A special air condit ioning system designedfor smal l-sized bui ldings
PCVAU0737F
HEAT PUMPHeat Pump 50 Hz
SSThe 5S+1E concepts of
Extending the core “5S” concept—Space saving, Sufficient capacity, Slim design, Sound-reduced operation and Single phase power supply—Daikin’s VRVIII-S offers added value with the “1E” concept—Easy installation. With all these features and more, we proudly present the ideal air conditioning system designed for small-sized buildings.
The ideal air conditioning
small office
Space saving
Sufficient capacity
Slim design
Sound-reduced operation
Single phase power supply
Easy installation E1Econcept
5Sconcept
1
system for
s and shops
2
765 mm
The VRVIII-S is highly space saving, featuring slim and compact outdoor units. It is suitable for small offices and shops with capacities of 4, 5 and 6 class (11.2, 14 and 15.5 kW).
Slim, compact and sufficient capacity
Approx. 40%reduction
Approx. 50%reduction
635 mm 900 mm
320 mm
Volume
VRVIII(5 class (14 kW))
Footprint
(4, 5, 6 class (11.2, 14, 15.5 kW))
VRVIII(5 class (14 kW)) (4, 5, 6 class (11.2, 14, 15.5 kW))
The compact, trunk-shaped outdoor unit can easily be installed on a balcony, realising complete system installation within each floor. This enables more useful utilisation of the space on the building rooftop.
Outdoor unit can be installed on a balcony
ContentContents
Introduction..............page 1
Main features...........page 3
Control systems.....page 9
Indoor unit lineup.....page 15
Specifications.................page 27
Indoor units............page 27Outdoor units........page 34
Option list..........................page 35
Indoor units..............page 35Outdoor units...........page 37Control systems......page 37
MAIN FEATURES
3
Wide range of choicesTo suit the variety of rooms found in small offices and shops, the VRVIII-S system offers a wide range of indoor and outdoor units.VRVIII-S indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
Outdoor unit can be selected from three models to provide the power that suits
your needs. The trunk-shaped outdoor unit can be neatly installed outside the office.
3 modelsOutdoor units
Model Name
Capacity Range
Capacity Index
RXYMQ4PV4A RXYMQ5PV4A RXYMQ6PV4A
4 class (11.2 kW) 5 class (14 kW) 6 class (15.5 kW)
100 125 140
Outdoor unit lineup
Indoor unit lineup 14 types 78 models
A wide range of indoor units includes 78 models in 14 types. The indoor units can be selected to match rooms and preferences.
14 types 78 modelsIndoor units
4
New
Ceiling MountedCassette (Round Flow)
Type Model Name Capacity Range
Capacity Index 20 40 62.5 80 100 1405031.2525
2.2 kW 4.5 kW 7.1 kW 9 kW 11.2 kW 16 kW
125
14 kW
145
16.2 kW
140 145
5.6 kW3.6 kW2.8 kW
Ceiling Mounted Cassette(Compact Multi Flow)
FXFQ-PVE
FXZQ-MVE
Slim CeilingMounted Duct
Ceiling MountedDuct
Ceiling Suspended
Wall Mounted
Floor Standing
ConcealedFloor Standing
Ceiling Mounted Cassette(Double Flow)
FXDQ-NBVE(900/1,100 mm width type)
FXMQ-PVE
FXHQ-MAVE
FXAQ-PVE
FXLQ-MAVE
FXNQ-MAVE
FXCQ-MVE
Ceiling MountedBuilt-in FXSYQ-MVE
FXDQ-PBVE(700 mm width type)
R-410A VRV system indoor units are not compatible with the R-22 VRV system.Note:
Ceiling MountedCassette Corner FXKQ-MAVE
Ceiling Concealed (Duct) FXDYQ-MAV1
BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.Note:
Ceiling Suspended Cassette
Type Model Name
—
4.5 kW2.2 kW 3.6 kW2.8 kW
FXUQ-MAV1
20 4031.2525BEVQ125MAVE
14 kW
BEVQ100MAVEBEVQ71MAVE
5.6 kW 11.2 kW8 kW50 12510071
Capacity Range4020 3225 12550 10071
Connection UnitCapacity Index
20 40 63 80 100 125503225
Connection unit series indoor units
New New New New New New
Energy efficiency and quiet operationOutdoor units use Daikin’s unique scroll compressor for energy efficiency and quiet operation.
MAIN FEATURES
High COP during both cooling and heating operations
Quiet operation provides luxurious comfortQuietness is yet another important feature of Daikin’s VRVIII-S system. To reduce noise and realise comfortable operation, latest technologies and features are applied to the outdoor units.
One of the top features of the VRVIII-S is its energy efficiency. It achieves high COP during cooling and heating operations by utilising Daikin’s unique scroll compressor.
Above values are based on the following nominal conditions:• 2 built-in units are connected (4 class (11.2 kW): FXSYQ50M x 2; 5 class
(14 kW): FXSYQ63M x 2; and 6 class (15.5 kW): FXSYQ63M + FXSYQ80M.)• Cooling: Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.• Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
VRVII-SPrevious modelRXYMQ-MV4A
VRVII-SPrevious modelRXYMQ-MV4A
Lower operation sound is achieved!
Cooling
Heating
2.94
3.62
2.81
3.45
3.733.58
3.032.82
Cooling 505153
4 class (11.2 kW)
5 class (14 kW)
6 class (15.5 kW)
5 class (14 kW)
3.153.074 class (11.2 kW)
6 class (15.5 kW)
5 class (14 kW)
3.373.274 class (11.2 kW)
6 class (15.5 kW)
Heating 525355
53
54
56
51
52
54
4 class (11.2 kW)
5 class (14 kW)
6 class (15.5 kW)
5
Nighttime quiet operation function
Set on the outdoor PCB. Time of maximum temperature is memorised. The low operating mode will initiate 8 hours*1 after the peak temperature in the daytime, and normal operation will resume 10 hours*2 after that. The operation sound level for the night mode can be selected from 47 dB(A) (Step 1), 44 dB(A) (Step 2) and 41 dB(A) (Step 3).
Automatic modeMode 1.
Automatic modeMode 1.
Starting time and ending time can be input. (An external control adaptor for outdoor unit, DTA104A53/61/62, and a locally obtained timer are necessary.)
Manual modeMode 2.
Combinations of modes 1 and 2 can be used depending on your needs.
Combined modeMode 3.
*1. Initial setting. Can be selected from 6, 8 and 10 hours.*2. Initial setting. Can be selected from 8, 9 and 10 hours.
Note: • This function is available in setting at site.
• The relationship of outdoor temperature (load) and time shown in the graph is just an example.
Peak in outdoor temperature
Capa
city
%
8 hrs 10 hrs
Oper
atio
n so
und
dB(A
)
47
8:00 12:00 16:00 20:00 0:00 4:00 8:00
50
100
500
Load
%
Night mode endsNight mode starts Night mode endsNight mode starts
Night Mode
44
41
(Initial setting)(Initial setting)
Step 1 max. - 3 dB(A)( 4 class/11.2 kW)
Step 2 max. - 6 dB(A)( 4 class/11.2 kW)
Step 3 max. - 9 dB(A)( 4 class/11.2 kW)
Step 1: 47 dB(A)
Step 2: 44 dB(A)
Step 3: 41 dB(A)
Operation sound level selectablefrom 3 steps for the night mode
The capacity reduction rate differs depending on the operation sound level step selected.
-1dB(A)
-1dB(A)
-1dB(A)
-1dB(A)
-1dB(A)
-1dB(A)
1 dB(A) reduced in each model!
High COPachievedin all ranges!
6
These two features work to reduce sound. Guides are added to the bell mouth intake to reduce turbulence in the airflow generated by fan suction. The Aero Spiral Fan features fan blades with the bent blade edges, further reducing turbulence.
Smooth Air Inlet Bell Mouth and Aero Spiral Fan
A collection of cutting-edge technologies results in efficient and quiet operation.The high efficiency compressor to achieve a higher COP
2
1
Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.
Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory using Daikin products.
*1 A neodymium magnet is approximately 10 times stronger than a standard ferrite magnet.
*2 The torque created by the change in power between the iron and magnet parts.
DC fan motorEfficiency improved in all areas compared to conventional AC motors, especially at low speeds.
Sine wave DC inverter >> Smooth sine wave DC inverter Use of an optimised sine wave smoothes motor rotation, further improving operating efficiency.
Daikin DC inverter models are equipped with the Reluctance DC motor for compressor. The Reluctance DC motor uses 2 different types of torque, neodymium magnet*1 and reluctance torque*2. This motor can reduce energy used because it generates more power with a smaller electric power than an AC or conventional DC motor.
Compressor equipped with Reluctance DC motor
3DC motor efficiency
(comparison with AC motor)
200 300 400 500 600 700 800 900 1000
0
20
40
80
60
100
Eff
icie
ncy
(%
)
Motor speed (rpm)
AC motorAC motorAC motorAC motorAC motorApprox.
40%increase
Approx.
20%increase
DC motorDC motorDC motorDC motorDC motor
Reluctance DC motor
Conventional DC motor
AC motor
Rotational speed (rps)
Mo
tor
effi
cien
cy (
%)
DC fan motor structure
ReluctanceDC motor
3
1
2
Escaping eddies are sucked in by the bent blade edges, reducing overall turbulence.
With the bent blade edge
Without the bent blade edge
90
80
70
60
500 30 60 90 120
More than 20%More than 20%
Small loadLow capacity
Large loadHigh capacity
RXYMQ4PV4ARXYMQ5PV4ARXYMQ6PV4A
Design flexibilityVRVIII-S systems offer broad design flexibility with long refrigerant piping lengths and multiple indoor unit combinations, which provides generous freedom for office and shop design both inside and out.
MAIN FEATURES
For a 6 class (15.5 kW) installation
Multiple indoor unit combinations are possible. * As many as 9 indoor units can be connected to a 6 class (15.5 kW) unit, making the VRVIII-S a versatile system.* Total capacity index of connectable indoor units must be 50 - 130 % of the capacity index of the outdoor unit.
