meet the zone airflow requirements.

Note: Compare the Zone Damper size selected againstthe duct size to determine if the next size up ordown will provide acceptable performance withoutrequiring a transition fitting.

Up to a maximum of two Slaved-Zone Dampers may be slavedtogether with the main Zone Damper for large zones. Thisdesign should be reserved only for situations when it is notpractical to use a single Zone Damper. See the Slaved-ZoneDamper specification sheet for information regarding applicationand selection of Slaved-Zone Dampers.

2ZMD00470xxxx

Pressure Dependent Zone

Damper - Fahrenheit

Page 11: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Meridian Control Systems

Form: 036-22289-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

DescriptionThe 2ZMD004701xxxxx series PressureDependent Zone Damper for Celsius op-eration consists of a round air damper,zone controller, and actuator. An optionalauxiliary relay board (2ZRE0047000024) isavailable for control of auxiliary heat and/orcontrol of series or parallel flow fan terminalunits.

The Zone Controller (2ZC0047000124) ismicroprocessor based and communicateswith the Zone Manager on the Meridiannetwork communications loop. The ZoneController monitors the space temperatureand allocates the proper airflow into its as-signed space to achieve the desired com-fort and ventilation levels.

Pressure Dependent Zone Dampers areused in air conditioning systems that do notrequire pressure independent airflow con-trol. If your system requires pressure inde-pendent control of the airflow, see the“2ZMD004701xxxxx series - Pressure In-dependent Zone Damper - Celsius” datasheet for the correct specifications.

All Zone Dampers are tested and certifiedin accordance with ARI standard 880. An ARI label is affixed to all units.

MountingThe Zone Damper assembly should be mounted according to standard duct installation practices with airflow di-rection as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation shouldbe applied around any remaining uninsulated surface on the air valve inlet and outlet. The Zone Damper shouldbe mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclo-sure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or bottomof the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allowfor removal of the control panel cover and access to the controls.

2ZMD004701xxxxx

Pressure Dependent

Zone Damper - Celsius

Technical Data 2ZMD00471xxxxx Pressure Dependent Zone Damper - CelsiusZone Controller: Air Damper Construction:Supply Power 24 Volt AC Damper Body 24 Ga. Galv. SteelPower Consumption 12 VA Maximum Damper Blade Round -18 Ga. Galv. SteelOperating Temperature 17°C to 52°C Damper Bearings Oil Impregnated BronzeOperating Humidity 90% RH Non-Condensing Damper Seal Volara Type A GasketCommunications RS-485 - 9600 Baud Leakage Less Than 1% @ 3” SP

Insulation ½” Foil Faced FiberglassInputs: Dimensions:Room Temperature Sensor Air Damper Model “A” “B” “C”Setpoint Adjustment 2ZMD0047010624 (6”) 19.00 5.88 9.38Actuator Position Feedback 2ZMD0047010824 (8”) 19.00 7.88 11.38

2ZMD0047011024 (10”) 19.00 9.88 13.38Outputs: 2ZMD0047011224 (12”) 21.00 11.88 15.38Expansion Port for Auxiliary Relay Board 2ZMD0047011424 (14”) 21.00 13.88 17.38Actuator Port for Connection to Damper Actuator 2ZMD0047011624 (16”) 21.00 15.88 19.38York reserves the right to change specifications without notice

Three Year Warranty On Electronic Components One Year Warranty On Air Damper

1/2" Foil FacedInsulation

Actuator

Zone Controller

Round DamperBlade Assembly

Control Enclosure(Cover Removed)

AIRFLO

W AIRFLOW

Page 12: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Meridian Control Systems

Form: 036-22289-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Zone Damper SizingUse a load program to determine the peakload for each zone. These calculations will beused to select Zone Damper sizes.

The Meridian Systems utilize a typical lowpressure duct design. To reduce noise prob-lems, duct pressures should not exceed 1”W.C.

Primary trunk ducts used with Meridian sys-tems should not be “undersized”. This is es-pecially true of “pressure dependent” sys-tems. With larger trunk ducts, it is easier toassure relatively constant pressure to eachZone Damper. Runs should be as short aspossible, and the trunk duct system kept assymmetrical as possible to facilitate systembalancing. Wherever possible, run the trunkducts above corridors and locate the ZoneDampers above corridors to reduce the noisein the space and facilitate service of thevalves. Trunk ducts should be sized for nomore than 0.1” W.C. drop per 100 ft. of duct,and a maximum duct velocity of 2000 FPM.

Using the maximum acceptable velocity for abranch duct (typically 1000-1500 FPM forminimal noise), find the smallest ZoneDamper that will deliver the required CFM asdetermined by the load program.

Zone Damper Selection Data 2ZMD004701xxxxx Pressure Dependent Zone Damper - CelsiusZone Damper Round Duct Size

(Area Ft2)6”

(0.188)8”

(0.338)10”

(0.532)12”

(0.769)14”

(1.050)16”

(1.375)

Velocity Through Zone DamperFPM

Airflow Through Zone Damper - CFM(∆PS inches W.C. w/ Damper Full Open)

500 94(0.01)

169(0.01)

266(0.01)

385(0.01)

525(0.01)

687(0.01)

750 141(0.03)

254(0.02)

399(0.01)

577(0.02)

788(0.01)

1031(0.01)

1000 188(0.05)

338(0.03)

532(0.02)

769(0.03)

1050(0.02)

1375(0.01)

1250 235(0.07)

423(0.04)

665(0.03)

961(0.04)

1313(0.03)

1718(0.02)

1500 282(0.09)

507(0.06)

798(0.04)

1154(0.05)

15750.04)

2062(0.03)

1750 329(0.12)

592(0.08)

931(0.06)

1346(0.06)

1838(0.05)

2405(0.04)

2000 376(0.15)

676(0.10)

1064(0.07)

1538(0.07)

2100(0.07)

2749(0.05)

York reserves the right to change specifications without notice

Locate the branch velocity used in the duct design program inthe left hand column of the Zone Damper Selection Data table.Move across the table and find the Zone Damper which will pro-vide the acceptable CFM to meet the zone airflow requirements.

Note: Compare the Zone Damper size selected againstthe duct size to determine if the next size up ordown will provide acceptable performance withoutrequiring a transition fitting.

Up to a maximum of two Slaved-Zone Dampers may be slavedtogether with the main Zone Damper for large zones. Thisdesign should be reserved only for situations when it is notpractical to use a single Zone Damper. See the Slaved-ZoneDamper specification sheet for information regarding applicationand selection of Slaved-Zone Dampers.

2ZMD004701xxxxx

Pressure Dependent

Zone Damper - Celsius

Page 13: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22290-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

The 2ZMD00471xxxx series Pressure Independ-ent Zone Damper for Fahrenheit operation con-sists of a round air valve, zone controller, actua-tor, airflow sensor and a crossflow air pickupprobe. An optional auxiliary relay board(2ZRE0047000024) is available for control of aux-iliary heat and/or control of series or parallel flowfan terminal units.

The Zone Controller (2ZC0047000024) is micro-processor based and communicates with theZone Manager on the Meridian controller networkcommunications loop. The Zone Controller moni-tors the space temperature and allocates theproper airflow into its assigned space to achievethe desired comfort and ventilation levels.

The Pressure Independent Zone Damper is usedin systems that require pressure independentairflow control. If your system does not requirepressure independent control, please see the“2ZMD00470xxxx series - Pressure DependentZone Damper - Celsius” data sheet for the correctspecifications.

All Zone Dampers are tested and certified inaccordance with ARI standard 880. An ARI labelis affixed to all units.

The Zone Damper assembly should be mounted according to standard duct installation practices with airflow di-rection as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation shouldbe applied around any remaining uninsulated surface on the air valve inlet and outlet. The Zone Damper shouldbe mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclo-sure in a vertical plane. Do not mount the Zone Damper with the control enclosure on the top or bottom of theductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow forremoval of the control panel cover and access to the controls.

Technical Data 2ZMD00471xxxx Pressure Independent Zone Damper - CelsiusZone Controller: Air Damper Construction:Supply Power 24 Volt AC Damper Body 24 Ga. Galv. SteelPower Consumption 12 VA Maximum Damper Blade Round -18 Ga. Galv. SteelOperating Temperature 35°F to 125°F Damper Bearings Oil Impregnated BronzeOperating Humidity 90% RH Non-Condensing Damper Seal Volara Type A GasketCommunications RS-485 - 9600 Baud Leakage Less Than 1% @ 3” SP

Insulation ½” Foil Faced FiberglassInputs: Dimensions:Zone Temperature Sensor Air Damper Model “A” “B” “C”Setpoint Adjustment 2ZMD004710624 (6”) 19.00 5.88 9.38Actuator Position Feedback 2ZMD004710824 (8”) 19.00 7.88 11.38Air Flow Sensor 2ZMD004711024 (10”) 19.00 9.88 13.38Outputs: 2ZMD004711224 (12”) 21.00 11.88 15.38Expansion Port for Auxiliary Relay Board 2ZMD004711424 (14”) 21.00 13.88 17.38

2ZMD004711624 (16”) 21.00 15.88 19.38York reserves the right to change specifications without notice

Three Year Warranty On Electronic Components One Year Warranty On Air Damper

1/2" Foil FacedInsulation

Actuator

Zone Controller

Round DamperBlade Assembly

Control Enclosure(Cover Removed)

AIRFLO

W AIRFLOW

Page 14: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22290-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Use a load program to determine the peak loadfor each zone. These calculations will be used inselecting the appropriate zone damper sizes.

The Meridian Systems utilize a typical low pres-sure duct design. To reduce noise problems,duct pressures should not exceed 1” W.C.

Primary trunk ducts used with Meridian systemsshould not be “undersized”. This is especiallytrue of “pressure dependent” systems. Withpressure independent systems this is not as criti-cal. With larger trunk ducts, it is easier to assurerelatively constant pressure to each ZoneDamper. Runs should be as short as possible,and the trunk duct system kept as symmetricalas possible to facilitate system balancing. Wher-ever possible, run the trunk ducts above corri-dors and locate the Zone Dampers above corri-dors to reduce the noise in the space and facili-tate service of the valves. Trunk ducts should besized for no more than 0.1” W.C. drop per 100 ft.of duct, and a maximum duct velocity of 2000FPM. With pressure independent systems it ispossible to exceed this rule by up to 50%. How-ever it is advised that unless you are experi-enced with VAV duct design the 2000 FPM ruleshould be used.

