Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual For Amot 8630B Hawk-I B Revision 1

Transcript of Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan...

Page 1: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2

Spartan Controls Manual

For Amot 8630B Hawk-I

B Revision 1

Page 2: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Table Of Contents Hawk-I Configure Mode…………………………………………………………… page 1

Hawk-I Configure Mode Screens………………………………………………….. page 3

Hawk-I View Mode……………………………………………………………….. page 11

Hawk-I View Mode Screens………………………………………………………. page 12

Hawk-I Display Scroll……………………………………………………………... page 20

Hawk-I Test Mode……………………………………………………………….. page 21

Hawk-I Shutdown and Alarm Messages…………………………………………… page 24

Hawk-I Password………………………………………………………………….. page 28

Hawk-I Modbus Communications…………………………………………………. page 30

Calibration of T/C………………………………………………………………….. page 32

Calibration of WIKA Transmitters………………………………………………… page 33

Page 3: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 1

Hawk-I Configure Mode The following flow-charts show the general layout of the Configure Mode Menus, and the keystrokes that are required to navigate within the menus. Each block shown describes one screen as it would be seen on the HawkI. These flowcharts do not describe the keystrokes required to navigate within a specific screen, or how to change values. The Left/Right keys are used to move within a screen the same as they are to move from screen to screen. For example, to change the configuration of a Timer the Up/Down keys would be used to get to the “Timers” heading. Pressing Enter would take you to the “Timer 1 Configuration Page”:

TMR: 1 VAL: 120B TIMER

The Instance number (1) will be flashing. The Up key will take you to the configuration of Timer 2. The Down key will take you to the configuration for the last Timer being used. To change the value of the timer press the Right key. Now the preset value for the timer will be flashing:

TMR: 1 VAL: 120 B TIMER

The Up/Down keys will now change the value of the timer. When the desired time has been entered the Right key can be pressed to change the description:

TMR: 1 VAL: 120 B TIMER

The description will be flashing. To change the description press the Enter key. The first letter can now be changed with the Up/Down keys. To change the next/previous letter press the Right/Left key. When changes to the description are complete press Enter. The entire description will be flashing again. Now the Right key can be pressed and the Timer instance will flash. Pressing the Left key within the menus will move the flashing cursor between the parameters in reverse order. When a change has been made to a parameter in Configure Mode you will be asked to confirm the change when:

- exiting Configure Mode before confirming

Page 4: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 2

- moving to the next “Instance” (from Timer 1 to Timer 2) - pressing Reset to exit a menu before confirming - The following screen will appear:

CONFIRM: ENTER CANCEL: RESET

Pressing Enter will confirm the changes that have been made. Pressing Reset will cancel any changes that have been made. To change a Floating point number (such as Analog setpoints) the following keystrokes are required. With the number flashing press Enter. Now the number will stop flashing and the Up/Down keys can be used to change the value. The Left/Right keys can be used to move the position of the decimal point. When the desired number has been entered press the Enter key. The entire number will flash again. Again, the “Change Confirmation” screen will appear if you hit Reset or go to the next instance. Any menu can be exited by pressing Reset. If you are in one of the menus (DI:10 etc.) and you press Reset it will take you back to the main menu heading (Digital Inputs). Pressing Reset again will take you to the top of the menu list (Controllers).

Page 5: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 3

Hawk-I Configure Mode Screens

CONTROLLERS

ANALOG USER IN

Up ArrowDown Arrow

Enter

ANALOG INPUTS

DIGITAL INPUTS

FAULT LOGGING

TACHOMETER

AVG GROUPS

SPLIT RANGES

USER SETPOINTS

COMMUNICATIONS

TEST MODE TIMER

DIAGNOSTICS

HRS RUN/PWR DN

LOCK/UNLOCK

DIGITAL OUTPUTS

TIMERS

ANALOG OUTPUTS

TIME OF DAY

USER SWITCHES

Page 6: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Controllers Action: DIRECTGain: XXXX.X

Hawk-I Configure Mode Screens

PID: 1 Description

PID: 2 etc Description

AUI:1 XXXX.X Description

Intgrl: XXXX.XDeriv: XXXX.X

Analog User In

Enter Right

Left

Right

Reset

Down Up

DownUp

AUI: 2 etc Description

Up Down

Hrs Run/Pwr Dn Last Power OnDate/Time

Last Power OffDate/Time

RM: 1 XXX:XXDescription

Enter

Reset

Enter

Reset

Right Right

Left Left

Left

Right

Right

Left

Down Up

Fault Logging DI:1 SD OP Description

AI:1 etc. XXXXDescription

DI:1 SD OPDate/Time

Enter

ResetUp Down

Right

Left

AI:2 etc. XXXXDate/Time

Right

Left

Up Down

Down Up

Left

Filter: XXXX.XDeadband:XXX.X

CONF1

Up Down

RM:2 etc XX:XXDescription

Down Up

Right

Left

Page 4

Page 7: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Digital Inputs DI:1 Class A Description