Up to 9 indoor units can be connected to a single outdoor unit
The VRVIII-S provides the long piping length possibility of 150 m, with a total piping length of 300 m. If the outdoor unit is installed above indoor units the level difference can be up to a maximum of 50 m. These generous allowances facilitate an extensive variety of system designs.
Long piping design possible
Actual piping length
Max. 150 m
Total piping length
Max. 300 m
1 2 3 4
5 6 7 8 9
units
Max.
9 >> Max. 8 indoor units for a 5 class (14 kW) installation
>> Max. 6 indoor units for a 4 class (11.2 kW) installation
*1. 40 m when the outdoor unit is installed below indoor units.*2. Maximum piping length between the indoor unit and the first branch is 40 m.
Note:
The operation range of the VRVIII-S system works to reduce limitations on installation locations. The operation temperature range for heating goes all the way down to -20°C, while cooling can be performed with outdoor temperatures as high as 46°C. Both these achievements are due to the adoption of a high-pressure dome-type compressor.
Certified operation temperature rangeWide operation temperature range
7
-10
0
10
20
30
40
50
-20
-10
0
10
20 15.5°CWB
Heating
46°CDB
Cooling
-5°CDB-20°CWBO
utdo
or te
mpe
ratu
re (°
CD
B)
Out
door
tem
pera
ture
(°C
WB
)
Max. 50 m*1*2
Max. 15 m
Leveldifference
Level differencebetween indoorunits
Easy installationA variety of functions are provided that make installation easier, such as simple wiring and piping and automatic test operation.
A printed circuit board has been adopted that is much easier to see and wire during installation.
Easy wiring
Simply press the test operation button after refrigerant charging is completed, and the unit performs an automatic system check, including wiring, shutoff valves, and sensors. The results are returned automatically after the check finishes.
Automatic test operation
Previous modelVRVII-S
8
Unique piping and wiring systems make it possible to install a VRVIII-S system quickly and easily.
Simple wiring and piping connection
Daikin’s advanced REFNET piping system makes installation easy. Only two main refrigerant lines are required in any one system. REFNET greatly reduces the imbalances in refrigerant flow between units, while using small-diameter piping.
>> REFNET piping system
A super wiring system is used to enable shared use of the wiring between indoor and outdoor units and the central control wiring, with a relatively simple wiring operation. The DIII-NET communication system is employed to enable the use of advanced control systems.
>> Super wiring system
Outdoor unit
Centralremote
controllerIndoor unit
Control systemsThe VRVIII-S system uses the same DIII-NET communication system as the VRV, enabling the use of advanced control systems.
CONTROL SYSTEMS
Individual control systems
Digital display lets you set temperature in 1°C units.Lets you individually programme by timer the respective times for operation start and stop within a maximum of 72 hours.Equipped with a thermostat sensor in the remote controller that makes possible more comfortable room temperature control.Enables you to select cool/heat/fan operation mode with the indoor remote controller of your choice without using the cool/heat selector. (dependant on system)Equipped with self-diagnosis function that constantly monitors the system for malfunctions. Should a problem occur, the system alerts you of the problem through an alphanumeric code.The rubber switch and the oil-resisting resin casing have been adopted for durability.
* When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the air direction adjustment button is pressed.
Wired remote controller (Option)
BRC1C62
Outdoor unit
Indoor unit
Forced OFF input
Remote controllerRemote controller
Remote controllerRemote controller
Remote controllerRemote controller
Remote controller
Remote controller
Heat Reclaim Ventilator
The indoor unit can be connected by the two remote controller, for example one in the room and the other one in the control room, which can control the operation of indoor unit freely.(The last command has a priority.) Of course, the group control by two remote controllers is also possible.
Control by two remote controllers
The system can be expanded to add several controllers, such as BMS, Forced OFF input and etc.
Expansion of system control
In all the series of VRV, Cool/Heat changeover in the same refrigerant circuit can be changed by the master remote controller of an indoor unit.
Control of Cool/Heat changeover
One remote controller can control the operation of max.16 indoor units at the same time.
Group control
Equipment related to the central control
1 2 3
The wiring of remote controller can be extended to max.500 m and it is possible to install the remote controllers for the different indoor units in one place.
Remote control
The operation of Heat Reclaim Ventilator can be controlled by the remote controller of the indoor unit. Of course, the remote controller can display the time to clean the filter.
Control for the combined operation
4
4
3
2
1
Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.
The wired remote controller supports a wide range of control functions
9
Wired remote controller with weekly schedule timer (Option)
BRC1D61
24-hour clock function (1-hour backup for power failures)
Includes ventilation mode and airflow rate switching, the main functions of Heat Reclaim Ventilator series.
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit (5 settings/day)
Programming can be enabled or disabled.
Copy function for programmed schedules.
Adds advanced functions to those of the above wired remote controller.
Notes: 1. Standard remote controllers (BRC1C62) not required. 2. If the BRC1D61 is connected to the centralised remote controllers (DCS303A51, DCS302CA61,DCS301BA61, DST301BA61), the schedule function is not available.
The same operation modes and settings as with wired remote controllers (BRC1C62 only) are possible.
A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is included.
Signal receiver unit(Separate type)
Wireless remote controller
The concealed type remote controller smartly fits into a night table or console panel in a hotel room.
Wireless remote controller (Option)
Simplified remote controller (Option)
Wide variation of remote controllers for indoor units
Wired remote controller(BRC1C62)
Wired remote controller with weekly schedule timer
(BRC1D61)
Wireless remote controller*(Installed type signal receiver unit)
Wireless remote controller*(Separate type signal receiver unit)
Simplified remote controller(Exposed type)
(BRC2C51)
Simplified remote controller(Concealed type: for Hotel use)
(BRC3A61)
FXFQ FXZQ FXKQ FXDYQ FXMQ FXHQ FXUQFXAQ FXL(N)QFXDQ
*Wireless remote controller and signal receiver unit are sold as a set. * Refer to page 37 for the name of each model.
* Refer to page 37 for the name of each model.
• A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow, Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted type is mounted into the indoor unit.
Signal receiver unit can be installed on the panel ex. Ceiling Mounted Cassette (Round Flow) type
The remote controller has centralised its frequently used operation selectors and switches (on/off, operation mode, temperature setting and airflow volume), making itself suitable for use in hotel rooms or conference rooms.
The exposed type remote controller is fitted with a thermostat sensor.
Concealed type(For hotel use)
(BRC3A61)
Exposed type(BRC2C51)
FXCQ FXSYQ
10
Signal receiver unit(Installed type)
CONTROL SYSTEMS
Up to 64 groups of indoor units (128 units) can be centrally controlled.
Optional controllers for centralised control can be combined and optimised in
accordance with building scale and purpose.
System integration with various air-conditioning peripheral equipment such as
Heat Reclaim Ventilator is easy.
Wiring can be run up to a total length of 2 km, and adapts easily to large-scale
system expansion.
Centralised control systems
For more details, please refer to the Engineering Data Book.
1. Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.
• Certain indoor units limit the functions of some control systems.
11
Central control adaptor kit (DTA107A55)
Wiring adaptorfor other air-conditioners (DTA103A51)
Central remote controller(DCS302CA61)
Up to 2 units connectable
Unified on/off controller(DCS301BA61)
Connection of up to 8 unitspossible
Schedule timer (DST301BA61)1 unit connection possible ; 8 weekly schedule control patterns possible
Forced shut-down input
Independent and centralised control of Heat Reclaim Ventilator is possible.
Unification adaptor for computerised control (DCS302A52)
Interlink Building Management System (host computer monitor panel) also possible
6 cores 7 cores max.
Address setting of central control can be performed from the remote controller.
Group control of up to 16 units is possible (group control via automatic address setting)
System without remote control is also available.
Interface adaptor for SkyAir series (DTA102A52 or DTA112BA51)
Connectable number of centralised control equipment
Central remotecontroller 2 units
Unified on /offcontroller 8 units
Schedule timer 1 unit
Outdoor-air processing unit can be connected.
1
12
Residential central remote controller* (Option)Max. 16 groups of indoor units can be easily controlled with the large LCD panel.
Max. 16 groups (128 indoor units) controllable
Backlight and large LCD panel for easy readability
ON/OFF, temperature settings and scheduling can be controlled individually for indoor units.
All indoor units can be turned on or off at once with “ALL” button.
Each group has a dedicated button for convenience.
Outside temperature display
Unified ON/OFF controller (Option)
Max. 16 groups of indoor units can be operated simultaneously/individually.
Max. 16 groups (128 indoor units) controllable
2 remote controllers can be used to control from 2 different places.
Operating status indication (Normal operation, Alarm)
Centralised control indication
Max. wiring length 1,000 m (Total: 2,000 m)
Compact size casing (Thickness: 16 mm)
Connectable with Central Remote controller, Schedule timer and BMS system
Schedule timer (Option)
Max. 128 indoor units can be operated as programmed schedule.
Max. 128 indoor units controllable
When used in combination with a central remote controller, a maximum of 8 weekly schedule
patterns can be set, while the central controller can be used to select desired zones. Up to 2
ON/OFF pairs can be set per day.
Max. 48 hours back up power supply
Max. wiring length 1,000 m (Total: 2,000 m)
Compact size casing (Thickness: 16 mm)
Connectable with Central Remote controller, Unified ON/OFF controller and BMS system
DCS303A51
DCS301BA61
DST301BA61
Max. 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.
Max. 64 groups (128 indoor units) controllable
Max. 128 groups (128 indoor units) are controllable by using 2 central remote controllers,
which can control from 2 different places.
Zone control
Malfunction code display
Max. wiring length 1,000 m (Total: 2,000 m)
Connectable with Unified ON/OFF controller, schedule timer and BMS system
Airflow volume and direction can be controlled individually for indoor units in each group operation.