Zone Damper Selection Data 2ZMD00471xxxx Pressure Independent Zone Damper - FahrenheitZone Damper Round Duct Size

(Area Ft2)6”

(0.188)8”

(0.338)10”

(0.532)12”

(0.769)14”

(1.050)16”

(1.375)

CFM @ 1” Velocity Pressure(Air Flow Probe “K” Factor) 474 950 1417 2120 2908 3700

Velocity Through Zone DamperFPM

Airflow Through Zone Damper - CFM(∆PS inches W.C. w/ Air Damper Full Open)

500 94(0.01)

169(0.01)

266(0.01)

385(0.01)

525(0.01)

687(0.01)

750 141(0.03)

254(0.02)

399(0.01)

577(0.02)

788(0.01)

1031(0.01)

1000 188(0.05)

338(0.03)

532(0.02)

769(0.03)

1050(0.02)

1375(0.01)

1250 235(0.07)

423(0.04)

665(0.03)

961(0.04)

1313(0.03)

1718(0.02)

1500 282(0.09)

507(0.06)

798(0.04)

1154(0.05)

15750.04)

2062(0.03)

1750 329(0.12)

592(0.08)

931(0.06)

1346(0.06)

1838(0.05)

2405(0.04)

2000 376(0.15)

676(0.10)

1064(0.07)

1538(0.07)

2100(0.07)

2749(0.05)

York reserves the right to change specifications without notice

Using the maximum acceptable velocity for a branch duct(typically 1000-1500 FPM for minimal noise), find the small-est damper that will deliver the required CFM as determinedby the load program.

Locate the branch velocity used in the duct design programin the left hand column of the Zone Damper Selection Datatable. Move across the table and find the damper which willprovide the acceptable CFM to meet the zone airflow re-quirements.

Compare the Zone Damper size selectedagainst the duct size to determine if the nextsize up or down will provide acceptable per-formance without requiring a transition fitting.

Pressure Independent Zone Dampers may not be slavedtogether with Slaved-Zone Damper Assemblies. If more thanone damper is required for a zone, all dampers must beselected as pressure dependent. See the PressureDependent Zone Damper submittal sheet and Slaved-ZoneDamper submittal sheets for selection of master/slavedamper configurations.

Page 15: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22291-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

The 2ZMD0047011xxxx series Pressure Inde-pendent Zone Damper for Celsius operation con-sists of a round air valve, zone controller, actua-tor, airflow sensor and a crossflow air pickupprobe. An optional auxiliary relay board(2ZRE0047000024) is available for control of aux-iliary heat and/or control of series or parallel flowfan terminal units.

The Zone Controller (2ZC0047000124) is micro-processor based and communicates with theZone Manager on the Meridian controller networkcommunications loop. The Zone Controller moni-tors the space temperature and allocates theproper airflow into its assigned space to achievethe desired comfort and ventilation levels.

The Pressure Independent Zone Damper is usedin systems that require pressure independentairflow control. If your system does not requirepressure independent control, please see the“2ZMD0047010xxxx series - Pressure DependentZone Damper - Celsius” data sheet for the correctspecifications.

All Zone Dampers are tested and certified inaccordance with ARI standard 880. An ARI labelis affixed to all units.

The Zone Damper assembly should be mounted according to standard duct installation practices with airflow di-rection as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation shouldbe applied around any remaining uninsulated surface on the air valve inlet and outlet. The Zone Damper shouldbe mounted so the control enclosure is positioned to the left or right side of the ductwork with the control enclo-sure in a vertical plane. Do not mount the Zone Damper with the control enclosure on the top or bottom of theductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow forremoval of the control panel cover and access to the controls.

Technical Data 2ZMD0047011xxxx Pressure Independent Zone Damper - CelsiusZone Controller: Air Damper Construction:Supply Power 24 Volt AC Damper Body 24 Ga. Galv. SteelPower Consumption 12 VA Maximum Damper Blade Round -18 Ga. Galv. SteelOperating Temperature 17°C to 52°C Damper Bearings Oil Impregnated BronzeOperating Humidity 90% RH Non-Condensing Damper Seal Volara Type A GasketCommunications RS-485 - 9600 Baud Leakage Less Than 1% @ 3” SP

Insulation ½” Foil Faced FiberglassInputs: Dimensions:Zone Temperature Sensor Air Damper Model “A” “B” “C”Setpoint Adjustment 2ZMD00470110624 (6”) 19.00 5.88 9.38Actuator Position Feedback 2ZMD00470110824 (8”) 19.00 7.88 11.38Air Flow Sensor 2ZMD0047011024 (10”) 19.00 9.88 13.38Outputs: 2ZMD0047011224 (12”) 21.00 11.88 15.38Expansion Port for Auxiliary Relay Board 2ZMD0047011424 (14”) 21.00 13.88 17.38

2ZMD0047011624 (16”) 21.00 15.88 19.38York reserves the right to change specifications without notice

Three Year Warranty On Electronic Components One Year Warranty On Air Damper

1/2" Foil FacedInsulation

Actuator

Zone Controller

Round DamperBlade Assembly

Control Enclosure(Cover Removed)

AIRFLO

W AIRFLOW

Page 16: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22291-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Use a load program to determine the peak loadfor each zone. These calculations will be used inselecting the appropriate zone damper sizes.

The Meridian Systems utilize a typical low pres-sure duct design. To reduce noise problems,duct pressures should not exceed 1” W.C.

Primary trunk ducts used with Meridian systemsshould not be “undersized”. This is especiallytrue of “pressure dependent” systems. Withpressure independent systems this is not as criti-cal. With larger trunk ducts, it is easier to assurerelatively constant pressure to each ZoneDamper. Runs should be as short as possible,and the trunk duct system kept as symmetricalas possible to facilitate system balancing. Wher-ever possible, run the trunk ducts above corri-dors and locate the Zone Dampers above corri-dors to reduce the noise in the space and facili-tate service of the valves. Trunk ducts should besized for no more than 0.1” W.C. drop per 100 ft.of duct, and a maximum duct velocity of 2000FPM. With pressure independent systems it ispossible to exceed this rule by up to 50%. How-ever it is advised that unless you are experi-enced with VAV duct design the 2000 FPM ruleshould be used.

Zone Damper Selection Data 2ZMD0047011xxxx Pressure Independent Zone Damper - CelsiusZone Damper Round Duct Size

(Area Ft2)6”

(0.188)8”

(0.338)10”

(0.532)12”

(0.769)14”

(1.050)16”

(1.375)

CFM @ 1” Velocity Pressure(Air Flow Probe “K” Factor) 474 950 1417 2120 2908 3700

Velocity Through Zone DamperFPM

Airflow Through Zone Damper - CFM(∆PS inches W.C. w/ Air Damper Full Open)

500 94(0.01)

169(0.01)

266(0.01)

385(0.01)

525(0.01)

687(0.01)

750 141(0.03)

254(0.02)

399(0.01)

577(0.02)

788(0.01)

1031(0.01)

1000 188(0.05)

338(0.03)

532(0.02)

769(0.03)

1050(0.02)

1375(0.01)

1250 235(0.07)

423(0.04)

665(0.03)

961(0.04)

1313(0.03)

1718(0.02)

1500 282(0.09)

507(0.06)

798(0.04)

1154(0.05)

15750.04)

2062(0.03)

1750 329(0.12)

592(0.08)

931(0.06)

1346(0.06)

1838(0.05)

2405(0.04)

2000 376(0.15)

676(0.10)

1064(0.07)

1538(0.07)

2100(0.07)

2749(0.05)

York reserves the right to change specifications without notice

Using the maximum acceptable velocity for a branch duct(typically 1000-1500 FPM for minimal noise), find the small-est damper that will deliver the required CFM as determinedby the load program.

Locate the branch velocity used in the duct design programin the left hand column of the Zone Damper Selection Datatable. Move across the table and find the damper which willprovide the acceptable CFM to meet the zone airflow re-quirements.

Compare the Zone Damper size selectedagainst the duct size to determine if the nextsize up or down will provide acceptable per-formance without requiring a transition fitting.

Pressure Independent Zone Dampers may not be slavedtogether with Slaved-Zone Damper Assemblies. If more thanone damper is required for a zone, all dampers must beselected as pressure dependent. See the PressureDependent Zone Damper submittal sheet and Slaved-ZoneDamper submittal sheets for selection of master/slavedamper configurations.

Page 17: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22292-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

The 2ZSD00470xxxx Slaved-Zone DamperAssembly, consists of a round air valve, ac-tuator, (1) slave wiring interface cardmounted in the enclosure. It also includes (1)slave wiring interface card kit shipped loosefor field mounting to the master zone damperassembly. This kit contains a slave wiringinterface card and a cable.

The Slaved-Zone Damper, is used in sys-tems when it is not possible or practical touse a single large Zone Damper to satisfythe zones CFM requirements.

A total of two Slaved-Zone Dampers may beused in conjunction with a master ZoneDamper. The Slave Damper(s) are wired inparallel with the master Zone Damper andtrack the movement of the master ZoneDamper. Connection of the master ZoneDamper requires a slave wiring interface kitwhich is shipped loose for field mounting tothe master Zone Damper and is suppliedwith each Slaved-Zone Damper. The kit con-nects the Zone controller on the master tothe master actuator and provides wiring ter-minals for wiring to the Slaved-Zone Damp-ers. Only (1) of these kits is required for eachmaster/slave installation.

All Slaved-Zone Dampers are tested andcertified in accordance with ARI standard880. An ARI label is affixed to all units.

The Slaved-Zone Damper Assembly should be mounted according to standard duct installation practices with airflow direction as shown in the illustration above. After installation of the Air Damper in the ductwork, insulationshould be applied around any remaining uninsulated surface on the air valve inlet and outlet. The Air Dampershould be mounted so the control enclosure is positioned to the left or right side of the ductwork with the controlenclosure in a vertical plane. Do not mount the Air Damper Assembly with the control enclosure on the top orbottom of the ductwork. Adequate clearance should be maintained between the control panel and any obstructionto allow for removal of the control panel cover and access to the controls.