DI:1 ShutdownNormally Closed

DI:2 etc. Class ADescription

Analog Inputs LO SH: XXXXENHI SH: XXXXEN

AI:1 Class A Description

LO AL: XXXXENHI AL: XXXXEN

4mA VAL:XXX20mA VAL:XXX

Type: J T/CUnits: C

Digital Outputs DO:1 Description

Right

Left

Enter

Reset

Up DownRight

Left

Enter

Reset Left Left Left Left

Right Right Right Right Right

Left

AI:2 etc. Class ADescription

Up Down

Down Up

Down Up

DO:2 etc. Description

Up Down

Down

Reset

Enter

Analog Outputs AO:1 Description

AO:2 Description

Enter

Reset

Up Down

Down Up

Down Up

DI:2etcShutdownNormally Closed

Up Down

4mA:XXXX20mA:XXXX

Right

Left

Right

Left

Right

Left

Up CONF2

Page 5

Page 8: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Tachometer Tac:1 PPR:XXXDescription

Overspd: XXXXUnderspd: XXXX

CTS: XXXXPPS: XXXX

Timers Tmr:1 Val:XXXDescription

Tmr:2etc.Val:XXX Description

Up DownEnter

Reset

Down Up

Enter

Reset Left

Right Right Right

Left

Down

Up

Left

CONF3

Time Of Day Time/Date: 1Description

Up DownEnter

Reset

Time/Date: 2 etc.Description

Month Date DayE/D E/D E/D

Hour:MinuteE/D E/D

Right

Left Left

Right Right

Left

User Switches SUI:1 On/OffDescription

Up DownEnter

Reset

Up SUI:2 etc. On/OffDescription

Down

Down

Down Up

Up

Page 6

Page 9: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Avg Groups Dev A Lo: XXXXDev A Hi: XXXX

Dev B Lo: XXXXDev B Hi: XXXX

GRP:1 Description

Enter

Reset

Right

Left

Right

Left

Split Ranges SR:1 Description

A:XXXX= 0% XXXX=100%

Right

Left

B:XXXX= 0% XXXX=100%

SR:2 etc. Description

Down Up

Enter

Reset

Right Right Right

Left Left

Up Down

Left

User Setpoints Setpoint: 1 Description

ACTION: Rising Enter

Reset

Right Right Right

Left Left

Up Down

Left

Setpoint: 2 etc. Description

SP: XXXXX HYS: XXXXX

Communications ADDR: 1 BAUD: 9600

Enter

Reset

Down

Down

Up

Up

Down Up

Test Mode Timer Test Mode TimerSeconds: XX

Enter

Reset

Down CONF4

ADDR+1: NO RTS: TX HI

Right

Left

UpDown

Up

Page 7

Page 10: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Diagnostics

Digital Outputs

Digital Inputs

Key Test

Enter

Reset

Exit: Hold Reset Key:

Digital In StatCCCCCCCCCCCCCCCC

Relay: 1 DeenergizeRelay

Relay: 1 Energize Relay

Enter

Reset

Enter

Reset

Enter

Reset

Right

Left

Down

Down

Down

Up

Up UpDown Down

Down

Up

AI:1 XXXXCDescriptionAnalog Inputs

Analog Outputs Analog Out: 10%

AI:2 etc XXXXCDescription

Up Down

Up

Down Up

Enter

Enter

Reset

Reset

Analog Out: 20%

Right

Left

Down

CONF5

Relay: 2 etc. DeenergizeRelay

Relay: 2 etc. Energize Relay

Down

Up

Up

Up

Page 8

Page 11: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

System Clock

Hrs Run / Pwr Dn

Load Active Mem

Calibrate Inputs

DateTime

Parameter ResetReset To Exit

Calibrate InputsAI: T/C 1-8

Last Power OnDate/Time

Last Power OffDate/Time

Enter

Reset

Right Right

Left Left

Right

Left

Down

Down

Down

Up

Up

Up

Enter

Enter

Enter

Reset

Reset

Reset

Set 1st Cal PtCal Pt 1: XXX

Calibrate InputsAI: T/C 9-16

Set 2nd Cal PtCal Pt 2: XXX

Left Left

Right Right Right

Left

Up Down

Up Down

Calibrate InputsAI: T/C 1 etc.