Ventilation volume and mode can be controlled for Heat Reclaim Ventilator.
Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer.
DCS302CA61
Central remote controller (Option)
* For residential use only. Cannot be used with other centralised control equipment.
CONTROL SYSTEMS
13
Advanced control systems
One touch selection to total air comfort
Up to 2,560 groups (5,120 indoor units) can be controlled by one system
Air Conditioning Network Service System
Web Access
Web Access
LAN
Max. 50miTM plus adaptor line
Di/Pi port
Max. 500m
I/O expansion line
I/O System (Max. 30 modules)
iTM plus adaptor (Max. 7 adaptors)
I/O moduleI/O module I/O module
Lighting Pump Fan Sensor
InternetIntranet
System Architecture
Max. 64 groupsPhone line
LAN
Internal modem(option)
Fire alarm
Max. 200m
kWh meter
Di/Pi line
USB memory
line
DCM601A51
Daikin proudly introduces its new intelligent Touch Manager, a VRV system controller featuring an array of simple, useful system management functions for added value.
New
New
Features
• Handy area settings simplify detailed management of VRV.• Display of floor plans enables a quick search of desired air conditioning units.• Operation history shows manner of control and origin in past operations of air conditioning units.
Central control
• Remote access with a PC allows total air conditioning management using the same type of screens as those displayed in the intelligent Touch Manager.
• Authorised users can centrally control individual air conditioning units from their own computers.
Remote access
• VRVs are controlled automatically throughout the year by the schedule function.• Interlocking VRVs and other equipment enables easy automation of building facilities operation.• Setback adjusts temperature settings even when rooms are unoccupied.
Automatic control
• The Energy Navigator feature simplifies energy management by tracking energy consumption data and identifying inefficient operation.
Energy management
• Contact information of maintenance contractors can be registered and displayed.• E-mails are sent automatically to alert of malfunctions and potential trouble.• The intelligent Touch Manager can link to the Air Conditioning Network Service System for 24-hour monitoring of operating
conditions and status.
Troubleshooting
• A single intelligent Touch Manager can manage a small building or be expanded to handle medium- to large-sized buildings.• Large building properties can also take advantage of the iTM integrator to link up and expand system up to 5 intelligent Touch
Managers for integrated control.
Scalability
14
Communication functions in the user-friendly icon-based multilingual controller simplify centralised control of the VRV system.
FeaturesColour LCD touch panel icon display
Small manageable size
Simplified engineering
Multi language (English, French, Italian, German,
Spanish, Dutch, Portuguese, Chinese and Korean)
Yearly schedule
Auto heat/cool change-over
Temperature limitation
Enhanced history function
Simple Interlock Function
Built-in modem for connecting to Air Conditioning Network Service System (Option)
Management of facilities/equipment other than A/C units (By adding Dio unit or Di unit)
Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option)
Input (Lights)
Input (Key signal -General purpose ADP)
Dio UnitDEC102A51(Option)
Di UnitDEC101A51(Option)
System
Set temperature change command
OFFcommand
RS-232C
Air Conditioning NetworkService System modemfor connections
Number of indoor units expanded from 64 to 128.
D -NET
D -NET Plus AdaptorDCS601A52 (Option)
Indoor UnitHeat ReclaimVentilator
ACC centre• Air Conditioning Network Service System (Optional Maintenance Service)
System Components
Via internet
DCS601C51
System Architecture
INDOOR UNIT LINEUP
15
Ceiling Mounted Cassette(Round Flow) Type
FXFQ25P/FXFQ32P/FXFQ40PFXFQ50P/FXFQ63P/FXFQ80PFXFQ100P/FXFQ125P
360° airflow improves temperature distributionand offers a comfortable living environment.
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.
3-way flow L-shaped 2-way flowAll-round flow 4-way flow
850 mm
The industry’s first* Round Flow Ceiling Mounted Cassette type offers 360° airflow with improved temperature distribution.
All models are lighter than the conventional ones.Ex: Models FXFQ25P-50P are 4.5 kg lighter (reduced from 24 kg to 19.5 kg).
(dB(A))
A modern sophisticated decoration panel has been applied, with a panel surface that has been treated with a dirt-repellant coating.
An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours.
The horizontal louvres prevent dew condensation. Their non-flocking surfaces, which repel dirt, are easy to clean.
The air filter has an anti-mould and antibacterial treatment that prevents the growth of mould generated from dust or moisture that may adhere to the filter.
Example of airflow patterns:360° airflow is available, as well as 2- to 4-way flows, so you can choose the most suitable airflow pattern depending on location or room layout.
Drain pump is equipped as a standard accessory, and the lift height has been improved from 750 mm to 850 mm.
Treated surface Untreated surface
Resists soiling
• Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space.
Dirt andgrime
Control of the airflow rate has been improved from 2-step to 3-step control.
Low operation sound level
4-way flow Round Flow
There are areas of uneven temperature.
There are much fewerareas of uneven temperature.
* As of April 2004, the release date for Japan.
44/39/34
125
43/37.5/32
100
36/33.5/31
80
34/31/28
63
32/29.5/27
50
31/29/27
4025/32
30/28.5/27Soundlevel
(HH/H/L)
FXFQ-P
16
Quiet, compact, and designed for user comfort
Ceiling Mounted Cassette(Compact Multi Flow) Type
FXZQ20M/FXZQ25MFXZQ32M/FXZQ40MFXZQ50M
Dimensions correspond with 600 mm X 600 mm architectural module ceiling design specifications.
Wide discharge angle: 0° to 60°
2-, 3-, and 4-way airflow patterns are available, enabling installation in the corner of a room.
Comfortable airflow
Low operation sound level
0°
60°
0°
60°
Auto swing Fixed angles: 5 levels
Angles can be also set on site to prevent drafts (0°-35°) or soiling of the ceiling (25°-60°), other than standard setting (0°-60°).
For 3-way or 2-way flow installation, the sealing member for air dischargeoutlet (option) must be used to close each unused outlet.
750 mm
Drain pump is equipped as a standard accessory with 750 mm lift.
4-way flow 3-way flowL-shaped
2-way flow
1
2
0° 0°
60° 60°
(240 V)(dB(A))
32/26Sound level
(H/L)
20/25 32 40 50
34/28 37/29 42/35
FXZQ-M
INDOOR UNIT LINEUP
17
Designed with higher airflow suitable for high ceiling application up to 3 metres.
Providing 2 different settings of standard and ceiling soiling prevention, the auto swing mechanism achieves even distribution of airflow and room temperature.
Drain pump is equipped as a standard accessory with 600 mm lift.
Major maintenance work can be performed by removing the panel. A flat-type suction grille and a detachable blade make cleaning easy.
Ceiling Mounted Cassette(Double Flow) Type
FXCQ20M/FXCQ25M/FXCQ32MFXCQ40M/FXCQ50M/FXCQ63MFXCQ80M/FXCQ125M
Thin, lightweight, and easy to install in shallow ceiling spaces
FXCQ-M 20 25/32 6340/50 80 125
34/29 36/30 39/3437/32 41/36 46/40
(240 V)(dB(A))Low operation sound level
Sound level (H/L)
600 mm
305 mm
The low profile unit (only 305 mm high) can be installed in a ceiling space as shallow as 350 mm. All models feature a compact design with a depth of only 600 mm.
(When a high-efficiency filter is attached, the unit's height is 400 mm.)
Two types of optional high-efficiency filter are available (65% and 95%, colourimetric method).
A long-life filter (maintenance free up to one year*) is equipped as a standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
18
Ceiling Mounted CassetteCorner Type
Slim design for flexible installation
3
32˚C 30˚C28˚C 26˚C 24˚C
22˚C
20˚C
2
1
0 1 2 3 4 5 6 (m)
(m)
Main body
Air discharge grille (Option)
Set for front discharge using a suspended ceiling.
Downward discharge is shut off and air is blown straight out (front discharge).
Single-flow type allows effective air discharge from corner or from drop-ceiling.
Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Slim body needs only 220 mm space above the ceiling. If you use a panel spacer (option), the unit can be installed in the minimum space of 195 mm.
Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism achieves even distribution of airflow and room temperature.
Drain pump is equipped as a standard accessory with 500 mm lift.
Main body
Downward discharge
Air discharge grille (Option)
FXKQ25MA/FXKQ32MAFXKQ40MA/FXKQ63MA
500 mm
Panel spacer
20 mm
Min.195 mm
A long-life filter (maintenance free up to one year*) is equipped as a standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
INDOOR UNIT LINEUP
19
Slim Ceiling MountedDuct Type
Slim design, quietness and static pressure switching
External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.
1,100 mm in width for the FXDQ63NB model.
200 mm900 mm
Suction grille*AIR
AIR
Discharge grille*
Air filterSuspension bolt*
240 mm
* To be obtained locally
Only 700 mm
200 mm
Great for hotel use!
Suited for use in drop-ceilings!
Drain pump is equipped as a standard accessory with 750 mm lift.
750 mm
Ceiling
FXDQ20PB/FXDQ25PB/FXDQ32PBFXDQ40NB/FXDQ50NB/FXDQ63NB
Low operation sound level (dB(A))
The values of operation sound level represent those for rear-suction operation.Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). Values are based on the following conditions:FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
Control of the airflow rate has been improved from 2-step to 3-step control.
36/34/32
63
35/33/31
50
34/32/30
40
33/31/29
20/25/32
Sound level(HH/H/L)
FXDQ-PB/NB
20
Ceiling MountedBuilt-in Type
Highly flexible for various application
250 mm
Min.350 mm
Highly flexible installation is possible with a complete lineup of optional kits to satisfy various needs, such as the design concept, interior decoration and so on.
The unit can be installed, if there is a space of 350 mm above ceiling. (when suction panel is used.)
Drain pump is equipped as a standard accessory with 250 mm lift.
High external static pressure allows the use of flexible ducts of various length.