Technical Data 2ZSD00470xxxx Slaved-Zone DamperActuator: Air Damper Construction:Supply Power 24 Volt AC Damper Body 24 Ga. Galv. SteelPower Consumption 3.4 VA Maximum Damper Blade Round -18 Ga. Galv. SteelOperating Temperature 35°F to 125°F Damper Bearings Oil Impregnated BronzeOperating Humidity 90% RH Non-Condensing Damper Seal Volara Type A GasketPosition Feedback (Bypass) 10Kohm, 1 W Potentiometer Leakage Less Than 1% @ 3” SP

Insulation ½” Foil Faced FiberglassDimensions:Air Damper Model “A” “B” “C” Air Damper Model “A” “B” “C”2ZSD004700624(6”) 19.00 5.88 9.38 2ZSD004701224(12”) 21.00 11.88 15.382ZSD004700824(8”) 19.00 7.88 11.38 2ZSD004701424(14”) 21.00 13.88 17.382ZSD004700824(10”) 19.00 9.88 13.38 2ZSD004701624(16”) 21.00 15.88 19.38York reserves the right to change specifications without noticeThree Year Warranty On Electronic Components One Year Warranty On Air Damper

1/2" Foil FacedInsulation

Actuator

Round DamperBlade Assembly

Control Enclosure(Cover Removed)

AIRFLO

W AIRFLOW

Bypass & Slave Interface

Page 18: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22292-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Use a load program to determine the peak load foreach zone. These calculations will be used in se-lecting the appropriate Zone and Slaved-ZoneDamper sizes. Only pressure dependent ZoneDampers may be slaved.

The Meridian Systems utilize a typical low pres-sure duct design. To reduce noise problems, ductpressures should not exceed 1” W.C.

Primary trunk ducts used with Meridian systemsshould not be “undersized”. With larger trunkducts, it is easier to assure relatively constantpressure to each Zone Damper. Runs should beas short as possible, and the trunk duct systemkept as symmetrical as possible to facilitate sys-tem balancing. Wherever possible, run the trunkducts above corridors and locate the master Zoneand Slaved-Zone Dampers above corridors to re-duce the noise in the space and facilitate serviceof the valves. Trunk ducts should be sized for nomore than 0.1” W.C. drop per 100 ft. of duct, and amaximum duct velocity of 2000 FPM.

Up to a maximum of two additional Slaved-ZoneDampers may be connected together with themain Zone Damper(s) for large zone air flow re-quirements. This design should be reserved onlyfor situations when it is not practical to use a singlelarge Zone Air Damper.

It is recommended that the Slaved-Zone Damper(s) shouldbe of the same size as the master Zone Damper. This in-sures that adequate air flow and minimum noise will occurat all damper positions.

Divide the total zone CFM required by the total number ofair valves to be used.

Using the maximum acceptable velocity for a branch duct(typically 1000-1500 FPM for minimal noise), go to the AirDamper Selection Data Chart below and find the quantityand size of Air Dampers that will deliver the required CFMas determined by the load program

Compare the Zone and Slaved-Zone Dampersizes selected against the branch duct sizes todetermine if the next size up or down will pro-vide acceptable performance without requiringa transition fitting.

Order one 2ZMD004701XXX Pressure Dependent ZoneDamper of the size selected previously. Order one or two2ZSD00470XXXX Slaved-Zone Dampers as required, ofthe same size as the 2ZMD004701XXX Zone Damper justselected. The Slaved-Zone Dampers will track and maintainthe same damper position as the master Zone Damper.

Air Damper Selection Data 2ZSD00470XXXX Slaved-Zone Damper(Pressure Dependent Only)

Zone Air Damper Round Duct Size(Area Ft2)

6”(0.188)

8”(0.338)

10”(0.532)

12”(0.769)

14”(1.050)

16”(1.375)

Velocity Through Zone Air DamperFPM

Airflow Through Zone Air Damper - CFM(∆PS inches W.C. w/ Air Damper Full Open)

500 94(0.01)

169(0.01)

266(0.01)

385(0.01)

525(0.01)

687(0.01)

750 141(0.03)

254(0.02)

399(0.01)

577(0.02)

788(0.01)

1031(0.01)

1000 188(0.05)

338(0.03)

532(0.02)

769(0.03)

1050(0.02)

1375(0.01)

1250 235(0.07)

423(0.04)

665(0.03)

961(0.04)

1313(0.03)

1718(0.02)

1500 282(0.09)

507(0.06)

798(0.04)

1154(0.05)

15750.04)

2062(0.03)

1750 329(0.12)

592(0.08)

931(0.06)

1346(0.06)

1838(0.05)

2405(0.04)

2000 376(0.15)

676(0.10)

1064(0.07)

1538(0.07)

2100(0.07)

2749(0.05)

York reserves the right to change specifications without notice

Page 19: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22293-001 Rev. A (0602) Supersedes: Nothing Page 1 of 2

The Meridian 1ZRD00470xxxx Series Rectan-gular Damper is used in applications whererectangular duct is specified or required be-cause of space limitations or job requirements.The Rectangular Damper utilizes opposedblades of airfoil design for improved air flowcontrol. The Rectangular Damper frame is madeof .080 thick extruded aluminum. The blades arealso made of extruded aluminum. Blade pins are7/16” hexagon shaped aluminum fixed to a Cel-con inner bearing rotating within a polycarbonateouter bearing inserted in the damper frame. TheDamper linkage is mechanically assembled andlocated in the damper frame . The linkage com-ponents are constructed of aluminum, zinc andnickel plated steel. Blade gaskets are made ofextruded EPDM material and are secured withinan integral slot on the blade. Jamb seals are ofextruded TPE material for low leakage throughthe damper when closed. The control shaft is1/2” diameter hexagon shaped rod and can beextended 9” past the damper frame for connec-tion to the damper actuator. The damper shaft isshipped retracted into the frame area and mustbe adjusted to the required length in the field.

The Rectangular Damper should be mounted inthe ductwork according to standard duct instal-lation practices. The rectangular damper shouldbe selected for the nominal inside duct size (SeeFigure 3). All Rectangular Dampers are supplied with 1” flanges all around damper frame, making the overalldamper width and height 2” larger than the nominal inside duct size thus providing for external flange mounting toductwork. The damper shaft is shipped retracted into the damper frame. Loosen the two nuts on the U-bolt thatsecures the damper shaft to the damper blade and adjust to length. It is recommended that the shaft length beadjusted so approximately 4” of shaft extends beyond the inside of the damper frame. Retighten the two nuts onthe U-bolt that secures the damper shaft to the blade. After installation of the Rectangular Damper to the duct-work, it is recommended that insulation be applied around any non-insulated surface on the ductwork where theRectangular Damper was installed.

Use a load program to determine the peak load for each zone. These calculations will be used in selecting theappropriate Rectangular Damper sizes. The Meridian Systems utilize a typical low pressure duct design. To re-duce noise problems, duct pressures should not exceed 1” W.C.

Primary trunk ducts used with Meridian systems should not be “undersized”. This is especially true of “pressuredependent” systems. With pressure independent systems this is not as critical. With larger trunk ducts, it is easierto assure relatively constant pressure to each Rectangular Damper. Runs should be as short as possible, and thetrunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunkducts above corridors and locate the Rectangular Dampers above corridors to reduce the noise in the space andfacilitate service of the valves. Trunk ducts should be sized for no more than 0.1” W.C. drop per 100 ft. of duct,and a maximum duct velocity of 2000 FPM.

Dimensional Data

Opposed Blade ProfileFlanged to Duct Installation

Page 20: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22293-001 Rev. A (0602) Supersedes: Nothing Page 2 of 2

Using the maximum acceptable velocity for abranch duct (typically 1000-1500 FPM forminimal noise), find the smallest damper thatwill deliver the required CFM as determined bythe load program.

Locate the required CFM on the RectangularDamper Selection Data table below. This tableis based on an airflow velocity of 1000 FPMacross the damper. This is the recommendedvelocity for quiet operation and normal pres-sure drop through the damper.

1ZRD00470xxxx Rectangular Damper Selection DataDamperHeight

“B”8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36”

DamperWidth

“A”

Airflow Data with Full Open DamperCFM @ 1000 FPM Velocity

(∆PS - inches W.C. @ 1000 FPM Velocity)

8” 410(0.16)

530(0.10)

640(0.07)

740(0.05)

850(0.04)

970(0.03)

1080(0.03)

1190(0.02)

1300(0.02)

1410(0.02)

1520(0.01)

1630(0.02)

1740(0.01)

1850(0.01)

1970(0.01)

10” 510(0.10)

590(0.07)

690(0.05)

800(0.03)

910(0.03)

1030(0.02)

1150(0.02)

1260(0.01)

1380(0.01)

1500(0.01)

1610(0.01)

1730(0.01)

1840(0.01)

2000(0.01)

2080(0.01)

12” 560(0.07)

650(0.05)

730(0.03)

850(0.02)

970(0.02)

1090(0.01)

1210(0.01)

1330(0.01)

1460(0.01)

1580(0.01)

1700(0.01)

1820(0.01)

1940(-)

2060(-)

2190(-)

14” 660(0.05)

770(0.03)

880(0.02)

1030(0.02)

1180(0.01)

1330(0.01)

1480(0.01)

1630(0.01)

1760(0.01)

1910(0.01)

2060(-)

2210(-)

2360(-)

2510(-)

2640(-)

16” 750(0.04)

890(0.03)

1030(0.02)

1200(0.01)

1370(0.01)

1540(0.01)

1710(0.01)

1880(0.01)

2060(-)

2230(-)

2400(-)

2570(-)

2740(-)

2910(-)

3090(-)

18” 770(0.03)

980(0.03)

1180(0.01)

1380(0.01)

1580(0.01)

1780(0.01)

1980(0.01)

2180(-)

2350(-)

2550(-)

2750(-)

2950(-)

3150(-)

3350(-)

3540(-)

20” 850(0.03)

1090(0.02)

1330(0.01)

1550(0.01)

1770(0.01)

1990(0.01)

2210(-)

2430(-)

2650(-)

2870(-)

3090(-)

3310(-)

3530(-)

3750(-)

3990(-)

22” 930(0.02)

1210(0.01)

1480(0.01)

1730(0.01)

1980(0.01)

2230(-)

2480(-)

2730(-)

2950(-)

3200(-)

3450(-)

3700(-)

3950(-)

4200(-)

4440(-)

24” 950(0.02)

1290(0.01)

1630(0.01)

1900(0.01)

2170(-)

2440(-)

2710(-)

2980(-)

3250(-)

3520(-)

3790(-)

4060(-)

4330(-)

4600(-)

4880(-)

26” 990(0.02)

1390(0.01)

1780(0.01)

2080(0.01)

2380(-)

2680(-)

2980(-)

3280(-)

3550(-)

3850(-)

4150(-)

4450(-)

4750(-)

NA NA

28” 1070(0.01)

1500(0.01)

1930(0.01)

2250(-)

2570(-)

2890(-)

3210(-)

3530(-)

3850(-)

4170(-)

4500(-)

4820(-)

NA NA NA

30” 1020(0.01)

1550(0.01)

2080(0.01)

2430(-)

2780(-)

3130(-)

3480(-)

3830(-)

4150(-)

4500(-)

4850(-)

NA NA NA NA

32” 1090(0.01)

1660(0.01)

2230(-)

2600(-)

2970(-)

3340(-)

3710(-)

4080(-)

4450(-)

4820(-)

NA NA NA NA NA

34” 1150(0.01)

1770(0.01)

2380(-)

2780(-)

3180(-)

3580(-)

3980(-)

4370(-)

4750(-)

NA NA NA NA NA NA

36” 1060(0.01)

1790(0.01)

2520(-)

2670(-)

3090(-)

3510(-)

3930(-)

4350(-)

5040(-)

NA NA NA NA NA NA

York reserves the right to change specifications without notice

Notes:1. The table above is calculated based on 1000 FPM velocity across the full open damper. For other velocities use the

following multipliers to obtain the correct CFM: 500 FPM = 0.5, 1500 FPM = 1.5, 2000 FPM = 2.0. It is recommendedthe damper velocity does not exceed 1500 FPM for quiet operation.