Up

CONF6

Up Down

Save Active Mem

Parameter ResetReset To Exit

Reset

Enter

Enter

Enter

DownUp

Down

RM: 1 XXX:XXDescription

Up Down

RM:2 etc XX:XXDescriptionDown

Down Up

Up

Page 9

Page 12: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Firmware FirmwareVersionXXX XXX

Up

Enter

Reset

Lock/UnlockPassword: 0New PSWD:XXX

SequenceSequence Date

Date/Time

Enter

Reset

Down Up

Reset

Accesses D/L Count: XXEnter

Reset

Down Up

Clr Calibration Confirm: Enter Cancel: Reset

Enter

Reset

Down Up

Up

CONF7

Enter

Download Code Confirm: Enter Cancel: Reset

Enter

Reset

Down Up

Down

Down

Page 10

Page 13: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 11

Hawk-I View Mode The following flow-charts show the general layout of the View Mode Menus, and the keystrokes that are required to navigate within the menus. Each block shown describes one screen as it would be seen on the HawkI. Most of the parameters in View Mode are “Read Only”. Only the following parameters can be changed in View Mode:

- Controllers - all parameters except “Action” - Analog User Inputs - Analog Input Alarm Setpoints - Tachometer - PPR (Pulses Per Revolution) - Time Of Day functions - User Switches - Average Groups - Split Ranges - User Setpoints - System Clock

The same keystrokes used to change parameters in Configure Mode are used to change parameters in View Mode. When a change has been made to a parameter in View Mode you will be asked to confirm the change when:

- exiting View Mode before confirming - moving to the next “Instance” (from Timer 1 to Timer 2) - pressing Reset to exit a menu before confirming

The following screen will appear:

CONFIRM: ENTER CANCEL: RESET

Pressing Enter will confirm the changes that have been made. Pressing Reset will cancel any changes that have been made. Any menu can be exited by pressing Reset. If you are in one of the menus (DI:10 etc.) and you press Reset it will take you back to the main menu heading (Digital Inputs). Pressing Reset again will take you to the top of the menu list (Controllers).

Page 14: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 12

Hawk-I View Mode Screens

CONTROLLERS

ANALOG USER IN

Up ArrowDown Arrow

Enter

DIGITAL INPUTS

FAULT LOGGING

ANALOG OUTPUTS

DIGITAL OUTPUTS

HRS RUN/PWR DN

ANALOG INPUTS

TIMERS

TACHOMETER

AVG GROUPS

SPLIT RANGES

USER SETPOINTS

RUN DIAGNOSTICS

LOCK/UNLOCK

UNHEALTY CHANS

TEST MODE

TIME OF DAY

USER SWITCHES

Page 15: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Controllers

AUI:1 XXXX.X DescriptionAnalog User In

Down Up AUI: 2 etc Description

Up Down

Hrs Run/Pwr Dn Last Power OnDate/Time

Last Power OffDate/Time

Enter

Reset

Enter

Reset

Right Right

Left Left

Right

LeftDown Up

Unhealthy Chans DI: 1 AL OPDescription

DI: 2 AL OPDescription

Enter

Reset

Up Down

Down

Down Up

Hawk-I View Mode Screens

Action: DIRECTGain: XXXX.X

PID: 1 Description

PID: 2 etc Description

Intgrl: XXXX.XDeriv: XXXX.X

Enter Right

Left

Right

Reset

DownUp

Left

Right

Left

Filter: XXXX.XDeadband: XX.X

VIEW1

Up Down

Up

RM: 1 XXX:XXDescription

RM:2 etc XX:XXDescription

Right

Left

Page 13

Page 16: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Digital Inputs DI:1 Class A Description

DI:1 ShutdownNormally Closed

DI:2 etc. Class ADescription

Analog Inputs LO SH: XXXXENHI SH: XXXXEN

AI:1 Class A Description

LO AL: XXXXENHI AL: XXXXEN

4mA: XXXX.X20mA: XXXX.X

Type: J T/CUnits: C

Right

Left

Enter

Reset

Up DownRight

Left

Enter

Reset Left Left Left Left

Right Right Right Right Right

Left

AI:2 etc. Class ADescription

Up Down

Down Up

Down

Fault Logging DI:1 SD OP Description

AI:1 etc. XXXXDescription

DI:1 SD OPDate/Time

Enter

ResetUp Down

Down Up

Right

Left

DI:2etcShutdownNormally Closed

Up Down

Right

Left

AI:1 etc. XXXXDate/Time

Right

Left

Up Down

VIEW2

Down Up

Up

Page 14

Page 17: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Digital Outputs DO:1 Description