Low operation sound level
41/33.5Sound level
(H/L)
20/25/32 40 50 63 80/100 125
41/34.5 43/37 45/38.5 48/43 49/41.5
(230 V)(dB(A))
FXSYQ-M
Standard
With duct
Cassette style (standard filter)
Cassette style (high efficiency filter)
Long-life filter
Long-life filter
Air suction canvas bellows
Air suction panel
Air suction panel
Access panel
Access panel
Air suction canvas bellows
Ceiling return
Long-life filter
Screening door
High efficiencyfilter
Installation examples ( Optional parts)
The values of operation sound level are based on Australian Standard 1217.6-1985. Measurement is based on bottom-return air entry.
FXSYQ20M/FXSYQ25M/FXSYQ32MFXSYQ40M/FXSYQ50M/FXSYQ63MFXSYQ80M/FXSYQ100M/FXSYQ125M
INDOOR UNIT LINEUP
21
Ceiling Concealed(Duct) Type
High static pressure offers flexible duct designthat blends in with interior décor in stores and offices
FXDYQ80MA/FXDYQ100MAFXDYQ125MA/FXDYQ145MA
Quiet yet powerful supply air fan.
High external static pressure of 120 Pa allows comprehensive duct layout for various applications.
Two external static pressure settings for added flexibility.
Hi-X heat exchanger coils provide even more energy efficiency.
Design of indoor units allows installation in limited roof spaces.
Return air spigots included for ease of installation.
High strength galvanised steel casing.
22
Ceiling MountedDuct Type
Improved ease of installation
Improved ease of maintenance
Middle and high static pressureallows for flexible duct design
All models are only 300 mm in height, an improvement over the 390 mm height of conventional models. The weight of the FXMQ40P has been reduced from 44 kg to 28 kg.
A DC fan motor increases the external static pressure capacity range to include middle to high static pressures, increasing design flexibility.
FXMQ20P/FXMQ25P/FXMQ32PFXMQ40P/FXMQ50P/FXMQ63PFXMQ80P/FXMQ100P/FXMQ125PFXMQ140P
Drain pump is equipped as a standard accessory with 700 mm lift.
Control of the airflow rate has been improved from 2-step to 3-step control.
(dB(A))
700 mm
Ceiling
30 Pa–100 Pa for FXMQ20P-32P30 Pa–160 Pa for FXMQ40P50 Pa–200 Pa for FXMQ50P-125P50 Pa–140 Pa for FXMQ140P
Low operation sound level
300 mm
Easy installation in buildings with narrow ceiling spaces
Airflow rate can be controlled using a remote controller during test operation. With the conventional model, the airflow rate was controlled from the PC board. It is automatically adjusted to the range between approximately ±10% of the rated HH tap airflow for FXMQ20P-125P.
Energy-efficient
The adopted DC fan motor is much more efficient than the conventional AC motor, yielding an approximate 20% decrease in energy consumption (FXMQ125P).
The drain pan can be detached for easy cleaning. An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours.
46/45/43
140
42/40/38
63
43/41/39
80/100
41/39/37
50
39/37/35
40
34/32/30
32
33/31/29
20/25
Soundlevel
(HH/H/L)
FXMQ-P
44/42/40
125
INDOOR UNIT LINEUP
Ceiling Suspended Type
23
Slim body with quiet and wide airflow
Adoption of QUIET STREAM FAN
Drain pump kit (option) can be easily incorporated.
Easy-to-clean flat design
Maintenance is easier because servicing can be performed from below the unit.
Non-dew Flap with no implanted bristles
Uses the quiet stream fan and many advanced technologies.
Sound absorptionmaterial
Turbulent flow is produced
Straightening vane
Quiet stream fan
Installation is easy
Maintenance is easy
Bristle-free Flap minimises contamination and makes cleaning simpler.
Non-dew Flap
100°
Wide air discharge openings produce a spreading 100° airflow.
FXHQ32MA/FXHQ63MAFXHQ100MA
FXHQ-MA
Sound level(H/L)
32
36/31
63
39/34
100
45/37
(dB(A))Low operation sound level
Drain pump kit(Built inside main unit)
600 mm
A long-life filter (maintenance free up to one year*) is equipped as a standard accessory.* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
24
Wall Mounted Type
Stylish flat panel design harmonised with your interior décor
FXAQ20P/FXAQ25PFXAQ32P/FXAQ40PFXAQ50P/FXAQ63P
New
Drain pan and air filter can be kept clean by mould-proof polystyrene.
Drain pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.
Vertical auto-swing realises efficiency of air distribution. The louvre closes automatically when the unit stops.
5 steps of discharge angle can be set by remote controller.
Discharge angle is automatically set at the same angle as the previous operation when restarting. (Initial setting: 10˚ for cooling and 70˚ for heating)
Flexible installationDrain pipe can be fitted to from either left or right sides. Drain pump kit
1,000 mm
Height of drain-up
Indoor unit
Stylish flat panel design creates a graceful harmony that enhances any interior space.
Flat panel can be cleaned with only the single pass of a cloth across their smooth surface.Flat panel can also be easily removed and washed for more thorough cleaning.
Low operation sound level
47/41
63
42/37
50
39/34
40
38/31
32
36/31
25
35/31
20
Sound level(H/L)
FXAQ-P
(dB(A))
INDOOR UNIT LINEUP
Floor Standing Type
25
Suitable for perimeter zone air conditioning
Wall hanging Floor installation
Floor Standing types can be hung on the wall for easier floor cleaning. Running the piping from the back allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is considerably easier.
The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier.
Concealed FloorStanding Type
Designed to be concealed in the perimeter skirting-wall
Connecting port
Refrigerant piping
Applies also to Floor Standing type (FXLQ-MA).
The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.
The connecting port faces downward, greatly facilitating on-site piping work.
FXNQ20MA/FXNQ25MAFXNQ32MA/FXNQ40MAFXNQ50MA/FXNQ63MA
FXLQ20MA/FXLQ25MAFXLQ32MA/FXLQ40MAFXLQ50MA/FXLQ63MA
A long-life filter (maintenance free up to one year*) is equipped as a standard accessory.* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
A long-life filter (maintenance free up to one year*) is equipped as a standard accessory.* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
26
Ceiling SuspendedCassette Type
This thin indoor unit achieves optimumair distribution, and can be installedwithout the need for ceiling cavity
FXUQ71MAFXUQ100MAFXUQ125MA
Connection unit Connection unit is the device for connecting above indoor unit to VRVIII-S.
Depending on installation site requirements or room conditions, 2-way, 3-way and 4-way discharge patterns are available.
4-way airflowfrom the centre of the store.
The 3-way airflow can distributecomfortable air throughout the room.
Only one unit is needed to distribute comfortable airthroughout an L-shaped store.
BEVQ-MA
Connection unit for indoor unit
Indoor unitPiping length*1
Indoor unit
Remote controller
Super wiring (DIII-NET)
Single-phase 220-240 Vpower supply
VRV -S series outdoor unit
Refrigerant piping layout External wiring layout
Notes:
Gas pipeLiquid pipe
ModelMaximum piping lengthbetween the BEV unitand the indoor unit.
FXUQ-MA 5 m
*1
• When connecting centralised-control device, it is necessary to install an interface adaptor for an indoor unit (DTA102A52).
• Connection unit BEVQ-MA is necessary for each indoor unit.
• The refrigerant piping height difference between the indoor units and the BEV unit must be within 4 m.
• The BEV unit must be installed within a maximum height difference between indoor units of 15 m.
• Branching of the refrigerant piping is not possible downstream of the BEV unit.