2. Pressure drop (∆PS) is based on 1000 FPM Velocity. Any pressure drop less than 0.01” W.C. is shown as (-).

When space considerations or design criteria dictate, dampersmay be selected for other face velocities by using the multipli-ers listed in the notes associated with the table. Move acrossthe table and find the damper selection which will provide therequired CFM and fit within the ceiling area where the damperwill be located. Many size selections are possible for a givenCFM. Pressure drop across the damper is shown in parenthe-sis below the CFM.

Page 21: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22294-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The York Meridian 2ZDK0047000741Rectangular Bypass Damper Kit mounts toa Rectangular Damper and controls ductstatic pressure to insure proper system air-flow. The Rectangular Bypass Damper iscontrolled by the Meridian System ZoneManager. The Zone Manager modulatesthe Rectangular Bypass Damper in re-sponse to the duct static pressure basedon a signal received from a static pressuresensor located in the main system duct-work.

The Rectangular Bypass Damper Kit isused in conjunction with rectangular damp-ers for applications where rectangulardampers are specified or required becauseof space limitations or job requirements.The rectangular dampers may be pur-chased from York or you may get themfrom the supplier of your choice. For propercontrol, York recommends the use of lowleakage opposed blade dampers. Themaximum allowable damper face area forthe Rectangular Bypass Damper Kit is 6 sq.ft. The Rectangular Bypass Damper Kitcomes packaged with the Damper Actuatorand Wiring Interface pre-mounted in a gal-vanized steel enclosure. Each kit is sup-plied with mounting hardware and installa-tion instructions. For applications that dic-tate the use of more than a single bypass damper, up to 2 additional bypass dampers can be slaved together. Noother components are required. Each bypass is wired to the other bypass damper(s) by means of the Wiring In-terface.

Before mounting the Rectangular Damper Kit, the rectangular damper should be mounted in the ductwork ac-cording to standard duct installation practices. The damper should be mounted so the damper shaft turns in aclockwise direction to open the damper. The Rectangular Damper Kit is simply slid over the damper shaft, theactuator shaft collar setscrews tightened and the supplied self tapping screws are used to mount the enclosure tothe ductwork. Detailed mounting and installation instructions are provided with each kit. A knockout is provided inthe front access cover which can be punched out to allow for damper shaft lengths which extend past the enclo-sure depth. When mounting the Rectangular Damper Kit, be sure to allow clearance for removal of the accesscover. Conduit knockouts are provided in the top and bottom of the enclosure for simplified wiring.

Technical Data 2ZDK0047000741 - Rectangular Bypass Damper KitSupply Power 24 Volt AC Enclosure Base 22 Ga. Galv. SteelPower Consumption 3.0 VA Maximum Enclosure Cover 22 Ga. Galv. SteelOperating Temp -22°F(-97°C) to 122°F(50°C) Conduit Openings Top - (2) ½ & ¾” Comb. KnockoutsOperating Humidity 90% RH Non-Condensing Bottom - (2) ½ & ¾” Comb. KnockoutsActuator Feedback 10Kohm, 1W Potentiometer Shaft Clearance Front - (1) ½ & ¾” Comb. KnockoutActuator Rating 35 in/lbs (6 ft2 Damper Area Max.) Controls Factory Mounted Inside EnclosureMounting Hardware (4) Self Tapping Screws Controls Access Cover is Removable byInstructions Included with Each Kit Loosening 2 ScrewsYork reserves the right to change specifications without noticeThree Year Warranty

13.5

8.0

12.15

5.75

Dimensional Data

Component View

Page 22: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22295-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The York Meridian 2ZDK0047000740 Rec-tangular Zone Damper Kit provides a newsolution for rectangular zone damper appli-cations. The new Rectangular Damper Kit isused in conjunction with rectangular dampersfor applications where rectangular dampersare specified or required because of spacelimitations or job requirements. The rectan-gular dampers may be purchased from Yorkor you may get them from the supplier ofyour choice. For proper control, York rec-ommends the use of low leakage opposedblade dampers. The maximum allowabledamper face area for the RectangularDamper Kit is 6 sq. ft. The RectangularDamper Kit comes packaged with the ZoneController and Damper Actuator pre-mounted in a galvanized steel enclosure.Each kit is supplied with mounting hardwareand installation instructions.

Before mounting the Rectangular DamperKit, the rectangular damper should bemounted in the ductwork according to stan-dard duct installation practices. The dampershould be mounted so the damper shaftturns in a clockwise direction to open thedamper. The Rectangular Damper Kit is sim-ply slid over the damper shaft, the actuatorshaft collar setscrews tightened and the sup-plied self tapping screws are used to mountthe enclosure to the ductwork. Detailedmounting and installation instructions areprovided with each kit. A knockout is provided in the front access cover which can be punched out to allow fordamper shaft lengths which extend past the enclosure depth. When mounting the Rectangular Damper Kit, besure to allow clearance for removal of the access cover. Conduit knockouts are provided in the top and bottom ofthe enclosure for simplified wiring installation.

Technical Data 2ZDK0047000740 - Rectangular Zone Damper KitZone Controller: Damper Kit Features:

Supply Power 24 Volt AC Enclosure Base 22 Ga. Galv. SteelPower Consumption 12 VA Maximum Enclosure Cover 22 Ga. Galv. SteelOperating Temperature 10°F(-12°C) to 149°F (65°C) Conduit Openings Top - (2) ½ & ¾” Comb. KnockoutsOperating Humidity 90% RH Non-Condensing Bottom - (2) ½ & ¾” Comb. KnockoutsCommunications RS-485 - 9600 Baud Shaft Clearance Front - (1) ½ & ¾” Comb. Knockout

Inputs: Controls Factory Mounted inside the EnclosureZone Temperature Sensor Mounting Hardware Supplied with (4) Self Tapping ScrewsSetpoint Adjustment Instructions Included with Each KitActuator Position Feedback Controls Access Cover is Removable by

Outputs: Loosening 2 ScrewsExpansion Port for Auxiliary Relay Board Actuator Rating 35 in/lbs (6 ft2 Damper Area Max.)York reserves the right to change specifications without notice

Three Year Warranty

13.5

8.0

12.15

5.75

Dimensions

Component View

Page 23: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22296-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The York Meridian 2ZDK0047000739 Rectangu-lar Slaved-Zone Damper Kit provides a new solu-tion for rectangular damper applications. TheRectangular Slaved-Zone Damper Kit is used inconjunction with rectangular dampers for applica-tions in systems when it is not possible or practi-cal to use a single large Rectangular Zone AirDamper to satisfy the zones CFM requirements.

The rectangular dampers may be purchased fromYork or you may get them from the supplier ofyour choice. For proper airflow control, York rec-ommends the use of low leakage opposed bladedampers. The Rectangular Slaved-Zone DamperKit is supplied with the slave wiring interface cardand actuator factory mounted in a sheet metalenclosure. A total of two Slaved-Zone Air Damp-ers may be used in conjunction with a masterRectangular Zone Damper Kit. The RectangularSlaved-Zone Air Damper(s) are wired in parallelwith the master Rectangular Zone Damper Kit andtrack the movement of the master RectangularZone Damper. Connection to the master Rectan-gular Zone Damper Kit requires a Slave WiringAdapter Kit, part #2ZWA004700124 which is sup-plied with each Rectangular Slaved-Zone DamperKit. The kit connects the zone controller on themaster to the master actuator and provides wiringterminals for wiring to the Rectangular Slaved-Zone Damper Kit(s). Only one Slaved Wiring Kit isrequired for each Slaved-Zone system. Each kit issupplied with mounting hardware and installation instructions.

The rectangular damper should be mounted in the ductwork according to standard duct installation practices be-fore installing the Rectangular Slaved-Zone Damper Kit. The Rectangular Slaved-Zone Damper Kit is simply slidover the damper shaft, the actuator shaft collar setscrews tightened and the supplied self tapping screws are usedto mount the enclosure to the ductwork. Detailed mounting and installation instructions are provided with each kit.A knockout is provided in the front access cover which can be punched out for damper shaft lengths which extendpast the enclosure depth. When mounting the Rectangular Slaved-Zone Damper Kit, be sure to allow clearancefor removal of the access cover. Conduit knockouts are provided in the top and bottom of the enclosure for sim-plified wiring installation.

Technical Data 2ZDK0047000739 - Rectangular Slaved-Zone Damper KitActuator: Damper Kit Features:

Supply Power 24 Volt AC Enclosure Base 22 Ga. Galv. SteelPower Consumption 3.4 VA Maximum Enclosure Cover 22 Ga. Galv. SteelOperating Temperature 10°F(-12°C) to 149°F (65°C) Conduit Openings Top - (2) ½ & ¾” Comb. KnockoutsOperating Humidity 90% RH Non-Condensing Bottom - (2) ½ & ¾” Comb. Knockouts

Shaft Clearance Front - (1) ½ & ¾” Comb. KnockoutInputs: Controls Factory Mounted inside the Enclosure

Actuator Position Feedback Mounting Hardware Supplied with (4) Self Tapping ScrewsInstructions Included with Each KitControls Access Cover is Removable by

Loosening 2 ScrewsActuator Rating 35 in/lbs (6 ft2 Damper Area Max.)