Tachometer Tac:1 PPR:XXXDescription

Overspd: XXXXUnderspd: XXXX

CTS: XXXXPPS: XXXX

Timers Tmr:1 Val:XXXDescription

Tmr:2etc.Val:XXX Description

Up Down

Up DO:2 etc .Description

Up Down

Enter

Reset

Reset

Enter

Analog Outputs AO:1 Description

AO:2 Description

Enter

Reset

Up Down

Down Up

Down Up

Enter

Reset Left

Right Right Right

Left

Down

Left

4mA:XXXX20mA:XXXX

Right

Left

Right

Left

Down Up

VIEW3

Down

Up

Page 15

Page 18: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Avg Groups Dev A Lo: XXXXDev A Hi: XXXX

Dev B Lo: XXXXDev B Hi: XXXX

GRP:1 Description

Enter

Reset

Right

Left

Right

Left

Up

Split Ranges SR:1 Description

A:XXXX= 0% XXXX=100%

Right

Left

B:XXXX= 0% XXXX=100%

SR:2 etc. Description

Down Up

Enter

Reset

Right Right Right

Left Left

Up Down

LeftDown VIEW4

Down

Time Of Day Time/Date: 1Description

Up DownEnter

Reset

Time/Date: 2 etc.Description

Month Date DayE/D E/D E/D

Hour:MinuteE/D E/D

Right

Left Left

Right Right

Left

User Switches SUI:1 On/OffDescription

Up DownEnter

Reset

Up SUI:2 etc. On/OffDescription

UpDown

Down

Up

Page 16

Page 19: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Run Diagnostics

Analog Inputs

User Setpoints Setpoint: 1 Description

ACTION: Rising Enter

Reset

Right Right

Left Left

Up Down

Left

Setpoint: 2 etc. Description

SP: XXXXX HYS: XXXXX

Down

Up

Up

Enter

Reset

Enter

Reset

Enter

Reset

Down

Digital Inputs Digital In StatCCCCCCCCCCCCCCCC

AI: 2 XXXXCDescription

Up

Analog Outputs AO: 1 0.000% Description

Down Up

Up Down

DownUpEnter

Reset

Digital Outputs

Down Up

Digital Out StatCooo ooCCoooo

Enter

Down

Down

AI: 1 XXXXCDescription

AO:2 0.000% Description

VIEW5

Reset

Right

Down

Up

Up

Page 17

Page 20: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

System Clock

Communications

DateTime

Down

Down

Up

Up

Up

Enter

Enter

Reset

ADDR: 1 BAUD: 9600

Enter

Reset

System Info

Down Up

Enter

Reset

R: 100O: 0

Firmware FirmwareVersion XXX XXX

Reset

Sequence Sequence DateDate/Time

Enter

Reset

Down Up

Accesses D/L Count: XXEnter

Reset

Down Up

VIEW6

ADDR+1:NO RTS: TX HI

Right

Left

Down

Down Up

Page 18

Page 21: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Lock/Unlock

Up

Password: 0New PSWD:XXX

Enter

Reset

Test Mode DI: 1Description Digital Inputs

Analog Inputs

Tachometer

DI: 2 etcDescription

Enter

Reset

Down Up

Enter

Reset

Enter

Reset

Enter

Reset

Down

Down

Down

Down

Up

Up

Up

Up

AI: 1Description

AI: 2 etcDescription

SP: 1Description

Enter

Enter

Enter

Enter

Enter

VIEW7

Page 19

Page 22: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 20

Hawk-I Display Scroll The HawkI has a built in function which will display the status of the inputs in the following order: AI 1-24 readings (AI 1-16 are Thermocouple channels/AI 17-24 are 4-20 mA channels)

AI 1 XXXXX DESCRIPTION

RPM

RPM: XXXX

Note: RPM will not be displayed if the Pulses Per Revolution is set to 0. This display function is used throughout the start-up sequence. When a Sequence message is displayed (Crank Timer etc.) on one of the lines, the display scroll function will automatically shift the line with the input reading to the unused display line. When no sequence messages are using the display the display scroll will appear as follows:

AI 1 XXXXX DESCRIPTION

If a sequence message is written to line 1 the display will show:

CRANK: 120s AI 1 XXXXX

If a sequence message is written to line 2 the display will show:

AI 1 XXXXX CRANK: 120s

If there are sequence messages on line 1 and 2 of the display there will be no display scroll information. The display scroll automatically loops through the input displays. Pressing the Left key will stop the scroll on it’s current display. Pressing the Right key will resume the automatic scroll. Pressing the Up key will cause the scroll to move forward through it’s displays. Pressing the Down key will cause the scroll to move backwards through it’s displays.