BEVQ71MA/BEVQ100MA/BEVQ125MA
SPECIFICATIONS
27
INDOOR UNITSCeiling Mounted Cassette (Round Flow) Type
Ceiling Mounted Cassette (Compact Multi Flow) Type
FXFQ25PVE
2.9
9,900
2,500
3.2
10,900
Galvanised steel plate
2,800
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
BYCP125K-W1
Fresh white
50X950X950
5.5
50X950X950
5.5
50X950X950
5.5
50X950X950
5.5
50X950X950
5.5
50X950X950
5.5
50X950X950
5.5
50X950X950
5.5
6.4
12.7
FXFQ32PVE
3.7
12,600
3,200
4.0
13,600
3,400
250/216/183216/191/166 216/191/166
6.4
12.7
FXFQ40PVE
4.7
16,000
4,000
5.0
17,100
4,300
266/225/183
6.4
12.7
FXFQ50PVE
5.8
19,800
5,000
6.3
21,500
5,400
316/275/225
9.5
15.9
FXFQ63PVE
7.3
24,900
6,300
8.0
27,300
6,900
350/300/250
9.5
15.9
FXFQ80PVE
9.3
2.8 3.6 4.5 5.6 7.1 9.0
31,700
8,000
10.0
34,100
8,600
FXFQ100PVE
11.6
39,600
10,000
12.5
42,700
10,800
FXFQ125PVE
14.5
11.2 14.0
49,500
12,500
16.0
54,600
13,800
533/433/333
9.5
15.9
550/466/375
9.5
15.9
Heating capacity
kW
Btu/h
kcal/h
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
Airflow rate (HH/H/L) /s
48/46.5/45 48/46.5/45 49/47/45 50/47.5/45 52/49/46 53/51.5/49 60/54.5/50 61/56/52dB(A)Sound power (HH/H/L)
Power consumption
kWCooling
Heating
0.033 0.033 0.047 0.052 0.066 0.093 0.187 0.209
0.027 0.027 0.034 0.038 0.053 0.075 0.174 0.200
15/13/1113/11.5/10 13/11.5/10 16/13.5/11 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5m3/min
30/28.5/27 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
246X840X840
19.5
246X840X840
19.5
246X840X840
19.5
246X840X840
19.5
246X840X840
22
246X840X840
22
288X840X840
25
288X840X840
25
MODEL
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Power supply
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Drain
Panel(Option)
Model
Colour
mmDimensions (HXWXD)
Weight kg
Liquid (Flare)
Gas (Flare) mm
dB(A)Sound level (HH/H/L)
MODEL
kW(*1) 2.3
150/116
Btu/h(*1)
kcal/h(*1)
Heating capacitykW
Btu/h
9/7
FXZQ25MVE
2.9
9,900
2,500
3.2
10,900
2,800
150/116
9/7
FXZQ32MVE
3.7
12,600
3,200
4.0
13,600
3,400
158/125
9.5/7.5
FXZQ40MVE
4.7
(*2) 2.8 3.6 4.5
16,000
4,000
5.0
17,100
4,300
183/133
11/8
286X575X575
18
6.4
12.7
VP20 (External Dia, 26/Internal Dia, 20)
BYFQ60B8W1
White (6.5Y9.5/0.5)
55X700X700
2.7
6.4
12.7
55X700X700
2.7
6.4
12.7
55X700X700
2.7
6.4
12.7
55X700X700
2.7
Dimensions (HXWXD) mm
Machine weight kg
kcal/h
Casing
Power supply
Airflow rate (H/L)
Cooling capacity
FXZQ50MVE
5.8
5.6
19,800
5,000
6.3
21,500
5,400
233/166
14/10
6.4
12.7
55X700X700
2.7
m3/min
/s
8,500
2,200
Galvanised steel plate
2.5
7,800
2,000
1-phase, 220-240 V/220 V, 50 Hz/60 Hz
FXZQ20MVE
2.2
Sound power (H) dB(A)240 V 49 49 51 54 59
Sound level (H/L) dB(A)240 V 32/26 32/26 34/28 37/29 42/35
Power consumption kW
Cooling
Heating 0.064
0.073
0.064
0.073
0.068
0.076
0.080
0.089
0.107
0.115
Pipingconnections
Drain
Panel(Option)
Model
Colour
mmDimensions (HXWXD)
Weight kg
Liquid (Flare)
Gas (Flare) mm
Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
28
INDOOR UNITSCeiling Mounted Cassette (Double Flow) Type
Ceiling Mounted Cassette Corner Type
FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE
2.3
7,800
2,000
2.5
8,500
Galvanised steel plate
2,200
116/83
305X775X600
26
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
BYBC32G-W1
White (10Y9/0.5)
53X1,030X680
8.0
2.9
9,900
2,500
3.2
10,900
2,800
150/108
305X775X600
26
6.4
12.7
53X1,030X680
8.0
3.7
12,600
3,200
4.0
13,600
3,400
150/108
305X775X600
26
6.4
12.7
53X1,030X680
8.0
4.7
16,000
4,000
5.0
17,100
4,300
200/150
305X990X600
31
6.4
12.7
BYBC50G-W1
53X1,245X680
8.5
5.8
19,800
5,000
6.3
21,500
5,400
200/150
305X990X600
32
6.4
12.7
53X1,245X680
8.5
7.3
24,900
6,300
8.0
27,300
6,900
275/216
305X1,175X600
35
9.5
15.9
BYBC63G-W1
53X1,430X680
9.5
9.3
31,700
8,000
10.0
34,100
8,600
433/350
305X1,665X600
47
9.5
15.9
BYBC125G-W1
53X1,920X680
12.0
14.5
2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0
49,500
12,500
16.0
54,600
13,800
550/416
34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40
305X1,665X600
48
9.5
15.9
53X1,920X680
12.0
Heating capacity
kW
Btu/h
kcal/h
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
Airflow rate (H/L)/s
Sound level (H/L) 240 V dB(A)
0.077 0.092 0.092 0.130 0.130 0.161 0.209 0.256
0.044 0.059 0.059 0.097 0.097 0.126 0.176 0.223
7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25m3/min
Power consumption
kWCooling
Heating
MODEL
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Power supply
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Drain
Panel(Option)
Model
Colour
mmDimensions (HXWXD)
Weight kg
Liquid (Flare)
Gas (Flare) mm
kW(*1)
Btu/h(*1)
kcal/h(*1)
(*2)
Power supply
Cooling capacity
MODEL
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Drain
Panel(Option)
Model
Colour
mm
kg
Dimensions (HXWXD)
Liquid (Flare)
Gas (Flare) mm
Weight
FXKQ25MAVE
2.9
9,900
2,500
3.2
10,900
Galvanised steel plate
2,800
183/150
Heating capacity
kW
Btu/h
FXKQ32MAVE
3.7
12,600
3,200
4.0
13,600
3,400
FXKQ40MAVE
4.7
16,000
4,000
5.0
17,100
4,300
FXKQ63MAVE
7.3
2.8 3.6 4.5 7.1
24,900
6,300
8.0
27,300
6,900
183/150 216/166 300/250
kcal/h
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
Airflow rate (H/L) /s
215X1,110X710
31
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
BYK45FJW1
White (10Y9/0.5)
70X1,240X800
8.5
215X1,110X710
31
6.4
12.7
70X1,240X800
8.5
215X1,110X710
31
6.4
12.7
70X1,240X800
8.5
215X1,310X710
34
9.5
15.9
BYK71FJW1
70X1,440X800
9.5
40/35 40/35 42/36 44/39Sound level (H/L) 240 V dB(A)
Power consumption kW
Cooling
Heating
0.066 0.066 0.076 0.105
0.046 0.046 0.056 0.085
11/9 11/9 13/10 18/15m3/min
Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
SPECIFICATIONS
29
INDOOR UNITS
Slim Ceiling Mounted Duct Type (700 mm width type)
Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
Galvanised steel plate
7,800
2,000
9,900
2,500
12,600
3,200
2.2
133/120/106 133/120/106 133/120/106
33/31/29 33/31/29 33/31/29
8,500
2,200
10,900
2,800
13,600
3,400
Btu/h
2.5 3.2 4.0kW
kcal/h
Heating capacity
1-phase, 220-240 V/220 V, 50/60 HzPower supply
200X700X620
23
6.4
12.7
200X700X620
23
6.4
12.7
200X700X620
23
6.4
12.7
51 51 51dB(A)Sound power (HH)
2.8 3.6
2.3 2.9 3.7
VP20 (External Dia, 26/Internal Dia, 20)
30-10 1
MODEL FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
0.067 0.067 0.070
0.086 0.086 0.089
8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Drain
Liquid (Flare)
Gas (Flare) mm
Cooling
Heating
Airflow rate (HH/H/L) /s
m3/min
dB(A)
Casing
Sound level (HH/H/L)
PaExternal static pressure
32
Power consumption
kW
Galvanised steel plate
16,000
4,000
19,800
5,000
24,900
6,300
17,100
4,300
21,500
5,400
27,300
6,900
Btu/h
5.0 6.3 8.0kW
kcal/h
175/158/141 208/183/166 275/241/216
34/32/30 35/33/31 36/34/32
Heating capacity
1-phase, 220-240 V/220 V, 50/60 HzPower supply
200X900X620
27
6.4
12.7
200X900X620
28
6.4
12.7
200X1,100X620
31
9.5
15.9
52 53 54dB(A)Sound power (HH)
4.5 5.6 7.1
4.7 5.8 7.3
VP20 (External Dia, 26/Internal Dia, 20)
44-15 1
MODEL FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
0.160 0.165 0.181
0.147 0.152 0.168
10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Drain
Liquid (Flare)
Gas (Flare) mm
Casing
Cooling
Heating
Power consumption
kW
Airflow rate (HH/H/L) /s
m3/min
dB(A)Sound level (HH/H/L)
PaExternal static pressure
32
1: External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard".(Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).3: Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
30
INDOOR UNITSCeiling Mounted Built-in Type
Ceiling Concealed (Duct) Type
1-phase, 220-240 V, 50 Hz
FXDYQ80MAV1 FXDYQ100MAV1 FXDYQ125MAV1 FXDYQ145MAV1
8.8
31,700
8,000
11.2
39,600
10,000
13.9
49,500
12,500
16.0
9.3 11.6 14.5 16.9
57,600
14,500
Galvanised steel plate
9.9
33,800
8,480
510
30.6
12.5
42,700
10,800
778
46.7
16.0
54,600
13,800
852
51.1
18.4
62,800
15,800
957
57.4
120 120 120 120
VP25 (External Dia, 32/Internal Dia, 25)
360X1168X869
50
9.5
15.9
360X1478X899
60
9.5
15.9
360X1478X899
65
9.5
15.9
360X1478X899
66
9.5
15.9
45 46 48 51
3 3 3 3
0.415
0.415
0.700
0.700
0.780
0.780
0.880
0.880
MODEL
Cooling capacity
(*2)
Btu/h(*1)
kcal/h(*1)
Power supply
(*1)kW
Pa
Heating capacity
kW
Btu/h
kcal/h
/s
m3/min
External static pressure (H)
Casing
Airflow rate (H)
240 VSound level (H)
Dimensions (HXWXD) mm
Machine weight kg
Piping connections
Drain
dB(A)
Liquid (Flare)
Gas (Flare) mm
Power consumption kW
Cooling
Heating
Galvanised steel plate
FXSYQ20MVE FXSYQ25MVE FXSYQ32MVE FXSYQ40MVE FXSYQ50MVE FXSYQ63MVE FXSYQ80MVE FXSYQ100MVE FXSYQ125MVE
7,900
2,000
2.5
8,500
2,200
9,900
2,500
3.2
10,900
2,800
12,600
3,200
4.0
13,600
3,400
16,000
4,000
5.0
17,100
4,300
19,800
5,000
6.3
21,500
5,400
24,900
6,300
8.0
27,300
6,900
31,700
8,000
10.0
34,100
8,600
39,600
10,000
12.5
42,700
10,800
2.2
49,500
12,500
16.0
54,600
13,800
kW
Btu/h
kcal/h
150/112 150/112 158/112 191/143 250/190 350/235 450/355 466/370 633/457
Casing
1-phase, 220-240 V, 50 Hz
41/33.5 41/34.5 48/43 48/43 49/41.543/37 45/38.541/33.5 41/33.5Sound level (H/L)
2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
2.3 2.9 3.7 4.7 5.8 7.3 9.3 11.6 14.5
Heating capacity
300X550X800
30
6.4
12.7
VP25 (External Dia, 32/Internal Dia, 25)
300X550X800
30
6.4
12.7
300X550X800
30
6.4
12.7
300X700X800
34
6.4
12.7
300X700X800
35
6.4
12.7
300X1,000X800
44
9.5
15.9
300X1,400X800
57
9.5
15.9
300X1,400X800
57
9.5
15.9
300X1,400X800
57
9.5
15.9
White (10Y9/0.5)
55X650X500
3.0
55X650X500
3.0
55X650X500
3.0
55X800X500
3.5
55X800X500
3.5
55X1,100X500
4.5
55X1,500X500
6.5
55X1,500X500
6.5
55X1,500X500
6.5
BYBS32DJW1 BYBS32DJW1 BYBS32DJW1 BYBS45DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1
230 V dB(A)
58/50.5 58/51.5 65.5/60 65.5/60 66/5960/54 62/55.558/50.5 58/50.5Sound power (H/L) 230 V dB(A)
98-65-33 98-65-33 88-57-27 96-65-57 86-58-43 115-84-52 140-122-61 138-118-53 98-5811 1 1 1 1 1 21
Power consumption kW
Cooling
Heating 0.089 0.089 0.096 0.106 0.145 0.178 0.304 0.309 0.366
0.089 0.089 0.096 0.106 0.145 0.178 0.304 0.309 0.366
9/6.72 9/6.72 9.5/6.72 11.5/8.58 15/11.4 21/14.1 27/21.3 28/22.2 38/27.42
kW(*1)
Btu/h(*1)
kcal/h(*1)
(*2)
Power supply
Cooling capacity
MODEL
External static pressure Pa
Airflow rate (H/L) /s
m3/min
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Drain
Panel(Option)
Model
Colour
mm
kg
Dimensions (HXWXD)
Liquid (Flare)
Gas (Flare) mm
Weight
Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: (FXSYQ) Anechoic chamber conversion value, based on Australian Standard 1217.6-1985. Measurement is based on bottom-return air entry. (FXDYQ) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.•For FXDYQ models, an air filter is not a standard accessory. A suitable locally obtained filter must be installed in the return air duct. 1: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard-Low static pressure". 2: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard". 3: External static pressure is changeable to change over the connectors inside electrical box (High static pressure-Standard static pressure). The data above is for high static pressure setting.