Three Year Warranty York reserves the right to change specifications without notice

13.5

8.0

12.15

5.75

Dimensional Data

Component View

Page 24: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22297-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The York Meridian 2ZDA00470024Damper Actuator is a shaft mounted,floating point control actuator. Actuatorsare 24VAC/24VDC with a 10Kohm feed-back signal for position monitoring.Wiring connection to the actuator is bymeans of a modular phone cable con-nector located on the actuator cover. Theactuator is rated for 35 in-lb of torque. Allactuators are electronically protectedagainst overload. The angle of rotation ismechanically limited to 95°. When theend position of the actuator or damper isreached, the actuator automaticallystops. For adjustment purposes, thegears can be manually disengaged bypushing the manual override button onthe actuator cover.

The actuator is mounted and adjusted inthe following manner:1. Turn the damper blade to its fully

closed position.2. With the manual override button de-

pressed, rotate the actuator clamp toabout 1/16” to 1/8” between the ac-tuator stop and the clamp, depend-ing on the damper seal design. Slidethe actuator over the shaft and fingertighten the nuts.

3. Slide the L-type anti-rotation bracket(supplied) up under the actuatorcenter cut-out on the back of theactuator. Secure the bracket with thesupplied self-tapping screws. Tightenthe two nuts on the actuator shaftclamp with an 8mm wrench to 3 to 5ft-lbs.

4. Adjust the end stops, if required.

Technical Data 2ZDA00470024Damper Actuator

Power Supply 24VAC ± 20% 50/60HZ Angle of Rotation Max. 95°, AdjustableLife Cycle Rating 2.5 Million Cycles with Mechanical StopsPower Consumption 3 VA Maximum Power Connection RJ-11 Modular PlugOperating Temp 22°F(-97°C) to 122°F(50°C) Servicing Maintenance FreeOperating Humidity 5 to 95% RH Non-Condensing Quality Standard ISO 9001Overload Protection Electronic Throughout 0 to 95°

RotationAgency Listings UL873 listed

CSA 4813 02 CertifiedFeedback Signal 10Kohm, 1 W potentiometer Torque Minimum 35 in-lbRunning Time 80-110 Seconds. Weight 1.2 lb.York reserves the right to change specifications without notice

Three Year Warranty

10

2.56“

4.53

1 .28 “

0.85

3.68

2 .32“

2.57“

OE282Y

York# 2ZDA004700124A

Page 25: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22298-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The Zone Controller Board is used tocontrol the zones on a Meridian Basic orPlus System. The 2ZZC004700024 is theFahrenheit version of the controller. The2ZZC004700124 is the Celsius version ofthe controller. The Zone Controller is mi-croprocessor based and communicateswith the Zone Manager on the Meridiannetwork communications loop. The2ZZC004700xxx Zone Controller Con-nects to the 2ZDA00470024 Damper Ac-tuator via a modular cable. The ZoneController monitors the space tempera-ture and modulates the Damper Actuatorallocating the proper airflow into its as-signed space to achieve the desiredcomfort and ventilation levels.

The Zone Controller Board is designed tobe used as a pressure dependent controlor with the addition of an optional airflowsensor connected to the modular con-nector on the board it can be used forpressure independent control applica-tions.

An optional 2ZRE0047001024 - 4 RelayOutput Expansion board is available forcontrol of auxiliary heat, box heat and/orcontrol of series or parallel flow fan termi-nal units. The 4 Relay Output ExpansionBoard connects to the 2ZZC004700xxxseries Zone Controller board by means ofa modular cable provided with the 4 RelayOutput Expansion Board.

The 2ZZC004700xxx Zone Controller Board is supplied mounted on a plastic Snap Track channel. The SnapTrack channel has two mounting holes which are used to field mount the board with the provided screws. Theboard should be mounted in close proximity to the Damper Actuator to allow for connection of the modular cableto the actuator.

Technical Data 2ZZC004700xxxZone Controller Board

Operating Power: 24VAC Power Consumption: 10 VA MaximumOperating Temp: 10°F(-12°C) to 149°F (65°C) Operating Humidity: 90% RH Non-CondensingCommunications: RS-485 9600 Baud Weight : 0.50 lb.

Inputs: Outputs:Room Sensor Airflow Sensor (P.I. Only) Expansion Port: Modular Cable to Expansion BoardActuator Feedback Signal Setpoint Slide Adjust Actuator Port: Modular Cable to Damper ActuatorYork reserves the right to change specifications without notice

3 Year Warranty

7.0

0"

4.00"C

X6

SW

1

U10

75176

EX

PA

NS

ION

Q3

Q2

D3

VR

17824

GND

24VAC

M

7824CT

MC34064A

9936

R17

R16

U7

C7

R15

PO

WE

RR

21

RE

V.2

YS

101

562

MDL

F1

250D4

R26

LD3

L1

SCAN REC

R12

C6

R11

TOKEN

NET

LD

2

32

R14

R13

R100

LD

1

C5

D1

K1

V2

fTimes NewRoman|b0|i0|c0|p18;G5L-114P-PS24VDCCONTACT:UL / CSA 5A250VAC

fTimes NewRoman|b0|i0|c0|p18;OMRON

K2

D2

AC

TU

AT

OR

fTimes NewRoman|b0|i0|c0|p18;OMRON

fTimes NewRoman|b0|i0|c0|p18;G5L-114P-PS24VDCCONTACT:UL / CSA 5A250VAC

R10

R9

PJ2

V1

C4

AZ

ZO

NE

V4

.00

FC

09

4

74H

C573N

B31920P

S

TC

U3

2K

2V

9936

MS

6264L-7

0P

C

EPROM

VR

EF

AD

J

R23

C10

PC

B8

0C

55

2-5

-16

WP

50

06

50

=1

/3D

FD

99

40

SM

PH

ILIP

S

EW

DO

G

CO

MM

D7

CX10

R25

R2

8

T'STAT U

11

C15

R2

0

C11

R24

8

16

2

4

ADDRESS ADD

1 U6

93C

46

U5

R1

9

PH

ILIP

S

U9CX9

R32

D5

C14

P.U.

R22

C13

LM

C6

62

R2

7

D5

RAM

C9

C8

80C552

CX

5P

J1

C3

R8

R7

R5

R6

R4

C2

C1

X1 74H

C259

B31920P

S

U2

R1

R2

R3

CX2

Q1

16L8

32K

R34FLOW

U8

1

RN1

CX8 U4R

18 CX4

8KRAM

U3

CX3

U1

CX1

Zone Controller Board

Snap Track

Page 26: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22299-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The 2ZRE0047000024 - 4 Relay OutputModular Expansion Board is used inconjunction with the 2ZZC00470024 –Zone Controller Board to allow for controlof auxiliary heat, box heat, series andparallel fan terminal units. The Relay Ex-pansion Board provides 4 relay outputsfor pilot duty switching control.

The 4 Relay Output Expansion Boardconnects to the Zone Controller board bymeans of a modular cable provided withthe 4 Relay Output Expansion Board.24VAC power is supplied to the board bymeans of this modular cable. Screw ter-minals are provided for connection of fieldwiring to the relay outputs.

The relay outputs are N.O. contacts withone common terminal. All outputs and therelay common are electrically isolatedfrom all other circuitry on the board. Allrelay outputs are supplied with transientsuppression devices across each set ofcontacts to reduce EMI and arcing. Therelay output contacts are rated for pilotduty control of a maximum of 2 Amps @24 VAC or 24 VDC.

The Relay Output Expansion Board issupplied mounted on a plastic SnapTrack channel. The Snap Track channelhas two mounting holes which are used tofield mount the board with the providedscrews. The board should be mounted inclose proximity to the Zone Controllerboard to allow for connection of themodular cable,

Technical Data 2ZRE0047000024 – 4 Relay OutputExpansion Board

Operating Power 24VAC Power Consumption 10 VA MaximumOperating Temp 10°F to 149°F Operating Humidity 90% RH Non-CondensingWeight 0.25 lb Connection to Controller: Modular Cable

Outputs:Relay Qty. 4 – Electrically Isolated Relay Contact Rating 2 Amp @ 24 VACYork reserves the right to change specifications without notice

3 Year Warranty

G5L-114P-PS

24VDC

CONTACT:

UL / CSA 5A250VAC

OMRON

Q1

D1 K

1

R1

R2

R3

V1

Q2

R4

R5

R6

D2

G5L-114P-PS

24VDC

CONTACT:

UL / CSA 5A250VAC

OMRON V2

R9

R8

R7

Q3

D3

G5L-114P-PS

24VDC

CONTACT:

UL / CSA 5A250VAC

OMRON V3

CR1

CR2

CR3

M

7824C

T

VR1

D5

YS

-10

15

43

RE

V.2

C1

V5

1

2

3

4

TB1

G5L-114P-PS

24VDC

CONTACT:

UL / CSA 5A250VAC

Q4

R10

R11

CR4R9

D4

OMRON

V4

4

1

2

3

4

K4

C2

COM

4.0

0"

3.00"

4 Relay Output Board

Snap Track

Page 27: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22274-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

The patented design of the York Meridian RoomSensor provides accurate sensing of the roomtemperature. Its design allows for flush wallmounting yet rejects the influence of surface andinternal wall temperatures. The Room Sensor’sattractive styling and off white casing color make itsuitable for most building decors. If interior deco-ration requires, the Zone Sensor casing can alsobe painted or wall papered without affecting thesensor's performance. Room Sensors are avail-able in 4 different configurations:

• 2ZTS004704024 - Sensor Plain• 2ZTO004704024 - Sensor with Setpoint

Adjustment• 2ZTA004704124 - Sensor with Override• 2ZTB004704124 - Sensor with Setpoint

Adjustment and Override

The Room Sensor Plain and Room Sensor withOverride, require (2) wires to be connected fromthe controller to the sensor. The Room Sensorwith setpoint adjustment and Zone Sensor withSetpoint and Override options, require 3 wires beconnected to the sensor. Twisted cable is rec-ommended for wiring of all Room Sensors. Wiringshould not be run in conduit with other AC linevoltage wiring, or with any conductors carryinghighly inductive loads. Most applications do notrequire shielding.

The Room Sensors are designed to be mounted on a vertical, 2” x 4” electrical box recessed in the wall. If the wallcannot be penetrated, a plastic surface mount box such as those made by Wiremold, may be used to mount thesensor to the wall surface.