Page 23: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 21

Hawk-I Test Mode The Hawk-I Test Mode allows any input to be tested without causing a shutdown or alarm. Only one input can be put in Test at a time. The length of the Test Mode is set by the Test Mode Timer in Configure Mode (Test Mode Timer is not within the “Timers” menu. It is a separate menu area). The Test Mode is most easily accessed as follows: 1. Press Enter to access the VIEW MENU.

VIEW MENU CONTROLLERS

2. Press the Up key once to display VIEW MENU/TEST MODE.

VIEW MENU TEST MODE

3. Press Enter. 4. Use the Up/Down keys to select DIGITAL INPUTS, ANALOG INPUTS, or TACHOMETER.

TEST MODE DIGITAL INPUTS

TEST MODE ANALOG INPUTS

TEST MODE TACHOMETER

5. Press Enter. 6. If you selected DIGITAL INPUTS or ANALOG INPUTS use the Up/Down keys to select which

input you want to Test. 7. Press Enter. If you have you have selected a digital input (i.e. DI 1) you will see the following screen:

Page 24: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 22

DI: 1 CL T

DESCRIPTION

The CL indicates that the channel is closed. If the channel is open it will display OP. The flashing T in the top right corner indicates that Test Mode is active. During the final 30 seconds of the Test Mode Timer the T will flash at twice the normal rate. From this screen pressing the Reset key will end the Test. If the input is forced to the unhealthy state (when channel’s class is enabled) the display will show a shutdown message. This shutdown is for display only, and will not actually shut down the unit.

DI: 1 SD OP T DESCRIPTION

The top line of the display will flash until the Reset key is pressed. If the input is healthy when Reset is pressed the normal Test display will return. If the input is still unhealthy when Reset is pressed the top line will stop flashing (the T will continue to flash). This screen will remain until the input returns to the healthy state. If the Test Mode Timer expires and the input is still unhealthy it will cause the unit to shutdown. The Test Timer can be reset at any time during the test by pressing the Enter key. If you have selected an analog input (i.e. AI 1) the test displays will appear as follows :

AI:1 XXXX T DESCRIPTION

AI:1 SD XXXX T DESCRIPTION

NOTE: XXXX = present reading/units As with the Digital Inputs, the channel in Test will not cause a shutdown unless it is in an unhealthy state when the Test Mode Timer expires. If you have selected Tachometer the test display appears as follows:

SPEED: XXX RPM TDESCRIPTION

Page 25: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 23

NOTE: XXX = present RPM reading When the Tachometer is in Test the OVERSPEED parameter (located in the Tachometer Menu) is reduced by 10%. If the speed exceeds this new OVERSPEED setting it will cause the unit to shutdown. When an input is put in Test it will have no effect on the Sequence/Analog logic. If an input is used in the Ladder Logic Sequence or Analog Logic Page all contacts/values associated with that input will be maintained at the state last read before entering Test Mode.

Page 26: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 24

Hawk-I Shutdown and Alarm Messages

The Hawk-I displays a specific message when a fault occurs. There are 8 types of faults that the Hawk-I will annunciate: 1. Digital Input Alarm 2. Digital Input Shutdown 3. Analog Input Alarm 4. Analog Input Shutdown 5. Analog Input Sensor Failure Alarm 6. Analog Input Sensor Failure Shutdown 7. General Purpose Alarm 8. General Purpose Shutdown A sensor failure occurs when the Hawk-I detects an Analog Input reading that is beyond the acceptable range. A thermocouple channel (AI 1-16) will sensor fail if the thermocouple is open or grounded. A 4-20 mA loop channel (AI 17-24) will sensor fail if the reading is below 3.82 mA or above 20.38 mA. A sensor failure will cause a shutdown if the Analog Input has any shutdown setpoints enabled and the class is anything other than “NONE”. If there are no shutdown setpoints enabled, or the class is “NONE”, a sensor failure will only cause an alarm. General Purpose Shutdowns/Alarms are used internally in the Hawk-I ladder logic program. They are used when the programmer wants to cause a shutdown or alarm if a certain set of conditions exist. Some common User Shutdowns/Alarms are:

• Failed To Start • Permissive Fault • Overspeed • Underspeed • Mag Pick-up Fault