SPECIFICATIONS
31
INDOOR UNITSCeiling Mounted Duct Type
FXMQ40PVE FXMQ50PVE
4.7
16,000
4,000
5.0
17,100
Galvanised steel plate
4,300
267/216/183
300X700X700
28
VP25 (External Dia, 32/Internal Dia, 25)
5.8
19,800
5,000
6.3
21,500
5,400
300/275/250
300X1,000X700
36
4.5 5.6
Heating capacity
kW
Btu/h
kcal/h
/s
External static pressure
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
6.4
12.7
6.4
12.7
Power consumption kW
Heating
Cooling 0.194 0.215
0.182 0.203
Airflow rate (HH/H/L)16/13/11 18/16.5/15m3/min
Pa 30-160 50-2001 1
39/37/35
FXMQ20PVE
2.3
7,800
2,000
2.5
8,500
2,200
150/125/108
300X550X700
25
2.2
6.4
12.7
0.081
0.069
9/7.5/6.5
30-100
33/31/29
FXMQ25PVE
2.9
9,900
2,500
3.2
10,900
2,800
150/125/108
300X550X700
25
2.8
6.4
12.7
0.081
0.069
9/7.5/6.5
30-100
33/31/29
FXMQ32PVE
3.7
12,600
3,200
4.0
13,600
3,400
158/133/116
300X550X700
25
3.6
6.4
12.7
0.085
0.073
9.5/8/7
30-100
34/32/30 41/39/37Sound level (HH/H/L) dB(A)
5751 51 52 59Sound power (H) dB(A)
(*1)
(*2)
MODELPower supply
Cooling capacity
kW
Btu/h(*1)
kcal/h(*1)
Drain
Dimensions (HXWXD) mm
Machine weight kg
Pipingconnections
Liquid (Flare)
Gas (Flare) mm
1 1 1
FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE
Galvanised steel plate
VP25 (External Dia, 32/Internal Dia, 25)
7.3
24,900
6,300
8.0
27,300
6,900
325/292/267
300X1,000X700
36
9.5
15.9
9.3
31,700
8,000
10.0
34,100
8,600
417/375/333
300X1,000X700
36
9.5
15.9
11.6
39,600
10,000
12.5
42,700
10,800
533/450/383
300X1,400X700
46
9.5
15.9
14.5
49,500
12,500
16.0
54,600
13,800
650/550/466
300X1,400X700
46
9.5
15.9
7.1 9.0 11.2 14.0
Heating capacity
kW
Btu/h
kcal/h
/s
External static pressure
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
Power consumption kW
Heating
Cooling 0.230 0.298 0.376 0.461
0.218 0.286 0.364 0.449
Airflow rate (HH/H/L)19.5/17.5/16 25/22.5/20 32/27/23 39/33/28m3/min
Pa 50-200 50-200 50-200 50-200 1 1 1 1
42/40/38 43/41/39 43/41/39 44/42/40
FXMQ140PVE
16.7
57,000
14,300
18.0
61,400
15,500
766/649/533
300X1,400X700
47
9.5
15.9
16.0
0.461
0.449
46/39/32
50-140 1
46/45/43Sound level (HH/H/L) dB(A)
60 61 61 62 64Sound power (H) dB(A)
(*1)
(*2)
MODELPower supply
Cooling capacity
kW
Btu/h(*1)
kcal/h(*1)
Drain
Dimensions (HXWXD) mm
Machine weight kg
Liquid (Flare)
Gas (Flare) mmPipingconnections
Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50-
125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.
32
INDOOR UNITSCeiling Suspended Type
MODELPower supply
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
m3/min
Dimensions (HXWXD) mm
Machine weight kg
/sAirflow rate (H/L)
dB(A)Sound level (H/L)
Pipingconnections
Drain
Liquid (Flare)
Gas (Flare) mm
FXHQ32MAVE
3.7
12,600
3,200
4.0
13,600
White (10Y9/0.5)
3,400
FXHQ63MAVE
7.3
24,900
6,300
8.0
27,300
6,900
FXHQ100MAVE
11.6
3.6 7.1 11.2
39,600
10,000
12.5
42,700
10,800
Heating capacity
kW
Btu/h
kcal/h
200/166 291/233 416/325
195X960X680
24
6.4
12.7
VP20 (External Dia, 26/Internal Dia, 20)
195X1,160X680
28
9.5
15.9
195X1,400X680
33
9.5
15.9
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
36/31 39/34 45/37
kW0.111 0.115 0.135
0.111 0.115 0.135
12/10 17.5/14 25/19.5
Power consumption
Cooling
Heating
Wall Mounted Type
Note : Specifications are based on the following conditions;•Cooling: Indoor temp.: (*1) 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level : Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
FXAQ25PVE
2.9
3.2
White (3.0Y8.5/0.5)
36/31
290X795X238
11
Casing
1-phase, 220-240/220V, 50/60Hz
38/31
290X795X238
11
FXAQ40PVE
4.7
5.0
39/34
290X1,050X238
14
9,900 16,000
2,500 4,000
10,900 17,100
2,800 4,300
Airflow rate (H/L)
13,600
3,400
FXAQ32PVE
3.7
12,600
3,200
4.0
2.8
FXAQ20PVE
2.3
2.5
35/31
290X795X238
11
7,800
2,000
8,500
2,200
2.2 4.53.6
VP13 (External Dia, 18/Internal Dia, 13)
6.4 6.4 6.4 6.4
12.7 12.7 12.7 12.7
42/37
290X1,050X238
14
FXAQ63PVE
7.3
24,900
6,300
27,300
6,900
8.0
47/41
290X1,050X238
14
21,500
5,400
6.3
5,000
FXAQ50PVE
5.8
19,800
7.15.6
6.4 9.5
12.7 15.9
0.028 0.030 0.020 0.033 0.0500.019
0.034 0.035 0.020 0.039 0.0600.029
Heating capacity
kW
Btu/h
kcal/h
MODELPower supply
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Dimensions (HXWXD) mm
Machine weight kg
dB(A)Sound level (H/L)
Pipingconnections
Drain
Liquid (Flare)
Gas (Flare) mm
Power consumption kW
Heating
Cooling
8/5 8.5/5.5 12/9
/s
m3/min
133/83 142/91
7.5/4.5
125/75 200/150 250/200 316/233
15/12 19/14
SPECIFICATIONS
/s
33
INDOOR UNITS
Connection unit series indoor units
Ceiling Suspended Cassette Type
kW(*1)
(*2)
Kcal/h(*1)
Power supply
8.3
7,100
1-phase, 220-240 V, 50 Hz
Btu/h(*1) 28,300
kW
Kcal/h
Heating capacity (Max.)
9.0
7,700
Btu/h 30,700
Ind
oo
r u
nit Airflow rate (H/L)
Sound power (H)
Casing
dB(A)
mmDimensions (HXWXD)
kgMachine weight
56
Piping connections
Liquid
Gas
Drain VP 20 (External Dia. 26/Internal Dia. 20)
25
White(10Y9/0.5)
316/233
165X895X895
9.5 (Flare)
15.9 (Flare)
11.6
10,000
39,600
12.5
10,800
42,700
59
31
483/350
230X895X895
14.5
8.0 11.2 14.0
12,500
49,500
14.0
12,000
47,800
60
Sound level (H/L) dB(A) 40/35 43/38 44/39
31
533/383
230X895X895
mm
Cooling capacity
MODELIndoor unit
Connection unit BEVQ71MAVE
FXUQ71MAV1
BEVQ100MAVE
FXUQ100MAV1
BEVQ125MAVE
FXUQ125MAV1
* A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data Book for details.* If indoor units from the Connection unit series are connected within a single refrigerant system to indoor units from any other series, cooling/heating switchover will
not be possible using the remote controller of the Connection unit series indoor units. However, if the remote controller of an indoor unit from the other series is set as a master remote controller, cooling/heating switchover will be possible.