TechnicalData

2ZTS004704024, 2ZTO004704024, 2ZTA004704124,2ZTB004704124 Room Sensors

Sensor Element Type III Thermistor 10k ohm @ 77º F

Mounting Designed to be Flush Mounted to Wallusing Vertical 2” x 4” Handy Box (by others)

Accuracy ±0.4º F between 30º F to 150º F Line Loss 0.25º F max. error, using 22 AWG wire at 1000 ft.Range -30º F to 150º F Weight 4 oz.York reserves the right to change specifications without notice

Three Year Warranty

OE210 OE211 OE212 OE213

Room Sensor - Plain Room SensorWith Override

Room SensorWith Setpoint Adjust

Room SensorWith Setpoint Adjust

& Overide

O O

A A

O O

R R

L L

M M

E E

E E

C C

W W

R R

R R

OVR OVR

0.25“

TMP

GND

AUXOUT

2.7

5“

2.00“

Wall Cut-Out DimensionsWhen Sensor Is To BeMounted WithoutHandy Box (By Others)

2.75“

3.2

5“

4.5

0“

2.5

0"

0.88“

O

A

O

R

L

M

E

E

C

W

R

R

Page 28: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Duct Temperature Sensor - 2ZDS0047002242ZDS004700124 &

Mounting Plate

Gasket

Adhesive Backed Drill GuideMounting Template

Mounting Plate

4.0"

3/4"

1/4" Hex Head Sheet Metal Screws

ThreadTogether

Duct Work

Drill 5/16" Hole In Ductwork For Probe

Leads Are Non-polarized.Butt Splice Leads To 24 GaugeWire Minimum. Connect LeadsTo "Analog In" And "Ground"At Controller.

Notes:

1.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.

Temperature Sensor Resistance/Voltage Chart

Temp Resistance* Voltage

F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.39010..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605

Temp Resistance* Voltage

F Ohms @ Input*

45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810

Temp Resistance* Voltage

F Ohms @ Input*

69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407

Temp Resistance* Voltage

F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469

125............3656..........1.369

*Chart Notes:1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).

2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltageis above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.

The Duct Sensor Is Used For Sensing SupplyOr Return Air Temperatures. Location Of TheSensors Is Very Important In Order To ObtainAccurate Temperature Readings. TheFollowing Recommendations Should BeFollowed:

When Used As A Supply Air Sensor TheSensor Should Be Mounted In The Supply AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.

Supply Air

Return AirWhen Used As A Return Air Sensor TheSensor Should Be Mounted In The Return AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.

See The Systems Installation And OperationManual For Other Design Considerations AndRecommendations Regarding DuctTemperature Sensor Location.

Caution!

FILENAME

JOB NAME

DESCRIPTION:

6" & 12" Duct Sensor

2ZDS004700124 & 2ZDS004700224

DATE DRAWN:

PAGE

1 of 1

B. CREWSDRAWN BY:

11-1/2" ( )2ZDS004700224

5-1/2" ( )2ZDS004700124

036-22275-001-A-0602.CDR

06/28/02

Form: 036-22275-001 Rev. A (0602) Supersedes: Nothing

Page 29: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

4.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.

3.)Gasket Must Be Installed Under CoverPlate To Provide Raintight Seal.Rainwater Can Damage Sensor!

Temperature Sensor Resistance/Voltage Chart

Temp Resistance* Voltage

F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.39010..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605

Temp Resistance* Voltage

F Ohms @ Input*

45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810

Temp Resistance* Voltage

F Ohms @ Input*

69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407

Temp Resistance* Voltage

F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469

2.)Unused Conduit Opening(s) MustHave Closure Plugs Installed And MustBe Coated with Sealing Compound ToProvide Raintight Seal. Water CanDamage Sensor!

1.)The Outside Air Sensor Must BeMounted In A Vertical Position AsShown (Sensor Tube PointingDown).

Sensor Must Be LocatedWhere It Will Not Be Affected ByDirect Sunlight Or Heat ProducingEquipment. If Possible Mount UnderRoof Eave Or Similar ProtectedLocation. If Sensor Is Not LocatedAs Specified, Erroneous Outside AirTemperature Readings Will Result.

Water Must Not BeAllowed To Stand In SensorTube. Rainwater Will DamageSensor.

*Chart Notes:1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).

2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DCvolts. Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. Ifthe voltage is above 5.08 VDC, then the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor orwiring is shorted.

Outside Air Sensor - OE250Y

Notes:

Closure PlugCAUTION!See Note 2

Gasketed CoverCAUTION!See Note3

CoverMountingScrew - Typ.

Mounting Tab& Screw - Typ.

0.21" Dia. x 0.73Lg. Slot - Typ.

4.5

0”

2.2

5”

3.00”

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Outside Air Temperature Sensor1

JOB NAME

2ZOT004704424

Front View Side View Back View

Closure PlugCAUTION!See Note 2

Sensor TubeCAUTION!See Note 1

Mounting Tab& Screws - Typ.

Correct

Incorrect

Incorrect

See Note #1

Sensor MountingPostion

2.70”

1.1

3”

2.30”

3.0

0”

036-22276-001-A-0602.CDR

06/28/02

Form: 036-22276-000 Rev. A (0602) Supersedes: Nothing

Page 30: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Notes:

In Order To Obtain Accurate Static Pressure ReadingsThe Static pressure Pickup Probe Should Be MountedPer The Following Recommendations:

1.)The Probe Should Be Mounted In a Straight SectionOf Ductwork Approx. 2/3 The Length Of the Supply Duct,Downstream Of The HVAC Unit.

2.)The Probe Should Not Be Mounted Less Than 3 DuctDiameters Downstream Or Not Less Than 2 DuctDiameters Upstream Of Any Elbow or Takeoff.

See The Systems Installation And Operation Manual ForOther Design Considerations And RecommendationsRegarding Static Pressure Pickup Tube Location.

Caution!

1.)The Static Probe Is Supplied With A 14“ Length OfTubing For Connection To The Static PressureSensor. The Static Pressure Sensor Is Designed ToBe Mounted Adjacent To The Location Where TheStatic Pickup Tube Is Mounted And Wired Back ToThe Controller Board. The Static Pressure SensorCan Also Be Mounted Close To The Controller BoardAnd Tubing (By Others) Routed From The Sensor ToThe Static Pickup Probe. Be Sure Not To Kink TheTubing Between The Static Pickup Probe And TheStatic Pressure Sensor.

Static Pressure Pickup Tube - 2ZSP004704424

Mounting Plate

Gasket

Adhesive Backed Drill GuideMounting Template

2-3/4“ Mounting Plate

4.0"

3/4"

1/4" Hex Head Sheet Metal Screws

ThreadTogether

1/8“ MPTThreaded Pipe

Duct Work

Drill 5/16" Hole In Ductwork For Probe

1/4“ Barb Fitting

1/4“ O.D. X 3/16” I.D. x 14” Long - Fire Rated TubingSlide Over 1/4“ Barb FittingTubing Not To Exceed 250 Ft. Length.Do Not Splice Tubing.

Connect This End Of Tubing To “Hi”Port Of Pressure Sensor

FILENAME

JOB NAME

DESCRIPTION:

Static Pressure Pickup Tube

2ZSP004704424

DATE DRAWN:

PAGE

1 of 1

B. CREWSDRAWN BY:

036-22300-001-A-0602.CDR

06/28/02

Form: 036-22300-001 Rev. A (0602) Supersedes: Nothing

Page 31: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

General Notes

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Pressure Sensor

JOB NAME

2.)All Wiring To Be In Accordance With Local AndNational Electrical Codes And Specifications.

2ZPS004704324

Top View

Side View

OU

T

IN

GN

D

UP

(-)LO

0.35"

0.55"

1.00"

2.20"

0.15" DIA.

0.15"

2.94"

2.50"

0.125" (1/8" Tubing Conn.)

0.200" (3/16" Tubing Conn.)

1.95"

0.60"

12.0" APPROX.

Full Scale Output(Positive Pressure)

Null Offset

Span*

Minimum Typical Maximum

Hystereisis And Repeatability

Temperature ErrorNull +10 To 40 C

Stability (1 Year)

Supply Voltage (Vs)

Pressure Overload

Burst Pressure

Positive Pressure (Hi Side)Negative Pressure (Lo Side)

Positive Pressure (Hi Side)Negative Pressure (Lo Side)

Non-Linearity

Span +10 To 40 C

Common Mode Pressure

0-5“ H O Pressure Range - 5 VDC Operation2

3.92 VDC

0.17 VDC 0.2-0.3 VDC 0.33 VDC

3.59 VDC 3.91 VDC

.05 % Span

4.75 VDC 5.0 VDC 8.0 VDC

15 PSI

25“ H O2

50“ H O2

15“ H O2

25“ H O2

4.08 VDC3.95-4.05 VDC

3.65-3.85 VDC

.3 % Span .5 % Span

.03 % Span

1.0 % Span

0.5 % Span

1.0 % Span1.5 % Span1.5 % Span

*Span Is The Algebraic Difference Between End Points (Null Offset And Full Scale Output)

The plastic housing on the sensor is electricallyconductive. Avoid contact with any electrical components.It is acceptable to mount the sensor on grounded sheetmetal such as ductwork, electrical panels, etc.

Use extreme care when mounting the sensor to avoiddamage to the plastic housing. Do not overtighten themounting screws! Do not use mounting screws which aretoo large for the holes!

Warning!

Warning!

When The Sensor Is Used As A DuctIt May Be Mounted To The

Ductwork Near The Static Pressure Pickup Tube. IfThe Sensor Is Mounted In This Manner, AwayFrom The Controller, The Modular Plug Must BeCut Off And 3-conductor 24 Gauge Minimum WireMust Be Butt Spliced To The Sensor Leads. TheController Has A Terminal Block Which IsParalleled With The Modular Jack To Allow WiringConnections. Total Wire Length Should NotExceed 100Ft. If Desired The Sensor May Also BeLocated Near The Controller, With The ModularPlug On The Sensor Directly Connected To TheMating Controller Jack. When This Method Is UsedTubing Must Be Run From The Sensor To TheStaic Pressure Pickup Tube. Tubing Should NotExceed 250 Ft. And Must Be Continuous WithoutAny Splices.

StaticPressure Sensor

1.) The Pressure SensorShould Be Mounted In A Vertical Position As ShownWith Arrow Pointing Up. ( Tubing ConnectionsPointing Down). If This Mounting Position Is NotPossible In Your Application, It May Be Mounted InA Horizontal Position. When Mounted In AHorizontal Position Accuracy Will Be Affected ByApproximately 2% Full Scale Null Shift Due ToDiaphragm Gravity Effect Error.