Digital Input Alarm

DI: 1 AL OPENG OIL LEVEL

When a Digital Input Alarm occurs line 1 of the display will show the DI number (1-16) , AL for Alarm, and OP/CL to indicate whether the input is presently open or closed. Line 2 of the display will show the description for the Digital Input. Line 1 of the display will flash until the Reset key is pressed. At this time the fault display will clear. If the alarm condition still exists it will be present in the Unhealthy Channels menu. Digital Input Shutdown

Page 27: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 25

DI: 1 SD OPENG OIL LEVEL

When a Digital Input Shutdown occurs line 1 of the display will show the DI number (1-16) , SD for Shutdown, and OP/CL to indicate whether the input is presently open or closed. Line 2 of the display will show the description for the Digital Input. Line 1 of the display will flash until the Reset key is pressed. If the channel is healthy at this time the fault display will clear. If the shutdown condition still exists when Reset is pressed line 1 of the display will stop flashing, but the message will remain. The shutdown message will now automatically clear when the fault clears. Analog Input Alarm

AI: 1 AL XXX.XXCOMP OIL TEMP

When an Analog Input Alarm occurs line 1 of the display will show the AI number (1-24) , AL for Alarm, and the current input reading. Line 2 of the display will show the description for the Analog Input. Line 1 of the display will flash until the Reset key is pressed. At this time the fault display will clear. If the alarm condition still exists it will be present in the Unhealthy Channels menu. Analog Input Shutdown

AI: 1 SD XXX.XXCOMP OIL TEMP

When an Analog Input Shutdown occurs line 1 of the display will show the AI number (1-24) , SD for Shutdown, and the current input reading. Line 2 of the display will show the description for the Analog Input. Line 1 of the display will flash until the Reset key is pressed. If the channel is healthy at this time the fault display will clear. If the shutdown condition still exists when Reset is pressed line 1 of the display will stop flashing, but the message will remain. The shutdown message will now automatically clear when the fault clears.

Page 28: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 26

Analog Input Sensor Failure Alarm

AI: 1 AL S.FAILCOMP OIL TEMP

When an Analog Input Sensor Failure Alarm occurs line 1 of the display will show the AI number (1-24) , AL for Alarm , and S.FAIL for sensor failure. Line 2 of the display will show the description for the Analog Input. Line 1 of the display will flash until the Reset key is pressed. At this time the fault display will clear. If the alarm condition still exists it will be present in the Unhealthy Channels menu. Analog Input Sensor Failure Shutdown

AI: 1 SD S.FAILCOMP OIL TEMP

When an Analog Input Sensor Failure Shutdown occurs line 1 of the display will show the AI number (1-24) , SD for Shutdown, and S.Fail for sensor failure. Line 2 of the display will show the description for the Analog Input. Line 1 of the display will flash until the Reset key is pressed. If the channel is healthy at this time the fault display will clear. If the sensor failure condition still exists when Reset is pressed line 1 of the display will stop flashing, but the message will remain. The shutdown message will now automatically clear when the fault clears. General Purpose Alarm

GP: 1 ALPermissive Fault

When a General Purpose Alarm occurs line 1 of the display will show the GP number and AL for Alarm. Line 2 of the display will show the description for the User Alarm. Line 1 of the display will flash until the Reset key is pressed. At this time the fault display will clear.

Page 29: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 27

General Purpose Shutdown

GP: 1 SDPermissive Fault

When a General Purpose Shutdown occurs line 1 of the display will show the GP number and SD for Shutdown. Line 2 of the display will show the description for the User Shutdown. Line 1 of the display will flash until the Reset key is pressed. If the shutdown condition has cleared at this time the fault display will clear. If the shutdown condition still exists when Reset is pressed line 1 of the display will stop flashing, but the message will remain. The shutdown message will now automatically clear when the fault clears.

Page 30: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 28

Hawk-I Password The Hawk-I has a password function that can be used to block any parameter changes with the keypad. Setting the password to 0 will allow access to all parameters in View Mode and Configure Mode without having to enter a password. Entering a New Password The password functions are in the Lock/Unlock menu. To enter a new password in View Mode (Password changes can also be made in Configure Mode) use the following keystrokes: 1. Press Enter to access the VIEW MENU.

VIEW MENU CONTROLLERS

2. Press the Up key to display VIEW MENU - LOCK/UNLOCK.

VIEW MENULOCK/UNLOCK

3. Press Enter. 4. The password screen will be displayed. The 0 next to PASSWORD will be flashing.

PASSWORD: 0NEW PSWD: ***

5. Use the Up/Down keys to enter the current password (password will be 0 if this is the first time

a new password has been entered). 6. Press the Right key. The *** beside NEW PSWD will automatically change to match the

PASSWORD. Now the NEW PSWD can be entered with the Up/Down keys. If the wrong PASSWORD is entered, pressing the Right key will not allow access to the NEW

PSWD field. If this happens press the Left key. The PASSWORD will flash again allowing the user another attempt.