* If all indoor units are from the Connection unit series, an outdoor unit Cool/Heat selector will be needed to enable cooling/heating switchover. * Group control between Connection Unit series equipment within one system is possible. However, group control with the other VRV indoor units is not possible.
kWPowerconsumption 0.169
0.189
0.278
0.298
0.278
0.298Cooling
Heating
m3/min 19/14 29/21 32/23
230 V
Floor Standing Type/Concealed Floor Standing Type
FXLQ
FXNQ
FXLQ20MAVE
2.3
7,800
2,000
8,500
FXLQ:Ivory white (5Y7.5/1) / FXNQ:Galvanised steel plate
2,200
Heating capacity
kW
Btu/h
kcal/h
Casing
Airflow rate (H/L) /s 116/100
600X1,000X222
25
6.4
12.7
21O.D.
2.2
FXLQ25MAVE
2.9
9,900
2,500
10,900
2,800
116/100
600X1,000X222
25
6.4
12.7
2.8
FXLQ32MAVE
3.7
12,600
3,200
13,600
3,400
133/100
600X1,140X222
30
6.4
12.7
3.6
FXLQ40MAVE
4.7
16,000
4,000
17,100
4,300
183/141
600X1,140X222
30
6.4
12.7
4.5
FXLQ50MAVE
5.8
19,800
5,000
6.3
21,500
5,400
233/183
600X1,420X222
36
6.4
12.7
5.6
FXLQ63MAVE
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
7.3
24,900
6,300
8.0
27,300
6,900
266/200
600X1,420X222
610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220
36
19 19 23 23 27 27
9.5
15.9
7.1
2.5 3.2 4.0 5.0
37/34 37/34 37/34 40/35 41/36 42/37
1-phase, 220-240 V/220 V, 50/60 Hz
Sound level (H/L) dB(A)240 V
0.049 0.049 0.090 0.090 0.110 0.110
0.049 0.049 0.090 0.090 0.110 0.110
m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12
kWPower consumption
Cooling
Heating
MODEL
Power supply
Cooling capacity
kW(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Dimensions (HXWXD)
Machine weight
mmFXLQ
FXNQ
kgFXLQ
FXNQ
Pipingconnections
Drain
Liquid (Flare)
Gas (Flare) mm
Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: (FXLQ-MA,FXNQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXUQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.During actual operation, these values are normally somewhat higher as a result of ambient conditions.
34
OUTDOOR UNITS
Heat PumpMODEL
ø15.9 (Flare)
Note: Specifications are based on the following conditions;• Cooling: Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.• Refrigerant charge is required.
68
9,600
RXYMQ4PV4A
50/52
10,800
38,200
42,700
11.2
12.5
2.95
3.27
2.5
71
13,300
RXYMQ6PV4A
ø19.1 (Brazing)
53/55
15,500
52,900
61,400
15.5
18.0
4.44
4.82
3.5
1-phase, 230–240 V, 50 Hz
24 to 100
Hermetically sealed scroll type
1,345 x 900 x 320
125
ø9.5 (Flare)
69
R-410A
-5 to 46-20 to 15.5
12,000
RXYMQ5PV4A
51/53
13,800
47,800
54,600
14.0
16.0
3.97
4.09
4.0
106
3.0
Ivory white (5Y7.5/1)
1,766
%
m3/min
mm
Kcal/h
Kcal/h
kg
kW
mm
dB(A)
kg
dB(A)
kW
°CWB
°CDB
Btu/h
Btu/h
kW
kW
/s
Motor output
Type
Liquid
Gas
Charge
Type
Heating
Cooling
Heating
Cooling
Power supply
Cooling capacity
Capacity control
Casing colour
Compressor
Dimensions (H x W x D)
Heating capacity
Machine weight
Piping connections
Sound power
Operation range
Refrigerant
Sound level (Cooling/Heating)
Power consumption
Airflow rate
OPTION LIST
35
Ceiling Mounted Cassette (Double Flow) Type
No.
1
2
Decoration PanelHigh efficiency filter 65% 1
High efficiency filter 90% 1
Long life replacement filter
Filter related bottom suction
FXCQ20MFXCQ25MFXCQ32M
FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M
KAFJ532G36 KAFJ532G56 KAFJ532G160KAFJ532G80KAFJ533G36 KAFJ533G56 KAFJ533G160KAFJ533G80KDDFJ53G36Filter chamber KDDFJ53G56 KDDFJ53G160KDDFJ53G80KAFJ531G36 KAFJ531G56 KAFJ531G160KAFJ531G80
Type
ItemBYBC32G-W1 BYBC50G-W1 BYBC125G-W1BYBC63G-W1
Note: 1 Filter chamber is required if installing high efficiency filter.
Ceiling Mounted Cassette Corner Type
Ceiling Mounted Cassette (Compact Multi Flow) Type
INDOOR UNITS
Ceiling Mounted Cassette (Round Flow) Type
Slim Ceiling Mounted Duct Type (900/1,100 mm width type)Type
No. FXDQ20PB FXDQ25PB FXDQ32PB
1 KDT25N32Insulation kit for high humidity
Slim Ceiling Mounted Duct Type (700 mm width type)TypeItem
No.
1 KDT25N50 KDT25N63Insulation kit for high humidity
TypeItem FXDQ63NBFXDQ50NBFXDQ40NB
FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125PNo. TypeItem
1
4
BYCP125K-W1
KAFP556B80 KAFP556B160KAFP557B80 KAFP557B160KAFP552B80 KAFP552B160KAFP553B80 KAFP553B160
KDTP55K160
KDJP55B160
Filter related
5 Fresh air intake kit
Decoration panel2 KDBH55K160FSealing member of air discharge outlet3 KDBP55H160FAPanel spacer
High efficiency filter unit 65%High efficiency filter unit 90%Replacement high efficiency filter 65%Replacement high efficiency filter 90%Filter chamberLong life replacement filter Non-woven type
Chamber typeWithout T shape and fanWith T shape without fan
KDDFP55B160
Ultra long-life filterReplacement ultra long-life filter
Direct installation type
KAFP551K160KAFP55B160
KAFP55H160HKDDP55B160
KDDP55B160KKDDP55X160
6 KDJP55B80Branch duct chamber7 KKSJ55KA160Chamber connection kit8 KDTP55K80Insulation kit for high humidity
No. FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M1 Decoration panel2 Sealing member of air discharge outlet3 Panel spacer4 Replacement long-life filter
BYFQ60B8W1KDBH44BA60
KDBQ44BA60AKAFQ441BA60
5 Fresh air intake kit Direct installation type KDDQ44XA60
TypeItem
No. TypeItem FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA
1
2
BYK45FJW1 BYK71FJW1KPBJ52F56W KPBJ52F80WKAFJ521F56 KAFJ521F80
K-HV7AW K-HV9AWKDBJ52F56W KDBJ52F80WKFDJ52FA56 KFDJ52FA80
Panel related
Air inlet and air discharge outlet related
Decoration panelPanel spacerLong life replacement filterAir discharge grilleAir discharge blind panelFlexible duct (with shutter)
36
INDOOR UNITS
Ceiling Suspended Type
Wall Mounted TypeFXAQ25PFXAQ20P
1 Drain pump kit K-KDU572EVE
FXAQ32P FXAQ40P FXAQ50P FXAQ63PNo. TypeItem
Floor Standing TypeFXLQ20MA
1 Long life replacement filter
FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA
KAFJ361K28 KAFJ361K45 KAFJ361K71
No. TypeItem
Ceiling Concealed (Duct) TypeFXDYQ80MA
1 Run/fault status PCB KRP1B5X
FXDYQ100MA FXDYQ125MA FXDYQ145MANo. TypeItem
Ceiling Mounted Built-in Type
Ceiling Mounted Duct Type
FXSYQ20MFXSYQ25MFXSYQ32M
1BYBS32DJW1
KTBJ25K36W
FXSYQ40MFXSYQ50M
BYBS45DJW1
KTB25KA56W
FXSYQ63M
BYBS71DJW1
KTB25KA80W
FXSYQ80MFXSYQ100MFXSYQ125MBYBS125DJW1
KTB25KA160WPanel related
Decoration panel
Access panel
2
KAFJ252L36
KAFJ253L36
KAF252LA56
KAF253LA56
KAF252LA80
KAF253LA80
KAF252LA160
KAF253LA160Filter related
High efficiency filter 65%
High efficiency filter 90%
KAFJ251K36 KAFJ251K56 KAFJ251K80 KAFJ251K160
KAJ25L36D KAJ25LA56D KAJ25LA80D KAJ25LA160D
Long life replacement filter
KSA-25K36
KBBJ25K36
KSA-25KA56
KBBJ25KA56
KSA-25KA80
KBBJ25KA80
KSA-25KA160
KBBJ25KA160
Air suction canvas
Screening door3 Air inlet related
Filter chamber for bottom suction
No.Type
Item
Note: 1 If installing a high efficiency filter in the Ceiling Mounted Built-in type, a filter chamber for bottom suction is required.