Caution: 2ZPS004704324

Pressure Sensor - 2ZPS004704324

1.29"

OU

T(B

lack)

GN

D(G

ree

n)

IN(R

ed

)

2ZPS004704324S.P. Sensor

Duct Static Pressure Sensor ApplicationsMounting Information

1 of 1

036-22301-001-A-0602.CDR

06/28/02

Form: 036-22301-001 Rev. A (0602) Supersedes: Nothing

Page 32: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Notes:

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Pressure Independent Air flow Sensor1

JOB NAME

2.)All Wiring To Be In Accordance With Local AndNational Electrical Codes And Specifications.

2ZPS004704224

Top View

Side View

OU

T

IN

GN

D

UP

(-)LO

0.35"

0.55"

1.00"

2.20"

0.15" DIA.

0.15"

2.94"

2.50"

0.125" (1/8" Tubing Conn.)

0.200" (3/16" Tubing Conn.)

1.95"

0.60"

12.0" APPROX.

Full Scale Output(Positive Pressure)

Null Offset

Span*

Minimum Typical Maximum

Hystereisis And Repeatability

Temperature ErrorNull +10 To 40 C

Stability (1 Year)

Supply Voltage (Vs)

Pressure Overload

Burst Pressure

Positive Pressure (Hi Side)Negative Pressure (Lo Side)

Positive Pressure (Hi Side)Negative Pressure (Lo Side)

Non-Linearity

Span +10 To 40 C

Common Mode Pressure

0-1“ H O Pressure Range - 5 VDC Operation2

3.92 VDC

0.17 VDC 0.2-0.3 VDC 0.33 VDC

3.59 VDC 3.91 VDC

.05 % Span

4.75 VDC 5.0 VDC 8.0 VDC

15 PSI

5“ H O2

10“ H O2

3“ H O2

5“ H O2

4.08 VDC3.95-4.05 VDC

3.65-3.85 VDC

.3 % Span .5 % Span

.03 % Span

1.0 % Span

0.5 % Span

1.0 % Span1.5 % Span1.5 % Span

*Span Is The Algebraic Difference Between End Points (Null Offset And Full Scale Output)

The plastic housing on the sensor is electricallyconductive. Avoid contact with any electrical components.It is acceptable to mount the sensor on grounded sheetmetal such as ductwork, electrical panels, etc.

Use extreme care when mounting the sensor to avoiddamage to the plastic housing. Do not overtighten themounting screws! Do not use mounting screws which aretoo large for the holes!

Warning! Warning!

1.) The Static Pressure Sensor Should BeMounted In A Vertical Position As Shown WithArrow Pointing Up. ( Tubing Connections PointingDown). If This Mounting Position Is Not Possible InYour Application, It May Be Mounted In A HorizontalPosition. When Mounted In A Horizontal PositionAccuracy Will Be Affected By Approximately 2% FullScale Null Shift Due To Diaphragm Gravity EffectError.

Caution:

2ZPS004704224- For Pressure Independent Zone ControlAirflow Sensor

1.29"

OU

T(B

lack)

GN

D(G

ree

n)

IN(R

ed

)

% Span

2ZPS004704224P.I. Sensor

036-22302-001-A-0602.CDR

06/28/02

Form: 036-22302-001 Rev. A (0602) Supersedes: Nothing

Page 33: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form: 036-22303-001 Rev. A (0602) Supersedes: Nothing Page 1 of 1

Project: ___________________________ Location ____________________________________

CommLink Installed: Yes No Remote Link Installed: Yes No Phone: ______________

Stages of Cooling _____ Stages of Heating _____ Gas Electric Economizer Yes No

Zoning: Pressure Dependent Pressure Independent

ZoneAddress

Zone Description or Location AirDamper

Size

RoomSensor Type

RelayExp. Board

1 S SO SA SOA

AH BH SF PF

2 S SO SA SOA

AH BH SF PF

3 S SO SA SOA

AH BH SF PF

4 S SO SA SOA

AH BH SF PF

5 S SO SA SOA

AH BH SF PF

6 S SO SA SOA

AH BH SF PF

7 S SO SA SOA

AH BH SF PF

8 S SO SA SOA

AH BH SF PF

9 S SO SA SOA

AH BH SF PF

10 S SO SA SOA

AH BH SF PF

11 S SO SA SOA

AH BH SF PF

12 S SO SA SOA

AH BH SF PF

13 S SO SA SOA

AH BH SF PF

14 S SO SA SOA

AH BH SF PF

15 S SO SA SOA

AH BH SF PF

16 S SO SA SOA

AH BH SF PF

[S=Sensor] [SO=Sensor w/ Override] [SA=Sensor w/ Setpoint adjust] [SOA=Sensor w/ Override & Setpoint adjust][AH=Auxiliary Heat] [BH=Box Reheat] [SF=Series Fan Terminal] [PF=Parallel Fan Terminal]

Page 34: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Form

: 036

-223

04-0

01 R

ev. A

(060

2) S

uper

sede

s: N

othi

ngPa

ge 1

of 1

Jo

b N

ame:

Loca

tion:

____

____

____

____

____

____

____

_

Sche

dulin

gSe

tpoi

nts

Con

trol

ler

Add

ress

Con

trol

ler

Des

crip

tion

Zone

Loc

atio

nSt

art T

ime

Stop

Tim

eC

oolin

gH

eatin

g0

Zone

Man

ager

1Zo

ne C

ontr

olle

r2

Zone

Con

trol

ler

3Zo

ne C

ontr

olle

r4

Zone

Con

trol

ler

5Zo

ne C

ontr

olle

r6

Zone

Con

trol

ler

7Zo

ne C

ontr

olle

r8

Zone

Con

trol

ler

9Zo

ne C

ontr

olle

r10

Zone

Con

trol

ler

11Zo

ne C

ontr

olle

r12

Zone

Con

trol

ler

13Zo

ne C

ontr

olle

r14

Zone

Con

trol

ler

15Zo

ne C

ontr

olle

r16

Zone

Con

trol

ler

Page 35: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

ZoneManager

SupplyAir TempSensor

To HVAC UnitControl Panel

ReturnAir TempSensor

Bypass AirDamper

Economizer(Actuator By Others)

Outside AirTemp Sensor

StaticPressureSensor

Local Loop

Zone Air DampersUp to 16 Zone Air Dampers Allowed

#1 #16

24VAC(25 VA)

24VAC(10 VA)

24VAC(10 VA)

Remote Link(Optional)

Computer(Optional)

CommLink IISingle Loop

Interface(Optional)

RS-4859600 Baud

110/24 VAC

110/9 VAC

Power Pak(14 VA@24VAC)

Power Pak

W

C

LI

ATTMASTER

ONTRO

S,NC

W

C

LI

ATTMASTER

ONTRO

S,NC

CO

MM

LINK

II

CO

MM

LINK

II

L

C

M

M

O

O

O

O

M

D

P

PE

Notes:

1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.

3.)The Local Loop May Have Up To 16Zone Controllers Connected.

4.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.

5.)For Individual Component Wiring SeeSpecific Component Wiring Diagram.

6.)It Is Recommended That AllControllers Address Switches AreSet Before Installation.

2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.

SeeFor

Zone Manager WiringDetails

Drawing Filename:MBAWRNEW3.CDR

See

For CommLink WiringDetails

Drawing Filename:MBAWRNEW6.CDR

See

For Zone ControllerWiring Details

Drawing Filename:MBAWRNEW4.CDR

Remote

Link

C

O

N

T

R

O

L

S

SIG

DE

T

RD

Y

SN

D

RE

C

PW

R

FAN

COO

L1

COO

L2

HEAT1

HEAT2

BYPASSO

PEN

BYPASSCLO

SE

COM

MUNIC

ATION

ALARM

A=

ALLZO

NES

B=

EACHZO

NE

C=

HVACUNIT

/CLEAR

D=

ALARMS

#=

STEP/ENTER

* =DECIM

AL

+

+

+

+

Meridian

Cool

Mode

08-08-01

03:48PMFRI

OCCUPIED

NOALARMS

2

8

5

0

A

C

B

D

1

7

4

*

3

9

6

#

Heating and Air Conditio

ning

®

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

System Wiring Diagram1

JOB NAME

Meridian Basic

035-18965-000-A-0602.CDR

06/28/02

Form: 035-18965-000 Rev. A (0602) Supersedes: Nothing

Page 36: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Zone Manager

Notes:

1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.

3.)All Communication Wiring To Be 18Ga. Minimum, 2 Conductor TwistedPair With Shield. Belden #82760 OrEquivalent.

4.)For Individual Component Wiring SeeSpecific Component Wiring Diagram.

5.)It Is Recommended That AllControllers Address Switches AreSet Before Installation

2.)All Wiring To Be In Accordance WithLocal And National Electrical Codesand Specifications.

RS-485Communications To Zone

Controllers

Return Air Temp.Sensor

Supply Air Temp.Sensor

LineVoltage

HV

AC

Unit

24VAC Only

Red

Blk

To Relief / Exhaust Fans

Grn

StaticPick-up

StaticPressureSensor

Splice AsRequired

LO HI

GND

24VAC

Belimo Actuator Wiring Shown.Consult Factory For Other

Models Of Economizer Actuators.Some Actuators Require IsolationTransformers In Order To PreventDamage To The Controller Board.

WARNING!

Use Extreme Care When WiringEconomizer Actuators

Never Connect Or DisconnectWiring With Power Applied!

Never Apply Power If TheGnd ( 1 Com ) Terminal On The

Actuator Is Not Connected.

See Note 1 &2

Outdoor Air Temp.Sensor

(See Note 4)

Aux3Forced

OccupiedMode

Aux1Economizer

Disable

Aux2FilterAlarm

Auxiliary Inputs( Dry Contacts )

R

G

Y1

Y2

W1

W2

Economizer Actuator

133 IN-LB

AF24-SR

1 COM

2 +

3 Y1

4 Y2

5 UBELIMO

For Detailed ConnectionsAnd Slave WiringSee Bypass ActuatorWiring Drawing Filename:MBAWRNEW3.CDR

Bypass Air DamperActuator

10

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Zone Manager Wiring2

JOB NAME

Meridian Basic

C987

CABLE

R6

R5

HEAT 2 SW

1

W2

W1

Y2

HEAT2

HEAT1

COOL2

COOL1

FAN

HEAT 1

COOL 2

COOL 1

C 1992

1

1632

BNET

248

AD

D

COMM DRIVER

RS-485

75176

MADE IN U.S.A.