7. Press Reset. The confirmation screen will appear.

CONFIRM: ENTER CANCEL: RESET

Page 31: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 29

8. Press Enter to confirm that you want to accept the password change. Press Reset to cancel the password change.

Entering The Password To Make Parameter Changes If there is a password (other than 0 ) it must be entered in View Mode or Configure Mode before any parameter changes can be made. To enter the password in View Mode in order to make a parameter change use the following keystrokes (the same keystrokes are required in Configure Mode): 1. Press Enter to access the VIEW MENU.

VIEW MENU CONTROLLERS

2. Press the Up key to display VIEW MENU - LOCK/UNLOCK.

VIEW MENULOCK/UNLOCK

3. Press Enter. 4. The password screen will be displayed. The 0 next to PASSWORD will be flashing.

PASSWORD: 0NEW PWD: ***

5. Use the Up/Down keys to enter the current password. 6. Press the Reset key once. The View Menu parameters can now be changed. If the password is active (not 0) it must be entered every time View Mode or Configure Mode are accessed. The Master Password If you forget the password there is a master password that will allow access. The master password is entered in the Windows program, and is downloaded with the sequence. Contact the programmer if the master password is required.

Page 32: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 30

Hawk-I Modbus Communications

8/10/98 Function Code 3 Registers (all16 bit registers)

Register Description Contents 40001 Spare Spare 40002 Common Alarm First out Alarm (source and Type

Number) 40003 Common Shutdown First out Shutdown (source and

Type Number) 40004 Tachometer 1 Tach1 (RPM) 40005 Tachometer 2 (Unused) 40006 Digital Inputs 1-16 Packed Digital Input Status

0=open 1=closed 40007 Digital Inputs 17-32 (Unused) 40008 Relay Output Status 1-12 Packed Relay Output Status

0=open 1=closed 40009 Spare 40010 MODBUS Packed Logical Coils 1-16 40011 MODBUS Packed Logical Coils 17-32 40012 Runtime Hours 40013 Runtime Minutes 40014 Spare 40015 Spare 40016 Spare 40017 Spare 40018 Thermocouple Analog Input 1 IEEE Floating Point (2 registers) 40020 Thermocouple Analog Input 2 " " " " 40022 Thermocouple Analog Input 3 " " " " 40024 Thermocouple Analog Input 4 " " " " 40026 Thermocouple Analog Input 5 " " " " 40028 Thermocouple Analog Input 6 " " " " 40030 Thermocouple Analog Input 7 " " " " 40032 Thermocouple Analog Input 8 " " " " 40034 Thermocouple Analog Input 9 " " " " 40036 Thermocouple Analog Input 10 " " " " 40038 Thermocouple Analog Input 11 " " " " 40040 Thermocouple Analog Input 12 " " " " 40042 Thermocouple Analog Input 13 " " " " 40044 Thermocouple Analog Input 14 " " " " 40046 Thermocouple Analog Input 15 " " " " 40048 Thermocouple Analog Input 16 " " " "

Page 33: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 31

40050 4-20mA Analog Input 17 IEEE Floating Point (2 registers) 40052 4-20mA Analog Input 18 " " " " 40054 4-20mA Analog Input 19 " " " " 40056 4-20mA Analog Input 20 " " " " 40058 4-20mA Analog Input 21 " " " " 40060 4-20mA Analog Input 22 " " " " 40062 4-20mA Analog Input 23 " " " " 40064 4-20mA Analog Input 24 " " " " 40066 4-20mA Analog Output 1 (percent) HEX 0=0% FFFF=100% 40067 4-20mA Analog Output 2 (percent) HEX 0=0% FFFF=100% 40070 Analog User Output Register 1 IEEE Floating Point (2 registers) 40072 Analog User Output Register 2 " " " " 40074 Analog User Output Register 3 " " " " 40076 Analog User Output Register 4 " " " "

In the Quick Data Table certain registers do not update when the Hawk-I is in Configure Mode. To obtain valid readings, the Hawk-I should be in Run Mode. Registers 40002/40003 Common Alarm/Shutdown Byte 1 = Input Type (Hex) 1 = DI 4 = AI 13=General Purpose Shutdown/Alarm Byte 2 = Input Number (Hex Value) DI 1-16 or AI 1-24 or General Purpose Shutdown/Alarm

Number i.e. Register 40003 = 01 03 = DI 3 04 12 = AI 18 13 01 = General Purpose Shutdown 1 Register 40006 Digital Inputs Bit 0 = DI 1 Register 40008 Relay Output Status Bit 0 = Relay 1 Display Text The display characters are stored in ASCII format starting at register 220. Each register contains 2 characters, and there are 20 characters reserved for each line of the display (the standard Hawk-I display contains 16 characters per line). The characters for the second line of display start at register 230.