1
1
No. FXMQ40PFXMQ50PFXMQ63PFXMQ80P
FXMQ20PFXMQ25PFXMQ32P
FXMQ100PFXMQ125PFXMQ140P
FXMQ200MAFXMQ250MA
KDU30L250VE—
KAFJ372L280KAF372AA80 KAF372AA160
KAFJ373L280KAF373AA80 KAF373AA160
KDJ3705L280KDDF37AA80 KDDF37AA160
KAFJ371L280KAF371AA80 KAF371AA160
KAF375AA80
KAF372AA56
KAF373AA56
KDDF37AA56
KAF371AA56
KAF375AA56
KAF372AA36
KAF373AA36
KDDF37AA36
KAF371AA36
KAF375AA36 KAF375AA160
KTB25KA80W KTB25KA160W
KTBJ25K80F KTBJ25K160F
KTBJ25K80T
KTB25KA56W
KTBJ25K56F
KTBJ25K56T
KTBJ25K36W
KTBJ25K36F
KTBJ25K36T KTBJ25K160T
—
KDAJ25K71AKDAJ25K56AKDAJ25K36A KDAJ25K140A
Item1 Drain pump kit
3 Filter chamber
2 High efficiency filter65%
90%
4 Long life replacement filter
5 Long life filter chamber kit
6 Service panel
White
Fresh white
Brown
7 Air discharge adaptor
Type
FXHQ32MA
1 Drain pump kit
2 Replacement long-life filter (Resin net)
KDU50N60VE
KAF501DA56
3 L-type piping kit (for upward direction) KHFP5MA63
FXHQ63MA
KDU50N125VE
KAF501DA80
KHFP5MA160
FXHQ100MA
KAF501DA112
No. TypeItem
OPTION LIST
37
Heat PumpNo.
1
1-1
2
3
RXYMQ4P
KJB111A
KHRP26M22H (Max. 4 branch)
KHRP26M33H (Max. 8 branch)
KHRP26A22T
KRC19-26A
RXYMQ5P RXYMQ6P
5 KPT-60B160
6 K-KYZP15C
4 KKPJ5F180
Concealed Floor Standing TypeFXNQ20MA
1 Long life replacement filter
FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
KAFJ361K28 KAFJ361K45 KAFJ361K71
No. TypeItem
Ceiling Suspended Cassette Type
Item
CONTROL SYSTEMS
INDOOR UNITS
OUTDOOR UNITS
Operation Control System Optional AccessoriesNo.
3
4
Remote controllerWireless
Simplified remote controller (Exposed type)
5 Adaptor for wiring
6-1 Wiring adaptor for electrical appendices (1)
6-2 Wiring adaptor for electrical appendices (2)
Remote controller for hotel use (Concealed type)
7 Remote sensor (for indoor temperature)
9 External control adaptor for outdoor unit
TypeItem
8 Installation box for adaptor PCB
1
Note: 1. Installation box is necessary for each adaptor marked .2. Up to 2 adaptors can be fixed for each installation box.
5. Installation box is necessary for second adaptor.6. Installation box is necessary for each adaptor.
3. Only one installation box can be installed for each indoor unit.4. Up to 2 installation boxes can be installed for each indoor unit.
FXFQ-P
BRC7F634F
—
—
KRP1C63
KRP2A62
KRP4AA53
KRCS01-4B
10 Adaptor for multi tenant — DTA114A61DTA114A61DTA114A61 ——
Note 2,3KRP1H98
DTA104A62
FXZQ-M
BRC7E530W
KRP1BA57
KRP2A62
KRP4AA53
KRCS01-1B KRCS01-4B KRCS01-1B
Note 4,6KRP1BA101
FXCQ-M
BRC7C62
KRP1B61
KRP2A61
KRP4AA51
Note 2,3KRP1B96
DTA104A61
FXKQ-MA
BRC4C61
KRP1B61
KRP2A61
KRP4AA51
—
DTA104A61
FXDQ-PBFXDQ-NB
BRC4C65
BRC2C51
BRC3A61
KRP1B56
KRP2A53
KRP4A54
Note 4,6KRP1BA101
DTA104A53
FXSYQ-M
BRC4C62
KRP1B61
KRP2A61
KRP4AA51
Note 5KRP4A91
FXDYQ-MA
BRC4C62
KRP1B61
KRP2A61
KRP4AA51
—
DTA104A61
FXMQ-P
BRC4C65
KRP1C64
KRP2A61
KRP4AA51
Note 2,3KRP4A96
DTA104A61
FXHQ-MA
BRC7EA63W
—
—
KRP1BA54
KRP2A62
KRP4AA52
Note3KRP1CA93
DTA104A62
FXAQ-P
BRC7EA618
—
KRP2A61
KRP4AA51
Note 2,3KRP4AA93
DTA104A61
FXLQ-MAFXNQ-MA
BRC4C62
BRC2C51
BRC3A61
KRP1B61
KRP2A61
KRP4AA51
—
DTA104A61
FXUQ-MA
BRC7CA528W
—
—
—
—
KRP4AA53
KRP1BA97
—
No.
Replacement long-life filter1
2
3
4
5
Sealing member of air discharge outlet (*1)
Decoration panel for air discharge
Vertical flap kit
L-shape piping kit
FXUQ71MA
KDBH49FA80
KDBT49FA80
KDGJ49FA80
KHFP49MA140
KDBH49FA140
KDBT49FA140
KDGJ49FA140
FXUQ100MA FXUQ125MA
KAF495FA140
(*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.Note:
TypeItem
Wired BRC1C62
Wired remote controller with weekly schedule timer2 BRC1D61
Cool/Heat selector
Fixing box
REFNET header
REFNET joint
Fixture for preventing overturning
Wire fixture for preventing overturning
Central drain plug
TypeItem
38
CONTROL SYSTEMS
Building Management System
System ConfigurationNo. Item Model No. Function
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through LONWORKS® communication.DMS504B514
3
•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable independently.DAM411B513-1
No. Item Model No. Function
*2 Interface for use in LONWORKS®
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through BACnet ® communication.DMS502B51
•Additional 64 groups (10 outdoor units) is possible. Max. 7 iTM plus adaptors can be connected to intelligent Touch Manager.DCM601A52
*1 Interface for use in BACnet®
Optional DIII board
KJB411A
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable independently.DAM412B51Optional Di board
•8 pairs based on a pair of On/Off input and abnormality input.DEC101A51Di unit2-5
3-2
1-2
1
Electrical box with earth terminal (4 blocks)
DCS601A521-1 •Additional 64 groups (10 outdoor units) is possible.
•Wall embedded switch box.
DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.intelligent Touch Controller
DIII-NET plus adaptor
intelligent Touch Controller
Hardware
HardwareBasic
DCM601A51 •Air-conditioning management system that can be controlled by touch screen.intelligent Touch Manager
DCM601A53 •Max. 5 intelligent Touch Managers can be integrated.iTM integrator
HardwareBasic
Option
iTM plus adaptor
•Building energy consumption is visualised. Wasted air-conditioning energy can be found out.DCM008A51iTM energy navigator
•Power consumption of indoor units are calculated based on operation status of the indoor unit andoutdoor unit power consumption measured by kWh metre.DCM002A51iTM power proportional
distribution
2
2-2
2-1
2-4
2-3
Hardware
Software
Option
•4 pairs based on a pair of On/Off input and abnormality input.DEC102A51Dio unit2-6
•Interface between the central monitoring board and central control units.DCS302A525 Unification adaptor forcomputerised control
Notes: *1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS® is a trademark of Echelon Corporation registered in the United States and other countries. *3. Installation box for adaptor must be obtained locally.
Communication line
Contact/analoguesignal
intelligent Touch Manager
•Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one system.
Note 2
DCS302CA61Central remote controller2
•Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF, temperature settings and scheduling can be controlled individually for indoor units.
Note 3
DCS303A51Residential central remote controller1
•Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
Note 2
DCS301BA61Unified ON/OFF controller3
KJB212AAElectrical box with earth terminal (2 blocks)3-1
KEK26-1ANoise filter (for electromagnetic interface use only)3-2
KJB311AAElectrical box with earth terminal (3 blocks)2-1
DTA102A52Interface adaptor for SkyAir series5
DTA107A556
DTA103A51Wiring adaptor for other air-conditioner7
•Up to 1024 units can be centrally controlled in 64 different groups.•Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16) apply to each adaptor.
DTA109A51D -NET
Expander Adaptor8
•Fixing plate for DTA109A51KRP4A92Mounting plate8-1
•Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be controlled.For UAT(Y)-K(A),FD-K
For SkyAir, FD(Y)M-FA, FDY-KA,
FDYB-KA, FVY(P)J-A, FXUQ-MA
Central control adaptor kit
DTA112BA51For SkyAir FFQ-B, FHQ-BV,
FAQ100BV, FBQ-B
Notes: 1. Installation box for adaptor must be obtained locally. 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary. 3. For residential use only. Cannot be used with other centralised control equipment.
•Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.
Note 2
DST301BA61Schedule timer4
All rights reservedPrinted in Australia 09/12 Y.K.c
DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
Specifications, designs and other content appearing in this brochure are current as of September 2012 but subject to change without notice.
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Daikin products are manufactured for export to numerous countries throughout the world. Prior to purchase, please confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion and may have resultant impacts on warranty.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Daikin AustraliaPty Limited (ISO9001)
QEC23256 May 31, 2006Sydney, Brisbane, Adelaide,
Melbourne, Newcastle, Townsville, Perth, Auckland
Daikin AustraliaPty Limited (ISO14001)
CEM20437 October 27, 2006Sydney, Brisbane, Melbourne,
Adelaide
JQA-1452JMI-0107
Organization:DAIKIN INDUSTRIES, LTD.AIR CONDITIONING MANUFACTURING DIVISION
Scope of Registration:THE DESIGN/DEVELOPMENT AND MANUFACTURE OF COMMERCIAL AIR CONDITIONING, HEATING, COOLING, REFRIGERATING EQUIPMENT, HEATING EQUIPMENT, RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, COMPRESSORS AND VALVES.
Organization:DAIKIN INDUSTRIES (THAILAND) LTD.
Scope of Registration:THE DESIGN/DEVELOPMENT AND MANUFACTURE OF AIR CONDITIONERS AND THE COMPONENTS INCLUDING COMPRESSORS USED FOR THEM
All of the Daikin Group’s business facilities and subsidiaries in Japan are certified under the ISO 14001 international standard for environment management.