D1

7

D1

8

D1

9

D2

0

D2

1

D2

2

D2

3

D2

4

0* # D

R

SH

T

COMM

C1C2

+

P1

RIBBON

GN

D

G

Y1V6

V5

CLOSE

V4

V3

OPEN

GND

FDBK

FAN

CLOSE

OPEN

+

REC

+

GND

NE5090

4 5 6

KEYPAD

1 2 3

B

A

LCD DISPLAY

&

++

24VAC

TB2

POWER

+

++

ADJUST

5.11V

PJ1

+

+PRESSU

RE

SEN

SO

RJA

CK

+5

V

SIG

BUSS

EXP

TB2

A2

G

OUTPUTS

ANALOG

A1

N.O.

CONTACTS

EXHAUST

AUX3

GND

GND

AUX2

AUX1

ANALOG

SAT

OAT

RAT

INPUTS

+12V

TB1

2

BYPASS

BYPASS

Local Loop

Address Switch Must Always Be SetTo Address 0 on Zone Manager Board

As Shown

Zone ManagerAddress Switch

These Switches Must BeIn The OFF PositionAs Shown

ADD

12

481632B

NET

AD

D

32

BNE

T

16 8 4 12

OF

F>

OF

F>

RockerDown

RockerDown

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CLO

SE

OPEN

GND

PJ1

PJ2LD

2

LD

1

CLOSE

TB

1T

B2

Bypass Interface Card

OPEN

CLOSE

FDBK

GND

035-18966-000-A-0602.CDR

06/28/02

Form: 035-18966-000 Rev. A (0602) Supersedes: Nothing

Page 37: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

BYPASS ACTUATOR #3 (SLAVE)(WHEN USED) BYPASS ACTUATOR #2 (SLAVE)

BYPASS ACTUATOR #1(MASTER)

MODULAR CABLE

MODULARCABLE

1 10 0

10

ZONE MANAGER BOARD

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

V4

V3

REC

CLOSE

OPENK1

K2

NE

TW

OR

K

SH

R

T

NE5090

FDBK

GND

OPEN

CLOSE

NOT USED FORTHIS APPLICATION NOT USED FOR

THIS APPLICATION

NOT USED FORTHIS APPLICATION

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Bypass -Slave Wiring3

JOB NAME

Meridian Basic

FR

OM

ZO

NE

CO

NT

RO

LLER

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

101824

TO

AC

TU

AT

OR

OP

EN

CLO

SE

FDBK

OPEN

GND

GND

PJ1

PJ2 LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

BYPASS ANDSLAVE INTERFACE CARD

BYPASS ANDSLAVE INTERFACE CARD

BYPASS ANDSLAVE INTERFACE CARD

HZ000095

035-18967-000-A-0602.CDR

06/28/02

Form: 035-18967-000 Rev. A (0602) Supersedes: Nothing

Page 38: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Notes:

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Zone Controller Wiring

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring IsStraight Thru

Required VA For TransformerEach Zone Controller = 10 VA Max.

(Includes Actuator)

24VAC

GND

GND

AUX

TMP

NORMAL

OVR

RELO

C

REMR

O

AW

1632TOKENNET

8421

Caution!Zone Controllers Must Have Address Switches Set Between1 And 16 ( Up To 16 Zone Controllers On Local Loop ).

Room Sensor

Diagnostic Blink Code LED

Zone Actuator

Local LoopRS-485

9600 Baud

Airflow Sensor (Optional)Only Used For PressureIndependent Applications

Connect ToNext Controller

And/Or ZoneManager On

Address Switch Shown IsSet For Address 9

Address Switch Shown IsSet For Address 13

ControllerAddress Switch

This Switch Must BeIn The ON PositionAs Shown

Switches Labeled 32 AndToken Should Be In TheOFF Position As Shown

Note:The Power To The Zone Controller Must BeRemoved And Reconnected After Changing TheAddress Switch Settings In Order For Any ChangesTo Take Effect.

Caution:Disconnect All Communication Loop WiringFrom The Zone Controller Before Removing PowerFrom The Zone Controller. Reconnect Power AndThen Reconnect Communication Loop Wiring.

ADDRESS ADD

ADDRESSADD

ADDRESSADD

The Address For Each ControllerMust Be Between 1 And 16 And Be

Unique To The Other ControllersOn The Local Loop

Connection To AUXTerminal Required OnlyWhen Sensor Is SpecifiedWith Slide Adjust Option

JOB NAME1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.

2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.

3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent.

Meridian Basic4

10

FLOW

COMM

24VAC24VAC

GNDGND

AUX

REV.

0REV.

0YS1

01

47

0YS1

01

47

0

F1F1

SHIELD

R

T

TEMP

GND

GND

AUX1

+VS

AUX2

C1

2C

12

3406334063VR1

VR1

TB4

TB4

IIGO GO

78

24

78

24

K2

K1

U7

U7

U5

U5

LD

1LD

1

NET

PO

WER

SCANSCAN++L1

L1

RECREC

++

LD

2LD

2

LD3LD3

TB3

TB3

75

17

6

CX10CX10

SW

1SW

1

4488

32TOKEN

1616

ADDRESSON

EW

DO

G

1122

C6

C6

93

46

93

46

CX

6C

X6

U6

U6

PJ1

PJ1

TB2

RV1

RV1

AD

J

VREF

CX9CX9

++

35

83

58

U9U9

TB1

TB1

RAMRAM

HC

25

9

80C55280C552

EPROMEPROM

CX2CX2

16L816L8

AC

TUATO

RA

CTU

ATO

REX

PA

NSIO

NEX

PA

NSIO

NU

2

CX8

PJ3

HC

57

3H

C5

73

U8

U4

32KCX4

U3CX3 CX1CX1

RAM8K

HiLo

Airflo

w

SeeFor

Slaved-Zone WiringDetails

Drawing Filename:MBAWRNEW5.CDR

035-18968-000-A-0602.CDR

06/28/02

Form: 035-18968-000 Rev. A (0602) Supersedes: Nothing

Page 39: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

SLAVED- ZONE ACTUATOR #2(WHEN USED) SLAVED-ZONE ACTUATOR #1

ZONE ACTUATOR #1(MASTER)

MODULAR CABLE

MODULAR CABLE

MODULARCABLE

MODULARCABLE

1 10 0

10

BYPASS ANDSLAVE INTERFACE CARD

BYPASS ANDSLAVE INTERFACE CARD

BYPASS ANDSLAVE INTERFACE CARD

ZONE CONTROLLER BOARD

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

FR

OM

ZO

NE

CO

NT

RO

LLE

R

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

1018

24

TO

AC

TU

AT

OR

OP

EN

CL

OS

E

FDBK

OPEN

GND

GND

PJ1

PJ2LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2

NOT USED FORTHIS APPLICATION NOT USED FOR

THIS APPLICATION

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

Slaved-Zone Wiring5

JOB NAME

Meridiane Basic

FR

OM

ZO

NE

CO

NT

RO

LLER

BY

PA

SS

AN

DS

LAV

EIN

TE

RFA

CE

YS

101824

TO

AC

TU

AT

OR

OP

EN

CLO

SE

FDBK

OPEN

GND

GND

PJ1

PJ2 LD

2

LD

1

OPEN

CLOSE

CLOSE

TB

1T

B2PJ2PJ1

ACTUATOREXPANSION

Note:1.) A Slave Wiring Adapter consisting of a bypass & slave interface cardand modular cable is supplied with the Round Slaved-Zone Damper,Rectangular Slaved-Zone Damper Kit and the Slaved Zone Package. It isrequired when attaching slave actuator(s) to the master zone damper.The bypass & slave interface card should be mounted in the controlenclosure of the master zone damper. It is mounted by fastening theplastic snap-track to the control enclosure with sheet metal screws.Connect modular cables to the bypass and slave interface card and themaster zone actuator as shown.

035-18969-000-A-0602.CDR

06/28/02

Form: 035-18969-000 Rev. A (0602) Supersedes: Nothing

Page 40: Heating and Air Conditioning Submittal Data Sheet …...Includes: Actuator, Zone Controller, Mounted on Round Air Damper with Control Enclosure. 2ZMD004700624 2ZMD0047010624 Zone Air

Commlink II Communications Interface

(Jumper Set For Multiple Loop)

Caution: Use The “Molded Cable” ToConnect To The Computer (DCE) Connector.This Cable Is Only To Be Used To ConnectFrom The CommLink (DTE) Connection ToThe Modem (When Used).

Do Not

Caution:Disconnect All Communication Loop WiringFrom The CommLink Before Removing PowerFrom The CommLink. Reconnect Power And ThenReconnect Communication Loop Wiring.

Use 25 Pin Or 9 Pin Connector AsRequired By Available Serial (COM) Port

JOB NAME

Caution: Use The “25 Pin Or 9 Pin Cable” ToConnect To The Modem (DTE) Connector.. ThisCable Is Only To Be Used To Connect From TheCommLink (DCE) Connection To The Computer

Serial Port (COM) Connection.

Do Not

(When Used) Note:Place Jumper BetweenPins 1 & 2 for MultipleLoop Applications &Between Pins 2 & 3 forSingle Loop ApplicationsSee Note 4.

COMM DRIVER CHIP( U1 )PIN 1

MULTI

SINGLE

12

3

CommLink Jumper Switch SettingsNotes:

FILENAME

DATE: B. CREWS

DESCRIPTION:PAGE

DRAWN BY:

CommLink II Wiring6

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Communication LoopWiring Is Straight Through

Connect To First Zone

Network LoopRS-485

19200 Baud

Required VA For TransformerCommLink = 14VA Max.

CommLink Is Supplied With 110/24VAC Power Supply.If Desired A Transformer (By Others)

May Be Wired To The CommLink Instead

Molded Modem Cable.Supplied With CommLink

(DTE)MODEM COMPUTER

(DCE)

GT R

POWER

4 Piece ComputerCable Kit.Supplied WithCommLink

Connect To Modem .Only

9P

inF

em

ale

9 PinFemale

25 PinFemale

9P

inF

em

ale

120/24 VacTransformer

25 PinMale

Connect Supplied RJ12 Modular Phone CableTo Supplied 9 Pin Or 25 Pin Connector As ReqdBy Your Computer Com Port Connection

1.)24 VAC Must Be Connected SoThat All Ground Wires RemainCommon.

2.)All Wiring To Be In AccordanceWith Local And National ElectricalCodes And Specifications.

3.)All Communication Wiring To Be2 Conductor Twisted Pair WithShield. Use Belden #82760 OrEquivalent. Meridian Basic

4.)CommLink Is Shipped With TheJumper In The Multiple LoopConfiguration, So It Is NecessaryTo Move It To The Single LoopConfiguration For A Basic System.

485 LOOP 24V

GND

035-18970-000-A-0602.CDR

06/28/02

Form: 035-18970-000 Rev. A (0602) Supersedes: Nothing