Page 34: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 32

Calibration Of Thermocouples 1. Remove T/C from AI 1 and install calibrator leads in it's place. Observe correct polarity. 2. Select Configure Mode using the switch on the rear of the HAWK-I. 3. Pressing the <UP> arrow key twice brings you to the DIAGNOSTICS section. 4. Press the <ENTER> key, screen will display KEY TEST. 5. Scroll with the <DOWN> arrow key to reach the CALIBRATE INPUTS screen. 6. Press the <ENTER> key. The screen will display Calibrate Inputs AI: T/C 1-8. 7. Press the RIGHT arrow key once. 8. Display will read Set 1st Cal Pt / Cal Pt 1: 0.00 9. Press <ENTER> key once and you will see the decimal place flashing. 10. Enter 0 degrees from your calibrator. 11. Press the <ENTER> key once more and you will see the display flash. 12. Let the display flash a few times to give the calibrator time to send it's signal. 13. Press the <RIGHT> arrow key once. 14. The display now reads Set 2nd Cal Pt / Cal Pt 2: 100.00. 15. Press <ENTER> key once and you will see the decimal place flashing. 16. Using the <UP> arrow key set the value displayed to 600.0. 17. Enter 600 degrees from your calibrator. 18. Press the <ENTER> key once more and you will see the display flash. 19. Let the display flash a few times to give the calibrator time to send it's signal. 20. Now press the RIGHT arrow key once. 21. The display will read CALIBRATION SUCCEEDED. 22. Set calibrator back to 0 degrees. 23. Install the T/C back at AI 1 and remove the T/C at AI 9. 24. Install the calibrator at AI 9, paying attention to proper polarity. 25. Press the <RESET> key until the display reads Calibrate Inputs AI: T/C 1-8. 26. Press the <UP> arrow key once and the display will read Calibrate Inputs AI: T/C 9-16. 27. Repeat steps 7 to 22. 28. Press the <RESET> key until you get back to the CONTROLLERS screen. 29. Remove the HAWK-I from Configure Mode and reconnect the T/C to AI 9. 30. Press the <RESET> key to clear any alarms.

NOTE: A ladder diagram of the Configure Mode screens is shown in this manual. If calibrations are not successful the message Calibration Failed will be displayed. If this occurs repeatedly go to the Diagnostics/Analog Inputs menu. Use the UP/DOWN keys to select the channel that the calibrator is connected to. Enter various values into the calibrator and confirm that the Hawk-I reading responds as expected. If the Hawk-I does not display valid readings check the calibrator connections. To test the input without a calibrator install a jumper wire across the T/C input. The channel should read the panel ambient temperature. NOTE: After a program download the Hawk-I should be switched out of Configure Mode once before a T/C calibration is performed.

Page 35: Hawk-I Manual BREV1 - Spartan Controls/media/resources/spartan controls/u/67_spartan...Spartan Controls Ltd. 305 - 27 Street S.E., Calgary, Alberta T2A 7V2 Spartan Controls Manual

Page 33

Calibration of WIKA Transmitters NOTE: The majority of sensors will be well within acceptable tolerances without calibration. The transmitter range should be considered when judging the

accuracy of a reading. For example, if an error of 25 kPa is seen on a 0-2000kPa transmitter the error would be 1.25% of full scale. The same 25 kPa error on a 0-10,000kPa transmitter would only be 0.25% of full scale.

1. Remove the cap from the transmitter. 2. Pop the socket out of the cap to access the wires. 3. Pull the pin connector head out of the transmitter housing. 4. Now re-attach the socket to the pin connector. 5. Install a current meter in series with the output of the transmitter (pin 2). 6. With no pressure applied to the transmitter the meter should read 4 ma and the Hawk-I should

read 0 kPa. 7. Adjust the ZERO on the transmitter if not within acceptable tolerances. 8. Apply full scale pressure if possible. Meter should read 20 ma. 9. Adjust SPAN as necessary. The Hawk-I will sensor fail if the input is above 20.3 mA or below 3.8 mA.